Marley W400 Cooling Tower User Manual
Contents
1. to 8 C below the design cold water temperature When a reducing ambient wet bulb permits the tower to reach that target cold water temperature level further reductions in the wet bulb temperature permit manipulation of fan speeds or operation to maintain that temperature level Single speed fans can be cycled on and off for cold water temperature control with the steps of control depending upon the number of fan cells in the tower Two speed motors offer twice as many control steps with the added bonus that half speed which produces half of the normal airflow through the tower requires less than 20 of the full speed power requirement If your tower is equipped with a Marley Motor Control Center please refer to the appropriate User Manuals IL 2 AN Caution A Warning 10 Excessive fan cycling may shorten the motor s expected service life On fans 20 feet 6 meter diameter and smaller allow for 4 to 5 starts per hour On larger fans 2 or 3 starts per hour may be the limit On two speed motors each low speed start and each high speed start count as one start Variable frequency drives of course provide the ultimate in both tempera ture control and energy management and can be easily retrofitted to your system Please discuss this with your Marley representative If your tower is equipped with a Marley VFD drive please refer to the appropriate Owners Manual Unit Maintenance Always shut off electrical power to the t
2. Internal rot as the name implies occurs inside the wood members For this reason it is more difficult to detect than is soft rot Internal rot is most commonly found in the heavier members in the plenum areas of the tower One of the best methods of inspection for internal rot is sounding with hammer blows Members which have internal rot sound dead while non rotted members have a ring or live sound Areas which sound dead can be probed with a screwdriver or other pointed tool to verify the presence of internal rot The strength of a member with soft rot is not seriously affected However if internal rot is discovered the infected members should be replaced SPX has personnel on its staff experienced in all aspects of wood deteriora tion and preservative treatment In addition several Marley publications are available which give detailed information on the subject of wood deteriora tion and treatment Contact the nearest Marley sales office or representative for more information about wood inspection services and for copies of the publications Cooling Tower Cleaning Any evaporative type cooling tower must be thoroughly cleaned on a regular basis to minimize the growth of bacteria including Legionella Pneumophilla to avoid the risk of sickness or death Service personnel must wear proper personal protective equipment during decontamination Do NOT attempt any service unless the fan motor is locked out Op
3. Marley Class W400 Cooling Tower User Manual 92 1312D aM Marley Tower Schematic MOTOR Fa PVC DRIFT CORRUGATED ELIMINATORS FRP CASING AIR INLET GUIDE ja IF REQD AIR FLOW ANCHORAGE CONCRETE BASIN TRANSVESE CROSS SECTION A Warning AN Caution Note Contents General ner dr ten ne 4 Before Stari passi dish een adds iv edie delesh der reres seri 4 Initial Starting de sisi 5 Routine Starting Procedure sisi 6 OP TATION A ren ie eee annees ni mar 6 Temperature Control and Energy Management 9 Malhiten an CO ics inst vd dani od da vd ve dit 10 CUE AMIN Ge nccsssrav v s st et ndo n z o s v b r d s v dbe Sb si sdo d SH sea 12 Water Ir aim nt ss ennemies nine 13 Seasonal Shutdown Instructions sn 17 Spare PASSES a annuaire Mini ire 18 ACCESS ONES nee eee ira re dt dt ee ear vehte 18 Inspection and Maintenance Schedule enen 19 TroubleShOOtIN GJ ni isa snco voto sn E en nan ete 20 DATE dya v ves u o i e n iaa ndo t n sit doni d t 21 Inspection CheGkliSts isssci v s v s Er d T r s El v s v eee vie deine 22 The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product Indicates presence of a hazard which can cause severe personal injury death or substantial property
4. damage if ignored Indicates presence of a hazard which will or can cause personal injury or property damage if ignored Indicates special instructions on installation operation or main tenance vhich are important but not related to personal injury hazaras A Warning AN Caution General A cooling tower like any heat exchanger exchanges all heat imposed upon it from one fluid to another fluid For a cooling tower heat from the water is put into the air The plant process replenishes the heat to the water typically at another heat exchanger such as a condenser A cooling tower differs from many heat exchangers in that heat is transferred in two forms sensible and latent heat As heat is transferred from the water the air temperature increases sensible and the air s water content or humidity also increases latent As the heat load inlet air wet bulb temperature or airflow on a cooling tower changes the cooling tower will respond by finding a new equilibrium with the process The cooling tower will still dissipate all the heat from the process but at new water temperatures The cooling tower cold water temperature is the supply water temperature to the condenser and changes in the cold water temperature usually affect efficiency of the plant output Although the reduced cold water temperatures that result from maximum fan power utilization are usually beneficial to plant output the amount of fan power affects the cost
