Untitled - Eurocid

image

Contents

1. 8 4 11 u nennt nnn nnns 5 5 REGULATIONS AND REQUIREMENTS I nennen nannte nnn nns 6 6 REFERENCE DOCUNMENTS cl 7 7 ENVIRONMENTAL CONDITIONS I u uuu 7 8 OPERATING THE SYSTEM 2 ier ene priest eate ue ern eua cun EE evi ng eoo cpu 8 8 1 A loss of voltage on the ET1 ET2 or ET3 bus bars EE1 priority from CN 28 8 8 2 Return to the normal 21 eene nnne nn 8 8 3 Manual 6eperall Ru uuu l lil aliene 9 8 4 Mecum EE 9 9 TECHNICAL DESCRIPTION OF THE SUPRPLY iii 9 9 1 Composition and features of the new generating 5 9 9 2 General electrical features ii 16 9 3 General manufacturing features essen nenne 16 9 4 Principle ot operato M pem 16 9 5 Signals and alanis det 20 9 6 ro e n 23 10 EXCLUSIONS FROM THE SUPPLY M iii 25 11 DOCUMENTATION u Ua iena 26 12 MANUFACTURE TESTS AND 8 4 u u nennen 28 12 1 Tests the COMPONENTS 28 12 2 ACCEPTANCE tests iet ana 28 T2 9 GertificationN isa c EEEE E EE 28 139 TRANSPORT
2. 29 14 DATA SHEETS ici oo dl 29 COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 3 of 32 3 1 SCOPE The scope of this document is to define the general requirements for the design supply assembly commissioning and maintenance during the guarantee period of the new generating set replacing the EE1 generating set located in building 85 sited at the JRC Ispra VA COMPONENTS OF THE SUPPLY The supply consists of a item EE1 three phase generating set for IT system min 1350kVA max 1400 400V 50Hz cosg 0 8 in sound proof container complete with distribution board and all the systems necessary for operation The installation shall include the delivery of all the material to the JRC Ispra building 85 the testing phases and the subsequent staff training b item MAINTENANCE maintenance service routine and corrective during the 2 years guarantee period with corrective maintenance within 48 hours from the call following Monday for a call made on Friday including the spare parts needed to carry out the routine maintenance liquids included DISASSEMBLY SUPPLY AND ASSEMBLY General comments The activities in question concern building 85 Diesel Room at the Ispra JRC VA where at present there are 3 generating sets having items EE1 EE2 with compressed air starting and water cooling with
3. 20 Nostop 0 0 0 0 21 Prehea ngsystemfaut 22 Lowoilpressure Prealarm _ 23 Very lowoilpressure Stop 24 Lowwaterlevel Prealarm 25 Verylowwaterlevel Stop 0 2 26 Highwatertemperature Prealarm x x 27 Maxmumwatrtemperaue Stp x x 28 Hihoitempratre Preaam x __ x 2NO amp 2NC 29 Veryhighoiltemperature Sop x SR 30 Maxmumtemperauemoor X S 2NO amp NC 31 Bateychagefaut x J x 2NO2NC 32 outofuer 0 0 x S 2NOeNC TYPE OF DISPLAY OPERATION DESCRIPTION DISPLAY LED SIRENA STOP AVAILABLE FOR REMOTE 1 7 2 3 x 33 Bateovevotage x 34 Batteryundervotage x e2woevw i 0 00 GENERATORPROTECTIONDEvices 36 Overvoltage Prealarm x x 37 Overvoltage stop 0 0 x s 2NO NC 38 Undervoltage Prealarm x x 2NOsNC 39 Undevotage Sop 0 1 1 x x s 2NO NC 40 Ova 0 0 0 0 0 0 x 2NO NC 41 Shorcieuit 0 0 0 0 0 x x s f noen 42 Maximum frequency Stop x S 2NosNC 43 Minimum frequency Stop 1 x 2Noevwc 44 Maxmumacivepower Preaam x x 2NOs2NC 45 Maxmumacivepower Stop
4. x sn aNwoewc 46 Maxmumreadivepower Preaam x x NON 47 Maxmumreadivepower Stp x x 2Noevwc 48 Highwindingtemperaue x x SR 2NO 2NC 49 Highbearingtemperaue x x s 2Noevwc s x gt lt x lt gt lt gt gt lt x gt lt px px LE gt lt gt gt COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 22 of 32 mmeosmrPROTECTON 51 Circuitbreakershort circuittip J x x 2 NO 2 NC 52 Switching off Rheostat Prealarm by Rheostay x x 2 NO 2 NC 53 Switching off Rheostat alarm by Rheostat 2 2 NC Max daily tank level Low daily tank level Fault on the diesel pumps 58 Leaks bottom storage tank vessel FIRE FIGHTING SYSTEM Fire fighting system Prealarm note 6 Switching on extinguishing system note 6 Extinguishing push button fault note 6 380Vac VOLTAGE SYSTEM PRESENT Loss of voltage EC1 1 3 logic ic Loss of voltage EC3 1 3 logic Loss of voltage ET1 ET2 logic Loss of voltage ET3 logic X X 1 7 VARIOUS _ 68 Emergency stop x x 2 NO 2 NC 69 Airshutters closed 1 2 logic 2 NO 2 NC Leaks on the bottom of the container
5. 9 3 9 4 Caratteristiche costruttive generali Gruppo Elettrogeno e Quadro Elettrico in container Installazione container in locale chiuso riscaldato Tempo max avviamento 5s Tempo max dall avviamento alla presa di carico 16s Ingresso cavi dal basso Ingresso tubazioni carico combustibile dal basso Principio di funzionamento 9 4 1 Selettore Locale 0 Distanza sul Quadro Elettrico di Potenza Il selettore Locale 0 Distanza posto sul Quadro Elettrico di Potenza consente le seguenti condizioni di funzionamento a Selettore in posizione Locale In questa posizione l interruttore ED13 pu essere comandato tramite i pulsanti di apertura e chiusura posti sul fronte del Quadro Elettrico di Potenza L apertura dell interruttore ED13 sempre possibile con l avaria del Gruppo Elettrogeno come da paragrafo 9 4 2 b Selettore in posizione 0 In questa posizione se l interruttore ED13 si trova in stato di chiusura questo deve essere mantenuto possibile aprire l interruttore con il pulsante di apertura posto sul fronte del quadro elettrico di potenza c Selettore in posizione Distanza In questa posizione l interruttore ED13 non pu essere comandato dai pulsanti locali posti sul fronte del Quadro Elettrico di Potenza ma deve avere la possibilit di essere comandato a distanza i relativi comandi devono essere disponibili a morsettiera L apertura dell interruttore ED13 sempre possibile
6. Presenza mancanza tensione EC1 1 NA 1 NC nota 3 Guasto trafo EC1 Mains tripped 1 NA 1 NC a registratore i 3 3 Presenza mancanza tensione EC3 1 NA 1 NC TIPO DI SEGNALE 1 2 Presenza mancanza tensione ET3 2NA amp 2NC BI Misura frequenza generatore 380Vea asiS T a registratore Misura di corrente Inserieall amperometropostosulquadro Misura di corrente generatore da TA con secondario 5A a registratore Guasto PLC amicroprocessore INAHNC 00000 00 0 0 00 0 Posizione interruttore ED13 5 NA 5 NC Per verifica segnalazione interruttore chiuso aperto Scatto termico interruttore ED13 Posizione interruttore ED101 4 NA 4 NC Scatto interruttore ED101 ORNA y HE BOB Bu Ed EN VH EE EH KA EN EH EE TR ES E EN E EE EN ER NOTE 1 Quantit e posizione contatti in ingresso alla morsettiera 2 Quantit e posizione contatti in uscita dalla morsettiera 3 Quantit e posizione contatti resi disponibili a morsettiera tramite rel gestiti in fail safe COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 26 of 33 10 ESCLUSIONI DALLA FORNITURA Sono esclusi dalla fornitura a opere civili occorrenti all installazione del Gruppo Elettrogeno b isolamento elettrico e smontaggio del Gruppo Elet
7. x 2 NO 2 NC Operation of 24V dc power supply protection devices 2 NO 2 NC X X 72 Operation of 380V ac power supply protection X X 2 NO 2 NC devices TYPE OF DISPLAY OPERATION DESCRIPTION DISPLAY LED SIRENA STOP AVAILABLE FOR REMOTE 1 7 2 3 2 2 NC 2 2 NC 2 2 NC 2 2 NC x gt lt px Oo 2 2 2 2 2 2 d 2 NO 2 NC 2 2 NC 2 2 NC 2 2 NC X X X NNNM 73 ra ee S NOTES 1 Alarm display with description of the type of fault 2 SI Immediate stop SR Stop delayed 3 min 3 Quantity and position of contacts made available on the terminal board the alarm contacts must be made available on the terminal board by means of relays managed in fail safe 4 The alarm stops the diesel pumps 5 Operation of protection devices with the unit stopped alarm and block start Operation protection devices with the unit working only alarm 6 Alarms to be provided on the fire fighting system control board 7 Siren operation can be timed 0 2 min COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 23 of 32 9 6 Interface signals The states and the commands necessary for the interface with the existing system shall be available on the terminal board as follows the list represents the minimum requirement other si
8. 03 04 05 06 07 COPIA CONFORME ARCHIVIO NDU 2012 06 12 eni Rev 0 Sostituzione gruppo elettrogeno EE1 INE 2 of 33 1 Llee jlo 3 2 CONSISTENZA DELLA 3 3 ATTIVITA DI SMONTAGGIO FORNITURA E 3 3 1 Generalta 3 3 2 Elenco delle attivita M 4 4 LIMITI DI BATTERIA PRECISAZIONI u nennen nnne nnne nnn nns 5 5 NORMATIVE E PRESCRIZIONI iii 6 6 DOCUMENTI Dl RIFERIMENTO 7 rnt ia 7 7 CONDIZIONI AMBIENTAL cca rin 8 8 FUNZIONAMENTO DEL SISTEMA I u u u u 9 8 1 Mancanza tensione sulle sbarre ET1 ET2 o ET3 EE1 prioritario da CN 28 9 8 2 Ritorno alla situazione normale aaa 9 8 3 Funzionamento 10 8 4 Funzionamento in prova ii 10 9 DESCRIZIONE TECNICA DELLA FORNITURA 10 9 1 Composizione e caratteristiche del nuovo Gruppo 10 9 2 Caratteristiche elettriche generali entren 17 9 3 Caratteristiche costrut
9. COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 32 of 32 L V DISTRIBUTION BOARD DATA SHEETS NUMBER OF BOARDS ITEM GENERAL DATA MANUFACTURER TYPE REFERENCE STANDARDS REFERENCE SPECIFICATION REFERENCE DWGS INSULATION VOLTAGE V FREQUENCY RATED VOLTAGE V SHORT CIRCUIT CURRENT 1s MAXIMUM VOLTAGE RATED CURRENT BUSBAR MATERIAL CONTROL CIRCUIT AVAILABLE VOLTAGE CROSS SECTION DEGREE OF PROTECTION ON EXTERNAL HOUSING IP41 INSIDE THE SWITCHBOARD IP 20 ENCLOSURE L DUTDOOR INCOMING CABLES FROM THE BOTTOM THE FASTENING L WALL OUTGOING CABLES THE BOTTOM FROM THE TOP PANEL ARRANG FRONT TWO FRONTS BACK ACCESS NES NO INCOMING _ FIXED DRAWOUT Li MECHANICAL DATA FEEDER FIXED DRAWOUT TIE BREAKER FIXED IDRAWOUT BUS BARS BARE TAPED TOTAL WEIGHT kg LENGHT TOT WEIGHTS HEAVIEST PANEL kg OVERALL HEIGHT DIMENSIONS MAX CRANE LIFTING WEIGHT DEPTH kg MANUFACTURER TYPE RATED VOLTAGE V MANUFACTURER TYPE RATED VOLTAGE V DEVICE MANUFACTURER TYPE RATED VOLTAGE V 0 PAINTING INTERNAL COLOUR EXTERNAL COLOUR CYCLE ACCESSORIES L SPACE HEATER FOUNDATION PLATES EEr ETERNAL LIGHT
10. DATI GENERALI general data DATI NOMINALI rating DATI MECCANICI mechanical data APPARECCHIATURA device VERNICIATURA painting ACCESSORI accessories FOGLIO DATI QUADRO DI DISTRIBUZIONE IN B T L V distribution board data sheets No QUADRI number of boards COSTRUTTORE manufacturer NORME DI RIFERIMENTO reference standard SIGLA item TIPO constructor type SPECIF DI RIFERIMENTO reference doc DISEGNI DI RIFERIMENTO reference dwgs TENSIONE NOMINALE TENSIONE MASSIMA maximum voltage CORRENTE NOMINALE rated current MATERIALE Ha material SEZIONE cross section UBICAZIONE INTERNO ESTERNO enclosure indoor outdoor FISSAGGIO PAVIMENTO PARETE disposition at floor at wall DISP PANNELLI UN FRONTE DUE FRONTI panels arrangements a front two fronts ARRIVO FISSO STRAIBILE incoming Ll fixed B uie PARTENZA O FISSO STRAIBILE feeder fixed rawout CONGIUNTORE O FISSO STRAIBILE tie breaker fixed drawout SBARRE ON UDE ASTRATE bus bar bare ape total weight PANNELLO PIU PESANTE kg heavist panel PESO MAX ALLA GRU kg max lifting weight INTERRUTTORE COSTRUTTORE manufacturer CONTATTORE COSTRUTTORE manufacturer SEZIONATORE COSTRUTTORE manufacturer FUSIBILE COSTRUTTORE manufacturer COLORE INTERNO internal RAL RES ANTICOND space heater TENSIONE DI ISOLAMENTO V insulation voltage V SBARRE bus bar PESI weights COLORE ESTERNO external RAL PROF D APPOGGIO foundation pla
11. dell Edificio b 9 Pulsanti prova riconoscimento e tacitazione sirena reset degli allarmi c Strumentazione c 1 Indicatori analogici temperatura acqua olio c 2 Indicatori digitali temperatura acqua olio c 3 Indicatore di carica della batteria di avviamento c 4 Indicatori di tensione corrente frequenza potenza attiva Generatore c 5 Indicatore di corrente Reostato c 6 Indicatore livello combustibile serbatoio giornaliero COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 16 of 33 c 7 Indicatore livello combustibile serbatoio di stoccaggio 4 20 mA c 8 Indicatore di velocit 9 Totalizzatore ore di funzionamento e numero di avviamenti c 10 Indicatore digitale pressione olio c 11 Indicatori di temperatura avvolgimenti generatore fasi R S T c 12 Trasformatori di corrente secondario 5A lato generatore per protezioni e misure d Alimentazione Circuiti ausiliari Circuito di comando e allarme a 24Vdc alimentato dalle batterie del circuito di avviamento e dall alimentatore 380Vca 24Vcc da questo circuito dovr essere prevista una partenza a 24Vcc per l alimentazione dei circuiti ausiliari degli automatismi energia e Sistemi di Comando e Controllo e 1 Sistema di controllo presenza tensione 380V 50Hz trifase come da paragrafo 9 4 4 e 2 Sistema di controllo presenza e sga
