Home
TECHNICAL & SERVICE MANUAL DC INVERTER
Contents
1. OVAT u High pressure DD Muffler E switch 3 9 52 1 J k 4 way valve 1 I I 1 c c I he l Kan I O O x x I i J E I 1 Capillary tube for i Narod Electric split flow a expansion tube valve h service Narrow tube valve i x diD J O D Strainer Muffler I qe 035mm Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit both the wide and narrow tubes of this air conditioner become cold To P Insulation prevent heat loss and wet floors due to dripping of condensation both tubes must be well insulated with a Thickness proper insulation material The thickness of the insulation should be a min 5 16 8 mm After a tube has been insulated never try to bend it into a narrow curve because it can cause the tube to break or crack Min 5 16 8 mm Wide tube 20 js Cooling cycle Defrosting cycle Heating cycle Thickness Min 5 16 8 mm Narrow tube Indoor Unit XHS1872 amp PNR XS1872 Outdoor Unit CH1872 Indoor unit Heat exchanger Strainer Outdoor unit Service High pressure switch Heat exchanger Capillary tube for N Electric split flow t expansion a valve service Narrow tub
2. Freeze prevention During COOL or DRY operation freezing is detected and operation is stopped when the temperature of the indoor heat exchanger matches the conditions below 1 Freeze prevention operation is engaged when the temperature of the indoor heat exchanger is below 43 F 6 C 2 Restart after freeze prevention operation occurs when the temperature of the indoor heat exchanger reaches 46 F 8 C or above Indoor heat exchanger temperature F C Area Automatic capacity control When the temperature drops below Point A the operation frequency is reduced by a certain proportion Area Frequency increase is prohibited When the temperature reaches Point C or above freezing prevention is ended and control is the same as in the a area When the temperature drops to below 36 F 2 C continuously for 2 minutes or longer the compressor stops Once the freeze condition is detected the air conditioner will work less than the maximum frequency until it is turned off 48 H Cold air prevention during heating During heating the fan speed is set to LL very low or stopped As the temperature of the indoor heat exchanger rises the fan speed is changed to the set speed Set fan speed At stability of operation At start of operation LL Stopped Approx 104 40 77 36 25 30 Indoor heat exchanger temperature F C NOTE The fan speed is forcib
3. W B Heating Indoor air temperature 70 F D B Outdoor air temperature 95 F D B 75 F W B Outdoor air temperature 47 F D B 43 F W B 11 2 2 Major Component Specifications 2 2 1 Indoor Unit Indoor Unit Body XHS1271 Control PCB CB XHS1271 Control Circuit Fuse 250V 3A Remote Control Unit RCS 7MHVPSWAU Q ty Dia and Length inch mm 1 D12 5 8 L5 3 4 D322 L147 FNo ofPoles O 8 Coil Resistance Ohm Ambient Temp 68 F 20 C Type Internal Controller Over Current Protection Over Heat Protection Ces Run Capacitor O OO VAC 0 0 0 0 0 0 0 0 0 0 0 0 0 0 00m O Drain Pump Model Q ty PLD 12115ST 1 1 Rating Voltage Hz S 60Hz Input W 10 Coil Resistance Ohm 101 10 Ambient Temp 68 F 20 C Safty Device Type Thermal Fuse Open F 293 145 Heat Exchanger Coil Face Area f m DATA SUBJECT TO CHANGE WITHOUT NOTICE Indoor Unit Panel PNR XS1872 Flap Motor Stepping Motor Model Q ty MPZN 12V 2 DC 12V Coil Resistance Ohm Each Pair of Terminal 380 796 Ambient Temp 77 F 25 C DATA SUBJECT TO CHANGE WITHOUT NOTICE 12 Indoor Unit Body XHS1872 Control PCB CB XHS1872 Control Circuit Fuse 250V 3A Remote Control Unit RCS 7MHVPSWAU Q ty Dia and Length inch mm 1 D12 5 8 L5 3 4 D322 L147 No ofPdes Coil Resistan
4. Refer to Fig 9 on page 4 to locate the ACL Reset but ton MEL Press the ACL Reset button after changing switch settings Fig 1 SANYO Commercial Solutions In Canada A Division of SANYO North America Corporation SANYO Canada Inc 1300 Michael Drive Suite A 1 300 Applewood Crescent Concord 85264190481000 SANYO 2008 Wood Dale IL 60191 U S A Ontario LAK 5C7 Canada W A Installing with in wall junction box 1 2 3 Install the junction box locally purchased into the wall Figs 2 a and 3 Pass the wire harness through the junction box and conduit Fig 3 Insert a flathead screwdriver into the 5 tab locations and disconnect the back plate of the remote controller by lifting up slightly Fig 2 b The tabs are thin take care not to chip them Pass the wire harness connector through the cord open ing on the back plate of the remote controller Use nippers or a similar tool to cut out the slots for the remote controller back plate screws Insert the spacers and use the machine screws to install the remote con troller back plate Fig 3 Insert the connector into the PCB of the remote con troller unit and wrap the wire harness around the hook Fig 4 Store the excess wire harness inside the junction box then hook the remote controller unit onto the top of the back plate and install the remote controller unit To remove the remote controller unit after it has been
5. See 11 3 Tools Specifically for R410A 11 5 1 Procedure for Replacing Compressor 1 Recovering refrigerant e Anyremaining refrigerant inside the unit should not be released to the atmosphere but recovered using the refrigerant recovery unit for R410A e Do notreuse the recovered refrigerant since it will contain impurities 2 Replacing Compressor e Soon after removing seals of both discharge and suction tubes of the new compressor replace it quickly 3 Checking for sealing e Use nitrogen gas for the pressurized gas and never use a refrigerant other than R410A Also do not use oxygen or any flammable gas 4 Evacuation e Use a solenoid valve installed vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption the valve will prevent the pump oil from flowing back e The equipment may be damaged if moisture remains in the tubing thus carry out the evacuation thoroughly e When using a vacuum pump with exhaust air volume more than 0 883 cu ft min and ultimate vacuum pressure rate of 50 micron Hg Standard time for evacuation 1 Recover refrigerant OK 2 Replace compressor OK 3 Check for sealing OK 4 Evacuation OK b Recharge Length of tubing Less than 33 ft 10 m More than 33 ft 10 m More than 10 minutes More than 15 minutes 64 5 Recharging Be sure to charge the specified amount of refrigerant in l
6. remote controller you will need the following information Model No Date of purchase Dealer s address ALERT SYMBOLS The following symbols used in this manual alert you to potentially dangerous conditions to users service personnel or the appliance ANCE N This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage INSTALLATION LOCATION We recommend that this wired remote controller be installed properly by qualified installation technicians in accordance with the Installation Instructions provided with the unit ANN e Do not install this wired remote controller where there are fumes or flammable gases or in an extremely humid space such as a greenhouse Do not install the wired remote controller where excessively high heat generating objects are placed Avoid To protect the air conditioner from heavy corrosion avoid installing the outdoor unit where salty sea water can splash directly onto it or in sulphurous air near a spa 1 All wiring must conform to the local electrical codes Consult your dealer or a qualified electrician for details 2 Each unit must be properly grounded with a ground or earth wire or through the supply wiring 3 Wiring must be done by a qualified electrician SAFETY INSTRUCTIONS e Re
7. 30 cm to 40 cm to dampen vibration between units 2 Foamed polyethylene insulation for the specified copper tubes as required to precise length of tubing Wall thickness of the insulation should be not less than 5 16 8 mm Use insulated copper wire for field wiring Wire size varies with the total length of wiring Refer to 3 7 Wiring Instructions for details CAUTION Table 2 Check local electrical codes Model Sr SHE MDC and regulations before XHS1271 1 4 6 35 mm 0 0314 0 8 mm 3 8 9 52 mm 0 0314 0 8 mm any specified instructions or XHS1872 1 4 6 35 mm 0 0314 0 8 mm 1 2 12 70 mm 0 0314 0 8 mm limitations 1 5 Additional Materials Required for Installation 1 Refrigeration armored tape 2 Insulated staples or clamps for connecting wire See local codes 3 Putty 4 Refrigeration lubricant 5 Clamps or saddles to secure refrigerant tubing 2 Installation Site Selection Indoor Unit VT To prevent abnormal heat genera tion and the possibility of fire do not place obstacles enclosures and grilles in front of or surround ing the air conditioner in a way that may block air flow AVOID direct sunlight e nearby heat sources that may affect performance of the unit e areas where leakage of flammable gas may be expected places where large amounts of oil mist exist DO select an appropriate position from which every corner of t
8. After the test run is completed be sure to press the ACL Reset button to return to normal mode The air condi tioner will not operate correctly if this is not done HIGH POWER button ne FAN SPEED MODE FLAP NIGHT SETBACK TIMER lamp ex HIGH POWER lamp REMOTE CONTROL receiver Fig 31 19 ON OFF Wo operation button ACL Reset button Basic Functions of the Service Valves The basic functions of the service valves are given in Table 7 below Table 7 Narrow Tube Service Valve 2 Way Action CLOSED O ring Shipping 22 Wide Tube Service Valve 3 Way lt gt Valve VIS PB TD Fully OPEN Operating and test running the air conditioner Measuring pressure and gas charging 27721 Air purging with a Vacuum pump 7022222 C A V IN The service port on the wide tube ser vice valve Uses a Schrader core valve to access the refrigerant system Therefore be sure to use a hose con nector which has a push pin inside When opening or clos Close ing the service valve Open stem use the accessory kan hex wrench Be sure to fully seat the wrench Fig 33 before turning the valve Pump Down Pump down means collecting all refrigerant gas in the system back into the outdoor unit without losing any of the gas Pump down is u
9. Outdoor Unit CH1872 26 3 8 670 34 21 32 880 11 7 32 285 Dimensions amp Weight Outdoor Unit Unit Dimensions Height Package Dimensions Height 14 31 32 380 kg 97 0 44 0 kg 105 8 48 0 Weight Net Ib Shipping Ib Shipping Volume cu ft m 9 88 0 28 DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks Rating conditions are Cooling Indoor air temperature 80 F D B 67 W B Heating Indoor air temperature 70 F D B Outdoor air temperature 95 F D B 75 F W B Outdoor air temperature 47 F D B 43 F W B 2 1 3 Indoor Unit XHS1872 amp PNR XS1872 Outdoor Unit CH1872 lt 208V gt Voltage Rating 208V Single Phase 60Hz Cooling Heating 17 500 4 000 to 17 500 20 400 4 400 to 20 400 kW 545 1 2105 15 60 1 3106 0 10 600 6 900 Air Circulation High ft min m h 341 580 383 650 4 89 Performance Moisture Removal High Pints Available Voltage Range Running Amperes Power Input Power Factor 187 to 253 9 1 1 2t09 1 11 5 1 310 11 5 1 860 250to 1 860 2 340 270 to 2 340 9 41 Electrical Rating Om sie I CD U Tl 5 oo e m m JJ O N gt Compressor Locked Rotor Amperes 17 5 Fuse or Circuit Breaker Capacity Controls Temperature Control Control Unit Timer Fan Speeds Indoor Outdoor Airflow Direction Indoor Horizontal Vertical Auto Washable Anti Mold DC Twi
10. TECHNICAL amp SERVICE MANUAL SANYI XHS1271 amp PNR XS1872 1271 XHS1872 amp PNR XS1872 CH1872 Destination North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No Product Code No Body Panel cm n 185233022 _ XHS1872 PNR XS1872 XHS1271 Body amp PNR X8S1872 Panel XHS1872 Body amp PNR XS1872 Panel CH1872 Wired Remote Controller RAT 0 Option REFERENCE NO SM700766 Important Please Read Before Starting This air conditioning system meets strict safety and operating standards As the installer or service person it is an important part of your job to install or service the system so it operates safely and efficiently For safe installation and trouble free operation you must Carefully read this instruction booklet before beginning Follow each installation or repair step exactly as shown Observe all local state and national electrical codes Pay close attention to all warning and caution notices given in this manual This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death This symbol refers to a hazard or unsafe practice which can CAUTION result in personal injury or product or property damage If Necessary Get Help These instructions are all you need for most installation sites and maintenance conditions If you r
11. c L N Grounding line Fig 7a CH1872 NT n switc Terminal Field supply es fae a ae ey Single phase 230 208V 60HZ Power supply Grounding line Fig 7b e A disconnect switch may be required by national or local codes Always comply with national and local code requirements 3 9 Wiring Instructions for Inter unit Connections 1 Remove the 1 screw from the terminal cover then open the cover Be careful that the cover does not fall 2 Remove the 3 screws from the power box cover then open the cover Be careful that the cover does not fall 3 Use the screw to securely fasten the ground wire from the outdoor unit in place 4 Remove the transparent plastic cover from the 3P terminal plate 5 While viewing the wiring diagram connect the inter unit and power supply line to terminals 1 2 and 3 on the 3P terminal plate 6 Remount the transparent plastic cover onto the 3P terminal plate 7 Be sure to use the clamping strap to fasten the wires in place 8 Tighten the screws to remount the terminal and the power box cover WARNING Loose wiring may cause the ter minal to overheat or result in unit malfunction A fire hazard may also exist Therefore be sure all wiring is tightly connected When connecting each power wire to the corresponding terminal fol low the instructions How to connect wiring to the terminal and fasten the wire securely tight with
12. method that ensures that the unit will be securely Ceiling opening dimensions and safely suspended Fig 6 1 21 1 32 534mm Suspension bolt pitch Follow the diagram to make the holes in the ceiling Suspension bolt pitch 23 5 8 600mm Ceiling opening dimensions Determine the pitch of the suspension bolts using the supplied full scale installation diagram The dia gram shows the relationship between the positions of the suspension fitting unit and panel Fig 6 2 3 3 Placing the Unit Inside the Ceiling R 1 Be sure to remove the fan protection 4pcs for M 22 5 8 575mm Drain tube i i i i 2 3 32 6 5 16 6 11 16 connection port transportation before hanging up the indoor unit tam Mom T aol outer dia 1 1 32 26mm 2 When placing the unit inside the ceiling determine the pitch of the suspension bolts using the supplied full scale installation diagram Fig 6 3 Tubing and wiring must be laid inside the ceiling when suspending the unit If the ceiling is already constructed lay the tubing and wiring into position 2 Power supply port Refrigerant tubing joint for connection to the unit before placing the unit inside the ceiling 1 4 6 35mm flared Fig 6 2 The length of suspension bolts must be appropriate for a distance between the bottom of the bolt and the bottom of the unit of
13. installed insert a flathead screwdriver into the slot on the bottom of the case and turn it Fig 5 B Installing directly onto the wall 1 5 Insert a flathead screwdriver into the 5 tab locations and disconnect the back plate of the remote controller by lift ing up slightly Fig 2 b The tabs are thin take care not to chip them Use tapping screws to directly fasten the remote con troller back plate onto the wall Fig 6 Insert the connector into the PCB of the remote con troller unit and wrap the wire harness around the hook Fig 4 Use nippers or a similar tool to cut out the slot on the top of the remote controller unit Pass the wire harness through the slot then hook the remote controller unit onto the top of the back plate and install the remote con troller unit In order to conceal the exposed wiring use a wire cover locally purchased or similar means When installing the remote controller back plate be sure that it is flat and straight Do not over tighten the installa tion screws Install the remote controller away from all sources of elec trical noise Install a noise filter or take other appropriate action if elec trical noise affects the power supply circuit of the unit In wall junction box locally purchased E N co 5 5 NR V V 2 3 8 R Back 60mm plate Fig 2 a Fig 2 b from the indoor unit In wall junct
14. screws manual 5 32 x 15 16 Tapping 4x25mm Installation screws Instructions other object so that it is separated from the air circula tion of the room Mount the remote controller inside the room being air Spacers D 2 conditioned Switching the room temperature sensor Room temperature sensors are separately incorporated in both the indoor unit and the remote controller Either sensor can be used to sense the room temperature The indoor unit sensor is usually used If you wish the remote controller to sense the room temperature press the SENSOR button with a ballpoint pen or tool with a small tip Refer to Fig 9 on page 4 to locate the SENSOR button H How to install the remote controller IMPORTANT The remote controller is set to Cool Dry Heat model at the time of shipment from the factory If the purchased air C conditioner is a COOL DRY model follow the instructions on the label and change the switch on the reverse side of A the remote controller unit to Cool Dry model Fig 1 ener a The remote controller is also set to Single at the time of Circuit Board with a metal shipment from the factory For multiple use set the switch rod a screwdriver edge nor a bare hand when power is on the reverse side of the remote controller unit to Multi Fig 1 supplied e After all work is completed if any switches have been changed then be sure to press the ACL Reset button
15. use the remote controller and follow the steps below to conduct the test run 1 Set the remote controller in Test Run mode Fig 9 a Press and hold the NIGHT SETBACK button and the 1HR TIMER button b Then press and hold the ACL Reset button with a pointed object such as the tip of a pen After 5 seconds release the ACL button first c Then release the NIGHT SETBACK and 1HR TIMER buttons d appears and oP 1 blinking in the remote con troller clock display area Fig 10 2 Start Cooling mode test run by pressing the ON OFF operation button of the remote controller Fig 9 his starts the fan producing uncooled forced air with the 3 indicator lamps OPERATION lamp TIMER lamp and HIGH POWER lamp on the main unit blinking Fig 11 After 3 minutes the system shifts into cooling operation and cool air will start to be felt Cooling mode test run is unaffected by the room tempera ture 3 Press the ON OFF operation button of the remote controller again to stop the test run Fig 9 4 Finally press the ACL Reset button of the remote controller to release it from Test Run mode to return to normal mode Fig 9 e and oP 1 will disappear from the remote controller clock display area Troubleshooting In the event that the green OPERATION lamp is blinking upon powering up the system an error condition exists In this case refer to the self diagnostics procedure which can
16. 15 770 20 440 21 690 22 950 25 970 1 Rating conditions Indoor Unit Entering Air Temp 70 F 21 1 D B 383 CFM 80 26 7 11 510 11 890 12 780 13 710 14 730 15 810 16 930 18 090 19 240 20 460 21 700 22 960 24 190 25 460 25 950 Outdoor Ambient Temp 47 F 8 3 C 43 F 6 1 C W B 2 Above data does not take Defrost Operation Overload Prevention Protection and or Cold Air Prevention Protection during heating operation into account For this reason the value may vary from the actual heating characteristics 3 Above data represents the value when the operation frequency of a compressor is fixed 31 6 ELECTRICAL DATA 6 1 Electrical Characteristics Indoor Unit XHS1271 amp PNR XS1872 Outdoor Unit CH1271 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 115V Single phase 60Hz Rating conditions Running amp 12 39 Power input 1 242 1 260 Rating conditions Indoor air temperature 80 F 26 7 C D B 67 F 19 4 C W B Outdoor air temperature 95 F 35 Indoor Unit Outdoor Unit Complete Unit Fan Motor Compressor Heating Performance at 115V Single phase 60Hz Rating conditions Running amp 14 35 Power input 1 440 1 460 Rating conditions Indoor air temperature 70 F 21 1 C D B Outdoor air temperature 47 F 8 3 C D B 43 F 6 1 C W B 32 Indoor Unit XHS1872
17. 3 23 9 29 4 35 0 40 6 46 1 17 300 15 920 72 22 2 11 920 11 060 59 76 24 4 150 80 26 7 14 380 84 28 9 15 570 88 31 1 16 760 72 22 2 63 76 24 4 11 590 11 390 17 2 80 26 7 12 650 84 28 9 13 850 88 31 1 15 110 12 22 2 67 76 24 4 19 4 80 26 7 11 130 10 930 84 28 9 12 190 88 31 1 13 380 22 71 76 24 4 217 80 26 7 84 28 9 88 31 1 75 76 24 4 23 9 80 26 7 84 28 9 88 31 1 TC Total Cooling Capacity BTU h SHC Sensible Heat Capacity BTU h 1 Rating conditions Indoor Unit Entering Air Temp 80 F 26 7 C D B 67 F 19 4 C W B Outdoor Ambient Temp 95 F 35 C D B 2 Above data does not take Freeze Prevention Protection during cooling operation into account For this reason the value may vary from the actual cooling characteristics 3 Above data represents the value when the operation frequency of a compressor is fixed 27 5 3 Cooling Capacity Low Ambient Indoor Unit XHS1271 amp PNR XS1872 Outdoor Unit CH1271 Power Supply 115V Single Phase 60Hz lt Cooling Capacity Low Ambient gt RATING CAPACITY 11 900 BTU h AIR FLOW RATE 235 CFM INDOOR OUTDOOR ENT TEMP F C AMBIENT TEMP F C 17 8 9 4 3 9 1 7 7 2 W B D B 0 15 25 35 45 12 092 59 76 24 4 15 0 80 26 7 84 28 9 88 31 1 T2 222 76 24 4 17 2 80 26 7 84 28 9 8
18. 8 Retro Fitting Existing Systems 11 8 1 Use of Existing Units Never use new refrigerant R410A for existing units which use R22 This will cause the air conditioner to operate improperly and may result in a hazardous condition 11 8 2 Use of Existing Tubing e lf replacing an older unit that used refrigerant R22 with a R410A unit do not use its existing tubing Instead completely new tubing must be used 67 APPENDIX A INSTRUCTION MANUAL 51271 amp PNR XS1872 CH1271 XHS1872 amp PNR XS1872 CH1872 Ol 852 6 4181 107 00 0 A 1 51271 XHS1872 COOL DRY HEAT Model SANYO INSTRUCTION MANUAL Inverter Controlled Split System Air Conditioner EG MODE D EMPLOI Climatiseur de type s par contr l par inverseur This air conditioner uses the new refrigerant R410A Save These Instructions Conserver ce mode d emploi NS das r SPY e e 5 S d DUCI OL Wo e SENSN pt My i SF s OST ESQ a Lig SN Pu RENE T NM WEN E I 0 3 SENS ZW Ol 85264181107000 SANYO 2008 FEATURES This air conditioner is an inverter type unit that automatically adjusts capability as appropriate Details on these functions are provided below refer to these descriptions when using the air conditioner Microprocessor Controlled Operation e Auto Flap Control The interior compartment of the remote control unit This automatically sets the
19. FDB 2 SPECIFICATIONS 2 1 Unit Specifications 2 1 1 Indoor Unit XHS1271 amp PNR XS1872 Outdoor Unit CH1271 Voltage Rating 115V Single Phase 60Hz Cooling Heating Total Capacity BTU h 11 900 3 000to 11 900 13 600 3 000 to 13 600 kw 35 091035 40 0 9104 0 Sensible Capacity BTU h 7 200 Latent Capacity BTU h 4 700 Air Circulation High ft min m h 235 400 268 455 4 26 Performance Moisture Removal High Pints Available Voltage Range Running Amperes Power Input Power Factor 104 to 126 12 6 2 5t0 12 6 14 6 2 5t014 6 1 260 250to 1 260 1 460 250to 1 460 co N oo N 9 44 Electrical Rating 9m m 20 O I n U TI 5 gt gt ND o Oi Compressor Locked Rotor Amperes Fuse or Circuit Breaker Capacity Controls Temperature Control Control Unit Timer Fan Speeds Indoor Outdoor Airflow Direction Indoor Horizontal Vertical Auto Washable Anti Mold DC Rotary Inverter RATOA 2 43 1 100 Electric Expansion Valve Operation Sound Indoor Hi Me Lo dB A 34 32 31 35 34 32 Outdoor Hi dB A 47 49 Refrigerant Tubing Connections Flare Type 25 7 5 Refrigerant Narrow tube inch mm 1 4 6 35 Tube Diameter Wide tube inch mm 3 8 9 52 Air Clean Filter Wired Remote Controller Option STK RCS 7TWSU N O Microprocessor Thermister Wireless Remote Control Unit 24 Hour ON or OFF Timer 1 Hour OFF Timer Auto a