5. of running the cooling tower As these variables interact on a cooling tower the operator must find the proper trade off between these opposing forces These instructions will assist in obtaining efficient long life from Marley cooling equipment Direct questions concerning tower operation and maintenance to your Marley sales office or representative Always include your tower serial number when writing for information or ordering parts Look for this number on the nameplate on the tower endwall access door Before Start up Among other sources outbreaks of Legionnaires disease have reportedly been traced to cooling towers Maintenance procedures that prevent amplification and dissemination of Legionella and other airborne bacteria should be formulated and implemented BEFORE systems are operated and continued reqularly thereafter to avoid the risk of sickness or death SAFETY Temporary safety barricades should be placed around any exposed openings in the operating or non operating tower safety harnesses for fall protection should be worn and used by personnel where appropriate and other safety precautions should be taken in compliance with appropriate OSHA regulations and standards Note AN Caution CLEANING Nevw installations should be cleaned and treated with biocides by a water treatment expert before startup Remove any dirt and trash which has accumulated in the cold water basin Remove any sediment from the basin sump an
6. required to maintain different concen trations with various cooling ranges Number of Concentrations sreo 73 s 25 te n ofo Multipliers are based on drift of 0 02 of the circulating water rate EXAMPLE 7000 GPM 441 7 L s circulating rate 18 F 10 C cooling range To maintain 4 concentrations the required blowdown is 0 458 or 00458 times 7000 GPM 441 7 L s which is 32 1 GPM 2 02 L s If tower is operated at 4 concentrations circulating water will contain four times as much dissolved solid as the makeup water assuming none of the solids form scale or are otherwise removed from the system The use of corrosion and scale inhibitors is strongly recommended CHEMICAL TREATMENT In some cases chemical treatment of the cir culating water is not required if adequate blowdown is maintained In most cases however chemical treatment is required to prevent scale formation and corrosion Sulfuric acid or one of the polyphosphates is most generally used to control calcium carbonate scale Various proprietary materials containing phosphates or other compounds are available for corrosion control When IL 2 13 AN Caution 14 companies should be obtained water treatment chemicals are required the services of reliable water treating When handling any hazardous materials read the material safety data sheet for proper personal protective equipment and handling procedures PREFERRED COOLING TOWER WATER CON
7. 3 months Each month drain water condensate from the lowest point of the Geareducer and its oil system Check oil level and add oil if necessary Operate Geareducer to recoat all interior surfaces with oil Before start up drain water condensate and check oil level Add oil if necessary Refer to Geareducer User Manual for maintenance and lubrication instruc tions Shutdown for 3 months or longer Ifthe motors have space heaters operate mechanical equipment one hour each month Space heaters should be energized anytime motor is not operating If the motors do not have space heaters operate mechanical equipment one hour each week At start up operate mechanical equipment one hour or until oil is warm then shut the equipment down Drain the oil and refill with new oil Refer to Geareducer Manual for instruction on changing oil Refer to Marley Downtime Instruction Manual for downtime of 6 months or longer Electric Motors Do not start motor without determining that there will be no inter ference with free rotation of the fan drive Refer to Marley Electric Motor Service Manual If shutdown period is longer than seasonal contact your Marley sales office or representative for additional information 17 18 Spare Parts SPX manufactures and maintains a stock of common replacement parts for all cooling tower mechanical equipment Shipment of these parts are normally made within ten days after an orderis received If emergen
