TEXA, TEXB, TEXR, TEXW - Advanced Protection Technologies Inc
Contents
1. TIPO 4X DIAGRAMAS MEC NICOS NO MET LICOS 24 x24 See ea EE Para dibujos de mejor visualizaci n visite www aptsurge com
2. TEXR TEXW Series Surge Protective Device SPD amp Installation Operation amp Maintenance Manual WARNING IMPORTANT PLEASE READ WARNING Safety First Hazardous Voltage amp Shock Hazard Only qualified licensed electricians should install or service SPDs Hazardous voltages exist within SPDs SPDs should never be installed or serviced when energized Use appropriate safety precautions including Personal Protection Equipment Failure to follow these instructions can result in death serious injury and or equipment damage This manual shall be read in its entirety prior to installing Bonding and Grounding Hazard Verify that the neutral conductor in the service entrance equipment is bonded to ground in accordance with the National Electric Code NEC and all applicable codes Verify that the neutral terminal XO on the secondary side of distribution transformers are grounded to the system ground in accordance with the NEC and all applicable codes During installation into an electrical system the SPD must not be energized until the electrical system is completely installed inspected and tested All conductors must be connected and functional including the neutral if required The voltage rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The
3. 4X Non Metallic 4X Stainless Pullbox amp Flush mount XR Standard With Opt Disc Switch on alum backplane xw Standard 10 75 x 10 88 4 5 273 x 276 x 114 H W D mm 9 x 11 x 4 5 229 x 279 x 114 With Opt Disc Switch on alum backplane 14 75 x 12 9 x 5 25 875 x 328 x 133 Longitud del Cableado y Optimizaci n del funcionamiento del DPS Los DPSs deben ser ubicados lo m s cerca posible al circuito para minimizar las perdidas por corrientes par sitas Las Sobretensiones son de gran corriente y alta frecuencia eventos que causan sustanciales ca das de tensi n a trav s de los conductores Esto causa dafios en el funcionamiento del DPS Utilice cableado lo m s corto y directo como le sea posible Planifique las instalaciones asegure que est utilizando elinterruptor m s cercano Si es una construcci n nueva ajuste la posici n del interruptor seg n corresponda TIP Las ca das de voltaje para l neas normales de 120V o 277V podr an ser 2 3V por cada cien pies 30 mts En aplicaciones de sobretensiones las ca das de voltaje podr an ser 100 150V por pie 30 cms Estas ca das de voltaje se al voltaje remanente o clampling de voltaje afectando de esta manera su funcionamiento Trate al m ximo de mantener los conductores cortos y directos En tanto que el centro de distribuci n sea m s grande es m s dif cil lograr cables m s
4. Do not perform on other enclosures or ratings NEMA DRAIN HOLES T To obtain a Type 3R enclosure rating you must drill two holes not smaller than 0 125 inch 3 2mm or larger than 0 25 inch 6mm diameter in opposite corners of the bottom surface of the enclosure Installing the drainage holes will void any other ratings except Type 3R BOTTOM VIEW LAM DIAGNOSTIC DISPLAY PANEL Advanced Protection Technologies Surge Counter Phase A Phase B Phase C Service e Test Count Reset e Advanced Protection Technologies Phase Service Test Count Reset Phase A B amp C Green LED indicators one per phase Green is good Out indicates problem Every suppression element in this SPD is monitored N G indicates on Phase A Service LED Red LED illuminates in the event of problems This indicator is logic connected to the Phase LEDs Should a Phase LED go out the Service LED will illuminate and the Audible Alarm will sound Test Tests red Service LED and Audible Alarm and changes state of Dry Contacts Alarm Silence Turns Audible Alarm off Alarm is deactivated when the Silence LED is illuminated Surge Counter Count if equipped Increments optional surge counter by one 1 Surge Counter Reset if equipped Resets optional surge counter to zero 0 Remote Monitor Accessory Option A Remote Monitor is available fo
5. 150kA 200kA 250kA 10 Modes Delete N G Protection reduces rating 11 120V Single Phase Fig 5 Delete Noise Filter 12 240V Single Phase Fig 5 Not split phase 13 127V Single Phase Fig 5 Surge Current Rating Enclosure Rating 14 300V Single Phase Fig 5 10 100kA Phase El NEMA 1 12 3R 4 16 277V Single Phase Fig 5 15 150kA Phase 4X NEMA 4X Non Metallic 17 480V Single Phase 1 Hot 1 Neu 1 Grnd Fig 5 20 200kA Phase 4S NEMA 4X Stainless Steel 25 250kA Phase FM 1 Flush Mount 30 300kA Phase P1 NEMA 1 pullbox indoor 31 300kA Phase 40 400kA Phase 45 450kA Phase 50 500kA Phase 60 600kA Phase 80 800kA Phase 90 900kA Phase 1000kA Phase Figure 1 Figure 5 Phase A BLK Phase BLK Phase C BLK Ground GRN SPLIT WYE DELTA B High DELTA amp HRG WYE SINGLE POLE CORNER GROUND 2 Hots 1 Neu 1 Gmd 3 Hots 1 Neu 1 3 Hots B HIGH Hots 1 1 Hot 1 Neu 1 DELTA B grounded 1 Neu 1 2 Hots 1 TYPICAL PARALLEL Precautionary Statement Regarding SPDs on Ungrounded Systems CONNECTED SPD ON Caution Ungrounded systems are inherently unstable and can produce ELECTRICAL PANEL excessively high line to ground voltages during certain fault conditions During Loan these fault conditions any electrical equipment including an SPD may be lads subjected to voltages which exceed their
6. Las series XA y XB incluyen gabinetes y son requeridos para el montaje en la pared Las series XR y XW son componentes de los DPSs previstos para la instalaci n dentro de otra celda el ctrica que ya tiene gabinete Mirar la Tabla 2 Los Diagramas Mec nicos est n incluidos al final de este manual paginan 12 TABLA 2 DIMENSIONES Y PESOS H W D Peso 12 x 12 x 77 23 lbs 305 x 305 x 177 10 4 kg Standard and w Opt Disc Switch amp 300kA With Opt Disc Switch amp gt 300kA 6 x 14 x 6 5 32 Ibs 406 x 356 x 165 14 5 kg 14 x 12 x 7 356 x 305 x 178 16 x 14 x 7 406 x 356 x 178 2 12 x 7 5 305 x 305 x 191 6 14 x 7 5 406 x 356 x 191 12 x 12 x 6 305 x 305 x 152 16 14 x 6 406 x 356 x 152 H WID Peso 20 x 20 x 7 5 52 lbs 508 x 508 x 191 23 6 kg 4X Non Metallic std gt 300kA w disc 4X Stainless gt 300 w disc Pullbox amp Flush mount gt 300 w disc Standard includes Disc Switch 24 x 24 x 8 52 lbs 610 x 610 x 203 23 6 kg 20 x 20 x 7 5 bs 508 x 508 x 191 kg 20 x 20 x 6 43 508 x 508 x 152 1 H W D in mm Peso 23ko 6 5 x 11 x 4 5 9 lbs 4 1 kg 165 x 279 x 114 7 lbs 3 2 kg 11 Ibs 5 kg Espacio para Mantenimiento El margen de servicio que se necesita al frente de la unidad m nimo de 36 pulgadas se requieren de distancia libre de acuerdo con el
7. warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with the NEC Do Not Hi Pot Test SPDs Any factory or on site testing of power distribution equipment that exceeds normal operating voltage such as high potential insulation testing or any other tests where the suppression components will be subjected to higher voltage than their rated Maximum Continuous Operating Voltage MCOV must be conducted with the SPD disconnected from the power source For 4 wire systems the neutral connection at the SPD must also be disconnected prior to performing high potential testing and then reconnected after test completion Failure to disconnect SPD and associated components during elevated voltage testing will damage the SPD and will void the warranty European Authorized Representative Obelis s a Boulevard G n ral Wahis 53 1030 Brussels BELGIUM Tel 32 2 732 59 54 Fax 32 2 732 60 03 E Mail mail obelis net 12 30 14 Ih 8169 Advanced Protection Technologies 14550 58th Street North Clearwater Florida 33760 800 237 4567 727 535 6339 Fax 727 539 8955 www aptsurge com info apttvss com UL is a registered trademark of Underwriters Laboratories NEC and National Electrical Code are registered trademarks of National Fire Protection Association C62 41 1 2002
8. 1 Neu 1 Grnd 2 Hots 1 Grnd Pantalla Diagn stica Todos los indicadores y mandos son localizados sobre el panel diagn stico El panel diagn stico es localizado sobre el frente del recinto SPD o detr s de la puerta sobre ciertos recintos opcionales Cada fase destaca un indicador de LED Verde LEDs verde indica la operaci n correcta Si una condici n inoperante de ocurriera la alarma empotrada audible sonar y el Servicio rojo CONDUCIDO iluminar Esto indica que la unidad necesita la evaluaci n por un electricista calificado o el t cnico Hasta que una persona calificada eval e la unidad el Silencio de Alarma de prensa para hacer callar la alarma CONDUCIDO encima del Silencio Despertador ilumina cuando la alarma es desactivada La operaci n normal ocurre con el Silencio Despertador CONDUCIDO extinguida el Servicio rojo CONDUCIDO permanecer iluminado aun cuando hayan hecho callar a la Alarma Audible La prueba prueba el Servicio rojo CONDUCIDO la Alarma Audible y cambia el estado de Contactos Secos de ser equipado Si LEDs es iluminado en una manera que sugiere la informaci n contradictoria puede haber un problema interno l gico y las necesidades de unidad substituidas Si ninguno del LEDs es iluminado la unidad no puede ser instalada correctamente Para solucionar la ayuda por favor p ngase en contacto con el Soporte t cnico APROPIADO en 727 535 6339 Opci n de Contador de Olead
9. 32 mm y no m s grande de 0 25 inch 6 mm en las esquinas del lado contrario del encapsulado LADO POSTERIOR PANTALLA DIAGN STICA Advanced Protection Technologies Surge Counter Phase A Phase B Phase C Service e Test Count Reset e Advanced Protection Technologies Phase Service Test Count Reset Divida en fases A B y C Indicadores de LED verdes un por fase Verde esta bien Hacia fuera indica el problema Cada elemento de supresi n en este SPD es supervisado g de indica sobre la Fase A El servicio CONDUJO Rojo CONDUCIDO ilumina en caso de problemas Este indicador es unido por l gica la Fase LEDs Si una Fase CONDUCIDA sale el Servicio CONDUCIDO iluminar y la Alarma Audible sonar Prueba Prueba el Servicio rojo la Alarma CONDUCIDA y Audible y cambia el estado de Contactos Secos Silencio Despertador Apaga la Alarma Audible La alarma es desactivada whtn el Silencio CONDUCIDO es iluminado Contador de Oleada Conde de ser equipado Incrementa el contador de oleada opcional por un 1 Puesta a cero de Contador de Oleada de ser equipado Reinicializa el contador de oleada opcional para poner a cero 0 Retro apto En Panel Existente sin Ola grande Disponible Posiciones Estos pueden ser dif ciles con opciones limitadas Siga todo C digos aplicables Pensar consolidar cargas en una maner
10. SPD XR s and XW s are essentially XA s without enclosures XR s and XW s are intended for installation within host electrical equipment having suitable enclosures The experienced integrator will appreciate the simplicity of XR XW XR XW s are Type 4 SPDs and have been evaluated by UL for use as Type 1 or Type 2 SPDs when installed in appropriate enclosures All UL required safety testing is complete without needing additional safety apparatus Contact factory for UL file Engineering Considerations Mount SPD in appropriate enclosure mount Diagnostic Display in appropriate location and follow appropriate instructions including short leads UL evaluation within your completed product should be easy and trouble free Do not Hi Pot test with SPD in circuit In many instances a disconnecting means is appropriate for future service A breaker serves this function as well as provides overcurrent protection to the connecting conductors If a breaker or optional Disconnect Switch are not used consider a disconnect or safety switch having appropriate SCCR rating including any required overcurrent protection Line side is likely to require a UL 98 switch where load side is likely to require a UL 508 or UL 98 switch This may be more time consuming more expensive and physically larger than anticipated APT offers an optional Disconnect Switch that has been UL evaluated as part of the SPD The optional Disconnect Switch is fully engineered and al
