Home
        Installation & Maintenance Manual
         Contents
1.                                                                     44             8  Additional Refrigerant Charge    8 1 Air Tight Test   1  Check to ensure that the stop valves are closed completely before air tight test      lt  Tightening Check of Stop Valves  gt   a  After connecting the pipe  remove the cap of stop valve for gas and liquid      Tighten the open close spindle in the close direction with a torque  1       1  Stop Valve for Gas 86 to 114 18 to 22 N m  136 to 154 20 to 25 N m    Stop Valve for Liquid 7to9 N m    b  Perform the air tight test after the above check         lt  Gas Valve  gt   lt  Liquid Valve  gt     Cap  Tightening Torque  50 to 58N m       Check Joint for Service Port  Refrigerant Pressure Only the charging hose  can be connected   Hexagonal Wrench Tightening Torque  14 to 18 N m    To open or close Cap H  spindle valve g   Tightening Torque  33 to 42 N m  S GEN r mr  oN TENA  E  d                                 La 5 P  A  Rubber  Hexagonal Wrench Refrigerant  To open or close Pressure  spindle valve Ae a    f   Spindle Valve     Counterclockwise   Open H   Clockwise                 Close   Tightening Torque  a N m Spindle Valve  Counterclockwise    Open  Clockwise               Close    Gas Valve Tightening Torque  7 to 9 N m       Check Joint for Service Port   Tightening T  Only the charging hose x   x KBtu h    9 ony ta ala    can be connected     Tightening Torque  9 to 14N m 86 to 114 18 to 22  I 136 to 154  20 to 25                
2.                 DES                                              E E       e Function Setting             External Input Output and Function Setting          armer J      Press PSW1 once                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 m Start of Setting Menu Mode       Turn ON DSW4 No 4    i i i  Press PSW1 for 3 seconds or more  f  pon   oe gn E i Arrangement of Dip Switch Setting     Menu Mode    will be indicated  LVA p F dai d  j     gt   For more details  1  m End of Setting eee id refer to    Checking of   NI PSW2 Dsw2    psw3  SR Outdoor Unit by PCB       TJ  Press da e 3 E or more  VA j in the Service Manual  Psws  lPsw1 swg  DSW4 DSW5  e display indication become to External Input    A i  normal indication  and Code     gt j For the setting mode    SEG2 SEG1 PSW4 pswel DSW7  Turn OFF DSW4 No 4  Ie SF  je  efer to  1  below     VA     H   DSW1    Rsw1  NOTE  Function      gt   For the function setting     Release    Menu Mode    after    Setting  le refer to  2  below  l  the setting is completed 
3.                Code  Category Content of Abnormality Leading Cause  i i   Incorrect Capacity Code Setting of Combination  31 Incorrect Capacity Setting of Outdoor Unit and Excessive or Insufficient Indoor Unit Total  Indoor Unit Capacity Code  System  35 Incorrect Setting of Indoor Unit No  Duplication of Indoor Unit No  in same Ref  Gr   36 Incorrect of Indoor Unit Combination Indoor Unit is Designed for R22  38 Abnormality of Picking up Circuit for Protection Failure of Protection Detecting Device  in Outdoor Unit  Incorrect Wiring of Outdoor PCB   Abnormality Running Current at Overcurrent  Blowout Fuse  Current Sensor Failure   39 Compressor Instantaneous Power Failure  Voltage Drop   Constant Speed Compressor Abnormal Power Supply  3A Abnormality of Outdoor Unit Capacity Outdoor Unit Capacity  gt  1350KBtuh  3b _   Incorrect Setting of Outdoor Unit Models Incorrect Setting of Main and Sub Unit s   Outdoor Unit   Combination or Voltage Combination or Voltage  3d Abnormality Transmission between Main Unit Incorrect Wiring  Disconnect Wire  Breaking Wire   and Sub Unit s  PCB Failure  Activation of Low Pressure Decrease Protection Defective Compression  Failure of Compressor  43 Device of Inverter  Loose Power Supply Connection   Activation of Low Pressure Increase Protection Overload at Cooling  High Temperature at Heating   44 Device Expansion Valve Locking  Loose Connector   Protection Activation of High Pressure Increase Protection Overload Operation  Clogging  Short Pa
4.              Cord Clamp   For fixing power supply cable              Cord Clamp   For Transmission Wiring                                            Transmission Wiring             Connection Hole of Power Supply Wiring   0 52        Connection Hole of Power Supply Wiring      52                                                                                          Power Supply Wiring       Connection Hole of Transmission Wiring       Fig  7 1 Wiring Connection    34    7 2 Electrical Wiring Connection    The ELB  earth leakage breaker   FUSE and S  main switch  must be installed to the each power source of  outdoor unit  If not  it may cause of electrical shock or fire     NOTE   Supply the power source of outdoor units and indoor units respectively      1  Power Source Wiring  Supply the power sources to the each outdoor unit respectively   Power source wiring is fundamentally according to this method                                                                                                                                                                                      Power Source    220 240V   50Hz    Outdoor Unit Power Source    ELB  Earth Leakage Breaker      FUSE  380   415V 3N  50Hz    S  Main Switch    4  Power Source Wiring  O U           B  Earth Wiring  O U    i    ELB i  1  ELB Li    ELB    Transmission Wiring  O U    I U      FUSE   FUSE   FUSE TD Transmission Wiring  O U    O U    I  s I  s I  s Power Source Wiring  LU    Q  Earth Wiring  LU        
5.           Min  300   h1 2          Min  10                gt                             Min  500   h2 2 Min  500   h2 2  Front Side Front Side          Min  10   Side Space                    i Min  900             5                Min  200   3      SW             Min  500   Rear Side Space                       Gi    SS          Min  400       Front Side                         Front Side  Min  500   gt       gt       f Front Side      e o Front Side  Min  20   Min  20 t Min  500   h2 2 Min  20 Ik    Min  20 t Min  500   h2 2          Min  400 1 Min  500   h2 2             No limit for side wall height      lt Top View gt     No limit       or side wall height      lt Top View gt     No limit for side wal     lt Top View gt        height     13    3  Walls on 4 Directions  e Single Installation    No limit for    side wall height     Ly    Min  200    Min  300   h1 2       D       N Min  200       ated          N 4    No limit for          Min  800 Front Side side wall height   Open De  Min  500   h2 2   lt Top View gt     e Multiple      Serial Installation     lt  Installation in the Same Direction gt        di                                              Min  300   h1 2  N  Min  2007 Min  200   e  Front Side i  No limit for Min  900 No limit for  side wall height  Se Q side wall height   SE WEE  Min  w Front Side Min  800  Open e Open  iN N N    Min  200 Min  200 Min  500   h2 2     lt Top View gt      lt  Rear to Rear Installation 1  gt        Fotad   N Min  500   h2 2 
6.       E Indoor Unit Side  Outdoor Outdoor Outdoor    Unit Unit Unit    eo B     a                       D D       l       l I  l EUSE Indoor Indoor    ag Unit       Unit_ _                d  i Indoor Unit              l       35    36     2  The recommended wiring  ELB  breaker size are shown as follow    B Field Minimum Wire Sizes for Power Source    Maximum    Outdoor Unit  KBtu h     Transmitting   Earth  EN60335 1  1  EN60335 1 1  Si   mm   j    Nominal  a    E  Sensitive                  Refer to the NOTES for selection of the power source cable size   ELB  Earthleakage Breaker     NOTES     1  Follow local codes and regulations when selecting field wires   2  The wire sizes marked with  1 in the above table are selected at the maximum current of the unit according to  the European Standard  EN60335 1 Use the wires which are not lighter than the ordinary polychloroprene sheathed  flexible cord  code designation HOSRN F    3  Use a shielded cable for the transmitting circuit and connect it to ground   4  In the case that power cables are connected in series  add each unit maximum current and select wires below     wech                                        According to EN60335 1  Current A  Wire Size mm      i lt 3 1 2 5  3 lt i lt  6 1 2 5  6 lt i lt 10 1 2 5  10 lt i lt 16 1 5 4  16 lt i  lt 25 2 5 6  25 lt i lt 32 4 10  32 lt i lt 50 6 16  50 lt i lt 63 10 25          In the case that current exceeds 63A Don t series connection       a  30  40  40  50    Install a mul
7.    Refrigerant Piping     2  Connect the indoor unit and the outdoor unit with field supplied refrigerant piping   Suspend the refrigerant piping at specified points and prevent the refrigerant piping from touching  weak parts of the building such as wall  ceiling  etc    Abnormal sound may occur due to the vibration of the piping  Pay special attention in case of short  piping length      3  Connect the gauge manifold using charging hoses with a vacuum pump or a nitrogen cylinder to the  check joints of the liquid line and the gas line stop valves   Perform the air tight test   Connect a manifold gauge to the check joints of the liquid and gas stop valves in the outdoor unit   Do not open the stop valves  Apply nitrogen gas pressure of 4 15MPa for Hi Multi series     A DANGER    Be sure to use Nitrogen Gas for air tight test  If other gases such as oxygen gas  acetylene gas or  fluorocarbon gas are accidentally used  it may cause explosion or gas intoxication     45    46     4  Check for any gas leakage at the flare nut connections  or brazed parts by gas leakage tester or by  use of a foaming agent or gas leak detector     Recommended Forming Agent  G  proflex Yokogawa  amp  CO  Ltd     5  Mount the piping cover equipped with the outdoor unit after connecting the pipe     Procedure    Completion of mb Applying   gt  Check of    gt   Ref  Piping Nitrogen Gas Pressure Decrease    4  Repairing of  Leakage Part                 Outdoor Unit  Nitrogen Tank   for Nitrogen Blow du
8.    for R410A  a  for Extruded Portion    In case of material 1 2H  flaring is not available  of Tube after Flaring   Use elbow for bend and braze       A 2   In case of material 1 2H  expanding of tube is not Expanding Tubes    mpo Torque Wrench       Ka   For 012 7  615 88  spanner size is up 2mm  Connection of       lt     lt  Ir For 66 35  69 53  619 05  spanner size is the same    Flare Nut       Measuring Instrument and Tool    Brazing Tool Ka   Perform correct brazing work  Brazing for Tubes    Nitrogen Gas  Lubrication Oil   for Flare Surface       Strict Control against Contamin Prevention from   Blow nitrogen during brazing   Oxidation during  Brazing    Use a synthetic oil which is equivalent to the oil used   Applying Oil to  in the refrigeration cycle  the Flared Surface    Synthetic oil absorbs moisture quickly   Refrigerant Check refrigerant cylinder color  Refrigerant Charging      Liquid refrigerant charging is required regarding  Cylinder      zeotoropic refrigerant       The current ones are applicable  However  it is Vacuum Pumping       vacuum Pump     K required to mount a vacuum pump adapter which  Adapter for can prevent from reverse flow when a vacuum pump  Vacuum Pump stops  resulting in no reverse oil flow       No interchangeability is available due to higher Vacuum Pumping   pressures when compared with R22  Vacuum Holding      Do not use current ones to the different refrigerant    Refrigerant Charging  If used  mineral oil will flow into the cycl
9.   A  WARIS oola io  N ractcaeses E n T E r a E E 9  4 2 Handling of Outdoor Un    10   5  Outdoor Unit Installation sisao a a E E E E E EE 11  5 1 Factory Supplied Accessories     nnen ennnnernennnnereeneneeenenenernennnenennnneerennenernennneennennneenennnneneennenen 11  5 2 MMStANANON 2  itn oerernnte tetteren tende Reen RE ee 12  DiS  EE 13  5 4 FOUNDATION eet ee Mace edad ante EENEG SOERENSEN EES 15  5 5 Drain Water Treatment    szarenensensenenenensennananenontnnenannnacdne saesnnennssccond cba SAAE ERARE EAER 17   6     Refrigerant Piping WORK  nan cece Shir ENEE aie andl E ele en dees 18  6 1  Piping EE 18  6 2  Faring  ang  dente eege eessen te eet ae 20  6 3 Caution about Outdoor Unit Installation                 nnnnnnnnnner eneen eeennneneneneeenenneervennenennensneeenennenn 21  6 4 Piping Connection for Cooling Heating Changeover Operation System nnn ennen renee eneen 23  6 4 1 Piping Size for AVWT 86U6SR to AVWT 154U6SS  Base Units  nennen ooren oernenoneneeneneenrnens 24   6 4 2 Piping Size for AVWT 182U6SZ to AVWT 307U6SZ  Two Units Combination      nana 24   6 4 3 Piping Size for AVWT 328U6SZ to AVWT 460U6SZ Three Units Combination  nnen nanne 25   E ee WE 26   6 4 5 Piping Connection                cccccccceecccceeeeeeeeeeceeeeeeeeeaeeeeeeaeeeeceeaeeeeeeaneeeseeaeesecscaeeeesceseeeeseaeeeesseeeeeta 27   T  Elecrical WIM EE 33   Ml     General OE ed 34  1 2  Electrical Wining ConnectOM seee ee aaneen Eee ege dg 35  LS Electrical Wiring Tor Outdoor UMi  reisien
10.  C       i   d Gas Accessory Pipe    i  i                 Field Supplied     A           Gas Accessory Pip   Field Supplied      I                                                                      La  Manifold Pipe 1   PN 424   Liquid     Dae ef     x  Liquid Accessory D  Pipe   Field Supplied   Manifold Pipe 2 Liquid Accessory  G Pipe   Gas   Field Supplied   Manifold Pipe 2 Gas Piping Liquid Piping   Liquid   Field Supplied   Field Supplied              28    e Branch Pipe  Optional Parts      lt  Line Branch  gt     First Branch Pipe Diameter and Branch Pipe after First Branch    Outdoor Unit  KBtuh  Total Indoor Unit  KBtu h  eee facia   Model      Lower than 57 15 88  HFQ 102F    86 and 96 HFQ 102F  114 and 154 HFQ 162F    182 and 232 HFQ 242F   250 and460   HFO 302F    HFQ 162F  154 to 172 28 6 12 7             29    e Piping Size  pmm  and Branch Pipe Selection                                                                                                                                                  CT  Pipe Diameter for Outdoor Unit ham SER     Main Pipe Diameter ee Sr Outdoor   Base Unit or Manifold Pipe 1 to First Branch  gece Une     Unit   Branch Pipe of First Branch    2  A B c  p   lt  y    a  Outdoor Unit  KBtu h  en Piping Length 100m D    KS     1   l Manifold Pipe 1 Manifold Pipe 2 L5  114 and 136    3  182 to 232      gd H1  250 to 328 i     E 8  4   4  4 L3  345 to 460    is E id  Indoor Indoor  Indoor A  Unit Unit Unit  Total der Unt  KS  Lower tha