20. HIGH POWER button on the remote controller It can be set regardless of the temperature and fan speed settings HIGH POWER operation from remote controller The unit operates at maximum output for 30 minutes regardless of the desired temperature The fan speed is 1 step above High Frequency 30 min 5 min V Start End NOTE e When HIGH POWER operation ends the unit operates at low Hz for 5 minutes regardless of the thermostat OFF conditions When in DRY mode operation is in the cooling zone H Lamp colors OPERATION lamp HEAT operation Red DRY operation Orange COOL operation Green FAN operation Green DEFROSTING operation Red and Orange alternately OPERATION lamp Green TIMER lamp Green HIGH POWER lamp Green H Timer backup Operation stops if there are no operator controls for 25 hours or longer after unit operation switched from OFF to ON by use of ON timer operation NIGHT SETBACK When NIGHT SETBACK operation is set the temperature and fan speed settings will be adjusted automatically to allow comfortable sleep When NIGHT SETBACK operation is set mark appears on the remote controller The main unit display lamp also becomes dimmer e COOL and DRY modes When the night setback mode is selected the air conditioner automatically raises the temperature setting 2 F 1 C when 30 minutes have passed after the selection was made and then another 2 F 1 C after another 30 min
21. Installation 5 5 5 6 9 7 AIR PURGING in anina ian aana naan anaana aaaann 17 BI Air Purging with a Vacuum Pump for Test Run Basic Functions of the Service Valves E Pump Down H Service Valve Connections SANYO Commercial Solutions A Division of SANYO North America Corporation 1300 Michael Drive Suite A Wood Dale IL 60191 U S A 8526419047 7000 SANYO 2008 Model Combinations Combine indoor and outdoor units only as listed below Indoor Unit Outdoor Unit XHS1271 CH1271 Power Source 60 Hz single phase 115 V XHS1872 CH1872 Power Source 60 Hz single phase 230 208 V Ceiling Panel PNR XS1872 Be sure to read the yellow instruction sheet attached to the outdoor unit for models using the new refrigerant R410A 7 REMOTE CONTROL UNIT INSTALLATION POSITION 21 7 1 Mounting Wall 8 ADDRESS SWITCH 22 8 1 Address Setting of the Remote Control Unit NOTE The illustrations are based on the typical appearance of a standard model Consequently the shape may differ from that of the air conditioner that you are installing In Canada SANYO Canada Inc 1 300 Applewood Crescent Concord Ontario L4K 5C7 Canada W IMPORTANT Please Read Before Starting This air conditioning system meets strict safety and operating standards As the installer or service person it is an imp
22. Model KTEC 35 S98 50 59 68 77 86 95 10 15 20 25 30 85 gt Temperature F 40 Resistance k ohm 16 Indoor heat exchanger sensor Model PT2M 51H S3 Compressor temp sensor CH1271 Model DTN TKS274Y TH2 CH1872 Model DTN TKS293B 32 50 68 86 104 122 140 158 176 194 0 10 20 30 40 50 60 70 80 90 Temperature F C Outdoor air temp sensor CH1271 Model DTN TKS269B CH1872 Model TKS295B Outdoor heat exchanger sensor CH1271 Model DTN TKS274Y TH1 CH1872 Model TKS292B 40 sA LL 30 N LLLLI sN ST o NII _ tt DER pti tt 14 23 32 41 50 59 68 20 15 10 5 0 5 10 15 20 Temperature F XHS1271 amp PNR XS1872 XHS1872 amp PNR XS1872 3 DIMENSIONAL DATA Indoor Unit pe ejsui eq jouueo HUN eui pue jeued Buieo eui 1261000 00 SI 109 uoisuedsns eui j ye y ui UMOUS se HUN y JO eoeuns J9M0 y MOJ 9q 9JOUJ JO Z L2 Bulao y JO 91 JO deb e si 3194 Jey os eq p nous soq uoisuedsns eui Jo uiBue eu YG C3 N N E 90 CE L UEY SSO LE 5591 0016 00 90 9L LL 9 909 9
23. ON OFF button again ELA A h The 3 lamps remain OFF if no trouble has occurred d Bg IMPORTANT After self diagnostics is completed be sure to press the ACL reset button to return to normal mode The air conditioner will not operate if this is not done 50 1 Self diagnostics Lamps OPERATION button OPERATION lamp gt TIMER lamp A HIGH POWER lamp REMOTE CONTROL receiver e Since the indications cover various units the corresponding parts listed below may not be present in some models Indication on indoor unit X OFF 3 Blinking 4 ON Illuminated OPERATION HIGH POWER 2 Diagnostics items Diagnostics contents Room temperature sensor failure Timer 1 Sensor open circuit or short circuit 2 Contact failure at connector or open circuit at terminal crimping location Indoor heat exchanger sensor failure 3 Indoor outdoor PCboard failure Compressor temperature sensor failure m 1 Sensor open circuit or short circuit 2 Contact failure at connector or open circuit at terminal crimping location Outdoor heat exchanger sensor failure 3 Outdoor PCboard failure Outdoor air temperature sensor failure 07 ee electrical current detection Gi tdcorPObosrd failure 1 Mis wiring 2 AC power failure 3 Blown fuse 4 Power Relay failure E01 Indoor outdoor communications failure 5 Indoor or outdoor PCboard failure 6 Outdoor Fan Motor failure 7 Reactor failure seria
24. PM 11 is displayed e Press the MM button until 30 is displayed Press the ON OFF button to start the air conditioner Press the TIMER SELECT button twice to set OFF time The display will change automatically back to show the present time after about 10 sec The present time is displayed The present time and are displayed 3 How to set the ON time Example To start operation at 7 10 am UAM 00 4 nen Kl re l L PM h MI ON TIME E _ 1 Press the SET button once The timer indication alone flashes and the previous set time is only displayed Present time 2 Press the HH button until AM 7 is displayed Press the MM button until 10 is displayed 3 Press the ON OFF button to start the air conditioner 4 Press the TIMER SELECT button once to set ON time The display will change automatically back to show the present time after about 10 sec The present time is displayed The present time and are displayed 4 How to set daily ON OFF repeat timer Example To start operation at 7 10 am and stop the air conditioner at 11 30 pm E4 re 4 14 451 Z6 D Co OPM O 00 0 Present time OFF TIME UAM 00 Wl L4 w Co L COMOPM 4 L ON TIME Programmed daily ON OFF 9 10 pm 7 10 am 11 30 pm Present time ON OFF Set the timer ON OFF times as shown in 2 and 3 Press the ON OFF button to start the
25. When set to 80 F Model temperature indication Model 4 Timer MILD 24 hour clock with ON OFF Co program Timer DOS EN O OFF Timer o N O 2 Fan speed 1 hour OFF Timer 1 H R D Automatic operation 5 NIGHT SETBACK 6 Flap angle indication Sweep indication N Ol 119 3 EG 3 REMOTE CONTROL UNIT The descriptions on the AUTO A or HEAT operation mode are only for the COOL DRY HEAT Model and not for the COOL DRY Model Display Information on the operating conditions is displayed while the remote control unit is switched on lf the unit is turned off only the mode that was set previously is still displayed Temperature setting buttons TEMP Press the a button to increase the set temperature Press the S button to reduce the set temperature The temperature setting changes by 2 F each time one of the TEMP buttons is pressed FAN SPEED selector button A The air conditioner automatically decides the fan speeds e High fan speed amp Medium fan speed e Low fan speed NIGHT SETBACK button For details see 5 Night Setback Mode When you press this button in the HEAT DRY or COOL mode the Fe mark appears in the display and the remote control unit will auto
26. XS1872 Indoor Unit Q gt 20 o O AL r C n lt S S Gc ZI e 620 ol V oo 2 pus O c 0069t 0S29 cV 48 a UO o H3TIOHLINOO C gt OO 13A d LHM dS LHM dZ LHM dv C a NOOH S4 QNI OH d MOd INMd o 9 c is e e e t 2 e s v z t L 9 s v e E HTC isivieizhi 121915191110 1 e s v e 2 1 CITT TTT YITIOYLNOI LHM d9 N1g N1g d9 dz MOd NMd 9 6 2 Zjojsjr ejc r TaNNYD t HOLIMS 1VO 14 YOLSINYAHL ASSY dNV1 YOLOW NVA dNNd NIVHG 3SV8 TVNIINH3 L DOO LINN HOOALNO OL IS cOV LOV Q 4409 6 IHH D 34 Outdoor Unit CH1271 To avoid electrical shock hazard be sure to disconnect power before checking servicing AN and or cleaning any electrical parts REACTANCE L POWER RELAY 1P CONNECTOR WHT 1P CONNECTOR WHT 2P CONNECTOR BLK E I C HEATER2 1 CRANKCASE HEATER CONTROLLER TO INDOOR UNIT M OUTDOOR COIL COMP yyy 112131415 7 IL H O 2 Q ku HIGH PRESSURE SWITCH BLK 1 917 2P CONNECTOR WHT BLK BLK YEL YEL BLK BLK FERRITE COIL THERMISTOR COMPRESSOR THERMISTOR YEL xy s
27. YEL 7P CONNECTOR WHT PNK H OUT DOOR THERMISTOR 4WAY VALVE COIL S U MAGNETIC COIL GRN YEL OVERLOAD RELAY amp COMPRESSOR MOTOR OLR FAN MOTOR 2P CONNECTOR BLK 8FA2 5257 69100 3 35 Outdoor Unit CH1872 To avoid electrical shock hazard be sure to WARNING disconnect power before checking servicing and or cleaning any electrical parts REACTANCE L WHT WHT POWER RELAY 2P CONNECTOR WHT N WHT WHT GRN YEL GRN YEL BD BD HIC HIC 2 2 A2 ET E FERRITE TERMINAL CORE H CONTROLLER TO INDOOR UNIT COMP A TH COIL OUTDOOR AONGA Hvo 1121314 1121314 gt N SUPPLY IL O 2 pd Q BLK BLK BLK BLK YEL YEL FERRITE HIGH PRESSURE SWITCH BLK 19173 BLK 2P CONNECTOR BLK PNK CORE COMPRESSOR THERMISTOR OUT DOOR THERMISTOR COIL THERMISTOR 7P CONNECTOR WHT 2P CONNECTOR WHT AA LU LU MAGNETIC COIL GRN YEL OVERLOAD RELAY AWAY VALVE COMPRESSOR MOTOR OLR FAN MOTOR COIL 2P CONNECTOR RED 8FA2 5257 64000 2 36 7 MAINTENANCE 7 1 Address Setting of the Remote Control Unit The address can be set in order to prevent interference between remote controllers when two indoor units are installed near each other The address is normally set to A To set a different address it is necessary to change the address on the second remote controller N
28. and DRY Mode and When the night setback mode is selected the air conditioner automatically raises the temperature setting 2 F when 30 minutes have passed after the selection was made and then another 2 F after another 30 minutes have passed regardless of the indoor temperature when night setback was selected This enables you to save energy without sacrificing comfort This function is convenient when gentle cooling is needed Setting temperature L Press the NIGHT SETBACK button B In Heating Mode x When the night setback mode is selected the air conditioner automatically lowers the temperature setting 4 F when 30 minutes have passed after the selection was made and then another 4 F after another 30 minutes have passed regardless of the indoor temperature when night setback was selected This enables you to save energy without sacrificing comfort This function is convenient when gentle heating is needed Setting temperature Press the NIGHT SETBACK button HIGH ON I OFF O POWER FAN SPEED MODE FLAP NIGHT SETBACK HIGH POWER mode can be used to increase the output of the indoor unit for all operation modes except automatic operation Press the HIGH POWER button while operation The 7 mark appears in the display To cancel press HIGH POWER button again Ol 107 10 EG e When the HIGH POWER button is pressed the unit operates at maximum output for 30 minut
29. be allowed to touch refrigerant tubing the compressor or any moving part e avoid the risk of electric shock each air ditioner unit must be grounded For the installation of a grounding device please observe local electrical codes Grounding is necessary especially for units using inverter circuits in order to release charged electricity and electrical noise caused by high tension Otherwise electrical shock may occur Place a dedicated ground more than 7 2 m away from other grounds and do not have it shared with other electric appliances Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram The indoor unit draws its power from the outdoor unit e Do not run wiring for antenna signal or power lines of television radio stereo telephone secu rity system or intercom any closer than 3 3 1 m from the power cable and wires between the indoor and outdoor units Electrical noise may affect the operation Cross Sectional A B A Power Supply Wiring Length ft C Control MEN Area AWG B Power Line Length ft Line Length tt Fuse or Circuit Breaker Capacity Model 414 412 414 CH1271 131 Max 230 Max 65 Max 20A CH1872 131 Max 230 Max 98 Max 20A 12 AWG American Wire Gauge WIRING SYSTEM DIAGRAM CH1271 INDOOR OUTDOOR UNIT switch UNIT Terminal Field supply gt
30. coaxial cable Use a noise filter for the wireless device Use a signal booster 58 10 CHECKING ELECTRICAL COMPONENTS 10 1 Measurement of Insulation Resistance e The insulation is in good condition if the resistance exceeds 1M ohm 10 1 1 Power Supply Cord Clamp the grounding wire of power cord with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on either of the two power wires Fig 1 Then also measure the resistance between the grounding and other power terminals Fig 1 10 1 2 Indoor Unit Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw on the terminal plate Fig 2 Note that the ground line terminal should be skipped for the check 10 1 3 Outdoor Unit Clamp a metallic part of the unit with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw where power supply lines are connected on the terminal plate Fig 2 10 1 4 Measurement of Insulation Resistance for Electrical Parts Disconnect the lead wires of the desired electric part from terminal plate capacitor etc Similarly disconnect the connector Then measure the insulation resistance Figs 3 and 4 Refer to Electric Wiring Diagram If the probe cannot enter the poles because the hole is too narrow the
31. indoor and outdoor units have been proper ly connected and all wiring for the test run has been completed Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage 2 Using an adjustable wrench or box wrench remove the valve caps from the service valve on both narrow and wide tubes 3 Connect a vacuum pump and a manifold valve with pressure gauges to the service port on the wide tube service valve Fig 27 l Clamp Insulated tubes Drain hose Apply putty here Tubing Fig 26 Indoor unit E Outdoor unit EX lg KY e xe Manifold valve Exclusively for R410A gauge The service port on the wide tube service valve CAUTION uses a Schrader core valve to access the refrigerant system The valve core is similar to those used in automobile tires Therefore be sure to use a vacuum hose connector which has a push pin inside Be sure to use a manifold valve for CAUTION air purging If it is not available use a stop valve field supply for this purpose The Hi knob of the mani fold valve must always be kept closed 17 Eze 2S ROSS oc EE 905904 ssi Besesesy Charging hose Exclusively for R410A Vacuum pump adapter Exclusively for R410A Lel aro with reverse flow prevention 7 fo O Vacuum pump Fig 27 4 With the Lo knob of the manifold valve op
32. is stopped Even when operation is stopped during an ON timer program the unit will start operating when the set time is reached provided that the program is not canceled When the ON timer and OFF timer are set to the same time the timer operates as if it is turned off Ol 107 12 EG USING THE 1 HOUR OFF TIMER 1 1 Hour OFF Timer HIGH ON OFF O POWER This function causes the unit to operate for one hour and then stop regardless of whether the unit is on or off when this button is pressed The indicator in the display indicates that this function is operating Setting procedure Regardless of whether the unit is operating or stopped press the 1 HR TIMER button appears in the display Cancellation procedure Press the ON OFF operation button to turn the unit off wait for the unit to stop operating and then press the ON OFF operation button again The 1 Hour Timer function is now cancelled and the unit operates normally f while the 1 Hour Timer function is operating the 1HR TIMER button is pressed once to cancel the function and then again the unit continues to operate for one hour from that point in time and then stops e It is not possible to use the OFF Timer and 1 Hour OFF Timer together Whichever function is set last takes precedence If the 1 HR TIMER button is pressed while the TIMER OFF function operates the OFF Timer is cancelled and the unit will stop operating one hour later 2
33. more than 19 32 15 mm as shown in the diagram Fig 6 3 23 32 13 18mm 1 2 Thread the 3 hexagonal nuts locally purchased 2 supplied washers onto each of the 4 suspension bolts as shown in the diagram Use 1 nut and 1 E RD T washer for the upper side and 2 nuts and 1 washer 7 for the lower side so that the unit will not fall off the printed on top of container box suspension lugs Fig 6 4 Fig 6 3 5 Adjust so that the distance between the unit and the Suspension bolt ceiling bottom is 1 2 13 mm to 23 32 18 mm Tighten the nuts on the upper side and lower side of the suspension lug Fig 6 4 Nuts and washers Suspension lug used for upper and lower Double nut 1 2 23 32 13 18mm Fig 6 4 Twist tie 3 4 Installing the Drain Piping 4 vinyl ties supplied 1 Prepare standard hard PVC pipe locally purchased O D ee C Position to 1 1 32 26 mm for the drain and use the supplied hose supplied 1 1 32 26mm fasten hose locally purchased band to prevent water leaks Fig 6 5 2 To install the drain hose first place 1 of the 2 hose bands ARR over the unit drain port and the other hose band over the PVC pipe supplied Then connect both ends SY do vh us 7773 ec the supplied drain hose Fig 6 5 277 24 Drain
34. on the outdoor unit terminal strip Serial Communication Line Fig 1 1 Turn OFF the power and wait until the power lamp LED No of the outdoor unit controller is turned OFF 2 Disconnect the cable from the terminal 3 on the indoor unit terminal strip Fig 2 3 Turn ON the power Yes A B Continued to the next page A Continued to the next page B 53 Continued from the previous page A Continued from the previous page B Is the voltage of about DC22V to 24V given between the terminals 2 and 3 on the indoor unit terminal strip Serial Communication Line Yes Defect or connection error Defect in the indoor unit in the inter unit cable P C board Turn OFF the power and wait until the power lamp LED Outdoor Unit of the outdoor unit controller is turned OFF Short circuit between the terminals 2 and 3 on the outdoor unit terminal strip Fig 3 Indoor Unit Turn ON the power and operate the system using the remote controller or the operation button on the indoor unit Fig 3 Perform the self diagnosis five seconds after the operation start Condition E12 Defect in the outdoor unit P Ai 9 What is the latest self diagnosis result P C board Condition EO1 Outdoor Unit Outdoor Unit Turn off the power and wait until the power lamp LED of the outdoor unit controller is turned OFF Remove the short circuit between the terminals
35. ring connector fastener or pliers securely clamp each stripped wire end with a ring connector Fig 11 4 Place the ring connector wire and replace and tighten the removed terminal screw using a screwdriver Fig 13 Special washer 7 Screw 1 ao M Buandedwite Twist wire ends TE gt E P Ring connector special washer o gt Rj B Wire Terminal plate mW Ring X R connector oD 2 in 2 E 4 Wire Fig 11 Fig 12 Fig 13 4 How to Install the Outdoor Unit First refer to Section 2 Installation Site Selection Lock nut Cabinet 4 1 Wiring Instructions for the Outdoor Unit Regulations on wire size differ from locality to locality For field wiring requirements please refer to your local electrical codes Make sure that the installation S fully complies with all local and national regulations block 1 Remove access panel C Fig 14 2 Connect the inter unit and power supply line according to the drawing on the panel side Conduit plate 3 Be sure to size each wire allowing approx 4 10 cm longer than the required length for wiring Store excess wiring inside the cabinet 4 When connections are completed check that all Access panel C connections are correct as shown in the wiring system diagram on panel side Plug Inter unit Power supply Conduit Conduit S b Be sure to ground the unit according to your l
36. second indoor unit approximately 5 times The sound you hear is the signal that the remote controller address has been changed 9 7 Finally press the remote controller ACL Reset button to cancel the blinking oP 7 display Fig 39 Changing of the second remote controller address is now completed 22 ACL button OOOO OOOO AIR CONDITIONER A39 68888 FZ SET TEMP SA PF LN EN OFFS AM 7444 TAITI PM L 4 104 DAS HIGH ON T OFF O POWER ON OFF O OT operation button HIGH POWER 1 button TEMP 1 CS7 1 ADH a button FAN SPEED MODE FLAP NIGHT SETBACK TIMER SENSOR C F 12H4b 24H ADR ACL A J IC ACL Reset d p button Fig 39 APPENDIX C INSTRUCTION MANUAL STK RCS 7TWSU 01 852 6 4181 119 00 0 STK RCS 7TWSU This wired remote controller is designed for both the COOL DRY HEAT Model and COOL DRY indoor unit Before using the remote controller be sure to confirm the model type specified on the front cover of the INSTRUCTION MANUAL supplied with the indoor unit ASA X i 90009 UA ARN UE ELPA THE SS STEN xT A Cop Sea RAO SAND DEA cancer S NS EN Ue REASONS STR BOTN KAR STR que e FAAS ZIRE ES MS CH EK Q Ai Cay Cay 01 852641811 19000 SANYO 2008 SANYO
37. settings are used for the temperature and time indicator selector button on the bottom front section of the remote control Temperature F Time AM PM 1 How to set the present time Example To set to 10 30 pm 1 Press the CLOCK button The time indication alone once if the time indicator is flashes not flashing Press the Advance Return The time can be set in 1 minute a v button until PM 10 30 increments Holding down the is displayed button advances the time rapidly in 10 minute increments Press the CLOCK button This completes the setting of the again current time 11 2 How to set the OFF time Example To stop the air conditioner at 11 00 am Wem 1 Press the OFF TIME setting button once 2 Press the Advance Return a v button until AM 11 00 is displayed 3 Wait a few seconds and then the setting is complete The timer 0 indication is displayed and the present OFF time is shown The timer indication blinks The time can be set in 10 minute increments Holding down the button advances the time rapidly in 10 minute increments The timer OFFO J indication stops blinking and the present time is displayed 3 How to set the ON time Example To start operation at 7 10 am gt ju w mee ee a gt wy ka gt l p al an gt R 1 Press the ON TIME setting bu
38. the drain hose or other elements Air leakage Air leakage from N Uf ceiling surface 47 AA AA AV AV AY AV AV AV AY AP AV ATA TZZZA Staining i Staining o Adjust so that there are no gaps Condensation water leakage Fig 6 20 9 3 6 3 Wiring the Ceiling Panel and the Indicator SS 1 Remove the 2 screws from the control box cover then open the cover Be careful that the cover does not fall M 2 Connect the 5 FLAP wiring connector from the ceiling Control box panel to the connector on the control PCB in the control box Fig 6 21 Refrigerant tube side K EN 3 Connect the 7P IND and 4P RC wiring connector from the Indicator cover indicator to the connectors on the control PCB in the control Power box box Fig 6 21 As to how to attach the indicator cover refer to Fig 6 23 4 Be sure to use the clamps to fasten the connector wires in place Fig 6 21 Fig 6 22 5 Tighten the 2 cover screws to Ceiling panel Indoor unit Indicator 7P IND and 4P RC wiring connector close the cover 5P FLAP wiring connector Check that the wiring connectors are not caught between the electrical component box and the cover e the indicator connector is not securely connected HNT remote controller ame P signal w
39. zojc z GZS 8 9 5 8 4 elp uod JONp ygu usoJJ 2 o 10y 8 1 1 X 2 1 7 9Iou YO uorsuedsng 2 Ph Ajddns Jamod o N L 821p uod uonoeuuoo eqni 2 d peavey etp eqni seb Buiqni juejeDujeg o 5 pasel b L eip eq pinbi juejeDujeu 2 Ol 3S FQ Beyosiq Qe 3 YB JUI 2 2 o youd y0q uoisuedsng VES 2E L LC Suoisueuiip Buiuedo bullo 009 8 S 2 V Unit inch mm 17 Outdoor Unit CH1271 3 19 32 21 3 16 3 19 32 10 13 16 R R 11 13 32 10 7 16 265 28 11 32 720 2 1 8 21 9 16 548 18 12 7 16 Wide tube service valve dia 3 8 9 52 Narrow tube service valve dia 1 4 6 35 F F JaK T Unit inch mm 852 0 0010 12700 0 Outdoor Unit CH1872 23 15 16 5 11 32 11 17 32 Wide tube service valve dia 1 2 12 70 Narrow tube service valve dia 1 4 6 35 34 21 32 880 2 17 32 Unit inch mm 852 0 0010 13200 0 19 4 REFRIGERANT FLOW DIAGRAM 4 1 Refrigerant Flow Diagram Indoor Unit XHS1271 amp PNR XS1872 CH1271 Outdoor Unit Indoor unit Outdoor unit Wide tube Accumulator P a es ag service i Wide tube valve