11. SPD Types Types 1 2 3 amp 4 Based on Location within electrical distribution system also coincides with C62 41 2 2002 Categories C amp A Figure 1 10m 30feet This SPD complies with the latest regulatory actions and is UL Listed as such For further information please review latest editions of NEC Article 285 UL 1449 or contact APT Tech Support at 800 237 4567 GENERAL INFORMATION Product Family Outline XA Single Module in enclosure XB Two Modules in enclosure XR Single small module for integration by OEM XW Single large module for integration by OEM 2 Each is available with an S or L suffix which designate Standard modes most common or discrete 10 modes specific application respectively For example XAS is SPD in enclosure with Standard modes of protection XRL is SPD without enclosure to go inside host gear having discrete ten mode protection XR amp XW versions without enclosures are available for internal mounting within electrical gear The XR version is rated 100 300kA The XW version is rated 300 500kA Both are available with S or L designations The XA amp XB families are intended for use as a Type 1 external mount SPD XR and XW families are Type 4 SPDs intended for Type 1 applications See Model Number Decoder in Table 1 Type 1 SPD Type 1 SPDs include internal overcurrent protection and have been evaluated by UL to more stringent requ
12. a criterios diferentes cUL Los m dulos del DPS XR y XW son componentes Tipo 4 que han sido evaluados por UL para uso en aplicaciones Tipo 1 Los XR s y los XW s son esencialmente XA s sin gabinete para instalaci n dentro de la celda para equipo el ctrico Puede haber circunstancias donde la instalaci n del Lado de la Acometida es preferible Siga todas las exigencias de los C digo aplicables para la instalaci n en el Lado de la Acometida Generalmente recomendamos que el DPS sea instalado con un mecanismo de desconexi n por razones de mantenimiento TIP APT ofrece un Interruptor de Desconexi n opcional que ha sido certificado por UL como una parte del DPS Esto incluye un SCCR y un conmutador del lado de la Acometida Si usted no necesita el uso de esta opci n de desconexi n por parte de APT seleccione un interruptor para desconexi n calculado para el lado de la acometida UL 98 teniendo un valor de SCCR adecuado que incluya cualquier requerimiento de protecci n por sobrecorriente Esto puede tomar m s tiempo y ser m s costoso que lo esperado Interruptor de Desconexi n opcional est 4 completamente hecho a la medida y casi seguramente m s f cil m s pequefio y menos costoso Por favor p ngase en contacto con el Soporte t cnico de APT en caso de requerirlo Ruido Audible El ruido de fondo del DPS es insignificante o inexistente y no limita la ubicaci n de instalaci n Montaje Dimensiones y pesos
13. certificados como un DPSs Tipo 1 por UL 1449 Tercera Edici n y NEC 2008 Este DPS puede ser instalado sobre el lado de la l nea del dispositivo de sobrecorriente de la acometida de acuerdo con NEC 2008 Art culo 285 Por lo general es m s pr ctico instalar al lado de la carga respecto al dispositivo principal de sobrecorriente por motivos de mantenimiento Cuando conectamos al lado de la carga desde el interruptor principal recomendamos conectarlos a trav s de un interruptor breaker de 50 30 A El interruptor sirve como un conmutador de desconexi n y proporciona la protecci n de cortocircuito a los cables que se est n conectando La Serie XD tiene elementos internos de protecci n de sobrecarga dentro del producto Un interruptor o breaker no se requiere para la protecci n por sobrecorriente del DPS Los DPSs XD han sido probados para 200kA de Corriente Nominal de Cortocircuito SCCR El XD S 120V y 120 240V se han probado para un nivel de 100kA SCCRs Consulte la etiqueta en la unidad Terminales Se permite el uso de terminales 14 2 AWG para conductores y son suministrados para la l nea la fase neutro si es usado y conexiones de tierra de equipo de seguridad 8 AWG es el tama o m nimo recomendado de cable porque las pruebas de UL y la evaluaci n fueron realizadas utilizando 8 AWG De cable y Torque de Instalaci n Este es un DPS conectado en paralelo no est conectado en serie El calibre del cable
14. cortos Cuando es inevitable un cableado m s largo entorche con cuidado los conductores junt ndolos una a dos vueltas por pie 30 cms o utilice amarras bridas pl sticas para juntar los cables TIP las sobretensiones crean campos magn ticos seg n la regla de la mano derecha Cuando la corriente entra en la direcci n de pulgar el campo magn tico est en la direcci n que cierran los dedos De la manera como la corriente de la sobretensi n va al DPS los campos son creados en una direcci n Cuando el DPS env a aquellas corrientes a neutro y o la tierra la corriente entra en direcci n de frente Viniendo y yendo est n sobre el mismo eje los campos magn ticos pueden ser cancelados evitando as la disminuci n de desempe o Esto se logra haciendo un entorchado suave y atando con amarras bridas Cables tan cortos como sea posible Los cables deben ser tan cortos y directos como sea posible Vea NEC Art 285 12 Suponga que el cable cuesta 1000 d lares por pie si y utiliza m s del necesario estar perdiendo dinero No utilice cables largos No haga curvas cerradas No utilice conectores de entrada a rosca Qu tan corto es bastante corto Tan corto como usted pueda hacerlo Qu tan largo es demasiado largo Si aun puede hacerlo m s corto Protecci n por sobrecorriente Los DPSs toman muy poca corriente en condiciones normales y conducen por un breve momento al encontrase una corriente de un sob
15. designed ratings This information is being provided to the user so that an informed decision can be made before installing any electrical equipment on an ungrounded power system Cascade Surge Protection For optimum surge protection cascade or staged surge suppression should be implemented at the service entrance and downstream locations as appropriate Known or expected surge sources as well as sensitive loads should also have localized surge suppression For interconnected electronic loads data cabling SPDs should also be utilized to protect the devices on either end of the interconnecting data cables Unpacking amp Preliminary Inspection Inspect the entire shipping container for damage or signs of mishandling Remove the packing materials and further inspect the unit for any obvious shipping damages If any damage was found and is a result of shipping or handling immediately file a claim with the shipping company and forward a copy to APT Storage Environment This SPD should be stored in a clean dry environment Storage temperature range is 40 C 40 F to 60 C 140 F Avoid exposure to high condensation PRE INSTALLATION amp INSTALLATION PLANNING Operating Environment The standard unit uses a Type 1 12 3R 4 enclosure Non metallic polycarbonate 4X stainless steel and Type 1 flush mount or pull box enclosures are available as options Before installing ensure that your enclosure type and application are
16. incluye respaldo de memoria 02 208Y 120V Wye 30 4W Grnd Fig 2 XAL DPS para Montaje EPROM sin mantenimiento 03 240 120V High Leg Delta B High Fig 3 Externo 10 Modos de Contador de Eventos Sefial de 04 480Y 277V Wye 30 4W Grnd Fig 2 Protecci n 05 480V Delta 30 3W Grnd Fig4 amp HRG Wye XBS DPS para Montaje Contador de Oleada External 08 00Y 347V AW G d Fig2 Externo Dos M dulos Pantalla para instalaci n remota con 28 pi yers Gmd Fig2 Modos de Protecci n pulgadas 71 12 cm de cable se puede Otros sistemas Disponibles Se sugiere solicitar confirmaci n Est ndar especificar otra longitud 15 254 127V Split Phase 19 3W Grnd Fig 1 DPS para Montaje Externo Pantalla de montaje en el DPS en lugar Dos M dulos del cable 18 480 240V Split Phase or Two legs of Wye Call 10 Modos de Protecci n Filtrado de ruidos extensi n de rango y 21 220Y 127V Wye 30 4W Gind Fig 2 41 520Y 300V Wye 30 4W Grnd Fig 2 Sin gabinets R entes modelos de 42 415Y 240V Wye 30 4W Grnd Fig 2 Para montaje Interno Seccionador rotativo Bussmann seg n UL98 43 400Y 230V Wye 39 4W Grnd Fig 2 Sin gabinete Seccionador rotativo con accionamiento en 44 440Y 250V Wye 30 4W Grnd Fig 2 XRS Componente de un puerta Bussmann seg n UL 98 solo 51 480V B Corner Delta 30 3W Grnd Fig 6 Certificado por UL Modos para caja tipo E1 06 240V De
17. incluye un rojo CONDUCIDO encima de las etiquetas de conexi n de fase cerca del interm dulo el alambrado diagn stico Un iluminado rojo CONDUCIDO indica el m dulo da ado Informaci n suplementaria Si un m dulo da ado ser quitado el DPS todav a puede funcionar correctamente con un m dulo Si el cable de demostraci n Figura 12 177 44 91 1 93 48 92 4 62 117 25 7 4 30 109 22 7 200 208 50 80 52 86 3 60 3 44 91 44 87 33 diagn stico fuera unido al m dulo quitado unir de nuevo el cable al conector de liberaci n r pido de otro m dulo Si el cable de demostraci n diagn stico fuera unido al m dulo quitado unir de nuevo el cable al conector de liberaci n r pido de otro m dulo La demostraci n diagn stica funcionar correctamente El XBs con el Tipo 4X o 45 recintos tiene la demostraci n diagn stica montada dentro del recinto sobre el m dulo de lado derecho Si este m dulo es quitado la demostraci n diagn stica puede ser movida a otro m dulo Quite los cuatro tornillos de la demostraci n la demostraci n y EST NDAR Y TIPO 4S RUBOR DE DIBUJOS INDUSTRIUALES CONNECTOR DRY CONTACT CUSTOMER CONNECTION 2449 621 92 B ICRENM MONTAJE DE RUBOR SCREWCOVER PULLBOX DIBUJOS INDUSTRIUALES 16 14
18. que el sistema es conectado de acuerdo con NEC y est libre de peligro o defectos antes de energizar si la conexi n entre N T no est de acuerdo con el NEC fallar n los DPSs principal causa de falla en los DPSs Energizar y confirmar la adecuada operaci n del LED Energize and confirm proper operation of indicators and or options If Red LED flashes amp Audible Alarm cycles deenergize immediately and call for help INSTALACI N T PICA EN TABLEROS Use el interruptor m s cercano al DPS A cargas protegidas Ubique el DPS cerca al interruptor 4 d breaker que quiere utilizar Mantenga los conductores lo mas directo y cortos como le sea posible Evitar curvas cerradas Para instalaci n exterior se requiere un empaque para intemperie apropiado en la uni n o ring conduleta etc GR FICOS EL CTRICOS PARA CONEXIONES T PICAS SINGLE POLE THREE POLE THREE POLE W Hot BLK W Phase A BLK Hot BLK qni Neutral WHT Phase B BLK Neutral WHT lo emen Ground GRN SPLIT DELTA amp HRG WYE SINGLE POLE 2 Hots 1 Neu 1 Grnd 3 Hots 1 1 Hot 1 Neu 1 Grnd Phase A BLK Phase A BLK A B Phase B BLK Phase B ORNG mase 84 res i inc WYE HI LEG DELTA B High CORNER GROUND 3 Hots 1 Neu 1 Grnd 3 Hots B HIGH DELTA B grounded
19. se alados Todo este Manual de Operaci n y Mantenimiento debe ser le do antes de iniciar la instalaci n Estas instrucciones no pretenden sustituir c digos nacionales o locales Siga todos los c digos el ctricos aplicables para asegurar su cumplimiento La instalaci n de este DPS s lo debe ser realizada por un electricista calificado Los DPSs APT son probados extensivamente conforme a las normas de la industria como ANSI IEEE C62 41 1 C62 41 2 C62 45 C62 62 C62 72 UL 1449 UL 1283 IEC 61643 etc Este DPS es un dispositivo de puerto nico conectado en paralelo para la entrada de servicio o acometida tablero de distribuci n o aguas abajo de la instalaci n para la Categor a C BoAde la IEEE Importantes cambios en la Nomenclatura de la Industria Efectivos 2008 2009 Tener en cuenta que UL 1449 Tercera Edici n y NEC 2008 Art culo 285 gener cambios sustanciales El termino TVSS cambio a DPS Fueron creados los DPSs Tipo 1 2 3 y 4 L la prueba UL 1449 de desempe o del voltaje remanente cambi de 500A a 3 000A UL 1449 a adi una nueva prueba corriente nominal que consiste en pruebas de ciclo de operaci n m s rigurosas NEC Article 285 amp UL 1449 3 SPD Types Types 1 2 3 amp 4 Based on Location within electrical distribution system also coincides with ANSI IEEE C62 41 2 2002 Categories C B amp A Figura 1 10m 30feet Este DPS cumple con la m s recientes accion
20. switch and provides short circuit protection to the connecting conductors These SPDs have internal overload protection elements within the product A breaker or disconnectis not required for the SPDs overcurrent protection These SPDs have demonstrated 200kA Short Circuit Current Ratings SCCRs 120V amp 120 240V models have demonstrated 100 SCCRs Refer to label on unit Terminals Terminals will accept 14 2 AWG conductor and are provided for line phase neutral if used and equipment safety ground connections 8 AWG is the minimum recommended wire size because UL testing and evaluation was performed using 8 AWG Wire Size and Installation Torque This is a parallel connected it is not series connected The size of the SPD wiring is independent of the ampere rating of the protected circuit Recommended wire is 6 AWG for phase neutral and ground connections Torque connections to 18 inch pounds Conductor length should be as short as possible If other wire sizes are used we recommend that all conductors be the same gauge Note that larger conductor might appear to be beneficial However large conductor tends to have the same inductance as smaller conductor thus netting limited improvement in exchange for being more difficult to work with Terminals accept 14 2 AWG conductor with 6 AWG being preferred Coordinate conductor size and overcurrent protection per applicable codes If equipped Disconnect Switch will a