8. DITION LIMITS FOR STANDARD CONSTRUCTION MATERIALS Maximum Water Temperature Langelier Saturation Index MPA Kalinity perce E Silica a Manganese Oil and Grease Sulfides Ammonia Chlorine Organic solvents Total Dissolved Solids 6 5 to 9 0 120 F 48 9 C 0 0 to 1 0 100 to 500 ppm as CaCO 150 ppm as SiO 3 ppm 0 1 ppm 10 ppm for splash filled towers None allowed for film filled towers 1 ppm 50 ppm if copper alloys are present 1 ppm free residual intermittently shock or 0 4 ppm continuously none allowed over 5000 ppm can affect thermal performance and be detrimental to wood in certain areas of the tower Cations Calcium 800 ppm as CaCO Magnesium depends on pH and Silica level Sodium e no limit Anions Chlorides 750 ppm as NaCl 455 ppm as CF S lfates 800 ppm as CaCO Nitrates 300 ppm nutrient for bacteria Carbonates Bicarbonates 300 ppm as CaCO maximum for wood Biological Bacteria Film Type Fills Aerobic Bacteria Plate Count Less than 10 000 CFU mL Less than 1 000 000 CFU mL when TSS lt 25 ppm and less than 100 000 CFU mL when TSS gt 25 ppm Total Suspended Solids Film Type Fill Splash Type Fill Mis
9. Li Low check again soon Li Oil Condition Good J Contains Water LJ Contains Metal J Contains Sludge J Oil Used type Seals Back Lash Fan Shaft End Play Any Unusual Noises No LJ Yes U Action Required Drive Shafts Manufacturer Material TT oo Fans Manufacturer Fixed Pitch LJ Adjustable Pitch LJ Diameter Number of Blades Blade Material Hub Material Hub Cover Material Blade Assembly Hardware A Blade Tip Clearance min max Vibration Level Fan Cylinder Height Mech Eqpt Support Mat l Oil Fill amp Drain Lines Oil Level Sight Glass Vibration Limit Switches Other Components Motor Manufacturer Name Plate Data hp RPM Phase Cycle Volts F L Amps Frame SF Special Info Last Lubrication Date Grease Used Type Any Unusual Noise No LJ Yes U Action Required Any Unusual Vibration No LJ Yes U Action Required Any Unusual Heat Build up No LJ Yes QI Action Required 23 SPX COOLING TECHNOLOGIES 7401 WEST 129 STREET OVERLAND PARK KANSAS 66213 UNITED STATES 913 664 7400 spxcooling spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2009 SPX Cooling Technologies Inc Printed in USA Manual 92 1312D
10. ance with the following schedule Inspect for General Condition Repair for Safe Use Semi annually As Required Ladders Stairways Walkways Handrails Covers Decks and Access Doors Davits Derricks and Hoists Semi annually As Required 21 Inspection Checklist Date Inspected Inspected By Owner Location Owner s Tower Designation Tower Manufacturer Model No Serial No Process Served by Tower Operation Continuous Intermittent L Seasonal LI Design Conditions GPM HW F CW F WB F Number of Fan Cells Condition 1 Good 2 Keep an eye onit 3 Needs immediate attention Comments Structure Casing Material Structural Material Fan Deck Material Stairway Material Ladder Material Handrails Material Interior Walkway Material Cold Water Basin Material Water Distribution System Distribution System Header Material Manifold Material Branch Arms lli Nozzles Orifice diameter inches Heat Transfer System Fill Inlet Face of Fill Eliminators Use this space to list specific items needing attention 22 Inspection Checklist Condition 1 Good 2 Keep an eye onit 3 Needs immediate attention Mechanical Equipment ATEIST comms Gear Drive Units Manufacturer Model Ratio Oil Level Full LJ Add Immediately
11. by which to adjust the level of thermal performance to suit the requirements of the load See Temperature Control and Energy Management page 9 If two speed motors are used allow a time delay of a minimum of 20 seconds after de energizing the high speed winding and be fore energizing the low speed winding Tremendous stresses are placed on driven machinery and motor unless the motor is allowed to slow to low speed RPM or less before the low speed winding is energized HOT WATER DISTRIBUTION SYSTEM Hot water from the process flows through an inlet to each cell which supplies a distribution header and a system of branch arms and nozzles Each distribution header pipe may be equipped with a vent standpipe to minimize water hammer to maintain a slightly pressurized water distribution system and to provide vacuum release at pump shutdown If an Amertap condenser tube cleaning system is part of plant equipment care should be taken during operation to backwash the strainer section only after the sponge rubber cleaning balls are removed from the system by trapping them in the collector Balls that are allowed to enter the cooling tower supply piping may clog some of the nozzles although the generous flow paths through the nozzles make this unlikely However balls escaping the nozzles will accumulate on top of the fill ultimately causing unequal water distribution that will affect thermal performance The top of the fill should be frequently ch
