Manuale d`uso User manual
Contents
1. 5562 oOOo r 5 Ceo 23 DP1 EELJON 0 5to1V DP2 ELE OFF R mi DP1 ELEJOFF 910 1 y 1 kohm Jumpersfor configu ring the outputs DP2 ELE OFF on models with two active outputs both K are configured in the same way DP1 ELEIOFF 4 to 20 mA Li DP2 FELJON 0 kohm DPWxxx2xxx Out both DPWxxx5xxx Out NTC Res temperature DPDxxx2xxx 0 10V DPDxxx5xxx 0 10 V humidity DPPxxx2xxx DPPxxx5xxx DI E dic PA E on O 0 10V o De 0 10V DP1 DP2 m SBE 55 6 9 o 2 2 00 3 DPI GEE ON i Y DP2 CEL ON Oto 10V ro E 0 10 V version default configuration Fig 4 a Key out T temperature output 0 5 to 1 Vdc or Oto 1 Vdc or 4 to 20 mA for models DPxxx0 or 1 out T temperature output Oto 10 Vdc for models DPxooo2 or 5 outH humidity output 0 5to 1 Vdc or Oto 1 Vdc or 4 to 20 mA for models DPxxx0 or 1 outH humidity output O to 10 Vdc for models DPxxxx2 or 5 out NTC outputwith NTC resistive sensor 10K at 25 C Carel standard M GO reference for both power supply and outputs G power supply 12 to 24 Vac or 8 to 32 Vdc Note with output configured for 0 to
2. G NTC OUT NTC OUT M G out H CAREL ITA Cablaggio della sonda allo strumento Vdc Bn Bm GND PA a Fig 4 b Vdc SI Bn SI Bm SI GND GS1 TRA12 TRA24 230 Vac A 12 24 Vac Trasformatore Transformer Fig 4 c Cablaggio della sonda con uscita in tensione o corrente Connessione sonda con uscite in tensione o corrente e con alimentazione diretta dal controllo Da valutare la capacit corrente massima di alimentazione del controllo Per distanze gt 10 metri da preferire la connessione in corrente 4 20 mA per evitare errori di misura dovuti alla caduta sul riferimento M G0 Connessione sonda con alimentazione separata mediante trasformatore da utilizzare per evitare errori di misura dovuti alla corrente sulla connessione M GO di riferimento oppure per problemi di alimentazione su GO con connessione a terra vdc Sl Bn SI Bm Sl GND SI Weare EEE Fig 4 d Cablaggio della sonda allo strumento con uscita NTC resistiva Connessione sonda con uscita NTC resistiva importante che i due segnali vengano connessi direttamente ai morsetti dello strument
3. G power supply The shield must be connected to 7 IRDR IRDR Sensor 2 ntc sensor NTC output res 3 ntc sensor NTC output res The shield must be connected to 2 IRDR Sensor 3 out T active temperature or humidity output 1 M reference 2 G power supply u The shield must be connected to Cod 030220660 DP Sensors Rel 2 1 10 09 10 17 CAREL Example of connection with two IR i nstruments that must be powered separately from the power supply line by two different transformers M GO Sensor a Fig 4 FCM FCM Ist sensor 7 out T H 4 to 20 mA active temperature or humidity output 8 M reference 6 G power supply The shield must be connected to 8 FCM Ist sensor 10 out T H 4 to 20 mA active temperature or humidity output 11 M reference 9 G power supply FCM 2nd Sensor 10 out T H 4 to 20 mA active temperature or humidity output 11 M reference 9 G power supply The shield must be connected to 11 Note with one sensor the R200 Q res SD humidifiers istor does not need to be connected if terminals 7 B1 and 10 B2 are jumpered SD Sensor 57 out H active humidity output 58 59 M reference 56 G power supply The shield must be connected to 58 5 9 heaterSteam humiFog and humiSteam humidifiers Humicontrol Sens
4. aggiornato per problemi di comunicazione 12C Bit8 Il parametro RUG non corretto per problemi di fuori range di UMI e TMP Bit9 Il parametro RUG non aggiornato per problemi di comunicazione 12C Cod 030220660 Sonde DP rel 2 1 10 09 10 17 CAREL ITA 4 10 Avvertenze generali e Per mantenere il grado di protezione dichiarato nelle versioni con contenitore IP55 il cablaggio deve essere realizzato con cavetti multipolari con guaina esterna avente un diametro massimo di 8 mm e Si consiglia di usare cavi schermati cavi che portano i segnali di temperatura e umidit non devono essere alloggiati vicino al cavi dell alimentazione a 115 230 o 400 480 Vac o vicino a cavi di teleruttori che portano potenza ai carichi Si devono evitare errori di misura causati da accoppiamenti elettromagnetici e L alimentazione e i segnali elettrici della sonda sono in bassissima tensione tuttavia per il collegamento con i controlli tenere in considerazione che l isolamento elettrico previsto supplementare escluso il cappuccio protezione sensore La protezione metallica dei sensori collegata al riferimento di alimentazione della sonda Per conformit alle normative di sicurezza si deve prevedere un doppio isolamento per l alimentazione della sonda e del controllo cui si collega se la zona sensore accessibile all utilizzatore nell installazione Le sonde sono integrabili in apparecchiature di Classe o Il con le seguenti a
5. as 17 4 10 Avvertenze generali 4 11 AAA a eA aA 19 4 12 Tabella compatibilit chimica per i sensori di UMMICItA sssssssssssssssssessssssssseesssscssssssusssssssssssessssssessssusssssssnnsessseccesssisussssssssssseesesccncessussssssansseeeeeeses 21 4 13 Montaggio e fissaggio dello strumento 4 14 Cambio della configurazione di default per sonda ambiente e condbtta uunnnnnnnnnneeeeennnn 23 4 15 Versione consola SEI IN ICs Pes ee e PO PO COI OOO 24 4 16 Valori di resistenza delle sonde di temperatura NTC CAREL cc cin 25 CARATTERISTICHE TECNICHE rele 26 Dil PUIIZIA MANUTENZIONE EA EA RO RO RR 28 52 Smaltimento dellg trameto i O RI oo 28 Avvertenze per la sostituzione delle serie Aci rn 28 DIMENSIONI meccaniche Ti IMOdelloDPW Lee RARI OA RIGO 125 ModelloDPDi r OOO III 7 35 Modello DPPkc o o o RR R RNEER CAREL ITA Le sonde della serie DP temperatura e umidit rappresentano l ultima versione dei sensori CAREL per i modelli ambiente ambiente tecnico e condotta realizzate per il mercato HVAC R residenziale e industriale leggero con la qualit che contraddistingue i prodotti CAREL La gamma include i modelli con uscita 0 10V e con uscita seriale RS485 Carel o Modbus Le sonde della serie DP utilizzano sensori con uscita digitale e presentano un range di temperatura e umidit pi esteso in temperatura rispetto ai precedenti modelli offrendo tutta la versatilit richiesta dalle applicazioni del mercato specifi
6. sensor sensor Turbocor compressor Fig 4 h 4 5 Example of connection to the RS485 supervisor network touch screen graphic display PlantVisorPRO MS BD PlantWatchPRO up to 32 sensor Cod 030220660 DP Sensors Rel 2 1 10 09 10 12 CAREL LENG 4 6 Power supply connection For alternating current power supply 12 to 24 Vac just one transformer can be used connected to G GO on all the sensors with GO to earth paying special care to observe the polarity by connecting together the terminals with the same name or alternatively using an isolating transformer for each individual sensor For the serial sensors the type of power supply depends on the model of sensor used sensors with optical isolation can be powered with one power supply G G0 for all the sensors as well as for the controller In this case make sure that the cable shield on the controller side is connected to EARTH directly or via the GO Earth connection on the controller Sensors that are NOT isolated for short distances these can be powered with one power supply for distances over 10 m an isolating transformer may be required for each sensor 47 Wiring For wiring a shielded multicore cable with 3 to 5 wires depending on the model The maximum cross section of the wires allowable for the terminals is 1 5 mm In versions DPP and DPD the maximum inside diameter of the cable gland is 8 mm Serial version with R
7. D 1200 LI DPWxx3 AN pa e DPWsox4 4 ND i VDC Supply max 100 mA ProbeT G M GO GND Y L Nazi BMS sl A 32 3 ms Field Bus Protocollo ModBus sensore fem u sensore sensore compressore Turbocor Fig 4 h 45 Esempio di collegamento alla rete RS485 di supervisione PlantVisorPRO MS y PlantWatchPRO upto 32 sensor Cod 030220660 Sonde DP rel 2 1 10 09 10 14 CAREL ITA 46 Collegamento alimentazione Per l alimentazione in tensione alternata 12 24 Vac si pu prevedere un unico trasformatore connesso a G G0 di tutte le sonde con GO a terra prestando la massima attenzione nel rispettare la polarit collegando insieme i morsetti dello stesso nome oppure prevedere un trasformatore di isolamento per ogni singola sonda Per le sonde seriali il tipo di alimentazione dipende dal modello di sonda utilizzato sonde con optoisolamento possono essere alimentate con una singola alimentazione G GO per tutte le sonde ed anche per il controllo In questo caso importante verificare che lo schermo del cavo sul lato controllo sia collegato a TERRA direttamente o tramite la connessione GO Terra del controllo Sonde NON isolate per brevi distanze possono essere alimentate con singola alimentazione per distanze maggiori di 10 m pu essere necessario di un trasformatore di isolamento per ogni sonda 4 7 Cablaggio Per effettuare il cablaggio si consiglia un cavo multipolare sch
8. Depending on the installation the shield of the analogue signal connection cables may need to be earthed Cod 030220660 DP Sensors Rel 2 1 10 09 10 16 CAREL LENG 4 11 Examples of applications Applications All the sensors can be connected to CAREL controllers for measuring the temperature and humidity values below are examples of some connections to CAREL controllers Examples of connections pco pCO Sensor Bn 1 4 ntc sensor NTC output res Bn 5 8 out T active temperature output Bm 5 8 out H active humidity output AVSS M reference 24 Vdc G power supply The shield must be connected to AVSS pCO pCO Sensor Bn 1 10 ntc sensor NTC output res Bn 1 3 out T active temperature output 6 8 Bn 1 3 out H active humidity output 6 8 GND M reference Vdc G power supply The shield must be connected to GND pco pCO Sensor Bn 1 8 ntc sensor NTC output res Bn 1 4 out T active temperature output Bn 1 4 out H active humidity output GND M reference Vdc G power supply The shield must be connected to GND IR universal IR32 Sensor 7 ntc sensor NTC output res 8 ntc sensor NTC output res IR32 Sensor 9 out T active temperature or humidity output 7 M reference 8