21. will need to accomplish the following Meet all National and Local codes NEC Article 285 addresses SPDs Mount SPD as close to panel or equipment as possible to keep leads short Ensure leads are as short and straight as possible including neutral and ground Consider a breaker position that is closest to the SPD and the panel s neutral amp ground Suggested breaker amp conductor size is 60A 30A with 6 AWG Make sure system is grounded per NEC and clear of faults before energizing SPD Certain options or implementations require extra consideration See appropriate sections within this manual qs codo 10 11 Line Side Installation page 4 Internal or Integral Mount Installation inside electrical gear page 7 Disconnect Switch Option page 7 Flush Mount Option page 6 Retro fit where no breaker positions are available page 11 UL NEMA 3R Drain Holes page 10 Use a voltmeter to check all voltages to ensure correct SPD If SPD has Dry Contact Remote Monitoring or Remote Display pre plan their installation Remove power for panel Confirm panel is deenergized Identify connection breaker location and SPD location Make sure leads are short Reducing inches matters Pretend that connector leads cost you 1000 foot to make leads short Installation Tips SPD module is mounted on backplane within its enclosure In many cases the backplane assembly can be unbolted and rotated in two or four directions to yiel
22. 2 2007 Para la electr nica sensible y sistemas inform ticos recomendamos que la medida de impedancia del sistema de puesta a tierra sea tan baja como sea posible Cuando utilizamos un ducto met lico como un conductor adicional de tierra un conductor aislado para el sistema de puesta a tierra debe ir dentro del ducto y el tamafio de acuerdo con el NEC Se debe mantener una adecuada continuidad el ctrica en todas las conexiones de circuito No use bujes aislados para interrumpir el recorrido un ducto met lico No se recomienda a una tierra aislada separada para el DPS Las conexiones adecuadas de equipos al sistema de puesta a tierra y la continuidad de la malla de tierra deben ser verificadas mediante inspecci n y pruebas peri dicas como parte de un programa integral de mantenimiento el ctrico En un Sistema de potencia de 4 hilos con conexi n neutro a tierra el Puente de conexi n Principal debe ser instalado de acuerdo con el NEC no hacerlo de esta manera da ar los DPSs En sistema de potencia de 4 hilos la conexi n neutro a tierra Empalme de conexi n principal debe ser instalado de acuerdo con el NEC hacer lo contrario da ar los Montaje Interno del XR y XW como componentes del DPS Los XRs y XWs son esencialmente XAs sin gabinete El y XW s y el XR est previsto para instalaci n dentro de las celdas del equipo el ctrico que tiene gabinetes adecuados Un integrador con experiencia apreciar la sencillez
23. 50 en relaci n a la humedad la suciedad el polvo excesivo materiales inflamables o atm sferas vapores corrosivos etc Si necesito un cambio en el gabinete por favor consulte en f brica Este DPS es dise ado para un rango de temperatura ambiente de 40 c 40 F to 60 C 140 F con una humedad relativa del 0 al 95 sin condensaci n La temperatura excesiva puede accidentalmente operar las protecciones t rmicas de Sobre temperatura En raras ocasiones en climas con altas temperaturas los DPSs con tapa clara de policabonato dentro del gabinete han experimentado temperaturas internas que exceden 200 F 94 C Recomendamos colocar la unidad de modo que evite durante el verano que la luz del sol llegue directa sobre la tapa frontal clara para protegiendo del sol o no instalarlo de cara al oeste Instalaci n del Lado de L nea versus del Lado de Carga La familia XA y XB DPSs son probados y calificados como DPSs Tipo 1 por UL 1449 Tercera Edici n y NEC 2008 Este DPS puede ser instalado sobre el Lado de la Acometida del dispositivo de sobrecorriente de servicio por 2008 NEC Art 285 Los DPSs Tipo 1 tambi n pueden ser instalados en aplicaciones del Tipo 2 Generalmente es m s pr ctico para instalar como Tipo 2 al lado de carga respecto al dispositivo principal de sobrecorriente por motivos de mantenimiento Tales instalaciones ser an similares alas instalaciones tradicionales de TVSSs Nota cUL modelos son el Tipo 2 debido
24. 7 33 _ DISPLAY CONNECTOR CUSTOMER CONNECTION 2449 621 92 m Figure 13 FLUSH MOUNT amp SCREWCOVER PULLBOX MECHANICAL DRAWINGS 20 x20 ILALAH 4X NON METALLIC MECHANICAL DRAWINGS 24 x24 16 14 For larger drawings please visit www aptsurge com Serie TEXB TEXR TEXW Dispositivo Protector contra Sobretensiones Transitorias DPS Qu LISTED Manual de Instalaci n Operaci n amp Mantenimiento PRECAUCION IMPORTANTE POR FAVOR LEA ESTE DOCUMENTO La Seguridad Primero Voltaje Peligroso y Riesgo de Choque El ctrico S lo Electricistas calificados autorizados podr an instalar o dar servicio a un DPS Existe un nivel de voltaje peligroso dentro del DPS Un DPS nunca debe ser instalado y revisado cuando est energizado durante tormentas el ctricas Tomar precauciones de seguridad adecuadas incluyendo Equipo de Protecci n Personal El no seguir las siguientes instrucciones puede causar la muerte serias lesiones y o el da o de equipo Este manual debe ser le do completamente antes de la instalaci n Riesg
25. C62 41 2 2002 C62 45 2002 C62 72 2007 are registered trademarks of IEEE INTRODUCTION Thank you for choosing an APT Surge Protective Device SPD This is a high quality high energy surge suppressor designed to protect sensitive equipment from damaging transient overvoltages Proper installation is important to maximize performance Please follow steps outlined herein This entire Operation amp Maintenance Manual should be read prior to beginning installation These instructions are not intended to replace national or local codes Follow all applicable electrical codes to ensure compliance Installation of this SPD should only be performed by qualified electrical personnel APT SPDs are extensively tested in accordance with industry standards such as ANSI IEEE C62 41 1 C62 41 2 C62 45 C62 62 C62 72 UL 1449 UL 1283 IEC 61643 etc This SPD is a single port parallel connected device intended for service entrance panelboard or downstream installation for IEEE Category C B or A applications Major Industry Nomenclature Changes Effective 2008 2009 Be aware that UL 1449 Third Edition and 2008 NEC Article 285 generated substantial changes The term TVSS changed to SPD Types 1 2 3 8 4 SPDs are created UL 1449 clamping voltage performance testing changed from 500A to 3 000A UL 1449 added new nominal testing which consists of more rigorous duty cycle testing NEC Article 285 amp UL 1449 3
26. ENANCE SPDs require minimal maintenance We recommend periodic inspection of diagnostic indicators to ensure proper operation We also recommend keeping the SPD clean as appropriate Troubleshooting amp Service Please contact us for any service related issues We want to take care of any problems Quality SPDs are designed and tested to withstand severe duty However there are various electrical anomalies that SPDs cannot protect against These are generally Sustained Overvoltages also known as Temporary Overvoltages TOVs In this context Sustained Overvoltages may be only a few cycles Failed SPDs tend to be symptoms not root causes A failed SPD should be treated as a canary in the coalmine suggesting further investigation as there may be a larger issue at play Regardless of cause SPDs attempt to protect their load until failure As noted above the single largest killer of SPDs is reference to ground issues If the SPD shows problems on startup there is reasonable chance of bonding grounding misapplication issue This permanently damages the unit If not corrected it will happen again Tip Visually confirm N G bonding Be aware that a voltmeter measuring N G can be misleading For example N G voltage could read OV because neutral and ground are at the same potential by happenstance not because they are bonded Visually confirm bonding Tip Experience indicates that regulation challenged generators can cause Su
27. ER CONNECTIONS SINGLE POLE THREE POLE THREE POLE Hot qni Neutral WHT Phase B BLK Neutral WHT lo Genie Ground GRN SPLIT DELTA amp HRG WYE SINGLE POLE 2 Hots 1 Neu 1 Grnd 3 Hots 1 1 Hot 1 Neu 1 Grnd Phase A BLK Phase A BLK A B Phase B BLK Phase B ORNG mase 84 res i inc WYE HI LEG DELTA B High CORNER GROUND 3 Hots 1 Neu 1 Grnd 3 Hots B HIGH DELTA B grounded 1 Neu 1 Grnd 2 Hots 1 Grnd Phase A BLK Hot BLK Diagnostic Display Panel All indicators and controls are located on the diagnostic panel The diagnostic panel is located on the front of the SPD enclosure or behind the door on certain optional enclosures Each phase features a Green LED indicator Green LEDs indicate correct operation If an inoperative condition were to occur the built in audible alarm will sound and the red Service LED will illuminate This indicates that the unit needs evaluation by a qualified electrician or technician Until a qualified person evaluates the unit press Alarm Silence to silence the alarm The LED above Alarm Silence illuminates when the alarm is deactivated Normal operation occurs with the Alarm Silence LED extinguished The red Service LED will remain illuminated even though the Audible Alarm has been Silenced Test tests the red S
28. En este caso p ngase en contacto con la f brica DRY CONTACTS NO C NCNC C NO Los DPSs requieren m nimo mantenimiento Recomendamos inspecci n peri dica de los indicadores de diagn stico para asegurar la operaci n adecuada Tambi n recomendamos mantener el DPS limpio como corresponde Soluci n de problemas y Servicio Por favor p ngase en contacto con nosotros para cualquier Situaci n relacionada con el servicio Queremos estar atentos a cualquier problema La Calidad de los DPSs debe soportar un r gimen severo e intenta proteger su carga hasta fallar Hay anomal as el ctricas contra las cuales DPSs no puede proteger Estas son generalmente Sobretensiones sostenidas tambi n conocidas como Sobretensiones Temporales TOVs En este contexto las Sobretensiones Sostenidas pueden ser s lo unos ciclos Los DPSs que fallan tienden a ser s ntomas no el origen de las causas Aconsejamos tratar el DPS que ha fallado como una sefial de la existencia de un problema de calidad de energ a en el sistema y no como un problema individual Como una generalizaci n el mayor asesino de DPSs son los problemas de referencia a tierra Si el DPS muestra problemas en el arranque existe la posibilidad razonable de problemas de conexiones tierras aplicaci n errada Esto permanentemente la unidad Si no es corregido suceder otra vez Tip Confirme visualmente la conexi n N T Tenga en cuen
29. STEP 3 Install Flush Mount Plate amp Cover STEP 2 Mount SPD Mounting Plate 6 1 16 from outside of front wall Disconnect Switch Opt on XA Std on XB The disconnect switch provides manual disconnection means for phase conductors and the neutral conductor Ground is not switched Special care should be taken while pre planning installation to ensure that leads are as short as possible Most XA s amp XB s in square enclosures have backplanes that can be removed and repositioned to reduce leads See Figure 8 Models with rectangular enclosures may be repositioned by inverting only Excludes thru door handle options There is limited working space around the Disconnect Switch This is a consequence of reducing internal size and lead lengths Please be patient Disconnect switch will accept 6 AWG to 1 0 AWG with 6 AWG preferred Torque connections to 18 inch pounds OVER TORQUING connections WILL BREAK the Disconnect Switch and will not be covered by warranty The disconnect switch is mounted on DIN rail It may be removed by gently pulling out the mounting tab at the bottom of the switch assembly APT is one of few SPD manufacturers that make Disconnect Switches available as a fully UL qualified option The Disconnect Switch was included during UL certification and testing The Short Circuit Current Rating posted on the UL label of the SPD includes the Disconnect Swit
