        TC-24 Initial Settings Service Manual
         Contents
1.   General Equipment    appears    2  To change the icons  touch the Icon Selection button  labeled   in the figure   and select the desired one    3  Touch the General equipment operation setting button  labeled     in the figure  to allow or disallow  monitor only  the user to  start stop the connected equipment via the TC 24A     In batch and on individual group Units can be turned on or off either collectively or by group from the TC 24A   On individual group Only certain groups of units can be turned on or off from the TC 24A        No operations  Monitor only  Units cannot be turned on or off from the TC 24A     4  Touch the General equipment display setting button  labeled    in the figure  and choose between the following ON OFF  Status display options on the HOME screen   Output status to the general equipment    or    Input status from the general  equipment       5  Touch the Unit selection button  labeled    in the figure   On the popup window that appears  check the address and the  contact number of the DIDO controller  PAC Y G66DCA  to which the general equipment is connected    6  After all the settings have been made  touch the Save button on the Groups screen                      D  etahtcaneaninae oe      rs     7  O  ak             le     eee a        Group setting screen Model selection screen     2  3  Interlocked settings between indoor units and ventilation units  LOSSNAY and OA processing units     To interlock the ON OFF status of the ventilation unit
2.   to run a test on the group     Test Run screen    Touch the OFF ON  button to starta  test run  Touch the Test Run button to  Stop the test run    These buttons are active only for the  units Ee Support the uk run function    2  operation mee   cing mode er Meng mae   Operation mode  Cooling mode and the Heating mode   The pipe temperature of the indoor unit     3  Pipe temperature   with the lowest address in a given  group will appear     D Advanced Touch this button for advanced  settings settings     TA    A Indoor Indoor air temperature will appear   temperature    Use the up down arrows to select the  indoor unit whose pipe temperature you  want to check    The pipe temperature of the indoor unit  C  Pipe temperature   whose address is shown on the screen  will appear     ge The remaining time for the test run will  Remaining time  appear      3  During the test run  verify that air conditioned air is blowing out of the supply air outlet    4  After checking for normal operation of each unit  stop the units through TC 24A or the local remote controllers     Refer to the indoor unit installation manual for the detailed information about test run     OFF ON  Test  Run          Unit address  up down arrows       Maintenance    Touch the Maintenance button       1  To view the System information  Touch  System View  button on the Maintenance screen to view a list of equipments connected to the same refrigerant system       Only the ones whose startup procedures have been 
3.  The temperature set range for each option is shown below   Standard   67  F  19  C  to 83  F  28  C   Low   46  F  8  C  to 872F  30  C      Manual   Can be set to any arbitrary range between 46  F  8  C  and  87  F  302C   2  When    Manual    is selected  set the lower and upper temperature limits  using the up and down arrows  labeled   in the figure         Clock Setting Signal  1  Touch the Clock Setting Signal button  labeled   in the figure  to send or not  send the clock synchronization signals to other controllers and units       f the Clock Setting Signal is set to    ON     signals to synchronize the current  time will periodically be sent to all system controllers and remote  controllers that have a built in clock function      MA remote controllers that are connected to Mr  SLIM   units will not  synchronize the clock and date  Also  the clock and date synchronization  may not operate on certain CITY MULTI units        Saving the Settings    1  Touch the Save button to save the settings      2  2  Group Settings  Enter the group settings on the Groups screen  air conditioning units  general equipment  and their respective group names  that  are connected to TC 24A   Touch Initial S ettings Groups button   prey  on the Service Menu screen  and then touch Groups button      a   on the Initial Settings Groups screen to access the Groups screen  The DIDO controller  PAC Y G66DCA  by Mitsubishi    Electric is required to control general equipments      General equipm
4. a MITSUBISHI ELECTRIC    Air conditioner Control System    Touch Controller TC 24A  Initial Setting Manual    This Initial Setting Manual contains information about the settings to be made at the time of installation  Please read the  instructions carefully and make the settings accordingly  Refer to the Installation Manual for how to install the TC 24A Touch  Controller  and refer to the air conditioning unit installation manuals for how to connect the controller cable to the air conditioning  units  or how to install the air conditioning units  Please remember to give all manuals to the end users after installation Is    complete        TC 24A Touch Controller    Collective ON OFF  button with LED    ee    i tk  MEE    Touch panel    HOLD button with LED    a    FLE        p          hen  SETBACK button with LED        reat THEI STALLS Wo oad  we TEE    PowerLED       List of functions available under the    Service menu       M NET address Sets the M NET address for the TC 24A  pA    Remote controller Selects the type of controllers to prohibit access  from  remote controllers only  access or both remote controllers and system controllers      Access to ON OFF  Mode  Set Temp  and Filter Reset     External input mode __  Selects the external input mode  PA  Initial Settings   Filter sign Displays or Suppresses the Filter sign on the HOME screen  za  Basic System Includes or excludes Dry mode as an option for the operation mode  O4    Serene e anie Selects the settable temp