12. j 73 Sganciotensione da pulsante x x S 2NA2NC m WA oR 2 6 1 NOTE 1 Visualizzazione allarme con descrizione del tipo di anomalia 2 SI Stop immediato SR Stop ritardato 3 min 3 Quantit e posizione contatti resi disponibili a morsettiera i contatti degli allarmi devono essere resi disponibili a morsettiera tramite rel gestiti in fail safe 4 L allarme provoca l arresto delle pompe gasolio b Intervento protezioni con Gruppo all arresto allarme e blocco start Intervento protezioni con Gruppo in marcia solo allarme 6 Allarmi da prevedere sul Quadro di Controllo Impianto Antincendio 7 Intervento sirena temporizzabile 0 2 min COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 nct ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 24 of 33 9 6 Segnali di interfaccia Dovranno essere disponibili a morsettiera gli stati e i comandi necessari all interfaccia con l impianto esistente come segue quanto in elenco rappresenta il minimo requisito altri segnali potranno essere aggiunti durante la definizione di dettaglio dell interfaccia con la logica remota 9 6 1 Segnali da remoto TIPO DI SEGNALE comando solo con Gruppo in Automatico comando solo con Gruppo in Automatico Il contatto chiuso autorizza lo start diesel Apertura chiusura interruttore ED13 i Apertura chiusura interruttore ED101 2NA 7 Presenz
13. Annual average relative humidity lt 85 COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 8 of 32 8 1 8 2 OPERATING THE SYSTEM With reference to annex B In normal operation both transformers EC1 and EC3 are powered by means of the 8000EQ01 medium voltage board Transformer EC1 supplies the ET1 and ET2 bus bar systems and transformer EC3 supplies the ET3 bus bar system of the 8100EQ01 low voltage board Starting the EE1 generating set can be automatic or manual and shall be coordinated with the operation of the EE3 generating set so that the two units cannot be operated at the same time The type of operation and the priority unit backup unit shall be selected by means of the CN26 CN 27 and CN 28 key circuit breakers from the main control room Normally the type of operation selected shall be automatic and the ED13 circuit breaker will normally be closed The ED14 and ED35 circuit breakers must however be open to close the ED13 circuit breaker A loss of voltage on the ET1 ET2 or ET3 bus bars EE1 priority from CN 28 If there is a loss of voltage on the ET1 ET2 or ET 3 bus bars 8100 EQ01 board measured on the Unit after about 1 sec after checking the availability of the EE1 generating set that the CN26 changeover switch is in the automatic position the CN 28 changeover switch in the EE1 priority position and that t
14. DI RIFERIMENTO reference dwgs POTENZA NOMINALE KVA CLASSE ISOLAMENTO STATORE FAT DI POT IN SOVRAECCITAZ CLASSE ISOLAMENTO ROTORE TENS NOMINALE V FORMA COSTRUTTIVA FREQUENZA Hz CHIUSURA NUMERO DI POLI n SISTEMA DI RAFFREDDAMENTO VELOCITA g 1 FLUIDO REFRIGERANTE NUMERO FASI n PORTATA FLUIDO REFRIG mc h COLLEGAMENTO FASI PERDITA DI CARICO NEI REFR mmo NUMERO MORSETTI n SISTEMA DI ECCITAZIONE PD DEL GENERATORE TIPO DI ACCOPPIAMENTO RAFFREDDAMENTO ECCITATR PD MOTORE PRIMO SIGLA item TIPO constructor type SPECIF DI RIFERIMENTO reference doc RAPPORTO DI C C IN REGIME VARIAZIONI DI TENSIONE DA AV SATURO A TENS NOMINALE PIENO CARICO REATTANZA SUBTRANSITORIA VUOTO CON ECCITAZIONE E VELOCITA COSTANTI Rendimento 44 carico x REATTANZA TRANSITORIA DIR REATTANZA SINCRONA POTENZA REATTIVA REG SOTTOECC convenzion COS 0 REG SOVRAECC RES L T m ECCE ui L la PESO STATORE Kg PESO ROTORE Kg PARTE PESANTE DA SOLLEV Kg IMPIANTO DI REFRIGERAZIONE DISPOS SEGNAL CIRC ACQUA DOSP SEGN CIRC ARIA O GAS TERMORESISTENZE QUADRO PER REGOLATORE PLATINO 1009 0 C 0 3 854103 il i O VERNICIATURA COLORE CICLO painting NOTE COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 33 of 33
15. MECCANICI Mechanical requirements PROVA DI FUNZIONAMENTO Operation test 13 TRASPORTO Il fornitore dovr comunicare con almeno 10 giorni di anticipo le seguenti informazioni a data prevista di spedizione b data prevista arrivo in cantiere c mezzo di trasporto 14 DATA SHEETS Data Sheets seguenti sono da completare a cura del fornitore COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 31 of 33 DATI GENERALI general data DATI NOMINALI rating CILINDRI cylinders COMBUSTIBILE fuel CUSCINETTI bearings CARATTERISTICHE characteristics SERB STOCCAG NAFTA fuel storage tank MOT ELETTR AVVIAM electric motor ACQUA RAFFREDDAM cooling water OLIO DI LUBRIFICAZ lube oil STRUMENTAZIONE instrumentation FOGLIO DATI MOTORE DIESEL Diesel Engine data sheets QUANTITA SIGLA quantity item COSTRUTTORE TIPO manufacturer constructor type NORME DI RIFERIMENTO SPECIF DI RIFERIMENTO reference standard reference doc DISEGNI DI RIFERIMENTO reference dwgs TIPO DI MOTORE LI PC SE DE engine type POT CONTINUA lt N GIRI MINUTO rpm power COPIA MASSIMA N GIRI MINUTO max torque rpm N CILINDRATA ALESAGGIO number volume bore DISPOSIZIONE CORSA position stroke VISCOSITA viscosity PESO SPECIFICO Kgdm PORTATA l min specific gravity flo
16. No of No of i i i days from Copies copies copies P A inspection 1 1 Ba Lem ROUTINE TEST INSPECTION REPORT PACKING TRANSPORT STORE SPECIFICATIONS 3N 30 NOTE 1 PA For approval PI For information DF Final documentation N Opaque copies C On EDP support 2 3 After the inspection 4 After the tests 5 All the documentation concerning the supply in question shall be drawn up in MS Word MS Excel Autocad 2004 formats produced with the rating plates and identifications as per the Customer s procedure see annex C sent to European Commission Joint Research Centre Via E Fermi 2749 21020 Ispra Va 21020 Ispra VA ISM Ispra Site Management Deactivation of Nuclear Systems Unit TP 800 Attn F Maniaci COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 28 of 32 12 MANUFACTURE TESTS AND INSPECTIONS The supplier shall issue Quality Control Plans to be subjected for approval to the Customer on which will be listed all the tests carried out on the individual materials used to manufacture the components of the supply with reference to the applicable legislation The document cited shall be drawn up using the Customer s format see annex C and will indicate the examinations checks tests and inspections to be present at and those which the supplier can c
17. Quadro Elettrico di Comando e Controllo manuale automatico con almeno a Circuiti di potenza Arrivo linea a 380V 50Hz SF sistema IT per l alimentazione di COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 15 of 33 a 1 Sistema carica batteria e tampone a 2 Pompa di reintegro gasolio a 3 Scaldiglie anticondensa a 4 Servizi vari del G E a 5 Alimentatore 380Vac 24Vcc con trasformatore di sicurezza per i circuiti ausiliari a 6 Persiane esistenti a 220Vca poste sul tetto dell Edificio tramite contattore con contatti in scambio L arrivo linea dovr essere protetto con scaricatori di sovratensione e relativi fusibili da verificare necessit in base all allegato D b Comandi sul fronte quadro b 1 Pulsante luminoso per apertura chiusura interruttore ED101 b 2 Pulsante luminoso lampeggiante per chiusura interruttore ED101 b 3 Selettore Automatico Manuale Test Stop con chiave estraibile per la gestione del Gruppo Elettrogeno EE1 b 4 Pulsanti di marcia arresto del G E EE1 Abilitati solo con selettore a chiave su Manuale b 5 Pulsanti luminosi di marcia arresto per pompe gasolio b 6 Pulsante di inserzione sistema di Spegnimento incendio nel container b 7 Pulsante arresto di emergenza G E EE1 b 8 Pulsante per apertura chiusura persiane esistenti poste sul tetto
18. con l avaria del Gruppo Elettrogeno come da paragrafo 9 4 2 9 4 2 Apertura dell interruttore ED13 in condizioni di avaria del G E L interruttore ED13 viene comunque aperto nelle seguenti condizioni di avaria del Gruppo Elettrogeno ed in particolare a bassa pressione circuito di lubrificazione b alta temperatura motore COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 19 of 33 alta bassa velocit d alta bassa tensione Generatore lt 65 gt 120 e avaria Generatore f azionamento pulsante di emergenza Gruppo Elettrogeno g azionamento pulsante sgancio tensione posto all esterno dell Edificio h azionamento pulsante per l inserzione Spegnimento incendio nel container i preallarme incendio container 9 4 3 Selettore Automatico Manuale Test Stop sul Quadro Elettrico di Comando e Controllo Il selettore Automatico Manuale Test Stop posto sul Quadro Elettrico di Comando e Controllo consente le seguenti condizioni di funzionamento a Selettore in posizione Automatico In questa posizione il Gruppo Elettrogeno EE1 non pu essere comandato dai pulsanti di marcia e arresto posti sul fronte del Quadro Elettrico di Comando e Controllo ma solo dagli automatismi di funzionamento del Gruppo e con i seguenti segnali vedere paragrafo 9 6 1 a 1 start diesel da SCP CN26 in po
19. line IT system to supply a 1 Battery charge and backup system a 2 Makeup diesel pump a 3 Anticondensation heating units a 4 Various G S services a 5 380Vac 24Vdc power supply with safety transformer for the auxiliary circuits a 6 220Vca louvres existing on the building roof by means of contactor with change over contacts The incoming line shall be protected with overvoltage arresters and fuses this requirement is to be checked on the basis of annex D COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 14 of 32 b Commands on the front of the board b 1 Luminous push button to open close circuit breaker ED101 b 2 Flashing luminous push button to close circuit breaker ED101 b 3 Automatic manual Test Stop selector switch with drawout key to manage the EE1 generating set b 4 EE1 G S start stop push buttons only enabled with key selector switch on Manual b 5 Luminous start stop push buttons for diesel pumps b 6 Push button to switch on the fire extinguishing system in the container b 7 EE1 G S emergency stop push button b 8 Push button to open close louvres existing on the building roof b 9 Test recognition push buttons and silencing siren reset of the alarms c Instrumentation c 1 Analogue water oil temperature indicators c 2 Digital water oil t
20. livello del mare b Temperatura interna c Clima d Umidit relativa media annua lt 1000 m lt 35 C continentale 85 NE 45 0860 A 009 FERRI ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 8 of 33 7 CONDIZIONI AMBIENTALI COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 9 of 33 8 1 8 2 FUNZIONAMENTO DEL SISTEMA Con riferimento all allegato B In funzionamento normale entrambi i trasformatori EC1 ed EC3 sono energizzati tramite il quadro media tensione 8000EQ01 Il trasformatore EC1 alimenta i sistemi di sbarre ET1 ed ET2 e il trasformatore EC3 alimenta il sistema di sbarre ET3 del quadro bassa tensione 8100EQ01 L avviamento del Gruppo Elettrogeno EE1 potr essere automatico e manuale e dovr essere coordinato con il funzionamento del Gruppo Elettrogeno EES3 in modo che sia impossibile il funzionamento contemporaneo dei due Gruppi La selezione del tipo di funzionamento e del gruppo prioritario gruppo di backup sar fatta tramite gli interruttori a chiave CN26 CN 27 e CN 28 dalla sala controllo principale Normalmente il tipo di funzionamento selezionato sar automatico e l interruttore ED13 sar normalmente chiuso La condizione di aperto degli interruttori ED14 e ED35 comunque condizione necessaria per chiudere l interruttore ED13 Mancanza tensione sulle sbar
21. materials shall be incombustible and free of dangerous materials 9 1 9 Electrical generator Electrical generator manufactured by leading companies in the European market with the following features a synchronous three phase without brushes self adjusted self excited and self ventilated b with class H insulation and class F overtemperature c with suitably protected moving parts with removable guards mechanical protection IP23 d with automatic adjustment to 1 from empty to full load COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 12 of 32 e with tachimetric device to measure the speed above 380g min there must be an intervention contact f including anti condensation heating elements and thermostat g bearings lubricated with grease roller 9 1 10 Coupling Direct motor generator coupling by means of flexible disc and flanging bell 9 1 11 Power distribution board Power distribution board with at least a power circuits machine three pole thermal magnetic circuit breaker item ED13 as follows a 1 open type drawout with support rails ABB Schneider or equivalent with In 2500 A Icu275 a 2 with 24Vdc spring loading motor a 3 with 24Vdc opening closing coil a 4 with auxiliary position trip contacts a 5 with electronic control to protect the generator a 6 with s