30. V Wye 39 4W Grnd Fig2 Standard mode emote Locatable Display on 28 Cable External Mount SPD custom cable lengths available Other Available Systems Confirmation encouraged Two Modules Mount Display on SPD instead of cable 15 254 127V Split Phase 12 3W Grnd Fig 1 10 Mode 18 480 240V Split Phase or Two legs of Wye Call Noise Filtering Extended Range amp For Internal Mount Attenuation 21 220Y 127V Wye 38 4W Gmd Fig 2 No Enclosures Rotary Disconnect Switch 41 520Y 300V Wye 30 4W Grnd Fig 2 XRS Component SPD Bussman UL98 42 415Y 240V Wye 30 4W Grnd Fig 2 UL Recognized T Thru door Rotary Disconnect Switch 43 400Y 230V Wye 30 4W Grnd Fig 2 Standard Modes Bussman UL 98 NEMA 1 12 3R only 44 440Y 250V Wye 39 4W Grnd Fig 2 Component SPD K Rotary Disconnect Switch 51 480V B Corner Delta 30 3W Grnd Fig 6 UL Recognized Katco UL 508 06 240V Delta 30 3W Grnd Fig 4 10 Modes Thu Rotary Disconnect Switch 61 240V B Corner Delta 30 3W Grnd Fig 6 Component SPD 07 380Y 220V Wye 30 4W Grnd Fig 2 UL Recognized ee 09 600V Delta 30 3W Grnd Fig 4 amp Wye Standard Modes Delete Options Available 100 150kA 200 250kA Component SPD Delete L N Protection reduces kA rating 91 600V B Corner Delta 32 3W Grnd Fig 6 UL Recognized Delete L G Protection reduces kA rating Available 100kA
31. a El contador de oleada registra el numero de sobrevoltajes transitorios sobre todo la n de y modos la g de desde el contador era la ultima puesta a cero El contador inductivamente es acoplado de cada modo de protecci n Esto incrementa sobre el cambio significativo corriente en un per odo de rato di dt grande El contador de oleada incluye la Prueba y Puestas en cero sobre la demostraci n de touchpad El Apretamiento de la Prueba afiade una cuenta El Apretamiento de la Puesta a cero limpia la memoria del contador y pone la demostraci n poner a cero El contador incluye una viruta de memoria Eprom para almacenar la cuenta de oleada en caso de una p rdida de poder El Eprom no requiere ning n mantenimiento que lo da una ventaja Sobre pilas reemplazables La demostraci n de contador de oleada ser en blanco si todo el poder es perdido al DPS pero conservar la ltima cuenta mostrada sobre la demostraci n una vez que el poder es devuelto con Agujeros de Drenaje para Gabinete Est ndar de Acero Para mantener una normativa en la UL 3R dos orificios de 0 25 6 mm deber abrirse en las esquina del lado posterior del encapsulado Tratar de no dafiar el m dulo DPS limpiar el rea en donde fue trabajado Figura 8 AGUJEROS DE DESAGUE Para mantener una clasificacion en el encapsulado tipo 3R deber s de abrir 2 orificios cuyo di metro es no m s peque o de 0 125 inch
32. a que podr a liberar posiciones de ola grande Una regla de llave de diez pies en NEC 240 21 B 1 le permite para dar un toque el autob s mientras los revisores de llave son tasados al menos el 10 del ampacity del panel Esto trabaja bien si el panel es sobre 600A o menos La llave el autob s anda escaso 6 AWG conduce al DPS UN DPS con un Interruptor Desconectar permite para DPS m s f cil que revisa en el futuro Si el panel comienza a hacerse grande gt 800A entonces los aumentos de de revisor que tambi n pueden hacerse demasiado grandes para caber en el DPS arrastran o demasiado inc modo para trabajar con En aquel caso piense dar un toque el autob s por NEC 240 21 B 1 Revisores de controlados apropiados aun interruptor de seguridad fundido a 60A Monte el DPS inmediatamente adyacente al interruptor de seguridad Una DPS allado de carga del interruptor de seguridad con 6 AWG Guarde todo conduce tan corto como posible Instalar el Lado en l nea por aprovechando el Tipo 1 posici n de DPS Considere un DPS con un Interruptor Desconectar Opci n de Contacto Seca Dos juegos de Forma C contactos secos son incluidos con el Opci n de Contacto Seca Contactos Secos cambian el estado durante condiciones inoperantes incluyendo la p rdida de poder Cualquier cambio de estado puede ser supervisado en otra parte v a Contactos Secos OPCI N DE CONTACTO SECA Un Bloque Terminal incl
33. ado del DPS es independiente de capacidad en amperios del circuito protegido El cable recomendado es 6 AWG para la fase neutro y las conexiones de tierra El torque de conexi n hasta 18 libras por pulgada La longitud del conductor deber ser tan corta como sea posible Si usa otros tamafios de cable recomendamos que todos los conductores sean del mismo calibre Note que un conductor m s grande podr a parecer ser favorable sin embargo este tiende a tener la misma inductancia que un conductor m s pequefio y este es m s dif cil de manipular Se requieren terminales para conductores 14 2 AWG siendo preferible 6 AWG Coordine el tama o del conductor y la protecci n por sobrecorriente de acuerdo con los c digos aplicables De existir el Interruptor de desconexi n permitir 6 AWG a 1 0 AWG con 6 AWG preferiblemente El torque de conexi n a 18 libras de pulgada No haga un torque mayor a las conexiones en el Interruptor Desconexi n esto Romper el Interruptor Desconexi n y no ser cubierto por la garant a Sistema de Puesta a Tierra Un conductor de puesta a tierra del equipo debe ser usado en todo el circuito el ctrico conectado al DPS Para un mejor funcionamiento use un solo punto del sistema de tierra donde el electrodo de tierra de la acometida es conectado 5 unido con todos los otros electrodos disponible acero del edificio tanques de agua met licos barras conductoras etc para la referencia ver IEEE Std 14
34. appropriate per NEMA 250 with regard to moisture dirt excessive dust flammable materials or atmospheres corrosive vapors etc Please consult factory if enclosure needs to be changed This SPD is designed in an ambient temperature range of 40 C 40 F to 60 C 140 F with a relative humidity of 0 to 95 non condensing Excessive temperature may inadvertently operate internal thermal overtemperature protectors On rare occasions in high temperature climates SPDs inside clear cover polycabonate enclosures have experienced internal temperatures exceeding 200 F 94 C We recommend positioning the unit so that the clear front avoids direct summer sunlight by shading or not facing west Line Side versus Load Side Installation The XA amp XB family SPDs are tested and qualified as Type 1 SPDs UL 1449 Third Edition and 2008 NEC This SPD can be installed on the Line Side of the service overcurrent device per 2008 NEC Article 285 Type 1 SPDs may also be installed in Type 2 applications As a generalization it is more practical to install as Type 2 on load side of main overcurrent device for maintenance reasons Such installations would be similar to traditional TVSS installations Note cUL models are Type 2 due to different cUL criteria XR and XW SPD modules are Type 4 components that have been evaluated by UL for use in Type 1 applications XR s XW s are essentially XA s without enclosures for installati
35. atures two redundant modules One diagnostic display monitors both modules simultaneously via the parallel wire connections between the modules These connectors plug in to each module transferring information to internal logic on board both modules ABNORMAL N G VOLTAGE INDICATORS If inoperate condition were to occur the diagnostic display will indicate a problem via red Service LED audible alarm and dry contact change Operation is identical to XA XR or XW series Each XB module includes a red LED above the phase connection tabs near the inter module diagnostic wiring An illuminated red LED indicates the damaged module Extra Information Should one damaged module be removed the SPD can still function correctly with one module If the diagnostic display cable was connected Figure 12 to the removed module reconnect the cable to the other module s quick release connector The diagnostic display will function correctly XB s with Type 4X or 4S enclosures have the diagnostic display mounted inside the enclosure on the right side module If this module is removed the diagnostic display may be moved to the other module Remove the display s four screws the display and appropriate internal ribbon cable Remove blank cover from the remaining module and reassemble in reverse order STANDARD amp TYPE 4S MECHANICAL DRAWINGS 177 4491 1 93 48 92 462 117 25 430 109 22 3 60 344 91 44 8
36. ccept 6 AWG to 1 0 AWG with 6 AWG preferred Torque connections to 18 inch pounds Do Not overtorque connections on Disconnect Switch as it Will Break the Disconnect Switch and will not be covered by warranty System Grounding An equipment grounding conductor must be used on all electrical circuits connected to the SPD Forthe best performance use a single point ground system where the service entrance grounding electrode system is connected to and bonded to all other available electrodes building steel metal water pipes driven rods etc for reference see IEEE Std 142 2007 For sensitive electronics and computer systems we recommend that the ground impedance measurement be as low as possible When metallic raceway is used as an additional grounding conductor an insulated grounding conductor should be run inside the raceway and sized the NEC Adequate electrical continuity must be maintained at all raceway connections Do not use isolating bushings to interrupt a metallic raceway run Aseparate isolated ground for the SPD is NOT recommended Proper equipment connections to grounding system and ground grid continuity should be verified via inspections and testing on a regular basis as part of a comprehensive electrical maintenance program On 4 Wire Power Systems neutral to ground bonding Main Bonding Jumper must be installed per the NEC Failure to do so WILL damage SPDs Internal Mounting of XR and XW Component
37. ch and supersedes any rating on the individual Disconnect Switch When used in a Type 1 line side application the SPD including its Disconnect Switch has been UL tested and approved Further evaluation is not required by UL nor is a separate UL 98 rated switch required Figure 4 INTERNAL MOUNT DISPLAY DIMENSIONS ANTON MEO BLACK LETTERS SURGE COUNTER PANTONE 441C PIO anm 2545 ge jag 1 125 TRANSLUCENTWINDOW S PL 229 2077 QEARWNDOWTYR 0951 RED LETTERS ALARM SILENCE ONLY PANTONE se he Module Rotation Feature Installation lead wire length must be minimized because longer leads hurt performance Lead length may be reduced by rotating the module inside the enclosure SPD ships with terminals pointing down If installation lends itself toward other orientation the module s aluminum backplane can be unscrewed and reoriented For example if leads enter from top rotate module assembly such that leads are shortest Be careful with ribbon cable connector and take care to retighten screws amp secure ribbon cable Mounting screws are in four corners Rectangular enclosures may be rotated up or down only See Figure 5 Figure 5 ROTATING MODULE DESIGN ALLOWS FOR SHORTER LEADS Mounting Screws Diagnostic Cable Connector in Comers INSTALLATION Pre Plan your installation You
38. ctar y reemplaza cualquier posici n sobre el individuo Desconectan el Interruptor Cuando usado en un Tipo 1 uso de lado de l nea el DPS incluyendo su Para desconectar el Interruptor ha sido UL probado y se ha aprobado UL no requiere la remota evaluaci n tampoco UL separado 98 es tasado el interruptor requerido Rasgo de Rotaci n de M dulo La longitud de cable de plomo de instalaci n debe ser reducida al m nimo porque m s largo conduce a hacer da o el funcionamiento Pueden reducir la longitud de plomo haciendo girar el m dulo dentro del recinto DPS embarca con terminales que sefialan abajo Si la instalaci n se presta hacia otra orientaci n la placa madre de aluminio del m dulo puede ser desatornillada y reorientada Por ejemplo si conduce a entrar de la cima hacer girar la asamblea de m dulo tal que conduce son lo m s corto Tenga cuidado con el conector de cable de cinta y tenga cuidado para DIMENSIONES PARA UNA MONTURA INTERNA DEL DISPLAY BACKGROUND TO BE PANTONE 445 JUND TO BE PANTONE 441 sE 1 80 180 THRU 4 PL em ON BLACK BORDER 10 125 TRANSLUCENT WINDOW S PL am 2545 220 2077 1304 CLEARWINDOWTYP ASOBLACKEORDERTYR A rz RED LETTERS ALARM SILENCE ONLY PANTONE A apretar de nuevo tornillos y el cable de cinta seguro Tornillos creci