5. cess the page to paste the copied group name onto  and touch the    Paste button   Fa     Group Settings for air conditioning units    1  Touch the Model selection button  labeled   in the figure  to access the  Model Selection screen  Touch the Model selection button  labeled    in  the figure  so that    Air Conditioners    or    LOSSNAY    appears on the screen    2  Touch the Unit selection button  labeled    in the figure  On the popup  window that appears  check the address of the units to be included    3  To assign a remote controller to a group  check the address of controller on  the popup window that appears when the Remote controller selection  button  labeled    in the figure  is touched      Up to two remote controllers can be assigned to each group   Group  settings do not need to be made for the MA remote controllers     4  To assign a system controller to a group  check the address of the controller  on the popup window that appears when the System controller selection  button  labeled    in the figure  is touched      Up to four remote and system controllers combined can be assigned to  each group    5  After all the settings have been made  touch the Save button           pe   e ee ree  f i    l             m F    Model selection screen    Group Settings for General Equipment    1  Touch the Model selection button  labeled   in the figure  to access the Model selection screen   Touch the Model selection button  labeled   in the figure  a few times so that  
6. e  Unable to read the SD card  appears  check to make sure that the SD memory card is properly inserted     If a message  Update file was not found  appears  check to make sure the SD memory card contains the updated program   3  Following the instructions on the screen  remove the cover on the controller by unscrewing the screws at the bottom  turn  DIP switch 4 to ON  and then touch the OK button     If the message  The DIP switch 4 is set to OFF   appears  check to make sure that the DIP switch 4 is turned to ON   The DIP switch is located at the left bottom of the controller under the cover   4  Touch the OK button on the confirmation screen   5  Touch the OK button on the popup message to begin the update process         Note  Software updates will take approximately five minutes  Do not remove the SD card or switch off the power while an    update is in progress  If the power is turned off during the update process  the program may be lost and the system  will not be able to start        6  The lit LEDs on the three buttons  HOLD  SETBACK  and Collective ON OFF  will indicate a successful completion of the  update  While update Is in progress  the LEDs on the HOLD and SETBACK buttons will alternately blink     Consult your dealer if the update is not completed in 10 minutes    7  After the update has been completed  turn the DIP switch 4 to OFF to restart the TC 24A  When the initialization screen  appears  check that the software version that appears at the bottom righ
7. ents  Refer to the types of equipments such as fans and lighting fixtures that are connected to the contacts   Each contact of general equipment counts as one unit  and up to 24 units  indoor units and LOSSNAY units combined  or their  equivalent can be connected to each TC 24A      Sample system     TC 24A M NET   201     DIDO controller        ee  001    DIDO controller indicates Mitsubishi    T    Electric PAC Y G66DCA     1   2    DIDO controller can control up to six H i   equipments with contact points    Fan  lighting   I Fan  lighting     Fan  lighting    Fan  lighting     Fan  lighting     Fan  lighting        M NET Address or other or other or other or other or other or other        Contact Point No  Nequipments     equipments     equipments     equipments     equipments     equipments    e I  l unit    Up to 16 units can be assigned to each group  Indoor units  LOSSNAY units  and general equipment cannot be combined in one  group  General equipment groups cannot include remote controller or system controllers  Touch Page turn button  le Il EJ   to  turn the pages  and follow the directions below to make the settings for each group     Group Name   1  Touch the Group Name Input button  labeled   in the figure   and enter the   group name in the screen   up to 16 characters maximum    2  The name of a group can be copied and pasted into another group name field   Access the name of the group to be copied using the arrow buttons  and  touch the Copy button   E      Ac