11.  CHECKING PRODUCT RECEIVED      Upon receiving this product  inspect it for any shipping damage   Claims for damage  either apparent or concealed  should be filed immediately with the shipping  company      Check the model number  electrical characteristics  power supply  voltage and frequency  and  accessories to determine if they are correct     The standard utilization of the unit shall be explained in these instructions    Therefore  the utilization of the unit other than those indicated in these instructions is not recommended   Please contact your local agent  as the occasion arises    HISENSE   s liability shall not cover defects arising from the alteration performed by a customer without  HISENSE   s consent in a written form     TABLE OF CONTENTS    1  Safet SUMMAN mercan seni cba pAistice yaauahbe pact eayoed E sd ba pleuskeaybodschesdee ceeayoes chi E E sehen 1  SEELEN ee Ses ea ee 5  2 1 Outdoor Unit  amp  Refrigerant Cycle     nnen eennnnereennneereenneeenennnnerennnnenrennnnenrnnnnnenennnneenennneeenn 5  2 2 Necessary Tools and Instrument List for Installation         nnn nnnnnennennenernennneereeneneeneenenersennneer nennen 5   3  Before  Installationo2  445 2008 2h i ep a Pe a ce e E retarded be eee aren 7  3 1  Line Up of Outdoor Unit  onee reren ee i rie ies 7  3 2 Combination of Indoor Unit and Outdoor Unit     nennen ennenenrennneeenennnereennnnervenenernennnnee eenen 7   4  Transportation and Handimg  enen en ennn nnnn ennn nnn nennen neren eneen eneen  9
12.  E ae 38  7 4 Electrical Wiring Connection of Indoor Unit  Outdoor Unit ee enenereennenerennnenerennnneerennen 40  7 5 Dip Switch Setting of Outdoor UNitessssesiresssssieressrank ierre a Ea an ects 42   8  Additional Refrigerant Charge  45  Bl SAM Ne Lu 45  8 2 VACUUMING EE 47  8 3 Additional Refrigerant Charge Calculation         nnen enennereennnenrennenenrenneernenneennenneeneennnnen  48  84 Charging Work     arnnasraaarerrzennsnenrengnsersdrendenndnkonrrneensdanmtskeettntenadiinierndietnkadikndntaaikedspsdikadenoditndikndikedsndinnn 59  8 5 Automatic Simple Judgement System for Refrigerant Amount     nnen nennneeenennnereeenener nennen 50  EC a ee ee EE 52  SCT Before Test  bp ee EE 52  Q2 eet UE ee ee Ee 54  10  Safety and Control Device Setting  arseen sereen evert erie eter nerd eend 59    1  Safety Summary     lt  Signal Words  gt        Signal words are used to identify levels of hazard seriousness   Definitions for identifying hazard levels are provided below with their respective signal words     AA DANGER      ACAUTION        NOTICE    amp     NOTE    DANGER indicates a hazardous situation which  if not avoided   will result in death or serious injury       WARNING indicates a hazardous situation which  if not avoided     could result in death or serious injury     CAUTION  used with the safety alert symbol  indicates a hazardous situation which   if not avoided  could result in minor or moderate injury     NOTICE is used to address practices not related to person
13.  Outdoor Unit A                      Outdoor Unit A  7         Outdoor Unit B Outdoor Unit C  H    Outdoor UnitC Outdoor Unit B                             em  SC                                                                                                 To Indoor Units  Manifold Pipe 1    Manifold Pipe 2          Manifold Pipe 2          AVWT 444U6SZ    AVWT 328U6SZ7   AVWT 345U6SZ   AvWT 365U6SZ   AVWT 386U8SZ__  AvwT 402uesz   AVWT 426U6SZ    Outdoor  AVWT 154U6SS   AVWT 154U6SS   AVWT 136U6SS   AVWT 154U6SS   asss   AVwT 154u6SS  ec E Go AVWT 96U6SR_   AVWT 96U6SR AVWT 114U6SR   1 AVWT 114U6SR     AVWT 136U6SS   AVWT 154U6SS  Outdoor  Unit   AVWT 86U6SR   AVWWT 96U6SR AVWT 114U8SR   AVWT 114U6SR   1 AVWT 114UGSR   AVWT 114UGSR            AVWT 154U6SS    AVWT 154U6SS         AVWT 136U6SS                     To Indoor Units       Manifold Pipe 1                 mm   AVWT 460U6SZ    AVWT 154U6SS  AVWT 154U6SS    AVWT 154U6SS             Manifold Pipe 1 HFQ M32F HFQ M32F  Manifold Pipe 2 HFQ M22F HFQ M32F  Gas 31 75 38 1 38 1 38 1 38 1 38 1 38 1 38 1  a  19 05 19 05 19 05 19 05 19 05 19 05 19 05 19 05  15 88 15 88 15 88 15 88 19 05 19 05 19 05 19 05  Gas 28 6 28 6 25 4 28 6 28 6 28 6 28 6 28 6  Piping Size c  Liquid 12 7 12 7 12 7 12 7 12 7 12 7 12 7 12 7  Gas 19 05 22 2 25 4 25 4 25 4 25 4 25 4 28 6  e  Liquid 9 53   9 53   12 7   12 7   12 7   12 7   12 7 12 7            Perform the installation of the outdoor unit and piping connection according to the figure   Refer t
14.  Punc JEN     Otherwise  the air conditioner v A d DSW10  may not operate appropriately  L UE H  lt  PCB1  gt      External Input and Output Setting       Function Setting    By pressing the push switches PSW3   gt   and PSW5  4   By pressing the push switches PSW3  p gt   and PSW5  4   the setting can be changed   the function No  can be selected  PSW4        forward  PSW2  A   backward  PSW4  W    forward  PSW2  A   backward Refer to the Technical Catalog for more details    lt  Example  gt   lt  Example  gt   Fill out the selected function setting No  1 Fill out the selected function setting No  1  in the space of the table as shown  in the space of the table as shown   Item SEG2   SEG1 SET  F Item SEG2   SEG1 SET Item SEG2   SEG1 SET  1 Input Setting 1 fi 1  CN17  1 2 pin  a t  Circulator at Heating ce    m  2 Input Setting 2 ja  5 1_ Function Thermo OFF Tm Li 14  Not Prepared ce D  CN17  2 3 pin  It a  7 Input Setting 3 D  lt  2  Night Shift re D 15  Not Prepared a   2 pi a a  CN18  1 2 pin  Cancellation of Ge  _ i m  i Output Setting 1 i j 3 E Di Ll 16  Not Prepared zm D  3 nj Di I emperature Limit  CN16  1 2 pin  Defrost for Cold Area   i En  Output Setting 2     4   Change of Defrost oe d D 17  Not Prepared d O D  5 CN16  1 3 pin  OC C Condition    Setting before shipment  5 SS ee Speed  l  f H H 18  Demand d E H  Before shipping  the input output function settings are specified to each SIS setting pin   es a  input output terminal according to above table  The detail
15.  Refrigerant Gas Ss  Pipe 22 2  19 05 02220254 025 4   028 6  Connection for   B    Refrigerant   Liquid Pipe 09 53   012 7   For Connection Hole of   ner Supply we                             136                         Screw  Spare       Combination Unit Model Label                            NOTE    If any of these accessories are not packed with the unit  please contact your contractor      9     Installation   Install the outdoor unit in a dry well ventilated environment    Install the outdoor unit where it is in the shade or it will not be exposed to direct sunshine or direct  radiation from high temperature heat source    Install the outdoor unit where the sound or the discharge air from the outdoor unit does not affect  neighbors or surrounding ventilation  The operating sound at the rear or right left sides is 3 to 6dB A   higher than the value in the catalog at the front side    Install the outdoor unit in a space with limited access to general public    Check to ensure that the foundation is flat  level and sufficiently strong    Do not install the outdoor unit where dust or other contamination could block the outdoor heat  exchanger    When installing the outdoor unit in snow covered areas  mount the field supplied hoods on the top of  the outdoor unit and the inlet side of the heat exchanger    While heating or defrosting operation  drain water is discharged  Provide adequate drainage around  the foundation  If installing the unit on a roof or a veranda  avoid dr
16.  Unit  B A                   unit side   Outdoor Unit Capacity  A  gt  B  gt  C Outdoor  Unit  A  Indoor Unit Side  m           lt  Piping Work between Outdoor Units  gt    1  Piping length between Manifold Pipe  at outdoor unit side  and outdoor unit should be    La lt LB lt Lc lt  10m                                   Outdoor Outdoor  Unit Unit  A B                Outdoor  Unit  C                Indoor Unit Side       Manifold Pipe       Outdoor Unit  Capacity  A  gt  B  gt  C    Keep the direct distance  of 500mm or more after  the Manifold Pipe     Indoor Unit Side    Lc                   Outdoor Unit Capacity  A  gt  B  gt  C    Indoor Unit Side                                     Upstream Side                                   2  Place the Manifold Pipe lower than the outdoor unit piping connection   In case that the Manifold Pipe is placed higher than the outdoor unit piping connection  keep  300mm  max   between the Manifold Pipe and the bottom of the outdoor unit  Also  provide the  oil trap  min  200mm  between the Manifold Pipe and the outdoor unit                                         Indoor Unit Side                       lt _                       gt   Outdoor Outdoor EN  Unit Unit c e  A B Max  lift  difference between  outdoor units is 100mm  Manifold Pipe                                  Oil Trap Oil Trap Oil Trap  Min  200mm Min  200mm Min  200mm  eas X    i  Indoor Unit Side        Jo  Max  n   Max   300  300mm   mm                         A        3  In 
17.  devices operate correctly    Has the unit been checked for refrigerant leakage   Is the unit clean inside and outside    Are all cabinet panels fixed    Are all cabinet panels free from rattles    Is the filter clean    Is the heat exchanger clean    Are the stop valves open     Does the drain water flow smoothly from the drain pipe     No  3 DB    DB    No  7 DB    bels    DB    COMPRESSOR MFG  No     DATE       C     C     C     C     No  4 DB    DB    No  8 DB    Li    DB       Table 9 2 Alarm Code                                  Code  Category Content of Abnormality Leading Cause  Activation of Float Switch  01 Indoor Unit   Activation of Protection Device  Float Switch   High Water Level in Drain Pan   Abnormality of Drain Pipe  Float Switch or Drain Pan        Activation of Protection Device Activation of PSH  Pipe Clogging  Excessive  02   Outdoor Unit  High Pressure Cut  Refrigerant  Inert Gas Mixing     Incorrect Wiring  Loose Terminals  Disconnect Wire   03 Abnormality between Indoor and Outdoor Blowout of Fuse  Outdoor Unit Power OFF  04   Transmission   Abnormality between Inverter PCB and Outdoor PCB eee eE Gund ea  04  Abnormality between Fan Controller and Outdoor PCB  ene dee  g Incorrect Power Source  Connection to  05  Supply Phase   Abnormality Power Source Phases Reversed Phase  Open Phase  06 Abnormal Inverter Voltage Outdoor Voltage Drop  Insufficient Power Capacity  Voltage  06  Abnormal Fan Controller Voltage Outdoor Voltage Drop  Insufficient Power 
18.  easily  Do not attach the main label    on the sub unit  outdoor unit B and CH     52    Caution for Insulation Resistance   If total unit insulation resistance is lower than 1 megohm  the compressor insulation resistance may  be low due to retained refrigerant in the compressor  This may occur if the unit has not been used  for long periods     1     Disconnect the cables to the compressor and measure the insulation resistance of the compressor  itself  If the resistance value is over 1 megohm  then insulation failure has occurred of other  electrical parts       If the insulation resistance is less than 1 megohm  disconnect the compressor cable from the    inverter PCB  Then  turn on the main power to apply current to the crankcase heater    After applying current for more than 3 hours  measure insulation resistance again   Depending on  the air conditions  pipe length or refrigerant conditions  it may be necessary to apply the current  for a longer period of time   Check the insulation resistance and reconnect the compressor     If the leakage breaker is activated  check the recommended size shown in Table 7 1     NOTICE    1  Confirm that field supplied electrical components  main switch fuse  fuse free breaker  earth leakage    breakers  wires  conduit connectors and wire terminals  have been properly selected according to the  electrical data given in the Technical Catalog of the unit and ensure that the components comply with  national and local codes       Use shield
19.  ront Side x          d  HO                 lt  Rear to Rear Installation 2  gt     La LLLLLLL LL     Front Side           L Min  500   h2 2                Min  200 Min  200 Min  200 Min  200   Side Space  7 Es  Min  900  No limit for Min  1600  Rear Side Space     side wall height   oF    No limit for  side wall height                 JG                               No limit for  side wall height                                      Min  800 Front Side Min  800  Min  800 Front Side Min  800 Open 4 4 Open  Open kK Open j  SIS INN K Min  400 Min  400 Min  500   h2 2  Min  200 Min  200 Min  500   h2 2  lt Top View gt    lt Top View gt              Min  1m                                                    B                NOTE  1  Keep the upper side open to prevent mutual interference of inlet and outlet air of each outdoor unit   2  The figure dimensions are sufficient spaces around outdoor units for operation and maintenance at typical  installing conditions as follows    Operation Mode  Cooling Operation  Outside Temp   35  C    In case that the outdoor unit ambient temperature is higher and also the short circuit is likely to occur  compared to the installation condition  find an appropriate dimension by calculating air flow current   3  For the multiple installation  1 group allows 6 outdoor units  max     The space of 1m between each group is required   1 Group  Max  6 Outdoor Units   4  Partly open a wall if the unit is surrounded by walls in four directions     14    
20.  side is higher than 1 500mm  the  space of  500   h2 2  mm for the front side is required     When the wall of rear side is higher than 500mm  the  space of  300   h1 2  mm for the rear side is required     When install the wall in front of the unit  make the vent  hole on the wall     When the space to the obstacle above the unit is less  than 1 500mm or the space above the unit is closed   set up the duct at the air outlet side in order to prevent  short circuit     When there are obstacles above the unit  the four  front   rear  right and left  sides of the unit shall be open in  principle     buildings and there are no walls in 2 directions  the    No limit for side wall Sai    No limit for side wall Kai    No limit for side wall H                                                    t Min  300   Min  300   Min  300   gt   Rear Side Space   gt   Rear Side Space   Rear Side Space   Front Side Front Side Front Side Front Side   Front Side i  Min  500   h2 2  Min  400 Min  400   lt Top View gt   lt Top View gt    lt Top View gt     2  Walls on 3 Directions    e Single Installation    Front Side Zo 500   h2 2        No limit for side wall height     Min  300   h1 2       Min  10                 lt Top View gt     e Multiple   Serial Installation     lt  Installation in the Same Direction gt      lt  Rear to Rear Installation 1  gt           wa  This indicates the direction of the unit  Front Side   when installing the units                  lt  Rear to Rear Installation 2  gt 
21.  the conduit        Apply insulation and  check that no clearance exists              23    6 4 1 Piping Size for Base Unit    Outdoor Unit    CH                                                 6 4 2 Piping Size for Two Units Combination     lt  Figure for AVWT  232U6SZ  gt                                                                                                                                             Indoor Unit on Left Side   Indoor Unit on Right Side   Outdoor Unit A   Outdoor Unit B Outdoor Unit B Outdoor Unit A  L J i J  bot T IST Id KC  KC  Cao    l   f  E c  J hensen en             To Indoor Units      Manifold Pipe          Manifold Pipe          To Indoor Units   gt            omm     Model    Juutagues    James _ AvwT 210u6sz _JAVWT 232U6SZ   AavwrT 250uesz   AVWT 272U6SZ _TAvwT 290u6sZ     AVWT 307U6SZ    Outdoor  Combination AVWT 96U6SR AVWT 96U6SR AVWT 136U6SS AVWT 136U6SS AVWT 136U6SS AVWT 136U6SS AVWT 154U6SS AVWT 154U6SS       Unit Outdoor  Unit B AVWT 86U6SR AVWT 96U6SR AVWT 86U6SR AVWT 96U6SR AVWT 114U6SR AVWT 136U6SS AVWT 136U6SS AVWT 154U6SS    Manifold Pipe HFQ M22F HFQ M32F       Piping Size               Perform the installation of the outdoor unit and piping connection according to the figure   Refer to the table for the outdoor unit model  the Manifold Pipe model and the piping diameter    24    6 4 3 Piping Size for Three Units Combination   lt  Figure for AVWT  365U6SZ  gt      Indoor Unit on Left Side   Indoor Unit on Right Side          