39. d shortest leads See Fig 8 Carefully disconnect ribbon cable s and unbolt backplane assembly Various configurations have limited work space Please be patient Installation may be easier if disconnect switch is temporarily removed from DIN rail or module backplane is temporarily removed Remove an appropriately sized knockout from panel Create an appropriately sized and lo cated hole in the SPD enclosure Mount SPD Connect to equipment using an approved wiring method including seals appropriate for the enclosure rating Carefully reinstall backplane or disconnect switch as appropriate Connect conductors as appropriate short and straight as possible Note that Hi Legs are Phase B Label or mark conductors as appropriate neutral white ground green energized black hi leg orange Make sure system is bonded per NEC and is clear of hazards or faults before energizing N G bonding not NEC will fail SPDs 1 cause of SPD failures Energize and confirm proper operation of indicators and or options If Red LED flashes amp Audible Alarm cycles deenergize immediately and call for help UA TYPICAL PANEL INSTALLATION Use closest breaker to SPD To Protected Loads Locate SPD close to intended breaker Keep Leads Short as Possible Avoid Sharp Bends Outdoor installation requires appropriate weather sealing at nipple o ring sealing condulet etc Ii TAE ELECTRICAL DRAWINGS FOR CUSTOM
40. de de lo que hab a previsto APT Ofrece un Interruptor opcional de desconexi n el que ha sido UL evaluado como la parte del DPS Montaje para el display de diagfiostico El montaje del display es accesible y de f cil localizaci n Las dimensiones se encuentran en la figura 4 pag 7 El desplay contiene un cable para la instalaci n Las extensiones de cable est n disponibles en la f brica El display es directamente compatible en el m dulo XR XW y requiere cables cortos El esplay standard en estos m dulos no son permeables Cantactar la f brica para un display permeable calificado Nema 4 Incluye esparr gos y material especial de la etiqueta UL 746c f1 y UL 97 5VA UL 1283 Lenguaje necesario concerniente a la instalaci n de filtros EMI Un conductor aislado de tierra que es id ntico en tama o material aislante y calibre al de tierra y a los conductores no aterrizados del circuito de alimentaci n excepto que este es verde con o sin uno o m s l neas amarillas va a ser instalado como parte del circuito que alimentar el filtro Podemos referirnos a la tablea 250 122 de el C digo El ctrico Nacional que recomienda el tamafio apropiado para el conductor de tierra b El conductor del sistema de puesta a tierra mencionado en el item a va a ser aterrizado a la tierra de el equipo de la acometida u otra tierra aceptable construida en el edificio como la estructura del edificio en el caso de una estructura de acer
41. de los XR XW XR XW s son DPSs del Tipo 4 y han sido evaluados por UL para el uso como DPSs Tipo 1 o Tipo 2 cuando son instalados en gabinetes apropiados Todas las pruebas de seguridad requeridas por UL se llevan a cabo sin necesidad de elementos de seguridad adicionales P ngase en contacto con la f brica para obtener el archivo UL de los an lisis de ingenier a Instale el DPS en el gabinete adecuado monte la pantalla de diagn stico en la posici n apropiada y siga las instrucciones incluyendo el uso de conductores cortos La evaluaci n de UL del producto terminado debe ser f cil y sin problemas No haga pruebas de Alta Tensi n Hi Pot con el DPS en el circuito En muchos casos un mecanismo de desconexi n es apropiado para dar mantenimiento en el futuro Un Interruptor breaker cumple esta funci n as como proporciona protecci n por sobrecorriente al cableado de conexi n Si no utiliza un interruptor o conmutador de desconexi n opcional que ofrecemos considere un interruptor o conmutador de seguridad que tenga el valor apropiado de SCCR incluyendo cualquier protecci n por sobrecorriente requerida En el lado de l nea probablemente se requiere un interruptor UL 98 mientras que en el lado de carga probablemente requiere un interruptor UL 508 O UL 98 Esto puede tomar m s ETIQUETA DE DIMENSIONES PASO 1 Prepare la pared y el DPS Must support 25 55lbs Figura 3 tiempo ser m s costoso y f sicamente m s gran
42. dre Instale de nuevo en orden inverso No hay ning n usuario partes tiles dentro del m dulo Fuerte recomendamos contra el desmontaje Los m dulos pueden ser devueltos a la f brica para el servicio de la f brica la calificaci n y la vuelta Por favor p ngase en contacto con la f brica en 727 535 6339 para la ayuda Reemplazo de Demostraci n La demostraci n es el campo reemplazable Deenergize DPS confirme con el equipo de medida apropiado y descargue la capacitancia interna para moler Las posiciones de se al y con cuidado desconectan cables diagn sticos contactos uniendo a revisores etc Desatranque la demostraci n y sustituir Instale de nuevo al rev s Note que una junta de caza de focas entre la demostraci n y el recinto es un componente clave que asegura la resistencia meteorol gica Sustituya la junta siempre que la demostraci n sea quitada XB Serie con dos m dulos EI XB destaca dos m dulos redundantes Una demostraci n diagn stica supervisa ambos m dulos simult neamente v a las conexiones paralelas de cable entre los m dulos Estos conectores se enchufan a cada m dulo transfiriendo la informaci n a la l gica interna de a bordo ambos m dulos Si una condici n de inoperate de ocurriera la demostraci n diagn stica indicar un problema v a el Servicio rojo la alarma CONDUCIDA audible y secar el cambio de contacto La operaci n es id ntica a XA XR o la serie XW Cada m dulo XB
43. e nominal M ximo Continuo de operaci n se deben llevar cabo con el DPS desconectado de la fuente de energ a Para sistemas de 4 hilos la conexi n de neutro en el DPS tambi n debe ser desconectada antes desarrollar la prueba de alto potencial y luego reconecte despu s de terminada la prueba El no desconectar el DPS y los componentes asociados durante pruebas de elevado voltaje da ar n el DPS y anular la garant a Advanced Protection Technologies Clearwater Florida 33760 800 237 4567 727 535 6339 Fax 727 539 8955 14550 58th Street North www aptsurge com info aptsurge com UL is a registered trademark of Underwriters Laboratories NEC and National Electrical Code are registered trademarks of National Fire Protection Association C62 41 1 2002 C62 41 2 2002 C62 45 2002 C62 72 2007 are registered trademarks of IEEE European Authorized Representative Obelis s a Boulevard G n ral Wahis 53 1030 Brussels BELGIUM Tel 32 2 732 59 54 Fax 32 2 732 60 03 E Mail mail obelis net 12 30 14 Ih 8169 INTRODUCCI N Gracias por seleccionar un Dispositivo Protector contra Sobretensiones Transitorias DPS marca APT Este es un equipo de alta calidad suprime Sobretensiones de alta energ a y fue dise ado para proteger equipos sensibles contra da os por Sobretensiones Una adecuada instalaci n es importante para maximizar su desempe o Por favor siga los pasos aqu
44. ectrical system Because of parallel connection installation of the SPD anywhere near the equipment to be protected is satisfactory This effect is similar to flushing any toilet in a house pressure in the shower goes down In an electrical system a parallel connected SPD will remove excessive voltage off the entire system assuming reasonable proximity Tip Itis very important that wiring leads be configured as short amp straight as possible Avoid long leads Avoid sharp bends Route SPD conductors in the same conduit Leads do not have to be sized for the entire load this SPD is parallel connected not series connected As a generalization 6 AWG works fine TABLE 1 MODEL NUMBER DECODER Do not create model numbers from this chart as all features are not available on all models 02 20 Transient Eliminator 1 Voltage Code for Electrical System Model Family Options Common North American Systems XAS eile Mount SPD X Surge Counter six digit LCD counter 01 240 120V Split Phase 19 3W Grnd Fig 1 tenders Modes includes maintenance free Eprom memory 02 208Y 120V Wye 30 4W Grnd Fig 2 KAL External Mount SPD backup 03 240 120V High Leg Delta B High Fig 3 10 0089 Surge Counter plus External Surge 04 480Y 277V Wye 32 4W Grnd Fig 2 External Mount SPD Counter Signal i Two Modules 05 480V Delta 30 3W Grnd Fig4 amp HRG Wye R L le Disp 2 l 08 600Y 347
45. el c digo NEC y libre de defectos antes de energizar el DPS Ciertas opciones o puestas en pr ctica requieren la consideraci n suplementaria Mirar secciones apropiadas dentro de este manual 10 11 la Instalaci n de Lado de L nea paginan 4 la Instalaci n de Montaje Interna o Integral dentro del engranaje el ctrico paginan 7 Desconectan la Opci n de Interruptor paginan 7 la Opci n de Montaje de Rubor paginan 6 Retro apto donde ningunas posiciones de ola grande est n disponibles paginan 11 UL NEMA 3R los Agujeros de Desag e paginan 10 Utilice un voltimetro para comprobar los voltajes y asegurar que el DPS es el adecuado Si la unidad tiene opci n para montaje empotrado refi rase al montaje empotrado siguiendo las instrucciones de instalaci n Si el DPS tiene el Contacto Seco opcional planifique su instalaci n Quitar la energ a del tablero de alimentaci n Confirme que el tablero de alimentaci n est desenergizado Identificar la ubicaci n del interruptor y la ubicaci n del DPS Remueva el tamafio adecuado del orificio troquelado en el tablero Para el montaje del DPS utilice los elementos a prueba de agua segun sea necesario Conecte los conductores adecuadamente cortos y directos como le sea posible Fase Alta es la Fase B Marque o identifique los conductores adecuadamente neutro blanco tierra verde l neas energizadas negro Fase Alta naranja Asegurar
46. entes est n en cuatro esquinas Recintos rectangulares pueden ser hechos girar encima de o abajo s lo Mirar la Figura 5 Opci n Complementaria de Monitoreo Remoto Un Monitor Remoto est disponible para la supervisi n remota Esto requiere una fuente de alimentaci n de 120V independiente un transformador de enchufe en la pared y utiliza el juego de contactos secos Forma C El Monitor Remoto puede ser configurado para supervisar varios DPSs marca APT simult neamente La instalaci n es detallada en un documento aparte En este caso p ngase en contacto con la f brica INSTALACI N DE LOS M DULOS EN FORMA ROTATIVA UTILIZANDO CABLES CORTOS Instale los Tornillos in Diagn stico Cable Connector Saques de esquina INSTALACI N Planifique su instalacion Usted necesitar cumplir con lo siguiente Busque todas las Normas Nacionales y Locales NEC Art culo 285 y UL 1449 dirigido a los DPSs Monte el DPS lo m s cerca al tablero o al equipo a proteger como sea posible mantenga el conductor corto un cableado largo afecta el funcionamiento considerablemente Garantice un cableado tan corto y directo como sea posible incluyendo el neutro y la tierra Si est usando un interruptor utilice la posici n que est m s cercana al DPS al neutro y la tierra del tablero segurito del interruptor y el conductor es 50A 30A con 8 AWG Asegurese que el sistema es aterrizado de acuerdo con
47. ervice LED the Audible Alarm and changes the state of Dry Contacts if equipped If LEDs are illuminated in a manner that suggests contradictory information there may be an internal logic problem and the unit needs replaced If none of the LEDs are illuminated the unit may not be installed correctly For troubleshooting assistance please contact APT Technical Support at 800 237 4567 Surge Counter Option The surge counter registers the number of transient overvoltages on all L N and L G modes since the counter was last reset The counter is inductively coupled from each mode of protection It increments upon significant current change in a short time period large di dt The surge counter includes Count and Reset buttons on the touchpad display Pressing Count adds one count Pressing Reset clears the counter s memory and sets the display to zero The counter includes an Eprom memory chip to store the surge count in the event of a power loss The Eprom requires no maintenance giving it an advantage over replaceable batteries The surge counter display will be blank if all power is lost to the SPD but will retain the last count shown on the display once power is returned NEMA 3R Drain Holes for Standard Steel Enclosure In order to maintain a UL 3R rating two 0 25 6mm holes must be drilled in opposite corners of the bottom surface of the enclosure Take care to not damage internal SPD components Remove any drilling remnants