22. o dispositivi che si rendessero necessari 9 1 14 Sistema di insonorizzazione e container Sistema di insonorizzazione realizzato con container per l abbattimento acustico della pressione sonora fino a un livello di 70 dBA misurati a 7 metri di distanza e contenente quanto indicato dal punto 9 1 1 fino al punto 9 1 13 Dimensioni indicative max del container LxPxH 10500x2200x2900 mm Il container deve essere dotato di a impianto luce e prese FM a 220V b sensore sul fondo del container per il rilievo delle perdite liquide 9 1 15 Basamento di supporto container Il basamento del container dovr essere dotato di struttura metallica progettata e costruita per essere adatta al supporto del container stesso ed alla posa su fondazione civile esistente avente dim 7300x2400mm 9 1 16 Materiali e o attivit varie a completamento come Elettrovalvole valvole pulsanti cartelli monitori e quanto altro richiesto dalle normative in vigore Caratteristiche elettriche generali Potenza nominale da 1350 a 1400 KVA 10 Sovraccarico 110 x 1h ogni 12h Fattore di potenza coso 0 8 Sistema elettrico classificazione IT Regolazione tensione 1 5 Regolazione frequenza t196 Quadro Elettrico Tensione di esercizio 380 V 50 Hz 3F Portata sbarre principali 2500 COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 18 of 33
23. shall present a detailed programme with times and working phases to be agreed with the Customer he shall also supply precise indications for any civil works and or modifications e g air inlet and outlet system from the room to be carried out in the existing Diesel Room to adapt it to the regulations in force and or to the installation of the new generating set The supply shall include all the means and the materials necessary for carrying out disassemblies design supplies and assemblies according to the rules of the trade With reference to the documents in the annex section 6 the main activities to be carried out are the following a complete dimensioning design including piping diesel and air expulsion duct and layout fully respecting the regulations and laws in force b supply information for any new and or modifying civil works necessary for the assembly of the new generating set c dimensional drawings and or calculations for the static and dynamic check of the support structure of the container to be laid on the base d development of the Diesel Room layout e detail drawings of the layout systems and of assembly of the new Unit checking that the maintenance distances have been respected f drawing up of the OSP Operational Safety Plan after receiving the SCP Safety and Coordination Plan from the Customer The OSP will be submitted for approval to the safety coordinator in the execution phase as lai
24. un Quadro Elettrico di Comando e Controllo locale ove sar previsto un selettore Test che avvia la sequenza di prova del Gruppo Elettrogeno interessato Il funzionamento in prova non inibisce i funzionamenti sopra descritti infatti in caso di richiesta d intervento del Gruppo Elettrogeno la prova viene interrotta ed il Gruppo interviene ad alimentare le sbarre in emergenza DESCRIZIONE TECNICA DELLA FORNITURA Composizione e caratteristiche del nuovo Gruppo Elettrogeno Il Gruppo Elettrogeno sar essenzialmente costituito da 9 1 1 Basamento Gruppo Elettrogeno a Basamento unico in profili di acciaio di costruzione sufficientemente rigida da assicurare un perfetto allineamento munito di supporti elastici antivibranti b Il Basamento con relativo Gruppo Elettrogeno sar posizionato all interno del container insonorizzante di cui al punto 9 1 14 COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 11 of 33 9 1 2 Motore diesel a Motore costruito da ditte di primaria importanza nel mercato Europeo adatto per impiego continuo e gravoso e con regolatore di giri di tipo elettronico classe A1 e con le seguenti caratteristiche a 1 4 tempi a 2 iniezione diretta a 3 12 cilindri a V a 4 aspirazione turboalimentata ed interrefrigerata a 5 tipo di combustibile secondo BS 2869 1970 classe A1 A2 9 1 3 Sist
25. 0 Replacement of EE1 INE generating set 7 of 32 I DPR 547 of 27 04 1955 and subsequent integrations m DPR 459 of 24 07 1996 on the machine directive n Circ 73 of 1971 on fuel deposits Ref Circ 31 o Circ 31 of 31 08 1978 safety standards for the installation of generating sets p Circ 12 of 08 07 2003 Modifications and completions to Circ 31 of 31 08 78 q Lgs D 626 94 Safety in the workplace r Lgs D 494 96 Operational Safety Plan OSP s Lgs D 81 08 and subsequent integrations The supplier is however obliged to apply all the regulations and laws in force in the country for which the supply is intended and the EEC directives applicable with the duty of communicating and taking steps when they become out of date or are made obsolete by others which are more restrictive All the devices must bear the CE marking REFERENCE DOCUMENTS The following documents form an integral part of this specification a Annex A Diesel Room Diesel Room floor plan and cross sections b Annex B dwg NE 68 0820 A 020 General power room single wire diagram c Annex C doc NE 80 1010 A 009 Management of the documentation d Annex D Report on the Evaluation of the Risk from Lightning ENVIRONMENTAL CONDITIONS The environmental conditions assumed for setting up the project are a Height above sea level 1000 m b Inside temperature 35 C c Climate continental d
26. 2 GENERAL DATA RATING DATA CHARACTERISTIC WEIGHTS ACCESSORIES ALTERNATOR DATA SHEETS QUANTITY MANUFACTURER REFERENCE STANDARD REFERENCE DWGS RATED POWER kVA STATOR INSULATION CLASS OVEREXCITATION POWER cosp ROTOR INSULATION FACTOR CLASS RATED POWER MANUFACTURING SHAPE FREQUENCY Hz CLOSING NUMBER OF POLES No COOLING SYSTEM SPEED g l COOLANT FLUID NUMBER OF PHASES No COOLANT FLUID FLOW RATE mc h PHASE CONNECTION LOSS OF LOAD IN THE mmo COOLANT NUMBER OF TERMINALS No EXCITATION SYSTEM CURRENT AT RATED POWER A EXCITATION VOLTAGE RATED kVA OVERSPEED EXCITATION CURRENT RATED kVA GENERATOR PD2 Kgm MAX EXCITATION CURRENT TYPE OF COUPLING EXCITER COOLING PD2 FIRST MOTOR Kem EXCITER RATED POWER COOLANT C EXCITER CLOSING TEMPERATURE ITEM TYPE REFERENCE SPECIFICATION D C RATIO IN SATURATED VOLTAGE VARIATIONS REGIME AT RATED VOLTAGE FULL LOAD TRANSIENT REACTANCE EMPTY WITH EXCITAION AND STRAIGHT TRANSIENT CONSTANT SPEEDS REACTANCE SYNCHRONOUS REACTANCE yield 4 4 load REACTIVE POWER UNDER EXC ADJ convention 5 0 OVEREXC ADJ STATOR WEIGHT Kg WEIGHT OF ACCESSORIES ROTOR WEIGHT Kg TOTAL WEIGHT HEAVIEST PART TO BE LIFTED Kg COOLING SYSTEM L TA x PROTECT DIFFERENTIAL No CONTROL AIR OR GAS CIRC SIGNAL L VOLTAGE AND ACCESS BOARD FIELD ELEMENTS SIDE PLATES DO O D O D O PAINTING COLOUR CYCLE NOTES
27. A 009 Wii ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 21 of 33 9 4 5 Sistema di presenza tensione e sgancio tensione Nel Quadro Elettrico di Comando e Controllo dovr essere predisposto un sistema di presenza tensione per a tensione uscita dal trasformatore EC1 b tensione uscita dal trasformatore EC3 c tensione sbarra ET1 ET2 d tensione sbarra ET3 e tensione arrivo linea a 380V 50Hz Ogni linea in ingresso dovr essere dotata oltre agli scaricatori di sovratensione e relativi fusibili di protezione come paragrafo 9 1 12 paragrafo 9 4 4 di alimentatore con trasformatore di sicurezza avente secondario a 24Vcc Il sistema dovr segnalare una presenza tensione all interno del Quadro 9 4 6 Sistema Antincendio e Spegnimento Nel Quadro di Controllo Impianto Antincendio dovr essere predisposto un sistema di Spegnimento con la seguente logica a intervento di 1 2 rivelatori preallarme che dovr fornire allarmi a 1 al pannello di controllo sul Quadro Elettrico di Comando e Controllo a 2 alla sala controllo a 3 al sistema di supervisione b intervento in logica 2 2 deve generare allarmi b1 ai pompieri b2 al pannello di controllo sul Quadro Elettrico di Comando e Controllo b3 alla sala controllo b4 al sistema di supervisione e dovr comandare il sistema di Spegnimento condizionato dal pulsante posto all esterno del container 9 5 Segnalazioni e allarmi Du
28. CHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 5 of 33 j montaggio tubazioni elettrovalvole valvole ecc comprensivi di tutte le staffe ed i sistemi di supporto k realizzazione e o ripristino dei collegamenti meccanici al nuovo Gruppo Elettrogeno EE 1 sistemi gas di scarico e ventilazione I verifica condizioni di ricambio aria locale verifica condizioni di immissione ed emissione aria comburente e di raffreddamento del gruppo m verifica dell idoneit della tubazione di scarico gas e relativo silenziatore esistenti e rilascio di dichiarazione di conformit per il nuovo gruppo n consegna manuali d uso e manutenzione o training almeno 2 giornate per l esercizio e la manutenzione del Gruppo Elettrogeno p messa in servizio collaudi ed avviamento del nuovo Gruppo Elettrogeno EE 1 con simulazione degli automatismi dell impianto nuovo e o esistente LIMITI DI BATTERIA PRECISAZIONI Per la fornitura ed il montaggio del nuovo Gruppo Elettrogeno saranno considerati i seguenti limiti di batteria a morsettiere e o interruttori sul Quadro Elettrico Generatore per il collegamento di potenza e o dei circuiti ausiliari con la parte di impianto non oggetto di fornitura b punti di attacco tubazioni del troppo pieno serbatoio giornaliero e per il carico gasolio dal serbatoio di stoccaggio esterno alla sala diesel sono a cur
29. COPIA CONFORME ARCHIVIO NDU 2012 06 12 JOINT RESEARCH CENTRE ISPRA SITE MANAGEMENT European NUCLEAR DECOMMISSIONING UNIT Commission pe WBS Project title Safely conserving INE Project sub project code WBS ref 1 08 01 01 NE 45 0860 A 009 Document number ND 45 0801015 A 001 Rev 0 Page 0 of 33 Document type Specifica tecnica Title Sostituzione gruppo elettrogeno EE1 INE Abstract Il documento contiene dettagli tecnici per l acquisizione e l installazione di un nuovo Gruppo Elettrogeno che andr a sostituire il Gruppo Diesel EE1 INE Key words Supersedes document ref Name Signature Date Prepared by MANIACI Federico JAD BOOS Z 2 HUHTINIEMI lipo 30 05 2242 CHINDAMO Alessio Verified by Jo COVINI Roberto RTI 30 03 i OSIMANI Celso lt verified by MACAVERO Egidio L b 2 Approved by C e e eu Action Information i Huhtiniemi A Chindamo Internal distribution G Munda E Vaccarezza Appfoval External distribution Candidate Contractors ai Limited Pai distribution PO FILING Date OB gt 2 Signature COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 1 of 33 Revision Revision Description 00 Initial release 01 02
30. ME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE PROTEZIONE REOSTATO Corto circuito da scatto interruttore Disinserzione reostato Preallarme da reostato SISTEMA CARICAMENTO COMBUSTIBILE Max livello serbatoio giornaliero Basso livello serbatoio giornaliero 57 Guasto pompe gasolio Perdite fondo vasca serbatoio di stoccaggio SISTEMA ANTINCENDIO i 2 NA 2 NC 2 NA 2 NC 2 NA 2 NC 2 NA 2 NC 2 NA 2 NC 2 NA 2 NC 2 NA 2 NC 2 NA 2 NC 23 of 33 nserzione sistema spegnimento nota i 2 NA 2 NC x x X 2 NA 2 NC o Guasto pulsante di spegnimento nota Sistema antincendio Preallarme nota SISTEMA PRESENZA TENSIONE 380Vca 2 NA 2 NC Disinserzione reostato Allarme da reostato 64 Mancanza tensione ECS logica 1 8 2 NA 2 NC 65 Mancanza tensione ET1 ET2 logica 1 3 2 NA 2 NC Mancanza tensione EC1 logica 1 3 X X X Mancanza tensione ET3 logica 1 3 X X 2 NA 2 NC Arresto diemergenza o J X X 2 NA 2 NC 69 aria chiuse logica 1 2 x X 2 NA 2 NC 70 Perdite sulfondodelcontainer d x X 2 NA 2 NC Intervento protezioni alim 24Vcc 2 NA 2 NC 71 X Intervento protezioni alim 380Vca 2 NA 2 NC SIRENA 7 TIPO DI VISUALIZZAZIONE INTERVENTO DESCRIZIONE DISPLAY LED STOP DISPONIBILE Tee Fe O j j
31. TRANSPORT The supplier shall give the following information with at least 10 days notice a expected delivery date b expected date of arrival on site c means of transport 14 DATA SHEETS The following Data Sheets are to be completed by the supplier COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 30 of 32 DIESEL ENGINE DATA SHEETS QUANTITY ITEM GENERAL DATA MANUFACTURER TYPE REFERENCE STANDARDS REFERENCE SPECIF REFERENCE DWGS Cee RATING DATA POWER MAXIMUM Kgm RPM nre 7 NUMBER POSITION STROKE TYPE VISCOSITY RE k SPECIFIC Kgdm FLOW RATE l min BRE M _ RADIAL TYP THRUST TYPE L E COMPRESSION WIEGHT t m eee WEIGHT TO LENGHT ma __ CHARACTERISTICS EFFICIENCY HEIGHT TYPE OF SERVICE WIDTH mm STARTUPS E JOINT Kgm REQUIRED IN A MONTH TYPE MATERIAL DIAMETER FUEL STORAGE TANK CAPACITY HEIGHT TYPE FEEDING ELECTRIC MOTOR POWER kW ISOLATING CLASS SPEED RPM LI EXCLUDED INCLUDED TYPE FLOW RATE l sec COOLING WATER TYPE CASING 1 ON LUBE OIL CHANGE TIME NOTES DI DIRECT INJECTION ADVANCE COMBUSTION CHAMBER TC TURBOLENCE CHAMBER SE SINGLE EFFECT DE DOUBLE EFFECT COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 31 of 3