40. 13 490 12 810 15 070 14 220 13 460 12 770 15 050 14 190 13 430 12 740 2 Above data does not take Defrost Operation Overload Prevention Protection and or Cold Air Prevention Protection during heating operation into account For this reason the value may vary from the actual heating characteristics 3 Above data represents the value when the operation frequency of a compressor is fixed 30 Indoor Unit Outdoor Unit XHS1872 amp PNR XS1872 CH1872 Power Supply 230V Single Phase 60Hz lt Heating Capacity gt RATING CAPACITY OUTDOOR ENT TEMP F C W B 0 17 8 3 16 1 8 13 3 13 10 6 18 7 8 23 5 0 28 2 2 33 0 6 38 3 3 43 6 1 48 8 9 53 11 7 58 14 4 63 17 2 65 18 3 NOTE 20 400 BTU h TH TH TH TH TH TH TH TH TH TH TH TH TH TH TH 60 15 6 11 350 11 720 12 600 13 520 14 540 15 610 16 730 17 900 19 050 20 290 21 550 22 830 24 080 25 390 25 900 65 18 3 11 400 12 700 12 750 12 650 13 580 14 600 15 670 16 800 16 850 16 890 17 960 18 010 18 060 19 120 19 170 19 210 20 350 21 610 22 890 24 130 25 940 TH Total Heating Capacity BTU h AIR FLOW RATE INDOOR AMBIENT TEMP F C 70 21 1 11 440 13 630 14 650 15 730 20 400 21 650 22 930 24 170 24 180 25 430 25 450 25 460 25 960 75 23 9 11 480 11 850 13 670 14 700
41. 2 and 3 on the outdoor unit terminal strip Disconnect the cable from the terminal 3 on the indoor unit terminal strip Fig 4 Indoor Unit Indoor Unit Short circuit between the terminals 2 and 3 on the indoor unit Fig 4 Fig 5 terminal board Fig 5 1 Turn ON the power and operate the system using the remote controller or the operation button on the indoor unit 2 Perform the self diagnosis five seconds after the operation start Condition E12 Defect or connection error What is the latest self diagnosis result in the inter unit cable Condition E01 Defect in the indoor unit P C board 54 3 2 Condition E12 Troubleshooting Serial Communication Outdoor Unit Turn off the power and wait until the power lamp LED of the outdoor unit controller is turned OFF Disconnect the cable from the terminal 3 on the Outdoor unit terminal strip Fig 6 Indoor Unit Fig 6 Turn ON the power and operate the system using the remote controller or the operation button on the indoor unit Perform the self diagnosis five seconds after the operation start Condition E01 What is the latest self diagnosis result gt Defect in the outdoor unit P C board Condition E12 Outdoor Unit Turn off the power and wait until the power lamp LED of the outdoor unit controller is turned OFF Disconnect the cable from the terminal 3 on the indoor unit termina
42. 4 25 30 35 40 Outdoor inlet air D B temp F C 3 Indoor discharge air performance chart NOTE Indoor discharge air temperature F C S ARTI bue 6 95 1 25 30 35 40 Outdoor inlet air D B temp F C Check each performance value in test run mode Electrical performance values represent a combined indoor outdoor value 24 Indoor Unit XHS1872 amp PNR XS1872 Outdoor Unit CH1872 Heating Characteristics RH 85 Indoor fan speed High fan 60Hz 230V 1 High pressure performance chart psig MPaG i eo 1 5 23 32 41 50 59 68 77 5 0 5 10 15 20 25 Outdoor inlet air D B temp F C High pressure at wide tube service valve 2 Operating current performance chart Operating current A 23 32 41 50 59 68 77 5 0 5 10 15 20 25 Outdoor inlet air D B temp F C 3 Indoor discharge air performance chart 131 Indoor discharge air temperature F C 5 0 5 10 15 20 25 Outdoor inlet air D B temp F C NOTE Check each performance value in test run mode Electrical performance values represent a combined indoor outdoor value Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in heating mode Refer to 8 2 Overload prevention during heating 25 5 2 Cooling Capacity Indoor Unit XHS1271 amp PNR XS1872 Outdoor
43. 8 31 1 12 22 2 67 76 24 4 19 4 80 26 7 84 28 9 88 31 1 72 22 2 71 76 24 4 21 7 80 26 7 84 28 9 88 31 1 75 76 24 4 23 9 80 26 7 84 28 9 88 31 1 TC Total Cooling Capacity BTU h SHC Sensible Heat Capacity BTU h 1 Above data does not take Freeze Prevention Protection during cooling operation into account For this reason the value may vary from the actual cooling characteristics 2 Above data represents the value when the operation frequency of a compressor is fixed 28 Indoor Unit XHS1872 amp PNR XS1872 Outdoor Unit CH1872 Power Supply 230V Single Phase 60Hz lt Cooling Capacity Low Ambient gt RATING CAPACITY 17 500 BTU h AIR FLOW RATE 341 CFM INDOOR OUTDOOR ENT TEMP F C AMBIENT TEMP F C W B D B 0 15 25 35 45 55 17 8 15 0 9 4 3 9 1 7 7 2 12 8 14 930 14 970 14 980 14 970 72 22 2 10 530 10 530 10 600 10 530 59 76 24 4 15 0 80 26 7 12 980 12 980 84 28 9 14 80 14 180 88 31 1 14 930 14 970 14 980 14 970 72 22 2 63 76 24 4 17 2 80 26 7 11 060 11 130 11 330 84 28 9 12260 12 320 88 31 1 13 450 13 510 13 510 13 580 72 22 2 67 76 24 4 19 4 80 26 7 84 28 9 10 330 10 400 88 31 1 721222 71 76 24 4 21 7 80 26 7 84 28 9 88 31 1 75 76 24 4 23 9 80 26 7 84 28 9 88 31 1 TC Total Cooling Capacity BTU h SHC Sensible Heat Capacity B
44. 87 to 253 8 3 1 2108 3 10 5 1 3 to 10 5 1 860 250 to 1 860 2 340 270 to 2 340 co N N oo co 9 41 Electrical Rating egim m 20 O I CD U Tl 5 gt Compressor Locked Rotor Amperes 17 5 Fuse or Circuit Breaker Capacity Controls Temperature Control Control Unit Timer Fan Speeds Indoor Outdoor Airflow Direction Indoor Horizontal Vertical Auto Washable Anti Mold DC Twin Rotary Inverter RATOA 2 87 1 300 Electric Expansion Valve Operation Sound Indoor Hi Me Lo dB A 44 40 36 44 40 36 Outdoor Hi dB A 51 52 Refrigerant Tubing Connections Flare Type 25 7 5 Refrigerant Narrow tube inch mm 1 4 6 35 Tube Diameter Wide tube inch mm 1 2 12 7 Air Clean Filter Wired Remote Controller Option STK RCS 7TWSU N O Microprocessor Thermister Wireless Remote Control Unit 24 Hour ON or OFF Timer 1 Hour OFF Timer Auto and 3 steps Auto Hi Me Lo Indoor Unit XHS1872 amp PNR XS1872 Outdoor Unit CH1872 230V Individual Unit Indoor Unit Dimensions amp Weight Indoor Unit Body Panel XHS1872 amp PNR XS1872 XHS1872 51872 Unit Dimensions Height Package Dimensions Height P84 13782 290 4 1 8 105 Pd 2 4 18 16 630 26 3 16 665 28 1 8 714 26 11 16 678 Weight Net Ib kg Siang o tig T 88 Shipping Volume o cuft m 4 59 0 13
45. ANYO INSTALLATION INSTRUCTIONS Inverter Split System Air Conditioner COOL DRY HEAT Model This air conditioner uses the new refrigerant R410A Refrigerant service valve size 5 16 Contents Page IMPORTANT Please Read Before Starting 2 1 GENERAL annaaianaaaaaaaaai aaas aasavunaann 3 Tools Required for Installation not supplied Accessories Supplied with Unit Optional Copper Tubing Kit Type of Copper Tube and Insulation Material Additional Materials Required for Installation ee ee INSTALLATION SITE SELECTION 4 2 1 Indoor Unit 2 2 Outdoor Unit HOW TO INSTALL THE INDOOR UNIT 6 3 1 Preparation for Suspending 3 2 Suspending the Indoor Unit 3 3 Placing the Unit Inside the Ceiling 3 4 Installing the Drain Piping 3 5 Checking the Drainage 3 6 How to Install the Ceiling Panel 3 7 Wiring Instructions 3 8 Recommended Wire Length and Diameter 3 9 Wiring Instructions for Inter unit Connections HOW TO INSTALL THE OUTDOOR UNIT 14 4 1 Wiring Instructions for the Outdoor Unit REFRIGERANT TUBING 15 5 1 Use ofthe Flaring Method 5 2 Flaring Procedure with a Flare Tool 5 3 Caution before Connecting Tubes Tightly 5 4 Connecting Tubing between Indoor and Outdoor Units Insulation of Refrigerant Tubing Taping the Tubes Finishing the
46. EEANING nsa abu s r dide a k 14 TROUBLESHOOTING ecu Td 16 OPEBRATNGOBANGE s l sa boe e seu de emet edt du bola Potente Seaside 16 WIRED REMOTE CONTROLLER oie E 16 2 OI 107 2 EG PRODUCT INFORMATION If you have problems or questions concerning your Air Conditioner you will need the following information Model and serial numbers are on the nameplate on the bottom of the cabinet Model No Serial No Date of purchase Dealer s address ALERT SYMBOLS The following symbols used in this manual alert you to potentially dangerous conditions to users service personnel or the appliance ANEN This symbol refers hazard practice which result severe personal injury or death This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage INSTALLATION LOCATION We recommend that this air conditioner be installed properly by qualified installation technicians in accordance with the Installation Instructions provided with the unit Before installation check that the voltage of the electric supply in your home or office is the same as the voltage shown on the nameplate ANEN e Do not install this air conditioner where there are fumes or flammable gases or in an extremely humid space such as a greenhouse Do not install the air condi
47. F PIPE and DRAIN marks on the ceiling panel corner with the correct positions on the unit Refrigerant tubing joint 2 Align the panel installation holes and the unit screw holes Fig 6 18 3 Tighten the supplied special screws at the 4 panel installation locations so that the panel is attached tightly to the unit e Check that the wiring connectors are not caught between the unit and the ceiling panel 4 Check that the panel is attached tightly to the ceiling Fig 6 19 e Atthis time make sure that there are no gaps Drainage check DRAIN mark between the unit and the ceiling panel or between M On TR the ceiling panel and the ceiling surface 4 locations Special screws e lfthere is a gap between the panel and the ceiling Fig 6 18 leave the ceiling panel attached and make fine adjustments to the installation height of the unit to xis D t all eliminate the gap with the ceiling R ui 75 Ceiling surface Ceiling panel CAUTION Fig 6 19 f the screws are not sufficiently tightened f a gap remains between the ceiling The height of the unit can be adjusted from the ceiling trouble such as that shown in the figure surface and the ceiling panel even panel corner hole with the ceiling panel attached to below may occur Be sure to tighten after the screws are tightened an extent that does not affect the unit levelness the screws securely adjust the height of the unit again
48. ID e heat sources exhaust fans etc Fig 3 e damp humid or uneven locations DO choose a place as cool as possible choose a place that is well ventilated install in a location where at least two sides are unob structed so that the flow of air at the intake port or exhaust port is not blocked and so that sufficient space is ensured for maintenance to be carried out without trouble In general the top also must be unob structed Figs 4a and 4b e provide a solid base level concrete pad concrete block 4 x 1 4 10 x 40 cm beams or equal a mini mum of 4 10 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased service life Figs 5a and 5b A solid base must not cover the hole of the bottom plate install cushion rubber under unit s feet to reduce vibra tion and noise Fig 5c e use lug bolts or equal to bolt down unit reducing vibra tion and noise install in a location where no antenna of a television or radio exists within 10 3 m Anchor bolts 4 pcs ZL ZEEE F L J S LA Air intak 222222225 Min 4 10 cm Ir Intake BEER BECAME rrr r Se eas ase BLZ 222222227222 Concrete EEE E EFF or equal N Mm NO yz j Hot air P i Outdoor unit CH1271 Air intake Min 2 5 Valve
49. INSTRUCTION MANUAL Wired Remote Controller MODE D EMPLOI T l commande Filaire Save These Instructions OR ON 4 N S e S ERE the Conserver ce mode d emploi CONTENTS Page PRODUCT INFORMATION 2 ALERT SYMBOLS ra R R R 2 INSTALLATI N c kaa n r R kaa 2 ELECTRICAL REQUIREMENTS se cat tees 2 SAFETY INSTRUC TONS neroian cream nent ere eee EET teen eee EE ee ee eee 2 REMOTE CONTROL UNIT M D 4 OPERATION WITH THE REMOTE CONTROL UNIT 6 1 Automatic Operation only for COOL DRY HEAT Model 6 2 Mantal 6 Adjusting the Fan Speed 7 Sak 7 5 Night Setback 7 SPECIALE REMARK r 7 SETHNG N 8 USING THE T HOUR OFF TIMER 5 lp l r ntes hia de 9 ADJUSTING THE AIRFLOW DIRECTION nennen nnn nnn nnne nnne nnn nnn nnn nnns 9 PRODUCT INFORMATION ELECTRICAL If you have problems or questions concerning your wired REQUIREMENTS
50. N Ventilate any enclosed areas when installing or testing the refrigeration system Escaped refrigerant gas on contact with fire or heat can produce dangerously toxic gas Confirm upon completing installation that no refrigerant gas is leaking If escaped gas comes in contact with a stove gas water heater electric room heater or other heat source it can produce dangerously toxic gas Table of Contents Page OPERAINGHBANGE 5 SPECIFICATIONS ARR 6 2 2 Major Component SPECIFICATIONS uaaiaaaaaaaaaaaaaaaaaaaaaaaaanaaaauaaaanaaaanaaaanaaannaaanunaannaaanaaaaanaaa 12 2 3 Other Component Specifications 16 DIMENSIONAL DATA eee eee ln v tk Sk Va aaa ere ee 17 REFRIGERANT FLOW DIAGRAM 4 1 Refrigerant Flow Diagram a uaaaaaaaaaaaaaaaaaaaaaaaaaananaunanaanunanaanuannannannnannananannaananannanaannnnnaanaa 20 PERFORMANCE DATA 93 515 1116 aU Cris a LM LL LUE D UE 22 28 11 26 5 3 Cooling Capactiy Low Ambient aaaaaaaaaaaaaaaaaasasa aanananatnannanannanannannnnanannnnnnnnnannnnnnnnannnnnaaa 28 ISAC CAD ACU M 30 ELECTRICAL DATA Orie Blecuical GiaraclerisH S 32 6 2 Electric Wiring Diagrams 34 MAINTENANCE 7 1 Address Setting
51. OE OE E11 Outdoor fan operating failure 1 Fan motor failure 2 Contact failure at connector 3 Outdoor PCboard failure Outdoor system communications failure 1 OLR operation 5 Mis wiring 2 Blown fuse 3 Power Relay failure 4 Outdoor PCboard failure Compressor failure Outdoor power supply open phase i mM Outdoor ae See detailed flowchart in this section 13 Freeze prevention operation activated 1 Indoor fan system failure 2 Shortage of refrigerant 3 Low temperature operation BLINKING 3 SEC INTERVAL FLOAT SWICTH FS IS ACTIVED 1 DRAIN PUMP FAILURE 2 FS FAILURE 3 CHOKED DRAIN HOSE flee x faele x ea x x x amp U gy 51 2 If the self diagnostics function fails to operate No indicators illuminate and the Check the indoor unit indoor fan does not rotate Check the power voltage Blown Is the fuse blown Normal Replace the circuit Replace the controller board or the fuse 9 3 Checking the Indoor and Outdoor Units 1 Checking the indoor unit NN Check tems unit operation Use the remote controller to operate the The rated voltage must be present between inter unit wirings 1 and 2 unit in TEST run mode To determine Connect a 5 k ohm resistor between inter unit wirings 2 and 3 When the whether the mode is currently in voltage at both ends is measured approximately 12 to 15V DC must TEST
52. OFF After turning on power to the air conditioner use the remote controller and O CD operation follow the steps below to execute self diagnostics Mw Z button Step 1 Press and hold the remote controller HIGH POWER button and 1 HIGH POWER un 2 TIMER button Then press and hold the ACL reset button button with a pointed object such as the tip of a pen After 5 seconds TEMP 1HR release ACL button first then release HIGH POWER and 1 HR VIA TIMER TIMER buttons oP 1 test run appears blinking in the remote AN J button controller clock display area FANSPEED Step 2 Next press the 1 HR TIMER button once to change the display from oP 1 to oP 3 self diagnostics The display continues to FLAP NIGHT SETBACK blink Step 3 Finally press the ON OFF button to engage self diagnostics mode The self diagnostics function utilizes the 3 indicator lamps on the main TIMER unit in combinations of ON lamps blinking lamps and OFF lamps to report the existence of sensor trouble or a protective operation The gt 2 lamps blink or remain ON for 5 seconds then turn OFF for 2 seconds CD c Self diagnostics is completed when the buzzer sounds 3 short beeps CANCEL A maximum of 3 self diagnostics reports are displayed for 5 seconds ae each beginning with the most recent report Following this display the Ou nae lamps turn OFF In order to view the self diagnostics results again press the
53. OTE Once changed you cannot restore the original address setting of the air conditioner 1 Switch on the power source 2 Break the address setting tab marked A on the second remote controller to change the address Fig 13 When the tab is removed the address is automatically set to B Fig 14 3 Press and hold the remote controller HIGH POWER button and 1 HR TIMER button Then press and hold the ACL reset button with a pointed object such as the tip of a pen After 5 seconds release ACL button first then release HIGH POWER and 1 HR TIMER buttons oP 1 test run appears blinking in the remote controller clock display area 4 Each time the 1 HR TIMER button is pressed the display changes as shown below Press this button 2 times to change the display to oP 7 address setting Fig 15 D um 34 Self diagnostic mode Test run mode a p 4 Address setting mode D mal 5 oP 7 has now been selected for address setting 6 Press the ON OFF operation button on the remote controller Fig 15 Check that the beep signal received sound is heard from the second indoor unit approximately 5 times The sound you hear is the signal that the remote controller address has been changed 7 Finally press the remote controller ACL reset button to cancel the blinking oP 7 display Fig 15 Changing of the second r
54. Operation together with the daily ON OFF repeat timer The 1 Hour OFF Timer setting is given priority over the DAILY ON OFF REPEAT setting TIPS FOR ENERGY SAVING Do not Block the air intake and outlet of the unit If they are obstructed the unit will not work well and may be damaged Let direct sunlight into the room Use sunshades blinds or curtains If the walls and ceiling of the room are warmed by the sun it will take longer to cool the room Do Always try to keep the air filter clean Refer to CARE AND CLEANING A clogged filter will impair the performance of the unit To prevent conditioned air from escaping keep windows doors and any other openings closed Ol 107 13 EG ADJUSTING THE AIRFLOW DIRECTION The vertical airflow can be adjusted by moving the flap with the remote control unit Do not move the flap with your hands Confirm that the remote control unit has been turned on Use the FLAP button to set either the sweep function or one of the six airflow direction settings FANSPEED C FLAP NIGHT SETBACK PSN _ A Sweep function The flap starts moving oN up and down to deliver air over the sweep range B Setting the airflow manually Referring to the above illustration use the COOL FLAP button to set the DRY airflow direction within the range used during the heating cooling or dehumidifying E operation C Auto flap function NY T
55. TU h 1 Above data does not take Freeze Prevention Protection during cooling operation into account For this reason the value may vary from the actual cooling characteristics 2 Above data represents the value when the operation frequency of a compressor is fixed 29 5 4 Heating Capacity Indoor Unit XHS1271 amp PNR XS1872 Outdoor Unit CH1271 Power Supply 115V Single Phase 60Hz lt Heating Capacity gt RATING CAPACITY 13 600 BTU h OUTDOOR ENT TEMP F C W B 60 15 6 0 17 8 TH 7 510 3 16 1 TH 7 760 8 13 3 TH 8 350 13 10 6 TH 8 980 18 7 8 TH 9 660 23 5 0 TH 10 390 28 2 2 TH 11 150 33 0 6 TH 11 930 38 3 3 TH 12 720 43 6 1 TH 13 560 48 8 9 TH 14 420 53 11 7 TH 15 290 58 14 4 TH 15 990 63 17 2 TH 16 000 65 18 3 TH 15 980 TH Total Heating Capacity BTU h NOTE 1 Rating conditions Indoor Unit Entering Air Temp 70 F 21 1 C D B Outdoor Ambient Temp 47 F 8 3 C D B 43 F 6 1 C W B AIR FLOW RATE 268 CFM INDOOR AMBIENT TEMP F C 65 70 75 80 18 3 21 1 23 9 26 7 7 540 7 560 7 580 7 590 7 790 7 810 7 830 7 840 8 380 8 410 8 420 8 440 9 000 9 030 9 050 9 060 9 690 9 720 9 730 9 750 10 420 10 440 10 460 10 470 11 180 11 200 11 210 11 220 11 960 11 980 12 000 12 000 12 750 12 770 12 780 12 550 13 580 13 600 13 300 12 670 14 440 14 120 13 400 12 760 15 020 14 200 13 470 12 810 15 080 14 240
56. Unit CH1271 Power Supply 115V Single Phase 60Hz lt Cooling Capacity gt RATING CAPACIT Y 11 900 BTU h AIR FLOW RATE 235 CFM INDOOR OUTDOOR ENT TEMP F AMBIENT TEMP F C W B D B 65 15 85 95 105 115 18 3 23 9 29 4 35 0 40 6 46 1 11 940 11 720 11 460 10 440 72 22 2 8 210 8 080 7 940 7 340 59 76 24 4 150 80 26 7 84 28 9 10 590 88 31 1 11 550 11 280 10 440 72 22 2 76 24 4 17 2 80 26 7 84 28 9 88 31 1 10 270 12 22 2 67 76 24 4 19 4 80 26 7 84 28 9 88 31 1 22 71 76 24 4 217 80 26 7 84 28 9 88 31 1 75 76 24 4 23 9 80 26 7 84 28 9 88 31 1 TC Total Cooling Capacity BTU h SHC Sensible Heat Capacity BTU h 1 Rating conditions Indoor Unit Entering Air Temp 80 F 26 7 C D B 67 F 19 4 C W B Outdoor Ambient Temp 95 F 35 C D B 2 Above data does not take Freeze Prevention Protection during cooling operation into account For this reason the value may vary from the actual cooling characteristics 3 Above data represents the value when the operation frequency of a compressor is fixed 26 Indoor Unit XHS1872 amp PNR XS1872 Outdoor Unit CH1872 Power Supply 230V Single Phase 60Hz lt Cooling Capacity gt RATING CAPACITY 17 500 BTU h AIR FLOW RATE 341 CFM INDOOR OUTDOOR ENT TEMP F AMBIENT TEMP F C W B D B 65 15 85 95 105 115 18
57. ad this Instruction Manual carefully before using this air conditioner If you still have any difficulties or problems consult your dealer for help e This air conditioner is designed to give you comfortable room conditions Use this only for its intended purpose as described in this Instruction Manual WARNING e Never use or store gasoline or other flammable vapor or liquid near the air A conditioner it is very dangerous e This air conditioner has no ventilator for intaking fresh air from outdoors You must open doors or windows frequently when you use gas or oil heating appliances in the same room which consume a lot of oxygen from the air Otherwise there is a risk of suffocation in an extreme case Do not turn the air conditioner on and off from the power mains switch Use the ON OFF operation button Do not stick anything into the air outlet of the outdoor unit This is dangerous News because the fan is rotating at high speed Do not let children play with the air conditioner Do not cool or heat the room too much if babies or invalids are present Ol 119 2 EG REMOTE CONTROL UNIT DISPLAY Displayed when indoor unit sensor is in use Displayed when operating NIGHT SETBACK mode Displayed when setting temperature G Displayed when temperature is shown Displayed when setting timer Symbols 1 Operation mode 3 Temperature setting 00560 Fi a AUTO only for COOL DRY HEAT A
58. adapter reverse flow prevention adapter 3 Solenoid valve installed adapter attached to a conventional vacuum pump Electronic scale for charging refrigerant Flare tool Bender Tools which can be com Torque wrench monly used for R22 R407C and R410A Cutter reamer Welding tool nitrogen gas cylinder J N e The above tools specifically for R410A must not be used for R22 and R407C Doing so will cause malfunction of the unit e For the above vacuum pump 1 2 and vacuum pump adapter 3 those for R22 type units can be used for R410A type However they must be used exclusively for R410A and never alternately with R22 and R407C e To prevent other refrigerants R22 R407C from being mistakenly charged to this unit shape and external diameter of the service port screw has been altered lt External diameter of service port gt R410A 5 16 R22 R407C 1 4 11 4 Tubing installation Procedures When the tubes are connected always apply HAB oil on the flare portions to improve the sealing of tubing The following is the HAB oil generally used Esso ZERICE S32 For details on tubing installation procedures refer to the installation manuals attached to the indoor unit and outdoor unit 63 11 5 In Case of Compressor Malfunction CAUTION e Should the compressor malfunction be sure to make the switch to a replacement compressor as quickly as possible e Use only the tools indicated exclusively for R410A
59. afety Device Type Internal Controller Over Current Protection Yes Run Capacitor Heat Exchanger Coil Fins par inch Face Area t External Finish Acrylic baked on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE Outdoor Unit CH1872 Control PCB CB CH1872 Control Circuit Fuse 250V 25A Compressor DC Twin Rotary Hermetic Compressor Model Nominal Output C 6RVN93HOM 1 050W Compressor Oil Amount Pints cc FV50S 0 74 350 Coil Resistance Ambient Temp 68 F 20 C Ohm Safety Device Y es Compressor Discharge Temp Control es es Operation cutoff control in abnormal ambient Temp vese Overload Relay Model CS 7L115 Operation Temp Open 239 F 115 C Close 203 F 95 C Run Capacitor Micro F md VAC Crankcase Heater MMX Propeller Q ty Dia inch mm 1 D16 17 32 D420 or B Coil Resistance RED WHT 77 5 Ambient Temp 68 F 20 C WHT BLU 77 5 BLU RED 77 5 Safety Device Type Internal Controller Over Current Protection Yes Run Capacitor Heat Exchanger Coil Fins per inch Face Area ft m External Finish Acrylic baked on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE 2 3 Other Component Specifications Indoor Unit XHS1271 amp PNR XS1872 XHS1872 amp PNR XS1872 Outdoor Unit CH1271 gt Resistance k ohm CH1872 Indoor air temp sensor