12. cellaneous Solids Other nutrients GENERAL RULE Less than 25 ppm preferred bacteria plate count is particularly important if TSS is above 25 ppm No specific limit For film fill avoid fibrous greasy fatty or tarry contamination For film fill avoid fats glycols alcohols sugars and phosphates Film type fill should not be used for certain applications in steel plants paper mills or food processing operations Unless unusual water conditions have been anticipated and compensated for by the use of premium materials in the construction of the tower then it is the owner operator s responsibility to maintain water conditions within the limits tabled above by the appropriate use of blowdown chemical treatment filtration cleaning etc Slime a gelatinous bacteria growth and algae a green or brown plant growth may grow in the cooling tower or heat exchangers Their presence can inter fere with cooling efficiencies Proprietary compounds are available from water treating companies for the control of slime and or algae however compounds which contain copper are not recommended The Langelier index calcium carbonate saturation index has proven to be an effective tool in predicting the aggressiveness of cooling tower water toward concrete The Langelier index relates the methyl orange alkalinity the calcium hardness the total solids the pH value and the temperature of the water From
13. clean and the water distribution uniform to obtain continued maximum cooling capacity See Warning note page 12 Do not allow excessive deposits of scale or algae to build up on the fill or eliminators Keep the nozzles free of debris to assure correct distribution and cooling of water Uniform water distribution over the entire fill plan area is vital to the efficient operation of a film filled cooling tower The capacity of a tower to cool water to a given cold water temperature varies with the wet bulb temperature and the heat load on the tower As the wet bulb temperature drops the cold water temperature also drops However the cold water temperature does not drop as much as the wet bulb temperature Wet bulb temperature is the temperature indicated by the wet bulb thermometer of a psychrometer AN Caution AN Caution A tower does not control the heat load For a given heat load the quantity of water circulated determines the cooling range The hot and cold water tem peratures increase with higher heat loads Cooling range is the temperature difference between the hot water coming into the cooling tower and the cold water leaving the tower FAN DRIVE Air is caused to move through the tower by the operation of electric motor driven fans At full speed these fans are designed and pitched to move the amount of air required to accomplish the design thermal perfor mance Proper utilization of these fans provides the operator ameans
14. cy service is neces sary contact the local Marley sales office or representative for assistance To prevent prolonged shutdown periods in case of damage to the mechanical equipment it is suggested that the follovving parts be carried in the ovvner s stock e One fan assembly e One Geareducer assembly e One driveshaft assembly One motor Be sure to furnish the tower serial number when ordering parts Accessories Marley accessories are designed for improved maintenance access safety component handling and the general customizing of the tower to suit your process These accessories include stairways walkways externalandinternal derricks davits motor control centers page 9 as well as variable frequency drives page 10 and other retrofittable control devices Please discuss your needs with your Marley sales representative Inspection and Maintenance Schedule General Recommendations More frequent inspection and mainte nance may be desirable Fan Motor Drive Shaft and Guards Geareducer Cold Water Basin Float Valve Structural Members Casing and Louvers Fan Cylinder Stairs Ladders Walkway Doors Handrails Davits Derricks Hoists dd nd sd dd dd to Son NO RD NM OD TF WON gt N O Inspect for clogging Check for unusual noise or vibration Inspect keys keyways and set screws Make sure vents are open Lubricate grease Check oil seals C
15. d screens Use a water hose to flush cold water basins If you are restarting or recommissioning a previously used tower see Warning note on page 12 OPERATE WATER SYSTEM Complete steps 1 thru 4 under Initial Start ing Procedure below Circulate water over the tower continuously for several days before starting the mechanical equipment and putting the tower into continuous operation Do not circulate water over the tower in freezing weather without a heat load See caution page 6 Initial Starting Procedure 1 Fill the cold water basin and circulating water system to a level 1 2 13 mm below the overflow 2 Completely open all flow control valves in the circulating water system 3 Prime and start the circulating water pumps one at a time Increase the flow of circulating water gradually to design water rate to avoid surges or water hammer which could damage the distribution piping 4 When flow has stabilized at or near the design rate adjust water makeup to maintain the level that the water has pumped down to in the cold water basin See Cold Water Collecting Basin on page 8 This should coincide reasonably with the recommended operating water level indicated on the Marley project drawings 5 Start the fan After 30 minutes operating time to permit Geareducer oil to come up to operating temperature check motor load with watt meter or take operating volt and ampere readings and calculate motor hp Refer to Marley Fan User Manual f