32. URA Painting technical specification ELENCO MATERIALI RICAMBI E ATTREZZATURE PER MESSA IN SERVIZIO Spare part material and special tools list for the commissioning QUOTAZIONE PER SERVIZIO ANUTENZIONE 2 anni ELENCO PREZZATO PARTI DI RICAMBIO Priced spare part list PIANI CONTROLLO QUALITA Quality control plans PIANO OPERATIVO DI SICUREZZA POS MANUALI DI USO E MANUTENZIONE Erection operation and maintenance manuals COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 28 of 33 Descrizione della documentazione PROVA DI TIPO RAPPORTO DI COLLAUDO Type test certificates PROVA DI ROUTINE RAPPORTO DI COLLAUDO Routine test certificates SPECIFICHE IMBALLO TRASPORTO MAGAZZINAGGIO Packing Transport Store Specifications NOTE 1 PA Per approvazione PI Per informazione DF Documentazione finale N Copie opache C Su supporto EDP Prima del collaudo Dopo il collaudo Dopo le prove Prima della spedizione 2 3 4 5 we wa TLC DN Tutta la documentazione relativa alla fornitura in oggetto dovra essere Modalita di consegna con dopo ordine offerta PA 1 PI 1 n n n gg n n gg copie copie da copie da 1 ordine 1 ordine redatta nei formati MS Word MS Excel Autocad 2004 prodotta con le targhette e le identificazioni come da procedura della Committente ved a
33. a del Fornitore i collegamenti fino alle tubazioni da al serbatoio esterno che verranno predisposte al di sotto della soletta su cui poser il gruppo c flangia e tubazione gas di scarico fino al giunto di dilatazione esistente A titolo esemplificativo ma non limitativo si riepilogano di seguito le attivit e o i materiali compresi nello scopo dei lavori d tutti i mezzi di sollevamento e o attrezzature per sollevamento e installazione e bulloni di fondazione e sistema di ancoraggio per il container f spessori di livellamento eventuali g viti di registrazione eventuali h pezzi di centraggio da annegare nella fondazione eventuali i tutti i tipi di chiavi utilizzate j tutte le targhette di identificazione k targhe di pericolo COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 6 of 33 elenco materiali ricambi e attrezzature per messa in servizio m olio e liquidi di primo riempimento n materiali per la messa in servizio e avviamento o messa in servizio e avviamento con simulazione degli automatismi dell impianto esistente p attrezzature per l esercizio del Gruppo Elettrogeno q cavi elettrici di interconnessione all interno del container r collegamenti di messa a terra all interno del container con predisposizione per la connessione alla rete generale dell impiant
34. a mancanza tensione EC1 880Vca 8F V lt 85 segnalazione Presenza mancanza tensione EC3 380Vca 8F V lt 85 segnalazione Presenza mancanza tensione ETW ET2 380Vca 3F mancanza V startdiesel Presenza mancanzatensione 380Vca SF mancanza V start diesel Presenza mancanza tensione linea 380Vca AmvolineaSB0Vca 8F Wh Wa 0 NOTE Quantit e posizione contatti in ingresso alla morsettiera Quantit e posizione contatti in uscita dalla morsettiera Quan iz Quantit e posizione contatti resi disponibili a morsettiera tramite rel gestiti in fail safe 4 contatti di pos 7 8 devono essere in scambio e resi disponibili a morsettiera 4 5 6 7 v 19 lt OA 13 14 15 16 18 k W 1 2 3 COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 25 of 33 9 6 2 Segnali a remoto TIPO DI SEGNALE DESCRIZIONE OUT 1 2 Gruppo pronto a prendere carico 1 NA 1 NC Dispon in pos Auto Dispon in pos Auto Test senza segnali di blocco Velocit Gruppo 380 g min 1 NA 1 NC a registratore a registratore 7 a registratore Sovracorrente corto circuito generatore 2 NA 2 NC nota Arresto di emergenza 2 NA 2 NC nota Tensione generatore lt 70 Alt Volt lt 1 NA 1 NC 70
35. acture to ensure perfect alignment with anti vibration elastic supports b The base with generating set will be positioned inside the sound proof container as per point 9 1 14 9 1 2 Diesel motor a Motor manufactured by leading companies in the European market suitable for continuous and heavy duty use and with class A1 electronic rev regulator and with the following features a 1 4 stroke a 2 direct injection COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 10 of 32 a 3 12 V cylinders a 4 turbo supplied and inter cooled exhaust a 5 fuel type in compliance with BS 2869 1970 classes A1 and A2 9 1 3 Exhaust and cooling systems a Air exhaust system with dry filters with replaceable components with clogging indicator The system s manufacture shall allow easy replacement of the filtering components b Cooling system with fan driven by the motor and radiators The system shall be supplied complete with alarm devices and high temperature protection c The system shall be supplied complete with silenced ducts with gravity shutters and firebreak shutters inside the container in compliance with regulations and ministerial directives in force The supplier shall supply and install gravity shutters on the existing window of the building on the exhaust side with dimensions to be checked In any case the su
36. arry out autonomously sending the Customer the connected certification later at most within 15 days preceding the inspections 12 1 Tesis on the components Before the assembly all the tests laid down by the standards will be carried out on the individual components of the supply or the individual certificates of inspection that attest that the acceptance test had been carried out will be required 12 2 Acceptance tests All the tests laid down by the standards and or agreed previously will be carried out on the completely assembled device 12 3 Certification The certificates concerning the materials and tests and inspections laid down agreed shall be supplied The certificates concerning the type tests laid down by the standards will be sent to the Customer within a month from the order The type test certificates can also be relative to devices similar to those which are the subject of the supply as long as the manufacturer can supply evidence that the tests carried out can be extended to the devices in question COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 29 of 32 GENERATING SET MANUFACTURER S ROUTINE TEST CERTIFICATE OR DECLARATION OF CONFORMITY TO THE APPLICABLE STANDARDS L V DISTRIBUTION BOARDS TEST LIST APPLICABLE STANDARD IEC 439 1 DESCRIPTION OF THE TEST TYPE TESTS ROUTINE TESTS ASSEMBLY INSPECTION 13
37. ating set c piping to expel exhaust gas to outside the Diesel Room and external duct d disconnection and recovery of existing electrical components cables boards generating sets etc e disposal of the existing generating set COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 26 of 32 11 DOCUMENTATION The supplier shall carry out the functional and manufacturing design of the equipment in question and shall supply the drawings as indicated below No of days from order offer Description of the documentation PA 1 PI 1 DF 1 No of No of i i i days from copies copies copies copies i A 1 pi inspection ree o OF DOCUMENT peu None DIMENSIONAL DRAWINGS AND CALCULATIONS OF THE CONTAINER BASE STRUCTURE DIMENSIONAL DRWGS WITH STATIC AND DYNAMIC LOADS FOR TRASP amp INSTALL DATA 5 a TERMINAL BOARD DRAWINGS LAYOUT OF ASSEMBLY COMPONENTS SPARE PART MATERIAL AND SPECIAL AND SPECIAL TOOLS LIST FOR THE COMMISSIONING repay T c NE FOR N 1 OPERATION AND MAINTENANCE MANUALS 5 2 3N 20 3 COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 27 of 32 No of days from order with after order offer Description of the documentation PA 1 PI 1
38. d down by Lgs D 81 08 g supply transport and placement of the sound proofing container complete with generating set distribution board and all the systems necessary for complete operation h inserting the new EE 1 generating set through the existing entry door i assembly of the new EE 1 generating set j assembly piping solenoid valves valves etc including all the brackets and support systems k making and or restoring the mechanical connections to the new EE 1 generating set gas exhaust and ventilation systems COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 5 of 32 checking room air change conditions checking combustive air intake and emission and unit cooling conditions m checking the suitability of the discharge gas piping and its existing silencer and issuing of a declaration of conformity for the new Unit n consignment of the user and maintenance manual o training at least 2 days for the operation and maintenance of the generating set commissioning inspections and starting of the new 1 generating set with simulation of the new and or existing system control units BATTERY LIMITS CLARIFICATIONS The following battery limits will be considered for the supply and assembly of the new generating set a terminal boards and or circuit breakers on the generator distributi
39. de the container r earth connections inside the container with setup for the connection to the system main power supply REGULATIONS AND REQUIREMENTS The applicable IEC ISO standards are a CEI EN 60034 1 Rotating electrical machines Part 1 rated features 2 3 and features of operation b CEIEN 60947 2 Low voltage switchgear and control gear Part 2 17 5 automatic circuit breakers c CEI EN 60439 1 Low voltage switchgear and controlgear assemblies 17 13 Part 1 standard type tested AS devices and non standard partially type tested devices ANS d CEI EN 60204 1 Electrical equipment of machines 44 5 e CEI EN 50081 2 Electromagnetic compatibility Generic emission standard 110 13 Part 2 Industrial environment f CEI EN 50082 2 Electromagnetic compatibility Generic immunity standard 110 25 Part 2 Industrial environment g IEC 227 PVC Insulated cables of rated voltages up to and including 450 750 V h IEC 228 Conductors of insulated cables Part A First supplement Guide to the dimensional limits of circular conductors i IEC 332 Test on electric cables under fire conditions Part 3 tests on bunched wires or cables j IEC 439 1 Modular low voltage switchgear system k ISO 3046 Reference conditions and tests for internal combustion engines and subsequent variants and completions Also COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev
40. di tutti i sistemi necessari al funzionamento L installazione dovr comprendere la consegna di tutto il materiale presso il CCR di Ispra edificio 85 le fasi di testing ed il successivo training per il personale b item MAINTENANCE servizio di manutenzione programmata e correttiva nel corso del periodo di garanzia di 2 anni con intervento per correttiva entro 48 ore dalla chiamata Luned successivo per chiamata effettuata il venerd incluse le parti di ricambio necessarie per eseguire la manutenzione programmata liquidi compresi ATTIVITA DI SMONTAGGIO FORNITURA E MONTAGGIO Generalit Le attivit in oggetto interessano l edificio 85 Sala Diesel ubicato nel CCR di Ispra VA dove attualmente esistono n 3 Gruppi Elettrogeni aventi item EE1 EE2 con avviamento ad aria compressa e raffreddamento ad acqua con scambiatore acqua acqua ed EE3 con avviamento a motore elettrico e raffreddamento ad acqua con scambiatore acqua aria Con riferimento ai documenti in allegato paragrafo 6 Ogni Gruppo Elettrogeno collegato elettricamente ad un proprio sistema di sbarre ET1 ET2 ET3 ed a un reostato di prova comune a tutti i Gruppi Elettrogeni Il Gruppo Elettrogeno esistente EE1 da 1500 kVA dovr essere sostituito con un Gruppo Elettrogeno EE1 nuovo avente avviamento con motore elettrico e raffreddamento ad acqua con radiatore acqua aria ved paragrafo 8 1 La Sala Diesel attualmente dotata tra l altro di n 8 g
41. e COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 14 of 33 a 6 con predisposizione adeguata per la connessione dei cavi in uscita n 3x 7x185 mm b Interruttore magnetico tripolare item ED101 per reostato come segue b 1 del tipo fisso ABB Schneider o equivalente con In 2500 A 5 b 2 con motore carica molle 24Vcc b 3 con bobina di apertura chiusura a 24Vcc b 4 con contatti ausiliari di posizione scatto b 5 con predisposizione adeguata per la connessione dei cavi in ingresso n 3 7 185 mm b 6 con scaricatori di sovratensione e relativi fusibili sulla linea in ingresso c Comandi e segnalazioni sul fronte quadro c 1 Selettore Locale 0 Distanza per il comando dell interruttore ED13 c 2 Pulsante luminoso di colore verde come da esistente per chiusura interruttore ED13 c 3 Pulsante luminoso di colore rosso come da esistente per apertura interruttore ED13 c 4 Indicatore luminoso di colore bianco come da esistente per scatto termico interruttore ED13 d Comandi Segnalazioni Allarmi resi disponibili a morsettiera per interruttore ED13 Vedere tabella al paragrafo 9 6 e Comandi Segnalazioni Allarmi resi disponibili a morsettiera per interruttore ED101 Vedere tabella al paragrafo 9 6 9 1 12 Quadro Elettrico di Comando e Controllo del G E