48. es regulatorias y son certificadas por UL como tal Para mayor informaci n por favor revise las m s recientes ediciones de Art 285 UL 1449 INFORMACION GENERAL Familia de Productos XA Un M dulo en el Gabinete XB Dos M dulos en el Gabinete XR Un M dulo peque o para la integraci n por XW Un M dulo Grande large para la integraci n por OEM Cada uno est disponible con el sufijo S o L que designa modos Est ndar el m s com n o espec fico de 10 modos para aplicaciones espec ficas respectivamente Por ejemplo XAS es un DPS en un gabinete con los modos de protecci n Est ndar XRL es un DPS sin gabinete para ir dentro del tablero de distribuci n principal que tiene diez modos protecci n espec ficos Las versiones XR y XW sin gabinete est n disponibles para montaje interno dentro del tablero el ctrico La versi n XR est en 100 300kA La versi n XW est en 300 500kA Ambos est n disponibles con la denominaci n L o S El XA y familias XB son requeridos para el empleo como un Tipo 1 montaje externo DPS XR y familias XW son el Tipo 4 DPSs intencionados para el Tipo 1 usos Mirar el Decodificador de N mero de modelo en la Mesa 1 DPS Tipo 1 Los DPSs Tipo 1 incluyen protecci n por sobrecorriente interna y han sido evaluados por UL para los m s rigurosos requerimientos Los DPSs Tipo 1 son apropiados para instalaci n en el lado de la l nea de acometida o de la car
49. est amp straightest possible leads Pre Plan installations and ensure that nearest breaker positions are used If new construction adjust breaker locations as appropriate Tip Voltage drops for normal 120V or 277V lines might be 2 3V per hundred feet In surge applications voltage drops might be 100 150V per foot These voltage drops add to clamping voltage thus hurting performance Make every effort to keep leads short and straight As distribution gear becomes larger shorter leads are more difficult to accomplish When longer leads are unavoidable gently twist leads together one to two twists per foot or tie wrap leads together Tip surges create magnetic fields per the right hand rule When current goes in direction of thumb magnetic field is in direction of curl of fingers As surge current goes to SPD fields are created in one direction When the SPD sends those currents to neutral and or ground current goes in the opposite direction If coming amp going are on the same axis the magnetic fields can be cancelled thus avoiding performance decrease Gentle twists bundling amp tie wraps accomplish this Shortest Leads Possible Leads must be as short and straight as possible See NEC Art 285 12 Pretend wire is 1000 per foot coming out of your pocket No long leads No sharp bends No wire nuts How short is short enough As short as you can make it How long is too long If anyone else can make it shor
50. ga con respecto a la protecci n principal de sobre corriente Los DPSs Tipo 1 pueden ser utilizados en aplicaciones Tipo 2 Protecci n Interna Este dispositivo tiene al interior protecci n por sobrecorriente y por sobre temperaturas que desconectar los componentes de supresi n daf ados al final de su vida til pero mantendr la carga energizada ahora sin protecci n Si esta situaci n es indeseable para la aplicaci n siga estas instrucciones para reemplazar el dispositivo Instrucciones de Mantenimiento El mantenimiento de esta unidad consiste en el reemplazo del m dulo s internos desconecte el interruptor si cuenta con un interruptor y o pantalla ensamblada en el equipo No hay partes utiles para el usuario dentro del m dulo reemplazable No intente desensamblar la unidad para economizar gastos Explicaci n Simplificada de Operaci n El DPS censa un sobrevoltaje y crean un cortocircuito moment neo para redireccionar la energ a dafiina del sobrevoltaje a la puesta a tierra Ellos reinician autom ticamente y esperan el siguiente sobrevoltaje Esto es similar a la v lvula de alivio de presi n sobre un calentador de agua la presi n Sube la v lvula abre para relevar la presi n y luego reinicia En un sistema el ctrico el DPS detecta un sobrevoltaje cortos temporales env an energ a a la puesta a tierra y luego se reinician Los DPSs son capaces de repetir esta funci n miles de veces Conexi n en Parale
51. gh rise steel frame structure c Any attachment plug receptacles in the vicinity of the filter are to be of a grounding type and the grounding conductors serving these receptacles are to be connected to earth ground at the service equipment or other acceptable building earth ground such as the building frame in the case of a high rise steel frame structure d Pressure terminal or pressure splicing connectors and soldering lugs used in the installation of the filter shall be identified as being suitable for the material of the conductors Conductors of dissimilar metals shall not be intermixed in a terminal or splicing connector where physical contact occurs between dissimilar conductors unless the device is identified for the purpose and conditions of use Optional Flush Mount Installation Considerations The XA amp XB are approximately 6 deep The unit will not mount flush unless there is at least 6 of depth clearance The XA amp XB are not designed to mount flush on a typical 2 x 4 stud wall Back Flange Mounting Mount as close as possible to protected panel Create a wall opening slightly larger than SPD See Figure 4 Configure a robust backing plate inside the wall cavity 6 1 16 from the wall face such that the SPD is supported from its back Note the mounting holes on the back flange Also note that the SPD weighs 22 52 lbs careful not to drop the SPD into the wall Cutout slightly larger than SPD base L
52. irements Type 1 SPDs are suitable for installation on the line side or load side of the service disconnect overcurrent device Type 1 SPDs may be used in Type 2 applications Internal Protection This device features internal overcurrent and overtemperature protection that will disconnect effected surge suppression components at the end of their useful life but will maintain power to the load now unprotected If this situation is undesirable for the application follow these instructions for servicing or replacing the device Service Guidelines Service of this unit consists of replacing the internal module s disconnect switch if equipped and or display assembly There are no user serviceable parts inside the replaceable module Do not attempt to disassemble the module as it stores charge Simplified Explanation of Operation SPDs sense overvoltage and create a momentary short circuit to redirect harmful surge energy SPDs reset automatically and wait for the next surge This is similar to the pressure relief valve on a water heater pressure goes up valve opens to relieve pressure and then resets In an electrical system an SPD senses overvoltage shorts temporarily which equalizes damaging voltages and then resets SPDs are capable of repeating this function thousands of times Parallel Connection This is a Parallel connected SPD not series connected As outlined above an SPD drains off excessive voltage from an el
53. la pared frontal para revisores de fase y el revisor neutro La tierra no es cambiada El cuidado especial deber a ser tomado preplanificando la instalaci n para asegurar que conduce son tan corto como posible El y XB S de la Mayor parte de XA en recintos cuadrados tiene las placas madre que pueden ser quitadas y colocadas de nuevo para reducir conduce Mirar la Figura 8 Los modelos con recintos rectangulares pueden ser colocados de nuevo por invirtiendo s lo Excluye opciones a trav s de picaporte All es limitado trabajando el espacio alrededor del Interruptor Desconectar Esto es una consecuencia de reducir el tama o interno y longitudes de plomo Por favor est paciente Desconecte el interruptor aceptar 6 AWG a 1 0 AWG con 6 AWG preferidos Conexiones de momento de rotaci n 18 libras de pulgada OVERTORQUING conexiones ROMPERA el Interruptor Desconectar y no ser cubierto seg n la garant a El interruptor desconectar es montado sobre el RIEL DIN Puede ser quitado por con cuidado sacando la etiqueta creciente en el fondo de la asamblea de interruptor DPS es uno de pocos fabricantes DPS que hacen Desconectan Interruptores disponible como un totalmente UL la opci n calificada El Interruptor Desconectar fue incluido durante la certificaci n UL y pruebas La corriente de Cortocircuito la Posici n de al corriente sobre la etiqueta de UL DEL DPS incluye el Interruptor Descone
54. lo Este es un DPS conectado en paralelo no conectado en serie Tal como indicamos arriba un DPS drena el exceso de voltaje de un sistema el ctrico Debido a la conexi n en paralelo es conveniente la instalaci n del DPS en cualquier lugar cerca al equipo a proteger Este efecto es similar a vaciar el agua de alg n inodoro en una casa la presi n en la ducha baja En un sistema el ctrico un DPS conectado en paralelo quitar el voltaje excesivo de todo el sistema asumiendo una proximidad razonable TIP Es cr ticamente importante que los cables de la instalaci n el ctrica sean configurados tan cortos y directos como sea posible Evite conductores largos Evite curvas cerradas El recorrido de los conductores del DPS sea en el mismo ducto El conductor no tiene que ser dimensionado para toda la carga este DPS es conectado en paralelo no conectado en serie Generalmente calibre No 8 AWG funciona bien en este producto TABLA 1 DECODIFICADOR DEL DE MODELO No cree n meros de modelo de esta tabla ya que todas las caracter sticas no est n disponibles en todos los modelos TE 02 XAS 20 Eliminador de Transitorios C digo de Voltaje para el Sistema El ctrico Familia del Modelo Opcionales Sistemas mas comunes en Norte Am rica KAS DPS para Montaje X Contador de transitorios contador LCD de Externo Modos de 01 240 120 Split Phase 19 3W Grnd Fig 1 Protecci n Est ndar seis d gitos
55. lta 30 3W Grnd Fig 4 de Protecci n Est ndar Rotary Disconnect Switch 61 240V B Corner Delta 30 3W Grnd Fig 6 Componente de un DPS Katco UL 508 07 380Y 220V Wye 30 4W Grnd Fig 2 Certificado por UL 10 Thru door Rotary Disconnect Switch 09 600V Delta 32 3W Grnd Fig 4 amp Wye Modos de Protecci n UL 508 NEMA 1 12 4 only Available 100 150 200 250kA XWS Componente de un DPS Delete Options Certificado por UL Modos 91 600V B Corner Grnd Delta 39 3W Grnd Fig 6 de Protecci n Est ndar Delete L N Protection reduces kA rating Available 100kA 150kA 200kA 250kA XWL Componente de un DPS Delete L G Protection reduces kA rating 11 120V Single Phase Fig 5 Certificado por UL 10 Delete N G Protection reduces kA rating 12 240V Single Phase Fig 5 Not split phase Modos de Protecci n Delete Noise Filter 13 127V Single Phase Fig 5 Surge Current Rating Tipo de Gabinete 14 300V Single Phase Fig 5 16 277V Single Phase Fig 5 10 100KA Fase pi NEMA1 12 3R 4 15 150kA Fase medidas 12 12 7 5 305 305 191 mm 17 480V Single Phase 1 Hot 1 Neu 1 Grnd Fig 5 20 200kA Fase nae xdi no met lica 25 250kA Fase medidas 14 x 12 x 6 356 305 x 152 30 300kA Fase 31 300kA Fase 40 400kA Fase 45 450kA Fase NEMA 1 para montaje empotrado 50 500kA Fase medidas de la cavidad en la
56. mas de griega donde DPSs es dise ado para Sistemas conectados con tierra DPSs para sistemas infundados generalmente tienen m s alto MCOV para tener fluctuaciones de voltaje en cuenta g de los Fracasos de esta naturaleza no son defectos en la habilidad DPSs o el material Esto es un error de instalaci n no una situaci n justificable Un circuito de voltaje diferencial supervisa neutro para moler el voltaje Cuando el voltaje g de n se hace excesivo un shrinkwrap la resistencia cubierta se calentar Despu s de varios minutos el pl stico se encoger alrededor de la resistencia Este instrumento diagn stico no descubrir voltajes al instante excesivos g de De encogido o ser embrollado la garant a es anulada Cuando el DPS es deenergized esta resistencia puede ser tenida acceso por el personal calificado bajo la cubierta de plato de demostraci n Mirar la Figura 12 Reemplazo de M dulo y Servicio EI m dulo s es el campo reemplazable Deenergize DPS confirme con el equipo de medida apropiado y descargue la capacitancia interna para moler Las posiciones de sefial y con cuidado desconectan cables diagn sticos conexiones de contacto secas dividen en fases a revisores intapan conexiones paralelas sobre XB modela etc Dependiendo el modelo el m dulo puede ser echado el cerrojo a la placa madre o placa madre puede ser la parte de la asamblea de m dulo Quite el m dulo placa ma