8. erature range   rican 9     Standard  67  F  19  C  to 83  F  28  C   Low  46  F  8  C  to   F  30  C    Manual  Settable to any arbitrary range between 46  F  8  C  and 87  F  30  C      Sends or does not send the clock synchronization ena once a day to the  Time notification  controllers and units   Eroni Makes the group settings for the indoor units  LOSSNAY units  DIDO 5  Initial Settings P controllers  PAC Y G66DCA   remote controllers  and sub system controllers   Groups Interlocked operation   Enters the interlock settings between indoor and LOSSNAY units  6  Batch deletion Deletes all group and interlock settings collectively  O6      System view Displays the information about the indoor units connected to each outdoor unit   Maintenance   Malfunction log Stores the latest errors   up to 50    S oftware update Updates software   Test run Test run Runs a test on the connected air conditioning units        TC 24A Screen Configurations     1  Screen sequence and Service menu configuration    HOME screen    GRID  zoom out  view GRID  zoom in  view    LIST view GROUP view       Touch E   or    EH 1 Touch    a1     Main Menu screen    Touch     E Touch  EJ     Login Page screen  1    Touch M       Touch  a Touch R   Touch a    Service Menu screen  Service Menu    Touch  ER      oe wi Initial settings   Basic system  Touch   ksa    ial Initial settings   Groups    T       Touch h      Password Change screen    Button name  TI     Service Menu Touch Ez  Password Change z Inte
9. figure   to switch between    SC RC    and    RC only        Select    SC RC    to prohibit access  from both the system controllers and  remote controllers  and select    RC only    to prohibit access from only the remote controllers     Access to ON OFF  Mode  Set Temp  and Filter R eset        External Input Mode  1  Press the External Input setting button  labeled   in the figure  to select  between    Not used       Emergency Stop  Level signal         ON OFF  Level  Signal      and    ON OFF Prohibit P ermit  Pulse signal         Refer to the Installation Manual for detailed information on how to connect  the TC 24A to external devices        Filter Sign Display  1  Press the Filter Sign Display button  labeled   in the figure  to switch   between ON and OFF      Setting this item to OFF will remove the Filter Sign from the HOME screen  display   This item can be set to OFF if there is no need for the sign to appear on the  HOME screen  for example  in cases where filters are regularly changed  regardless of the filter sign status     Dry Mode  1  Press the Dry Mode Setting button  labeled   in the figure  to switch between   Used  and    Not Used         f this item is set to    Not Used     the Dry mode will be unavailable for selection           Set Temperature Range  Schedule     Set the temperature range that Is available from the Set Schedule screen   1  Touch the Set Temperature Range button  labeled   in the figure  to switch  between Standard  Low  and Manual  
10. ocked LOSSNAY button to make the interlocked operation  settings   Refer to 3 2  3 for details    The initial startup settings are now complete    3  Touch HOME button E  at the top right corner of the screen     4  Touch the OK button on the popup screen to start the initialization process      e  The message  shown left  will appear on the screen  displaying the  initialization progress  When initialization is complete  the screen will  automatically return to the HOME screen     Initialization will take up to five minutes      To change settings later  perform a test run  or verify the maintenance    information      Touch MAIN MENU button Ei   on the HOME screen      Touch SERVICE MENU button    ij   on the Main Menu screen     3  Enter the password to log on to the Service Menu screen    Refer to Chapters 3  4  and 5          2  Other Initial Settings   2  1  Basic controller setting    Touch Initial S ettings Basic System button   La   on the Service menu screen to  access the Initial Settings Basic System screen   Touch Page turn button   Il Ea   to turn the pages  and follow the directions  below to make the settings for each group   M NET Address  1  Touch the M NET Address button  labeled   in the figure   and set the  TC 24A Controller address on the screen that pops up     The address can be set to 000 or to a value between 201 and 250  the  factory setting is 201    Remote Controller Access  1  Touch the Remote Controller Access setting button  labeled    in the 
11. rlocked LOSSNAY  Touch       id T Delete All  HOME  Cancel Touch  REA   Login  OK Touch    i    Initial S ettings Basic system    System view  Initial S ettings Groups Touch         Malfunction log  Maintenance    Touch    Test run E    Groups    Software update    Interlocked LOSSNAY    Touch  EF    T Delete Al    System view    Malfunction Lo       Touch  m on each screen to return to a previous screen   Software Update     1 A password is required to access the Service menu     e The initial Service password is    9999     Change the password as necessary to prevent unauthorized access   e Make sure the password is available to the maintenance and other necessary personnel   e The password can be setto an arbitrary number between four and eight digits      If you forget your password  log in with the master password   Master password  105638    e The same master password is used to log in to specific screens under the    Main Menu    and the    Service Menu           Initial Settings     Notes on using the TC 24A with the AG 150A controllers    In addition to making the group and interlock settings on the TC 24A  the same setting information must be entered on the AG 150A    controllers  Also  enter the M NET address for the TC 24A in the System Controller field on the Group Setting screen  Register the  M NET address of the AG 150A on the TC 24A s Group Setting screen    When combining TC 24A with the AG 150A controllers  the Setback  Hold  and External Input Function set