42. e pressures and alarms and led to show the main alarms as in the table of section 9 5 f Commands signals alarms made available on the terminal board See tables in sections 9 5 amp 9 6 9 1 13 Fire fighting and extinguishing system Fire fighting and extinguishing system for the generating set in container made in compliance with the laws and Ministerial Provisions in force The system shall be supplied complete with a Fire fighting system control board b 2 detectors of suitable type c cylinders placed outside the building and connected between this and the container with adequate piping d Push button to switch on the fire extinguishing system placed outside the container and near the control board fire fighting system In each case the supplier is obliged to check the above and if necessary provide any further devices and or devices that prove to be necessary 9 1 14 Sound proofing system and container Sound proofing system made with container to lower the sound pressure to a level of 70 dBA measured at a distance of 7 metres and containing what is indicated from point 9 1 1 to point 9 1 13 Max indicative dimensions of the container LxDxH 10500x2200x2900 mm The container must be fitted with a light system and 220V FM sockets b sensor on the bottom of the container to detect the liquid leaks COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Rep
43. emi di aspirazione e di raffreddamento a Sistema di aspirazione aria con filtri del tipo a secco a elementi sostituibili con indicatore di intasamento La costruzione del sistema dovr permettere una facile sostituzione degli elementi filtranti b Sistema di raffreddamento con ventola azionata dal motore e radiatori Il sistema sar completo di dispositivi di allarme e protezione per alta temperatura c Il sistema dovr essere completo di condotti silenziati con serrande a gravit e serrande tagliafuoco all interno del container secondo normative e direttive ministeriali vigenti Il fornitore dovr provvedere alla fornitura ed installazione di serrande a gravit sulla finestra esistente dell edificio posta sul lato aspirazione con dimensioni da verificare In ogni caso il fornitore dovr una volta effettuato il sopraluogo individuare le condizioni ed opere necessarie per una corretta aspirazione e scarico dell aria tenuto conto che il gruppo fornito potrebbe funzionare in condizioni di test contemporaneamente al gruppo elettrogeno EE3 9 1 4 Sistema di preriscaldamento Sistema di preriscaldamento con resistenze del tipo corazzato Il sistema provveder a riscaldare l acqua di raffreddamento nel motore fermo in modo da assicurare l immediato avviamento da freddo anche con temperatura ambiente di 10 C Il sistema di preriscaldamento sar inserito automaticamente all arresto del motore e disinserito al suo avvia
44. emperature indicators c 3 Starting battery charge indicator c 4 Voltage current frequency power active generator indicators c 5 Rheostat current indicator c 6 Daily fuel tank level indicator c 7 Fuel storage tank level indicator 4 20 but c 8 Speed indicator c 9 Hours of operation and number of starts totaliser c 10 Digital oil pressure indicator c 11 Generator winding temperature indicators phases R S T c 12 Current transformers secondary 5A generator side to protect devices and measurements d Power supply auxiliary circuits 24V dc command and alarm circuit supplied by the starting circuit batteries and the 380V ac 24V dc power supply this circuit shall have 24V dc starting for the power supply of the power control unit auxiliary circuits COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 15 of 32 e Command and control systems e 1 System to check the presence of 380V 50Hz three phase voltage as in section 9 4 4 e 2 System to control presence and voltage release as in section 9 4 5 e 3 Relay logic for command control and protection of the automatic fuel supply system e 4 Command and control logic with microprocessor to manage the G S with connection available to connect the programming diagnostic system e 5 Panel complete with display to read the temperatur
45. etup adequate for the connection of the output cables 3x 7x185 mm b Magnetic three pole circuit breaker item ED101 for rheostat as follows b 1 fixed type ABB Schneider or equivalent with In 2500 A 5 KA b 2 with 24Vdc spring loading motor b 3 with 24Vdc opening closing coil b 4 with auxiliary position trip contacts b 5 with adequate setup for the connection of the incoming cables No 3x 7x185 mm b 6 with overvoltage arresters and fuses on the incoming line COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 13 of 32 c Commands and signals on the board front c 1 Local 0 Distance selector switch to command circuit breaker ED13 c 2 Green luminous push button as existing to close circuit breaker ED13 c 3 Red luminous push button as existing to open circuit breaker ED13 c 4 White luminous indicator as existing to trip thermal device circuit breaker ED13 d Commands signals alarms made available on the terminal board for circuit breaker ED13 See table in section 9 6 e Commands signals alarms made available on the terminal board for circuit breaker ED101 See table in section 9 6 9 1 12 G S command and control distribution board Command and control manual automatic distribution board with at least a Power circuits Incoming 380V 50Hz 3P
46. gnals can be added during the detailed definition of the interface with the remote logic 9 6 1 Remote signals TYPE OF SIGNAL Command only with unit in Automatic Opening closing circuit breaker ED18 __ Opening closing circuit breaker ED101_ 2NO 7 Presencelloss of voltage ECI 7 S80Vca SF V 85 signal Presencellossofvoltage EC 80 V lt 85 signal Presencelloss of voltage ETIET2 880Vca SF noV statdiesel Presencellossofvoltage ET3 S80Vca SF noV statdiesel Presencelloss of voltage line 380Vac Incomingline3B0Vca 8F 6 EA 19 hu 12 14 15 16 18 19 NOTES 1 Quantity and position of contacts to the terminal board 2 Quantity and position of contacts from the terminal board 3 Quantity and position of contacts made available on the terminal board by means of relays managed in fail safe 4 The contacts of pos 7 8 must be in exchange and on the terminal board made available COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 24 of 32 9 6 2 Remote signals TYPE OF SIGNAL DESCRIPTION OUT 1 2 Unit ready to be filled 1 NO 1 NC Available in Auto pos Unit in standby 1 NO 1 NC Available in Auto Test pos without block signal
47. he required power is reached Circuit breaker ED101 can always be opened with the following faults c 1 low pressure lubrication circuit c 2 high motor temperature c 3 high low speed c 4 alternator failure c 5 operating generating set emergency c 6 push button voltage release placed outside the building pressed c 7 the push button for switching on fire extinguishing in the container and container fire prealarm pressed c 8 switching off rheostat for alarm c 9 request for help for loss of voltage contact from Electron board The Test position does not inhibit the operation if there is a request for help as in section 8 4 d Selector switch in Stop position In this position generating set EE1 will not be available and circuit breaker ED13 will be opened automatically COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 19 of 32 9 4 4 380V 50Hz three phase voltage present control system The command and control distribution board shall have a voltage present 380V 50Hz system IT three phase control system for a voltage from transformer EC1 b voltage from transformer EC3 c bus bar ET1 ET2 voltage d bus bar ET3 voltage The system shall include terminal boards for the connection of the incoming lines and each of them shall be fitted with overvoltage arresters and protection fuses this re
48. here are no faults on the ET1 ET2 or ET3 the EE1 generating set will start with the following sequence starting the EE1 generating set opening circuit breakers ED11 and ED31 checking that circuit breakers ED14 and ED35 are open checking that circuit breakers ED13 and ED12 are closed these circuit breakers are normally closed closing circuit breaker ED35 after checking that circuit breakers ED11 and ED31 have opened and that the EE3 generating set has reached regime and closing circuit breaker ED14 Return to the normal situation The power supply will exclusively return automatically from emergency to normal and with the CN26 changeover switch in automatic position if there is power to the two LV incoming lines of the transformers on the Unit after a delay which can be set between 1 and 30 minutes after the voltage returns the ET1 ET2 and bus bars will automatically switch from the generating set to the respective transformers and the generating set will be stopped on a signal from external logics after about 3 minutes from the reset of the normal configuration With changeover switch CN26 in the manual position the operator will return the system to the normal configuration COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 9 of 32 8 3 8 4 9 1 Manual operation In manual operation i e with CN26 in Manual p
49. lacement of EE1 INE generating set 16 of 32 9 1 15 Container support base The base of the container shall be fitted with a metal structure designed and manufactured to be adapted to the support of the container itself and to being laid on an existing foundation having dim 7300X2400mm 9 1 16 Materials and or various finishing activities such as Solenoid valves valves push buttons warning signs and whatever else is required by the regulations in force 9 2 General electrical features Rated power from 1350 to 1400 kVA 10 Overload 11096 x 1h each 12h Power factor 50 0 8 Electrical system classification IT Adjustment voltage 1 5 Adjustment frequency 1 Distribution board Operating voltage 380 V 50 Hz 3F main bus bar output 2500 9 3 General manufacturing features Generating set and distribution board in container Container installation in heated closed room Max starting time 5s Max time from starting to filling 16s Cable entry from the bottom Entry of fuel filling piping from the bottom 9 4 Principle of operation 9 4 1 Local 0 Distance selector switch on the power distribution board The local 0 Distance selector switch on the power distribution board allows the following operating conditions a Selector switch in Local position In this position circuit breaker ED13 can be controlled by means of the opening and closing push buttons on the front of the powe
50. li di isolamento e o di protezione dovranno essere incombustibili ed esenti da materiali nocivi 9 1 9 Generatore Elettrico Generatore Elettrico costruito da ditte di primaria importanza nel mercato Europeo con le seguenti caratteristiche a di tipo sincrono trifase senza spazzole autoregolato autoeccitato auto ventilato b con isolamento classe H e con sovratemperatura classe F c con parti in movimento adeguatamente protette con ripari asportabili protezione meccanica IP23 d con regolazione automatica di tensione fino a 1 da vuoto a pieno carico e con dispositivo tachimetrico per la rilevazione della velocit sopra i 380g min deve essere presente un contatto di intervento f comprensivo di resistenze anticondensa e relativo termostato g con cuscinetti di rotolamento lubrificati a grasso 9 1 10 Accoppiamento Accoppiamento Motore Generatore diretto tramite disco flessibile e campana di flangiatura 9 1 11 Quadro Elettrico di Potenza Quadro Elettrico di Potenza con almeno a Circuiti di potenza Interruttore magnetotermico tripolare item ED13 di macchina come segue a 1 del tipo aperto estraibile con apposite guide di sostegno ABB Schneider o equivalente con In 2500 A 5 KA a 2 con motore carica molle a 24Vcc a 3 con bobina di apertura chiusura a 24Vcc a 4 con contatti ausiliari di posizione scatto a 5 con controllo elettronico per la protezione del generator
51. llegato C trasmessa a Commissione Europea Centro Comune di Ricerca Via E Fermi 2749 21020 Ispra Va 21020 Ispra VA ISM Ispra Site Management Unit di Disattivazione Impianti Nucleari TP 800 Attenzione F Maniaci COPIA CONFORME ARCHIVIO NDU 2012 06 12 a Rev 0 Sostituzione gruppo elettrogeno EE1 INE 29 of 33 12 FABBRICAZIONE PROVE E COLLAUDI Il Fornitore dovr emettere dei Piani di Controllo della Qualit da sottoporre per approvazione alla Committente sui quali con riferimento alla normativa applicabile saranno elencate tutte le prove eseguite sui singoli materiali utilizzati per la costruzione dei componenti della fornitura Il documento citato dovr essere redatto sul format della Committente ved allegato C la quale indicher gli esami controlli prove e collaudi a cui intende presenziare e quelli che il Fornitore potr eseguire autonomamente inviando in seguito alla Committente la relativa certificazione al massimo entro i 15 giorni precedenti i collaudi 12 1 Prove sui componenti Prima del montaggio saranno eseguite sui singoli componenti della fornitura tutte le prove previste dalle norme o saranno richiesti i singoli certificati di collaudo che attestano l avvenuta prova di accettazione 12 2 Prove d accettazione Sull apparecchiatura completamente montata saranno eseguite tutte le prove previste dalle Norme e o concordate in precedenza 12 3 Cer