9. 0 1V 0 1V 0 10V 0 10V 4 20mA 4 20mA Sonde con uscita 0 5 1V 30 70 C 0 100 rH 0 3 0 7V 0 0 1V Limiti da impostare nei controlli per inizio e fine range Sono indipendenti dal range effettivo di misura Esempio Per codice DPWC110000 10 60 C e 10 90 r H Per uscite 0 1V 0 10V 4 20mA impostare 0 1V OV a 30 C e 0 r H i 1V a 70 C e 100 r H 0 10V OV a 30 C e 0 r H DE 10V a 70 C e 100 r H 4 20mA 4mA a 30 C e e 0 r H 20mA a 70 C e 100 r H Per uscita 0 5 1V generalmente non amp necessario impostare limiti 0 3V a 30 C au 0 7V a 70 C OV a 0 r H a 1V a 100 rH Cod 030220660 Sonde DP rel 2 1 10 09 10 16 CAREL ITA 49 Tabella Variabili Parametri principali per sonde seriali Le sonde seriali hanno la caratteristica di comunicare i dati via seriale RS485 configurabili da dip switch possibile accedere ai parametri via linea seriale utilizzando i protocolli Supervisore Carel o Modbus Il codice macchina della scheda 59 parametro MAC In seguito la tabella e variabili di stato Nome Descrizione Read Tipo U M N D Min Max Def Indice Indirizzo Write A I D SPV Modbus OFT Offset di temperatura R W A Cx 10 EEPROM 100 100 0 1 0 OFH Offset d umidit R W A x 10 EEPROM 100 100 10 2 1 DLT Differenziale per l aggiornamento della temperatura R W A Cx10 EEPROM
10. 90 rH ASDC111000 DPDC110000 Temperature 10160 C and humidity 10 to 90 rH ASDC110000 ASDH100000 humidity only DPDC210000 Temperature 20T70 C and humidity 0 to 100 rH ASDC230000 ASDH20000 humidity only DP series DPDC112000 DPDC212000 Description of DP range Active duct sensors power supply 18 to 32 Vdc 12 to 24 Vac 0 to 10 Vdc output AS series Temperature 10160 C and humidity 10 to 90 rH Temperature 20T70 C and humidity 0 to 100 rH DP series Description of DP range Active duct sensors power supply 8 to 32 Vdc 12 to 24 Vac optically isolated RS485 serial output DPDT014000 DPDC114000 DPDC214000 DP series optically isolated Temperature 20T70 C Temperature 10T60 C and humidity 10 to 90 rH DPDT013000 DPDC113000 Neutral or customised versions available upon specific request Cod 030220660 DP Sensors Rel 2 1 10 09 10 8 CAREL LENG 4 1 Connections for sensors with analogue output Below are the wiring diagrams showing the connections to the terminal block and the position of the jumpers for configuring the universal voltage or current output default DPWxxx0xxx Out both DPWxxx1xxx Out NTC Res temperature DPDxxx0xxx 0 1 V o 4 20 m A 0 5 1 Vdc DPDxxx1xxx 0 1 V o 4 20 m A 0 5 1 Vdc humidity DPPxxx0xxx DPPXxx1xxx
11. O 20 5 3 2 DLH Differenziale per l aggiornamento dell umidit R W A x 10 EEPROM O 20 5 4 3 RSV Reserved NON utilizzata R A 0 Jo 16 4 TMP Valore di temperatura letto dalla sonda R A Cx 10 RAM 500 1000 6 5 UMI Valore d umidit letto dalla sonda R A x 10 RAM 0 1000 7 6 RUG Valore del punto di rugiada R A Cx 10 RAM 500 2000 8 7 DIP Riporta lo stato del dipswitch R RAM 0 255 16 133 ERR Riporta lo stato degli errori per la sonda TH e della R RAM O 4095 7 134 temperatura di rugiada EEP Comando ripristino valori di default 1 default torna R W D RAM 0 1 16 5 a 0 automaticamente ERT Errore lettura sonda Temperatura R D RAM 0 1 17 6 ERH Errore lettura sonda Umidit R D RAM o Jl 18 7 ETR Errore lettura calcolo Temperatura di rugiada R D RAM o 1 9 8 Note A indica variabili analogiche il valore trasferito in decimi x10 D indica variabili digitali indica variabili intere Variabili di uscita TMP valore analogico della temperatura letta dal sensore UMI valore analogico dell umidit relativa letta dal sensore RUG valore di temperatura di dew point press atm std viene calcolato in base alle due misure di temperature ed umidit Range da 20 a 70 C con umidit da 5 a 95 rh DIP riporta lo stato dei dip switch Parametri di configurazione memorizzati in Flash Eeprom
12. configuring the RS485 serial SENSora R N 4 4 Example of connection to the RS485 Fieldbus network 4 5 Example of connection to the RS485 supervisor NEW Kin res 2 6 e ROWE Ie SLID IVs CONDECION o IO EEEE IT MIE iene 4 8 Functional notes and differences between DP and AS sensors with analogue output 4 9 Table of main variables parameters for serial SENSOFS ninna 4 10 General Waigo ee ee ee 4 11 lA nn II III 4 12 Chimical compatibility table for humidity sensor 4 13 ao APP a 4 14 Changing the default configuration for the wall sensor and duct sensor 4 15 Version with NTC output only 4 16 Resistance values of the CAREL NTC temperature SENSOrS iii Technical Spectator euere ns 5 1 Cleaning and maintenance 5 2 Disposal of the instrument 6 Warnings for the replacement of the AS series 7 Mechanical dimensions 71 Model DPW 72 Model DPD E LTT DI CAREL LENG The DP series temperature and humidity sensors represent the latest version of the CAREL sensors for rooms industrial environments and ducts developed for the residential and light industrial HVAC R market with the quality that CAREL stand out for The range includes models with 0 to 10 V output and with RS485 serial output Carel or Modbus The DP series sensors use sensors with a digital output and feature a wider temperature and humidity range than the previous models ensuring all
13. danni diretti indiretti incidentali patrimoniali di copertura punitivi speciali o consequenziali in qualunque modo causati siano essi contrattuali extra contrattuali o dovuti a negligenza o altra responsabilit derivanti dall installazione utilizzo o impossibilit di utilizzo del prodotto anche se CAREL o le sue filiali affiliate siano state avvisate della possibilit di danni SMALTIMENTO Smaltimento del prodotto L apparecchiatura o il prodotto deve essere oggetto di raccolta separata in conformit alle vigenti normative locali in materia di smaltimento Indice 1 2 3 4 ga No PP O ROOITIITIOA 7 E a o O A 7 PP o 8 Codici e compatibilit con la serie AS A O NN 11 4 1 Collegamento delle sonde con uscita analogica ssssssssssssssssessssssssssssssssesssssusssssssssssssssesessesssssssssssssssssssceesessssusssssnsssssseccceecssassssssssesssseseesecsscussssssees 1 42 Collegamenti per sonde con uscita aia 13 4 3 _ Esempio di contigurazione sondaisetiale RS485 a 13 44 Esempio di collegamento alla rete RS485 Field DUS un ncnnci ri 14 4 5 Esempio di collegamento alla rete RS485 di SUPERVISA a 14 4 6 Collegamento alimentazioness RIA PP E A 15 A e a E A EA A EE EE EEE E 15 4 8 Note funzionali e differenze tra sonde DP e AS con uscita analogica uuneeeee 16 4 9 Tabella Variabili Parametri principali per sonde Serial
14. described in the documentation relating to the product In addition to observing any further wamings descnbed in this manual the following warnings must be heeded for all CAREL products e Prevent the electronic circuits from getting wet Rain humidity and all types of liquids or condensate contain corrosive minerals that may damage the electronic circuits In any case the product should be used or stored in environments that comply with the temperature and humidity limits specified in the manual e Do not install the device in particularly hot environments Too high temperatures may reduce the life of electronic devices damage them and deform or melt the plastic parts In any case the product should be used or stored in environments that comply with the temperature and humidity limits specified in the manual e Do not attempt to open the device in any way other than described in the manual e Do not drop hit or shake the device as the internal circuits and mechanisms may be irreparably damaged e Do not use corrosive chemicals solvents or aggressive detergents to clean the device e Do not use the product for applications other than those specified in the technical manual All of the above suggestions likewise apply to the controllers serial boards programming keys or any other accessory in the CAREL product portfolio CAREL adopts a policy of continual development Consequently CAREL reserves the right to make changes and improv
15. screws supplied with the fastening kit paying attention to use the proper spacers to not damage the sensor s electronics e Close the sensor with the top cover by pressing lightly Note Pay attention not to remove the sensors board from the relevant housing and avoid taking away the connector that connects it to the basic board Industrial environment version The industrial environment version is wall or panel mounted fastening holes EG 216 Fig 4 n Assembly notes 1 Open the case by turning the top cover anticlockwise 2 Fasten the rear of the sensor case to the panel or the wall use the screws supplied together with the sensor placing the screws in the holes provided Fig 4 n1 Fig 4 n2 Cod 030220660 DP Sensors Rel 2 1 10 09 10 20 CAREL 3 Make sure that the screws that hold the board protective cover are 4 Close the sensor by turning the cover clockwise fastened tightly Fig 4 n3 Fig 4 n4 For the electrical connections remove the top cover of the sensor For the configuration see the instructions shown below Duct version The duct version is connected to the air duct using the special fastening bracket n 3 holes Y 2 74da non filettee 120 120 gl je J N m 4 7 61 x 3 HSA Fig 4 0 Assembly notes e Fasten the bracket to the air duct e Insert the rod on the bracket to the required depth e Tighten the screw on the bracket to
16. signals must be connected directly to the terminals on the instrument Do not use M GO as the common for the connection of NTC resistive sensor Connection wiring diagram Wde _ G Bn OUTNTC OUT NTC Bm M G0 GND oe x Out H Controller terminals Sensor terminals Cod 030220660 DP Sensors Rel 2 1 10 09 10 10 CAREL LENG 42 Connections for sensors with RS485 serial output Below are the wiring diagrams showing the connections to the terminal block and the settings of the dipswitches for configuring the RS485 serial communication mode with Carel or ModBus protocol E BD Dipswitch settings valid for all models DPDxxx4xxx DPPxxx4xxx E Dip switch 1 to 5 Baud rate z 12305 _ 9600 IL Address 128 159 En 0 lll el ll SES CC 1a de ze e RS485 protocol Bit Parity Stop ON i OFF tu CAREL supervisor 8 N 2 DL1 DL2 ON OFF Hh ModBus 8 N 2 2 2 DE CAREL supervisor 8 N 2 ModBus 8 E 1 cEzE2 SA moss 8 E1 OS Automatic recognition of protocoll Fig 4 e DPWxxx3xxx Non Optoisolato Not insulated Key TxRx RS485 serial output positive XXX3XXX TxRx RS485 serial output negative GND reference for RS485 serial connection LD1 Led green RX function LD2 Led yellow TX function O ON de 12345678 M GO pow
17. togliere la scheda sensori dall apposito alloggiamento evitando di sfilare il connettore che lo collega alla scheda base Versione ambiente tecnico La versione ambiente tecnico prevede il fissaggio su parete o pannello fori di fissaggio 216 Fig 4 n Note di montaggio 1 Aprire il contenitore ruotando in senso antiorario il coperchio 2 Fissare il retro contenitore del sensore al pannello o alla parete superiore utilizzare le viti fornite insieme al sensore posizionando le viti nell apposito alloggiamento Fig 4 n1 Fig 4 n2 Cod 030220660 Sonde DP rel 2 1 10 09 10 22 CAREL ITA 3 Assicurarsi che le viti che bloccano la protezione della scheda siano 4 Chiudere il sensore con il coperchio ruotando in senso orario il ben fissate coperchio Fig 4 n3 Fig 4 n4 Per le connessioni elettriche necessario togliere il coperchio superiore della sonda Per la sua configurazione vedi istruzioni in seguito riportate Versione condotta La versione per condotta collegata alla conduttura dell aria tramite la staffa di fissaggio predisposta 98 n 3 holes Y 2 7Xda non filettae Fig 4 0 Note di montaggio e Fissare la staffa alla condotta dell aria e Infilarelostelo sulla staffa alla profondit desiderata e Awitare la vite presente sulla staffa per il suo fissaggio Per le connessioni elettriche necessario togliere il coperchio superiore della sonda Per la sua configur