12. s with the indoor units  make the settings through the    Interlocked LOSSNAY       screen     Touch the Initial Settings Groups button E on the Service Menu  and then touch the Interlocked LOSSNAY button Fea on  the Initial S ettings Groups screen to access the Interlocked LOSSNAY screen        1  Touch the LOSSNAY button  labeled   in the figure   On the popup window that appears  check the address of the ventilation  units to be interlocked with the operation of the indoor units    2  Touch the Interlocked indoor unit button  labeled   in the figure   On the popup window that appears  check the address of  the indoor units to be interlocked with the ventilation units     Up to 16 indoor units can be assigned to each ventilation unit    3  After all interlocked operation settings have been made  touch the Save button      2  4  Batch deletion    To delete all group and interlocked operation settings collectively  follow the procedure below    1  Touch the Initial Settings Groups button   eres   on the Service Menu screen  then touch the Delete All button   T   on the  Initial Settings Groups screen  A popup message    Do you want to delete all group settings and interlocked LOSSNAY  settings     will appear    2  Touch the OK button to delete group and interlock     6     4   Test Run      To run a test  follow the procedure below    1  Touch the Test Run button on the Service Menu screen to access the Test Run screen    2  Touch the OF F ON  button  labeled   in the figure
13. successfully completed will appear in the list          on the Service Menu screen to access the Maintenance screen            The addresses of the outdoor units that  Outdoor unit are connected to TC 24A will appear   address  The number in the parentheses  Peo Urti indicates the address of the Sub unit    fl    83 64 84 H   G7  BS 89 14 The addresses of the indoor units that    Indoor unit  are connected to given outdoor units  address    will appear         2  To view the Malfunction Log  Touch the Malfunction Log button on the Maintenance screen to view  The latest 50 malfunctions will appear three ata time     Display content  The date on which the error occurred     a_i  No  ime Um reyd ra Kk    ath  tie na eed Error source unit The address of the unit with the error   DA ical ati address  81 Nal S6 2018 89  288M      Error detection  The address of the unit that detected  1   unit address the error     as  91 20 Nee tape TEY Erorcode  Ihe error code that corresponds to the  error     Clear Log button Use this button to clear all records on  the Malfunction Log       Refer to the Instruction Book on how to make the settings not mentioned in this manual  e g   schedule settings and button lock  settings      To Update The Software  as necessary   1  Touch the Software Update button         on the Maintenance Menu   2  Following the instructions on the screen  insert the SD memory card with the update program into the SD slot  and then touch  the OK button     If a messag
14. t corner is correct  If it shows the old version  the  update failed  Try updating the software again      Only 1 GB and 2 GB SD memory cards by SanDisk are supported     SanDisk is a registered trademark of SanDisk Corporation in the United States and other countries       gt  DP    SD Logo is a trademark of SD 3C   LLC        a MITSUBISHI ELECTRIC CORPORATION    HEAD OFFICE   TOKYO BLDG   2 7 3  MARUNOUCHI  CHIYODA KU  TOKYO 100 8310  J APAN    WT05824Xx01    
15. tings should be made  only on the TC 24A  If using the Hold function on the TC 24A  schedule settings should not be made on the AG 150A controllers   To prohibit the operation of local remote controllers  set the prohibition settings either from the TC 24A or AG 150A  but not both       AG 150A Controllers   AG 150A  GB 24A  GB 50A  G 50A     1  Initial startup settings   Before turning on the controller  first make sure that the controller  indoor units  and outdoor units have been installed    properly according to the instructions detailed in the respective manuals   Turn on the controller and the units      a  The Language screen will appear   S elect the display language   Touch the button to select the language of your choice     Touch the OK button      b  The Date and Time screen will appear     Set the current date on the Date tab  and set the current time on the Time tab   using the    and A buttons to change the values     Click on the checkbox next to the date time format of your choice    3  Touch the Save button to save the settings      c  The Service Menu screen will appear   Q  Touch the Initial S ettings Basic System button to set the basic settings for the    controller   Refer to section 3 2  1 for details     2  When the settings have been chosen  touch the Initial Settings Groups button         d  The Initial Settings Groups screen will appear       Touch the Groups button to make the group settings   Refer to 3 2  2 for  details      2  Touch the Interl
    