Home
        Install Instructions
         Contents
1.  ANALYSIS  Remedy    GUIDE INDICATE     POSSIBLE CAUSE     SYMPTOM  System will not start  Compressor will not start   fan runs  Compressor and Condenser Fan will not start  Evaporator fan will not start  Condenser fan will not start  Compressor runs   goes off on overload  Compressor cycles on overload  System runs continuously   little cooling  Too cool and then too warm  Not cool enough on warm days  Certain areas to cool others to warm  Compressor is noisy  Low suction pressure  Low head pressure  High suction pressure  High head pressure    Test Voltage   Impact Fuse Size  amp  Type   Inspect Connection   Tighten   Test Circuits with Ohmmeter   Test Continuity of Overloads   Test Continuity of Thermostat and Wiring  Check Control Circuit with Voltmeter  Test Capacitor   Test Continuity of Overload   Test Motor Windings   Use Test Cord   Test Continuity of Coil and Contacts  Test Control Circuit with Voltmeter  Test Voltage   Repair or Replace   Test Motor Windings   Check Resistance of Anticipator   Test For Leaks  Add Refrigerant  Replace Restricted Part   Replace Line   Replace Line   Speed Blower  Check Duct Static Pressure  Reduce Blower Speed   Recover Part of Charge   Recover Charge  Evacuate  Recharge  Remove Obstruction to Air Flow  Check Windows  Doors  Vent Fans  Etc   Relocate Thermostat   Readjust Air Volume Dampers  Refigure Cooling Load   Replace Compressor   Test Compressor Efficiency   Test Compressor Efficiency   Reset and Test Control   Test Voltage   R
2.  a mechanical seal  separating the sides of the system       Close pump valve and hold vacuum for 10 minutes  Typi   cally pressure will rise during this period     5000       4500       4000               LEAK S   PRESENT    3500       3000       2500       VACUUM IN MICRONS    2000    CONDENSIBLES OR SMALL  LEAK PRESENT    1500       1000        NO LEAKS  NO CONDENSIBLES    500       MINUTES    If the pressure rises to 1000 microns or less and remains  steady the system is considered leak free  proceed to  startup     e  f pressure rises above 1000 microns but holds steady  below 2000 microns  moisture and or noncondensibles  may be present or the system may have a small leak   Return to step 2  If the same result is encountered check  for leaks as previously indicated and repair as necessary  then repeat evacuation     If pressure rises above 2000 microns  a leak is present   Check for leaks as previously indicated and repair as nec   essary then repeat evacuation     Electrical Connections    AA WARNING    HIGH VOLTAGE     Disconnect ALL power before servicing   Multiple power sources may be present   Failure to do so may cause property damage   personal injury or death due to electric shock   Wiring must conform with NEC or CEC and all  local codes  Undersized wires could cause  poor equipment performance  equipment damage  or fire     AA WARNING    To avoid the risk of fire or equipment damage  use  copper conductors     NOTICE         Units with reciprocating compresso
3.  between tubing and foundation  Any gap  between foundation or wall and refrigerant lines should be filled  with a pliable silicon based caulk  RTV or a vibration damping  material  Avoid suspending refrigerant tubing from joists and  studs with rigid wire or straps that would come in contact with  the tubing  Use an insulated or suspension type hanger  Keep  both lines separate and always insulate the suction line     These sizes are suitable for line lengths of 74 feet or less  Ifa  run of more than fifty feet is required  refer to Remote Cooling  Service Manual  or TP 106 Long Line Set Application R 22  or  TP 107 Long Line Set Application R 410A or contact your dis   tributor for assistance     REFRIGERANT LINE LENGTH  Ft     Line Diameter  In  OD     Cond  Unit    Tons Liq     __Suct_   __Suct_    Suct    3 8    3 8  3 8    7 8  required for full ratings      1 1 8  required for full ratings       Lines greater than 74 feet in length or vertical elevation changes more than 50 feet  refer to the Remote Cooling Service Manual or contact your distributor for  assistance                   Liquid Line    Suction Line       Mounting the evaporator coil above the  condensing unit will require an inverted  loop in the suction line adjacent or near  the connection to the evaporator  The top  of the loop must be slightly higher than the  top of the coil                                      Mounting the condensing unit above   the evaporator coil will require oil traps  at equal in