22.  to 114 KBtu h gt   lt 136 KBtu h to 154 KBtu h gt   131 131 Si 948 eee 131  co         a SZ gn  co 4 38x15   S    Hole of Anchor Bolt  gt        Fig  5 1 Position of Anchor Bolts    Secure the outdoor unit with the anchor bolts         Washer                                     Anchor Bolt  M12    Filled Mortar     6  When installing the unit on a roof or a veranda  drain water sometimes turns to ice on a cold morning   Therefore  avoid draining into an area where people often use because it is slippery      7  When drain piping is necessary for the outdoor unit  use the drain boss set  Optional  DBS 26      Do not use drain boss and drain pan kit in the cold area  The drain water in the drain pipe may be  frozen and then the drain pipe may crack     5 5 Drain Water Treatment    Drain water is discharged during heating and defrosting operation   Rain water is also discharged    Pay attention to the followings      1  Choose a place where well drainage is available  or provide a drain ditch      2  Do not install the unit over the walkways  Condensation water may fall on people   In case of installing the unit in such a place  provide the additional drain pan    3  When drain piping is necessary for the outdoor unit  use the drain boss set  Optional  DBS 26      Do not use drain boss and drain pan kit in the cold area  The drain water in the drain pipe may be  frozen and then the drain pipe may crack     Unit  mm   lt 86 KBtu h to 114 KBtu h gt   lt 136 KBtu h to 154 KBtu h g
23. 154U6SS AVWT 154U6SS          Combination          Combination          AVWT 154U6SS  Combination   AVWT 154U6SS  AVWT 154U6SS                Regarding the configuration of outdoor units especially for 182   460 KBtu h  combine the specified based units   2 or 3  as shown in the table above     3 2 Combination of Indoor Unit and Outdoor Unit  The following indoor units can be combined with the outdoor unit     Indoor Unit Type  07    Ceiling Ducted Type  Low Height Duct Type   Way Cassette Type    Table 3 1 Indoor Unit Type List    Wall Mounted Type    Floor Type    Floor Concealed Type  Ceiling Type       O  Available    e The number of connectable indoor unit with the outdoor unit is as follows   Comply with the condition as follows when installing the unit     e Amaximum total capacity of 130  and a minimum total capacity of 50  can be obtained by combination  of the indoor units when compared with the nominal outdoor unit capacity     Table 3 2 System Combination    Min  Capacity at Max  Number of Recommended R f  Model   KBtu h     Individual Operation en Number of Ee ec acit    KBtu h   Connectable I U  pacity    Ce  38    ee  CSR ES o  SECHS ES e  SECHS o e  s o e  a o e  e T o  o T s  en e Seal  ne enn  CSS ESCH NEEN  EZ  EZ  ee  EN  ee  ee  ee  ee  CE   NOTES     1  For the system which all indoor units are operated simultaneously  the total indoor unit capacity should be  less or equal to the outdoor unit capacity  If not  poor performance or narrow operation range 
24. 18    Table 6 1 Piping Size of Outdoor Unit                 mm   Model   KBtu h   Gas Liquid  19 05 69 53  22 2 09 53  25 4 012 7  28 6 012 7  28 6 15 88  28 6 15 88  31 75 19 05  31 75 19 05  328  938 1  19 05  386  di d    Table 6 2 Piping Size of Indoor Unit     mm     indoor  EST  07 to 14 12 7 6 35       17 to 18 15 88 6 35  22 to 54 15 88 9 53    76 19 05 09 53  22 2 9 53    e Piping Thickness and Material    Use the pipe as below    mm     1 0    1 2H material    12H material    1 2 material  631 75 1 2H material       1 0  1 0  1 1    1 35 1 2 material  1 45 1 2H material  044 45 1 55 1 2H material          6 2 Flaring and Joint    e Flaring Dimension  Perform the flaring work as shown below     90     2    mm      0   od   0 4  R410A       It is impossible to perform the flaring    work with 1 2H material  In this case   use an accessory pipe  with a flare         e Joint Selection  If you use 1 2H material  you can not perform the flaring work  In this case  use a joint selected from the  chart below      lt  Minimum Thickness of Joint  mm   gt   lt  Flare Nut Dimension B  mm   gt                 20    6 3 Caution about Outdoor Unit Installation     lt  Outdoor Unit Alignment  gt     Align the outdoor unit from large capacity as A gt  B  gt  C and outdoor Unit    A    should be located at the indoor                                                                         Outdoor Outdoor  Unit Unit  B C             Outdoor  Unit  c                Outdoor Outdoor  Unit
25. 32  C DB   23  C WB 27  C DB       Outdoor  5  C DB      20  C WB         Temperature   Maximum 43  C DB 15  C WB       DB  Dry Bulb  WB  Wet Bulb    NOTES       10  C DB    5  C DB  Operation Control Range        12  C WB    20  C WB  Operation Control Range       e Pay attention to the following items while the system is running   Do not touch any of the parts by hand at the discharge gas side  since the compressor chamber  and the pipes at the discharge side are heated higher than 90  C   DO NOT PUSH THE BUTTON OF THE MAGNETIC SWITCH ES    It will cause a serious accident   e Do not touch any electrical components for at least 3 minutes after turning OFF the main switch   e Check that the refrigerant piping setting and electrical wiring setting are for the same system  by  operating the indoor unit one by one     54    d  Depress    AUTO LOUVER       switch and check that the louver is activated normally without abnormal  sound  Depress    AUTO LOUVER    again so that the louver will stop  If abnormal sound is heard   remove the panel and adjust the fitting condition of connection parts in the panel corner cover   Ensure that the panel is mounted correctly to the unit body  otherwise the panel may be deformed   The temperature control will be invalid though the protection device will be activated during the test  run  If alarm occurs  find out the cause of abnormality according to Table 9 2    Alarm Code     And  again perform the test run after solving the problems    f  
26. 48    8 4 Charging Work    After vacuum pumping work  check that the gas stop valve  and liquid stop valve are fully closed   Charge the additional refrigerant  refer to Table 8 1  from the check joint of liquid stop valve  Charging    Refrigerant Amount Tolerance  0 5kg      If the specified refrigerant quantity can not be charged  follow the procedure below      1  Fully open the stop valve for gas     2  Operate the compressor at the cooling mode and add the refrigerant from the check joint of the  liquid stop valve  At this time  the liquid stop valve is slightly opened  Charging Refrigerant Amount    Tolerance  0 5kg      Outdoor Unit       Stop Valve   Liquid Line        Manifold  Stop Valve   Gas Line                           Nitrogen Tank   for Nitrogen Blow during Brazing  and Air Tight Test        Siphonic Refrigerant Cylinder   R410A                                                  Vacuum Pump Weigher  Gas Line  Liquid Line  Le a 2  S  e   a    if    oot Indoor Unit  alte  Branch Pipe Insulation  Cover the gas and liquid pipe with insulation            Charge the correct refrigerant quantity  according to Table 8 1  If not  a  compressor may be damaged due to an  excess or insufficient refrigerant charge                 Refrigerant charge from check joint of  gas stop valve may lead to compressor  failure  Be sure to charge refrigerant from  the check joint of liquid stop valve                 Insulate the liquid piping and gas piping  completely to avoid decreasi
27. 5  Is No 4 of DSW4  compressor forced stoppage  OFF                                                           Abnormal  Termination                             5  Turn No 4 of DSW5 OFF when the refrigerant amount is sufficient   Wait 3 minutes  at least  after turning No 4 of DSW5 OFF and then the outdoor unit is ready to operate   NOTE   The 7 segment indication during the check operation may be changed to the protection control code by  the activation of protection control  however it is normal  As for the protection control code  refer to the  sheet attached to the inside of the outdoor unit service cover           NOTE    1  Emissions of the fluorocarbons are prohibited    2  In case of disposal and maintenance of this product  collection of fluorocarbons is required    3  Regarding the fluorocarbon  the specification label or refrigerant label attached to the product should  be followed  After the additional refrigerant charge  record the total refrigerant    refrigerant before  shipment   additional refrigerant in the field  in the refrigerant label                       50    e Special Attention Regarding Refrigerant Gas Leakage    Pay attention to the critical gas concentration to avoid accidental refrigerant gas leakage before       installing air conditioning systems     Totally Charged Refrigerant Quantity in System  kg      lt  Critical Concentration  kg m      Room Space for each Indoor Unit  m       zier      In case of KHK S 0010  this value should be decided a
28. 5 0 N m    9 010 1 0 Nem          18 0 to 23 0 N m     4  When installing the unit in Australia  connect the both ends of shielded twist pair cable  remote control  switch cable and transmission cable  to the earth as shown bellow        K     Shielded Twist Pair Cable       Earth Earth             PCB1  for I U  to O U  for O U  to O U          Te2 BES                         Harness                                                                                                                                                                                                                                                                                                                                     Lifter Earth Wire  Shielded Twist    _  Shielded Twist Pair Cable  Pair Cable for between Outdoor Units  Indoor Unit to Transmission  Outdoor Unit Electrical Box  Terminal Board for Harness Lifter  Transmission Wiring  Fix the transmission wiring      2 Places  En  Earth Terminal Er  Fix with  ob eee  clamp band  Terminal Board for nee  Power Supply 2    Attach  N       Earth Wire En   Insulation Sleeve     I e  S Ki Cord Band S ly  T g Power Supply Wiring m      Cord Band   2 KL  Accessory   y   Cord Clamp  Accesso  B  Use an accessory screw    i For Power Supply Wiring    2 52  Knock out Hole   R  H H i Transmission Wiring  NS NOTE     d   Seal hermetically the entry of      conduit pipe by using putty or etc   TC  0    connection Hole for  for Water Protection   Connection H
29. 5 4 Foundation    e Concrete Foundations     1  The height of the foundation should be 150mm higher than the ground level    2  Install a drainage around foundation for smooth drain                 78    gas TT     mm               more than       d       Refrigerant   AE  H NAN    Mortar Hole    0100 x Depth 150    Drainage   Width 100 x Depth 20           d             100    more than  150mm or   400  Higher       A          LY  Z              Vibration  Proof Mat      Provide concrete foundation as shown in  the figure     CORRECT        Front Side of Unit    Foundation             Do not provide concrete foundation as  shown below  The foot of the outdoor unit  may be deformed     INCORRECT       Front Side of Unit       Foundation    sa  EA     3  Install the outdoor unit in the front rear and right left direction horizontally   Use a level gauge    Check to ensure that the gradient in four directions  front  rear  right and left  is within 10mm               Sy       Right Side  and Left Side     4  Provide a strong and correct foundation so that   a  The outdoor unit is not on an incline   b  Abnormal sound does not occur           Wiki     JA    Front Side  nd Rear Side    c  The outdoor unit will not fall down due to a strong wind or earthquake      5  When installing the outdoor unit  fix the unit by anchor bolts  field supplied    Refer to Fig  5 1 regarding the location of fixing holes                                                        Unit  mm   lt 86 KBtu h
30. According to the label    Checking of Outdoor Unit by 7 segment Display on PCB1    attached to the  rear side of the front cover of the outdoor unit  inspect temperature  pressure  operation frequency   and connected indoor unit numbers by the 7 segment displays    g  To end the test run  wait for 2 hours or push    RUN STOP    switch again     2    55    Table 9 1 Test Run and Maintenance Record    MODEL  SERIAL  No     CUSTOMER S NAME AND ADDRESS     10     11     12     13     14     15     16     17     18     19     20     21     56      Is the rotation direction of the indoor fan correct      Is the rotation direction of the outdoor fan correct      Are there any abnormal compressor sounds      Has the unit been operated at least twenty  20  minutes       Check Room Temperature  Inlet  No 1 DB  WB   C  No 2 DB  WB   C   Outlet  DB  WB   C  DB  WB   C     Inlet  No 5 DB  WB   C  No 6 DB  WB   C     Outlet  DB MWB   C  DB  WB   C       Check Outdoor Ambient Temperature    Inlet  DB   C  WB   C    Outlet  DB   C  WB   C      Check Refrigerant Temperature  Liquid Temperature    C  Discharge Gas Temperature    C      Check Pressure    Discharge Pressure  MPa  Suction Pressure  MPa    Check Voltage   Rated Voltage  Vv   Operating Voltage  L L  V   Starting Voltage  V   Phase Imbalance  Taa     Vm    Check Compressor Input Running Current  Input  kW    Running Current  A    Is the refrigerant charge adequate    Do the operation control devices operate correctly   Do the safety
31. B  fuse and main switch  S  to  each outdoor unit     2  Connect a power supply wiring to each indoor unit group to be connected to the same outdoor unit    Max  capacity of one indoor unit group is 250 KBtu h     Connect an ELB  fuse and main switch  S  to each indoor unit group     3  Connect the transmission wiring between indoor units and outdoor units  as shown in Fig  7 2  and 7 3     4  Connect the transmission wiring in the same refrigerant cycle unit   In case that the refrigerant pipe of  indoor unit is connected to the outdoor unit  connect the transmission wiring to the same indoor unit    Connecting the refrigerant pipe and transmission wiring to the different refrigerant cycle systems may  lead to malfunction     5  Use 2 Core lead wires such as shielded twist pair cable for the transmission wiring     Do not use 3 Core or over      6  Use the same kind of cables for the Hi NET system of the same refrigerant cycle     7  The transmission wiring is required to be separated from the power supply wiring    Keep at least 5cm between the transmission wiring and the power supply wiring  and also min  1 5m  between the transmission wiring and power supply wiring for other electrical device  If the above is not  secured  put the power supply wiring into the metal conduit tube to separate from other wirings     8  Connect the following transmission wiring to the terminals 1 and 2 of TB2 in the outdoor unit A  main  unit     e between outdoor unit and indoor unit  e betwe