60. air conditioner Press the TIMER SELECT button three times to set the ON OFF combination timer You can check the timer ON OFF times after you have set them by pressing the SET button The present time PM 9 10 and are displayed Ol 119 8 EG 5 Cancellation of the time setting You can cancel the time settings by pressing the TIMER SELECT button The time settings cannot be canceled by pressing the ON OFF operation button or MODE selector button 6 Backup function Even if the main power supply circuit breaker is cut off the capacitor inside the remote control store the mode settings in the memory for 3 hours after the power is off The mode settings are reset if the main power supply is off for 3 hours or more USING THE 1 HOUR OFF TIMER 1 1 Hour OFF Timer 1HR This function causes the unit to operate for one hour and then stop regardless of whether the unit is on or off when this button is pressed The indicator in the display indicates that this function is operating Setting procedure Regardless of whether the unit is operating or stopped press the 1 HR TIMER button appears in the display Cancellation procedure Press the ON OFF operation button to turn the unit off wait for the unit to stop operating and then press the ON OFF operation button again The 1 Hour Timer function is now cancelled and the unit operates normally NOTE f while the 1 Hour T
61. amp PNR XS1872 Outdoor Unit CH1872 1 Voltage 230V Cooling lt 230V gt Indoor Unit Outdoor Unit Comos Fan Motor Fan Motor Compressor Performance at 230V Single phase 60Hz Rating conditions Running amp Power input 1 838 1 860 Rating conditions Indoor air temperature 80 F 26 7 C D B 67 F 19 4 C W B Outdoor air temperature 95 F 35 Indoor Unit Outdoor Unit C acini Fan Motor Fan Motor Compressor Performance at 230V Single phase 60Hz Rating conditions Running amp 10 31 Power input 2 313 2 340 Rating conditions Indoor air temperature 70 F 21 1 C D B Outdoor air temperature 47 F 8 3 C D B 43 F 6 1 C W B Heating 2 Voltage 208V Cooling lt 208V gt Indoor Unit Outdoor Unit Cormolere Unii Fan Motor Compressor i Performance at 208V Single phase 60Hz Rating conditions Running amp Power input 1 838 1 860 Rating conditions Indoor air temperature 80 F 26 7 C D B 67 F 19 4 C W B Outdoor air temperature 95 F 35 D B Indoor Unit Outdoor Unit Conoce Uni Fan Motor Compressor Heating Performance at 208V Single phase 60Hz Rating conditions Running amp Power input 2 313 2 340 Rating conditions Indoor air temperature 70 F 21 1 C Outdoor air temperature 47 F 8 3 C D B 43 F 6 1 C W B 33 iagrams D iring 6 2 Electric W XHS1271 amp PNR XS1872 XHS1872 amp PNR
62. be seen by opening the air intake grille IMPORTANT After the test run is completed be sure to press the ACL Reset button to return to normal mode The air conditioner will not operate correctly if this is not done ON OFF NIGHT SETBACK button 1 HR TIMER button ACL GSENSOR CL TJ ACL Reset SENSOR button button Fig 9 _ button OG e gt OPERATION lamp TIMER lamp Que POWER lamp REMOTE CONTROL receiver c Fig 11 SANYO Commercial Solutions A Division of SANYO North America Corporation 1300 Michael Drive Suite A Wood Dale IL 60191 U S A Sanyo Canada Inc 1 300 Applewood Crescent Concord Ontario L4K 5C7 CANADA Oct 2008 T
63. cator Fig 7 Fig 8 Indicator 7P IND and 4P RC wiring connector Wire harness Remote S controller 5P FLAP wiring connector Clamping strap Fig 8 b Remove the terminal cover screws then remove the cover At this time take care not to drop the cover Fig 8 Pull in the wire harness from the remote controller as shown in Fig 8 b e Remove the putty before wiring After wiring make sure to restore the putty 7 Insert the wire harness 4P terminal into the control box PCB connector RC Fig 8 a 8 Install the terminal cover Then install the ceiling panel Refer to 3 6 How to Install the Ceiling Panel in the Installation Instructions supplied with the indoor unit 9 Insert only the 7P IND terminal of the 7P IND and 4P RC wiring connector into the connector IND on the control box PCB Store the 4P terminal inside the control box Fig 8 a 10 Next insert the 5P terminal of the 5P FLAP wiring connector into the connector FLAP on the control box PCB Fig 8 a 11 When the connections are completed fasten the wire harness and each wiring connector with the clamps 12 Install the power box cover and control box cover 13 Install the air intake grille Refer to 3 6 How to Install the Ceiling Panel in the Installation Instructions supplied with the indoor unit B How to Test Run the Air Conditioner After turning on the power of the air conditioner
64. ce Ambient Temp 68 F 20 C Type Thermal Fuse Over Current Protection yy Over Heat Protection yg Run Capacitor OOS vac Drain Pump Model Q ty PLD 12230ST 1 1 Rating Voltage Hz n to 240V 60Hz Input 10 BB Coil Resistance 333 10 Ambient Temp 68 F 20 C Safty Device Type Thermal Fuse Open F 293 145 Heat Exchanger Coil Face Area f m DATA SUBJECT TO CHANGE WITHOUT NOTICE Indoor Unit Panel PNR XS1872 Flap Motor Stepping Motor Model Q ty MP24ZN 12V 2 DC 12V Coil Resistance Ohm Each Pair of Terminal 380 7 Ambient Temp 77 F 25 C DATA SUBJECT TO CHANGE WITHOUT NOTICE 13 2 2 2 Outdoor Unit Outdoor Unit CH1271 Control PCB CB CH1271 Control Circuit Fuse 125V 25A Compressor DC Rotary Hermetic Compressor Model Nominal Output G4CO90LU1ER 900W Compressor Oil Amount Pints cc FV50S 0 68 320 Coil Resistance Ambient Temp 68 F 20 C Ohm Safety Device Y es Compressor Discharge Temp Control es es Operation cut off control in abnormal ambient Temp Yes Overload Relay Model CS 7L115 Operation Temp Open 239 F 115 C Close 203 F 95 C Run Capacitor Micro Ff VAC Crankcase Heater 115V 20W Propeller Q ty Dia inch mm 1 D15 3 4 D400 r B Coil Resistance RED WHT 77 5 Ambient Temp 68 F 20 C WHT BLU 77 5 BLU RED 77 5 S
65. e Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit both the wide and narrow tubes of this air conditioner become cold To OO Se Wide tube 7 _ Accumulator n Cooling cycle Defrosting cycle Eit Heating cycle Thickness Min 5 16 8 mm M Insulati prevent heat loss and wet floors due to dripping of condensation both tubes must be well insulated with a Thickness proper insulation material The thickness of the insulation Min 5 16 8 mm should be a min 5 16 8 mm After a tube has been insulated never try to bend it into a narrow CAUTION curve because it cause the tube to break or crack Wide tube 21 Narrow tube 5 PERFORMANCE DATA 5 1 Temperature Charts Indoor Unit XHS1271 amp PNR XS1872 Outdoor Unit CH1271 H Cooling Characteristics RH 46 Indoor fan speed High fan 60Hz 115V 1 Low pressure performance chart psig MPaG Low pressure at wide tube service valve Outdoor inlet air D B r F C 2 Operating current performance chart Operating current A 86 95 30 35 77 25 Outdoor inlet air D B temp F C 3 Indoor discharge air performance chart KASTI Indoor discharge air temperature F C 95 35 Outdoor inlet air D B temp F C NOTE e Check each performance value in test run mode Electrical p
66. e narrow tube connection For wide narrow tube flare nut connection For flare drain insulating connection For drain tube Drain hose insulation S T10 Flare insulation gt y 6 T5 Insulation tape 2 2 3 32 T2 Vinyl tie connection Remote control unit Remote control unit holder AAA alkaline battery Full scale installation diagram 1 Printed on container box 1 3 Optional Copper Tubing Kit For full scale installation _ diagram O For unit amp PVC 5 1 2 L140 tube connection For drain hose d a ef 2 5 32 5 Om MH Gram Cm Error Truss head screw 5x 10mm Drain hose Tapping screw Hex wrench Packed in the outdoor unit Cushion rubber Truss head screw Packed in the ceiling panel Special screw Om 5 32 x 15 32 5 x40mm a e 4x12mm 3 16 x 1 9 16 e Use M10 or 3 8 for suspension bolts e Suspension bolts and nuts locally purchased Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing fittings and insulation Consult your nearest sales outlet or air conditioning workshop 1 4 Type of Copper Tube and Insulation Material If you wish to purchase these materials separately from a local source you will need 1 Deoxidized annealed copper tube for refrigerant tubing as detailed in Table 2 Cut each tube to the appropriate lengths 1 to 1 4
67. e is set to the room temperature minus 4 F during the cooling operation and to the room temperature plus 4 F during the heating operation and the fan speed and flap are set to Auto 14 CARE AND CLEANING Cleaning and maintenance operations must be carried out by specially trained personnel While working in high places slipping or falling may result in serious injury For safety be sure to turn the air conditioner off and also to disconnect the power before cleaning Do not pour water on the indoor unit to clean it This will damage the internal components and cause an electric shock hazard Ceiling panel Indoor Unit Clean the ceiling panel of the indoor unit with a vacuum cleaner brush or wipe it with a clean soft cloth If itis stained use a clean cloth moistened with a mild liquid detergent When cleaning it be careful not to force the flaps out of place e Never use solvents or harsh chemicals N caution when cleaning the indoor unit Do not wipe the plastic casing using very hot water Some metal edges and the fins are sharp and may cause injury if handled improperly be especially careful when you clean these parts The internal coil and other components of the outdoor unit must be cleaned every year Consult your dealer or service center Cleaning the flaps The air outlet flap can be removed and washed with water Be sure to always stop operation before removing the flap e Af
68. ed values is not normal Outdoor unit controller trouble Replace the controller Reference DC motor connector pin arrangement Pin 1 Vs white Pin 2 Not used Pin 3 Not used Pin 4 Gnd black Pin 5 Vcc red Pin 6 FG blue Pin 7 Vsp yellow Trouble symptom 3 Motor rotates for some time several seconds but then quickly stops when the outdoor unit operates There is trouble in the system that provides feedback of motor rotation speed from the motor to the outdoor unit controller Trouble symptom 4 Fan motor rotation speed does not change during outdoor unit operation Trouble symptom 5 Fan motor rotation speed varies excessively during outdoor unit operation Remedy for symptom 3 to 5 It is not possible to identify whether the trouble is outdoor unit controller trouble or motor trouble Therefore first replace the outdoor unit controller then if necessary replace the DC motor 57 9 5 Noise Malfunction and Electromagnetic Interference An inverter A C operates using pulse signal control and high frequencies Therefore it is susceptible to the effects of external noise and is likely to cause electromagnetic interference with nearby wireless devices A noise filter is installed for ordinary use preventing these problems However depending on the installation conditions these effects may still occur Please pay attention to the points listed below 1 Noise malfunction This refers to the applicatio
69. efrigerant Therefore do not add new refrigerant Instead recover the remaining refrigerant with the refrigerant recovery unit Then after evacuation totally recharge the specified amount of refrigerant with the new refrigerant at its normal mixed composition state in liquid phase When refrigerant R410A is used the composition will differ depending on whether it is in gaseous or liquid phase and the basic performance of the air conditioner will be degraded if it is charged while the refrigerant is in gaseous state Thus always charge the refrigerant while it is in liquid phase Ether type oil is used for compressor oil for R410A type units which is different from the mineral oil used for R22 Thus more attention to moisture prevention and faster replacement work compared with conventional models are required 61 11 2 Checklist before Servicing Use a clutch type flare tool for R410A or the conventional flare tool Note that sizes of the resultant flares differ between these two tools Where a conventional flare tool is used make sure to observe A Specification amount of extrusion by using the flare spacer Specification A Diameter of tube D Flare tool for R410A Conventional flare tool for R22 Dia 1 4 6 35 mm Dia 3 8 9 52 mm 0 to 0 0196 0 0472 Dia 1 2 12 7 mm 0 to 0 5 mm 1 2 mm Dia 5 8 15 88 mm Size of flare Flare tool for R410A Conventional flare tool R22 e Tubing precauti
70. emote controller address is now completed 37 ACL button Fig 14 MP D F ga WIS OFS Ae Pw Bx Px 00061 001 HIGH ON I OFF O p ON OFF Yl operation Z button HIGH POWER 15 BO AMA VT LJ Tver LL button FANSPEED FLAP NIGHT SETBACK ON TIMER OFF O A v Cc CLOCK C ACL SENSOR 12H4 24H Reset iar 80 button A ee Cy Fig 15 7 2 Disconnecting and Connecting Positive Connector for Outdoor Unit One of the two types of connectors illustrated at left is used Their basic structure is the same for each How to Disconnect Hold the resin connector cover and pull the connector off You cannot disconnect the connector by pulling the wire since it is locked inside Always hold the cover to disconnect See illustration at left For the connector without the resin cover push the lock in the direction of 2 while pulling it off Pull the cover upward How to Connect In order to connect hold the resin cover of the connector and push it in Confirm the click sound for the inside lock When the cover is pulled upward the lock is released with the sequence of 1 and 2 38 7 3 Disassembly Procedure To avoid electrical shock hazard be sure to disconnect power before attempting to disassemble the unit When a footstool etc is used for disassembling the indoor unit be ca
71. en run the vacuum pump The operation time for the vacu um pump varies with tubing length and the capacity of the pump The following table shows the amount of time for evacuation Table 6 Required time for evacuation when 26 4 gal h 100 liter h vacuum pump is used If tubing length is less than 33 ft 10 m If tubing length is more than 33 ft 10 m 10 min or more 15 min or more With the vacuum pump still running close the Lo knob of the manifold valve Then stop the vacuum pump With the accessory hex wrench turn the valve stem on the narrow tube service valve counter clockwise by 90 degrees 1 4 turn for 10 seconds and then turn the stem clockwise to close it again Fig 28 Be sure to completely insert the hex soapy water Bubbles indicate a leak Tighten the joint more when leaks then check if there is no leak Be sure to wipe off the soap with a clean cloth counter clockwise to fully open the valve fully open the valve wrench before attempting to turn the valve Leak test all joints at the tubing both indoor and outdoors with With the hex wrench turn the wide tube service valve stem To prevent other refrigerants from being mistakenly charged to units which use R410A the size of the charge port on the service valve is different from the one for other refrigerant types For servicing such as recharging the specified charging hose manifold and vacuum pump adapter with reve
72. equire help for a special problem contact our sales service outlet or your certified dealer for additional instructions In Case of Improper Installation The manufacturer shall in no way be responsible for improper installation or maintenance service including failure to follow the instructions in this document SPECIAL PRECAUTIONS when wiring ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH ONLY A QUALIFIED EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked Highly dangerous electrical voltages are used in this system Carefully refer to the wiring diagram and these instructions when wiring Improper connections and inadequate grounding can cause accidental injury or death Ground the unit following local electrical codes Connect all wiring tightly Loose wiring may cause overheating at connection points and a possible fire hazard Install a protective leakage breaker depending on the installation location especially a damp or humid location If a leakage breaker is not installed electric shock can occur When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Cei
73. er in lukewarm soapy water rinse it in clean water and dry it 5 Insert the filter correctly again inside the grille close the grille letting the latches slide towards the outside and fix again the latch Ol 107 15 EG 15 TROUBLESHOOTING OPERATING RANGE If your air conditioner does not work properly first check the following The air conditioner is operable within the temperature ranges as points before requesting service If it still does not work properly listed below contact your dealer or service center Temperature Indoor air Outdoor air temperature temperature COOLING Max 95 F DB 115 F DB 71 F WB Air conditioner does 1 Power failure Restore power not run at all MA 2 Leakage circuit Contact service breaker tripped center Min 67 F DB F DB 57 F WB HEATING Max 80 F DB 75 F 67 F WB 65 F WB Min DB WB F DB 3 Line voltage is too Consult your low electrician or dealer 4 Batteries in remote 4 Replace batteries control unit have run down WIRED REMOTE CONTROLLER OPERATION lamp Trouble in system Contact service blinks and air center A separately sold wired remote controller STK RCS conditioner does not 7 TWSU used with this air conditioner is also available If operate you wish to use the wired remote control function you will Compressor runs but Obstruction in front of Remove obstruction need to purchase the op
74. er proof tape Flare fool to prevent dust or water from getting into the tubes Fig 18 before they are used inside surface is glossy and smooth edge is smooth tapered sides are of uniform length 5 3 Caution before Connecting Tubes Tightly b Be sure to apply refrigerant lubricant to the match ing surfaces of the flare and union before connect ing them together This is effective for reducing gas leaks Fig 19 DJ Apply refrigerant lubricant here and here C For proper connection align the union tube and Fig 19 flare tube straight with each other then screw in the flare nut lightly at first to obtain smooth match _ Fig 20 Union Flare nut Fig 20 15 5 4 Connecting Tubing between Indoor and Outdoor Units a Tightly connect the indoor side refrigerant tubing exten ded from the wall with the outdoor side tubing Fig 21 b To fasten the flare nuts apply specified torque as Table 5 Tube Dia Tightening Torque Approx 120 160 Ibs in 140 180 kgf cm Approx 300 360 Ibs in 340 420 kgf cm Approx 430 540 Ibs in 490 610 kgf cm Approx 590 710 Ibs in 680 820 kgf cm 5 5 Insulation of Refrigerant Tubing IMPORTANT To prevent heat loss and wet floors due to dripping of con densation both tubes must be well insulated with a proper insulation material The thickness of the insulation should be a minimum 5 16 8
75. eral minutes This interval will vary slightly depending upon the outdoor temperature and the way in which frost forms Cold draft prevention For several minutes after the start of heating operation the indoor fan runs at a lower speed until the indoor heat exchanger coil has warmed up sufficiently However the fan may remain stopped when the room temperature is low This is because the COLD DRAFT PREVENTION SYSTEM is in operation Cooling operation Sometimes the indoor unit may not get to the set fan speed such as LOW under cool operation at very low outdoor temperatures due to the indoor unit being protected from ice or frost Power failure during operation n the event of power failure the unit will stop When the power is resumed the unit will restart automatically within five minutes by the remote control unit Clicking Sound Clicking sound is heard from the air conditioner n heating or cooling operation any plastic parts may expand or shrink due to a sudden temperature change In this event a clicking sound may occur This is normal and the sound will soon disappear Remote Control Unit The remote control unit sends the setting condition to the air conditioner regularly at five minute intervals OI 107 11 EG SETTING THE TIMER FAN SPEED MODE NIGHT SETBACK FLAP SENSOR O ADR 12H49 24H O ac CO In the descriptions below the following
76. eration For cooling operation For fan only operation STEP 1 STEP 2 To start the air conditioner press the ON OFF operation button STEP 3 Press the TEMP setting buttons to change the temperature setting to the desired temperature Adjustable temperature range 86 F max 60 F min STEP 4 Set the FAN SPEED selector button to the setting you want STEP 5 Press the FLAP button and set the airflow direction as desired Refer to ADJUSTING THE AIRFLOW DIRECTION on page 9 To stop the air conditioner press the ON OFF operation button again Choose the best position in the room for the remote control unit which also acts as the sensor for room comfort and transmits the operating instructions Once you ve found this best position always keep the remote control unit there This appliance has a built in 5 minute time delay circuit to ensure reliable operation When the operation button is pressed the compressor will start running within three minutes In the event of power failure the unit will stop The display on the remote control unit shows the setting temperature and not the room temperature Ol 119 6 EG 3 Adjusting the Fan Speed A In Cooling and DRY Mode amp and A Automatic fan speed When the night setback mode is selected the air conditioner Simply set the FAN SPEED selector button to the automatically raises the temperature setting 2 F when 30 minutes positi
77. erformance values represent a combined indoor outdoor value 22 Indoor Unit XHS1271 amp PNR XS1872 Outdoor Unit CH1271 Heating Characteristics RH 85 Indoor fan speed High fan 60Hz 115V 1 High pressure performance chart psig MPaG TT o T High pressure at wide tube service valv 1 523 32 41 50 59 68 77 5 0 5 10 15 20 25 Outdoor inlet air D B temp F C 2 Operating current performance chart Operating current A 50 59 68 7 10 15 20 25 Outdoor inlet air D B temp F C 3 Indoor discharge air performance chart 13 Indoor discharge air temperature F C 20 23 32 41 50 59 68 77 5 0 5 10 15 20 25 Outdoor inlet air D B temp F C NOTE Check each performance value in test run mode Electrical performance values represent a combined indoor outdoor value Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in heating mode Refer to 8 2 Overload prevention during heating 23 Indoor Unit XHS1872 amp PNR XS1872 Outdoor Unit CH1872 H Cooling Characteristics RH 46 Indoor fan speed High fan 60Hz 230V 1 Low pressure performance chart Low pressure at wide tube service valve psig MPaG 86 95 1 25 30 35 40 Outdoor inlet air D B temp F C 2 Operating current performance chart Operating current A 77 86 95 10
78. es regardless of the desired temperature The fan speed is 1 step above High e HIGH POWER Mode cannot be used when the operation mode is Automatic Operation e When set to High fan speed during heating operation the fan runs at High fan speed even though the 7 mark is displayed Depending on the operating conditions the fan speed may be increased by a small amount only SPECIAL REMARKS How it works Once the room temperature reaches the level that was set the unit s operation frequency is changed automatically During DRY operation the fan speed automatically runs at lower speed for providing a comfortable breeze DRY operation is not possible if the indoor temperature is 59 F or less Heating Operation oye Heating performance Because this air conditioner heats a room by drawing in the heat of the outside air heat pump system the heating efficiency will fall off when the outdoor temperature is very low If sufficient heat cannot be obtained with this air conditioner use another heating appliance together with it Defrosting When the outdoor temperature is low frost or ice may form on the heat exchanger coil reducing heating performance When this happens a microcomputer defrosting system operates At the same time the fan on the indoor unit stops and the OPERATION lamp lights red and orange alternately until defrosting is completed Heating operation restarts after sev