16. ecked until such time as the operational sequence of the Amertap system assures that no balls enter the cooling tower distribution system FILL VVater leaving the nozzles is distributed uniformly over the fill plan area The water flows through the fill coating each fill sheet to maximize water surface exposure to the air being moved by the fans IL 2 DRIFT ELIMINATORS Air leaving the fill passes through a level of drift eliminators covering the entire plan area of the tower The purpose of these drift eliminators is to minimize the amount of water that is caused to exit the tower by the velocity of the moving airstream COLD WATER COLLECTING BASIN Water leaving the fill falls into the cold water basin that forms the base of the tower The normal water depth in wood steel or fiberglass basins is 5 to 8 inches 127 to 203 mm while in a concrete basin the normal water level is typically 12 inches 305 mm below the curb Adjust the makeup water supply to maintain this water level Maintain sufficient water depth to prevent cavitation WINTER OPERATION During periods of low temperature operation 35 to 40 F 2 C to 4 C or below ice will form on the relatively dry parts of the tower that are in contact with the incoming air Primarily this includes the air inlet and adjacent structural framing Ice forming characteristics on any given tower will vary depending on veloc ity and direction of wind circulating water rate and heat
17. erators of evaporative cooling equipment such as water cooling towers should follow maintenance programs which will reduce to an absolute minimum the opportunity for bacteriological contamination Public Health Service officials have recommended that good housekeeping procedures be followed such as regular inspections for concentrations of dirt scale and algae periodic flushing and cleaning and the following of acomplete water treatment program including biocidal treatment Note Visual inspection should take place at least once a week during the operating season Periodic flushing and cleaning should be done at least twice a year Nozzles louvers drift eliminators and easily accessible fill surfaces should be flushed by use of a moderate pressure water nozzle being careful not to cause physical damage A reliable water treatment program should be installed and maintained VVater Treatment BLOWDOWN Blowdown or bleed off is the continuous removal of a por tion of the water from the circulating system It is used to prevent dissolved solids from concentrating to the point where they will form scale The amount of blowdown required depends upon the cooling range design hot water temperature minus design cold water temperature and the composition of the makeup water water added to the system to compensate for losses by blowdown evaporation and drift The following table shows the minimum amount of blowdown percent of flow
18. heck operating oil level Check static oil level Check oil for water and sludge Change oil Check fan blade tip clearance Check water level Check for leakage Inspect general condition Tighten loose bolts Clean Repaint Rebalance Inspect repair for safe use Inspect and repair before each use Drift Eliminators z Fill Distribution System and Nozzles Suction Screen U 02 ao 02 02 OJEZ ISJO JZ ao DIDNI vjylolojaz lt i DIDID xjalvujalojo D daily W weekly M monthly Q quarterly S semi annually Y yearly R as required 19 Troubleshooting Trouble Motor Will Not Start Cause Remedy Power not available at motor terminals Check power at starter Correct any bad connections between the control apparatus and the motor e Check starter contacts and control circuit Reset overloads close contacts reset tripped switches or replace failed control switches If power is not on all leads at starter make sure overload and short circuit devices are in proper condition Wrong connections Check motor and control connections against wiring diagrams Low voltage Check nameplate voltage against power supply Check voltage at motor terminals O