32. Capacity  Excessive Refrigerant Charge  Failure of Thermistor   eoii Incorrect Wiring  Incorrect Piping Connection   oz Decrease  iniDischarge EES Expansion Valve Locking at Opened Position   Disconnect Connector   Insufficient Refrigerant Charge  Pipe Clogging   ee Failure of Thermistor  Incorrect Wiring   08 Increase in Discharge Gas Temperature Incorrect Piping Connection  Expansion Valve Locking  at Closed Position  Disconnect Connector   OA   Transmission   Abnormality between Outdoor and Outdoor Incorrect Wiring  Breaking Wire  Loose Terminals  A   Duplication of Address Setting for Outdoor Units  Ob NN Incorrect Outdoor Unit Address Setting  Sub Units  in Same Refrigerant Cycle System  utdoor Uni 8 SCH es  DC Incorrect Outdoor Unit Main Unit Setting Two  or more  SE RE  Exist in Same Refrigerant Cycle System  11 Inlet Air Thermistor  12 Sensor on Outlet Air Thermistor Incorrect Wiring  Disconnecting Wiring  13 Indoor Unit Freeze Protection Thermistor Breaking Wire  Short Circuit  14 Gas Piping Thermistor  19 Fan Motor Activation of Protection Device for Indoor Fan Fan Motor Overheat  Locking  21 High Pressure Sensor  22 Outdoor Air Thermistor  23   Sensor on Discharge Gas Thermistor on Top of Compressor Incorrect Wiring  Disconnecting Wiring  24 Outdoor Unit Heat Exchanger Liquid Pipe Thermistor Breaking Wire  Short Circuit  25 Heat Exchanger Gas Pipe Thermistor  29 Low Pressure Sensor             57                                                                      
33. DSW1 Ref  Cycle No  Setting DSW2   Capacity Setting  Setting is required  Setting No setting is required   Setting Before Shipment Position  DSW 86 96 114  On ON ON ON  pode wl Mass       oase  123456 123456   123456  1123456  Tens Digit Last Digit  Dsw1 psws 136 154  ON ON ON ON   EEEE kukk tale  Maan  123456 1234 123456  123456  Tens Digit Last Digit  DSW4  Test Operation and Service Setting   Emergency Operation    DSWS Test Operation and Service Settin  Setting is required    For Test Operation and p g  Operating Compressor No setting is required    Turn ON the dip switch  Setting Before Test Cooling Test Heating when use the below functions   Shipment Operation Operation Setting Before  ON ON ON Shipment  massas     anas    aneh a  123456   123456  1 23456 Banen  123456  Compressor Setting Item Pin No   gereed Stop Except No 1 Compressor Operation 1        B m Except No 2 Compressor Operation   2  123456 Refrigerant Amount Judgement 4  DSW6   Outdoor Unit No  Setting  Setting is required    Single Setting  IMPORTANT NOTICE   Setting Before Shipment  ee d  ON The outdoor unit is not single   WEIER the combination setting is necessary   1234 Be sure to do this setting           Combination Setting                                                                            UnitA Unit B Unit C   No 0 Unit     No 2 Unit     No 3 Unit   ON ON ON  BAe         nbat  1234 1234 1234  DSW3 DSW7  Power Supply Setting DSW10   Transmission Setting  INo setting is required  Setting is r
34. GER      Use refrigerant R410A in the refrigerant cycle   Do not charge oxygen  acetylene or other flammable and poisonous gases into the refrigerant cycle  when performing a leakage test or an air tight test  These types of gases are extremely dangerous  and can cause an explosion  It is recommended that compressed air  nitrogen or refrigerant be  used for these types of tests       Check to ensure that no pressure exists inside the stop valve before removing the flange     Ensure to connect the piping among the units in the same refrigerant cycle     6 1 Piping Materials     1  Prepare locally supplied copper pipes     2  Select the piping size from the Table 6 1 and Table 6 2     3  Select clean copper pipes  Make sure there is no dust and moisture inside of the pipes  Blow the  inside of the pipes with nitrogen or dry air  to remove any dust or foreign materials before connecting  pipes  Do not use any tools which produce a lot of swarf such as a saw or a grinder        e Cautions for Refrigerant Pipe Ends    When installing pipe through  the wall  secure a cap at the  end of the pipe    Correct Incorrect Correct Incorrect    Do not place the pipe    directly on the ground  Correct Incorrect    Om EX    Er Hole EJ  e    Attach a cap  or vinyl tape     O  SI     Z  dk    Attach a cap  or vinyl tape     Rain water can  enter     NS  Attach a cap  or vinyl bag with          rubber band        e Cautions for Piping Connection Work    1  Connect the indoor outdoor units with r
35. Hisense    Installation     amp     Maintenance  Manual    INVERTER DRIVEN    MULTI SPLIT    AIR CONDITIONER   HEAT PUMP       Outdoor Units      Model       AVWT 86U6SR    AVWT 96U6SR    AVWT 114U6SR       AVWT 136U6SS    AVWT 154U6SS    AVWT 182U6SZ       AVWT 190U6SZ    AVWT 210U6SZ    AVWT 232U6SZ       AVWT 250U6SZ    AVWT 272U6SZ    AVWT 290U6SZ             AVWT 307U6SZ    AVWT 328U6SZ    AVWT 345U6SZ       AVWT 365U6SZ    AVWT 386U6SZ    AVWT 402U6SZ       AVWT 426U6SZ    AVWT 444U6SZ    IMPORTANT     AVWT 460U6SZ    READ AND UNDERSTAND    THIS MANUAL BEFORE    USING THIS HEAT PUMP  AIR CONDITIONERS   KEEP THIS MANUAL FOR    FUTURE REFERENCE              ORIGINAL INSTRUCTIONS    IMPORTANT NOTICE      HISENSE pursues a policy of continuing improvement in design and performance of products   The right is therefore reserved to vary specifications without notice       HISENSE cannot anticipate every possible circumstance that might involve a potential hazard       This heat pump air conditioner is designed for standard air conditioning only  Do not use this heat pump  air conditioner for other purpose such as drying clothes  refrigerating foods or for any other cooling or  heating process       Do not install the unit in the following places  It may cause a fire  deformation  corrosion or failure      Places where oil  including machinery oil      Places where a lot of sulfide gas drifts such as in hot spring    Places where inflammable gas may generate or flow    Places w
36. Max  capacity of one indoor unit group is 250KBtu h     2  Check to ensure that the power supply voltage is within  10  of the rated voltage   If the power supply voltage is too low  the system cannot be started due to the voltage drop    3  Check the size of the electrical wires    4  In some cases  the packaged air conditioner may not be operated normally under the following cases     e Incase that the packaged air conditioner is supplied with the same power transformer as the device  with high electricity consumption     In case that the power source wires for the device  and the packaged air conditioner are located close  to each other        ex  Lift  container crane  rectifier for electric railway  inverter power device  arc furnace    electric furnace  large sized induction motor and large sized switch   For the cases mentioned above  induction surge of the power supply wiring for the packaged air  conditioner may occur due to a rapid change in electricity consumption of the device and an activation  of switch  Therefore check the field regulations and standards before performing electrical work in  order to protect the power supply wiring for the packaged air conditioner      5  Check to ensure that the earth wire of the outdoor unit  indoor unit     Terminal Board for Transmission Wiring       TT ar             Terminal Board for Power Supply                         Earth Wire            TB2 Lb  TE TB1 4 Cord Band  O SI EE    D       Plastic Band                     
37. aining in or over walkways to  prevent water dripping on people or the formation of ice in winter  In case of installing such a place   provide the additional drainage around the foundation    Do not install the outdoor unit in a space where a seasonal wind directly blows to the outdoor heat  exchanger or a wind from a building space directly blows to the outdoor fan     NOTES     1     Do not install the outdoor unit where there is a high level of oil mist  flammable gases  salty air or harmful    gases such as sulphur and an acid or alkaline environment       Do not install the outdoor unit where the electromagnetic wave is directly radiated to the electrical control  box     Install the outdoor unit as far as possible  being at least 3 meters from the electromagnetic wave radiator     5 3 Service Space    Make the service space when outdoor unit is installed as follows                                                                                                   Unit  mm   BS   Ai  zie    A      Vent Hole t    g  gt   y Front P Rear f  yy Side Side ku E  oO 1 1 Eed  S S Es 6    z ml  Vo CG SG    Y 4    T E  L 765   gt  lt  gt   Min  500   h2 2   Min  300   h1 2     lt  Side View  gt     1  Walls on 2 Directions  In case that the units are installed adjacent to tall  minimum rear side space is 300mm     In case of no walls at the front and the rear side of the  unit  the space of 500mm for the front side and 300mm  for the rear side is required     When the wall of front
38. al injury       NOTE is useful information for operation and or maintenance     A DANGER       Do not perform installation work  refrigerant piping work  drain pump  drain piping and electrical wiring  connection without referring to our installation manual  If the instructions are not followed  it may result in  a water leakage  electric shock or a fire       Use the adequate refrigerant  R410A  to the outdoor unit in the refrigerant cycle  Do not charge oxygen   acetylene or other flammable and poisonous gases into the refrigerant cycle when performing a leakage  test or an air tight test    These types of gases or extremely dangerous can cause an explosion  It is recommended that  compressed air  nitrogen or refrigerant be used for these types of tests       Do not pour water into the indoor or outdoor unit  These products are equipped with electrical parts   If poured  it will cause a serious electrical shock       Do not open the service cover or access panel for the indoor or outdoor units without turning OFF the main  power supply       Do not touch or adjust safety devices inside the indoor unit or outdoor units  If these devices are touched  or readjusted  it may cause a serious accident       Refrigerant leakage can cause difficulty with breathing due to insufficient air  Turn OFF the main switch   extinguish any naked flames and contact your service contractor  if refrigerant leakage occurs       Make sure that the refrigerant leakage test should be performed   Ref
39. als 1 and 2 for  Hi NET II     3  In case that alarm is indicated on the LCD of Main outdoor unit  follow the  7 segment  indication of the  Main outdoor unit for checking     4  Perform function setting from Main outdoor unit     5  Maximum refrigerant groups with one central controller are 64   Maximum indoor units to be connected are 160     380 415V 3N  50Hz                                                                                        Outdoor Unit A  Main  Outdoor Unit B  Sub   TB1 TB2    TB1 TB2     L1 L2 L3  N EAR  x L1 L2 L3  N 1 2 3 4     le  Q Q Q li 9191919 ofjofolo  H  Earth Earth  pups P  Main Switch TB   Terminal Board        PCB  Printed Circuit Board    Field Wiring           Transmission Line  Shielded Twist Pair Cable   DC5V  Non Pole Transmission Hi NET System   bne  S     Field Supplied  Main Switch xx   Optional Accessory    3N   380 415V 50Hz                                                                                                                                    CJ In Ze REH  Distribution Box or Pull Box Distribution Box or Pull Box Ss  C   Mai i i  Main Switch pe  a Dee     380 415V 50Hz   ra D HE D    lele d  EES IN ii 2E L1 L2 N  k i i   d    L      L 33    TB1 TB1   i  ELB   ELB No  0 No  1 i    Indoor Unit Indoor Unit   j  IN TB2   Remote TB2   Remote i    im Control Control ie ee  1 2 A B 1 2 A   H    220 240V 50Hz     ololole Cable     llo Cable lg A T E  AA  Shielded Twist AA  Shielded Twist     deii    TS Pair Cable  TS Pair Cab
40. at overload  may occur     2  For the system which all indoor units are not operated simultaneously  the total indoor unit capacity is  available up to 130  against the outdoor unit capacity     3  If the system is used in the cold area  ambient temperature becomes under  10  C  or under the high  heating load conditions  the total indoor unit capacity should be less than 100  against the outdoor unit  and total piping length is less than 300m     4  Compared to over 9 KBtu h of indoor units  7 KBtu h of indoor units are set with higher air flow Do not  install these units in the place where the cold draft may occur during heating operation  Determine the  usage environment and installation location carefully    If the unit is installed in such places  the number of connectable I U  should be less than the  recommended number on the table above        4  Transportation and Handling    4 1 Transportation    Transport the product as close to the installation location as practical before unpacking   When using a crane  hang the unit according to the description of the label attached to the outdoor unit     A DANGER    Do not hang the unit by the ropes at the wooden base           Rope Position          CORRECT INCORRECT            Wire Rope Wire Rope        Square Hole   Apply wire ropes   through square holes  Wooden  Base          Wooden  Base TT IT             1  Transportation and Storage    The corrugated paper frame is not sufficiently strong  therefore pay attention to th
41. case that the piping length between outdoor units is 2m or more  the oil trap should be provided for  the gas pipe so that accumulation of refrigerant oil may not occur       Less than 2m                               O       Indoor Unit Side                             lt        Less than 2m       Less than 2m J            2m or More                O    Indoor Unit Side                  n       Oil Trap  Min  200mm                                 Oil Trap  Min  200mm                                Less than 2m  2m or more           4  Place the outdoor unit pipe horizontally or with downward gradient towards the indoor unit side  or  refrigerant oil may accumulate in the pipe                                X                         Indoor Unit Side           lt  _    O    Indoor Unit Side    Refrigerant oil accumulates in the pipe                                                           21    22     5  For servicing  in case that the pipe is placed frontward of the outdoor unit  secure min  500mm  between the outdoor unit and Manifold Pipe   When the compressor is replaced  a space of  min  500mm is required      Min        6  Direction of Manifold Pipe  Place the Manifold Pipe vertically towards the ground  within  15    as shown in the figure     Outdoor Unit Outdoor Unit Outdoor Unit    O O Q                                  Manifold Pipe Manifold Pipe       O    TOG   within   15   x 5         6 4 Piping Connection  Perform the piping connection work for each outdoor un