79. ess the NIGHT SETBACK button SPECIAL REMARKS n the event of power failure the unit will stop When the power is resumed within 3 hours the unit will restart automatically within five minutes by the remote control unit Remote Control Unit The remote control unit sends the setting condition to the air conditioner regularly at five minute intervals Remote Control Unit Display f the display malfunctions press the ACL button This resets the remote control unit back to the initial settings Make the settings again Night Setback Mode is used for saving energy Press the NIGHT SETBACK button while operation The mark appears in the display To release the night setback function press the NIGHT SETBACK button again Ol 119 7 EG 7 SETTING THE TIMER HO 86 1 How to set the present time Example To set to 9 10 pm Kl 491 6 M mem 1 Press the SET button three The time indication alone times flashes 2 Press the HH button until PM 9 is displayed e Press the MM button until 10 is displayed The display will flash for 10 sec and automatically stop flashing except for the symbol 2 How to set the OFF time Example To stop the air conditioner at 11 30 pm Ft OPM Z4 D 1 Press the SET button twice The timer indication alone flashes and the previous set time is only displayed Press the HH button until
80. ettings as desired NOTE Check that the circuit breaker on the power panel is turned on Press the MODE selector button and select the desired mode Once mode is selected and the unit is preset by For heating operation _ following the steps below you can have the air For dehumiditying operation conditioner automatically bring the room to the desired For cooling operation temperature simply by pressing the ON OFF operation For fan only operation button STEP 2 To start the air conditioner press the ON OFF operation button STEP Press the TEMP setting buttons to change the temperature setting to the desired temperature Adjustable temperature range 30 C max or 86 F max 16 C min 60 F min NOTE change the temperature setting press the _ STEP 4 Set the FAN SPEED selector button to the temperature setting buttons and change the setting to setting you want STEP 1 Press the MODE selector button to STEP 2 Press the ON OFF operation button To stop the air conditioner press the ON OFF operation button again STEP 5 Press the FLAP button and set the airflow direction as desired Refer to ADJUSTING THE AIRFLOW DIRECTION on page 13 To stop the air conditioner press the ON OFF operation button again NOTE Choose the best position in the room for the remote control unit which also acts as the sensor for room comfort and transmits the operati
81. f the TEMP buttons is pressed MODE selector button Use this button to select AUTO HEAT DRY COOL or FAN mode AUTO When this setting is selected the air conditioner calculates the difference between the thermostat setting and the room temperature and automatically switches to the COOL or HEAT mode as appropriate HEAT The air conditioner makes the room warmer DRY The air conditioner reduces the humidity in the room COOL amp The air conditioner makes the room cooler FAN The air conditioner works only as a circulation fan HIGH POWER ON orc O NIGHT SETBACK button For details see 5 Night Setback Mode When you press this button in the HEAT DRY or COOL mode the mark appears in the display and the remote control unit will automatically adjust the set temperature to save energy CLOCK button Time display selector button This switches the time display between 24 hour time and 12 hour time ACL button ALL CLEAR Puts the remote control unit into pre operation status Always press this button after replacing the batteries Cover closed The illustration above pictures the remote control unit after the cover has been opened The remote control unit sends the temperature signal to the air conditioner regularly at five minute intervals If the signal from the remote control unit stops for more than 15 minutes due to the loss of the remote control unit or other tr
82. flap to the optimum position contains several features to facilitate automatic operation during heating cooling and drying operation OJCA OISDIGYGR TOF Sosy e Automatic Switching between Cooling and Heating Simple One touch Wireless Remote Control This unit automatically switches between cooling operation The remote control unit has several features to facilitate and heating operation according to the difference between automatic operation the room temperature and the temperature setting e 24 Hour ON or OFF Timer e Hot Start Heating System This timer can be set to automatically turn the unit on or off Right from the start the air is warm and comfortable This at any time within a 24 hour period system prevents any cold blasts at the beginning while the e 1 Hour OFF Timer heat pump is warming up or even defrosting This timer can be set to automatically turn off the unit at e Automatic Restart Function for Power Failure any time after one hour Even when power failure occurs preset programmed Night Setback operation can be reactivated once power resumes This function saves energy by controlling operation to e High Power Operation provide a quieter operating sound than normal If not in Auto Operation the unit operates at maximum Automatic and 3 step Fan Speed output for 30 minutes regardless of the desired temperature Auto High Medium L Run Lu Edd The fan speed is 1 step above High Air Sweep Con
83. ft inside the unit being serviced Ventilate any enclosed areas when installing or testing the refrigeration system Escaped refrigerant gas on contact with fire or heat can produce dangerously toxic gas Confirm upon completing installation that no refrigerant gas is leaking If escaped gas comes in contact with a stove gas water heater electric room heater or other heat source it can produce dangerously toxic gas 1 General This booklet briefly outlines where and how to install the air conditioning system Please read over the entire set of instruc tions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning 1 1 Tools Required for Installation not supplied 1 Standard screwdriver 6 Sabre saw or key hole saw 11 Tube cutter 2 Phillips head screwdriver 7 Hacksaw 12 Tube flaring tool 3 Knife or wire stripper 8 Core bits 13 Torque wrench 4 Tape measure 9 Hammer 14 Adjustable wrench 5 Carpenter s level 10 Drill 15 Reamer for deburring 1 2 Accessories Supplied with Unit 1 Figue Q y Remarks S nm For temporarily suspending indoor unit from ceiling For wid
84. he flap is set to the VV recommended position NOTE The flap automatically closes when the unit is off During the heating operation the fan speed will be very low and the flap will be in the horizontal position position until the air being blown out of the unit begins to warm Once the air warms up the flap position and fan speed change to the settings specified with the remote control N caution e Use the FLAP button on the remote control to adjust the position of the flap If you move the flap by hand the flap position according to the remote control and the actual flap position may no longer match If this should happen shut off the unit wait for the flap to close and then turn on the unit again the flap position will now be normal again Do not have the flap pointed down during cooling operation Condensation may begin to form around the air vent and drip down 13 OPERATION WITHOUT THE REMOTE CONTROL UNIT OPERATION button OPERATION lamp If you have lost the remote control unit or it has trouble follow the steps below When the air conditioner is not running Each time the OPERATION button is pressed the type of operation conducted is indicated by the changing color of the OPERATION lamp Press the button and select the lamp color that suits your preference for operation Cooling operation gt green Heating Stop operation red lamp off The temperatur
85. he room can be uniformly cooled select a location that will hold the weight of the unit select a location where tubing and drain hose have the shortest run to the outside allow room for operation and maintenance as well as unre stricted air flow around the unit Fig 1 install the unit within the maximum elevation difference H above or below the outdoor unit and within a total tubing length L from the outdoor unit as detailed in Table 3 and Fig 2 install the indoor unit more than 3 3 1 m away from any antenna or power lines or connecting wires used for television radio telephone security system or intercom Electrical noise from any of these sources may affect operation Tubing length L Outdoor unit Elevation difference H Fig 2 Air delivery will be degraded if the distance from the floor to the ceiling is greater than 10 ft 3 m Table 3 Max Allowable Tubing Limit of Tubing Limit of Elevation Required Amount of Model Length at Shipment Length L Difference H Additional Refrigerant ft ft ft 0z ft XHS1271 25 65 23 0 16 XHS1872 25 98 50 0 27 f total tubing length becomes 25 to 65 ft Max or 25 to 98 ft Max charge additional refrigerant R410A by 0 16 or 0 27 oz ft No additional charge of compressor oil is necessary For more detailed charging information refer to the Technical amp Service Manual 4 2 2 Outdoor Unit AVO
86. hose supplied 3 On the unit drain side grasp the hose band with pliers and insert the drain hose all the way to the base e f other commercially available hose bands are used the Hose band drain hose may become pinched or wrinkled and there is _ 5 1 2 140mm danger of water leakage Therefore be sure to use the Unit supplied hose bands When sliding the hose bands be Fig 6 5 careful to avoid scratching the drain hose e Do not use adhesive when connecting the supplied drain m bang hose to the drain port either on the main unit or the PVC CAUTION 9 Attach So that the nose pipe pets fastener is on the side of the drain port Reasons a It may cause water to leak from the connec e Attach the hose bands so that tion Since the connection is slippery just hi Iv 3 16 after the adhesive has been applied the 5 mmi c PM di m pipe easily slips off the end of the supplied drain b The pipe cannot be removed when mainte hose nance is needed 4 Wrap the hose with the supplied drain hose insulation hir bleeder prohibited and use the 4 twist ties so that the hose is insulated with no gaps e Do not bend the supplied drain hose 90 or more The hose may slip off NOTE Fig 6 6 Make sure the drain pipe has a downward gradient 1 100 or more and that there are no water traps CAUTION Do not install an air bleeder as this may cause water to spray from the dra
87. iagnostic procedure Disconnect the motor connectors and measure the voltage at the DC motor connectors on the indoor unit controller 3 locations Measurement location XHS1271 51872 1 Vm Gnd Between 1 DC 130V to 195V DC 280V to 340V 2 Vcc Gnd Between pin 4 and pin 3 DC 15V 10 3 Vs Gnd Between pin 5 and pin 3 Fluctuation between DC 1 8V to 5 7V Diagnostic results All of the above measured values are normal Fan motor trouble Replace the motor Any one of the above measured values is not normal Indoor unit controller trouble Replace the controller Reference DC motor connector pin arrangement Pin 1 Vm red Pin 2 Not used Pin 3 Gnd black Pin 4 Vcc white Pin 5 Vs yellow Pin 6 PG blue Trouble symptom 3 Motor rotates for some time several seconds but then quickly stops when the indoor unit operates There is trouble in the system that provides feedback of motor rotation speed from the motor to the indoor unit controller Trouble symptom 4 Fan motor rotation speed does not change during indoor unit operation Trouble symptom 5 Fan motor rotation speed varies excessively during indoor unit operation Remedy for symptom 3 to 5 It is not possible to identify whether the trouble is indoor unit controller trouble or motor trouble Therefore first replace the indoor unit controller then if necessary replace the DC motor 56 9 4 2 Outdoor Fan Moto
88. ig 6 11 J N Never place the panel face down Neither hang it ver Fig 6 12 Fig 6 13 tically nor place it on top of a projecting object Plac ing it face down will damage the surface Air intake grille e Do not touch the flap or apply force to it This may cause flap malfunction Fig 6 12 Ceiling side 3 6 1 Before Installing the Ceiling Panel 1 Remove the air intake grille and air filter from the ceiling panel a Press on and slide the two latches of the air intake grille Fig 6 14 Air intake grille hinge with your thumb in the direction shown by the arrow 1 to open the grille Figs 6 13 and 6 14 b With the air intake grille opened remove the grille hinge from the ceiling panel by sliding it in the direction shown by the arrow Fig 6 15 2 Removing the corner cover and indicator cover a While lightly pressing the cen ter of the corner cover pull up the tab for the screw hole Use the same procedure to remove the indicator cover Fig 6 16 D Press OR lt 2 Pull up Indicator cover Fig 6 16 3 6 2 Installing the Ceiling Panel Temporary latches 1 Hang the temporary latches on the inside of the ceil ing panel to the receptacle on the unit to temporarily Temporary ous latch attach the ceiling panel in place Fig 6 17 e The ceiling panel must be installed in the correct direction relative to the unit Align the RE
89. ill not be HT received e lf the connectors are not connected the auto flap will not operate Be sure to connect them securely SS 7PIND and 4P RC wiring connector Indicator Control box Pass the wiring connectors through the clamps to fasten them in place as shown in the figure Fig 6 21 3 6 4 How to Attach the Corner Cover and Air Intake Grille A Attaching the corner cover 1 Check that the safety strap from the corner cover is fas tened to the ceiling panel pin as shown in the figure Fig 6 23 2 Use the supplied screws to attach the corner cover to the ceiling panel B Attaching the air intake grille Place the corner cover so that the 3 tabs e lo install the air intake grille follow the steps for 3 6 1 fit into the holes in the ceiling panel Before Installing the Ceiling Panel in the reverse order TnI SEMIN PICO ety eevee By rotating the air intake grille it is possible to attach the Fig 6 23 grille onto the ceiling panel Hore for from any of 4 directions panel hook Fig 6 25 The grille can be installed with these hinges facing in any of 4 directions Can be installed rotated 90 When attaching the air intake grille be careful that the flap and the indicator wiring do not become caught Be sure to attach the safety cord that prevents the air intake grille from dropping off to the Hook that prevents the grille from ceiling panel u
90. imer function is operating the 1HR TIMER button is pressed once to cancel the function and then again the unit continues to operate for one hour from that point in time and then stops e t is not possible to use the OFF Timer and 1 Hour OFF Timer together Whichever function is set last takes precedence If the 1 HR TIMER button is pressed while the TIMER OFF function operates the OFF Timer is cancelled and the unit will stop operating one hour later 2 Operation together with the daily ON OFF repeat timer The 1 Hour OFF Timer setting is given priority over the DAILY ON OFF REPEAT setting Ol 119 9 EG ADJUSTING THE AIRFLOW DIRECTION The vertical airflow can be adjusted by moving the flap with the remote control unit Do not move the flap with your hands Confirm that the remote control unit has been turned on Use the FLAP button to set either the sweep function or one of the six airflow direction settings A Sweep function The flap starts moving up and down to deliver air over the sweep range dA B Setting the airflow manually g Referring to the above illustration use the COOL FLAP button to setthe DRY airflow direction within the range used during the heating cooling or dehumidifying in operation The flap automatically closes when the unit is off During the heating operation the fan speed will be very low and the flap will be in the horizontal position position until the air bei
91. in pipe outlet Fig 6 6 1 ft 300mm or less e In cases where it is necessary to raise the height of the drain piping the drain piping can be raised to a maximum Rl 2 78 f 850mn or less height of 2 78 ft 850 mm above the bottom surface of 0 45 P gt the ceiling Under no conditions attempt to raise it higher than 2 78 ft 850 mm above the bottom surface of the Length of supplied drain hose 5 1 2 140mm ceiling Doing so will result in water leakage Fig 6 7 e Do not use natural drainage Fig 6 7 e Do not install the pipe with an upward gradient from the connection port This will cause the drain water to flow X Uphill slope backward and leak when the unit is not operating Fig 6 8 e Do not apply force to the piping on the unit side when connecting the drain pipe The pipe should not be Fig 6 8 allowed to hang unsupported from its connection to the unit Fasten the pipe to a wall frame or other support as s close to the unit as possible Fig 6 9 e Provide insulation for any pipes that are run indoors Fig 6 9 3 5 Checking the Drainage Water drain After wiring and drain piping are completed use the following pro cedure to check that the water will drain smoothly For this pre pare a bucket and wiping cloth to catch and wipe up spilled water sure to do the wiring between the units before installing the ceiling panel Refer to 3 9 Wiring Instructions for Inter unit Con
92. ing Inspection or Repair After checking the self diagnostics monitor turn the power OFF before starting inspection or repair High capacity electrolytic capacitors are used inside the outdoor unit controller inverter They retain an electrical charge charging voltage DC 310V even after the power is turned OFF and some time is required for the charge to dissipate Be careful not to touch any electrified parts before the controller LED red turns OFF If the outdoor controller is normal approximately 30 seconds will be required for the charge to dissipate However allow at least 5 minutes for the charge to dissipate if there is thought to be any trouble with the outdoor controller 9 2 Method of Self Diagnostics lt Clock display gt Follow the procedure below to perform detailed trouble diagnostics 4E Test mode w ww L Q QM 2 Self diagnostics mode 1 If the operation lamp blinks every 0 5 seconds immediately when the power is turned ON there is an external ROM data failure on the indoor circuit board ROM socket insertion problem or the ROM O has not been installed JUL 2 The failure mode is stored memory even when the power is not ON Follow the procedure below to perform diagnostics 7 SETTEMP s Dr LILI OY OFFS AM 20070 V PM 2 02 0 3 000 es PROCEDURE HIGH ON OFF O PONER ON
93. ion It does not turn off when the desired room temperature is reached If Night Set Back mode is selected the fan will turn off intermittently during cooling operation in order to control air flow Ol 119 5 EG 5 OPERATION WITH THE REMOTE CONTROL UNIT 2 Manual Operation 1 Automatic Operation only for COOL DRY HEAT Model This unit automatically switches between cooling operation and heating operation according to the difference between the room temperature and the temperature setting NOTE STEP 2 STEP 1 Check that the circuit breaker on the power panel is turned on Once mode is selected and the unit is preset by following the steps below you can have the air conditioner automatically bring the room to the desired temperature simply by pressing the ON OFF operation button Press the MODE selector button to Press the ON OFF operation button To stop the air conditioner press the ON OFF operation button again To change the temperature setting press the temperature setting buttons and change the setting to the desired temperature STEP 4 STEP 5 NOTE Check that the circuit breaker on the power panel is turned on If the automatic operation settings of the unit do not meet your needs press the setting buttons as described below and change the settings as desired Press the MODE selector button and select the desired mode For heating operation For dehumidifying op
94. ion box controller Fig 3 Connector Fig 4 Fig 5 Wire harness Tapping screws Remote controller Fig 6 H How to wire the remote controller 1 Turn OFF the power and remove the ceiling panel air intake grille Refer to 3 6 1 Before Installing the Ceiling Panel in the Installation Instructions supplied with the indoor unit 2 Remove the 3 power box cover screws and 2 control box cover screws then remove both covers At this time take care not to drop the covers Fig 7 3 Disconnect the 7P IND terminal and 4P RC termi nal of the 7P IND and 4P RC wiring connectors and the 5P terminal of the 5P FLAP wiring connector from the control box PCB connectors IND RC FLAP Disconnect each wiring connector from the clamp that fastens it Fig 7 4 Remove the ceiling panel To remove the ceiling panel follow the steps for 3 6 How to Install the Ceiling Panel in the reverse order Refer to the Installation Instructions supplied with the indoor unit 5P FLAP wiring connector 7P IND and 4P RC wiring connector Ceiling panel Fig 8 3 J Terminal cover Wire harness Indicator 5P FLAP 7P IND and 4P RC Ceilin 9 wiring connector wiring connector panel Control box cover Power cover Indi
95. iquid state using the service port of the wide tube service valve The proper amount is listed on the unit s nameplate When the entire amount cannot be charged all at once charge gradually while operating the unit in Cooling Operation CAUTION Never charge a large amount of liquid refrigerant at once to the unit This may cause damage to the compressor When charging with a refrigerant cylinder use an electronic scale for charging refrigerant In this case if the volume of refrigerant in the cylinder becomes less than 20 of the fully charged amount the composition of the refrigerant starts to change Thus do not use the refrigerant if the amount in the charging cylinder is less than 20 Also charge the minimum necessary amount to the charging cylinder before using it to charge the air conditioning unit Example In case of charging refrigerant to a unit requiring 1 68 Ib 0 76 Kg using a capacity of a 22 Ib 10 Kg cylinder the minimum necessary amount for the cylinder is 1 68 22 x 0 20 6 08 Ib 0 76 10 x 0 20 2 76 Kg For the remaining refrigerant refer to the instructions of the refrigerant manufacturer If using a charging cylinder transfer the specified amount of liquid refrigerant from the refrigerant cylinder to the charging cylinder Prepare an evacuated charging cylinder beforehand CAUTION To prevent the composition of R410A from changing never bleed the refrigerant gas int
96. ir intake grille downward When cleaning the air filter never remove the safety cord If it is N necessary to remove it for servicing and maintenance inside be sure to reinstall the safety cord securely hook on the grille side after the work When the air intake grille has been opened rotating parts such as the fan electrically charged areas etc will be exposed in the unit s opening Bear in mind the dangers that these parts and areas pose and proceed with the Air intake grille 3 Press the tabs on both sides of the air filter indicated with lt work carefully marks on the grill to release the filter and then lift and pull the e Periodically check the outdoor unit to filter up and out using the tabs to remove it see if the air outlet or air intake is clogged with dirt or soot Care After a prolonged idle period Check the indoor and outdoor unit air intakes and outlets for blockage if there is a blockage remove it Care Before a prolonged idle period Operate the fan for half a day to dry out the inside Disconnect the power supply and also turn off the circuit breaker Clean the air filter and replace it in its original position RQ oe ru Q Outdoor unit internal components must be checked and cleaned Air filter SAR periodically WN Contact your local dealer for this service 4 Use a vacuum cleaner to remove light dust If there is sticky dust on the filter wash the filt