19. icantly on a daily basis and considerably from season to season As the wet bulb temperature reduces the tower becomes capable of producing colder and colder water or it becomes capable of producing a given cold water temperature at reduced airflow through the tower These characteristics are the opposing forces referred to under General on page 4 MAXIMIZING TOWER PERFORMANCE f your process is one which benefits from the coldest possible water that is if colder water allows you to produce more product or allows you to operate your system at significantly lower cost then continuous full speed operation of the fan s may be your best mode of operation In this mode of operation concern for the cold water temperature level would be limited to the potential for the tower to form ice during freezing weather See Caution page 6 and WINTER OPERATION page 8 Although the 70 F 21 C cold water temperature indicated on page 6 is appropriate for cold weather start up and operation acceptable temperatures during full op eration in spring summer and fall may be appreciably lower perhaps as low as 50 F 10 C or less Refer to your performance curves for expected tower cold water temperatures at varying flow rates ranges and wet bulb temperatures MINIMIZING TOWER ENERGY USE Most processes gain no operating or production benefits from water temperatures below a certain level and for many that level may be only 10 F to 15 F 5
20. load Excessive ice formation may be controlled by regulating air and water flow through the tower by one or more of the following procedures 1 Shut the fan down This reduces the cooling rate to a minimum and increases the quantity of warm water at the air inlet to a maximum However normal fan off operation can cause reverse airflow due to the aspirating effect of the water distribution spray system Although this reverse flow of air can be beneficial in deicing the inlet structure it may contribute to water blowout and therefore must be carefully monitored For automatic operation a timer switch can be provided to shut the fan down for a few minutes each hour 2 If the tower has two speed motors reduce the cooling rate by operating the fans at half speed forward 3 With no heat load on the circulating water icing cannot be controlled ef fectively by air control Towers must not be operated with reduced water rate and or no heat load during freezing weather If a bypass directly into the cold water basin is used all water must be bypassed so none is circulated over the tower Design of a bypass arrangement must include consideration of water impact effect on tower components Consult your Marley salesrepresentative Reverse operation of fans is not recommended See FAN DRIVE page 7 for fan speed change precautions AN Caution Temperature Control and Energy Management The wet bulb temperature of the ambient air varies signif
21. or instructions If it is necessary to pitch fans to pull correct contract horsepower measure results when circulating design water rate at design hot water temperature Horsepower will change with air density Lock out all electrical service before entering fan area AN Caution Routine Starting Procedure After periods of routine shutdown the following restarting procedure should be followed 1 Start the circulating water pump s Increase the flow of circulating water gradually to design water rate to avoid surges or water hammer which could damage the distribution piping Circulating cold water over a tower in freezing weather will cause ice to form which may cause damage to the fill system Water should be bypassed until the heat load causes its temperature to rise above 70 F 21 C at which time it may be directed over the tower Also towers must not be operated with reduced water rate and or no heat load during freezing weather If a bypass is used do not modulate Bypass design must be reviewed by SPX 2 Start the fan s On multicell towers only as many fans should be started as are needed to produce the desired cold water temperature If the tower is equipped with two speed motors fans may be progressively started at half speed increasing to full speed as necessary to maintain the desired cold water temperature See Temperature Control and Energy Man agement page 9 Operation TOWER PERFORMANCE Keep the tower
22. or must keep the circulating water clean by treatment screening or filtering to avoid the possibility of fill clogging Sea water if used will typically present increased clogging problems due to suspended solids and or biological growth if the water is not properly filtered and treated The dissolved ions do not present unusual clogging problems Contributors to the clogging of fill are trash and debris algae slime and scale with the effects of scale often being worsened by the presence of suspended muds All of these can be controlled with some combination of water treatment screening and filtration and it is the owner s responsibility to institute a program of water treatment and maintenance that will minimize their impact See Water Treatment page 13 TOWER FRAMEWORK Keep framework bolts tight Pay particular atten tion to bolts in the mechanical equipment supports Do not pull washers into the wood DRIVE SHAFT Check drive shaft alignment and condition of couplings every six months See the Drive Shaft User Manual for correcting misalignment balancing or replacing parts ELECTRIC MOTOR Lubricate and maintain each electric motor in accordance with the manufacturer s instructions If repair work is necessary contact the nearest representative of the motor manufacturer See Warranty Section of Marley Electric Motor User Manual FAN Inspect fan blade surfaces every six months For detailed maintenance information refe