42. ccording to the each country   s regulation such as ISO5149 and EN378     In the case that the calculated critical concentration is higher than 0 3kg m     take the following actions     1  Provide a gas leakage detector and exhaust fan s  controlled by its gas leakage detector    2  Provide each effective opening at the wall or door for ventilation to next door so that the critical gas  concentration can be maintained lower than the above value    Provide an opening more than 0 15  of floor surface at the lower part of a door      1  Maximum Permissible Concentration of HFC GAS R410A  The refrigerant R410A is an incombustible and non toxic gas   However  if leakage occurs and gas fills a room  it may cause suffocation  The maximum permissible  concentration of HFC gas  R410A in air is 0 3kg m     according to the refrigeration and air conditioning facility  standard  KHK S 0010  by the KHK  High Pressure Gas Protection Association  Japan  Therefore  some  effective measure must be taken to lower the R410A concentration in air below 0 3kg m    in case of leakage   As for R410A  this consideration is applied similarly     2  Calculation of Refrigerant Concentration   1  Calculate the total quantity of refrigerant R  kg  charged in the system connecting all the indoor units of  objective rooms    2  Calculate the room space where this unit is to be installed V  m    of each objective room    3  Calculate the refrigerant concentration C  kg m   of the room according to the follo
43. cted    e Regarding other optional remote control switch  wireless remote control or half size remote  control   follow    Installation  amp  Maintenance Manual    attached to each optional remote control  switch and perform the test run    e In case that the multiple indoor units are operated simultaneously controlled by one remote  control switch  check the connected number of indoor unit is indicated on LCD    e In case that the indicated number is not correct  the auto address function is not performed  correctly due to incorrect wiring  the electric noise or etc  Turn OFF the power supply and correct  the wiring after checking the following points   Do not repeat turning ON and OFF within 10  seconds     Power Supply for Indoor Unit is Not Turned ON or Incorrect Wiring    Incorrect Connection of Connecting Cable between Indoor Units or Incorrect Connection of  Controller Cable    Incorrect Setting of Rotary Switch and Dip Switch  The setting is overlapped   on the Indoor  Units PCB     b  Set the operation mode by pressing    MODE    switch   c  Press    RUN STOP    switch           The operation lamp will be turned ON before the test run starts   2 hour OFF Timer will be set automatically  and    OFF Timer    and    2HR    will be indicated on  LCD  Although the air flow initial setting is    HI     the setting can be changed     e Check the following operation range     P Cooling Operation Heating Operation    Indoor Minimum 21  C DB   15  C WB 15  C DB    Temperature 
44. e  For DC Fan Module  Fuse Capacity    40x4  Non Adjustable  3        380 415V 3N   50Hz A 20x 1 20x 1       59    60    Hisense Corporation  Add  17 Donghai Xi Road Qingdao 266071 China    P00397Q  2013 02 V01    
45. e and cause   and Check of  sludges  resulting in clogging or compressor failure    Pressures  Connection diameter is different  R410A  UNF 1 2    R407C  UNF7 16     x   Use the weight scale rl    Measuring Instrument  Ka   for Refrigerant  Charging    Vacuum  Drying Manifold Valve    Refrigerant  Charge Charging Hose    Charging Cylinder    Weight Scale    A        x  Refrigerant Gas       The current gas leakage detector  R22  is not Gas Leakage Check  Leakage Detector    applicable due to different detecting method        Interchangeability with R407C           3  Before Installation  3 1 Line Up of Outdoor Unit     lt  Base Unit  gt       Model    AVWT 36U6SR AVWT 96U6SR   AVWT 114U6SR   AVWT 136U6SS _  AVWT 154U6SS     lt  Combination of Base Units  gt         Model   AVWT 182U6SZ AVWT 190U6SZ AVWT 210U6SZ AVWT 232U6SZ AVWT 250U6SZ    AVWT 96U6SR AVWT 96U6SR AVWT 86U6SR AVWT 96U6SR AVWT 114U6SR  Combination  AVWT 86U6SR AVWT 96U6SR AVWT 136U8SS AVWT 136U6SS AVWT 136U6SS  Capacity KBtu h  307 328    Model   wues AVWT 290U6SZ AVWT 307U6SZ AVWT 328U6SZ AVWT 345U68Z    AVWT 136U6SS AVWT 136U6SS AVWT 154U6SS AVWT 86U6SR AVWT 96U6SR  AVWT 136U6SS AVWT 154U6SS AVWT 154U6SS AVWT 96U6SR AVWT 96U6SR        AVWT 154U6SS AVWT 154U6SS      Model   Lauras AVWT 386U6SZ AVWT 402U6SZ AVWT 426U6SZ AVWT 444U6SZ    AVWT 114U6SR AVWT 114U6SR AVWT 114U6SR AVWT 114U6SR AVWT 136U6SS    AVWT 114U6SR AVWT 114U6SR AVWT 136U6SS AVWT 154U6SS AVWT 154U6SS  AVWT 136U6SS AVWT 154U6SS AVWT 154U6SS AVWT 
46. e followings in  order to prevent the unit deformation     e Do not step or put any material on the product   e Apply two lifting wires onto the outdoor unit  when lifting it by crane   e Do not stack the product when storing   2  Transportation and Wire Rope  e To protect the unit  do not remove any packing   e Do not stack or put any material on the product   e Apply wire ropes on the both side of the unit as shown in the figure     Corrugated  Paper Frame                Apply rope on the  splints or corrugated  paper of more than  15mm thickness        Do not remove  corrugated paper  frame and plastic  bands                       Wooden Base    e Hanging Method    When hanging the unit  ensure a balance of the unit  check safety and lift up smoothly      1  Do not remove any packing materials      2  Hang the unit under packing condition with two  2  wire ropes  as shown in Fig  4 1     Wire Rope    Corrugated Paper Frame          Do not remove  corrugated paper frame  and plastic bands              Wooden Base                Apply rope through  the square holes                    Angle of wire rope  is more than 60                Apply rope on the splints or  corrugated paper of more than  15mm thickness              Do not apply any force  to thise place    Both Sides              Fig  4 1 Hanging Work for Transportation     3  Hang the unit without wooden base with two  2  wire ropes  as shown in Fig  4 2     Wire Rope    Corrugated Paper Frame                Rope Posi
47. ed wires   gt 0 75mm     for field wiring to protect electrically noise obstacle   Total length of    shielded wire shall be less then 1000m  and size of shielded wire shall comply with local codes        Check to ensure that the terminal for power source wiring  terminals    L1    to    L1    and    N    to    N    of each    terminal board  AC 380 415V    If not  some component will be damaged     9 2 Test Run     1  Check to ensure that the stop valves of the outdoor unit are fully opened and then start the system      In case of the combination of base units  check that the stop valves of all the connected outdoor units  are fully opened       2         Perform the test run of indoor units one by one sequentially and then check accordance of the  refrigerant piping system and electrical wiring system   If the multiple indoor units are operated  simultaneously  the system can not be inspected the system accordance       3     lt      Perform the test run according to the following procedure  Ensure that the test run is carried out  without any problem     NOTE   In case of 2 remote control switch  main and sub   firstly perform the test run of the main remote  control switch     a  Set the    TEST RUN    mode by pressing the    MODE    and    CHECK    switch of controller simultaneously  for at least 3 seconds          TEST RUN    is displayed on the LCD   The total number of the indoor units connected is indicated on the LCD   Hi 1 on Example when 5 indoor units are conne
48. efrigerant pipes  Fix the pipes and pay attention not to contact  with weak materials such as ceiling   Otherwise  abnormal sound may be heard due to the vibration of  the piping      2  Apply refrigerant oil slightly on the sheet surface of the pipe and flare nut before Apply Refrigerant Qil   the flaring work  And then tighten the flare nut with the specified tightening CTE  torque using two spanners  Perform the flaring work on the liquid piping side  before the gas piping side  Check the gas leakage after the flaring work  LI  NOTE    Refrigerant oil is field supplied  KD   Ethereal Oil FVC68D     3  In case that temperature and humidity inside the ceiling exceed 27  C RH80   apply additional  insulation  approx  10mm thickness  to the accessory insulation  It prevents dew condensation on the  surface of the insulation  refrigerant pipe only      4  Perform the air tight test  4 15MPa for the test pressure      5  Perform cold insulation work by insulating and taping the flare connection and reducer connection   Also insulate all the refrigerant pipes        e When tightening the flare nut  use two spanners     Do not apply the two spanners work here   Refrigerant leakage shall occur     a       ECH    Fa    Two Spanners Work Tightening Work for Stop Valve  Liquid           Do not apply excessive force to the flare nut when tightening  If applied  the flare nut may crack  due to aged deterioration and refrigerant leakage may occur  Use the specified tightening torque     
49. en outdoor unit and indoor unit in other refrigerant cycles     9  Do not connect the power supply wiring to the terminal board for transmission wiring  TB2    Printed circuit board may be damaged      10  Connect the earth wire for the outdoor indoor  The earth wiring work under the    condition of 100Q  max   ground resistance should be performed by the qualified person     e Transmission Wiring    40                                                                                                                                                                    Refrigerant Group 1 Refrigerant Group 2  Outdoor Unit Outdoor Unit Outdoor Unit Outdoor Unit   Main   Sub   Main   Sub   TB  TB  TB  TB  TB  TB  TB  TB   LifL2 La  N 3 4 LilL2 La N  1 2 3  4  OOlOO OOiOOlOlc  Transmission Wire  for Main   Sub  Hi NET II  Transmission Wire                                                                                                                                                                                  BIA BIA  TBz TBz       BIA BIA BIA  TB2 TB2 TB2       BIA  TB                                         TB  TB  TB  TB  TB  TB   Unit No  0 Unit No 1 Unit No  2 Unit No 0 Unit No 1 Unit No  2          Indoor Unit Indoor Unit Indoor Unit Indoor Unit Indoor Unit Indoor Unit                   NOTES   1  For the combination units  182 460KBtu h   DSW settings of Main and Sub are required     2  Alarm occurs if the transmission wires between outdoor units are connected to the termin
50. equired  Setting is required                    380 415V Unit  380 415V Setting Before Shipment       ON          ON       T          anys    380 415V                            For End Resistance Cancellation          Setting Before End Resistance  Shipment Cancellation  He  Tag  12 12                            If the transmission circuit fuse is short circuited   the printed circuit board PCB1 will be recovered  only once by turning DSW10  2 pin on           Fig  7 4 DSW Setting       e Setting for Transmitting  It is required to set the outdoor unit Nos   refrigerant cycle Nos  and end terminal resistance for this Hi NET  or Hi NET Il system     e Setting of Outdoor Unit No   In case of the combination of base unit  set DSW6 as shown below     Combination of Base Unit    Base Unit       Before Shipment  Unit A   Unit B Unit C   No 0   Main   No 2   No 3     e Setting of Refrigerant Cycle No   In the same refrigerant cycle  set the same refrigerant cycle No  for the outdoor unit and the indoor units  as shown below   As for setting indoor unit refrigerant cycle No   set the RSW2 and DSW5 on the indoor unit PCB     Setting Switch    10 digit 1 digit Ex   In Case of Setting Refrigerant Cycle No  25          Setting Position    SE ol   or lai i m W Setby neering ee i G SKS  I G x    into the groove  123456    Outdoor Unit DSW1 RSW1 Turn ON No  2 pin  Set Dial No 5   NE DSW5 RSW2 DSW and RSW setting before shipment is 0   Maximum in setting refrigerant cycle No  is 63   Settin
51. g      5  Insulate the gas pipe and liquid pipe completely      6  Mount the piping cover equipped with the outdoor unit after the piping connection   If not  the unit may damaged due to snow or rain water entering     Table  6 3 Tightening Work of Flare Nut  Required Tightening Torque  JIS B8607   Pipe Size Tightening Torque   66 35  1 4  14 to 18         9 53  318      m     12 7  1 2    49 to 61 Se m   919 05  3 4     e Details of Stop Valve Piping Connection    86   KBtu h   96   KBtu h      Stop Valve Stop Valve      Stop Valve  Liquid      Stop Valve  Liquid     4 Si  Liquid Pipe    a  Field Supplied  Socket Liquid Pipe   Field Supplied      Field Supplied   Accessory Pipe  B  Gas Pipe z  Elbow    Field Supplied     Field Supplied   5 Gas Pipe  Es Gas Pipe  Field Supplied   9 Et   Field Supplied   Field Supplied     114  KBtu h   136   KBtu h                                 Stop Valve S Stop Valve    d    Stop Valve  Liquid  g ai    Stop Valve  Liquid                          Accessory Pipe     Socket ee   Pa  Field Supplied     pipe a  u d U    Field Supplie  hans e Accessory Pipe  B  Gas Pipe g PP  Pea Liquid Pipe  Field Supplied   A   Gas Pipe U J  Field Supplied  Gas Pipe        Field Supplied        Field Supplied        Elbow   Field Supplied   armen  SSES    Stop Valve       a  Valve  Liquid           e 8 Pipe       Field Supplied   Elbow Accessory Pipe  B  EEEN Supplied        Gas EN     Field Supplied   J    NOTES   1  Ensure that the closing pipe of the gas st
52. g Switch  10 digit 1 digit    oN Fe m oo N e SR Setting of End Terminal Resistance  DSW10    Outdoor Unit DSW1 DSW8 Before Shipment Cancellation  ON      ON  Indoor Unit DSW5 RSW2 Au NN  Hi NET II 1 2 OFF   1 2  OFF    e Setting of End Terminal Resistance    Before shipment  No  1 pin of DSW10 is set at the    ON     side  In the case that the outdoor units quantity in the  same Hi NET or Hi NET Il is 2 or more  set No  1 pin  of DSW10 at the    OFF    side from the 2nd refrigerant  group outdoor unit  If only one outdoor unit is used   no setting is required                                                                                                                                                                                                                                                                                                        Turn OFF DSW10 No 1 pin for cancel of Turn OFF DSW10 No 1 pin for cancel of  end terminal resistance setting    Geng end terminal resistance setting  Geng    on fig   on  BE    orr D    or MB        ee eke eee eee En  Outdoor Unit l Outdoor Unit   a Outdoor Unit Outdoor Unit   l   1  i   mS l  DSW10   DSW10 DSW10 DSW10 DSW10 DSW10 DSW10  Pu   OT DN Au WW Pa l Wu  12 I 12 12 12 12 12 I 12  i Unit A Unit B 1  i  Main   Sub   Sub   Main   Sub     l I  1        Transmission Line   Hi NET II or Hi NET        Transmission Line   Hi NET II or Hi NET     Transmission Line   Hi NET II or Hi NET                     Indoor Unit               