18. u Fig 4 1 FCM FCM 18 Sonda 7 out T H 4 20 mA uscita attiva di temperatura o umidit 8 M riferimento 6 G alimentazione La calza va collegata al 8 FCM 1 Sonda 10 out T H 4 20 mA uscita attiva di temperatura o umidit 11 M riferimento 9 G alimentazione FCM 2 Sonda 10 out T H 4 20 mA uscita attiva di temperatura o umidit 11 M riferimento 9 G alimentazione La calza va collegata all 11 Nota con una sonda si pu omettere il collegamento della resistenza R200 Q previo ponticello tra i morsetti 7 B1 e 10 B2 Umidificatori SD SD humidifiers SD Sonda 57 out H uscita attiva di umidit 58 59 M riferimento 56 G alimentazione La calza va collegata all 58 59 Umidificatori heaterSteam humiFog e humiSteam Humicontrol Sonda 5 out H uscita attiva di umidit 6l M riferimento 4l G alimentazione La calza va collegata all 6l Umidificatori MC MC humidifiers MC Sonda 4 out H uscita attiva di umidit 3 M riferimento 5 G alimentazione La calza va collegata al 2 per entrambe le sonde Umidificatori Humisonic Humisonic humidifiers CDA 303 Sonda SI out H uscita attiva di umidit GND S2 M riferimento VR G alimentazione La calza va collegata a GND S2 N B prestare attenzione che gli ingressi dei cont
19. 0000 ASPC1 10000 DPPC210000 Temperatura 20T70 C ed umidit 0 100 rH ASPC230000 ASPC230010 Serie DP DPPC112000 DPPC212000 Temperatura 10T60 C ed umidit 10 90 rH Temperatura 20T70 C ed umidit 0 100 rH Serie DP DPPT014000 Temperatura 20T70 C DPPC114000 Temperatura 10T60 C ed umidit 10 90 rH DPPC214000 Temperatura 20T70 C ed umidit 0 100 rH Serie DP RS485 NON optoisolata Temperatura 20T70 C Temperatura 10T60 C ed umidit 10 90 rH DPPTO13000 DPPC113000 Cod 030220660 Sonde DP rel 2 1 10 09 10 9 CAREL ITA SONDE ATTIVE PER CONDOTTA DPD Serie DP Descrizione gamma DP Sonde attive per condotta alimentazione 8 32 Vdc 12 24 Vac uscita selezionabile Serie AS 0 1V 0 5 1 Vdc 4 20 mA DPDT010000 Temperatura 20T70 C ASDT030000 DPDTO11000 Temperatura 20T70 C solo uscita resistiva NTC CAREL ASDTO1 1000 DPDC111000 Temperatura 10T60 C uscita resistiva NTC CAREL ed umidit 10 90 rH ASDC111000 DPDC110000 Temperatura 10T60 C ed umidit 10 90 rH ASDC110000 ASDH100000 solo umidita DPDC210000 Temperatura 20T70 C ed umidit 0 100 rH ASDC230000 ASDH20000 solo umidit Serie DP DPDC112000 DPDC212000 Descrizione gamma DP Sonde attive per condotta alimentazione 18 32 Vdc 12 24
20. 1 Vdc or 0 10Vdc the load must be gt 1K Q with output configured for 4 to 20 mA the load must be lt 100 Q with NTC resistive output the two signals are isolated from the reference M GO Cod 030220660 DP Sensors Rel 2 1 10 09 10 9 CAREL y Wiring the sensor to the instrument Vdc Bn Bm GND A ESE AE Fig 4 b Vdc SI Bn SI Bm SI GND GS1 N TRA12 TRA24 Trasformatore Transformer Fig 4 c Wiring the sensor with voltage or current output Sensor connection with voltage or current output and power supply directly from the controller The power supply capacity maximum current of the controller must be evaluated For distances gt 10 metres the 4 20 mA current connection should be used to avoid measurement errors due to the drop in the reference M GO Sensor connection with separate power supply via transformer used to avoid measurement errors due to current on reference M GO connection or for power supply problems on GO with earth connection vdc Sl Bn SI Bm Sl GND SI MEERE Fig 4 d Wiring the sensor to the instrument with NTC resistive output Sensor connection with NTC resistive output the two
21. 20 30 s massimo Se i controlli prevedono segnalazioni di allarmi per fuori range si potrebbero avere delle segnalazioni che rientrano nel tempo indicato Per la modalit di misura digitale del segnale tra scheda base e scheda sensore si introdotto un periodo di aggiornamento della misura di temperatura ed umidit di 15s che pu introdurre un ritardo per la misura letta In caso di sovraccarico delle uscite tensione e corrente si ha un azzeramento dell uscita per minimo ciclo di misura 15s Anche errori di comunicazione con la scheda sensore causano un azzeramento delle uscite La condizione con uscita OV pu essere utilizzata per gestire gli errori sonda sui controlli ci possibile per le uscite 0 1V 0 10V e 4 20mA e non per 0 5 1V ATTENZIONE Le sonde sono configurate di default con uscita 4 20mA Prima di eseguire il collegamento al controllo si consiglia di verificare la compatibilit dell ingresso Per eseguire una diversa configurazione del sensore modificare la sua configurazione di default Nelle sonde con uscita temperatura e umidit entrambi i canali sono configurati nello stesso modo non sono possibili connessioni miste delle uscite Per le uscite 0 1V 0 10V e 4 20 mA i valori di inizio e fine scala sono diversi dalla sonde analogiche serie AS vedi tabella sotto riportata Sonde con uscita normalizzata 0 1V 0 10V 4 20mA 30 70 C 0 100 rH
22. ELJ oN 0 5to1V DP2 ELE OFF R min 1 kohm Ponticelli per configurazione uscite DPI DEI aL Oto1V nei modelli con due uscite attive si DP2 configurano entrambe nello stesso modo CE R max gt ED ns to20 mA 100 kohm DPWxxx2xxx Out entrambi DPWxxx5xxxOut NTC Res per temperatura DPDxxx2xxx 0 10V DPDxxx5xxx 0 10 V umidita DPPxxx2xxx DPPxxx5xxx 0 10V DP1 ON O DP2IM _ ON FR 8 I lt 8 3 DP1 GEEION 040 10V A DP2 GEEION iu Versione 0 10V configurazione di fabbrica Fig 4 a Legenda out T uscita temperatura 0 5 1 Vdco 0 1 Vdc o 4 20mA per modelli DPxxx0 o 1 out T uscita temperatura 0 10Vdc per modelli DPxxx2 0 5 out H uscita umidit 0 5 1 Vdco 0 1Vdco 4 20 mA per modelli DPxxx0 o 1 out H uscita umidit 0 10 Vdc per modelli DPxxxx2 0 5 out NTC uscita con sensore resistivo NTC 10K a 25 C standard Carel M GO riferimento sia per l alimentazione che per le uscite G alimentazione 12 24 Vac o 8 32 Vdc Nota con uscita configurata 0 1 Vdc o 0 10Vdc il carico deve essere gt 1K Q con uscita configurata 4 20 mA il carico deve essere lt 100 Q con uscita NTC resistiva i due segnali sono isolati rispetto al riferimento M GO Cod 030220660 Sonde DP rel 2 1 10 09 10 11 M GO out H E 2 O o E zZ NTC OUT
23. H a 10V at 70 C and 100 rH 4 to 20 mA AmA at 30 C and 0 rH si 20mA at 70 C and 100 rH For 0 5 to 1V output the limits generally do not need to be set 0 3V at 30 C int 0 7V at 70 C OV at 0 rH er 1V at 100 rH Cod 030220660 DP Sensors Rel 2 1 10 09 10 14 CAREL LENG 49 Table of main variables parameters for serial sensors The main feature of serial sensors is that they communicate data via the RS485 serial line which can be configured by dipswitch The parameters can be accessed via serial line using the Carel supervisor or Modbus protocols The unit code of the board is 59 MAC parameter Below is the table of the parameters and status variables Name Description Read Type UOM N D Min Max Def SPV ModBus Write A I D index address OFT Temperature offset R W A Cx 10 EEPROM 100 100 0 1 0 OFH Humidity offset R W A x 10 EEPROM 100 100 0 2 1 DLT Differential for updating the temperature R W A Cx10 EEPROM O 20 5 3 2 DLH Differential for updating the humidity R W A x 10 EEPROM O 20 5 4 3 RSV Reserved Not used R A 0 Jo 15 4 TMP Temperature value read by the sensor R A Cx 10 RAM 500 1000 6 5 UMI Humidity value read by the sensor R A x 10 RAM o 1000 7 6 RUG Dewpoint value R A Cx10 RAM 500 2000 18 7 DIP Describes the status of the dipswitch R RAM 0 255 6 133 ERR De
24. L and its subsdiaries affiliates nonetheless cannot guarantee that all the aspects of the product and the software included with the product respond to the requirements of the final application despite the product being developed according to start of the art techniques The customer manufacturer developer or installer of the final equipment accepts all liability and risk relating to the configuration of the product in order to reach the expected results in relation to the specific final installation and or equipment CAREL may based on specific agreements acts as a consultant for the positive commissioning of the final unit application however in no case does it accept liability for the correct operation of the final equipment system The CAREL product is a state of the art product whose operation is specified in the technical documentation supplied with the product or can be downloaded even prior to purchase from the website www carel com Each CAREL product in relation to its advanced level of technology requires setup configuration programming commissioning to be able to operate in the best possible way for the specific application The failure to complete such operations which are required indicated in the user manual may cause the final product to malfunction CAREL accepts no liability in such cases Only qualified personnel may install or carry out technical service on the product The customer must only use the product in the manner
25. OFT serve per calibrare l HW esterno collegato al sensore e specifica il valore di offset da sommare o sottrarre al valore letto prima di essere inviato al supervisore OFH serve per calibrare l HW esterno collegato al sensore e specifica il valore di offset da sommare o sottrarre al valore letto prima di essere inviato al supervisore DLT Il valore della variabile TMP non viene aggiornato se la temperatura non superara questo differenziale DLH ll valore della variabile UMI non viene aggiornato se l umidit non superara questo differenziale serve per limitare il n di variazioni con trasferimento di dati su seriale Errori Variabili d uscita EEP valore digitale per l errore di scrittura in Flash Pu essere scritto e serve per caricare i valori di default ERT indica che il dato del parametro TMP non corretto Questo allarme pu essere generato se la sonda rileva un valore fuori range oppure se c un problema di comunicazione ERH indica che il dato del parametro UMI non corretto L allarme pu essere generato se la sonda rileva un valore fuori range oppure se c un problema di comunicazione ETR indica che il dato del parametro RUG non corretto generato se ERT e o ERH sono a 1 ERR Riporta lo stato di tutti gli allarmi come segue BitO La sonda umidit fuori range Bitl Il parametro UMI non aggiornato per problemi di comunicazione I2C Bit4 La sonda temperatura fuori range Bit5 Il parametro TMP non