4. CONDENSING UNIT    AIR CONDITIONING  INSTALLATION  amp  SERVICE REFERENCE    Important Safety Instructions    The following symbols and labels are used throughout this  manual to indicate immediate or potential safety hazards  Itis  the owner s and installers responsibility to read and comply  with all safety information and instructions accompanying these  symbols  Failure to heed safety information increases the risk  of personal injury  property damage  and or product damage     AA WARNING    HIGH VOLTAGE     Disconnect ALL power before servicing   Multiple power sources may be present   Failure to do so may cause property damage   personal injury or death     AA WARNING    ONLY individuals meeting the requirements of an     Entry Level Technician    as specified by the Air  Conditioning and Refrigeration Institute  ARI  may use  this information  Attempting to install or repair this  unit without such background may result in product  damage  personal injury  or death                  Shipping Inspection   Always keep the unit upright  laying the unit on its side or top  may cause equipment damage  Shipping damage  and subse   quent investigation is the responsibility of the carrier  Verify  the model number  specifications  electrical characteristics   and accessories are correct prior to installation  The distribu   tor or manufacturer will not accept claims from dealers for trans   portation damage or installation of incorrectly shipped units     Codes  amp  Regulation
5. ed when installing the unit  Vibration  absorbing pads or springs can be installed between the con   densing unit legs or frame and the roof mounting assembly to  reduce noise vibration     Safe Refrigerant Handling    While these items will not cover every conceivable situation   they should serve as a useful guide     AA WARNING  To avoid cere injury  explosion or death  practice  safe handling of refrigerants     AA WARNING    Refrigerants are heavier than air  They can  push out   the oxygen in your lungs or in any enclosed space To    avoid possible difficulty in breathing or death     e Never purge refrigerant into an enclosed room or  space  By law  all refrigerants must be reclaimed       If an indoor leak is suspected  throughly ventilate the  area before beginning work      Liquid refrigerant can be very cold  To avoid possible  frostbite or blindness  avoid contact and wear gloves  and goggles  If liquid refrigerant does contact your  skin or eyes  seek medical help immediately      Always follow EPA regulations  Never burn refrig    erant  as poisonous gas will be produced     AA WARNING    To avoid possible explosion       Never apply flame or steam to a refrigerant cylinder   If you must heat a cylinder for faster charging   partially immerse it in warm water    e Never fill a cylinder more than 80  full of liquid re   frigerant      Never add anything other than R 22 to an R 22 cy   linder or R 410A to an R 410A cylinder  The service  equipment used must be lis
6. eplace Valve   Replace Valve   Replace Valve   Replace Valve          Loose Connection  Shorted or Broken Wires          Faulty Thermostat   Faulty Transformer   Shorted or Open Capacitor  Internal Compressor Overload Open  Shorted or Grounded Compressor  Compressor Stuck   Faulty Compressor Contactor  Faulty Fan Relay   Open Control Circuit   Low Voltage   Faulty Evaporator Fan Motor  Shorted or Grounded Fan Motor  Improper Cooling Anticipator  Shortage or Refrigerant  Restricted Liquid Line   Undersized Liquid Line  Undersized Suction Line   Not Enough Air across Indoor Coil  Too Much Air across Indoor Coil  Overcharge of Refrigerant  Noncondensibles   Recirculation of Condensing Air  Infiltration of Outdoor Air  Improperly Located Thermostat  Air Flow Unbalanced   System Undersized   Broken Internal Parts   Broken Valves   Inefficient Compressor   High Pressure Control Open  Unbalanced Power  3PH   Wrong Type Expansion Valve  Expansion Valve Restricted  Oversized Expansion Valve  Undersized Expansion Valve  Expansion Valve Bulb Loose Tighten Bulb Bracket    Inoperative Expansion Valve Check Valve Operation  Loose Hold down Bolts Tighten Bolts    For detailed service information refer to the Remote Condensing Unit Service manual                                                                                                                                         