53. g work  or a periodical check is performed     Protect the wires  electrical parts  etc  from rats or other small animals   If not protected  rats may gnaw at unprotected parts and which may lead to a fire     Avoid the wirings from touching the refrigerant pipes  plate edges and electrical parts inside the  unit  If not do  the wires will be damaged and at the worst  a fire will occur     Use a medium sensing speed type ELB  Earth Leakage Breaker  activation speed of 0 1 sec  or  less   If not used  it will cause an electric shock or a fire     Fix the cables securely  External forces on the terminals could lead to a fire     Tighten screws according to the following torque   M4  1 0 to 1 3 N m  M5  2 0 to 2 4 N m  M6  4 0 to 5 0 N m  M8  9 0 to 11 0 N m  M10  18 0 to 23 0 N m    33    7 1 General Check     1  Make sure that the field selected electrical components  main power switches  circuit breakers  wires   conduit connectors and wire terminals  have been properly selected according to the electrical data  indicated in the Technical Catalog  Make sure that the components comply with National Electrical Code   NEC     e Supply electrical power to each outdoor unit  An ELB  fuse and main switch should be used for each  outdoor unit  If not  it will be cause of fire or electrical shock   e The power supply for the indoor unit and outdoor unit should be provided separately   Connect a power supply wiring to each indoor unit group to be connected to the same outdoor unit    
54. here strong salty wind blows such as coast regions    Places with an atmosphere of acidity or alkalinity       Do not install the unit in the place where silicon gas drifts  If the silicon gas attaches to the surface of heat  exchanger  the fin surface repels water  As a result  drain water splashes outside of the drain pan and  splashed water runs inside of electrical box  In the end  water leakage or electrical devices failure may  occur       Pay attention to the following points when the unit is installed in a hospital or other facilities where  electromagnetic wave generates from medical equipment    Do not install the unit in the place where the electromagnetic wave is directly radiated to the electrical  box  remote control cable or remote control switch     Install the unit at least 3 meters away from electromagnetic wave such as a radio        Do not install the unit in the place where the breeze directly catches the animals and plants  It could  adversely affect the animals and plants       The installer and system specialist shall secure against leakage according to local regulations or  standards  The following standards may be applicable  if local regulations are not available   International Organization for Standardization  1505149 or European Standard  EN378 or Japan Standard   KHKS0010       No part of this manual may be reproduced without written permission       It is assumed that this heat pump air conditioner will be operated and serviced by English speak
55. ing people   If this is not the case  the customer should be add safety  caution and operating signs in the native  language       If you have any questions  contact your distributor or dealer of HISENSE      This manual gives a common description and information for this heat pump air conditioner which you  operate as well for other models       This heat pump air conditioner has been designed for the following temperatures  Operate the heat pump  air conditioner within this range       This heat pump air conditioner has been designed for the following temperatures  Operate the heat pump  air conditioner within this range     Temperature    C     Cooling Indoor 32 DB 23 WB 21 DB 15 WB    Heating Indoor  Operation Outdoor          DB  Dry Bulb  WB  Wet Bulb      The temperature may change depending on the outdoor unit     This manual should be considered as a permanent part of the air conditioning equipment and should  remain with the air conditioning equipment     IMPORTANT NOTICE    Correct Disposal of this product    This marking indicates that this product should not be disposed with other  household wastes  To prevent possible harm to the environment or human  health from uncontrolled waste disposal  recycle it responsibly to promote the  sustainable reuse of material resources  To return your used device  please use  the return and collection systems or contact the retailer where the product was  purchased  They can take this product for environmental safe recycling    
56. int for Service Port  Only the charging hose   can be connected   Tightening Torque  9 to 14N m            Refrigerant Pressure    Gas Valve             Tightening Torque  KBtu h a  N m   86 to 114 18 to 22  136 to 154 20 to 25           lt  Liquid Valve  gt     Check Joint for Service Port  Only the charging hose   can be connected   Tightening Torque  14 to 18 N m              Cap  Tightening Torque  33 to 42 N m          Hexagonal Wrench Refrigerant  To open or close Pressure  spindle valve Doen  lt            Spindle Valve  Counterclockwise   Open  Clockwise    Close  Tightening Tor               Do not apply an abnormal big force to the spindle valve at the end of opening   The back seat construction is not provided     At the test run  fully open the spindle  If not fully opened  the devices will be damaged     26    6 4 5 Piping Connection     1  Make sure that the stop valves are closed completely      2  Protect the compressor and sound proof cover with metal plate when brazing the gas  pipe as shown in Fig  6 2   Pay attention to the flame from the burner not to burn the stop valve body      3  Connect the indoor unit and the outdoor unit with refrigerant piping   Prevent the refrigerant piping from touching weak parts of the building such as wall  ceiling  etc    Abnormal sound may occur due to the vibration of the piping       4  As for the flaring work of the field pipe  use the specified tightening torque in Table 6 3   Put nitrogen gas into the pipe when brazin
57. ipe size of gas liquid line from the outdoor unit Manifold Pipe 1 to first branch  should be increased one size with the reducer  field supplied       3   If the refrigerant piping length is more than 100m  no need to increase the pipe size after first branch  If the  Branch Pipe size is larger than the first branch  adjust the Branch Pipe size to the first branch  In case that the  selected pipe size after the first branch is larger than the pipe size before the first branch  use the same pipe size  as before the branch      4   The pipe diameter EN should be the same as the indoor unit piping connection size      5   When the liquid piping length is longer than 15m  use 69 53 pipe and reducer  field supplied       6   Keep the direct distance of 500mm or more after the Manifold Pipe      7   The condition of refrigerant piping installation is different depending on the connected indoor unit quantities      8   Allowable total piping length may become shorter than 1 000m due to the limitation of maximum additional  refrigerant amount    NOTES     1  Check the gas pipe and liquid pipe are equivalent in terms of the piping length and piping system    2  Use a Branch Pipe  system components  for the branch pipe of indoor unit    3  Install the indoor unit and Branch Pipe according to each    Installation  amp  Maintenance Manual       4  If the piping length  L3  between each Branch Pipe and each indoor unit is considerably longer than other indoor unit   refrigerant may not fl
58. iring  for telephone        Connect a fuse of specified capacity        Before performing any brazing work  check to ensure that there is no flammable material around   When using refrigerant be sure to wear leather gloves to prevent cold injuries       Protect the wires  electrical parts  etc  from rats or other small animals   If not protected  rats may gnaw at unprotected parts and which may lead to a fire       Fix the cables securely  External forces on the terminals could lead to a fire     Provide a sufficiently strong foundation  If not  the unit may fall down and it may lead to injuries       Do not install the unit in a place where oil  vapor  organic solvent and corrosive gas  ammonia  sulfur  compound and acid  may be present in quantities   It may cause refrigerant leakage due to corrosion  electrical shock  deteriorated performance and  breakage       Perform electrical work according to Installation Manual and all the relevant regulation and standards   If the instructions are not followed  an electrical shock and fire may occur due to insufficient capacity and  inadequate performance       Use specified cables between units and choose the cables correctly  If not  an electrical shock or fire may  occur       Ensure that the wiring terminals are tightened securely with the specified torques  If not  generating fire or  electrical shock at the terminal connection part may occur     ACAUTION      Do not step or put any material on the product     Do not put any f
59. it     NOTE   Ensure that the refrigerant pipe should be connected to the same refrigerant cycle unit     e Prepare the refrigerant pipe in the field for the piping work   Refer to Fig  6 1 for the position of piping connection                                                                                                                             2  B g T  l e a S  Gas Line Refrigerant Piping   H  Connection 0      D     2       D      E  x      EPE  sl DI 0  Liquid Line Refrigerant Piping ofa  Connection Ss 85  40 00  e  Q O E  y  VE B el  kk kl i  a l SE A Gas Line Refrigerant Piping  mm   285 Connection Model   KBtu h A   B C D  S S B Liquid Line Refrigerant Piping  Connection sl 55   185   345       Fig  6 1 Refrigerant Piping Connection    e Piping Direction  Fix the pipes adequately in order to avoid vibration and excessive force to the valve      1  The pipes are available to connect in three directions   front  rear or bottom side  from the bottom base   For the vibration protection  properly fix the piping  connection and check that no excessive force applied to  the stop valve     Rear Side       Bottom Base Bottom Side     2  Operation of the stop valve should be performed according to Item 6 4 4    3  Connect the pipes according to Table 5 1 and this     Installation  amp  Maintenance Manual       4  Completely seal the penetration part of the bottom Gas Pipe  pipe with insulation in order to prevent rain water A  Pipe Cover X    Liquid Pipe       entering into
60. l  Insulate the unions and flare nuts at the  piping connections completely  Insulate the liquid  piping and gas piping completely to avoid decreasing  of performance and dewing on the surface of the pipe         Insulation   Field Supplied     Refrigerant Piping     Field Supplied     Fig  8 2 Insulation on Pipes    47    8 3 Additional Refrigerant Charge Calculation    Table 8 1 Additional Refrigerant Charge Calculation  Although refrigerant has been charged into this unit  additional refrigerant charge is required according to  piping length   Determine the additional refrigerant quantity according to the following procedure  and charge it into the system   Record the additional refrigerant quantity to facilitate maintenance and servicing activities thereafter     1  Calculating Method of Additional Refrigerant Charge  W kg     No    Symbol Contents Additional Charge  kg     1 Additional Refrigerant Charge Calculation for Liquid Piping  W1 kg        Total Piping Length   Refrigerant Amount   Additional Charge   m  for 1m Pipe  kg   22 2   0 36      Pipe Diameter          19 05 x0 26         615 88 x0 17    012 7 x0 11     09 53 x0 056     66 35 m x0 024    Total Additional Charge For Liquid Piping                                 2 Additional Refrigerant Charge Calculation for Indoor Unit  W2 kg   Additional refrigerant charge is 1kg unit of 76KBtu h and 96KBtu h indoor unit   Additional refrigerant charge of less than 76KBtu h indoor units is not needed        86 and 96 To
61. le  E            Remote  Control  Switch         yx Remote  Control  Switch             No  0 System Indoor Units No 1 System Indoor Units    Fig  7 2 Instruction for Electrical Wiring Connection    41    7 5 Dip Switch Setting of Outdoor Unit    TURN OFF all power sources before setting   Without turning OFF  the switches do not work and the contents of the setting are invalid    However  DSW4 No 1  2  4 can be operated during power source is ON      The mark of    W    indicates the position of dip switches  Set the dip switches according to the Fig 7 4     NO    TE      By using switch DSW4  the unit is started or stopped after 10 to 20 seconds  after the switch is operated       Number this outdoor unit to distinguish from other outdoor units for service    42    and maintenance     And write the number in the space right                                                                                                                                                                                                                                                                                                                                                                                                                                Arrangement of Dip Switch Setting Push Switches  Coho og Psw2 psw2   ew PSW2  LJ LI LI LI PSWS5   PSW1   PSW3 DSW4 DSW5 For EE  SEG2 SEG1 Fane naw  2 PSW5  lt   PSW1  p  PSW3  DSW1  1 Rsw1 For v Enter For  Checking Sau Checking  BSW For Checking  
62. mp   8 BE Cutter   13   Gauge Manifold   18   Hoist   for Indoor Unit            Megohmmeter Hexagon Wrench Gas Leak Detector Voltage Meter    Use tools and measuring instruments only for the new refrigerant R410A which is directly touch to refrigerant     A DANGER    The pressure of refrigerant R410A is 1 4 times higher than that of conventional refrigerant  impurities  such as moisture  oxide film  and grease affect easily R410A  Be sure to remove any moisture  dust   different refrigerant or refrigerant oil from the refrigerant cycle    Therefore  if the specified materials are not used  it may cause explosion  injury  leakage  electrical  shock or fire     NOTICE    Check the design pressure for this product is 4 15MPa    To avoid accidental mixing of the different refrigerant or different refrigerant oil  the sizes of the  charging connections have been changed    It is necessary to prepare the following tools before performing the installation work     oa     lt   Interchangeability is available with current R22     only for Refrigerant R410A  No Interchangeability with R22   X  Prohibited    only for Refrigerant R407C  No Interchangeability with R22     Interchangeabilit  with oie ne Reason of Non Interchangeability and Attention        Strictly Required   Chamfering Reamer   i 7 Removing Burrs   Flaring Tool ve Ka   The flaring tools for R407C are applicable to R22  Flaring for Tubes  i   If using flaring tube  make dimension of tube larger   Dimensional Control  ease