52. mento 9 1 5 Sistema di avviamento Sistema di avviamento elettrico completo di n 2 gruppi di batterie al Pb a 24V e raddrizzatore di ricarica Il raddrizzatore dovr essere dimensionato per l alimentazione dei carichi relativi ad EE1 e necessari al funzionamento del Gruppo e la contemporanea ricarica delle batterie COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 12 of 33 La batteria dovr assicurare in caso di fuori servizio del raddrizzatore l alimentazione dei carichi per almeno una settimana ed avere capacit tale da garantire n 6 avviamenti consecutivi ognuno della durata di 10 sec 9 1 6 Sistema di alimentazione e di carico combustibile Sistema di alimentazione e di carico combustibile comprensivo di a N 1 serbatoio gasolio giornaliero da minimo 1000 It montato a bordo macchina b N 2 elettropompe autoadescanti per il carico automatico pescante posto 4 1 pompa a mano montate a bordo macchina c Accessori necessari a rendere il sistema completo e funzionante In particolare per il serbatoio giornaliero c 1 tubazione per il carico combustibile con diametro adeguato verso il serbatoio di stoccaggio da 25000lt sulla tubazione il fornitore dovr installare all esterno del container 2 gruppi filtri di fornitura CCR per la separazione acqua gasolio c 2 tubazione di tropp
53. monitoring system b operation in 2 2 logic must generate alarms b1 to the fire brigade b2 to the control panel on the command and control distribution board b3 to the control room b4 to the monitoring system and shall control the extinguishing system conditioned by the push button placed outside the container 9 5 Signals and alarms During operation the generating set will be monitored by any faults displayed on the distribution board as in the table given below All the alarms given must be managed in fail safe COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 21 of 32 TYPE OF DISPLAY OPERATION DESCRIPTION DISPLAY LED SIREN stop AVAILABLE FOR 1 7 2 icd 1 Automatic oy Selector swit x NOH NC 2 Manual by selector swit J x 3 Test byselectorswitch __ x P 1NOHNC Stop by selector switch SI 5 Auxiliary voltage present X f 2NO2NC 6 Generatorvoltage present J x 2 NOH f nonne ui 2 Preheating OFF V 2 NO 2 NC 2 Em 9 19 11 0004 12 FuelpumpOFF 02 a 15 Battery charge ON 2 NO 2 NG NEZ J e en S 2 Stop by push button 17 Battery present MOTORPROTECTION DEVICES 19 Nostating
54. ncio tensione come da paragrafo 9 4 5 e 3 Logica a rel per comando controllo e protezione del sistema di adduzione automatica del combustibile e 4 Logica di comando e controllo a microprocessore per la gestione del G E con connessione disponibile per collegamento sistema di programmazione diagnostica e 5 Pannello completo di display per la lettura delle temperature pressioni e allarmi e di led per evidenziare gli allarmi principali come da tabella di paragrafo 9 5 f Comandi Segnalazioni Allarmi resi disponibili a morsettiera Vedere tabelle ai paragrafi 9 5 amp 9 6 9 1 13 Sistema Antincendio e di Spegnimento Sistema Antincendio e di Spegnimento per il Gruppo Elettrogeno in container realizzato secondo Leggi e Disposizioni Ministeriali vigenti Il sistema dovr essere completo di a Quadro di Controllo Impianto Antincendio b n 2 rivelatori del tipo idoneo COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 17 of 33 9 2 c bombole poste all esterno dell Edificio e collegate tra questo ed il container con tubazione adeguata d pulsante di inserzione sistema di Spegnimento incendio posto all esterno del container e nelle vicinanze del Quadro di Controllo Impianto Antincendio In ogni caso il Fornitore tenuto a verificare quanto sopra esposto ed eventualmente integrare con ulteriori apparecchiature e
55. ner c 8 disinserzione reostato per allarme c 9 richiesta di ripresa in soccorso per mancanza tensione contatto proveniente da Quadro Electron La posizione di Test non inibisce il funzionamento in caso di richiesta di soccorso come da paragrafo 8 4 d Selettore in posizione Stop In questa posizione il Gruppo Elettrogeno EE1 non sar disponibile e verr aperto automaticamente l interruttore ED13 9 4 4 Sistema di Controllo presenza tensione 380V 50Hz trifase Sul Quadro Elettrico di Comando e Controllo dovr essere predisposto un sistema di controllo presenza tensione 380V 50Hz sistema IT trifase per a tensione uscita dal trasformatore EC1 b tensione uscita dal trasformatore EC3 c tensione sbarra ET1 ET2 d tensione sbarra ET3 Il sistema dovr comprendere apposite morsettiere per il collegamento delle linee in arrivo e ognuna di esse dovr essere dotata di scaricatori di sovratensione e relativi fusibili di protezione da verificarne la necessit in base all allegato D In caso di mancanza tensione il sistema dovr generare per ogni linea con tempo 0 5 sec una segnalazione di allarme sul sistema di controllo del G E e renderla disponibile a morsettiera tramite rel cablati fail safe La logica di funzionamento sar a 1fase 3fasi allarme b 2fasi 3fasi intervento con l avviamento del Gruppo Elettrogeno COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860
56. o NORMATIVE E PRESCRIZIONI Le Norme CEI IEC ISO applicabili sono a CEI EN 60034 1 2 3 b CEI EN 60947 2 automatici 17 5 c CEI EN 60439 1 17 13 d CEI EN 60204 1 44 5 e CEI EN 50081 2 110 13 f CEI EN 50082 2 110 25 g IEC 227 h IEC 228 i IEC 332 Macchine elettriche rotanti Parte 1 Caratteristiche nominali e di funzionamento Apparecchiature a bassa tensione Parte 2 Interruttori Apparecchiature assiemate di protezione e manovra per B T Parte 1 Apparecchiature di serie soggette a prove di tipo AS e apparecchiature non di serie parzialmente soggette a prove di tipo ANS Equipaggiamenti elettrici delle macchine Compatibilit elettromagnetica Norma generica sull emissione Parte 2 Ambiente industriale Compatibilit elettromagnetica Norma generica sull immunit Parte 2 Ambiente industriale PVC Insulated cables of rated voltages up to and including 450 750 V Conductors of insulated cables Part A First supplement Guide to the dimensional limits of circular conductors Test on electric cables under fire conditions Part 3 tests on bunched wires or cables COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A me ND m i Rev 0 Sostituzione gruppo elettrogeno EE1 INE 7 of 33 j IEC 439 1 Modular low voltage switchgear system k ISO 3046 Condizioni di riferimento e prove per motori a combustione interna e s
57. o pieno con diametro adeguato verso il serbatoio di stoccaggio da 25000lt priva di valvole o saracinesche di qualsiasi genere c 3 le tubazioni devono essere collegate a quelle esistenti al di sotto del solaio nelle immediate vicinanze c 4 dispositivo di intercettazione del flusso e dispositivo di arresto delle pompe di alimentazione atti ad intervenire automaticamente quando il livello nel serbatoio giornaliero supera quello massimo consentito o in caso di allarme incendio c 5 sistema di allarme con max e min livello c 6 tutte le valvole a funzionamento automatico dovranno essere precedute e seguite da valvole di intercettazione manuali a sfera realizzate interamente in acciaio AISI 316 9 1 7 Sistema di lubrificazione Sistema di lubrificazione a circolazione forzata di olio a mezzo di pompa ad ingranaggi azionata meccanicamente dal motore completo di dispositivi di misura con allarmi di min pressione 9 1 8 Sistema di scarico Sistema di scarico dei gas costituito da un collettore da collegarsi alla tubazione gas di scarico esistente Il collettore dovr essere isolato termicamente in modo che nessun punto della superficie esterna del condotto che non sia COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 13 of 33 debitamente protetto dal contatto accidentale abbia una temperatura superiore a 60 C materia
58. of EE1 INE generating set 11 of 32 Accessories necessary to make the system complete and working In particular for the daily tank c 1 piping with adequate diameter for fuel filling to the 25000 It storage tank on the piping the supplier shall install 2 filter units JRC supply outside the container to separate the water diesel c 2 overflow piping with adequate diameter to the 25000 It storage tank with no valves or gates of any sort c 3 the piping must be connected to the piping below the floor immediately next to it c 4 flow shut off device and device to stop the supply pumps which acts automatically when the level in the daily tank exceeds the maximum allowed or if there is a fire alarm c 5 alarm system with max and min level c 6 all the automatically operated valves shall be preceded and followed by manual ball shut off valves made entirely in steel AISI 316 9 1 7 Lubrication system Lubrication system with forced oil circulation by means of a gear pump driven mechanically by the motor complete with measurement devices with minimum pressure alarms 9 1 8 Discharge system Gas discharge system made up of a collector to be connected to the existing gas exhaust piping The collector shall be thermally insulated so that no point of the external surface of the duct which is not properly protected against accidental contact has a temperature higher than 60 C The insulation and or protection
59. on board to connect power and or auxiliary circuits with the part of the system which is not the subject of the supply b piping connection points for the daily tank overflow and filling with diesel from the external storage tank to the diesel room the supplier is responsible for the connections to the piping from to the external tank which will be placed under the slab on which the unit will be laid c flange and exhaust gas piping to the existing expansion joint As an example but not limiting the activities and or materials included in the scope of the works are summarised below d all the lifting means and or equipment for lifting and installation e foundation bolts and anchoring system for the container f levelling shims if any g adjusting screws if any h centring pieces to be embedded in the foundation if any i all the types of keys used j all the identification plates k warning signs list of materials spare parts and equipment for commissioning m oil and liquids for first filling COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 6 of 32 n materials for the commissioning and starting o commissioning and starting with simulation of the control units of the existing system p equipment for operation of the generating set q electrical interconnecting cables insi
60. osition the commands can come either from the main control room or from the power room To guarantee double safety the circuit breakers can only be operated from the control room after authorisation by means of changeover switch CN 27 The circuit breakers that act in the switching logic are equipped with electrical command and each of them has a local local remote selector switch Locally the circuit breakers can only be closed with the selector switch in Local position while the opening will be always enabled Finally the EE1 unit can only be started manually with changeover switch CN 28 in position EE1 priority so as to inhibit in all cases the starting of the EES unit Changeover switch CN 28 included in the supply shall guarantee the same mode of operation with respect to the existing unit as well Test operation The generating set will be equipped with a local command and control distribution board which will have a Test selector switch that starts the test sequence of the generating set involved Test operation does not inhibit the workings above described in fact if operation of the generating set is required the test is interrupted and the unit supplies the bus bars in an emergency TECHNICAL DESCRIPTION OF THE SUPPLY Composition and features of the new generating set The generating set will essentially be made up of 9 1 1 Base generating set a Single base in steel sections of sufficiently rigid manuf