26. S485 output For sensors with serial connection the cable use must have the following characteristics twisted pair shielded preferably with earth wire size AWG20 diam 0 7 to 0 8 mm area 0 39 to 0 5 mm or AWG22 diam 0 55 to 0 65 mm area 0 24 to 0 33 mm rated capacitance between the wires lt 100 pF m Analogue version with 0 to 1 Vdc or 0 5 to 1Vdc output signal On the models with active outputs not NTC res configured for voltage signals the voltage drop over the cables must be kept in mind the effect of the drop over 1 mm in cross section means a variation of 0 015 C for each metre of cable 0 015 C m mm in the temperature measurement and a variation of 0 015 rH for each metre of cable 0 015 rH m mm2 in the humidity measurement Below is an example that shows the calculation of the variations that cause temperature and humidity errors Example Cable length Cable cross section Temperature error Humidity error 30m 0 5 mm 0 9 C 0 9 rH 30m 1 5 mm 0 3 C 0 3 rH To avoid measurement errors due to the supply current an additional power supply from an external transformer can be used CAREL transformer codes TRA12VDEOO or TRA2400001 to be connected as shown in the figure 2 with transf With this configuration the maximum distance is 100 m The transformer must not be earthed and can be installed in the panel together with the controller The connection cable must be mul
27. Sonde DP CAREL Sonde di temperatura e umidita Temperature and humidity sensors 2 ee a Manuale d uso END User manual Technology amp Evolution AWVERTENZE CAREL basa lo sviluppo dei suoi prodotti su una esperienza pluridecennale nel campo HVAC sull investimento continuo in innovazione tecnologica di prodotto su procedure e processi di qualit rigorosi con test in circuit e funzionali sul 100 della sua produzione sulle pi innovative tecnologie di produzione disponibili nel mercato CAREL e le sue filiali affiliate non garantiscono tuttavia che tutti gli aspetti del prodotto e del software incluso nel prodotto risponderanno alle esigenze dell applicazione finale pur essendo il prodotto costruito secondo le tecniche dello stato dell arte Il cliente costruttore progettista o installatore dell equipaggiamento finale si assume ogni responsabilit e rischio in relazione alla configurazione del prodotto per il raggiungimento dei risultati previsti in relazione all installazione e o equipaggiamento finale specifico CAREL in questo caso previ accordi specifici pu intervenire come consulente per la buona riuscita dello start up macchina finale applicazione ma in nessun caso pu essere ritenuta responsabile per il buon funzionamento del equipaggiamento impianto finale Il prodotto CAREL un prodotto avanzato il cui funzionamento specificato nella documentazione tecnica fomita col prodotto o scaricabile anche
28. Std in Max Std o gt N gt UN n ESS gt gt pla Wojo NIDU Cod 030220660 Sonde DP rel 2 1 10 09 10 25 CAREL Alimentazione Assorbimento uscite attive 0 1V 4 20mA e 0 10V Assorbimento in AC VA Assorbimento Uscita Seriale RS485 InDC MA Assorbimento In AC VA Campo di lavoro Precisione Immagazzinamento Funzionamento limiti Sensore Temperatura Sensore Umidit Cod 030220660 Sonde DP rel 2 1 10 09 10 ITA da 8 a 32 Vdc da 18 a 32 Vdc per versioni con uscita 0 10 V 12 24 Vac tolleranza 10 15 uscita in tensione carico 10kQ 2 uscite Vout max 10 mA 12 Vdc alimentazione 8mA 24Vdc alimentazione uscita in corrente 2 uscite a 20 MA 35mA 12 Vdc alimentazione 24mA 24Vdc alimentazione 50mA 12 Vac alimentazione 24mA 24Vac alimentazione 0 6 VA max consumo sonda versione Seriale diretta typ 5 max 12 mA 12 Vdc alimentazione typ 4 max 8mA 24 Vdc alimentazione versione Seriale Optoisolata typ max typ 14 max 20mA 12 Vdc alimentazione typ 9 max 13 mA 24 Vdc alimentazione 35 49mA rms 12 Vac 25 33mA rms 24 Vac 0 8 VA max consumo sonda sonde DPW Temperatura da 10 C a 60 C Umidit da 10 a 90
29. V 0 5 1 Vdc 4 20 MA DPWT010000 Temperatura 10T60 C ASWT030000 DPWT011000 Temperatura 10T60 C solo uscita resistiva NTC CAREL ASWTO11000 DPWC111000 Temperatura 10T60 C uscita resistiva NTC CAREL ed umidit 10 90 rH ASWC111000 ASWH100000 modello solo umidit DPWC110000 Temperatura 10T60 C ed umidit 10 90 rH ASWC110000 Serie DP Descrizione gamma DP Sonde attive per ambiente alimentazione 18 32 Vdc 12 24 Vac uscita 0 10 Vdc Serie AS DPWC115000 Temperatura 10T60 C uscita resistiva NTC CAREL ed umidit 10 90 rH ASWC115000 DPWC112000 Temperatura 10T60 C ed umidit 10 90 rH ASWC112000 Serie DP Descrizione gamma DP Sonde attive per ambiente alimentazione 8 32 Vdc 12 24 Vac uscita seriale RS485 Serie AS optoisolata DPWC114000 Temperatura 10T60 C ed umidit 10 90 rH DPWTO14000 Temperatura 10T60 C Serie DP Descrizione gamma DP Sonde attive per ambiente alimentazione 8 32 Vdc 12 24 Vac uscita seriale RS485 Serie AS NON optoisolata DPWC113000 Temperatura 10T60 C ed umidit 10 90 rH DPWT013000 Temperatura 10T60 C SONDE ATTIVE PER AMBIENTI INDUSTRIALI DPP Serie DP Descrizione gamma DP Sonde attive per ambienti industriali alimentazione 8 32 Vdc 12 24 Vac uscita Serie AS selezionabile 0 1V 0 5 1 Vdc 4 20 MA DPPT010000 Temperatura 20T70 C DPPTO1 1000 ASPTO1 1000 DPPC1 11000 DPPC 11
30. Vac uscita 0 10 Vdc Serie AS Temperatura 10T60 C ed umidit 10 90 rH Temperatura 20T70 C ed umidit 0 100 rH Serie DP Descrizione gamma DP Sonde attive per condotta alimentazione 8 32 Vdc 12 24 Vac uscita seriale RS485 optoisolata Temperatura 20T70 C Temperatura 10T60 C ed umidit 10 90 rH Temperatura 20T70 C ed umidit 0 100 rH DPDT014000 DPDC114000 DPDC214000 Serie DP Descrizione gamma DP Sonde attive per condotta alimentazione 8 32 Vdc 12 24 Vac uscita seriale RS485 NON optoisolata Temperatura 20T70 C Temperatura 10T60 C ed umidit 10 90 rH DPDT013000 DPDC113000 Versioni neutre o personalizzate disponibili su specifica richiesta Cod 030220660 Sonde DP rel 2 1 10 09 10 10 CAREL 4 1 Collegamento delle sonde con uscita analogica ITA Di seguito vengono riportati gli schemi delle connessioni alla morsettiera e la posizione dei ponticelli per l eventuale configurazione dell uscita universale in tensione o corrente default DPWxxx0xxx Out entrambi DPWxxx1xxx Out NTC Res per temperatura DPDxxx0xxx 0 1 V o 4 20 mA 0 5 1 Vdc DPDxxx1xxx 0 1 V o 4 20 m A 0 5 1 Vdc per umidit DPPxxx0xxx DPPXxx1xxx DP1
31. alza va collegata a AVSS pCO pCO Sonda Bn 1 10 ntc uscita NTC res della sonda Bn 1 3 out T uscita attiva di temperatura 6 8 Bn 1 3 out H uscita attiva di umidit 6 8 GND M riferimento Vdc G alimentazione La calza va collegata a GND pco pCO Sonda Bn 1 8 ntc uscita NTC res della sonda Bn 1 4 out T uscita attiva di temperatura Bn 1 4 out H uscita attiva di umidita GND M riferimento Vdc G alimentazione La calza va collegata a GND IR universale IR universal IR32 Sonda 7 ntc uscita NTC res della sonda 8 ntc uscita NTC res della sonda IR32 Sonda 9 out T uscita attiva di temperatura o umidit 7 M riferimento 8 G alimentazione La calza va collegata al 7 IRDR IRDR Sonda 2 ntc uscita NTC res della sonda 3 ntc uscita NTC res della sonda La calza va collegata al 2 IRDR Sonda 3 out T uscita attiva di temperatura o umidit 1 M riferimento 2 G alimentazione ii La calza va collegata al Cod 030220660 Sonde DP rel 2 1 10 09 10 19 CAREL ITA Esempio di collegamento con due strumenti IR che devono essere alimentati separatamente da due diversi trasformatori dalla linea di alimentazione Line 230 Vac 24 Vac IR a O Sensor
32. ance value Resistance value Max Std in Max Std in Max Std gt N gt UN 5 A gt gt pla Wojo NIDU Cod 030220660 DP Sensors Rel 2 1 10 09 10 23 CAREL Power supply Current input 0 to 1 V 4 20 mA and 0 to 10 V active outputs AC power consumption VA DC current input RS485 serial output mA AC power consumption VA Operating range Precision Storage Operating limits Temperature sensor Humidity sensor Cod 030220660 DP Sensors Rel 2 1 10 09 10 from 8 to 32 Vdc from 18 to 32 Vdc for output 0 10V versions 12 to 24 Vac tolerance 10 15 voltage output load 10kQ 2 outputs Vout max 10 mA 12 Vdc power supply 8 mA 24Vdc power supply current output 2 x 20 mA outputs 35mA 12 Vdc power supply 24mA 24Vdc power supply 50mA 12 Vac power supply 24mA 24Vac power supply 0 6 VA max power consumption sensor Direct serial version typ 5 max 12 mA 12 Vdc power supply typ 4 max 8 mA 24 Vdc power supply Optically isolated serial version typ max typ 14 max 20 mA 12 Vdc power supply typ 9 max 13 mA 24 Vdc power supply 35 49mA RMS 12 Vac 25 33mA RMS 24 Vac 0 8 VA max power consumption sensor DPW sensors Tempera
33. anteriormente all acquisto dal sito internet www carel com Ogni prodotto CAREL in relazione al suo avanzato livello tecnologico necessita di una fase di qualifica configurazione programmazione commissioning affinch possa funzionare al meglio per l applicazione specifica La mancanza di tale fase di studio come indicata nel manuale pu generare malfunzionamenti nei prodotti finali di cui CAREL non potr essere ritenuta responsabile Soltanto personale qualificato pu installare o eseguire interventi di assistenza tecnica sul prodotto Il cliente finale deve usare il prodotto solo nelle modalit descritte nella documentazione relativa al prodotto stesso Senza che ci escluda la doverosa osservanza di ulteriori avvertenze presenti nel manuale si evidenza che in ogni caso necessario per ciascun Prodotto di CAREL e Evitare che i circuiti elettronici si bagnino La pioggia l umidit e tutti i tipi di liquidi o la condensa contengono sostanze minerali corrosive che possono danneggiare i circuiti elettronici In ogni caso il prodotto va usato o stoccato in ambienti che rispettano i limiti di temperatura ed umidit specificati nel manuale e Non installare il dispositivo in ambienti particolarmente caldi Temperature troppo elevate possono ridurre la durata dei dispositivi elettronici danneggiarli e deformare o fondere le parti in plastica In ogni caso il prodotto va usato o stoccato in ambienti che rispettano i limiti di tempe