57. most certainly easier smaller and less expensive Please contact APT Technical Support as appropriate Mounting Diagnostic Display Mount the Display in a user friendly location with consideration to weather and vandalism Dimensions are in Figure 4 page 7 A Display with a 28 connector cable is typically included Longer FLUSH MOUNT INSTALLATION STEP 1 Prepare Wall Must support 25 55lbs Figure 3 lengths are available The Display is also mountable directly on the XR XW module shorter cables required The standard Display includes mounting thru holes and is not weather resistant Contact factory for weather resistant NEMA 4 rated Display with mounting studs instead of thru holes and label material including UL 746C f1 amp UL 94 5VA flame rating UL 1283 required language concerning the installation of EMI Filters a An insulated grounding conductor that is identical in size and insulation material and thickness to the grounded and ungrounded circuit supply conductors except that it is green with or without one or more yellow stripes is to be installed as part ofthe circuit that supplies the filter Reference should be made to Table 250 122 of the National Electrical Code regarding the appropriate size of the grounding conductor b The grounding conductor mentioned in item a is to be grounded to earth at the service equipment or other acceptable building earth ground such as the building frame in the case of a hi
58. neously excessive N G voltages If shrunk or tampered with the warranty is voided When the SPD is deenergized this resistor can be accessed by qualified personnel under the display plate cover See Figure 11 Module Replacement amp Service The module s is field replaceable Deenergize SPD confirm with appropriate measurement equipment and discharge internal capacitance to ground Mark locations and carefully disconnect diagnostic cables dry contact connections phase conductors unplug parallel connections on XB models etc Depending on model module may be bolted to backplane or the backplane may be part of the module assembly Remove module backplane Reinstall in reverse order There are no user serviceable parts inside the module We strongly recommend against disassembly Modules may be returned to the factory for factory service qualification and return Please contact the factory at 800 237 4567 for assistance Display Replacement The display is field replaceable Deenergize SPD confirm with appropriate measurement equipment and discharge internal capacitance to ground Mark locations and carefully disconnect diagnostic cables contacts connecting conductors etc Unbolt display and replace Reinstall in reverse Note that a sealing gasket between the display and the enclosure is a key component ensuring weather resistance Replace the gasket whenever the display is removed XB Series with two modules The XB fe
59. o de varios pisos Cualquier toma corriente de acoplamiento con enchufe alrededor del filtro debe ser del tipo aterrizado y los conductores de tierra que alimentan estos tomacorrientes van ser conectados al polo a tierra en el equipo de la acometida u otro polo a tierra aceptable de la edificaci n como el marco de edificio en el caso de una estructura de varios pisos con vigas de acero d Se usan en la instalaci n de los filtros terminal de presi n conectores de empalme a presi n o terminales soldados y ser n seleccionados como sea conveniente de acuerdo con el material de los conductores Los conductores de metales distintos no ser n entremezclados en un terminal o conector donde ocurre el contacto f sico entre conductores distintos a no ser que dispositivo est identificado para este prop sito y condiciones de uso Consideraciones Para La Opcion De Instalacion Empotrada chasis de la unidad XD tiene aproximadamente 4 10 16 cms de profundidad La unidad no puede ser empotrada a menos que haya 4 de espacio libre en profundidad El XD no est dise ado para montaje empotrado en una pared estructural t pica de 2 X4 Desconecte el Interruptor Optar sobre XA Std sobre XB El interruptor desconectar proporciona el medio de desconexi n manual Cutout slightly larger than SPD base L PASO 2 Insierte en la pared Install Flush Mount Plate amp Cover Placa de montaje 6 1 16 de
60. o en la conexi n y puesta a tierra Verifique que el conductor de neutro en la acometida del equipo est conectado a tierra de acuerdo con el C digo El ctrico Nacional NEC y todos los c digos aplicables Verifique que el terminal de neutro XO al lado secundario de los transformadores de distribuci n est aterrizado con el sistema de puesta a tierra de acuerdo con el NEC y todos los c digos aplicables Durante la instalaci n en un sistema el ctrico el DPS no debe ser energizado hasta que el sistema el ctrico est completamente instalado inspeccionado y probado Todos los conductores deben estar conectados incluyendo el neutro de ser requerido El voltaje nominal del DPS y el sistema debe ser verificado antes de energizar el DPS El incumplimiento de estas indicaciones puede conducir de modo anormal altos voltajes en el DPS Esto puede hacer que el DPS falle La garant a es anulada si el DPS es instalado incorrectamente ylo si el conductor neutro en el equipo de la acometida o aguas debajo de los sistemas tomados separadamente no est conectado a la puesta a tierra conforme al NEC No haga pruebas de sobretensi n Hi pot a los DPSs Cualquier prueba en f brica o en sitio del equipo de distribuci n de potencia que exceda el voltaje normal de operaci n como pruebas de aislamiento de alto potencial o cualquier otra prueba donde los componentes de supresi n vayan a ser sometidos a un voltaje m s alto que su Voltaj
61. on within host electrical equipment There may be circumstances where Line Side installation is desirable Follow all applicable Code requirements for Line Side installation We generally recommend that the SPD be installed with a disconnecting mechanism for servicing purposes Tip APT offers an optional Disconnect Switch that has been UL evaluated as part of the SPD This includes SCCR and Line Side suitability If you do not use the APT Disconnect option select a disconnect switch rated for line side UL 98 having appropriate SCCR rating including any required overcurrent protection This may be more time consuming and expensive than anticipated The optional Disconnect Switch is fully engineered and almost certainly easier smaller and less expensive Audible Noise SPD background noise is negligible or non existent and does not restrict the location of installation Mounting Dimensions and Weight The XA amp XB series include enclosures and are intended for wall mounting The XR amp XW series are component SPDs intended for installation within other electrical gear already having enclosures See Table 2 Mechanical drawings are included in back of this manual page 12 TABLE 2 DIMENSIONS amp WEIGHTS P xa AMID n mm Weight Standard and w Opt 12 x 12 x 7 23 Ibs Disc Switch amp lt 300kA 805 x 305 x 177 104 kg With Opt Disc 16 14 x 6 5 Switch amp gt 300kA 406 x 356 x 165 14 14
62. ones se debe implementar un sistema en cascada o en etapas de supresi n en la acometida y aguas abajo ubicando adecuadamente Como sabemos y esperamos las fuentes de sobretensiones as como cargas sensibles tambi n deben tener protecci n por sobretensiones Para cargas electr nicas interconectadas cableado de datos los DPSs tambi n deben ser utilizados para proteger los dispositivos en cualquier terminal de los cables de datos interconectados Desembalaje e Inspecci n Preliminar Inspeccione completamente el empaque en cuanto a dafio o se ales de mal manejo Quite los materiales de empaque adem s inspeccione la unidad por cualquier dafio evidente ocasionados durante el transporte Si encuentra alg n da o ocasionado por el transporte o manejo inmediatamente presentar una reclamaci n a la compa a transportadora y env e una copia a APT Ambiente de almacenamiento Este DPS debe ser almacenado en un ambiente limpio y seco El rango de temperatura de almacenamiento es 40 c 40 f a 60 C 140 F Evite la exposici n a alta condensaci n PLANIFICACI N amp PRE INSTALACI N Ambiente de Operaci n La unidad est ndar est en un gabinete Tipo 1 12 3R 4 El Tipo 4X no met lico en policarbonato acero inoxidable y el Tipo 1 para montaje empotrado o caja de derivaci n est n disponibles como opciones Antes de la instalaci n asegure que el tipo de gabinete y la aplicaci n son las adecuadas respecto a NEMA 2
63. pared 12 x 12 60 600kA Fase 305 x 305 mm profundidad 6 152 mm 80 800kA Fase _ NEMA 1 uso interior admite cableado de paso 90 900kA Fase medidas 12 x 12 x 6 305 x 305 x 152 mm 1000kA Fase NEMA 4X de acero inoxidable medidas 12 x 12 x 6 305 x 305 x 152 mm Figura 1 Phase A BLK Phase BLK Phase C BLK Ground GRN SPLIT WYE DELTA B High DELTA amp HRG WYE SINGLE POLE CORNER GROUND 2 Hots 1 Neu 1 3 Hots 1 Neu 1 3 Hots B HIGH Hots 1 1 Hot 1 Neu 1 Gmd DELTA B grounded 1 Neu 1 Gmd 2 Hots 1 Figura 2 Informaci n Preventiva en cuanto un DPSs en sistemas sin puesta tierra EN PARALELO DE UN Cuidado Los sistemas sin puesta a tierra son intr nsecamente inestables y pueden DPS EN UN TABLERO producir excesivos altos voltajes de l nea a tierra durante ciertas condiciones de A Cargas ELECTRICO falla Durante estas condiciones de falla cualquier equipo el ctrico incluyendo un a Proteger DPS puede estar sometido voltajes que exceden sus par metros de dise o Esta informaci n se esta suministrando al usuario de modo que pueda tomar una decisi n con todo conocimiento antes de la instalaci n de cualquier equipo el ctrico Sobre un sistema de potencia sin puesta a tierra Protecci n contra sobretensiones en Cascada Para una optima protecci n contra sobretensi
64. r remote annunciation It requires a standalone 120V power source wall plug transformer and uses one set of Form C dry contacts The Remote Monitor can be configured to monitor several APT SPDs simultaneously Installation is detailed in a separate document Contact factory as appropriate Retro fit Into Existing Panel with No Available Breaker Positions These can be difficult with limited options Follow all applicable Codes Consider consolidating loads in a manner that might free breaker positions Aten foot tap rule in NEC 240 21 B 1 allows you to tap the bus as long as the tap conductors are rated at least 1096 of the ampacity of the panel This works well if the panel is about 600A or less Tap the bus run short 6 AWG leads to the SPD An SPD with a Disconnect Switch allows for easier SPD servicing in the future If the panel starts getting large 800A then the conductor size increases which may also become too large to fit into the SPD lugs or too cumbersome to work with In that case consider tapping the bus per NEC 240 21 B 1 Run appropriate Size conductors to a safety switch fused to 60A Mount the SPD immediately adjacent to the safety switch Connect SPD to the load side of the safety switch with 6 AWG Keep all leads as short as possible Install on Line Side by taking advantage of Type 1 SPD rating Consider an SPD with a Disconnect Switch n no win situations consider asking the Authority Having Juri