97. ject such as a ballpoint pen the mark will appear at the display And the room temperature is ADDRESS switch The address switch changes to prevent mixing of signals from remote control units 1284 24H detected by the sensor which is built into the indoor unit and the air C Q CD conditioner is controlled accordingly If the remote control is located near a heat source such as a space heater or in direct sunlight press the SENSOR button to switch to the sensor on the indoor unit when two air conditioners are installed next to each other Normally the address switch Temperature display selector button is set to A For more information please contact the dealer where you made the This switches the temperature display purchase between C and F e Normally the tabs on the remote control unit should not be bent Ol 107 6 EG NOTE Me dal Sensor A temperature sensor inside the remote control unit senses the room temperature ON OFF operation button This button is for turning the air conditioner on and off 1 HR TIMER button 1 HOUR OFF TIMER EG When you press this button regardless of whether the unit is operating or stopping the unit operates for one hour and then shuts down Temperature setting buttons TEMP Press the DA button to increase the set temperature Press the Cv button to reduce the set temperature The temperature setting changes by 1 C or 2 F each time one o
98. klist before Servicing 11 3 Tools Specifically for R410A 11 4 Tubing Installation Procedures aaaaaaaaaasnaa naa naa naannannnannnannnannnannanannannnannnannnannanaannaanna 11 5 In Case of Compressor Malfunction aaaaaaaaaaaaaaaa aaa anunanunanavnnnnnnnnnnnnnnnnnnannnnnnnnnnnnnnannna 11 6 In Gase BHeirigerant iS Leaking asla an breed Ex Pena Core ta en Cor Ex vx EE tw E nba tr os gnis 11 7 Charging Additional Refrigerant 11 8 Retro Fitting Existing Systems a aaainaaaaaaaaaaaaaaauaanuaanuaannaaananaannannnanananauaanuaannaannananaaanaaani APPENDIX A INSTRUCTION MANUAL 1 1 essere nnne nnne nnn enne XHS1271 amp PNR XS1872 CH1271 XHS1872 amp PNR XS1872 CH1872 APPENDIX INSTALLATION INSTRUCTIONS 1 sees XHS1271 amp PNR XS1872 CH1271 XHS1872 amp PNR XS1872 CH1872 APPENDIX INSTRUCTION MANUAL 1 essere nnne n nen STK RCS 7TWSU APPENDIX D INSTALLATION INSTRUCTIONS seen nnne STK RCS 7TWSU 1 OPERATING RANGE Temperature Indoor Air Intake Temp Outdoor Air Intake Temp 95 F D B 71 F W B 115 F D B Cooling 67 F 57 F W B 0 F D B 80 F 67 F W B 75 F 65 F W B eatin D8 WB O
99. l communications 8 High Pressure Switch failure 9 Overload Relay failure 10 Magnetic Coil failure See detailed flowchart in this section 8 88 88 Oo 0 0 0 0 8 l alva 1 HIC or power Tr failure 2 Outdoor fan does not turn 3 Instantaneous power outage 4 Service valve not opened 5 Outdoor fan blocked 6 Continuous overload operation 7 Compressor failure 8 Outdoor PCboard failure HIC circuit failure Power Tr transistor circuit failure unit external ROM OTP data 4 External ROM data failure 2 Outdoor PCboard failure 1 Instantaneous power outage 2 HIC or power transistor failure Peak current cut off Xt Eos Fa Heol art 1 Outdoor PCboard failure 2 Outdoor power supply voltage failure E06 Compressor discharge overheat 1 Electric expansion valve failure 2 Capillaries choked 3 Shortage of refrigerant prevention activated 4 Continuous overload operation 5 Outdoor fan does not rotate 6 Outdoor PCboard failure 4 Indoor fan operating failure 1 Fan motor failure 2 Contact failure at connector 3 Indoor PCboard failure E 4 way valve switching failure 1 4 way valve failure heat pump model only iK O8 Indoor zero cross failure 2 Outdoor PCboard failure No refrigerant protection 1 Service valve not opened 2 Shortage of refrigerant E10 DCcompressor drive circuit failure 1 Open phase 2 Outdoor PCboard failure e O Q N ed pessum
100. l strip Fig 7 Indoor Unit Fig 7 Turn ON the power and operate the system using the remote controller or the operation button on the indoor unit Perform the self diagnosis five seconds after the operation start Condition E01 What is the latest self diagnosis result Defect in Ms inter unit cable Condition 12 Defect in the indoor unit P C board 55 9 4 Trouble Diagnosis of Fan Motor 9 4 1 Indoor Fan Motor This indoor DC fan motor contains an internal control PCB Therefore it is not possible to measure the coil resistance and the following procedure should be used to check the motor To perform diagnosis operate the unit in cooling mode with indoor fan speed High Next make sure that the indoor unit receive the signals from the remote controller when the ON OFF operation button is pressed Important A Turn OFF the power before connecting or disconnecting the motor connectors B When performing voltage measurement at the indoor controller connector for 3 in the table below the DC motor will trip and voltage output will stop approximately 1 minute after operation is started For this reason to measure the voltage again turn OFF the unit once using the remote controller and then start the air conditioner again Trouble symptom 1 The fan does not stop when the unit stops Indoor unit controller trouble Trouble symptom 2 The fan motor does not rotate when the unit is operating D
101. lf diagnostics procedure Operation Timer High Power X Off b D F Blinking D Muminated lt Before the Operation gt For terminal strip short circuit work or inter unit wiring removal turn off the power to N WARNING avoid an electric shock Release the terminal strip short circuit after the completion of self diagnostics Do not perform the short circuit work between any other terminals except for N CAUTION specified ones on the specified terminal strip If such work is performed between the incorrect terminals the unit might be broken lt Convenient Tool for Short Circuit Work for example gt i gt Alligator Clip lt Check Items before Troubleshooting Serial Communication Start gt After confirming that the following errors do not exist start the Troubleshooting Serial Communication in Condition E01 and E12 Mis wiring inter unit cable etc 6 Reactor failure defective insulation etc AC power failure 7 High Pressure Switch failure Blown fuse 8 Overload Relay failure Power Relay failure 9 Magnetic Coil failure defective insulation short circuit etc Outdoor Fan Motor failure defective insulation etc 10 Compressor failure defective insulation etc 3 1 Condition E01 Troubleshooting Serial Communication Outdoor Unit Indoor Unit _ Fig 1 Fig 2 Is the voltage of about DC12V or more given between the terminals 2 and 3
102. ling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floors In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid level foundation for the outdoor unit This prevents water damage and abnormal vibration In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised platform that is higher than drifting snow Provide snow vents When Connecting Refrigerant Tubing Use the flare method for connecting tubing Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them then tighten the nut with a torque wrench for a leak free connection Check carefully for leaks before starting the test run When Servicing Turn the power off at the main power box mains before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced Others CAUTIO
103. ly changed to LL beginning 30 seconds after the thermostat turns OFF At stability of operation refers to operation when the room temperature has approached the set temperature When HEAT operation starts the indoor fan is stopped until the temperature of the indoor heat exchanger reaches 68 F 20 C or higher or until the room temperature reaches 59 F 15 C or higher H Compressor discharge temperature control This function controls the operation frequency to prevent the compressor discharge temperature from rising more than a specified temperature Compressor discharge temperature F C Area Automatic capacity control When the temperature rises above Point A the operation frequency is reduced at a specified rate Area Further frequency increase is prohibited When the temperature falls below Point B prevention of a rise in frequency is released and the air conditioner operates as in a area The compressor will stop if the temperature of the compressor discharge exceeds 248 F 120 C due to shortage of gas or other reason H Defrost detection and release CT Peak current cut off control e Reverse Cycle Defrosting e This function prevents the circuit breaker or fuse from operating to open the circuit This function works when electrical current has increased due to an increase in the cooling heating load or to a decrease in the power supply voltage In these cases operation frequency is red
104. matically adjust the set temperature to save energy FLAP button Press this button either to select the setting of the airflow direction to one of the six possible positions manually or to select the sweep function which moves the flap up and down automatically The airflow direction can be set manually six positions NS The flap moves up and down automatically NOTE When you press the FLAP button the air flow direction will be changed one by one as follows 1 2 3 4 S 6 7 DE gt SWEEP Timer and Present Time setting buttons First press the SET button to select the mode ON OFF and Present Time operation button is ON all settings are cleared settings you want Press the ACL button if the air conditioner is not Each time you press the HH button the hours advance by one operating correctly PMO PM1 PM11 AMO AM1 AM11 Each time you press the MM button the minutes advance by one when setting Present Time and by ten when setting ON and OFF Time SET button For details see Setting the Timer Press this button to select the mode you want to program ACL button ALL CLEAR When you press the ACL button while the 4 Ol 119 4 EG ON OFF operation button This button is for turning the air conditioner on and off EG MODE selector button Use this button to select AUTO HEAT DRY COOL or FAN mode AUTO When this setting is selected the ai
105. mm Fig 22 Taping the flare nuts Wind the insulation tape around the flare nuts at the tube connections Secondly cover up the tubing connec tions with the flare insulation 1 8 T3 supplied Then wind the other flare insulation 3 16 T5 supplied Finally fasten the insulation at both ends with the sup plied vinyl ties Fig 23 Insulation material The material used for insulation must have good insula tion characteristics be easy to use be age resistant and must not easily absorb moisture After a tube has been insulat ed never try to bend it into a narrow curve because it can cause the tube to break or crack 16 Torque wrench Indoor unit Spanner Outdoor unit Fig 21 Insulation CN Thickness Min min 5 16 5 16 8 mm 8 mm Fig 22 Insulation tape Flare insulation 3 16 T5 supplied Flare insulation 1 8 T3 supplied NNNNNNNNNNSNNNNNNNNNNNNN c TENNESSEE FA bba R AIM IR N Tube insulation not supplied Flare nut Vinyl tie Supplied Fig 23 Drain hose insulation and vinyl tie Supplied Drain pipe and insulation not supplied Refrigerant tubing and insulation not supplied Insulation tape Drain hose and hose band Supplied Vinyl tie Supplied Flare insulation The procedure used for installing the insulation for both wide and narrow tubes are the same Fig 24 Never grasp the drain or refrigerant con
106. n Rotary Inverter RATOA 2 87 1 300 Electric Expansion Valve Operation Sound Indoor Hi Me Lo dB A 44 40 36 44 40 36 Outdoor Hi dB A 51 52 Refrigerant Tubing Connections Flare Type 25 7 5 Refrigerant Narrow tube inch mm 1 4 6 35 Tube Diameter Wide tube inch mm 1 2 12 7 Air Clean Filter Wired Remote Controller Option STK RCS 7TWSU N O Microprocessor Thermister Wireless Remote Control Unit 24 Hour ON or OFF Timer 1 Hour OFF Timer Auto and 3 steps Auto Hi Me Lo 10 Indoor Unit XHS1872 amp PNR XS1872 Outdoor Unit CH1872 208V Individual Unit Indoor Unit Dimensions amp Weight Indoor Unit Body Panel XHS1872 amp PNR XS1872 XHS1872 51872 Unit Dimensions Height Package Dimensions Height P84 13782 290 4 1 8 105 Pd 2 4 18 16 630 26 3 16 665 28 1 8 714 26 11 16 678 Weight Net Ib kg Siang o tig T 88 Shipping Volume o cuft m 4 59 0 13 Outdoor Unit CH1872 26 3 8 670 34 21 32 880 11 7 32 285 Dimensions amp Weight Outdoor Unit Unit Dimensions Height Package Dimensions Height 14 31 32 380 kg 97 0 44 0 kg 105 8 48 0 Weight Net Ib Shipping Ib Shipping Volume cu ft m 9 88 0 28 DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks Rating conditions are Cooling Indoor air temperature 80 F D B 67
107. n of high frequency noise to the signal wires resulting in abnormal signal pulses and malfunction 1 Locations near broadcast stations where Either of the following trouble may occur The fundamental concept is to make the there are strong electromagnetic waves 1 The unit may stop suddenly during system less susceptible to noise 2 Locations near amateur radio short wave operation Insulate for noise or stations 2 Indicator lamps may flicker distance from the noise source 3 Locations near electronic sewing machines 1 Use shielded wires and arc welding machines 2 Move unit away from the noise source 2 Electromagnetic interference This refers to noise generated by high speed switching of the microcomputer and compressor This noise radiates through space and returns to the electric wiring affecting any wireless devices televisions radios etc located nearby 1 A television or radio is located near the 1 Noise appears in the television picture 1 Select a separate power source A C and A C wiring or the picture is distorted Keep the A C and A C wiring at least 1 meter 2 The antenna cable for a television or 2 Static occurs in the radio sound away from wireless devices and antenna cables radio is located close to the A C and A C wiring 3 Locations where television and radio signals are weak Change the wireless device s antenna to a high sensitivity antenna Change the antenna cable to a BS
108. n use a probe with a thinner pin 59 Ground wire Probe Insulation tester Fig 1 Terminal plate ele SII V W Clip A Insulation tube or tester metallic part 2 Q Copper tube or metallic part O O Insulation tester Fig 3 From fan motor compressor and other parts 2 Metallic Clip Insulation tester Fig 4 10 2 Checking Continuity of Fuse on PCB Ass y xdi e Remove the PCB Ass y from the electrical component box Then pull out the fuse from the PCB Ass y Fig 5 e Check for continuity using a multimeter as shown in PCB Ass y Fig 6 9 3 Fig 5 Fuse Fig 6 60 11 REFRIGERANT R410A SPECIAL PRECAUTIONS WHEN SERVICING UNIT 11 1 Characteristics of New Refrigerant R410A 11 1 1 What is New Refrigerant R410A R410A is a new refrigerant that contains two types of pseudo non azeotropic refrigerant mixture Its refrigeration capacity and energy efficiency are about the same level as the conventional refrigerant R22 11 1 2 Components mixing proportions HFC32 50 HFC125 50 11 1 3 Characteristics Less toxic more chemically stable refrigerant e The composition of refrigerant R410A changes whether it is in a gaseous phase or liquid phase Thus when there is a refrigerant leak the basic performance of the air conditioner may be degraded because of a change in composition of the remaining r
109. nd 3 steps Auto Hi Me Lo _Fuse or Circuit Breaker Capacity A Indoor Unit XHS1271 amp PNR XS1872 Outdoor Unit CH1271 Individual Unit Indoor Unit Dimensions amp Weight Indoor Unit Body Panel 51271 amp PNR XS1872 XHS1271 51872 Unit Dimensions Height Package Dimensions Height Po 1143 82 290 4 1 8 105 Pd 24 18 16 630 26 3 16 665 28 178 714 26 11 16 678 Weight Net Ib kg CENE o tig 9769 Shipping Volume cuft m 4 59 0 13 Outdoor Unit CH1271 Unit Dimensions Height 21 9 16 548 28 11 32 720 10 7 16 265 Package Dimensions Height i Dimensions amp Weight Outdoor Unit 33 11 16 Weight Net Shipping DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks Rating conditions are Cooling Indoor air temperature 80 F D B 67 W B Heating Indoor air temperature 70 F D B Outdoor air temperature 95 F 75 F W B Outdoor air temperature 47 F 43 F W B 2 1 2 Indoor Unit XHS1872 amp PNR XS1872 Outdoor Unit CH1872 lt 230V gt Voltage Rating 230V Single Phase 60Hz Cooling Heating 17 500 4 000to 17 500 20 400 4 400 to 20 400 kW 545 1 2105 15 60 1 3106 0 10 600 6 900 Air Circulation High ft min m h 341 580 383 650 4 89 Performance Moisture Removal High Pints Available Voltage Range Running Amperes Power Input Power Factor 1
110. necting out lets when moving the unit 5 6 Taping the Tubes 1 At this time the 2 refrigerant tubes and electrical wire if local codes permit should be taped together with armoring tape The drain hose may also be included and taped together as 1 bundle with the tubing 2 Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall As you wrap the tubing overlap half of each previous tape turn Fig 25 3 Clamp the tubing bundle to wall using 1 clamp approx every 47 120 cm Do not wind the armoring tape too tightly since this will decrease the heat insulation effect Also be sure the con densation drain hose splits away from the bundle and drips clear of the unit and the tubing 5 7 Finishing the Installation After finishing insulating and taping over the tubing use sealing putty to seal off the hole in the wall to prevent rain and draft from entering Fig 26 6 Air Purging Air and moisture remaining in the refrigerant system have undesirable effects as indicated below Therefore they must be purged completely e pressure in the system rises e operating current rises e cooling or heating efficiency drops e moisture in the air may freeze and block capillary tubing e water may lead to corrosion of parts in the refrigerant system Air Purging with a Vacuum Pump for Test Run 1 Check that each tube both narrow and wide tubes between the
111. nections 1 Turn on the power Here power refers to the power supply Over 4 from the outdoor unit 100mm 2 Slowly pour approx 16 ounces 500 ml of water into the drain pan to check drainage Fig 6 10a 3 Remove the 2 screws from the control box cover then open a Plastic container C gt Drain pan outlet the cover Be careful not to drop the cover at this time for water intake Water 4 Disconnect the FS 3P connector red on the control PCB and S operate the drain pump Fig 6 10b Check the water flow Fig 6 10a through the transparent drain pipe and see if there is any leakage Control box 5 When the check of drainage is complete reconnect the FS 3P connector and remount the control cover The drain pump will continue to N CAUTION operate for a minimum of 6 min utes after the FS 3P connector is reconnected A must be within the range of 1 2 13mm to 23 32 18mm Fig 6 11 If not within this range malfunction or other trouble may occur Fig 6 10b 3 6 How to Install the Ceiling Panel Checking the unit position 1 Check that the ceiling hole is 23 5 8 600 mm x 23 5 8 BN Ceiling opening sss dimension 600 mm Fig 6 11 2 Confirm that the position of the indoor unit and the ceiling as shown in the diagram If the positions of the ceiling sur NO face and unit do not match air leakage water leakage flap operation failure or other problems may occur F
112. ng blown out of the unit begins to warm Once the air warms up the flap position and fan speed change to the settings specified with the remote control N caution e Use the FLAP button on the remote control to adjust the position of the flap If you move the flap by hand the flap position according to the remote control and the actual flap position may no longer match If this should happen shut off the unit wait for the flap to close and then turn on the unit again the flap position will now be normal again Do not have the flap pointed down during cooling operation Condensation may begin to form around the air vent and drip down APPENDIX D INSTALLATION INSTRUCTIONS STK RCS 7TWSU 11 852 6 4190 481 00 0 4 INSTALLATION INSTRUCTIONS SANYO STK RCS 7TWSU Wired Remote Controller B Parts supplied with the remote controller Table 1 See Table 1 Parts Figure Parts Figure B Remote controller installation guidelines Installation location e Mount the remote controller 3 3 to 4 9 ft 1 to 1 5 meters off the floor where it can sense the average temperature of the room Do not mount the remote controller in a place exposed to direct sunlight or where it is exposed to outside air such as near a window Do not mount the remote controller behind a curtain or 26 2 ft 8m Wired a Wire emm Mire harness J Non 5 32x 15 16 Machine 4x25mm Instruction
113. ng instructions Once you ve found this best position always keep the remote control unit there This appliance has a built in 5 minute time delay circuit to ensure reliable operation When the operation button is pressed the compressor will start running within three minutes In the event of power failure the unit will stop Ol 107 9 EG 9 3 Adjusting the Fan Speed A Automatic fan speed Simply set the FAN SPEED selector button to the position This automatically sets the best fan speed for the room temperature B Manual fan speed If you want to adjust fan speed manually during operation just set the FAN SPEED selector button as desired 3 3 or 4 Fan Only HIGH ON OFF O POWER C3 STEP 2 FAN SPEED MODE STEP 3 MED M eum STEP 1 FLAP NIGHT SETBACK CD If you want to circulate air without any temperature control follow these steps STEP 1 Press the MODE selector button to switch to the fan mode S8 2 Press the ON OFF operation button STEP 3 Press the FAN SPEED selector button to select the fan speed of your choice 9 or 5 Night Setback Mode FANSPEED FLAP NIGHT SETBACK C gt Night Setback Mode is used for saving energy Press the NIGHT SETBACK button while operation The mark appears in the display To release the night setback function press the NIGHT SETBACK button again 10 A In Cooling
114. nit as shown dropping in Fig 6 24 Fig 6 24 Fig 6 25 n 3 6 5 Checking After Installation Check that there are no gaps between the unit and the ceiling panel or between the ceiling panel and the ceiling sur face Gaps may cause water leakage and condensation e Check that the wiring is securely connected If it is not securely connected the auto flap will not operate In addition water leakage and condensation may occur 3 6 6 When Removing the Ceiling Panel for Servicing When removing the ceiling panel for servicing remove the air intake grille and air filter disconnect the flap and the indi cator wiring connectors inside the control box and then remove the 4 mounting screws 3 6 7 Adjusting the Auto Flap The air direction flap on the ceiling panel outlet can be adjusted as follows Adjust the flap to the desired angle using the remote controller The flap also has an automatic air sweeping mecha nism Never attempt to move the flap by hand Proper air flow depends on the location of the air conditioner the layout of the room and furniture etc If cooling or heating seems inadequate try changing the direction of the air flow 3 7 Wiring Instructions General precautions on wiring 1 Before wiring confirm the rated voltage of the unit as shown on its nameplate then carry out the wiring closely following the wiring diagram 2 Provide a power outlet to be used exclusively for each unit
115. o the atmosphere while transferring the refrigerant Fig 3 Do not use the refrigerant if the amount in the charging cylinder is less than 20 65 Configuration and characteristics of cylinders Valve Single valve Charge liquid refrigerant with cylinder in up side down position Fig 1 Single valve with siphon tube Charge with cylinder in normal position Fig 2 Charging cylinder Ope Refrigerant cylinder Fig 3 11 6 In Case Refrigerant is Leaking CAUTION Never attempt to charge additional refrigerant when refrigerant has been leaking from the unit Follow the procedure described below to locate points of leaks and carry out repairs then recharge the refrigerant 1 Detecting Leaks Use the detector for R410A to locate refrigerant leak points 2 Recovering refrigerant Never release the gas to the atmosphere recover residual refrigerant using the refrigerant recovery unit for R410A instead Do not reuse the recovered refrigerant because its composition will have been altered 3 Welding leaking points e Confirm again that no residual refrigerant exists in the unit before starting welding Weld securely using flux and wax for R410A Prevent oxide film from forming inside the tubes utilizing substitution with nitrogen N2 in the refrigerant circuit of the unit Leave ends of tubes open during welding 4 Checking for sealing e Use nitrogen gas for the pres