63. n 57 15 88    H2  5710 66 1905        86 to 114   22 2   9 53   al lo ol lm ul lo  114 to 154 25 4 12 7  154 to 172 ect ica Indoor SR  172 to 250 28 6 15 88 Unit Unit Unit                     25010345   31 75   19 05      Over 345     4   Pipe Diameter between Branch Pipe and Indoor Unit    4     indoor Unit  KBtu        07 to 14 6 35     5     17 to 18 15 88 6 35   5   22 to 54 15 88 9 53          e Piping Work Conditions    Allowable Piping Length   7      lt  the recommended  gt  the recommended  connectable number connectable number  of Indoor Unit of Indoor Unit     lt  1 000m   8   lt  300m       Total Liquid Piping    Total Piping Length Actual Length    B SCH Actual Length  Maximum Piping Length    Equivalent Length       Maximum Piping Length between          Branch Pipe of 1st Branch and Each Indoor Unit k zom SC  Maximum Piping Length between     Each Branch Pipe and Each Indoor Unit L3  lt  40m zaam  Piping Length between Manifold Pipe 1 and  lt i0m  lt  10m    Each Outdoor Unit    Height Difference between O U  is Higher H1  Outdoor Units and Indoor Units   O U isLower     O U isLower   is Lower       Height Difference between Indoor Units  lt  15m  lt  15m  Height Difference between Outdoor Units H5  lt  0 1m  lt 0 1m       30      1      The Manifold Pipe is counted from the indoor unit side  as Manifold Pipe 1        2   When the maximum length of the equivalent refrigerant pipe  L1  from the outdoor unit Manifold Pipe 1 to the  indoor unit is over 100m  the p
64. ng of  performance and dewing on the surface  of the pipe                 Insulate the flare nut and union of the  piping connection with insulation                       Check to ensure that there is no gas  leakage  If a large refrigerant leakage  occurs  it will cause difficulty with  breathing or harmful gases would occur if  a fire was being used in the room                 49    8 5 Automatic Simple Judgement System for Refrigerant Amount    Perform the refrigerant amount check operation according to the automatic judgement function after the  refrigerant charging work    When the judgement result is excessive refrigerant  insufficient refrigerant or abnormal termination  find out  the cause of abnormality and perform the refrigerant amount check operation again      lt  Procedure of Refrigerant Amount Check Operation  gt     1  Reassemble all the cover except for the electrical control box cover and service cover of No 1 unit     2  Turn ON the power supply of indoor unit and outdoor unit in the refrigerant cycle to be performed the  refrigerant amount check operation    Supply electrical power to the system 12 hours before starting this check operation to warm the  compressor oil      3  Turn No 4 of DSW5  PCB1  ON   7 segment Display     4  Check the 7 segment display and press PSW1   The outdoor fan and compressor will be activated and the 7 segment display will be indicated the  following figure     The judgement takes 30 to 40 minutes    Refer to the table below f
65. o the table for the outdoor unit model  the Manifold Pipe model and the piping diameter          25    6 4 4 Stop Valve     lt  Gas Valve  gt          2   3   4   5    1  Make sure that the all the spindles are closed completely   Connect the charging hose to the service port and release gas from the gas pipe   Cut the end of the closing pipe  6 35  and check that no gas exists inside the gas pipe      Remove the stop valve cover   Remove the closing pipe from the brazing portion by using a burner     Pay attention to the flame from the burner not to burn the stop valve body           Spindle       Gas Valve                                              Service Port       Gas Pipe                                        Details of Closing Pipe  Lou Position       Cut Here     6 35 Pipe             Closina Pipe    Stop Valve Cover    Brazing Portion of       __  Closing Pipe    Sound Proof Cover       Stop Valve        Compressor          Burner               Ensure that there is no gas inside the pipe when removing the closing pipe   Otherwise  the pipe may be blown out and it may lead to injury     Protect the return oil pipe and vibration proof of the compressor with the metal plate when using    a burner     e The details of stop valves are as follows      lt  Gas Valve  gt   Cap       Tightening Torque  50 to 58N m    Hexagonal Wrench    To open or close  spindle valve  SES  ZX  ISN    Spindle Valve  Counterclockwise   Open  Clockwise                    Close       Check Jo
66. ole for aE   Power Supply Wiring  Power Supply Wiring  952  2 Places    052  2 Places  Cord Clamp   Connection Hole for For Operation Wiring   For fixing power supply wiring  Transmission Wiring  26  Knock out Hole        38       Pay attention to the followings to run through the cables under the unit using conduit tube    The pipe cover is required to remove before performing piping and wiring works      NOTES     1  Do not lead the power supply wiring and transmission wiring through the same conduit tube   Moreover  keep at least 5cm between the power supply wiring and transmission wiring     2  Cut cross line at rubber bush  accessory  and securely attach it to the knock out hole for cable  protecting     3  Attach the pipe cover to avoid entering rats or other small animals into the unit   4  Avoid the wirings from touching the refrigerant pipes  plate edges and electrical parts inside the unit     5  Completely seal the end of conduit tube with sealing materials to avoid entering rain into the conduit  tube     6  Make a drain hole at the lowest part of the conduit tube     Liquid Piping        Transmission Wiring    Power Supply Wiring    Tightly secure the power source wiring using  the cord clamp inside the unit     NOTE    Fix the rubber bushes with adhesive when conduit  tubes to the outdoor unit are not used     Rubber Bush    39    74 Electrical Wiring Connection of Indoor Unit  Outdoor Unit     1  Connect a power supply wiring to each outdoor unit  Connect an EL
67. op valve  1 place  is removed firstly   2  Refer to the item 6 2 for the flaring work        27    e Manifold Pipe  Optional Parts   Item Operation Type Outdoor Unit Model   KBtu h  Number  for Cooling Heating    Manifold Pipe  Changeover  Operation          e Construction Example  In Case of AVWT 345U6SZ    Regarding the piping work for 190KBtu h and over  refer to Installation  amp  Maintenance Manual attached to the  Manifold Pipe    lt  Front Side or Rear Side Piping Connection  gt     Outdoor Unit A          Manifold Pipe 1     l   Gas         1 Outdoor Unit B                        Field Supplied     Liquid Piping    gt     Gas Accessory Pipe    i     Gas Piping i     Field Suppljed              Manifold Pipe 2       Gas  d                           Outdoor Unit C          Gas Accessory Pipe   Field Supplied  i                                         Field Supplied       Manifold Pipe 1 i   Liquid        i  Liquid Accessory i  Pipe al  S A J   Field Supplied     dr 424  ssl Ss Die  Liquid Piping Sy Os              Field Supplied  Liquid Accessory  Pipe   Field Supplied     Manifold Pipe 2 Liquid Piping Gas Piping   Liquid   Field Supplied    Field Supplied                 Gas Piping   Field Supplied                        lt  Downward Piping Connection  gt     Outdoor Unit A       Manifold Pipe 1   Gas         3 fe   8 Kaes Le    Gas Piping     JX 4 yY   Field Supplied        Liquid Piping     Field Supplied  S               Outdoor Unit B  H     i    1  Ba Outdoor Unit
68. or the result indication    When the judgement result is excessive refrigerant  insufficient refrigerant or abnormal termination   find out the cause of abnormality and perform the refrigerant amount check operation again     Judgement Result Indication  T segment Result Remarks  Indication      Sufficient The refrigerant amount is sufficient   Refrigerant Turn No 4 of DSW5 OFF and perform Test Run     The refrigerant amount is excessive   Excessive Calculate the additional refrigerant amount according to the piping length   Refrigerant Collect the refrigerant using a collector and charge the correct refrigerant  amount   The refrigerant amount is insufficient   Insufficient Check if the additional refrigerant has been charged   Refrigerant Calculate the additional refrigerant amount according to the piping length and  charge the refrigerant   Find out the cause of abnormal termination as shown below  After resolved the  cause of abnormal termination  restart the check operation    1  Is No 4 pin of DSW5 ON before turning on the power supply    2  Are all indoor units ready and waiting  before turned ON No 4 pin of DSW5    3  Is the outdoor ambient temperature within the applicable range   5 to 43  C     In some cases  when the connected indoor unit number exceeds the  recommended number and the outdoor ambient temperature exceeds 35  C   this check operation cannot be performed     4  Is the total indoor units operation capacity 30   indoor units capacity ratio  or  less    
69. oreign material on the unit or inside the unit       Provide a strong and correct foundation so that   a  The outdoor unit is not on an incline   b  Abnormal sound does not occur   c  The outdoor unit will not fall down due to a strong wind or earthquake      The appliance is not to be used by children or person with reduced physical  sensory or mental capabilities   or lack of experience and knowledge  unless they have been given supervision or instruction concerning use  of the appliance by a person responsible for their safety      Children should be supervised that they do not play with the appliance        Do not install the indoor unit  outdoor unit  remote control switch and cable within approximately 3 meters  from strong electromagnetic wave radiators such as medical equipment       Supply electrical power to the system to energize the oil heater for 12 hours before startup after a long  shutdown       Make sure that the outdoor unit is not covered with snow or ice  before operation       In some cases  the packaged air conditioner may not be operated normally under the following cases     In case that electrical power for the packaged air conditioner is supplied from the same power  transformer as the device        In case that the power source wires for the device  and the packaged air conditioner are located close to  each other     electric furnace  large sized induction motor and large sized switch     Device    Ex  Lift  container crane  rectifier for electric 
70. ow well and also performance may be deteriorated compared to other models    Recommended Piping Length  within 15m     31    e Piping Branch Restriction  Follow the table below when performing the field supplied piping work        Piping Length between Main Piping Branch     Indoor Unit  Branch Pipe  First Branch    Piping Length Capacity Ratio  and Each Indoor Unit  L2  After Branch Piping Branch After Main Branch  atb c  lt  30m  or without Limit  atb c  gt  30m  and within 2  dtetf  gt  30m  within 41m to 90m  NOTE       Main Piping Branch  Distribution from One  1  Branch Pipe to Two  2  Branch Pipes  The number of main piping branch depends on the piping length after branch  a to f       lt  40m                                                               a b  C  Main Piping Branch  Indoor Indoor  Unit Unit  e  f  Indoor Indoor  Unit Unit  x Main piping branches are 2 portions  x Indoor unit capacity ratio is less than 40    Within 41   90m Within 41   90m                   Indoor Unit Capacity Ratio  20     E CH Indoor Unit Capacity Ratio      80                           First Main Branch First Main Branch          IO          Second Main Branch             Fig  1 Fig  2    32    7     Electrical Wiring    Turn OFF the main power switch to the indoor unit and the outdoor unit and wait for more than  3 minutes before electrical wiring work or a periodical check is performed     Check to ensure that the indoor fan and the outdoor fan have stopped before electrical wirin
71. railway  inverter power device  arc furnace   It consumes a large quantity of electrical power     Regarding the cases mentioned above  surge voltage may be inducted in the power supply wiring for the  packaged air conditioner due to a rapid change in power consumption of the device and an activation of  switch    Therefore  check the field regulations and standards before performing electrical work in order to protect  the power supply for the packaged air conditioner     NOTE      It is recommended that the room will be ventilated every 3 to 4 hours       The heating capacity of the heat pump unit is decreased according to the outdoor air temperature   Therefore  it is recommended that auxiliary heating equipment be used in the field when the units is  installed in a low temperature region       Operate the heat pump air conditioner within this range   Regarding installation altitude below 1000m   Regarding frequency of supply power within  1 Hz of rated frequency   Regarding transport   storage temperature within  25 55  C     2  Structure    2 1 Outdoor Unit  amp  Refrigerant Cycle  Regarding structure drawings and refrigerant cycle diagram  please refer to Technical Catalogue     2 2 Necessary Tools and Instrument List for Installation    wl Toot  Nel Tool  no  Too  Del Toor           1   Handsaw   6   Copper Pipe Bender   11   Spanner   16   Leveller    ge F f 8   Camper for  2  Phillips Screwdriver 7  Plier 12   Charging Cylinder 17 Saidarase Terminals    3   Vacuum Pu
72. rigerant  Fluorocarbon  for this unit is incombustible  non toxic and odorless   However if the refrigerant is leaked and is contacted with fire  toxic gas will generate   Also because the fluorocarbon is heavier than air  the floor surface will be filled with it  which could cause  suffocation       The installer and system specialist shall secure safety against refrigerant leakage according to local  regulations or standards       Use an ELB  Earth Leakage Breaker    In the event of fault  there is danger of an electric shock or a fire if it is not used       Do not install the outdoor unit where there is high level of oil mist  flammable gases  salty air or harmful  gases such as sulfur        For installation  firmly connect the refrigerant pipe before the compressor starts operating   For maintenance  relocation and disposal  remove the refrigerant pipe after the compressor stops       Do not perform a short circuit of the protection device such as a pressure switch when operating   It may cause a fire and explosion       Do not use any sprays such as insecticide  lacquer  hair spray or other flammable gases within  approximately one  1  meter from the system       If circuit breaker or fuse is often activated  stop the system and contact your service contractor       Check that the ground wire is securely connected  If the unit is not correctly grounded  it lead electric  shock  Do not connect the ground wiring to gas piping  water piping  lighting conductor or ground w