65. r to be connected as a 480V Delta In actuality the serving distribution system might be a 480Y 277V grounded Wye with or without a neutral pulled to the motor or MCC The system is still a 480Y 277V Wye even though the load is connected as a Delta A grounded Wye has a defined reference to ground i e neutral is bonded to ground Some Delta systems are ungrounded which have no reference to ground and are known to become unstable in certain situations Such instability can cause line to ground voltage fluctuations that may prematurely fail SPDs For this reason the NEC Article 285 has placed SPD restrictions on ungrounded systems As generalizations SPDs for ungrounded systems can be installed on grounded systems with a clamping performance penalty However SPDs for grounded systems installed on ungrounded systems are almost certainly destined for premature failure Call APT Tech Support at 800 237 4567 for further information Circuit Breaker and Disconnect Switch The XA amp XB family SPDs are tested and qualified as a Type 1SPD per UL 1449 Third Edition and 2008 NEC This SPD can be installed on the line side of the service overcurrent device per 2008 NEC Article 285 As a generalization it is more practical to install on load side of main overcurrent device for maintenance reasons When connected on load side of main disconnect we suggest connecting via a 60A circuit breaker The circuit breaker is the intended disconnect
66. revoltaje transitorio Este DPS incluye la protecci n interna por sobrecorriente y sobre temperatura para proteger contra condiciones de voltaje anormales No se requieren protecci n por sobrecorriente adicional para proteger este DPS Sin embargo se requiere la protecci n para la conexi n de los conductores en aplicaciones Tipo 2 o 4 Siga las normas aplicables Voltaje Nominal Antes de la instalaci n DPS verifique que ste tiene el mismo voltaje nominal que el sistema de distribuci n de potencia Compare el voltaje en la etiqueta del DPS o el n mero de modelo y asegure que la configuraci n del DPS concuerda con la de la fuente de potencia prevista Vea la Tabla 2 La persona que especifica o el usuario del dispositivo deben estar familiarizados con la configuraci n y el arreglo del sistema de distribuci n de potencia en el cual cualquier DPS ha de ser instalado La configuraci n de cualquier sistema de distribuci n de potencia est basada estrictamente en como los devanados secundarios del transformador que suministra la acometida principal o la carga son configurados Esto incluye si realmente los devanados del transformador son referidos a tierra a trav s de un conductor de puesta a tierra La configuraci n del sistema no est basada en como cualquier carga espec fica o equipo son unidos a un sistema de distribuci n de potencia en particular Ejemplo un Sistema de 480V Los DPSs deben ser instalados de acuerdo con el
67. sdiction AHJ for guidance Some AHJ s iE DRY CONTACT OPTION appreciate SPD safety benefits on smoke detectors medical equipment security equipment etc Similarly some AHJ s appreciate the financial distress of failed microelectronic loads Dry Contact Option Two sets of Form C dry contacts are included with the Dry Contact option Dry Contacts change state during inoperative conditions including loss of power Any status change can be monitored elsewhere via Dry Contacts A Terminal Block includes two sets of Normally Open N O and Normally Closed N C contacts Both sets of contacts operate the same This is shown in Figure 10 A typical application using a Normally Closed configuration would connect to one set of the N C and Common terminals During an inoperative condition the SPDs dry contact would change state from normally closed to open We generally suggest the Normally Closed configuration because it will detect a wiring defect such as cut wire s where N O will not Please note Dry Contacts are designed for low voltage or control signals only Maximum switching current is 5A Maximum switching voltage is 240V DC or AC Higher energy applications require additional relay implementation outside the SPD An optional Remote Monitor accessory is available to provide visual and audible status The Remote Monitor will consume one of the two sets of Dry Contacts DRY CONTACTS NO C NCNC C NO MAINT
68. sistema el ctrico no por una carga o el alambrado la conexi n del motor Por ejemplo suponga que un motor trif sico de 480V parece estar conectado en Delta de 480V En la pr ctica el sistema de distribuci n que lo alimenta podr a ser un 480Y 277V en Y conectada a tierra con o sin un neutro tomado del motor o CCM El sistema es todav a una Y 480Y 277V aun cuando la carga est conectada en Delta Un sistema Y aterrizado tiene una referencia definida a tierra p Ej el neutro est conectado a tierra Algunos sistemas en Delta est n sin conexi n a tierra los cuales no tiene ninguna referencia a tierra y sabemos que van a causar inestabilidad en ciertas situaciones Tal inestabilidad puede causar fluctuaciones en el voltaje l nea a tierra que pueden ocasionar la falla prematura de los DPSs Por esta raz n el NEC Art culo 285 ha establecido restricciones para los DPSs en sistemas sin puesta a tierra Generalmente los DPSs para sistemas sin puesta a tierra pueden ser instalados en sistemas conectados a tierra con un detrimento en el desempe o del voltaje remanente Sin embargo los DPSs para sistemas con conexi n a tierra instalados en sistemas sin puesta a tierra casi seguramente est n destinados a la falla prematura Llame a Soporte t cnico de APT en Estados Unidos al 727 535 6339 o al Distribuidor Autorizado de su Pa s Interruptor Circuit Breaker e Interruptor de Desconexi n TLa familia de DPSs XA y XB son probados y
69. stained Overvoltages as well as ungrounded generators and or unusual load transfer systems Abnormal N G Voltage Indicators This SPD include N G voltage indicators and a tattletale If the SPD detects excessive N G voltage it will blink the Red Service LED and cycle the Audible Alarm while Phase LEDs are Green If this occurs DEENERGIZE THE SPD IMMEDIATELY and FIX THE N G BONDING NOW Otherwise the SPD will fail Incorrectly bonded distribution systems are the number one killer of SPDs If the XO or N G bonding jumper is not installed the electrical system has no reference to ground It becomes an ungrounded system Please see previous section regarding SPDs on ungrounded systems Such systems are known to eventually produce abnormally high L G voltages SPDs will attempt to chase this system level overvoltage abnormality until the SPD fails This effect is Figure 11 accelerated on Wye systems where SPDs are designed for grounded systems SPDs for ungrounded systems generally have higher MCOV to allow for L G voltage fluctuations Failures of this nature are not defects in the SPDs workmanship or material This is an installation error not a warrantable situation A differential voltage circuit monitors neutral to ground voltage When N G voltage becomes excessive a shrink wrap covered resistor will heat After several minutes the shrink wrap will shrink around the resistor This diagnostic tool will not detect instanta
70. ta que una medici n de volt metro L T puede Por ejemplo el voltaje N T podr a leer porque neutro y la tierra est n en el mismo potencial puramente por la casualidad no porque ellos est n conectados Visualmente confirme la conexi n Tip La experiencia indica que los generadores con regulaci n deficiente pueden causar Sobrevoltajes sostenidos as como generadores sin puesta a tierra y o sistemas de transferencia de carga habituales Indicadores de Voltaje Anormales g de n Este DPS incluye indicadores de voltaje g de y un sopl n Si el DPS descubre el voltaje excesivo la g den esto parpadear el Servicio Rojo CONDUCIDO el ciclo la Alarma Audible mientras la Fase LEDs es Verde Si esto ocurre DEENERGIZE EL DPS INMEDIATAMENTE Y FIJAR LA VINCULACI N la g de n AHORA De otra manera el DPS fallar Sistemas de distribuci n incorrectamente consolidados son el asesino n mero uno de DPSs Si el XO o el puente de vinculaci n la g de n no son instalados el sistema el ctrico no tiene ninguna referencia para moler Esto se hace un sistema Figura 11 infundado Por favor mirar la secci n anterior mirar DPSS sobre Sistemas infundados Saben que tales sistemas tarde o temprano producen de modo anormal altos voltajes la g de DPSs intentar perseguir esta anormalidad de sobrevoltaje de nivel de Sistema hasta los suspensos de DPS Este efecto es acelerado sobre siste
71. ter Overcurrent Protection SPDs draw very little current under normal conditions and conduct for a brief duration upon encountering a transient surge current This SPD contains internal overcurrent and overtemperature protection to protect against abnormal voltage conditions Supplemental overcurrent protection is not required to protect this SPD However connecting conductors require protection in Type 2 or 4 applications Follow applicable codes Voltage Rating Before installing SPD verify that it has the same voltage rating as the power distribution system Compare the SPDs nameplate voltage or model number and ensure that SPD configuration matches the intended power source See Table 1 The specifier or the user of the device should be familiar with the configuration and arrangement of the power distribution system in which any SPD is to be installed The system configuration of any power distribution system is based strictly on how the secondary windings of the transformer supplying the service entrance main or load are configured This includes whether or not the transformer windings are referenced to earth via a grounding conductor The system configuration is not based on how any specific load or equipment is connected to a particular power distribution system 480V System Example SPDs should be installed per the electrical system not per a load or motor s wiring connection For example a 480V three phase motor might appea
72. uye dos juegos de Normalmente Abierto N O y Normalmente Cerrado N C contactos Ambos juegos de contactos manejan el mismo Muestran esto en la Figura 10 Un uso t pico que usa una configuraci n Normalmente Cerrada se unir a a un juego del N C y terminales Comunes Durante una condici n inoperante el DPSS el contacto seco cambiar a el estado de normalmente cerrado para abrir Generalmente sugerimos la configuraci n Normalmente Cerrada porque esto descubrir un defecto de alambrado como el cable s de corte donde N O no va a Por favor note Contactos Secos son dise ados para el voltaje bajo o controlan se ales s lo m ximo que cambia la corriente es elM ximo que cambia el voltaje es 240V la corriente continua o la corriente alterna usos de energ a M s altos requieren la puesta en pr ctica de relevo adicional fuera del TVSS Un accesorio de Monitor opcional Remoto est disponible para proporcionar el estado visual y audible El Monitor Remoto consumir uno de los dos juegos de Contactos Secos Opci n Complementaria de Monitoreo Remoto Un Monitor Remoto est disponible para la supervisi n remota Esto requiere una fuente de alimentaci n de 120V independiente un transformador de enchufe en la pared y utiliza el juego de contactos secos Forma El Monitor Remoto puede ser configurado para supervisar varios DPSs marca APT simult neamente La instalaci n es detallada en un documento aparte
73. x 12 x 7 356 x 305 x 178 16 x 14 x 7 406 x 356 x 178 12 x 12 x 7 5 305 x 305 x 191 16 x 14 x 7 5 406 x 356 x 191 12 x 12 x 6 305 x 305 x 152 16 x 14 x 6 406 x 356 x 152 XB in mm Standard 20 x 20 x 7 5 52 includes Disc Switch 508 x 508 x 191 23 6 kg 24 24 8 52 lbs non 610 x 610 x 203 23 6 kg 20 x 20 x 7 5 53 lbs 4X Stainless 508 x 508 x 191 24 kg 4X Non Metallic std gt 300 w disc 4X Stainless gt 300 w disc Pullbox amp Flush mount gt 300 w disc i 6 5 x 11 x 45 5 Ibs Standard 165 x 279 x 114 2 3 kg 20 x 20 x 6 43 Ibs Pullbox amp Flush mount 508 x 508 x 152 19 5 kg XR j With Opt Disc Switch 10 75 x 10 88 4 5 9 Ibs on alum backplane 273 x 276 x 114 4 1 kg H W D mm mr 9x 1i x 45 7 Ibs Standard 229 x 279 x 114 3 2 kg With Opt Disc Switch on alum backplane Service Clearance Service clearance is needed at the front of the unit 36 inches minimum is the required distance for clearance pursuant to the NEC 14 75 x 12 9 x 5 25 375 x 328 x 133 11 Ibs 5 kg Lead Lengths amp Maximizing SPD Performance SPDs must be located as close to the circuit as possible to minimize parasitic losses Surges are high current high frequency events that cause substantial voltage drops across conductors This hurts SPD performance Use the short
Download Pdf Manuals
Related Search
Related Contents
How to use NV Flash Utility? zoom-sur-27-Les-beaux parents DeLonghi BCO 320 coffee maker ピトン類 取扱説明書 Horn Cover Kit Instruction Sheet - Harley Prevención de riesgos laborales en comercio (folleto) - CHTJ-UGT Targus TBC005EU Betriebsanleitung Operating Instructions Dampferzeuger VEIT 2365 Copyright © All rights reserved.