34. azione vedi istruzioni in seguito riportate 4 14 Cambio della configurazione di default per sonda ambiente e condotta Per cambiare la configurazione di default 1 Rimuovere il coperchio con una rotazione in senso antiorario Rimuovere le due viti e togliere la protezione Cambiare il pin di selezione in accordo con la configurazione desiderata Posizionare il coperchio di protezione e stringere le due viti assicurandosi che siano ben fissate Richiudere con il coperchio con una rotazione in senso orario TPN Cod 030220660 Sonde DP rel 2 1 10 09 10 23 CAREL ITA 4 15 Versione con sola uscita NTC La versione solo temperatura con uscita resistiva NTC utilizza un sensore NTC 10K 25 C beta 3435 vedi tabella temperatura resistenza riportata in seguito con le seguenti caratteristiche del morsetto Sezione nominale 2 5mm Dimensione massima cacciavite 2 8mm Materiale plastico morsetto Poliammide PA6 Morsetto Ottone cromato Vite del morsetto Acciaio cromato Esempio di collegamento Sonde da parete serie DPW Sonde per ambiente tecnico serie DPD Vista sonda senza coperchio Vista interna Sonde per ambiente tecnico serie DPP ES u Vista sonda senza coperchio Vista interna Cod 030220660 Sonde DP rel 2 1 10 09 10 24 CAREL ITA 4 16 Valori di resistenza delle sonde di temperatura NTC CAREL Valore di Resistenza Valore di Resistenza Valore di Resistenza Max Std in Max
35. cetate X b Motor Oil 10W 40 X b Butyle Acetate X b CH4 Methane 11 days 29000 ppm X NH3 Ammonium 11 Days 1000 ppm X Harshest Enviromental Test X X Motor Oil 160 C 100 times 250 times Liquid Nitogen 195C Toluole immersion for cleaning hydrochloric acid 32 X hydrofluoric acid 40 X sulfuric acid 90 X Test in presenza di prodotti chimici NH3 Ammonium 50 ppm X 0 NH3 Ammonium 100 ppm X c CO2 Carbon dioxide 5000 ppm X 0 NO2 Nitrogen bioxide 3 ppm X 0 H2S Hydrogen sulphur 1 ppm X c H2 Hydrogen 3500 ppm X 0 CI Chlorine 1 ppm X 0 Attenzione Non adatte per essere utilizzate in ambienti esplosivi Cod 030220660 Sonde DP rel 2 1 10 09 10 21 CAREL ITA 4 13 Montaggioe fissaggio dello strumento Versione ambiente La versione ambiente prevede il fissaggio su parete o pannello Fig 4 m Note di montaggio e Aprire il contenitore con un cacciavite a taglio posizionandolo nella fessura predisposta e prestando la massima attenzione a non danneggiare la parte elettronica e Fissare il retro contenitore del sensore al pannello o alla parete per il fissaggio del contenitore utilizzare le viti fornite insieme al kit di fissaggio prestando la massima attenzione ad usare gli appositi distanziali per non danneggiare l elettronica del sensore e Chiudere il sensore con il coperchio superiore con una leggera pressione Nota Prestare la massima attenzione a non
36. co con un ottimo rapporto prezzo qualit Questi sensori tipicamente sono utilizzati insieme ai controlli Carel ma possono essere utilizzati anche con controlli di terze parti 1 1 Caratteristiche generali Le sonde elettroniche CAREL di temperatura e o umidit sono state realizzate per applicazioni nei settori del riscaldamento della refrigerazione e del condizionamento Sono disponibili i seguenti modelli a ambiente b ambiente tecnico c condotta vari modelli si distinguono poi per le differenti uscite attive in corrente o tensione selezionabile da ponticelli ad eccezione dei modelli con uscita temperatura di tipo NTC resistivo in seguito indicato come modello NTC res compatibile con i controlli CAREL disponibile anche il modello con uscita seriale RS485 optoisolata per il collegamento alla linea seriale pCo o supervisione Carel Le sonde possono essere alimentate con tensione alternata 12 24 Vac o continua 8 32 Vdo Sonde ambiente DPW Vengono utilizzate in impianti di riscaldamento e condizionamento Presentano un estetica adatta ad un utilizzo in ambiente residenziale domestico Sono predisposte per il montaggio a parete Sonde per ambiente tecnico DPP Vengono utilizzate in ambienti tecnici celle di conservazione piscine ecc dove sia richiesto un elevato grado di protezione del contenitore IP55 e dei sensori IP54 Sono predisposte per il montaggio a parete Sonde da condotta DPD Veng
37. ded to use shielded cables The cables carrying the temperature and humidity signals must not run near the 115 to 230 or 400 to 480 Vac power cables or near cables that power from the contactors to the loads Measurement errors due to electromagnetic coupling must be avoided e The sensor power supply and electrical signals are very low voltage nonetheless for connection to the controllers remember that supplementary electrical insulation is required excluding the sensor protection cap The metal protection of the sensors is connected to the sensor power supply reference For conformity to the safety standards double insulation must used for the power supply to the sensor and the controller it is connected to if the sensor zone is accessible to the user in the installation The sensors can integrated into Class 1 or 2 equipment with the following warnings Class 1 the power supply reference GO must be earthed Class 2 double insulation or reinforced insulation must be used for the power supply to the sensor and the controller it is connected to If this is not possible in normal use the sensor zone must be made inaccessible to the users e Do not expose to sources of heat or direct sunlight Note For the connection of the analogue outputs at distances over 30 m the installer must make sure that the suitable precautions and protectors specified have been applied in compliance with the standards so as to avoid faults due to surge
38. ed this differential used to limit the number of variations with data transfer on the serial line Errors Output variables EEP digital value for the write error to Flash Can be written and used to load the default values ERT indicates that the data relating to the TMP parameter is not correct This alarm can be generated if the sensor measures a value that is out of range or if there is a communication problem ERH indicates that the data relating to the UMI parameter is not correct This alarm can be generated if the sensor measures a value that is out of range or if there is a communication problem ETR indicates that the data relating to the RUG parameter is not correct generated if ERT and or ERH are equal to 1 ERR Describes the status of all the alarms as follows Bit The humidity sensor is out of range Bit The UMI parameter is not updated due to I2C communication problems Bit4 The temperature sensor is out of range Bit5 The TMP parameter is not updated due to I2C communication problems Bit8 The RUG parameter is not correct due to UMI and TMP being out of range Bit9 The RUG parameter is not updated due to 12 communication problems Cod 030220660 DP Sensors Rel 2 1 10 09 10 15 CAREL LENG 4 10 General warnings e To maintain the index of protection declared in the versions with IP55 case the wiring must use multicore cables with the outer sheath having a maximum diameter of 8 mm e It is recommen
39. ements to any product described in this document without prior waming The technical specifications shown in the manual may be changed without prior waming The liability of CAREL in relation to its products is specified in the CAREL general contract conditions available on the website www carel com and or by specific agreements with customers specifically to the extent where allowed by applicable legislation in no case will CAREL its employees or subsidiaries be liable for any lost eamings or sales losses of data and information costs of replacement goods or services damage to things or people downtime or any direct indirect incidental actual punitive exemplary special or consequential damage of any kind whatsoever whether contractual extra contractual or due to negligence or any other liabilities deriving from the installation use or impossibility to use the product even if CAREL or its subsidiaries are warned of the possibility of such damage DISPOSAL Disposal of the product The appliance or product must be disposed of separately in compliance with the local standards in force on waste disposal Contents 1 EE EE E EE E E E E EEE E EE EEEE EES 5 1 1 General features 2 5 224 SCAREBCOAINg a entre 6 3 Codes and compatibility with the AS Series nn 7 O o e 4 1 Connections for sensors with analogue output 4 2 lt Connections for sensors with RS485 A 43 Example of
40. emperature 10T60 C resistive CAREL NTC output only ASWTO11000 DPWC111000 Temperature 10T60 C resistive CAREL NTC output and humidity 10 to 90 rH ASWC111000 ASWH100000 humidity model only DPWC110000 Temperature 10T60 C and humidity 10 to 90 rH ASWC110000 DP series Description of DP range Active wall sensors power supply 18 to 32 Vdc 12 to 24 Vac O to 10 Vdc output AS series DPWC115000 Temperature 10T60 C resistive CAREL NTC output and humidity 10 to 90 rH ASWC115000 DPWC112000 Temperature 10T60 C and humidity 10 to 90 rH ASWC112000 DP series Description of DP range Active wall sensors power supply 8 to 32 Vdc 12 to 24 Vac optically isolated RS485 AS series serial output DPWC114000 Temperature 10T60 C and humidity 10 to 90 rH DPWT014000 Temperature 10T60 C DP series Description of DP range Active wall sensors power supply 8 to 32 Vdc 12 to 24 Vac RS485 serial output NOT AS series optically isolated DPWC113000 Temperature 10T60 C and humidity 10 to 90 rH DPWT013000 Temperature 10T60 C ACTIVE SENSORS FOR INDUSTRIAL ENVIRONMENTS DPP DP series Description of DP range Active sensors for industrial environments power supply 8 to 32 Vdc 12 to 24 Vac AS series selectable output 0 1V 0 5 to 1 Vdc 4 to 20 mA DPPT010000 Temperature 20T70 C DPPTO1 1000 ASPTO1 1000 DPPC111000 DPPC 110000 ASPC1 10000 DPPC210000 Temperatu
41. er supply reference G power supply 12 to 24 Vac or 18 to 32 Vdc Note for the models that are NOT isolated GND is connected to M G0 for the optically isolated models GND is isolated from M G0 DL1 DL2 2 The following figure shows the connection between the sensors with serial output and the pCO1 controller which must be fitted with the PCO100FD10 option a YUE wz rece For the connection to supervisory systems all the RS485 interfaces featured can be used Fig 4 f 4 3 Example of configuring the RS485 serial sensor The 8 dipswitches DP2 8 can be configured to set the address the serial transmission mode and speed e Select address DIP 1 5 The selection follows the rules of 5 bit binary coding Example Off Off Off Off Off 128 On Off On Off Off 128 5 133 e CAREL Modbus supervisor protocol or Auto Serial speed 9600 19200 bit sec Cod 030220660 DP Sensors Rel 2 1 10 09 10 11 CAREL 4 4 Example of connection to the RS485 Fieldbus network 5 r 5 1200 E _ GND 7 HM ED DPWxx3 Sa GND DPWxx4 pCO a ProbeTH G M GO 1200 Mi DPWxx3 W 4 TL a DPWxx4 nn T VDC Supply max 100 mA Probet G M GO f i GND y dl BMS ModBus protocol sensor CE amp