73. ring Brazing  Stop Valve and Air Tight Test         Liquid Line  Manifold    Gauge oe  Siphonic Refrigerant Cylinder    7 Ch  R410A   Vacuum Pump Weigher    Stop Valve    Gas Line                      Gas Line    Liquid Line                   Indoor Unit       Branch Pipe Insulation  Cover the gas and liquid pipe with insulation      Fig  8 1 Vacuum Pumping and Refrigerant Charge    8 2 Vacuuming   1  Connect a manifold gauge and vacuum pump to the check joints      Gas Stop Valve  Liquid Stop Valve     2  Continue vacuum pumping work until the pressure reaches  0 1MPa   756mmHg  or lower for one to  two hours   After vacuum pumping work  stop the manifold valve   s valve  stop the vacuum pump and leave it for  one hour  Check to ensure that the pressure in the manifold gauge does not increase     3  Tighten the cap of check joint  9 to 14N m for gas valve  14 to 18N m for liquid  valve  after the vacuum pumping work     NOTES    1  If tools or measuring instruments come into contact with the refrigerant  use the tools or the measuring  instruments exclusive for R410A    2  If vacuum degree of  0 1MPa   756mmHg  is not available  it is considered that there is a gas leakage   Check for any gas leakage once again  If no leakage exists  operate the vacuum pump for one to two  hours     NOTICE    e Insulate the refrigerant pipes as shown in Fig  8 2     After connecting the refrigerant piping  seal the  refrigerant pipes by using the field supplied insulation Stop Valve  materia
74. s of   S _ S _ _  function No  and external input output settings are as shown below  6 noe of HI D 19 Ge UE DU  Setting of External Input and Output Function   Protection of Decrease   S  Function Input Output 7  Priority Capacity Mode rm y D 20  in Outlet Temperature E EI   i  No  for Cooling  1 Fixing Heating Operation Mode   Operation Signal Compressor   zee    2 Fixing Cooling Operation Mode   Alarm Signal 8  Frequency Control   He D 21  Not Prepared Fi D  3 Demand Stoppage Compressor ON Signal Target Value for Cooling    S Compressor   Adjustment of SS    4 Outdoor Fan Motor Start Stop   Defrost Signal o   Frequency Control H D r 1 22  Fan Rotation E o i 1  5 Forced Stoppage   Target Value for Heating    for multiple installation       6 Demand Current Control 40    Indoor Expansion Valve  P n NE e  7 Demand Current Control 60  a 10 gontrol argat Value Jk uw 23  Not Prepared Li LU  for Cooling  8 Demand Current Control 70  H Indoor Expansion Valve   z z    9 Demand Current Control 80    11  Control Target Value GH H 24  Not Prepared Fi D  10 Demand Current Control 100    for Heating a  11 Low Noise Setting 1   c EI co EI  12 Low Noise Setting 2 S 12  Not Prepared a LI 25  Not Prepared  me  uw  13 Low Noise Setting 3 P  0 No Setting No Setting 13  Not Prepared ei CO D 26  Not Prepared E EI 0                   different input output terminals        The same input output function setting can not be set to    If set  a setting of larger function number is became invalid   
75. ss   Pipe  45 Device Device Clogging  Excessive Refrigerant  Inert Gas Mixing  Activation of Low Pressure Decrease Protection Insufficient Refrigerant  Refrigerant Piping  Clogging   47 Device  Vacuum Operation Protection  Expansion Valve Locking at Open Position  Loose Connector   48 Activation of Inverter Overcurrent Protection Device Overload Operation  Compressor Failure  51 Sensor Abnormal Inverter Current Sensor Current Sensor Failure  e A Driver IC Error Signal Detection  Protection for  53 Inverter Error Signal Detection Overcurrent  Low Voltage  Short Circuit   Inverter z   Abnormal Inverter Fin Thermistor   54 Abnormality of Inverter Fin Temperature Heat Exchanger Clogging  Fan Motor Failure  55 Inverter Failure Inverter PCB Failure  ER   Driver IC Error Signal Detection  Protection for Overcurrent   57 Activation of Fan Controller Protection Low Voltage  Short Circuit   Instantaneous Overcurrent  5A Abnormality of Fan Controller Fin Temperature   e Failure  Heat Exchanger Clogging   Fan an Motor Failure  5b Controller   Activation of Overcurrent Protection Fan Motor Failure  e Failure of Current Sensor  Instantaneous Overcurrent   Sc Abnormality of Fan Controller Sensor Increase of Fin Temperature  Low Voltage  Earth Fault  Step Out   e This alarm code appears when the following alarms   Compressor Protection Alarm R Grp  EE   Compressor  It is can not be reset from remote Controller  occurs three times within 6 hours    02  07  08  39  43 to 45  47  b1 Outdoor Uni
76. t   Bottom Base Bottom Base  98_    227 300_ 227  Drain Hole  26 x 2  98 227 560 227 Drain Hole  626 x 2                 oo    a ae            Drain Boss Position  Option  Drain Boss Position  Option     Drain Hole  26 x 2                                 Drain Cap Position  Option     Le KI  N  e Aa   N   Es N   k wo   Q Drain Hole  26 x 2   Drain Cap Position  Option  ts  Power Source Connection     Power Source Connection  Refrigerant Piping Connection                                                       952 Knock out Hole   052 Knock out Hole   Refrigerant Piping Connection    Control Circuit Connection   235 x 113 Square Hole      626 x 2 Knock out Hole   235 x 113 Square Hole        Control Circuit Connection   026 x 2 Knock out Hole              e Drain Boss  Optional Parts     The drain boss is for the drain pipe connection in order to use outdoor unit bottom base as a drain pan     DBS 26    Component Formation of Drain Boss    Parts Name Material   Color Q ty Application  PP   Black Connecting for Drain Piping  DBS 26 PP   Black Embolization for Drain Hole       Rubber Cap CR   Black    Sealing for Boss and Cap     lt  Installation Position  gt   Example  AVWT 96U6SR     lt  Side View  gt     Drain Cap Position                                    247    91  i     Rear Side   52  y  Front Side   LWD     A  Bottom Base   73   Drain Cap  Drain Pipe Drain Boss Position  2 Places  Drain Boss   Field Supplied   Outdoor Unit Rear Side     6  Refrigerant Piping Work    A DAN
77. t   Incorrect Outdoor Unit Address Number Over 64 Number is Set for Address or Refrigerant  No  Setting or Unit Number Setting Cycle   Indoor Unit i     More than 17 Non Corresponding to Hi NET II  b5 No  Setting Incorrect Indoor Unit Connection Number Setting Units are Connected to One System        58       10  Safety and Control Device Setting    e Compressor Protection  The compressor is protected by the following devices and their combinations    1  High Pressure Switch  This switch cuts out the operation of the compressor when the discharge  pressure exceeds the setting    2  Oil Heater  This band type heater protects against oil foaming during cold starting  as it is energized  while the compressor is stopped     Model  KBtu h  ee   114  For Compressor Automatic Reset  Non Adjustable  Pressure Switches  each one for each compressor      0 05  0 05  0 05  High Cut Out MPa 4 15 015 4 15 015 4 15 015       Cut In   MPa   3 20 0 15   3 20 0 15   3 20 0 15    Fuse Capacity    380 415V 3N   50Hz          40x2    Oil Heater  Capacity  CCP Timer  Setting Time  For DC Fan Module  Fuse Capacity          Non Adjustable  3           380 415V 3N   50Hz A 20x1 20x1 20x1          Model  KBtu h   For Compressor  Pressure Switches    High Cut Out    Automatic Reset  Non Adjustable   each one for each compressor      0 05  4 15 015    3 20 0 15               MPa   3204015      Fuse Capacity    380 415V 3N   50Hz    40x2 32x2 40x2 32x2         Oil Heater  Capacity  CCP Timer  Setting Tim
78. tal Indoor Unit Numbers Additional Charge  3 W3 The Ratio of Indoor Unit Connection Capacity  Indoor Unit Total Capacity     Outdoor Unit Capacity  Additional Charge  Determine the ratio of indoor unit connection capacity           Condition Refrigerant Amount  e   U Capacity Ratio is less than 100    0 0kg  e   U Capacity Ratio is 100 115    0 5kg  e   U Capacity Ratio is 116 130    1 0kg kg  4 W Calculation of Additional Charge  W kg     W1   W2  W3 kg    Note     Ensure that the total additional charge should not be exceeded the max  additional refrigerant charge quantity  as shown in the table below      lt  Max  Additional Refrigerant Charge Quantity  gt     Outdoor Unit  KBtu h  86 96 136 154 190 232 250 460    Max  Additional Ref   Charge Quantity  kg        2  Charging Work  Charge refrigerant  R410A  into the system according to Item 8 4   3  Record of Additional Charge  Total refrigerant charge of this system is calculated in the following formula     Total Ref  Charge  This System    W   Wo Ref  Charge Amount of O U  Before Shipment  WO  kg      kg Outdoor Unit  KBtu h    WO Outdoor Unit Ref  Charge  kg                                         Total Additional Charge  W kg  Total Ref  Charge  kg  Date of Ref  Charge Work                                                      Note    e WO is outdoor unit ref  charge before shipment    e In case of the combination of the base unit  calculate the total  ref  charge before shipment of the outdoor units to be combined     
79. terminal of the electrical parts  If not  do not operate the system until the  electrical leakage is found and repaired  Refer to    Caution for Insulation Resistance    for details      Do not impress the voltage on the terminals for transmission  Outdoor Unit  TB2 1  2  3  4   Indoor Unit  TB2 1  2  A  B   HCH Unit  TB2 1  2  3  4      3  Check to ensure that each wire  L1  L2  L3 and N is correctly connected at the power source    If incorrectly connected  the unit will not operate and the remote control switch will indicate the alarm  code    05     In this case  check and change the phase of the power source according to the attached  sheet on the reverse side of the service cover      4  Check to ensure that the switch on the main power source has been ON for more than    12 hours  to warm the compressor oil by the oil heater   FSXN series outdoor units does not operate within 4 hours after power supply  Stoppage Code d1 22      In case of operating within 4 hours  release the protection control as follows   1  Supply power to the outdoor unit   2  Wait for 30 seconds   3  Push PSW5 on the outdoor PCB more than 3 seconds in order to release the d1 22   In case of using remote control switch for release  push    Air Flow    and    Auto Louver    switch  simultaneously for 3 seconds    5  Main Unit Label    In case of the combination of base units  attach the main unit label on a visible spot of the main  unit  outdoor unit A   so that the outdoor unit A can be identified
80. ti pole main switch with a space of 3 5mm or more between each phase     NOTES   1  When the power supply wiring is longer  select the minimum wiring size which the voltage drop is within 2    2  Power supply voltage should be satisfied with the followings   Supply Voltage  Rated Voltage within  10   Starting Voltage  Rated Voltage within  15   Operating Voltage  Rated Voltage within  10   Imbalance between Phases  within 3   3  Do not connect the earth wire to the gas pipe  water pipe  lightening conductor   Gas Pipe  An explosion and ignition may occur when gas leaks   Water Pipe  There is no effect of earth wire when a hard vinyl pipe is used   Lightening Conductor  The earth electric potential abnormally increases when a lightening conductor is used     37    7 3 Electrical Wiring for Outdoor Unit  Connect the electrical wirings according to the following figure    1  Connect the power supply wires to L1  L2  L3  and N  for 380 415V  for the three phase power source  on the terminal board TB1 and earth wire to the terminal in the electrical control box      2  Connect the transmission wires between the outdoor and indoor units to the TB2 terminals 1 and 2 on  the PCB1  As for the transmission wires between outdoor units in the same refrigerant cycle  connect    them to the TB2 terminals 3 and 4 on the PCB1      3  Tighten screws for the terminal board according to the following table      lt  Required Tightening Torque  gt     M4 1 0 to 1 3 N m  M5 2 0to2 4 N m  M6 4 0 to
81. tion Do not remove  CORRECT corrugated paper frame                and plastic bands   Wire Rope  Square  Hole I  E  O    INCORRECT    Wire Rope  Square  Hole            Apply rope through  E58 the square holes     QS                                  Angle of wire rope  is more than 60                Apply rope on the splints or  corrugated paper of more than  15mm thickness              Do not apply any force  to thise place            Both Sides              Fig  4 2 Hanging Work without Wooden Base    When using forklift  do not insert forks into  the holes on the unit side  The unit may be  damaged              E TT  EERE ei  ann  e    is             The holes on i  the unit side Forks    NOTE    Do not apply excessive force to the square holes  with forks or other materials  The bottom of the  unit may be deformed      Do not push the bottom base by fork      Do not use roller        Do not apply excessive force    Both Sides              In case of transportation after unpacking  protect the unit with the splints or cloth     4 2 Handling of Outdoor Unit    Do not put any foreign material into the outdoor unit and check to ensure that none exists in the  outdoor unit before the installation and test run  Otherwise  a fire or failure  etc  may occur     10    5  Outdoor Unit Installation    5 1 Factory Supplied Accessories  Check to ensure that the following accessories are packed with the outdoor unit     Table 5 1 Factory Supplied Accessories    Connection for  SS  A   
82. wing equation   R  Total Quantity of Charged Refrigerant  kg   V  Room Space Where This Unit Is to Be Installed  m      C  Refrigerant Concentration  lt  0 3  kg m        If local codes or regulations are specified  follow them      lt       lt      lt Example gt   Japanese Standard KHK S 0010 C 0 3  kg m       51    9  Test Run    Test run should be performed according to the Item 9 2  And use the Table 9 1 for recording test run       Do not operate the system until all the check points have been cleared   As for the test run of indoor unit  check    Installation  amp  Maintenance Manual    attached to the indoor  unit     9 1 Before Test Run     1  Check to ensure that the refrigerant piping and transmission between outdoor unit and indoor units  are connected to the same refrigerant cycle  If not  it will cause an abnormal operation and a serious  accident    Check that the dip switch setting of the refrigerant cycle No   DSW1  amp  RSW1  O U    DSW5  amp  RSW2   I U    and the unit number  RSW  for the indoor units apply to the system    Confirm that the dip switch setting on the printed circuit board of the indoor units and the outdoor units  are correct  Especially  pay attention to the setting of lift between indoor units and outdoor unit  the  refrigerant No  and the end terminal resistance  Refer to the chapter    7  Electrical Wiring         2  Check to ensure that the electrical resistance is more than 1 megohm  by measuring the resistance  between ground and the 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Samsung qHD General Display  サーベイメータ買い出し案内・巡回経路・貸出規定    FUSION Electronics CS-SW100  15C  Hitachi DV-PF33U DVD Player/VCR  KORG POLYSIX  Valueline VLCP73900B power cable    取扱説明書 P-06D 日本語    Copyright © All rights reserved. 
   Failed to retrieve file