7. hart packaged with indoor unit     Leak Testing  Nitrogen or Nitrogen Traced     AA WARNING    To avoid the risk of fire or explosion  never use  oxygen  high pressure air or flammable gases for leak  testing of a refrigeration system     AA WARNING    To avoid possible explosion  the line from the  nitrogen cylinder must include a pressure regulator  and a pressure relief valve  The pressure relief valve  must be set to open at no more than 150 psig                   Pressure test the system using dry nitrogen and soapy water  to locate leaks  If you wish to use a leak detector  charge the  system to 10 psi using the appropriate refrigerant then use  nitrogen to finish charging the system to working pressure then  apply the detector to suspect areas  If leaks are found  repair  them  After repair  repeat the pressure test  If no leaks exist   proceed to system evacuation     System Evacuation    Condensing unit liquid and suction valves are closed to contain  the charge within the unit  The unit is shipped with the valve  stems closed and caps installed  Do not open valves until  the system is evacuated     AA WARNING    REFRIGERANT UNDER PRESSURE     Failure to follow proper procedures may cause  property damage  personal injury or death          1  Connect the vacuum pump with 250 micron capability to  the service valves     2  Evacuate the system to 250 microns or less using suc   tion and liquid service valves  Using both valves is nec   essary aS some compressors create
8. ier while brazing  wrap the component  with a wet rag  or use a thermal heat trap compound as  recommended by the compound manufacturer  Use a  brazing alloy of 2  minimum silver content  Do not use  flux     1  The ends of the refrigerant lines must be cut square  de   burred  cleaned  and be round and free from nicks or dents   Any other condition increases the chance of a refrigerant  leak     2     Sweep    the refrigerant line with nitrogen or inert gas dur   ing brazing to prevent the formation of copper oxide in     side the refrigerant lines  The POE oils used in R 410A  applications will clean any copper oxide present from the  inside of the refrigerant lines and spread it throughout the  system  This may cause a blockage or failure of the me   tering device     3  After brazing  quench the joints with water or a wet cloth  to prevent overheating of the service valve     4  Ensure the filter drier paint finish is intact after brazing  If  the paint of the steel filter drier has been burned or chipped   repaint or treat with a rust preventative  This is especially  important on suction line filter driers which are continu   ally wet when the unit is operating     NOTE  Be careful not to kink or dent refrigerant lines  Kinked  or dented lines will cause poor performance or compressor  damage     Do NOT make final refrigerant line connection until plugs are  removed from refrigerant tubing     NOTE  Before brazing  verify indoor piston size by checking  the piston kit c
9. ow  adjust TXV to  7 to 9   F superheat  then check subcooling     NOTE  To adjust superheat  turn the valve stem clock     wise to increase and counter clockwise to decrease     c  If subcooling and superheat are high  adjust TXV b  If subcooling is low and superheat is high  add charge  valve to 7 to 9   F superheat  then check subcooling  to raise subcooling to 5 to 7   F then check super    d  If subcooling is high and superheat is low  adjust heat   TXV valve to 7 to 9   F superheat and remove charge c  If subcooling and superheat are high  adjust TXV  to lower the subcooling to 7   2  F  valve to 7 to 9   F superheat  then check subcooling   d  If subcooling is high and superheat is low  adjust    NOTE  Do NOT adjust the charge based on suction pres   sure unless there is a gross undercharge     TXV valve to 7 to 9   F superheat and remove charge  to lower the subcooling to 5 to 7   F     4  Disconnect manifold set  installation is complete     Subcooling Formula   Sat  Liquid Temp    Liquid Line Temp  NOTE  Do NOT adjust the charge based on suction pres     sure unless there is a gross undercharge   4  Disconnect manifold set  installation is complete   Subcooling Formula   Sat  Liquid Temp    Liquid Line Temp     NOTICE    Units with reciprocating compressors and non bleed TXV   s        require a Hard Start Kit     Troubleshooting Information    System  Operating  Pressures    Unsatisfactory  Cooling    Complaint No Cooling    POSSIBLE CAUSE    Test Method    DOTS IN