42. ermato da 3 a 5 fili in funzione dei modelli La sezione di cavo massima prevista dai morsetti di 1 5 mm Nelle versioni DPP DPD il diametro massimo interno del pressacavo di 8 mm Versione seriale con uscita RS485 Per le sonde con connessione seriale deve essere utilizzato un cavo con le seguenti caratteristiche aduefiliritorti schermato preferibilmente con filo di continuit di sezione AWG20 diam 0 7 0 8 mm area 0 39 0 5 mm o AWG22 diam 0 55 0 65 mm area 0 24 0 33 mm capacit nominale tra i conduttori lt 100 pF m Versione analogica con uscita segnale 0 1 Vdc o 0 5 1Vdc Con i modelli ad uscite attive non NTC res configurate in tensione si consiglia di tenere conto della caduta di tensione sui cavi l effetto della caduta su 1 mm di sezione di una variazione di 0 015 C per metro di cavo 0 015 C m mm sulla misura di temperatura e di una variazione di 0 015 U R per metro di cavo 0 015 U R m mm2 sulla misura di umidit Viene riportato di seguito un esempio per chiarire il calcolo delle variazioni che danno l errore di temperatura e quello di umidit Esempio Lunghezza cavo Sezione cavo Errore temperatura Errore umidit 30m 0 5 mm 0 9 C 0 9 rH 30m 1 5 mm 0 3 C 0 3 rH Per evitare gli errori di misura dovuti alla corrente di alimentazione si pu utilizzare un alimentazione supplementare da un trasformatore esterno utilizzando i codici tra
43. f the outputs voltage and current are overloaded the output is reset for a minimum measurement cycle 15 s Communication errors with the sensor board also reset the outputs The condition with 0 V output can be used to manage sensor errors on the controllers and is available for 0 to 1 V 0 to 10 V and 4 to 20 mA outputs yet not for 0 5 to 1V WARNING The sensors are configured by default with 4 to 20 mA output Before connecting to the controller check the compatibility of the input To set a different configuration on the sensor change the default configuration On sensors with temperature and humidity output both channels are configured in the same way and mixed connections of the outputs are not possible For 0 to 1 V 0 to 10 V and 4 to 20 mA outputs the start and end scale values are different from the AS series analogue sensors see the table below Sensors with normalised output O to 1 V 0 to 10 V 4 to 20 mA 30 to 70 C 0 to 100 rH Oto 1V Oto IV O to 10V O to 10V 4 to 20 mA 4 to 20 mA Sensors with output 0 5 to 1V 30 to 70 C 0 to 100 rH 0 3 to 0 7V 0 0 to 1V Start and end range limits to be set on the controllers These are independent of the effective range of measurement Example For code DPWC110000 10 to 60 C and 10 to 90 rH For 0 to 1V 0to 10V 4to 20 mA outputs set Oto 1V OV at 30 C and 0 rH 1V at 70 C and 100 rH 0 to 10V OV at 30 C and 0 r
44. fasten For the electrical connections remove the top cover of the sensor For the configuration see the instructions shown below 4 14 Changing the default configuration for the wall sensor and duct sensor To change the default configuration 6 Remove the cover by rotating it anticlockwise 7 Remove the two screws and remove the protective cover 8 Change the selection pin according to the required configuration 9 Place the protective cover and fully tighten the two screws 10 Close the cover again by rotating it clockwise Cod 030220660 DP Sensors Rel 2 1 10 09 10 21 CAREL LENG 4 15 Version with NTC output only The temperature only version with NTC resistive output uses an NTC sensor 10K 25 C beta 3435 see the table of temperature resistance shown below with the following characteristics of the terminal Rated cross section 2 5 mm Maximum screwdriver size 2 8 mm Terminal plastic material Polyamide PA6 Terminal Chrome plated brass Terminal screw Chrome plated steel Connection example DPW series wall sensors LAIEN Sn RR Inside view bottom shell DPD series duct sensors DPP series sensors for industrial environments i i je H w View of sensor without cover Inside view View of sensor without cover Inside view Cod 030220660 DP Sensors Rel 2 1 10 09 10 22 CAREL yy 4 16 Resistance values of the CAREL NTC temperature sensors Resistance value Resist
45. mpurities or dust in the site of installation 5 2 Disposal of the instrument The sensor is made up of plastic parts and metal parts Do not dispose of the device as household waste All the parts must be disposed of according to the local waste disposal legislation in force IMPORTANT WARNINGS The CAREL product is a state of the art device whose operation is specified in the technical documentation supplied with the product or can be downloaded even prior to purchase from the website www carel com The customer manufacturer developer or installer of the final equipment accepts all liability and risk relating to the configuration of the product in order to reach the expected results in relation to the specific final installation and or equipment The failure to complete such phase which is required indicated in the user manual may cause the final product to malfunction CAREL accepts no liability in such cases The customer must use the product only in the manner described in the documentation relating to the product The liability of CAREL in relation to its products is specified in the CAREL general contract conditions available on the website www carel com and or by specific agreements with customers The size and fittings of the DP series sensors are compatible with the AS series Specifically model ASW is perfectly compatible with model DPW for model ASP the outside dimensions and the drilling template are different than for m
46. o NON utilizzare M GO come comune per la connessione del sensore NTC resistivo Schema elettrico di collegamento id A 0 Ba AA QUTNTC OUT NTC Bm M 60 Morsettiera del controllo Morsettiera del sensore Cod 030220660 Sonde DP rel 2 1 10 09 10 12 CAREL ITA 42 Collegamenti per sonde con uscita seriale RS485 Di seguito sono riportati gli schemi delle connessioni alla morsettiera e le impostazioni dei Dip Switch per la configurazione della modalit di comunicazione seriale RE485 con protocollo Carel oppure ModBus DPWxxx4xxx Optoisolato Optoinsulated DPDxxx4xxx DPPxxx4xxx e ON fall lll el le 12345678 O Optoinsulation DL1 DL2 2 2 CcIXZ2 Pie DPWxxx3xxx Non Optoisolato Not insulated DPDxxx3xxx DPPXxxx3xxx O ON dee 12345678 DL1 DL2 2 oO GSxxkKe Fee Impostazioni Dip Switch valide per tutti i modelli BERDAN Dip switch 1to5 Baud rate WELT Address 128 159 Boo 19200 RS485 protocol OFF EL care supervisor 8 N 2 ON _ OFF Hi ModBus 8 N 2 CAREL supervisor OFF TA ModBus OFF DT ModBus 8 E 1 fie e EQ riconoscimento automatico del protocollo Bit Parity Stop co mez N Legenda T
47. odel DPP for model ASD the outside dimensions are different while the fastening flange remains unchanged for model DPD For the 0 to 1 V 0 to 10 V and 4 to 20 mA outputs the start and end scale values are different from those on the AS series analogue sensors For further information see the chapter Functional notes and differences between DP and AS sensors Cod 030220660 DP Sensors Rel 2 1 10 09 10 26 CAREL 7 1 Model DPW 127 22 80 N U DI 40 72 Model DPD 40 73 Model DPP CAREL reserves the right modify or change its products without prior waming Cod 030220660 DP Sensors Rel 2 1 10 09 10 27 CAREL CAREL Industries HQs Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 http www carel com e mail carel carel com 030220660 DP Sensors Rel 2 1 10 09 10
48. ono utilizzate negli impianti di riscaldamento e condizionamento che fanno uso di condotte Sono fornite insieme ad una staffa per il loro fissaggio Fig 1 a Ambiente Ambiente tecnico Condotta Serie DPW Serie DPP Serie DPD Cod 030220660 Sonde DP rel 2 1 10 09 10 7 CAREL ITA 2 CODIFICA CAREL le2 3 4 5 6 7 8e9 10 Serie Tipo Misura Sensore umid Sensore temp Tipo di uscita Personalizz Imballo 1 e 2 Serie DP Digital sensor 3 Tipo W Ambiente P Ambiente tecnico D Condotta 4 Misura T Temperatura H Umidit C Temperatura e Umidit 5 Tipo sensore Umidit 0 Non presente 1 10 90 rh 2 0 100 rh 6 Tipo sensore temperatura 0 Non presente 1 NTC 7 Tipo uscita 0 Uscita 0 1Vdc o 4 20mA 1 Uscita 0 1V o 4 20mA ed NTC resistiva 2 Uscita 0 10Vdc 3 Uscita seriale RS485 non optoisolata Modbus Carel 4 Uscita seriale RS485 optoisolata Modbus Carel 5 Uscita 0 10V ed NTC resistiva 8 e 9 Personalizzazioni Cliente 10 Imballo 0 Singolo 1 Multiplo N Neutro Personalizzato Cod 030220660 Sonde DP rel 2 1 10 09 10 8 CAREL ITA La tabella seguente riporta i codici disponibili e compatibilit con la serie AS SONDE ATTIVE PER AMBIENTE DPW Serie DP Descrizione gamma DP sonde attive per ambiente alimentazione 8 32 Vdc 12 24 Vac uscita selezionabile Serie AS 0 1
49. or 5 out H active humidity output 6l M reference 4l G power supply The shield must be connected to 6l MC humidifiers MC Sensor 4 out H active humidity output 3 M reference 5 G power supply The shield must be connected to 2 fo HumiSonic humidifiers r both the sensors CDA 303 Sensor SI out H active humidity output GND S2 M reference VR G power supply The shield must be connected to GND S2 N B make sure that the inputs on the cont parameters must be set accordingly Cod 030220660 DP Sensors Rel 2 1 rollers and the corresponding active outputs of the sensor connected have the same current or voltage configuration the 10 09 10 18 CAREL 4 12 Chimical compatibility table for humidity sensor Legend for the table below a gt b gt c gt 1 hour immersion 100 solution 30 min immersion Deviations in presence of chemicals ppm All tests are made in standard environments after exposure to liquids o gas Only if indicated with c tests are in presence of chemicals Immersion in liquids In GAS x ppm Chemicals No effect deviation less Reversible effect Large effect not No effect Reversible effect Large effect not than 1 rh deviation less than reversible failed deviation less de
50. possa circolare liberamente attraverso le fessure senza ostruzioni dovute ad impurit o polveri presenti nel sito di installazione 52 Smaltimento dello strumento Il sensore composto da parti in plastica e da parti in metallo Non gettare l apparecchio utilizzato nei rifiuti domestici Tutte queste parti vanno smaltite secondo le normative locali in materia di smaltimento AVVERTENZE IMPORTANTI Il prodotto CAREL un prodotto avanzato il cui funzionamento specificato nella documentazione tecnica fornita col prodotto o scaricabile anche anteriormente all acquisto dal sito intemet www carel com Il cliente costruttore progettista o installatore dell equipaggiamento finale si assume ogni responsabilit e rischio in relazione alla fase di configurazione del prodotto per il raggiungimento dei risultati previsti in relazione all installazione e o equipaggiamento finale specifico La mancanza di tale fase di studio la quale richiesta indicata nel manuale d uso pu generare malfunzionamenti nei prodotti finali di cui CAREL non potr essere ritenuta responsabile Il cliente finale deve usare il prodotto solo nelle modalit descritte nella documentazione relativa al prodotto stesso La responsabilit di CAREL in relazione al proprio prodotto regolata dalle condizioni generali di contratto CAREL pubblicate nel sito www carel com e o da specifici accordi con i clienti La sonde della serie DP presentano dimensioni e i fissaggi compa