116. ocal codes Fig 14 14 5 Refrigerant Tubing Deburring 5 1 Use of the Flaring Method Many of the conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units In this method the copper tubes are flared at each end and connected with flare nuts 5 2 Flaring Procedure with a Flare Tool 7 g 1 Cut the copper tube to the required length with a 4 4 Nf tube cutter It is recommended to cut approx 12 to Fig 15 20 30 to 50 cm longer than the tubing length you estimate C 2 Remove burrs at the end of the copper tube with a pe Nuus tube reamer or file This process is important and should be done carefully to make a good flare Fig 15 When reaming hold the tube end downward and be sure that no copper scraps fall into the tube Fig 16 Fig 16 3 Remove the flare nut from the unit and be sure to If the special R410A If the previous flare tool mount it on the copper tube flare tool is used clutch type is used 4 Make a flare at the end of copper tube with a flare T tool Figs 17 and 18 D 0 to 0 0196 0 0472 1 2 mm 0 to 0 5 mm Use RIDGID or equivalent Adjust so that the amount of tube protrusion is as shown in the figure Fig 17 A good flare should have the following characteristics Flare nut Copper NM vr tubing a sure to apply a sealing cap or wat
117. of the Remote Control Unit aaaiaaaaaaaaaasasa asa santananaananaaaaananannanaananaaa 37 7 2 Disconnecting and Connecting Positive Connector for Outdoor Unit 38 7 83 Disassembly Procedure aainaaaaaanaaaaaaaaaaanuaanuanunannannannnannnnnnannannnnnnnnnnannannannnannannnnnnannannd 39 FUNCTIONS 8 1 Operation Functions 46 RN FUN ee m 48 TROUBLESHOOTING 9 1 Precautions before Performing Inspection or Repair 50 9 2 Method of Self DiagnostiCs naninaaaaaaaaaaaaaaanaaanaaanaaanaaanaannaaanananananuannuannnannanaananaannaannaanuaanaa 50 9 3 Checking the Indoor and Outdoor Units 52 9 4 Trouble Diagnosis of Fan Motor aaaaaaaaaaaaaaaaaaasaaanaanaanuaanaanunanannuannannananannannannnannnannanna 56 9 5 Noise Malfunction and Electromagnetic Interference 58 10 CHECKING ELECTRICAL COMPONENTS 10 1 Measurement of Insulation Resistance a2aaaaaaaaaaaa aaasaaasnansansaaunaaunaaunaannaaunannnanaana 10 2 Checking Continuity of Fuse on ASS Y uauavnnaaanaaanaaaaaaaaaaaaaaaaaaaaaaaaaaanaaanaaanaaaanaaanaaanaann 11 REFRIGERANT R410A SPECIAL PRECAUTIONS WHEN SERVICING UNIT 11 1 Characteristics of New Refrigerant R410A sss nennen nnn 11 2 Chec
118. om the hook Bolt Fig 8 Fig 9 40 7 3 4 Remove the indoor air temperature sensor 1 Disconnect the connector CN08 ROOM 2P in the control box and remove the indoor air temperature sensor Fig 10 Indoor air temperature sensor r CNO8 __ l Z DL L7 AN LJ e Fig 10 7 3 5 Remove the power box and control box 1 Remove a screw and remove the terminal cover Fig 11 2 Remove the 2 screws and remove the power box cover Fig 11 3 Disconnect the power lines No 1 and No 2 signal line No 3 and ground cable from the terminals in the power box Fig 12 Ry SL JAR S FR Terminal 8 We Ground cable NN SS m Power lines Signal line 4 Disconnect the connector CNO7 DP 2P in the power box Fig 13 Remove a screw and disconnect the ground cable Fig 13 5 Disconnect the connector CNO3 DCM 6P in the power box Fig 14 6 Remove the 4 screws and remove the power box Fig 14 7 Disconnect the connectors CNO6 FS and CNO9 COIL 1 2P in the control box Fig 15 8 Remove the 2 screws and remove the control box Fig 15 5 6 7 8 Screw CNO3 Screw For the removal of the following components perform any work after removing the indoor unit main body from the ceiling Main body lower section Heat exchanger sensor Drain pump Float switch Turbo fan Fan motor Heat exchanger 1 Perform the work af
119. on The indoor unit should make a beeping sound to indicate that it has received the signal 7 Mounting screws 5 32 x 5 8 To prevent loss of the remote control 4 x 16 mm unit you can connect the remote included control unit to the mount by passing a string through the remote control unit and attachment hole To take out the remote control unit pull it forward WHEN HOLDING THE REMOTE CONTROL UNIT e When using the remote control unit and during air conditioner operation the transmitter on the remote control unit should be pointed towards the receiver on the indoor unit Make sure that there are no objects between the remote control unit and receiver which could block the signal Ol 107 8 EG OPERATION WITH THE REMOTE CONTROL UNIT 1 Automatic Operation 2 Manual Operation This unit automatically switches between cooling operation and heating operation according to the difference between the room temperature and the temperature setting i F AM 0 2071 HIGH OON T OFF O POWER STEP 2 AM 0 04 Dt STEP 3 HIGH POWER STEP 2 FAN SPEED MODE STEP 4 1 FLAP SETBACK STEP 5 SED FANSPEED STEP 1 NOTE Check that the circuit breaker on the power panel is turned on FLAP NIGHT SETBACK If the automatic operation settings of the unit do not meet your needs press the setting buttons as described below and change the s
120. on have passed after the selection was made and then another 2 F after another 30 minutes have passed regardless of the indoor temperature when night setback was selected This enables you This automatically sets the best fan speed for the room temperature to save energy without sacrificing comfort This function is B Manual fan speed convenient when gentle cooling is needed If you want to adjust fan speed manually during operation just set the FAN SPEED selector button as desired 9 or 4 Fan Only Setting temperature L STEP 2 Press the NIGHT SETBACK button STEP 3 STEP 1 B In Heating Mode out only for COOL DRY HEAT Model When the night setback mode is selected the air conditioner automatically lowers the temperature setting 4 F when 30 minutes have passed after the selection was made and then another 4 F after another 30 minutes have passed regardless of the indoor temperature when night setback was selected This enables you to save energy without sacrificing comfort This function is convenient when gentle heating is needed If you want to circulate air without any temperature control follow these steps STEP 1 Press the MODE selector button to switch to the fan mode STEP2 Press the ON OFF operation button STEP 3 Press the FAN SPEED selector button to select the fan speed of your choice 8 9 or 5 Night Setback Mode Setting temperature Pr
121. ons Refrigerant R410A is more easily affected by dust or moisture compared with R22 thus be sure to temporarily cover the ends of the tubing with caps or tape prior to installation Never use 0 0276 0 7 mm thick copper tubing or tubing which is less than 0 0315 0 8 mm in thickness since air conditioners with R410A are subject to higher pressure than those using R22 and R407C No addition of compressor oil for R410A No additional charge of compressor oil is permitted No use of refrigerant other than R410A Never use a refrigerant other than R410A e If refrigerant R410A is exposed to fire Through welding etc toxic gas may be released when R410A refrigerant is exposed to fire Therefore be sure to provide ample ventilation during installation work Caution in case of R410A leak Check for possible leak points with the special leak detector for R410A If a leak occurs inside the room immediately provide thorough ventilation 62 11 3 Tools Specifically for R410A e For servicing use the following tools for R410A Gauge manifold Charging hose Gas leak detector Refrigerant cylinder Charging cylinder Refrigerant recovery unit Tools specifically for R410A Vacuum pump with anti reverse flow 1 Solenoid valve installed type which prevents oil from flowing back into the unit when the power is off is recommended e Vacuum pump 2 be used if the following adapter is attached e Vacuum pump
122. operation the mode changes between Heating and Cooling mode according to changes in the relationship between the current room temperature and the set temperature Example Example of operation in AUTO mode with the set room temperature at 74 F 23 C Room temp Set temp Compressor OFF 46 SENSOR DRY During DRY operation the system adjusts the room temperature and fan speed according to the conditions in the room in order to maintain a comfortable room environment SENSOR DRY operation DRY operation is as shown in the figure below Load COOL zone Conditions are monitored at all times when the room temperature is below 59 F 15 C The compressor operation frequency varies The indoor fan operates with 1 f fluctuation The compressor operates at a low operating frequency The indoor fan operates with 1 f fluctuation Monitoring operation takes place when the room temperature is below 59 F 15 C or more than 5 F 3 C below the set temperature When the monitoring range is entered the compressor stops and the indoor fan operates with 1 f fluctuation B PAM o control n order to further improve inverter performance control is switched between PWM control at low operation speeds and PAM control at high operation speeds making the most effective use of power This function acts to raise the power but keeps the AC system in the same operating mode This function is set with the
123. ortant part of your job to Install or service the system so it operates safely and efficiently For safe installation and trouble free operation you must Carefully read this instruction booklet before beginning Follow each installation or repair step exactly as shown Observe all local state and national electrical codes Pay close attention to all warning and caution notices given in this manual This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death This symbol refers to a hazard or unsafe practice which can result in personal injury or prod CAUTION uct or property damage If Necessary Get Help These instructions are all you need for most installation sites and maintenance conditions If you require help for a special problem contact our sales service outlet or your certified dealer for additional instructions In Case of Improper Installation The manufacturer shall in no way be responsible for improp er installation or maintenance service including failure to follow the instructions in this document SPECIAL PRECAUTIONS when wiring 09990009090999090909990900900999090090909909009990990099990099999009909900909909909900909990900909990009099090009099090090909900900909999090999990990999099099 9 ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH ONLY A QUALIFIED EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM Do not sup
124. ouble the air conditioner will switch to the temperature sensor which is built into the indoor unit and control the room temperature In these cases the temperature around the remote control unit may differ from the temperature detected at the air conditioner s position The indoor fan runs continuously when the system is in normal operation It does not turn off when the desired room temperature is reached If Night Set Back mode is selected the fan will turn off intermittently during cooling operation in order to control air flow Ol 107 7 EG USING THE REMOTE CONTROL UNIT HOW TO INSTALL BATTERIES FAN SPEED MODE FLAP NIGHT SETBACK TIMER CANCEL CLOCK SENSOR C F _12H4 gt 24H ADR DOTS d p NOTE Initially the S M switch is set to S Leave this position ACL button 1 Slide the cover in the direction indicated by the arrow and remove it 2 Install two AAA alkaline batteries Make sure the batteries point in the direction marked in the battery compartment 3 Use a thin object such as the tip of a pen to press the ACL button NOTE The batteries last about six months depending on how much you use the remote control unit Replace the batteries when the remote control unit s display fails to light or when the remote control cannot be used to change the air conditioner s settings Use two fresh leak proof type AAA alkaline batteries In replacing batteries follo
125. ply power to the unit until all wiring and tubing are completed or reconnected and checked Highly dangerous electrical voltages are used in this system Carefully refer to the wiring diagram and these instructions when wiring Improper connections and inadequate grounding can cause accidental injury or death e Ground the unit following local electrical codes Connect all wiring tightly Loose wiring may cause over heating at connection points and a possible fire hazard When Transporting 090990009090999000999090090999000009909009990009999009999900909099000099990900090990009090999000090990900009909000090900900999900909099990999990990999 Be careful when picking up and moving the indoor and out door units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin alu minum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Properly insulate any tubing run inside a room to prevent sweating that can cause d
126. r e This outdoor DC fan motor contains an internal control PCB Therefore it is not possible to measure the coil resistance and the following procedure should be used to check the motor Perform the trouble diagnosis by Test Run mode described on Installation Instructions Important A Turn OFF the power before connecting or disconnecting the motor connectors B When performing voltage measurement at the outdoor controller connector for 3 in the table below the DC motor will trip and voltage output will stop approximately 10 seconds after operation is started For this reason to measure the voltage again first turn OFF the outdoor unit power then measure the voltage in Test Run mode Trouble symptom 1 The fan does not stop when the outdoor unit stops Outdoor unit controller trouble Trouble symptom 2 The fan motor does not rotate when the outdoor unit is operating Diagnostic procedure Disconnect the motor connectors and measure the voltage at the DC motor connectors on the outdoor unit controller 3 locations Measurement location 1 Vs Gnd Between pin 1 and pin 4 DC 110V or more 2 Vcc Gnd Between pin 5 and pin 4 DC 14V or more 3 Vsp Gnd Between pin 7 and pin 4 After fluctuating 4 times between DC 1 0 to 4 3V 1 sec ON and DC 0 V 1 sec OFF the DC motor trips Diagnostic results All of the above measured values are normal Fan motor trouble Replace the motor Any one of the above measur
127. r conditioner calculates the difference between the thermostat setting and the room temperature and automatically switches to the COOL or HEAT mode as appropriate HEAT The air conditioner makes the room warmer DRY 0 The air conditioner reduces the humidity in the room COOL amp The air conditioner makes the room cooler FAN The air conditioner works only as a circulation fan 1 HR TIMER button 1 HOUR OFF TIMER TE When you press this button regardless of whether the unit is operating or stopping the unit operates for one hour and then shuts down TIMER SELECT button No display The timer does not operate SANE The air conditioner starts at the set time The air conditioner stops at the set time Co The air conditioner stops and starts or starts and stops at the set times every day Sensor A temperature sensor inside the remote control unit senses the room temperature SENSOR button When you press this button use a small tipped object such as a ballpoint pen the B mark will disappear at the display And the room temperature is detected by the sensor which is built into the remote control unit and the air conditioner is controlled accordingly NOTE If the remote control is located near a heat source such as a space heater or in direct sunlight press the SENSOR button to switch to the sensor on the indoor unit The indoor fan runs continuously when the system is in normal operat
128. red temperature 7 SET TEMP The fan speed is 1step above HIGH it it DP D F FAN SPEED selector button LILI The air conditioner automatically decides the fan speeds e High fan speed AM TOA TATA ee Medium fan speed PM e Low fan speed 27 9 FLAP button Press this button either to select the setting of the airflow direction to the auto flap in each mode or one of the six possible positions manually or to select the sweep function which moves the flap up and down automatically 1 Auto flap setting If selected in a heating operation the flap is set to position 3 in the following chart lf selected in a cooling or dry operation the flap is set at position 7 in the following chart The airflow direction can be set manually six positions The flap moves up and down automatically When you press the FLAP button the air flow direction will be changed one by one as follows 1 _ 2 3 4 5 6 7 8 A St SAS a a 37 SWEEP ON TIME OFF TIME setting buttons Advance button Return button No display The timer does not operate The air conditioner starts at the set time The air conditioner stops at the set time OFF The air conditioner stops and starts or starts and stops at the set times every day For details see SETTING THE TIMER V 4 CANCEL button SENSOR button When you press this button use a small tipped ob
129. reful not to fall down If you fall down you might be injured seriously 7 3 1 Remove the air intake grill 1 Slide the 2 latches each to the corresponding arrow direction Fig 1 and Fig 2 Open downward the air intake grill located on the latch side 2 Undo the air intake grill drop preventive hook Fig 3 Undo the 2 hinges for the grill and remove the air intake grill Latch Latch Air intake grill Hinge Fig 1 Fig 2 Fig 3 7 3 2 Disconnect the connectors in the control box 1 Remove the 2 screws and remove the control box cover Fig 4 2 Disconnect the connectors CN04 FLAP 5P CN12 RC 4P and CN13 IND 7P Fig 5 Control PCboard CN13 CN12 Screw Control box cover Fig 4 Fig 5 39 7 3 3 Remove the ceiling panel 1 Open the clamp 4 locations and remove the 2 lead wires from the clamps Fig 6 2 Remove the 4 screws fixing the corner cover at 3 locations and indicator cover at 1 location Fig 6 3 Press the center 1 of the cover and remove the cover with the section 2 pulled down Fig 7 4 Remove the strap 3 locations from the hook on the ceiling panel Fig 8 There is no strap on the indicator cover 5 Remove the bolt 4 locations with a washer and remove the ceiling panel Fig 9 Coner cover Lead wire Pull down section 2 Cover Indicator cover Center 1 Coner cover Coner cover Fig 7 Bolt Strap Remove the strap fr
130. ripping and water damage to walls and floors In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid level foundation for the outdoor unit This prevents water damage and abnormal vibration In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised platform that is higher than drifting snow Provide snow vents When Connecting Refrigerant Tubing 0900990009090909090092999009909000099900099990009999909009900009909900090909009099000909900090090909900009909000090990900090999000990999099099999099 Use the flare method for connecting tubing Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them then tighten the nut with a torque wrench for a leak free connection Check carefully for leaks before starting the test run When Servicing 009099000099909090099909000999900009990900999900099990900929090009909000990999090099099000090900000909090009009900009990900090999000999990909099999099 Turn the power OFF at the main power box mains before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been le
131. rse flow prevention for R410A must be used The required time in Table 6 is calculated based on the assumption that the ideal or target vacuum condition is around 0 193 psi 10 mmHg abs 90 1 4 turn Narrow tube Hex wrench RO gt lt J Wide tube TE NJL P Valve cap Vacuum hose to manifold valve Fig 28 Turn the narrow tube service valve stem counter clockwise to 10 Loosen the vacuum hose connected to the wide tube service port slightly to release the pressure Then remove the hose hose quickly This may cause the refrigerant gas to leak In order to avoid this take off the 11 Fasten the valve cap on the wide tube service port securely with an adjustable wrench or box wrench Next mount the valve cap on the service valve and tighten it to 170 Ibs in 200 kgf cm with a torque wrench This process is very important to prevent gas from leaking from the system 12 Test run the air conditioner See next page 13 While the air conditioner is running apply liquid soap to check for any gas leaks around the service valves or caps 14 If there is no leakage stop the air conditioner 15 Wipe off the soap on the tubing This completes air purging with a vacuum pump and the air condi tioner is ready for actual operation 18 How to Test Run the Air Conditioner After turning on the power of the air conditioner use the remote controller and follow the step
132. run mode check the 3 indicator be output and the multimeter pointer must bounce once every 8 lamps on the unit If all 3 are blinking seconds the current mode is TEST run Or instead of measuring the voltage you can insert an LED jig and check that the LED flickers once every 8 seconds e f there are no problems with the above then check the outdoor unit For the Test run procedure refer to the Appendix B Installation Instructions 2 Checking the outdoor unit No _ Check items unit operation 1 Apply the rated voltage between outdoor The control panel LED red must illuminate unit terminals L and N 2 Short circuit the outdoor unit COM terminal The compressor fan motor and 4 way valve must all turn on to the T RUN terminal f there are no problems with the above then check the indoor unit Using the TEST T RUN terminals TEST T RUN terminals T RUN Test run compressor and fan motor turn ON TEST MV Compresses time to 1 60th accelerates operation by 60 times faster than normal 52 3 Serial Communication Error Identification Procedure If the lamps on the main body show the following conditions after the completion of self diagnostics a communication error between the indoor unit and outdoor unit might be considered In such a case identify the breakdown section by using the following procedure Refer to Method of Self Diagnostics for the se
133. s below to conduct the test run 1 Set the remote controller in Test Run mode Fig 29 a Press and hold the HIGH POWER button and the 1HR TIMER button b Then press and hold the ACL Reset button with a pointed object such as the tip of a pen After 5 seconds release the ACL button first c Then release the HIGH POWER and 1HR TIMER buttons d appears and oP 1 blinking in the remote con troller clock display area Fig 30 2 Start Cooling mode test run by pressing the ON OFF operation button of the remote controller Fig 29 his starts the fan producing uncooled forced air with the 3 indicator lamps OPERATION lamp TIMER lamp and HIGH POWER lamp on the main unit blinking Fig 31 After 3 minutes the system shifts into cooling operation and cool air will start to be felt Cooling mode test run is unaffected by the room tempera ture 3 Press the ON OFF operation button of the remote controller again to stop the test run Fig 29 4 Finally press the ACL Reset button of the remote controller to release it from Test Run mode to return to normal mode Fig 29 e se and oP 1 will disappear from the remote controller clock display area Troubleshooting In the event that the green OPERATION lamp is blinking upon powering up the system an error condition exists In this case refer to the self diagnostics procedure which can be seen by opening the air intake grille IMPORTANT
134. sed when the unit is to be moved or before servicing the refrigerant circuit Pump Down Procedure Be sure to carry out pump down with the unit in Cooling mode 1 Connect the Lo side charging hose of the manifold valve to the service port on the wide tube service valve 20 Fig 32 S mL in Q N AN WWW External diameter of service port R410A 5 16 Fig 32 Using a hex wrench turn the narrow tube service valve clockwise all the way to close the service valve Be sure to confirm that the wide tube service valve is fully open Press the operation button and start cooling oper ation When the low pressure gauge reading falls to 14 2 to 7 1 psi 1 to 0 5 kg cm fully close the wide tube valve stem Then quickly stop the unit Disconnect all gauges and hoses and replace the valve caps as they were before Service Valve Connections a Temporary connection Screw in 3 5 turns by hand Fig 34 b To fasten the flare nuts apply specified torque as Table 8 and Fig 35 Table 8 Tube Dia Tightening Torque Approx 120 160 Ibs in 140 180 kgf cm Approx 300 360 Ibs in 340 420 kgf cm Approx 430 540 Ibs in 490 610 kgf cm 5 8 15 88 mm Approx 590 710 Ibs in 680 820 kgf cm 7T Remote Control Unit Installation Position Torque wrench Fig 35 The remote control unit can be operated from either a 9 non fixed position or a