10. peed Application       Two Speed Application   Run the remote on low stage cooling for 10 minutes until refrig   erant pressures stabilize  Follow the guidelines and methods  below to check unit operation and ensure that the refrigerant  charge is within limits  Charge the unit on low stage     1  Purge gauge lines  Connect service gauge manifold to  base valve service ports  Run system at least 10 min   utes to allow pressure to stabilize     2  Temporarily install thermometer on liquid  small  line near  liquid line service valve with adequate contact and insu   late for best possible reading     1  Purge gauge lines  Connect service gauge manifold to  base valve service ports     2  Temporarily install thermometer on liquid  small  line near  liquid line service valve with adequate contact and insu   late for best possible reading     3  Check subcooling and superheat  Systems with TXV ap   plication should have a subcooling of 7   2   F and super   heat of 7 to 9   F    a  If subcooling and superheat are low  adjust TXV to  7 to 9   F superheat  then check subcooling     3  Check subcooling and superheat  Systems with TXV ap   plication should have a subcooling of 5 to 7   F and super     NOTE  To adjust superheat  turn the valve stem clock   wise to increase and counter clockwise to decrease    b  If subcooling is low and superheat is high  add  charge to raise subcooling to 7   2  F then check  superheat     heat of 7 to 9   F     a     If subcooling and superheat are l
11. r higher  Set the room  thermostat to COOL  fan switch to AUTO  and set the tem   perature control well below room temperature     After system has stabilized per startup instructions  check  subcooling and superheat as detailed in the following section     Fixed Orifice    AQ CAUTION    To prevent personal injury  carefully connect and disconnect  manifold gauge hoses  Escaping liquid refrigerant can cause  burns  Do not vent refrigerant into the atmosphere  Recover  all refrigerant during system repair and before final unit   disposal           1  Purge gauge lines  Connect service gauge manifold to  base valve service ports  Run system at least 10 minutes  to allow pressure to stabilize     2  Temporarily install thermometer on suction  large  line  near suction line service valve with adequate contact and  insulate for best possible reading      Refer to the superheat table provided for proper system    superheat  Add charge to lower superheat or recover  charge to raise superheat     SYSTEM SUPERHEAT    Return Air Temperature   F Drybulb     Ambient Condenser  Inlet Temp    F Drybulb        4  Disconnect manifold set  installation is complete     Superheat Formula   Suct  Line Temp    Sat  Suct  Temp     SATURATED SUCTION PRESSURE  TEMPERATURE CHART  SATURATED SUCTION  SUCTION PRESSURE TEMPERATURE   F    R 410A    SATURATED LIQUID PRESSURE  TEMPERATURE CHART  LIQUID PRESSURE SATURATED LIQUID    TEMPERATURE   F  R 410A     gt  o   e j a    Expansion Valve System  Single S
12. rs and non bleed TXV   s  require a Hard Start Kit     The condensing unit rating plate lists pertinent electrical data  necessary for proper electrical service and overcurrent protec                      4    tion  Wires should be sized to limit voltage drop to 2   max    from the main breaker or fuse panel to the condensing unit   Consult the NEC  CEC  and all local codes to determine the  correct wire gauge and length    Local codes often require a disconnect switch located near the  unit  do not install the switch on the unit  Refer to the installa   tion instructions supplied with the indoor furnace air handler for  specific wiring connections and indoor unit configuration  Like   wise  consult the instructions packaged with the thermostat  for mounting and location information     Overcurrent Protection    The following overcurrent protection devices are approved for  use     e Time delay fuses  e HACR type circuit breakers    These devices have sufficient time delay to permit the motor   compressor to start and accelerate its load     Three Phase Compressor Rotation    AA CAUTION  Use care when handling scroll compressors  Dome temp   eratures could be hot     Three phase scrolls are power phase dependent and can com   press in more than one direction     Verify proper rotation for three phase compressors by ensuring  the suction pressure drops and discharge pressure rises when  the compressor is energized  NOTE  When operated in re   verse  a three phase scroll compre
