1. 1 Introduction Fire protection systems as for example automatic fire extin guishing systems and automatic fire alarm systems are essential components of fire protection concepts They also provide a high success rate in extinguishing and or detecting fires Multiple examples of losses show that companies with out adequate fixed fire protection in place often suffer a total fire loss with high property damage and business inter ruption claims The efficiency and reliability of fixed fire protection is thus an essential factor to reduce potential fire damage and to maintain the business continuity of a company In order to guarantee this to a maximum extent repair works periodic In order to reduce the risk of fire during the impairment of fire protection systems additional fire prevention measures must be taken An impairment of fire protection systems increases the risk rh servicing and corrective maintenance to the fire protection systems cannot be avoided Important During an impair ment the risk of having a loss increases mainly because of two reasons Firstly the protection systems that are rel evant for the safety are not in operation Secondly servic ing and maintenance include activities that increase the risk of starting a Tire Proactive planning of the impairment plays an important role to ensure that servicing maintenance and repair works are carried out properly as well to restore the fir
2. Fax 49 511 645 4542 Verlagsgesellschaft mbH Internet www hdi gerling de Pictures HDI Gerling Sicherheitstechnik GmbH Imprint istockphoto com by_ alactr In charge of the content by_ bodo23 by_ SB 8NIHAT Clemens Lensing by_ gordondix by_ JimmiLarsen HDI Gerling Sicherheitstechnik GmbH reinobjektiv Although we made every effort possible to ensure the accuracy of the information provided no liability can be assumed for the currentness correctness and completeness of the information We neither intend nor assume any obligation to update or revise these statements in light of developments which differ from those anticipated
3. Maintenance of operational readiness of fire extinguishing systems with gaseous extinguishing agents Inerting and oxygen reduction systems planning and installation Sprinkler systems planning and installation 7 3 14 111 14 500 N 403 HGST SIFI149GB Risk Engineering Guideline Impairment of fire protection systems About HDI Gerling Risk Engineering Services HDI Gerling Risk Engineering Services supports mid size companies industrial companies and groups in preventing loss and damage and in setting up a com pany risk management system HDI Gerling Risk Engineering Services also offers customers access to more than one hundred engineers and technical specialists from a wide range of different disciplines The goal is to support companies in managing risks and working out an Individual risk based concept for insurance cover HDI Gerling Risk Engineering Services operates across the world in the technical safety lines of Fire Motor Engineering Insurance and Marine The focus of activities is on the identification and assessment of risks and the development of appropriate individual concepts for protection HDI Gerling Risk Engineering Services is part of the global Risk Engineering Network of the Talanx Group and a wholly owned subsidiary of HDI Gerling Industrial Lines HDI Gerling Sicherheitstechnik GmbH Layout RELAY CORPORATE HDI Platz 1 D 30659 Hannover PUBLISHING GmbH Phone 49 511 645 4126 Printers Lindendruck
4. Gerling Risk Engineering Guideline Hot works and Hot work permit In order to be able to respond at short notice in case of an unforeseen impairment of fire protection systems detailed procedures should be elaborated in advance These are then immediately avallable when ever required If fire alarm and extinguishing systems are a safety relevant element of the building permit and the occupancy permit this permit for use could be restricted in principle by this impairment Additional protective measures defined by the responsible authority e g fire protection service depart ment may have to be taken into account 4 Measures during the impairment The following should be considered during the impairment of fire protection systems Affixing of warning notices in protected areas and on components of the system clearly indicating that the fire protection system is under impairment Fire protection barriers such as fireproof doors and fireproof dampers should be closed during the impairment Hazardous or critical processes representing a fire risk should be discontinued to the maximum extent possible A fire watch should be provided if possible by the fire brigade or a specialist fire protection company with appropriate communication equipment radio links mobile phones in order to ensure that any fire alarm can be reported without any delay If longer interrup tions of the work are unavoidable patr
5. d to be com plete and does not provide any release from the duty of compliance with statutory or legal regulations Any liability is excluded Status February 2014 7 Sources references VdS 2000 VdS 2091en VdS 2093en VdS 2095en VdS 2106en VdS 2108en VdS 2109en VdS 2182 VdS 2212en VdS 2240en Not available in English Maintenance of operational readiness of water extinguishing systems CO fire extinguishing systems planning and installation Automatic fire detection and fire alarm systems planning and installation Spark detection spark separation and spark extinguishing systems planning and installation Foam extinguishing systems planning and installation Water spray systems planning and installation Not available in English Log book for water extinguishing systems Log book for gas and powder extinguishing systems VdS 2241 VdS 2304en VdS 2380en VdS 2381en VdS 2395 VdS 2496en VdS 2893en VdS 3527en VdS CEA 4001en Risk Engineering Guideline Impairment of fire protection systems Not available in English Local application protection for electric and elec tronic equipment planning and installation Fire extinguishing systems using non liquefied inert gases planning and installation Fire extinguishing systems using halocarbon gases planning and installation Not available in English Triggering of fire extinguishing systems guidelines