135. side Min 10 25 cm Min 2 5 cm Min Air discharge y 8 20 cm Fig 4a CH1872 Air intake Min 4 10 Valve side 1 Min 10 25 cm 7 Min 2 5 cm Min Air discharge V 1 4 40 cm Fig 4b 4 AW WW 222 22 N A IN WW ARAINN NN N V N AN WW N K NW IN NV ANN vit AN ANN N AN NW MIMI WWW WW NW SW W WW IN NW N N NUN NN HZ M y NW N ANS f Fig 5 Exhaust fan 1 Heat source Obstacle above 9 Min _ Min 2 m Vl C 113 n lt S d lt _ Q 8 Ground Min 2 5 cm Air intake Obstacle above O Min Min 2 m C 9 2 lt amp He 9 Ground Min 4 10 cm Air intake V Cushion rubber 3 How to Install the Indoor Unit Hole in anchor Hole in plug Concrete Insert 3 1 Preparation for Suspending WWMM WEE This unit uses a drain pump Use a carpenter s level to check that the unit is level ow 3 2 Suspending the Indoor Unit I 1 Fix the suspension bolts securely in the ceiling using a Orar ocally purchas the method shown in the diagrams by attaching Fig 6 1 them to the ceiling support structure or by any other 23 5 8 600mm
136. surized gas and never use a refrigerant other than R410A Also do not use oxygen or any flammable gas b Evacuation e Use a solenoid valve installed vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption the valve will prevent the pump oil from flowing back e The equipment may be damaged if moisture remains in the tubing thus carry out the evacuation thoroughly e When using a vacuum pump with exhaust air volume more than 0 883 cu ft min and ultimate vacuum pressure rate of 50 micron Hg Standard time for evacuation 1 Detect leaks OK 2 Recover refrigerant OK 3 Weld leaking points OK 4 Check for sealing OK 5 Evacuation OK 6 Recharge Length of tubing Less than 33 ft 10 m More than 33 ft 10 m More than 10 minutes More than 15 minutes 6 Recharging e Recharge unit in the same manner explained on the previous page 5 Recharging 66 11 7 Charging Additional Refrigerant 11 7 1 When Tubes are Extended Observe the proper amount of refrigerant as stated in this service manual or the installation manual that came with the indoor unit Charge additional refrigerant in liquid state only Never charge additional refrigerant if refrigerant is leaking from the unit Follow instructions given in 11 6 In Case Refrigerant is Leaking and completely carry out repairs Only then should you recharge the refrigerant 11
137. t interfer ence between remote controllers when 2 indoor units are installed near each other The address is normally set to A To set a different address it is necessary to change the address on the second remote controller Once changed you cannot restore the original address setting of the air conditioner 1 Switch on the power source 2 Break the address setting tab marked A on the second remote controller to change the address Fig 37 When the tab is removed the address is automatically set to B Fig 38 3 Press and hold the remote controller HIGH POWER button and 1HR TIMER button Then press and hold the ACL Reset button with a pointed object such as the tip of a pen After 5 seconds release the ACL button first then release the HIGH POWER and 1HR TIMER but tons oP 1 Test Run appears blinking in the remote controller clock display area 4 Each time the 1HR TIMER button is pressed the display changes as shown below Press this but ton 2 times to change the display to oP 7 Address setting Fig 39 0 ur 0 X w mode Q 4 vey a D 3 Self diagnostic mode Q ur gt E 1 Address setting mode G oP 7 has now been selected for address setting Press the ON OFF operation button on the remote controller Fig 39 Check that the beep signal received sound is heard from the
138. ter draining the water to prevent the water leakage from the drain pan e Put a bucket etc under the drain cap and remove the drain cap to drain the water Fig 16 2 Refer to the installation instructions for recovery of refrigerant or removal of the power cable or tubing 7 3 6 Remove the main body lower section 1 Remove the 4 screws Fig 16 2 Remove the 2 screws Fig 17 3 Disconnect the connector CNO3 DCM 6P in the power box Fig 18 4 Lift the main body lower section and remove it from the main body upper section Screw Screw Drain cap Main body lower section Main body lower section Screw R Screw Fig 16 FR Main body lower section TAR ZENS SE e O Main body el Ok upper section c Fig 17 Fig 18 43 7 3 7 Remove the heat exchanger sensor 1 Remove the heat exchanger sensor from the sensor holder Fig 19 Heat exchanger sensor Holder Fig 19 7 3 8 Remove the drain pump and float switch 1 Remove the 2 screws Fig 20 2 Loosen the clamp and disconnect the drain hose from the drain pump Fig 20 3 Remove the drain pump from the main body upper section Fig 20 4 Remove a nut and remove the float switch Fig 21 Drain pump Float switch Drain hose Clamp Fig 20 Fig 21 44 7 3 9 Remove the turbo fan and fan motor 1 Remove a nut and remove the turbo fan Fig 22 2 Remove the 2 screws and 3 nuts and remove
139. ter washing with water allow it to dry and then remount it N caution Do not move the flap with your hands When using a footstool or the like be careful not to let it tip over Cleaning the main unit and remote control unit Wipe clean using a soft dry cloth e To remove stubborn dirt moisten a cloth in warm water no hotter than 104 F wring thoroughly and then wipe Ol 107 14 EG Air filter How to remove the air intake grille The air filter collects dust and other particles from the air and should 1 Open the air intake grille be cleaned once every 6 months If the filter gets blocked the efficiency of the air conditioner drops 2 Detach the safety cord from the frame remember to attach it again after cleaning or maintenance greatly 3 Hold on the air intake grille and pull it towards you to detach the NOTE two air intake grille hinges The frequency with which the filter should be cleaned depends on 4 Clean the grille gently using a soft sponge or the like Then dry it the environment in which th it i d xL Neutral detergent may be used to remove stubborn dirt Then rinse thoroughly with water and dry it How to remove the filter S EG 1 Slide the two latches of the air intake grille with your thumbs in the direction of the arrow to open the grille Air intake grille hinge Air intake grille Ceiling Air intake grille hinge panel Safety cord 2 Open the a
140. the air outlet of the outdoor unit This is dangerous because the fan is rotating at high speed Do not let children play with the air conditioner e Do not cool or heat the room too much If babies or invalids are present NAMES OF PARTS UNIT DISPLAY AND OPERATION BUTTON INDOOR UNIT INDOOR UNIT OPERATION button OPERATION lamp Air outlet 4 locations c TIMER lamp e HIGH POWER lamp N IMPORTANT Avoid using radio equipment such as mobile phone near within 4 ft 1 2 m the remote control receiver Some radio equipment Drain hose may cause malfunction of the unit Refrigerant tubes OUTDOOR UNIT If the trouble happens disconnect power and restart the air conditioner after a few minutes REMOTE This section picks up infrared signals from the CONTROL remote control unit transmitter receiver OPERATION When the remote control cannot be used button pressing this button enables heating and cooling operation Air outlet Each time this button is pressed the type of operation conducted is indicated by the changing color of the OPERATION lamp Press the button and select the lamp color that suits This illustration is based on the external view of a standard model your preference for operation Consequently the shape may differ from that of the air conditioner which you have selected Cooling Heating M operation operation lamp off This air condi
141. the fan motor Fig 23 Turbo fan 7 3 10 Remove the heat exchanger 1 Remove the 3 screws Fig 24 2 Remove the 3 screws Fig 25 3 Remove the heat exchanger from the main body upper section with the heat exchanger lifted Heat exchanger Screw Screw Main body upper section Fig 24 Fig 25 45 8 FUNCTIONS 8 1 Operation Functions Emergency operation Emergency operation is available when the remote controller malfunctions has been lost or otherwise cannot be used To operate the system press the OPERATION button which is also used as the receiver below the unit display Each time this button is pressed the OPERATION lamp changes color to indicate the type of operation Select the desired type of operation COOL GREEN HEAT RED d gt STOP Lamp Off tL The set temperature is 4 F 2 C below the detected room temperature in the case of cooling operation and 4 F 2 C above the room temperature in the case of heating operation The flap and fan speed settings are AUTO H AUTO cooling heating operation Selecting the operation mode When AUTO mode is selected the microprocessor calculates the difference between the set temperature and the room temperature and automatically switches to Cooling or Heating mode Room temp gt Set temp COOL Room temp lt Set temp HEAT As shown by the example in the figure below with AUTO cooling heating
142. the fixing screw of the terminal plate How to connect wiring to the terminal a For Indoor Unit 1 Cut the wire end with a cutting pliers then strip the insulation to expose the wire about 9 32 7 mm See the label Fig 9 near the terminal plate 2 Using a screwdriver loosen the terminal screw on the terminal plate 3 Insert the wire and tighten the terminal screw completely using a screwdriver b For Outdoor Unit For solid core wiring or F cable 1 Cut the wire end with a cutting pliers then strip the insulation to expose the solid wire about 15 16 25 mm Fig 10 2 Using a screwdriver remove the terminal screw s on the terminal plate 3 Using the pliers bend the solid wire to form a loop suitable for the terminal screw 4 Shape the loop wire properly place it on the terminal plate and fix it securely with the removed terminal screw using a screwdriver 13 Power wiring Locally purchased Clamping strap Earth screw SD A F Inter unit Conduit Fig 8 9 32 7 mm ACTUAL STRIP Sie Fig 9 E Solid wire Loop EM E N Insulation Fig 10 For stranded wiring 1 Cut the wire end with a cutting pliers then strip the insulation to expose the stranded wiring about 3 8 10 mm and tightly twist the wire ends Figs 11 and 12 2 Using a screwdriver remove the terminal screw s on the terminal plate 3 Using a
143. tional wired remote controller soon stops condenser coil Poor cooling or 1 Dirty or clogged air 1 Clean air filter to heating performance filter improve airflow Heat source or Eliminate heat many people in source if possible room Doors and or Shut them to keep windows are open the heat or cold out Obstacle near air Remove it to ensure intake or air good airflow discharge port Thermostat is set Set the temperature too high for cooling lower or higher or too low for heating Outdoor Consult your temperature is too dealer or try to use low for heating another heat appliance Clicking sound is In heating or cooling This is normal and heard from the air operation any plastic the sound will soon conditioner parts may expand or disappear shrink due to a sudden temperature change In this event a clicking sound may occur OPERATION lamp The use of cellular Turn off the power lights but outdoor unit phones near the air then restart the air will not run conditioner may cause conditioner after a disturbance to its while normal operation Consult your dealer TIMER lamp blinks FLOAT SWITCH is Contact service 3 sec interval and actived center air conditioner does not operate 16 Ol 107 16 EG APPENDIX INSTALLATION INSTRUCTIONS XHS1271 amp PNR X 1872 CH1271 XHS1872 amp PNR X 1872 CH1872 11 852 6 4190 477 00 0 2 S
144. tioner consists of an indoor unit and an outdoor unit green red You can control the air conditioner with the remote control unit t Air from the room is drawn into this section and passes through air filters which remove dust OPERATION This lamp lights when the system is in the lamp continuous AUTO red or green HEAT red Conditioned air is blown out of the air DRY orange COOL green and FAN green conditioner through the air outlet iode Remote The wireless remote control unit controls power The OPERATION lamp lights up red and orange Control Unit ON OFF operation mode selection alternately when the system is defrosting lemper Aure Tan Soto TIMER lamp This lamp lights when the system is being sweeping controlled by the timer Refrigerant indoor and outdoor units are connected by HIGH POWER _ This lamp lights during operation in the HIGH Tubes copper tubes through which refrigerant gas POWER mode flows SAP Drain Hose Moisture in the room condenses and drains off NOTE Bn through this hose Outdoor The outdoor unit contains the compressor fan The unit s display lamps are dimmed during operation in the NIGHT Condensing motor heat exchanger coil and other electrical SETBACK mode components Unit 4 O1 107 4 EG REMOTE CONTROL UNIT DISPLAY Displayed when transmitting data Displayed when indoor unit sensor is in use Displayed when setting temperat
145. tioner where excessively high heat generating objects are placed Avoid To protect the air conditioner from heavy corrosion avoid installing the outdoor unit where salty sea water can splash directly onto it or in sulphurous air near a spa Ol 107 3 EG ELECTRICAL REQUIREMENTS 1 All wiring must conform to the local electrical codes Consult your dealer or a qualified electrician for details 2 Each unit must be properly grounded with a ground or earth wire or through the supply wiring 3 Wiring must be done by a qualified electrician SAFETY INSTRUCTIONS e Read this Instruction Manual carefully before using this air conditioner If you still have any difficulties or problems consult your dealer for help e This air conditioner is designed to give you comfortable room conditions Use this only for its intended purpose as described in this Instruction Manual ANEN Never use or store gasoline or other flammable vapor or liquid near the air conditioner it is very dangerous This air conditioner has no ventilator for intaking fresh air from outdoors You must open doors or windows frequently when you use gas or oil heating appliances in the same room which consume a lot of oxygen from the air Otherwise there is a risk of suffocation in an extreme case Do not turn the air conditioner on and N off from the power mains switch Use the ON OFF operation button Do not stick anything into
146. trol This function moves a flap up and down in the air outlet directing air in a sweeping motion around the room and providing comfort in every corner CONTENTS Page FEAIDRES S us nicole i inu LM M DE UM I LEE MIO 2 PRODUCTANFORMATION EE 3 ALERT SYMBOLS eT pne 3 INSTAELATIOPEOGQATIQD eei ba e deut a a aa 3 ELECTRICAL REQUIREMENT O 3 SAFETYAINSTR GTIONS ca kava a a a ME a 3 NAMESOF PART S etat E a a 4 USING THE REMOTE CONTROL INIT Tiri a ee ee 8 OPERATION WITH THE REMOTE CONTROL UNIT essen 9 1 Automatic O peralloh pese 9 2 EN 9 3 Adjusund the FANS POCO 2 10 a 10 5 Night Setpa k ModE 10 6 IG POWER NOG 10 SPECIAL REMARK S deua 11 SE THNG THE TIMER cu n tua dfe ree 11 USING THE 1 HOUR OFF 13 TIPS PORE NERGY 2S AW Cras vanscecas deacaadaed 13 ADJUSTING THE AIRFLOW DIBEG TION RE VIN B ER Sen aeons 13 OPERATION WITHOUT THE REMOTE CONTROL UNIT eeeeeeeeeennneennn nnn 14 CARE AND O
147. tton once 2 Press the Advance Return a v button until AM 7 10 is displayed 3 Wait a few seconds and then the setting is complete 12 The timer indication is displayed and the present ON time is shown The timer indication blinks The time can be set in 10 minute increments Holding down the button advances the time rapidly in 10 minute increments The timer indication stops blinking and the present time is displayed 4 How to set daily ON OFF repeat timer Example To start operation at 7 10 am and stop the air conditioner at 11 00 am 10 30 pm 11 00 am Present time OFF D QW o V 1 Set the timer ON OFF times The present time 10 30 pm and are displayed as shown in 2 1 2 3 and 3 1 2 3 The ON OFF combination timer uses the current time as the reference and it is activated starting from whichever set time comes first e With the ON OFF combination timer the settings are repeated every day You can check the timer ON OFF times after you have set them by pressing the ON TIME and OFF TIME setting buttons To cancel a timer program e Press the CANCEL button When either an ON or OFF timer is to be canceled press the button corresponding to the timer whose program is to be canceled and then press the CANCEL button The airflow direction fan speed and temperature setting can be changed after a timer program has been set even when the unit
148. uced or operation is interrupted auto matically to control the electrical current for operation When the cause of the increase in electrical current is rectified the system will resume operation in the original mode Heating operation A e 4 way valve ON Peak current cut off trips Hz down 14 0 15 0 Frost sensing Electrical current setting for COOL operation is Defrost detection occurs in either of the following cases l s a The temperature of the heat exchanger remains at or below the L1 line for 3 minutes after the start of HEAT operation The temperature of the heat exchanger remains at or below the L2 line for 120 minutes after the start of HEAT operation Outdoor heat A exchanger temp gt Ambient temp Frosting area Heverse cycle defrosting operation e Compressor 1 minute after it is stopped compressor is ON Outdoor fan gt OFF e Indoor fan OFF e 4 way valve OFF e Operation lamp Repeatedly switches between red and orange illumination Releasing of defrosting e Outdoor heating exchanger temp is over 68 20 e Defrosting operation lasts 12 minutes maximum 2 minutes after it is stopped compressor is ON 4 way valve is ON Outdoor fan is ON NOTE If the air conditioner is turned off during the defrosting cycle it will continue defrosting and turn itself off after defrosting is completed 49 9 TROUBLESHOOTING 9 1 Precautions before Perform
149. ure Displayed when temperature is shown EG Displayed when setting timer Displayed when the time display is set to 12 hour time Symbols 1 Operation mode 4 Timer AVTO ak 24 hour clock with ON OFF Mau program Timer O HEAT ON aoin ON MILD OFF OFF D OO E A 1 hour OFF Timer FAN 5 NIGHT SETBACK RR 2 Fan speed 6 Confirmation Of transmission 7 Auto flap indication A Flap angle indication Sweep indication Automatic operation 3 Temperature setting 8 High power operation 60 86 F When set to 80 F temperature indication Ol 107 5 EG 5 REMOTE CONTROL UNIT Transmitter When you press the buttons on the remote control unit the mark appears in the display to transmit the setting changes to the receiver in the air conditioner Display Information on the operating conditions is displayed while the remote control unit is switched on If the unit is turned off FLAP setting and FAN SPEED setting are not displayed HIGH POWER button If this button is pressed during HEAT DRY COOL or FAN operation the unit operates at maximum output for 30 minutes regardless of 20 9 92962 the desi
150. utes have passed regardless of the indoor temperature when night setback was selected This enables you to save energy without sacrificing comfort This function is convenient when gentle cooling is needed 2 F 1 C Setting temperature erao La D Press the NIGHT 30 min 30min Time SETBACK button HEAT mode When the night setback mode is selected the air conditioner automatically lowers the temperature setting 4 F 2 C when 30 minutes have passed after the selection was made and then another 4 F 2 C after another 30 minutes have passed regardless of the indoor temperature when night setback was selected This enables you to save energy without sacrificing comfort This function is convenient when gentle heating is needed Setting 4 F 2 C temperature 4 F 2 C Press the NIGHT 30 min 30min time SETBACK button 8 2 Protective Functions During HEAT operation the temperature of the indoor heat exchanger is used to control the frequency and lessen the load on the compressor before the protective device is activated Indoor heat exchanger A Control start B Control end Indoor heat exchanger temperature F C Area Automatic capacity control When Point A has been exceeded the operation frequency is reduced by a certain proportion Area Frequency increase is prohibited At Point and below overload prevention is ended and control is the same as in the a area
151. w the instructions as mentioned in the sub section HOW TO INSTALL BATTERIES e If you do not use the remote control unit more than 1 month take out the batteries e Dispose of the used batteries at the designated location in compliance with the applicable local ordinances HOW TO USE THE REMOTE CONTROL UNIT When using the remote control unit always point the unit s transmitter head directly at the air conditioner s receiver Receiver Remote control fA Transmitter unit head REMOTE CONTROL UNIT INSTALLATION POSITION The remote control unit may be operated either from a non fixed position or from a wall mounted position To ensure that the air conditioner operates correctly DO NOT install the remote control unit in the following places DO NOT In direct sunlight Behind a curtain or other places where it is covered More than 26 ft 8 m away from the air conditioner n the path of the air conditioner s airstream e Where it may become extremely hot or cold Where it may be subject to electrical or magnetic noise Where there is an obstacle between the remote control unit and air conditioner since a check signal is sent from the remote control unit every 5 minutes MOUNTING THE REMOTE CONTROL UNIT Before mounting the remote control unit press the ON OFF operation button at the mounting location to make sure that the air conditioner operates from that locati
152. wall mounted position Be sure to tighten the flare nut To ensure that the air conditioner operates correctly do CAUTION using the d torque If the not install the remote control unit in the following places nut is over tightened refrigerant In direct sunlight leakage may occur Behind a curtain or other place where it is covered More than 26 8 m away from the air conditioner In the path of the air conditioner s airstream Where it may become extremely hot or cold Where it may be subject to electrical or magnetic interference Where there is an obstacle between the remote con trol unit and the air conditioner since a check signal is sent from the remote control unit every 5 minutes 7 1 Mounting on a Wall Before mounting the remote control unit press the ON OFF operation button at the mounting location to make sure that the air conditioner operates from that location The indoor unit should make a beeping sound to indicate that it has received the signal Rear side Remote control unit mount To prevent loss of the remote control F Mounting screws unit you can connect the remote 5 32 x 5 8 4 x 16 mm control unit to the mount by passing included a string through the remote control unit and attachment hole To take out the remote control unit pull it forward Fig 36 21 8 Address Switch 8 1 Address Setting of the Remote Control Unit The address can be set in order to preven
153. with a power supply disconnect and circuit breaker for overcurrent protection provided in the exclu Sive line 3 To prevent possible hazards due to insulation failure the unit must be grounded 4 Each wiring connection must be done tightly and in accordance with the wiring system diagram Wrong wiring may cause the unit to misoperate or become damaged 5 Do not allow wiring to touch the refrigerant tubing compressor or any moving parts of the fan 6 Unauthorized changes in the internal wiring can be very dangerous The manu facturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes 3 8 Recommended Wire Length and Diameter Regulations on wiring diameter differ from locality to locality For field wiring require ments please refer to your local electrical codes Carefully observe these regula tions when carrying out the installation Table 4 lists recommended wire lengths and diameters for power supply systems Refer to the wiring system diagram Fig 7a or Fig 7b for the meaning of A B and C in Table 4 Refer to your local codes or in the absence of local codes see the National Electric Code ANSI NFPA70 11 Table 4 sure comply with local codes running the wire from the indoor unit to the outdoor unit size of wire and wiring method etc Each wire must be firmly connected No wire should
Download Pdf Manuals
Related Search
Related Contents
Modular In-Car Entertainment - Toyota Milwaukee 6177-20 Saw User Manual IFU - Wagner GmbH Planification Avaya one-X Deskphone Value Edition 1600 Series User's Manual Trevi MDV 6300 BT 取扱説明書 TMPV7528_7506 EVA BOARD CUBLOC Manual - Comfile Technology Copyright © All rights reserved.
Failed to retrieve file