23. ower fan motor prior to performing any inspections that may involve physical contact with the mechanical or electrical equipment in or on the tower Lock out and tag out any electrical switches to prevent others from turning the power back on Service personnel must wear proper personal protective clothing and equipment Well maintained equipment gives the best operating results and the least maintenance cost A regular inspection schedule is recommended to insure effective safe operation of the cooling tower Use the schedule on page 19 to obtain continuously good performance with the least tower maintenance See Inspection Checklist pages 22 and 23 in this manual Keep a continuous lubrication and maintenance record for each cooling tower Conduct regular inspection and repair of personnel safety items items 19 and 20 in Table on page 19 Maintaining a record of this is especially important For a supply of check list forms contact your Marley sales office or representative HOT WATER DISTRIBUTION SYSTEM Keep the circulating water and distribution system piping and nozzles clean and free of sand dirt algae and scale See Caution regarding cleaning on page 12 Algae and scale may clog nozzles eliminators fill and piping and may collect on the equipment served thus reducing its performance FILL Clean free flowing unobstructed fill is vital to the continued efficient operation and performance of a cooling tower The owner operat
24. pen circuit in motor winding Check stator windings for open circuits Motor or fan drive stuck Disconnect motor from load and check motor and Geareducer for cause of problem Rotor defectve Look for broken bars or rings Unusual Motor Noise Motor running single phase Stop motor and attempt to start it Motor will not start if single phased Check wiring controls and motor Motor leads connected incorrectly Check motor connections against wiring diagram on motor Ball bearings Check lubrication Replace bad bearings Electrical unbalance Check voltages and currents of all three lines Correct if required Air gap not uniform Check and correct bracket fits or bearing Rotor unbalance Rebalance Cooling fan hitting guard Reinstall or replace fan Motor Runs Hot Wrong voltage or unbalanced voltage Check voltage and current of all three lines against nameplate values Overload Check fan blade pitch See Fan Service Manual Check for drag in fan drive train as from damaged bearings Wrong motor RPM Check nameplate against power supply Check RPM of motor and gear ratio Bearings overgreased Remove grease reliefs Run motor up to speed to purge excessive grease Rotor rubs stator bore If not poor machining replace worn bearing Wrong lubricant in bearings Change to proper lubricant See motor manufacturer s instructions One phase open Stop motor and attempt to start it Motor will not start if single phased Check wiring controls and motor Poor ven
25. r to Marley Fan User Manual GEAREDUCER Make weekly and monthly oil checks Refer to the Geareducer User Manual for detailed maintenance instructions PAINTING Periodically clean and if necessary recoat any chipped or dam aged paint to prevent corrosion COLD WATER COLLECTING BASIN lnspect collecting basin occasion ally for cracks leaks and spalling and repair if necessary Maintain a positive Langelier index in your circulating water See Water Treatment page 13 Minor leaks may appear in wood basins when starting with a dry basin but these generally disappear after the wood becomes soaked Inspect steel basins for corrosion Recoat as necessary Keep cold water outlets clean and free of debris Makeup and circulating water controls must operate freely and maintain the desired water quantity in the system IL 2 11 A Warning 12 COOLING TOWER WOOD DETERIORATION Cooling tower wood is pressure treated to help prevent decay However after several years of service some members may develop decay Routine inspections should be made to assure that decay is discovered before it is heavily advanced Decay is commonly of two very general types soft rot and internal rot Soft rot is easier to detect because it is almost always on the surface of wood members It makes the surface soft and weak and in its more advanced stages the decayed wood can be easily removed This type of rot occurs primarily in the flooded areas of the tower