6. e protection system immediately after the works have been completed This guarantees that the work can be carried out as smoothly as possible and that the fire protection system Is again operational as quickly as possible For this reason it makes sense to subdivide the measures for the impairment of fire protection systems as follows Measures before the impairment Measures during the impairment Measures after the impairment restoration of the fire protection system 2 Risk situation Based on experience the majority of losses happen outside of the normal operations Why is the risk for a company increased specifically during repair service and mainte nance works The reason is given by the fact that the ad equate protection level is not provided and that activities can therefore be carried out outside everyday operations Additionally repair and service works often involve activi ties with an increased accident risk or ignition potential such as welding separating and cutting In order to reduce the risk of fire during the impairment of fire protection systems additional fire prevention measures must be taken 3 Measures before the impairment Servicing repair and maintenance works should be carried out by a VdS accredited installer preferably by the com pany that originally installed the fire protection system The servicing company must be certified for the systems concerned Risk Enginee
7. e area concerned Ol An emergency concept e g external supply of N for oxygen O The public fire brigade is informed reduction systems drains of the sprinkler system connected O The works fire brigade is informed via a fire hose with a hydrant O Stops blind flanges or similar spare parts are available on the spot Q Ordered works are done without interruption AAA nn r O DUNA a A A AA E A A AAA AAA AAA AA AAA A Precautions for the restoration E O All armatures switches on automatic operational readiness are O All parties involved in the process are informed employees safety checked and possibly padlocked in open position organisation public and private fire brigade insurer broker etc O The pipes are all flushed after the works a flush test was U The alarm system was reset and the alarm receiving station performed informed O Pressure testing was done A The full operational readiness of the system is confirmed in Q Warning signs indicating the impairment as e g the marking of written by the company doing the activities needed during the closed valves are removed impairment O The activities were recorded in the service manual Q Other e t DU MINA O ee AAA A A Further explanations and examples of protection measures are listed in the HDI Gerling Risk Engineering Guideline Impairment of fire protection sys
8. ntive measures and standard operating procedures If a system is not fully operational 3 os J gt ES E E ee a N e sae a ug Ale Eu y A e ee Be s ee Bun en age The following should be considered before the impairment Optimal preparation and organisation of the activities in order to keep the impairment as short as possible This includes among others the setting up of a time schedule the provision of all required materials e g replacement parts seals etc the coordination of required specialised staff the avoidance of work interruptions e g of repair works during night time periods week ends or public holidays Definition of the areas to be impaired restriction to small sections if possible no general impairment of the entire system If work is being carried out on the pipework of an extinguishing system only the respectively affected section should be shut off If the zone protected by one section covers several rooms appropriate meas ures should be taken e g by insertion of blind flang es protective caps etc to isolate the pipework only in the rooms where the work is being carried out m When work is being carried out on the water supply of e g a sprinkler system one source of water should be kept operational compressed air water tank or pump whenever possible or an alternative feed should be established When the only water suppl
9. ols should be carried out at intervals of maximum one hour These patrols should be documented The design concentration of an oxygen reduction system may not be exceeded during the impairment of the system Otherwise the emergency concept agreed with the departments responsible for fire protection and personal safety security must be implemented e g external supply with inert gas from a tanker Laufkarten 1310101 1340908 U6 2 06 Risk Engineering Guideline Impairment of fire protection systems Smoking and open flames are strictly prohibited in the affected areas avoidance of unnecessary ignition sources An increased number of control rounds must be carried out by trained and informed guards The use of third party companies within the affected area should be avoided If the use of third party com panies is unavoidable they must be properly informed and trained in accordance with the situation If possible the electrical power supply to the affected areas should be switched off 403 HGST249GB 1 14 1 14 500 N GERLING m Impairment notification m Restoration notification To be sent to your HDI or HDI Gerling contact person where applicable through your broker A A o A a Responsible person saicarticandaa a A A A a id a a s O Postal code Clientes Policy NUMBER mias das Herewith we declare that the O Sprinkler system O Foam extinguishing system O Water spray e