51. ratura ed umidit specificati nel manuale e Non tentare di aprire il dispositivo in modi diversi da quelli indicati nel manuale e Non fare cadere battere o scuotere il dispositivo poich circuiti interni e i meccanismi potrebbero subire danni irreparabili e Non usare prodotti chimici corrosivi solventi o detergenti aggressivi per pulire il dispositivo e Non utilizzare il prodotto in ambiti applicativi diversi da quanto specificato nel manuale tecnico o Tutti i suggerimenti sopra riportati sono validi altres per il controllo schedesenali chiavi di programmazione o comunque per qualunque altro accessorio del portaolio prodotti CAREL CAREL adotta una politica di continuo sviluppo Pertanto CAREL si riserva il diritto di effettuare modifiche e miglioramenti a qualsiasi prodotto descritto nel presente documento senza preavviso dati tecnici presenti nel manuale possono subire modifiche senza obbligo di preawiso La responsabilit di CAREL in relazione al proprio prodotto regolata dalle condizioni generali di contratto CAREL editate nel sito www carel com e o da specifici accordi con i dienti in particolare nella misura consentita dalla normativa applicabile in nessun caso CAREL i suoi dipendenti o le sue filiali affiliate saranno responsabili di eventuali mancati guadagni o vendite perdite di dati e di informazioni costi di merci o servizi sostitutivi danni a cose persone interruzioni di attivit o eventuali
52. re 20T70 C and humidity 0 to 100 rH ASPC230000 ASPC230010 DP series Description of DP range Active sensors for industrial environments power supply 18 to 32 Vdc 12 to 24 Vac 0 to 10 Vdc output Temperature 10T60 C and humidity 10 to 90 rH Temperature 20T70 C and humidity 0 to 100 rH DP series Description of DP range Active sensors for industrial environments power supply 8 to 32 Vdc 12 to 24 Vac AS series optically isolated RS485 serial output DPPT014000 Temperature 20T70 C DPPC114000 Temperature 10T60 C and humidity 10 to 90 rH DPPC214000 Temperature 20T70 C and humidity 0 to 100 rH DP series DPPC112000 DPPC212000 Description of DP range Active sensors for industrial environments power supply 8 to 32 Vdc 12 to 24 Vac RS485 serial output NOT optically isolated Temperature 20T70 C Temperature 10T60 C and humidity 10 to 90 rH DPPTO13000 DPPC113000 Cod 030220660 DP Sensors Rel 2 1 10 09 10 7 CAREL yy ACTIVE DUCT SENSORS DPD DP series Description of DP range Active duct sensors power supply 8 to 32 Vdc 12 to 24 Vac selectable output AS series 0 5 to 1 Vdc 4 to 20 mA DPDTO10000 Temperature 20T70 C ASDT030000 DPDTO11000 Temperature 20T70 C resistive CAREL NTC output only ASDTO1 1000 DPDC111000 Temperature 10T60 C resistive CAREL NTC output and humidity 10 to
53. rh onde DPD e DPP emperatura da 20 C a 70 C midita da 10 a 90 rh e da 0 a 100 rh a seconda del modello CC d per DPW il range di temperatura 10T60 C NTC resistivo 0 3 C a 25 C 0 5 C da 0 C a 50 C 0 7 C 20T70 C Temperatura uscite 1 0 5 1V 0 1V 0 10V e 4 20mA 0 5 C a 25 C 0 9 C 10T60 C 0 5 C a 25 C 0 9 C 20T70 C Umidit uscite 2 0 5 1V 0 1V 0 10Ve 4 20mA 39 orh a 25 C 50 rh 5 orh 20770 C e 10 90 rh 2 orh a 25 C 50 rh 5 orh 20770 C e 0 100 rh Temperatura uscita seriale 1 0 5 C a 25 C 0 9 C 10T60 C 0 5 C a 25 C 0 9 C 20T70 C Umidit uscita seriale 2 30 orh a 25 C 50 rh 5 rh 10T60 C e 10 90 rh 2 oth a 25 C 50 orh 50 rh 20170 C e 0 100 Yorh 1 Temperatura possibili variazioni entro 2 C in presenza di forti campi elettromagnetici 10Vm 2 Umidit possibili errori entro 5 rh in presenza di forti campi elettromagnetici 10Vm 20T70 C 10 90 rh non condensante 10T60 C 10 90 rh non condensante per versioni DPW 20T70 C 0 100 rh non condensante per versioni DPD DPP NTC 10KQ a 25 C 1 Sensore Capacitivo 26 CAREL Segnali d uscita di umidita Segnali d uscita di temperatura Morsettiera Grado di protezione contenitore Grado di protezione elemento sensibile Costante di tempo Temperatura Costante di tempo Umidita Classificazione secondo la protezione contro le scosse ele
54. rollori e le relative uscite attive della sonda collegate abbiano la stessa configurazione in corrente o in tensione parametri devono quindi essere impostati di conseguenza Cod 030220660 Sonde DP rel 2 1 10 09 10 20 CAREL ITA 4 12 Tabella compatibilit chimica per i sensori di umidit Legenda a gt 1 ora di immersione al 100 nella soluzione b gt 30 min di Immersione c gt Alterazione in presenza di sostanze chimiche ppm Tutti i test sono stati fatti in ambienti standard dopo esposizione a liquidi gas Solo se indicati con c i test sono stati fatti in presenza di sostanze chimiche Immersione in liquidi In GAS x ppm Prodotti chimici Nessun effetto Effetto reversibile Effetto ampio non Nessun effetto Effetto reversibile Effetto ampio alterazione inferiore alterazione inferiore reversibile sensore alterazione alterazione inferiore non reversibile a 1 U R a 5 U R danneggiato inferiore a 1 a 5 U R sensore U R danneggiato Test successivi all esposizione a prodotti chimici De lcing X a Pyrethyum Exctract X a Tricloroethane X a 1 2 Propandiole X a Cycloexane X a Di Isopropile Ether X b Isoproanole X b Ethile Glycole X b Ethanole X b Toluole X b Temperature Shock 20 93C X b Hot Water 93C 18h X b Tap Water X Pressure Cocker X Ethyle A
55. scribes the status of the errors for the TH sensor and R RAM 0 4095 7 134 the dewpoint EEP Reset default values 1 default returns to 0 R W D RAM 0 1 6 5 automatically ERT Temperature sensor reading error R D RAM o 1 7 6 ERH Humidity sensor reading error R D RAM o Jl 8 7 ETR Dewpoint calculation error R D RAM 0 1 9 8 Notes A indicates analogue variables the value transferred is in tenths x10 D indicates digital variables indicates integer variables Output variables TMP analogue value of the temperature read by the sensor UMI analogue value of the relative humidity read by the sensor RUG dewpoint temperature value std atm press calculated based on the two temperature and humidity measurements Range from 20 to 70 C with humidity from 5 to 95 rH DIP describes the status of the dipswitch Configuration parameters saved in Flash EEPROM OFT used to calibrate the external HW connected to the sensor and specifies the offset to add to or subtract from the value read before being sent to the supervisor OFH used to calibrate the external HW connected to the sensor and specifies the offset to add to or subtract from the value read before being sent to the supervisor DLT The value of the TMP variable is not updated if the temperature does not exceed this differential DLH The value of the UMI variable is not updated if the humidity does not exce
56. sformatori CAREL TRA12VDE00 o TRA2400001 da collegarsi come riportato in figura sopra 2 con trasf Con tale configurazione la distanza massima di 100m Il trasformatore non deve essere collegato a terra e pu essere posizionato nel quadro insieme al regolatore Il cavo di collegamento dovr essere un multipolare da 4 o 5 fili In tale situazione non scorre corrente di alimentazione sulla connessione M GO In installazioni con pi sonde utilizzare un trasformatore per ogni sonda per evitare errori di misura Versione analogica con uscita segnale 4 20 mA Per distanze maggiori di 30 m si consiglia di selezionare qualora il sistema lo permetta l uscita in corrente La distanza massima di remotazione per l uscita in corrente di 200 m Nel caso di alimentazione in alternata indispensabile utilizzare cavi aventi sezione di 1 5 mm per ridurre il rumore dovuto alla corrente di alimentazione Tale rumore pu provocare in qualche caso instabilit di misura che pu essere eliminata con alimentazione in continua o con un alimentazione supplementare come riportato in fig sopra 2 con trasf Cod 030220660 Sonde DP rel 2 1 10 09 10 15 CAREL ITA 48 Note funzionali e differenze tra sonde DP e AS con uscita analogica All accensione le sonde DP escluso le sonde seriali e temperatura NTC forniscono un valore di uscita tensione o corrente fuori range con valore negativo che si stabilizza al vertice finale in
57. stening bracket Fig 1 a Wall Industrial environment Duct DPW series DPP series DPD series Cod 030220660 DP Sensors Rel 2 1 10 09 10 5 CAREL land2 3 4 5 6 7 8 and 9 10 Series Type Measurement Humid sensor Temp sensor Type of output Custom Packaging 1 and 2 Series 3 Type 4 Measurement 5 Type of humidity sensor 6 Type of temperature sensor 7 Type of output 8 and 9 Custom features 10 Packaging DP Digital sensors W Wall P Industrial environment D Duct T Temperature H Humidity C Temperature and Humidity 0 Not present 1 10 to 90 rH 2 0to 100 rH 0 Not present 1 NIC 0 0to 1 Vdc or 4 to 20 mA output 1 0to 1 V or 4 to 20 mA and NTC resistive output 2 0 to 10 Vdc output 3 Modbus Carel RS485 serial output not optically isolated 4 Modbus Carel optically isolated RS485 serial output 5 0to 10 Vand NIC resistive output 0 Single 1 Multiple N Neutral Customised Cod 030220660 DP Sensors Rel 2 1 10 09 10 6 CAREL LENG The table below describes the codes available and compatibility with the AS series ACTIVE WALL SENSORS DPW DP series Description of DP range active wall sensors power supply 8 to 32 Vdc 12 to 24 Vac selectable output AS series 0 1V 0 5 to 1 Vdc 4 to 20 mA DPWT010000 Temperature 10T60 C ASWT030000 DPWTO11000 T
58. the versatility required by the applications in the specific market with excellent and quality price ratio These sensors are typically used together with the Carel controllers however they can also be used with third party devices 1 1 General features The CAREL electronic temperature and or humidity sensors have been developed for applications in the heating refrigeration and air conditioning sectors The following models are available a wall b industrial environment duct The various models differ due to the different active outputs current or voltage selectable by jumpers except for the models with NTC resistive temperature output hereinafter indicated as NTC res compatible with CAREL controllers A model is also available with optically isolated RS485 serial output for connection to the serial line pCO or Carel supervisor The sensors can have an alternating current 12 to 24 Vac or direct current 8 to 32 Vdc power supply Wall sensors DPW These are used in heating and air conditioning systems Their design makes them suitable for use in the home Ready for wall mounting Sensors for industrial environments DPP These are used in industrial environments cold rooms pools etc where a high index of protection is required both for the case IP55 and the sensors IP54 Ready for wall mounting Duct sensors DPD These are used in ducted heating and air conditioning systems Supplied together with a fa