13. s    This product is designed and manufactured to comply with  national codes  Installation in accordance with such codes and   or prevailing local codes regulations is the responsibility of the  installer  The manufacturer assumes no responsibility for equip   ment installed in violation of any codes or regulations    The United States Environmental Protection Agency  EPA   has issued various regulations regarding the introduc   tion and disposal of refrigerants  Failure to follow these  regulations may harm the environment and can lead to  the imposition of substantial fines  Should you have any  questions please contact the local office of the EPA     If replacing a condensing unit or air handler  the system must  be manufacturer approved and Air Conditioning and Refrigera   tion Institute  ARI  matched  NOTE  Installation of unmatched  systems is strongly discouraged     Operating the unit in a structure that is not complete  either as    Bee    Goodman Manufacturing Company  L P     2005 2006  2550 North Loop West  Suite 400  Houston  TX 77092  www goodmanmfg com  or  www amana hac com  P N 10 258D Date  October 2006    part of new construction or renovation  will void the warranty   Installation Clearances    Special consideration must be given to location of the con   densing unit s  in regard to structures  obstructions  other units   and any all other factors that may interfere with air circulation   Where possible  the top of the unit should be completely unob   str
14. ssors is noisier and its cur   rent draw substantially reduced compared to marked values     To correct  disconnect power and switch any two leads at the  unit contactor and re observe     High Voltage Connections    Route power supply and ground wires through the high voltage  port and terminate in accordance with the wiring diagram pro   vided inside the control panel cover     Low Voltage Connections    Condensing unit control wiring requires 24 Volt minimum  25VA  service from the indoor transformer  Low voltage wiring for two   stage units depends on the thermostat used and the number  of control wires between the indoor unit and the condensing  unit  Route control wires through the low voltage port and ter   minate in accordance with the wiring diagram provided inside  the control panel cover        Se    Thermostat        74   Single Stage Heating  I 5 yo   with           Single Stage Coolin     w             FURNACE OR      AIR HANDLER                      KOR ANS     f We  Rob    cae KF A ao  REMOTE    Single Stage Thermostat  with Two Low Voltage Wires to Remote    NOTE  For two stage condensing units  refer to the Installation  Instructions supplied with the variable speed indoor units for  field wiring connections     Thermostat  Two Stage Heating  with    Two Stage Cooling                             FURNACE OR  AIR HANDLER    oo NI ON N   NM N Loa ay  o j YLovyi  v2     Be     jf R    wi j  w2   PENN   ae oS DP wf ea Se et SCA                      OD UNIT  Two S
15. tage Thermostat  with Three Low Voltage Wires to Remote    System Start Up    Adequate refrigerant charge for a matching evaporator and 15  feet lineset is supplied with the condensing unit  NOTE  If lineset  exceeds 15 feet in length  refrigerant should be added at  6  ounces per foot of liquid line     Open each valve only until the top of the stem is 1 8    from the  retainer  To avoid loss of refrigerant  do not apply pressure to  the retainer     1  Break vacuum by fully opening liquid and suction base  valves       Set thermostat to call for cooling  Check indoor and out   door fan operation and allow system to stabilize for 10  minutes for fixed orifices and 20 minutes for expansion  valves     Charge Verification    AA WARNING    REFRIGERANT UNDER PRESSURE      Do not overcharge system with refrigerant      Do not operate unit in a vacuum or at negative pres   sure    Failure to follow proper procedures may cause   property damage  personal injury or death             5    AQ CAUTION    Use refrigerant certified to ARI standards  Used refrigerant  may cause compressor damage  and will void the warranty   Most portable machines cannot clean used refrigerant to  meet ARI standards           NOTICE  Violation of EPA regulations may result in fines or other  penalties     AQ CAUTION    Operating the compressor with the suction valve closed will  void the warranty and cause serious compressor damage          Final Charge Adjustment    The outdoor temperature must be 60 F o