10. ring Guideline Impairment of fire protection systems Basically the planned impairment should be reported to HDI Gerling possibly via the insurance broker at least 14 days before the start and any compensation measures required are to be clarified Attached form Impairment notification Unplanned interruptions disruptions are to be reported without any delay If an unplanned impairment should occur during the night HDI Gerling possibly via the insurance broker is to be intormed on the following day This obligation to inform does not apply if it concerns the impairment of e g a single automatic fire detector under the condition that monitoring of the area involved is not compromised The impairment can only be instructed by an employee familiar with the areas and their associated risks and hazards This should be closely coordinated with the fire safety officer The instruction should be given in written form and after the impairment the document Is to be kept on file for at least half a year The wide variety of different fire protection systems does not allow to go into detail on all necessary measures This is why the following list of items does not pretend to be complete and should be adopted or extended to the re spective fire protection system when required Further more reference is made to the relevant sections in the various VdS guidelines to ensure the operational readi ness or respectively for preve
11. tems HDI Gerling Sicherheitstechnik GmbH HDI Platz 1 30659 Hannover www hdi gerling de 5 Risk Engineering Guideline Impairment of fire protection systems gt Measures after the impairment Ensuring complete automatic operational readiness without delay should include the following Check of all fittings and switches for automatic operational readiness if necessary securing in open closed position with a pad lock Performing a flushing test at the riser of a sprinkler system Notification of all departments involved in the process employees safety organization public fire brigade or works fire brigade etc Resetting the fire alarm control panel and notification of the alarm receiving station After the work has been completed the full opera tional readiness of the system should be contirmed in writing by the specialist company carrying out the works Furthermore the activities should also be re corded in the logbook of the system m Notification of HDI Gerling possibly via the broker and if necessary the responsible public fire brigade and or building permit authority about the restoration of the fire protection system m Removal of the warning notices If fire protection systems are under impairment the risk of a major loss is increased but can be reduced to an accept able level by adopting the measures described above 6 Note This Risk Engineering Guideline is not intende
12. xtinguishing system U Automatic fire detection system O Spark extinguishing system O Water mist extinguishing system O Local application extinguishing system type neneeenenneenneennnsennneennsennneennsennneenne O Powder extinguishing system O Gas extinguishing system gas type unnnenen O Oxygen reduction system U will be under impairment on 201 for the estimated duration of is under impairment since 201 The restoration of the system will probably follow within hours days is restored on A Alena h The target value of rest O of the oxygen reduction system is will be reached on Reason for the impairment O Extension Change Repair works U Maintenance Damage O Other The following area is affected please mention alarm valve group number of sprinklers area etc nnnennenennenneneennennnenneennennnnnnne Q Production processes with an increased fire risk are suspended O The area under impairment is kept as small as possible QA ban on cutting and welding is valid for the duration of the U Fire doors and fire dampers are closed impairment O Appropriate alternative systems are put in place e g mobile fire U Closed valves are marked detection system QA person is posted at the control valve pump for fast reaction in OA fire watch is arranged case of a fire Q Pressurised fire hoses are ready for use QA smoking ban is valid in th
13. y for an extinguishing system is shut down or fails an alternative water supply should be provided If the system is equipped with a fire department connection e g DN 150 with 4 x B fitting a hose connection should be set up between this connection and the next hydrant integrating a booster pump If necessary Provision of suitable substitute systems e g mobile fire alarm systems Provision of suitable manual fire extinguishing equip ment fire extinguishers installation of fire hoses ready for use etc combined with a fire watch or at least an increased number of patrols e g by guards Before a system is partially or completely impaired all parts of the company site should be inspected in order to ensure that there are no hazards or signs of a fire f on a site with multiple users a common fire protec tion system Is operated all the users must be in formed about the impairment of the system and joint compensation measures should be taken m Notification of the responsible public fire brigade and the works fire brigade Notification of the employees the plant management and the internal security safety management Any work that involves a fire hazard e g welding cutting and burning operations may not be carried out in the areas affected by the impairment or may only be carried out with strict adherence for the appli cable safety regulations for operations involving fire hazards see HDI