59. tibili con la serie AS In particolar modo per il modello ASW perfettamente compatibile con il modello DPW ASP cambiano le dimensioni esterne e la dima di foratura rispetto al modello DPP ASD cambiano le dimensioni esterne mentre la flangia di fissaggio rimane invariata rispetto al modello DPD Per le uscite 0 1V 0 10V e 4 20 MA i valori di inizio e fine scala sono diversi dalla sonde analogiche serie AS Per ulteriori informazione si rimanda al capitolo Note funzionali e differenze tra sonde DP e AS Cod 030220660 Sonde DP rel 2 1 10 09 10 28 CAREL ITA 7 1 Modello DPW 127 22 83 22 40 ZI 80 N U 40 30 72 Modello DPD 73 Modello DPP CAREL si riserva la possibilit di apportare modifiche o cambiamenti ai propri prodotti senza alcun preavviso Cod 030220660 Sonde DP rel 2 1 10 09 10 29 CAREL ENS User manual CAREL WARNINGS CAREL bases the development of its products on decades of experience in HVAC on the continuous investments in technological innovations to products procedures and strict quality processes with in circuit and functional testing on 100 of its products and on the most innovative production technology available on the market CARE
60. ticore with 4 or 5 wires In this situation no supply current runs through connection M GO In installations with multiple sensors use a transformer for each sensor to avoid measurement errors Analogue version with 4 to 20 mA output signal For distances over 30 m the current output should be selected if the system allows The maximum installation distance for the current output is 200 m In the case of AC power supply the wires used must have a cross section of 1 5 mm to reduce noise due to the supply current Such noise may in some cases cause instability in the measurement which can be eliminated using a DC power supply or with an additional power supply as shown in the figure 2 with trasf Cod 030220660 DP Sensors Rel 2 1 10 09 10 13 CAREL LENG 4 8 Functional notes and differences between DP and AS sensors with analogue output On power up the DP sensors excluding the serial and NTC temperature sensors provide an output value voltage or current that is out of range with a negative value and that stabilises at the final reading in a maximum of 20 to 30 s If the controllers feature alarm signals for readings that are out of range such signals may be activated however they are cancelled in the time indicated For the digital measurement of the signal between the main board and the sensor board a temperature and humidity measurement refresh period of 15s is used which may introduce a delay in the reading I
61. time constant Classification according to protection against electric shock PTI of the insulating materials Period of stress across the insulating parts Environmental pollution Category of resistance to heat and fire Category immunity against voltage surges Cod 030220660 DP Sensors Rel 2 1 10 09 10 Range 0 to 100 rH Voltage 10 mV rH for Oto IV load Rmin 1 KQ Voltage 100 mV rH for Oto 10V load Rmin 1 KQ Current 4 to 20 mA 4mA 0 rH 20 mA 100 rH load Rmax 100 Q Range 30T70 C Voltage 10 mV rH for 0 5to IV load Rmin 1 kQ Voltage for 0 to 1V OV 30 C 1V 70 C load Rmin 1 KQ Voltage for 0 to 10V OV 30 C 10V 70 C load Rmin 1 kQ Current 4 to 20 mA 4 mA 30 C 20 MA 70 C load Rmax 1000 Screw terminals for cables max cross section 1 5 min 0 5 mm IP55 for DPD DPP ducts and ind env 1P30 for DPW wall 1P54 for DPP 1P40 for DPD 1P30 for DPW in still air 300 s in moving air 3 m s 605 in still air 605 in moving air 3 m s 205 Can be integrated in class 1 and 2 equipment 250 V Long Normal Category D for case and cover Category 2 25 CAREL LENG 5 1 Cleaning and maintenance When cleaning the instrument do not use ethyl alcohol hydrocarbons petrol ammonia and derivatives Use neutral detergents and water Periodically check the aeration slits on the sensor to make sure that air can flow freely through without obstructions due to i
62. ttriche PTI dei materiali per isolamento Periodo delle sollecitazioni elettriche delle parti isolanti Grado di inquinamento ambientale Categoria di resistenza al calore e al fuoco Categoria immunita contro le sovratensioni Cod 030220660 Sonde DP rel 2 1 10 09 10 Range 0 100 rh Tensione 10 mV rh per 0 1V carico Rmin 1 kQ Tensione 100 mV rh per 0 10V carico Rmin 1 KQ Corrente 4 20mA 4mA 0 rh 20mA 100 rh carico Rmax 100 Q Range 30T70 C Tensione 10 mV rh per 0 5 1V carico Rmin 1 KQ Tensione per 0 1V OV 30 C 1V 70 C carico Rmin 1 KO Tensione per 0 10V OV 30 C 10V 70 C carico Rmin 1 kQ Corrente 4 20 mA 4 mA 30 C 20 mA 70 C carico Rmax 1000 Morsetti a vite per cavi di sezione max 1 5 min 0 5 mm IP55 per DPD DPP per condotta e amb Tecnico IP30 per DPW da parete 1P54 per DPP 1P40 per DPD 1P30 per DPW in aria ferma 300 s in aria ventilata 3 m s 605 in aria ferma 60 s in aria ventilata 3 m s 205 Integrabili in apparecchiature di Classe I e Il 250 V Lungo Normale Categoria D per scatola e coperchio Categoria 2 27 ITA CAREL ITA 5 1 Pulizia e manutenzione Per la pulizia dello strumento non utilizzare alcool etilico idrocarburi benzina ammoniaca e derivati consigliabile usare detergenti neutri ed acqua Controllare periodicamente le fessure predisposte di aerazione del sensore per verificare che l aria
63. ture from 10 C to 60 C Humidity from 10 to 90 rH DPD and DPP sensors Temperature from 20 C to 70 C Humidity from 10 a 90 rH and from 0 to 100 rH according to the model for DPW the temperature range is 10T60 C NTC resistive 0 3 C at 25 C 0 5 C from 0 C to 50 C 0 7 C 20T70 C Temperature outputs 1 0 5 1V 0 1V 0 10V and 4 20 mA 0 5 C at 25 C 0 9 C 10T60 C 0 5 C at 25 C 0 9 C 20T70 C Humidity outputs 2 05 1V 0 1V 0 10V and 4 20 mA 3 1H at 25 C 50 rH 5 rH 20T70 C and 10 90 YorH 2 rH at 25 C 50 rH 5 rH 20T70 C and 0 100 rH Temperature serial output 1 0 5 C at 25 C 0 9 C 10T60 C 0 5 C at 25 C 0 9 C 20T70 C Humidity serial output 2 3 rH at 25 C 50 rH 5 IH 10T60 C and 10 90 rH 20 rH at 25 C 50 rH 5 rH 20T70 C and 100 rH 1 Temperature possible variations within 2 C in the presence of strong electromagnetic fields 10Vm 2 Humidity possible errors within 5 rH in the presence of strong electromagnetic fields 10Vm 20T70 C 10 90 rH non condensing 10T60 C 10 90 rH non condensing for DPW versions 20T70 C 0 100 rH non condensing for DPD DPP versions NTC 10KQ at 25 C 1 Capacitive sensor 24 CAREL Humidity output signals Temperature output signals Terminal block Case index of protection Sensor index of protection Temperature time constant Humidity
64. viation less reversible failed 5 rh sensor than 1 rh than 5 rh sensor Test after exposure to Chemicals De lcing X a Pyrethyum Exctract X a Tricloroethane X a 1 2 Propandiole X a Cycloexane X a Di Isopropile Ether X b Isoproanole X b Ethile Glycole X b Ethanole X b Toluole X b Temperature Shock 20 93C X b Hot Water 93C 18h X b Tap Water X Pressure Cocker X Ethyle Acetate X b Motor Oil 10W 40 X b Butyle Acetate X b CH4 Methane 11 days 29000 ppm X NH3 Ammonium 11 Days 1000 ppm X Harshest Enviromental Test X X Motor Oil 160 C 100 times 250 times Liquid Nitogen 195C Toluole immersion for cleaning hydrochloric acid 32 X hydrofluoric acid 40 X sulfuric acid 90 X Test in presence of chemicals NH3 Ammonium 50 ppm X 0 NH3 Ammonium 100 ppm X c CO2 Carbon dioxide 5000 ppm X c NO2 Nitrogen bioxide 3 ppm X 0 H2S Hydrogen sulphur 1 ppm X 0 H2 Hydrogen 3500 ppm X 0 CI Chlorine 1 ppm X 0 Warning Not suitable for use in explosive environments Cod 030220660 DP Sensors Rel 2 1 10 09 10 CAREL LENG 4 13 Assembly and fastening the instrument Wall version The wall version is wall or panel mounted Fig 4 m Assembly notes e Open the case using a flathead screwdriver in the slot paying extra care not to damage the electronic parts Fasten the rear of the sensor case to the panel or the wall For fastening the case use the
65. vvertenze Classe I Il riferimento GO di alimentazione deve essere collegato a terra Classe Il si deve prevedere un doppio isolamento o un isolamento rinforzato per l alimentazione della sonda e del controllo a cui collegato Nel caso non sia possibile necessario nell utilizzo normale rendere inaccessibile all utilizzatore la zona sensori e Non esporre vicino a grandi fonti di calore o a radiazioni solari dirette Note per le connessioni delle uscite analogiche con distanze superiori a 30m l installatore deve verificare se le opportune precauzioni e protezioni previste sono state applicate in conformit delle normative al fine di evitare guasti dovuti a Surge In funzione dell installazione pu essere necessario il collegamento a TERRA della schermatura dei cavi di connessione segnali analogici Cod 030220660 Sonde DP rel 2 1 10 09 10 18 CAREL 4 11 Esempi di applicazioni ITA Applicazioni Tutte le sonde possono essere collegate ai controllori CAREL per la misura delle grandezze di temperatura e umidit di seguito sono riportati gli esempi di alcune connessioni ai controlli CAREL Esempi di connessioni pco pCO Sonda Bn 1 4 ntc uscita NTC res della sonda Bn 5 8 out T uscita attiva di temperatura Bm 5 8 out H uscita attiva di umidit AVSS M riferimento 24 Vdc G alimentazione La c
66. xRx uscita seriale RS485 positiva TxRx uscita seriale RS485 negativa GND riferimento per connessione seriale RS485 LD1 Led verde funzione RX LD2 Led giallo funzione TX M GO riferimento per l alimentazione G alimentazione 12 24 Vac 0 18 32 Vdc Nota per i modelli NON isolati GND e collegato ad M G0 per i modelli Optolsolati GND e isolato da M G0 Nella figura successiva riportato il collegamento tra le sonde con uscita seriale e il controllo pCo1 nel quale deve essere installata l opzione PCO100FD10 Per la connessione con i sistemi di supervisione si possono utilizzare tutte le interfacce RS485 previste Fig 4 f 4 3 Esempio di configurazione sonda seriale RS485 La configurazione degli 8 dip switch DP2 8 permette Findirizzamento la modalit di trasmissione seriale e la velocit e Selezione indirizzo DIP 1 5 La selezione segue la regola della codifica binaria a 5 Bit Esempio Off Off Off Off Off 128 On Off On Off Off 128 5 133 e Protocollo Supervisore CAREL Modbus o Autom Velocita seriale 9600 19200 Bit sec Cod 030220660 Sonde DP rel 2 1 10 09 10 CAREL 4 4 Esempio di collegamento alla rete RS485 Field bus ITA 5 5 1200 GND i LT W ED DPWxx3 IGND DPWxx4 pCO i a ProbeTH G M G0