61. pplier shall once the on site inspection has been carried out identify the conditions and works necessary for correct air exhaust and discharge bearing in mind that the unit supplied should be able to work in test conditions at the same time as the generating set 9 1 4 Preheating system Preheating system with armoured heating elements The system will heat the cooling water in the stopped motor to ensure immediate cold starting even with a room temperature of 10 C The preheating system will be switched on automatically when the motor stops and switched off when it starts 9 1 5 Starting system Electrical starting system complete with 2 24V Pb battery units and recharge rectifier The rectifier shall be dimensioned for the power supply of the EE1 leads and needed for operation of the unit and simultaneous recharging of the batteries If the rectifier is out of service the battery shall ensure the power supply of the leads for at least a week and have sufficient capacity to guarantee 6 consecutive starts each lasting 10 sec 9 1 6 Power supply and fuel loading system Power supply and fuel loading system including a 1 daily diesel tank minimum 1000 It mounted on the machine b 2 electric pumps self priming for automatic filling suction tube placed at 4 m and 1 hand pump mounted on the machine COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement
62. quirement is to be checked on the basis of annex D If there is a loss of voltage the system shall generate for each line with time 0 5 sec an alarm signal on the G S control system and make it available on the terminal board by means of fail safe wired relays The operation logic will be a 1 phase 3 phases alarm b 2 phases 3 phases operation with starting of the generating set 9 4 5 Voltage present and voltage release system The command and control distribution board shall have a voltage present system for a voltage from transformer EC1 b voltage from transformer EC3 c voltage bus bar ET1 ET2 d voltage bus bar ET3 e voltage incoming line at 380V 50Hz Each incoming line shall be fitted as well as with the overvoltage arresters and their protection fuses as section 9 1 12 and section 9 4 4 with a power supply with safety transformer having 24Vdc secondary The system shall signal that there is voltage inside the board 9 4 6 Fire fighting and extinguishing system The fire fighting system control board shall have an extinguishing system with the following logic COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 20 of 32 a operation of 1 2 detectors prealarm that shall supply alarms a 1 to the control panel on the command and control distribution board a 2 to the control room a 3 to the
63. r distribution board Circuit breaker ED13 can always be opened if the generating set fails as in section 9 4 2 COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 17 of 32 b Selector switch in position 0 In this position if circuit breaker ED13 is closed it must be kept closed the circuit breaker can be opened with the opening push button on the front of the power distribution board c Selector switch in Distance position In this position circuit breaker ED13 cannot be controlled by the local push buttons on the front of the power distribution board but must be remotely controllable the commands must be available on the terminal board Circuit breaker ED13 can always be opened if the generating set fails as in section 9 4 2 9 4 2 Opening circuit breaker ED13 in G S failure conditions Circuit breaker ED13 is always open in the following generating set failure conditions and in particular a low lubrication circuit pressure b high motor temperature c high low speed d high low generator voltage lt 65 gt 120 e generator failure f generating set emergency push button pressed g voltage release push button placed outside the building pressed h push button for switching on fire extinguishing in the container pressed i container fire prealarm 9 4 3 Automatic manual Test Stop
64. ra motore x NA 2 NC 31 Guasto caricabatterie x NA 2 NC 32 Combustibiteesauto x X S TIPO DI VISUALIZZAZIONE INTERVENTO DESCRIZIONE DISPLAY LED SIRENA STOP DISPONIBILE PER REMOTO 1 7 2 3 X 34 Sototenioebateia do ox x 2NA2N CB s r L L PROTEZIONGENERATORE gt i p S pum EN o NEN ES NEN NEN S o S o S o S S S S s S S Oooo mm gt 36 Sovratensione Preallame x x 37 Sowaenione Sop x f x s NAN 38 Sottotensione Prealame x x 39 Sottotensione Siop x x s Sovraccarico x J x sn 2NAeNC Corto circuito x s NN 42 Massimafrequenza Stop x x S 43 Minimatrequenza Stop x x 44 Massimapotenzaativa Prealame x x 45 Massimapotenzaativa Stop x x 46 Massimapotenzareattiva Preallame x x 47 Massimapotenza reattiva Stop x x 48 Altatemperatura avvolgimeni x x SR 49 Alta temperatura cuscinetti x x s EE 1 Corto circuito X x x gt x px x x x gt lt Pas COPIA CONFOR
65. rante il funzionamento il Gruppo Elettrogeno dovr essere sorvegliato da eventuali anomalie visualizzate sul Quadro Elettrico come da tabella sotto riportata Tutti gli allarmi presenti devono essere gestiti in fail safe COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 22 of 33 TIPO DI VISUALIZZAZIONE INTERVENTO DESCRIZIONE DISPLAY LED SIRENA STOP DISPONIBILE PER REMOTO 1 7 2 3 SEGNALAZIONI DI STATO _1_ Automatico da selettore i pt NAH NC 2 Manuale da selettore INA INC 1 NA 1 NC Test da selettore Stop da selettore 1 NA 1 NC 2 NA 2 NC 5 Tensione ausiliari presente 2 NA 2 NC 1 NAH NC 2 NA 2 NC NA 2 NC 10 Prerscaldodiinserto OFF 11 PompacaruraneativaON 12 Pompa carburante disattiva OFF Arresto da pulsante 6 3 9 13 14 15 Batteria presente 18 W 20 24 25 26 2 2 NA 2 NC 2 NA 2 NC PROTEZIONI MOTORE 2 NA 2 NC 2 NA 2 NC 2 NA 2 NC 2 NA 2 NC 2 NA 2 NC 2 NA 2 NC 2 NA 2 NC A42 NC A42 NC NA 2 NC NA 2 NC 21 Guastosistemadipreriscaldamento 22 Bassapressione olio Preallarme 23 Bassissima pressione olio Stop Massima temperatura acqua Stop N Alta temperatura olio Preallarme 28 29 Altissima temperatura olio Stop 30 Massima temperatu
66. re ET1 ET2 o ET3 EE1 prioritario da CN 28 In caso di mancanza tensione sulle sbarre ET1 ET2 o ET 3 Quadro 8100 EQ01 rilevata sul Gruppo dopo circa 1 sec previa verifica della disponibilit del Gruppo Elettrogeno EE1 del commutatore CN26 in posizione automatico commutatore CN 28 in posizione EE1 prioritario e dell assenza di guasti sulle ET1 ET2 o ETS si avr l avviamento del Gruppo Elettrogeno EE1 con la sequenza seguente avviamento Gruppo Elettrogeno EE1 apertura interruttori ED11 ed ED31 verifica che gli interruttori ED14 ed ED35 siano aperti verifica che gli interruttori ED13 ed ED12 siano chiusi la condizione di questi interruttori normalmente chiusi chiusura dell interruttore ED35 previa verifica dell avvenuta apertura dell interruttore ED11 ed ED31 e della condizione di regime raggiunto dal Gruppo Elettrogeno EE3 ed infine chiusura dell interruttore ED14 Ritorno alla situazione normale Il ritorno dall aliImentazione di emergenza all alimentazione normale e con il commutatore CN26 in posizione automatico sar eseguito in modo automatico esclusivamente con la concomitanza della presenza tensione sui due arrivi linea BT dei trasformatori rilevate sul Gruppo dopo un ritardo impostabile tra 1 e 30 minuti dal ritorno delle tensioni si avr l attivazione automatica delle commutazioni delle sbarre 1 2 ed dal gruppo elettrogeno ai rispettivi trasformatori ed il Gruppo Elettrogeno sar arres
67. riglie per l ingresso dell aria n 3 condotti per lo scarico dei gas n 3 serbatoi giornalieri di gasolio n 3 pompe alimentazione gasolio n 1 portone di ingresso e n 1 gru da 10000 kg Il condotto esistente per lo scarico dei gas del Gruppo Elettrogeno esistente EE1 e relativa tubazione interna dovr essere riutilizzato per il nuovo Gruppo Elettrogeno EE1 COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 4 of 33 3 2 Esternamente la Sala Diesel dotata di serbatoio del gasolio interrato 25000 It e di reostato per la prova a carico In fase di gara verr organizzato un meeting informativo presso il CCR di Ispra al quale tutti i fornitori saranno invitati a partecipare durante lo stesso sar possibile anche effettuare un sopralluogo per prendere visione della situazione attuale nella Sala Diesel esistente Elenco delle attivit Entro 30 giorni dal ricevimento dell ordine il fornire dovr presentare un programma dettagliato con tempistiche e fasi di lavorazione da concordare con la Committente dovr inoltre fornire indicazioni precise per eventuali opere civili e o modifiche p e sistema di immissione ed emissione aria dal locale da eseguire nella Sala Diesel esistente per adeguarla alle normative vigenti e o all installazione del nuovo Gruppo Elettrogeno Nella fornitura dovrano essere compresi tutti i mezzi e i ma
68. s Diesel started gt 380 g min 1 NO 1 NC Unit speed gt 380 g min 1 NO 1 NC 3 stop stop delay on 3 3 NO 3 NC to recorder Diesel stopped 1 NO 1 NC to recorder 7 Diesel blocked 1 NO 1 NC to recorder Generator overcurrent short circuit 2 NO 2 NC note note to recorder TYPE OF SIGNAL 1 2 Presencelloss of voltage ET3 2NO amp 2NC f 7 Generator frequency measurement 880Vac S Tphases torecorde Curentmeasuemet In series to the ammeter on the board 1 NO 1 NC 3 note 3 3 1 Ea 5 6 s 8 o 10 EUN 12 15 17 18 19 21 NN 23 24 25 26 28 s Trip circuit breaker ED13 thermal device 2NO Trip circuit breaker ED101 NOT 1 Quantity and position of contacts to the terminal board 2 Quantity and position of contacts from the terminal board 3 Quantity and position of contacts made available on the terminal board by means of relays managed in fail safe COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 25 of 32 10 EXCLUSIONS FROM THE SUPPLY The following are excluded from the supply a engineering work needed for installation of the generating set b electrical insulation and disassembly of the existing gener
69. selector switch on the command and control distribution board The Automatic Manual Test Stop selector switch on the command and control distribution board allows the following operating conditions a Selector switch in Automatic position In this position generating set EE1 cannot be controlled by the start and stop push buttons on the front of the command and control distribution board but only by the unit operation control units and with the following signals See section 9 6 1 COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 18 of 32 a 1 start diesel by SCP CN26 in Manual position a 2 stop diesel by SCP CN26 in Manual position a 3 agreement to start diesel CN26 in Automatic position b Selector switch in Manual position In this position the generating set EE1 is started locally for maintenance only with ED13 ED14 ED35 open c Selector switch in Test position In this position generating set EE1 is started automatically after closing of circuit breaker ED101 by pressing the push button with flashing signal on the command and control distribution board circuit breaker ED101 will be closed with a delay which can be adjusted from 0 6 sec and only with generating set ready and after checking that circuit breakers ED13 ED14 ED35 are open The rheostat power will be increased in scalar mode until t
70. sizione Manuale a 2 stop diesel da SCP CN26 in posizione Manuale a 3 consenso allo start diesel CN26 in posizione Automatico b Selettore in posizione Manuale In questa posizione il Gruppo Elettrogeno EE1 viene avviato localmente per manutenzione solo con ED13 ED14 ED35 aperti c Selettore in posizione Test In questa posizione il Gruppo Elettrogeno EE1 viene avviato automaticamente dopo la chiusura tramite pulsante con segnalazione lampeggiante posto sul Quadro Elettrico di Comando e Controllo dell interruttore ED101 la chiusura dell interruttore ED101 avverr con ritardo regolabile 0 6 sec e solo con Gruppo Elettrogeno pronto e previa verifica che gli interruttori ED13 ED14 ED35 siano aperti La potenza del reostato verr incrementata in modo scalare fino al raggiungimento della potenza desiderata L apertura dell interruttore ED101 sar sempre possibile con le seguenti anomalie COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 20 of 33 c 1 bassa pressione circuito di lubrificazione c 2 alta temperatura motore c 3 alta bassa velocit c 4 avaria alternatore c 5 azionamento emergenza Gruppo Elettrogeno c 6 azionamento pulsante sgancio tensione posto all esterno dell Edificio c 7 azionamento pulsante per l inserzione spegnimento incendio nel container e preallarme incendio contai