16. ted or certified for the  type of refrigerant used       Store cylinders in a cool  dry place  Never use a cy    linder as a platform or a roller     AA WARNING    To avoid possible explosion  use only returnable  not   disposable  service cylinders when removing refrig    erant from a system      Ensure the cylinder is free of damage which could  lead to a leak or explosion       Ensure the hydrostatic test date does not exceed  5 years      Ensure the pressure rating meets or exceeds 400  Ibs     When in doubt  do not use cylinder                                                            Refrigerant Lines    AX CAUTION    The compressor POE oil for R 410A units is extremely  susceptible to moisture absorption and could cause   compressor failure  Do not leave system open to atmos   phere any longer than necessary for installation           Use only refrigerant grade  dehydrated and sealed  copper tub   ing to connect the condensing unit with the indoor evaporator   After cutting the tubing  install plugs to keep refrigerant tubing  clean and dry prior to and during installation  Tubing should  always be cut square keeping ends round and free from burrs   Clean the tubing to prevent contamination    Do NOT let refrigerant lines come in direct contact with plumb   ing  ductwork  floor joists  wall studs  floors  and walls  When  running refrigerant lines through a foundation or wall  openings  should allow for sound and vibration absorbing material to be  placed or installed
17. tervals along the suction line   Install 1 oil trap for a height difference of  15 25 feet between indoor and outdoor  units  Install 2 oil traps for a difference of  26 50 feet  3 for 51 100 feet  and 4 for  101 150 feet                    Insulation is necessary to prevent condensation from forming  and dropping from the suction line  Armflex  or satisfactory  equivalent  with 3 8    min  wall thickness is recommended  In  severe conditions  hot  high humidity areas  1 2    insulation may  be required  Insulation must be installed in a manner which  protects tubing from damage and contamination     Where possible  drain as much residual compressor oil from  existing systems  lines  and traps  pay close attention to low  areas where oil may collect  NOTE  If changing refrigerant  types  ensure the indoor coil and metering device is compat   ible with the type of refrigerant being used  otherwise  the in   door coil must be replaced     Burying Refrigerant Lines    If burying refrigerant lines can not be avoided  use the following  checklist     1  Insulate liquid and suction lines separately     2  Enclose all underground portions of the refrigerant lines  in waterproof material  conduit or pipe  sealing the ends  where tubing enters exits the enclosure     3  If the lines must pass under or through a concrete slab   ensure lines are adequately protected and sealed     Refrigerant Line Connections    IMPORTANT  To avoid overheating the service valve  TXV  valve  or filter dr
18. ucted  however  if vertical conditions require placement be   neath an obstruction there should be a minimum of 60  inches between the top of the unit and the obstruction s    The specified dimensions meet requirements for air circulation  only  Consult all appropriate regulatory codes prior to deter   mining final clearances    Another important consideration in selecting a location for the  unit s  is the angle to obstructions  Either side adjacent the  valves can be placed toward the structure provided the side  away from the structure maintains minimum service clearance   Corner installations are strongly discouraged                                               Pp A   B  C   AA    to  fo aor fo ae     10  10  18    This unit can be located at ground floor level or on flat roofs  At  ground floor level  the unit must be on a solid  level foundation  that will not shift or settle  To reduce the possibility of sound  transmission  the foundation slab should not be in contact with  or be an integral part of the building foundation  Ensure the  foundation is sufficient to support the unit  A concrete slab  raised above ground level provides a suitable base        Rooftop Installations    If it is necessary to install this unit on a roof structure  ensure  the roof structure can support the weight and that proper con   sideration is given to the weather tight integrity of the roof  Since  the unit can vibrate during operation  sound vibration transmis   sion should be consider
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
40V Brushless String Trimmer  Philips HD3902 MicroClean Filter  Manual de Informação e Lazer  GARAGE DOOR OPENER WITH AssureLink  2.04MB  Severin KA 4156    Copyright © All rights reserved. 
   Failed to retrieve file