26. s when a new tower is put into operation This type of foaming generally subsides after a relatively short pe riod of operation Persistent foaming can be caused by the concentrations of certain combinations of dissolved solids or by contamination of the circulating water with foam causing compounds This type of foaming can sometimes be minimized by increasing the blowdown but in some cases foam depressant chemicals must be added to the system Foam depressants are available from a number of chemical companies WATER DISCOLORATION Woods contain some water soluble substances and these commonly discolor the circulating water on a new tower This dis coloration is not harmful to any of the components in the system and can be ignored However a combination of foaming and discolored water can result in staining of adjacent structures if foam is picked up by air being pulled through the tower and discharged out the fan cylinders Avoid operation of fans until the foaming is controlled A Warning AN Caution Seasonal Shutdown Instructions TOWER Drain all tower piping During shutdown clean the tower and make any necessary repairs Apply protective coating as required to all metal parts Particular attention should be given to mechanical equipment supports drive shaft and drive shaft guards Visually inspect for concrete deterioration See Warning note on page 12 regarding tower cleaning MECHANICAL EQUIPMENT Shutdown for less than
27. these values it is possible to calculate the index and predict the corrosive tendencies of the tower water toward concrete An explanation and method of calculating the Langelier index can be found in all books on water treatment Maintaining a positive Langelier index provides excellent protection of concrete Data For Rapid Calculation of Saturation Index Saturation Index pH actual 9 3 A B C D A B c D Total Value Water Value Calcium Value M O Value Solids to Temp to Hardness to Alkalinity to ppm Apply F Apply ppm Apply ppm Apply 50 300 0 1 32 34 2 6 10 11 0 6 10 11 1 0 400 1000 0 2 36 42 2 5 1 ESS 0 7 12 13 V 44 48 2 4 14 17 0 8 14 17 12 50 56 23 18 22 0 9 18 22 eS 58 62 29 23 27 1 0 23 27 1 4 64 70 2 28 34 1 1 28 34 ii 72 80 2 0 35 43 12 35 43 1 6 82 88 1 9 44 55 1 8 44 55 lee 90 98 1 8 56 69 1 4 56 69 1 8 100 110 17 70 87 1 5 70 87 1 9 11258122 1 6 88 110 1 6 88 110 2 0 124 132 US 111 138 1 7 111 138 25 134 146 1 4 139 174 1 8 139 174 DD 148 160 J S 175 220 1 9 175 220 DIS 162 178 152 230 270 2 0 230 270 2 4 280 340 2 1 280 340 2 5 350 430 22 350 430 2 6 440 550 23 440 550 ONT 560 690 2 4 560 690 2 8 700 870 25 700 870 2 9 880 1000 2 6 880 1000 3 0 Based on Langelier formulas Larson Buswell residue temperature adjustments and arranged by Eskel Nordell 15 16 FOAMING Heavy foaming sometimes occur
28. tilation Clean motor and check ventilation openings Allow ample ventilation around motor Winding fault Check with Ohmmeter Bent motor shaft Straighten or replace shaft Insufficient grease Remove plugs and regrease bearings Deterioration of grease or foreign Flush bearings and relubricate material in grease Bearings damaged Replace bearings Motor Does Not Come Up Incorrect fan blade pitch See Fan Service Manual for blade pitching instructions T d z E o Spes Voltage too low at motor terminals Check transformer and setting of taps Use higher voltage on because of line drop transformer terminals or reduce loads Increase wire size or reduce inertia Broken Rotor bars Look for cracks near the rings A new rotor may be required 20 Have motor service person check motor Troubleshooting Trouble Cause Remedy Wrong Rotation Motor Wrong sequence of phases Switch any two of the three motor leads Geareducer Noise Geareducer bearings If new see if noise disappears after one week of operation Drain flush and refill Geareducer See Geareducer Service Manual If still noisy replace Gears Replace worn or damaged gears Unusual Fan Drive Loose bolts and cap screws Tighten all bolts and cap screws on all mechanical equipment Vibration and supports Unbalanced drive shaft or worn Make sure motor and Geareducer shafts are in proper couplings alignment and match marks properl
29. y matched Repair or replace worn couplings Rebalance drive shaft by adding or removing weights from balancing cap screws See Drive Shaft Service Manual Fan Make certain all blades are as far from center of fan as safety devices permit All blades must be pitched the same See Fan Service Manual Clean off deposit build up on blades Worn Geareducer bearings Replace bearings as necessary Unbalanced motor Disconnect load and operate motor If motor still vibrates rebalance motor Bent Geareducer shaft Check fan and pinion shaft with dial indicator Replace if necessary Fan Noise Loose fan hub cover Tighten hub cover fasteners Blade rubbing inside of fan cylinder Adjust cylinder to provide blade tip clearance Loose bolts in blade clamps Check and tighten if necessary Safety The tower has been designed to provide a safe working environment while either operating or shut down The ultimate responsibility for safety rests with the Operator and Owner When flow to the tower is shut off or when portions of the tower require maintenance temporary safety barricades may be required around openings Other safety precau tions such as safety harnesses lockout tagout and confined space entry etc should be utilized where appropriate for compliance with OSHA regulations and standards and good safety practices See Warning page 12 Routine periodic maintenance must be performed on all personnel access and material handling accessories in accord