71. stallation of a new generating set which will replace the EE1 INE Diesel Unit Key words Supersedes document ref Name Signature Date Prepared by MANIACI Federico PP SN 30 0 SA gy 2 rr 30 07 2402 OSS 20 lt 72 YL 30 05 12 OSIMANI Celso Naro zofo Sir QA verified by MACAVERO Egidio n Qe s u 4 2 Approved by C OSIMA E Ors et L HUHTINIEMI CHINDAMO Alessio Verified by COVINI Roberto RTI Action Information 1 Huhtiniemi A Chindamo Internal distribution G Munda E Vaccarezza roval External distribution Candidate Contractors Limited distribution r Copy NO FILING Date 8 06 i2 Signature j COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 1 of 32 Revision Revision Description 00 Initial release 01 02 03 04 05 06 07 COPIA CONFORME ARCHIVIO NDU 2012 06 12 22 Rev 0 Replacement of EE1 INE generating set 2 of 32 1 SCOPE DIU iaia 3 2 COMPONENTS OF THE SUPRLY iii 3 3 DISASSEMBLY SUPPLY AND ASSEMNBLY J u u 3 3 1 General comrents c ce isi upsay nia 3 3 2 List Of the actiVIlles ient secre rra ini 4 4 BATTERY LIMITS
72. tato su segnale proveniente da logiche esterne dopo circa 3 minuti dal ripristino della configurazione normale Con il commutatore CN26 in posizione di Manuale il ritorno alla configurazione normale sar fatto manualmente dall operatore COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 10 of 33 8 3 8 4 9 9 1 Funzionamento manuale In funzionamento manuale cio con CN26 in posizione Manuale i comandi potranno avvenire indifferentemente dalla Sala Controllo principale o dalla Sala Energia Per garantire una doppia sicurezza la manovra degli interruttori dalla Sala Controllo sar possibile solo previa autorizzazione tramite il commutatore CN 27 Gli interruttori che intervengono nella logica di commutazione sono equipaggiati con comando elettrico ed previsto localmente per ognuno un selettore locale remoto Localmente la chiusura sar possibile solo con selettore in posizione Locale mentre l apertura sar sempre abilitata L avviamento manuale del gruppo EE1 potr infine avvenire solo con commutatore CN 28 in posizione EE1 prioritario in modo da inibire comunque l avviamento del gruppo EES Il commutatore CN 28 compreso nella fornitura dovr garantire le stesse modalit di funzionamento anche rispetto al gruppo EE3 esistente Funzionamento in prova Il Gruppo Elettrogeno sar equipaggiato con
73. teriali necessari per effettuare smontaggi progettazione forniture e montaggi a perfetta regola d arte Con riferimento ai documenti in allegato paragrafo 6 le principali attivit da eseguirsi sono le seguenti a progettazione completa di dimensionamento incluso tubazioni gasolio e condotta aria di espulsione e sistemazione nel pieno rispetto delle normative e leggi vigenti b fornitura informazioni per eventuali opere civili nuove e o di modifica necessarie per il montaggio del nuovo Gruppo Elettrogeno c disegni dimensionali e o calcoli per la verifica statica e dinamica della struttura di supporto del container da posare sul basamento d sviluppo del layout Sala Diesel e disegni di dettaglio di sistemazione impiantistica e di montaggio del nuovo gruppo con verifica delle distanze di rispetto per la manutenzione f redazione del POS Piano operativo della sicurezza dopo avere ricevuto dalla committente il PSC Piano di sicurezza e coordinamento Il POS sar sottoposto per approvazione al coordinatore della sicurezza in fase di esecuzione come previsto dal D Lgs 81 08 g fornitura trasporto e posa in opera del container di insonorizzazione completo di Gruppo Elettrogeno Quadro Elettrico e di tutti i sistemi necessari al completo funzionamento h introduzione del nuovo Gruppo Elettrogeno EE 1 dal portone di ingresso esistente i montaggio del nuovo Gruppo Elettrogeno EE 1 COPIA CONFORME AR
74. tes FREQUENZA Frequency CORRENTE DI CORTO CIRC short circuit current 1s Hz VAL EFF SIMM kA symmetrical rms value VALORE DI CRESTA kA peak value STATO DEL NEUTRO neutral condition TENSIONE DISPONIB V PER I COMANDI available control circuit V voltage GRADO DI PROTEZIONE degree of protection ARRIVO CAVI incoming cables USCITA CAVI outgoing cables ACCESS RETRO back access DIMENSIONI DI INGOMBRO overall dimensions TIPO type TIPO type TIPO type TIPO type CHIAVE key B BASSO SI H yes ESTERNO on external housing INTERNO inside the switchbrd DALL ALTO from top DALL ALTO from top NO IP41 IP 20 from bottom DAL BASSO from bottom LUNGH TOT board total lenght ALTEZZA height PROFONDITA 800 depth TENS NOMINALE nominal voltage TENS NOMINALE nominal voltage TENS NOMINALE nominal voltage UCE INTERNA internal light COPIA CONFORME ARCHIVIO NDU 2012 06 12 JOINT RESEARCH CENTRE ISPRA SITE MANAGEMENT European NUCLEAR DECOMMISSIONING UNIT Commission WBS Project title Safely conserving INE Project sub project code WBS ref 1 08 01 01 NE 45 0860 A 009 D b ocument number ND 45 0801015 A 001 Rev 0 Page 0 of 32 Document type Technical specification Title Replacement of generating set EE1 INE Abstract The document contains the technical details for the purchase and in
75. tificazione Dovranno essere forniti i certificati relativi ai materiali ed alle prove e collaudi prescritti concordati certificati relativi alle prove di tipo prescritte dalle Norme saranno trasmessi alla Committente entro un mese dall ordine certificati delle prove di tipo potranno essere relative anche ad apparecchiature simili a quelle oggetto della fornitura a patto che il costruttore possa fornire l evidenza che le prove effettuate siano estendibili alle apparecchiature in oggetto COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 30 of 33 GRUPPO ELETTROGENO Generating Set CERTIFICATI DI PROVA DEL FORNITORE ODICHIARAZIONE DI CONFORMITA AGLI STANDARDS APPLICABILI Manufacturer s routine test certificate or Declaration of Conformity to the applicable standards ELENCO PROVE PER I QUADRI ELETTRICI L V Distribution Boards test list NORMA APPLICABILE IEC 439 1 Applicable standard DESCRIZIONE DELLA PROVA PROVE DI TIPO PROVE DI ROUTINE test description Type test Routine test ISPEZIONE DELL ASSEMBLAGGIO Assembly inspection VERIFICA DELLE TARGHE Name plates verification ISPEZIONE DEI CABLAGGI Wiring inspection INTEGRITA DEI COMPONENTI Integrity of the components MESSA A TERRA Earthing PROVA DI ISOLAMENTO Insulation test PROVA DI TENSIONE A FREQUENZA INDUSTR Power frequency withstand voltage test REQUISITI
76. tive generali ii 18 9 4 Principio di 18 9 5 Segnalazioni e allarmi eene nennen nnne 21 9 6 Ten Gi INS cR 24 10 ESCLUSIONI DALLA FORNITURA 1 11 uu u uu u 26 11 2 0220 reete terns re ria 27 12 FABBRICAZIONE PROVE E nennen nnne nnn 29 12 1 Prove SUI componenti tee cire ce eite rit ioca ctp erede ai 29 12 2 Prove d accettazione uken i a aiaia aaaea aan aaah 29 Tes eerte iaia 29 13 TRASPORTO m 30 14 _ DATA nias onn deca ecd rn decr eden re Don d no re OCIO DO dona De 30 COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 3 of 33 3 1 SCOPO Scopo del presente documento quello di definire le prescrizioni generali per le attivit di progettazione fornitura montaggio messa in servizio e manutenzione nel periodo di garanzia di nuovo Gruppo Elettrogeno in sostituzione del Gruppo Elettrogeno EE1 ubicato nell edificio 85 sito nel CCR di Ispra VA CONSISTENZA DELLA FORNITURA La fornitura consiste in a item EE1 Gruppo Elettrogeno trifase per sistema IT min 1350kVA max 1400KVA 400V 50Hz cosg 0 8 in container insonorizzante completo di Quadro Elettrico e
77. trogeno esistente c tubazione di espulsione gas di scarico all esterno della Sala Diesel e relativo condotto esterno d scollegamento e recupero di componenti elettrici esistenti cavi quadri gruppi elettrogeni ecc e smaltimento del Gruppo Elettrogeno esistente COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 nct ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 27 of 33 11 DOCUMENTAZIONE Il Fornitore dovr eseguire la progettazione funzionale e costruttiva di quanto in oggetto e dovr fornirne i relativi disegni come di seguito indicato Modalit di consegna con dopo ordine 3 offerta Descrizione della documentazione 1 n n n 2 n n gg da ow po collaudo REFERENZE Reference list PROGRAMMA DI FORNITURA Supply plan ELENCO DOCUMENTI List of document Em List of input output ELENCO COMPONENTI E SUBFORNITORI List of equipment and supplier see HH STRUTTURA DI BASE DEL CONTAINER DISEGNI DI ASSIEME CON CARICHI PER TRASPORTO E INSTALLAZIONE Sh 3N G 20 2 Dimensional drwgs with static and dynamic loads for trasp amp install FOGLI DATI Data sheets SCHEMI ELETTRICI UNIFILARI E FUNZIONALI Single line and schematic diagrams DISEGNI MORSETTIERE Terminal block drwgs PLANIMETRIA DISPOSIZIONE COMPONENTI Assembly components layout INFORMAZIONI OPERE CIVILI Information on civil works SPECIFICA TECNICA VERNICIAT
78. uccessive varianti ed integrazioni Inoltre I DPR n 547 del 27 04 1955 e successive integrazioni m DPR n 459 del 24 07 1996 sulla direttiva macchine n Circ n 73 del 1971 sui depositi di combustibili Rif Circ n 31 o Circ n 31 del 31 08 1978 Norme di sicurezza per l installazione dei Gruppi Elettrogeni p Circ n 12 del 08 07 2003 Modifiche ed integrazioni alla Circ n 31 del 31 08 78 q D 195 626 94 Sicurezza nei Luoghi di Lavoro D 105 494 96 Piano operativo di Sicurezza POS s D 195 81 08 e successive integrazioni Il fornitore comunque tenuto ad applicare tutte le normative e le leggi vigenti nel paese di destinazione della fornitura e le direttive CEE applicabili con il dovere di comunicare e di prendere provvedimenti in merito laddove le stesse siano superate o rese obsolete da altrettante pi restrittive Tutte le apparecchiature devono riportare la marcatura CE DOCUMENTI DI RIFERIMENTO Fanno parte integrante della presente specifica i documenti a Allegato A Sala Diesel Planimetria e Sezioni Sala Diesel b Allegato B dis NE 68 0820 A 020 Schema unifilare generale sala energia c Allegato C doc NE 80 1010 A 009 Gestione della documentazione d Allegato D Relazione sulla Valutazione del Rischio da Fulmini COPIA CONFORME ARCHIVIO NDU 2012 06 12 Le condizioni ambientali assunte per l impostazione del progetto sono a Altitudine sul
79. w rate RADIALI TIPO DI SPINTA TIPO radial type thrust type LUB LUB lube lube RAPP DI COMPR PESO compression rate wieght PESO POTENZA LUNGHEZZA mm weight to power rate lenght RENDIMENTO ALTEZZA mm efficiency height TIPO SERVIZIO LARGHEZZA mm type of service width N RICH AVV MES PD MOT GIUNTO startup n req in a month motor joint PD TIPO MATERIALE DIAMETRO type material diameter CAPACITA m ALTEZZA capacity height TIPO ALIMENTAZIONE type feeding POTENZA kW CLASSE ISOLAM power isolating class rpm excluded included TIPO PORTATA I sec TEMPERATURA C PRESSIONE bar temperature pressure TIPO CAPAC CARTER 1 type carter capacity VISCOSITA cSt PORTATA l s viscosity flow rate INTER RICAMBI changes time i eee NOTE DI INIEZIONE DIRETTA direct injection CAMERA PRECOMBUSTIONE advance combustion chamber TC CAMERA TURBOLENZA turbolence chamber SE EFFETTO SINGOLO single effect DE DOPPIO EFFETTO double effect COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Sostituzione gruppo elettrogeno EE1 INE 32 of 33 DATI GENERALI general data DATI NOMINALI rating CARATTERISTICHE characteristic PESI weights ACCESSORI accessories FOGLIO DATI ALTERNATORI Alternator data sheets QUANTITA quantity COSTRUTTORE manufacturer NORME DI RIFERIMENTO reference standard DISEGNI
80. water water exchanger and with electric motor starting and water cooling with water air exchanger With reference to the documents in annex section 6 Each generating set is connected electrically to its own bus bar system ET1 ET2 and to a test rheostat common to all the generating sets The existing 1500 kVA EE1 generating set shall be replaced by a new EE1 generating set which starts with an electric motor and has water cooling with water air radiator see section 8 1 At present the Diesel Room is fitted with among other things 3 grids for the air entry 3 ducts for the discharge of gas 3 daily diesel tanks 3 diesel supply pumps 1 entry door and 1 10000 kg crane The existing duct for the discharge of the gas of the existing EE1 generating set and its internal piping shall be reused for the new EE1 generating set COPIA CONFORME ARCHIVIO NDU 2012 06 12 NE 45 0860 A 009 ND 45 0801015 A 001 Rev 0 Replacement of EE1 INE generating set 4 of 32 3 2 Externally the Diesel Room is fitted with a buried diesel tank 25000 It and a rheostat for the load test In the tender phase an information meeting will be organised at the JRC Ispra to which all the suppliers will be invited during the meeting it will also be possible to make an on site inspection to see the current situation in the existing diesel room List of the activities Within 30 days of receiving the order the supplier

Download Pdf Manuals

image

Related Search

Related Contents

1. Wat is Linisol 2 %, oplossing voor injectie en waarvoor  GE 840099900 User's Manual  intext:Betriebsanleitung filetype:pdf  Marcum Technologies VX-1P User's Manual  Toshiba Satellite P75-A7200  Le carnet de suivi des véhicules utilitaires légers (VUL)  HP 6lIOA User's Manual  user manual Washing Machine  Metra Electronics 95-7326 User's Manual  NX10F 取扱説明書  