1. Especificaci n Certificado VdS Certificado CE Important Read these instructions carefully before starting assembly Claims under warranty will be invalidated in the event of damage caused by non compliance with the installation instructions No liability is accepted for any resulting consequential loss or damage Safety information e NEVER connect the IQ8FCT directly to a 230 V AC mains power supply e Only operate in the specified ambient temperature range e Only qualified technicians who are fully familiar with all the associated hazards and the applicable legislation and regulations may perform maintenance and repair work on the call point e ThelQ8FCT may not be changed or modified in any way General The IQ8FCT Part No 804867 is designated for hazard alarms in dry workplaces not subject to explosion hazards The operation mode is displayed via the flashing green LED H Fig 4 System requirements Panel IQ8FCT Programming software tools 8000 System software IQ8Control FlexES control 1Q8FCT Operation from Version V3 08 from Version V1 15 from Version V6 09 Push up the keyhole cover A to insert the key Installation Flush mounting The IQ8FCT is installed on a conventional standard housing 55 60 mm The IQ8FCT is installed on a back box for surface mounting option or with a universal installation frame for wall mounting option The call point securely on a suitable
2. wall with a smooth surface e g with 2 screws length gt 40 mm and dowels S6 Fig 7 8 Surface mounting Opening Insert the key with the both tenons in the opening at the bottom of the housing Fig 2 to release the cover lock Lift up the bottom edge of the cover a little to release it and then remove it Closing Turn key lock anti clockwise until the left stop position Fig 6 Position the upper edge of the cover in the groove at the top of the base and then press the cover down until it locks into position Symbolism Open the housing and remove the transparent plastic cover D E by prising it out Insert the appropriate identification label from the front Align the cover and snap it back into place Fig 3 Plastic screen Turn key lock clockwise until the right stop position Fig 5 Insert screen aligned J in the front recess und move screen upwards by turning the key anti clockwise until the left stop position Fig 6 Terminals The terminals Fig 10 can be removed to simplify the installation The cable shield of the connection cable must be interconnected by using a single terminal block The back box option provides an integrated terminal for the shield connection Fig 7 Hinged cover Part No 704965 Option To increase the protection rating from IP 43 up to IP 55 The hinged cover M is fixed by the sideway dents N of the housing and may be sealed B if required Fig 2 9 Typical w
3. ESSER by Honeywell Manual de Instalaci n IQ8FCT Installation Instruction IQ8FCT Art Nr Part No 804867 Cambios t cnicos reservados Technical changes reserved 798826 02 2011 O GD 2011 Honeywell International Inc Movar GmbH Dieselstra e 2 D 41469 Neuss 10 0786 CPD 20792 Novar GmbH a Honeywell Company Dieselstrafe 2 D 41469 Neuss Internet www esser systems de E Mail info esser systems de CE e Observe la secuencia correcta en el cableado de lazo anal gico e Terminales 1 4 UL Entrada gt ULour Salida e Use cable de comunicaciones claramente identificado I Y St Y n x 2 x 0 8 mm o cable para alarma de incendio e La conexi n de la malla del cable debe realizarse al Terminal de tierra para evitar interferencias e Use junta de paso para cableado para evitar el acceso de humedad e Antes de conectar cargas inductivas o equipos de alarma aseg rese de si para cada equipo conectado se precisa el diodo suministrado Tipo 1N4007 Informaci n adicional y actualizada Las especificaciones se refieren a la fecha de creaci n del documento y pueden ser modificadas o variadas sobre la normativa aplicada o la informaci n facilitada Para informaci n actualizada y homologaciones consulte www esser systems de Revise el Cat logo de Protecci n contra Incendios para ver otros accesorios esserbusO y essernet son marcas registradas en Alemania e Observe the correct wir
4. casa como se ha indicado y quite la l mina transparente de pl stico D E presionando hacia afuera coloque la etiqueta de identificaci n adecuada desde la parte frontal coloque la cubierta y presione hasta su posici n Fig 3 L mina de Gire la llave en sentido horario hasta el tope derecho Fig 5 pl stico Inserte la l mina o cristal en su posici n J en el hueco frontal deslice la l mina hacia arriba girando la llave en sentido antihorario hasta su tope izquierdo Fig 6 Terminales Los terminales pueden extraerse para facilitar la instalaci n Fig 10 La pantalla del cable debe interconectarse en regleta aparte La caja de superficie tiene un terminal apropiado para conectar la pantalla opcional Fig 7 Cubierta Abatible Para aumentar el grado de protecci n de IP43 a IP55 Ref 704965 La cubierta abatible M se inserta en los orificios laterales N opcional de la carcasa y puede precintarse en caso necesario B Fig 2 9 Conexionado T pico Fig 10 El transponder IQ8FCT se conecta al lazo anal gico terminales 1 4 de los sistemas de control de incendios de centrales IQ8Control FlexES Aislador de cortocircuito Los aisladores de cortocircuito de lazo aseguran el funcionamiento de los equipos incluso en el caso de p rdida parcial debido a cortocircuito en el lazo Cuando sucede un cortocircuito los aisladores anterior y posterior al cortocircuito se abren aislando el tramo entre aisladore
5. deben Ilevar a cabo las operaciones de reparaci n y mantenimiento del equipo El IQ8FCT no debe ser alterado ni modificado General El m dulo IQ8FCT Ref 804867 est dise ado para alarmas t cnicas de dentro de lugares secos en reas sin riesgo de explosi n El funcionamiento se indica con el parpadeo del LED Verde H Fig 4 Requerimientos del Sistema Central IQ8FCT Programa Configuraci n tools Versi n de Software 8000 IQ8Control desde Versi n V3 08 FlexES control desde Versi n V1 15 1Q8FCT desde Versi n V6 09 Funcionamiento Suba la cubierta de llave A e inserte la llave Instalaci n Montaje El IQ8FCT puede instalarse sobre caja de mecanismo empotrado est ndar 55 60mm Montaje en El IQ8FCT se instala sobre caja de superficie opcional o con Superficie marco de montaje universal opcional Instale el IQ8FCT de forma segura en una pared apropiada sobre una superficie lisa ej con 2 tornillos Long gt 40 mm y tacos adecuados S6 Fig 7 8 Apertura Inserte la llave por sus dos patillas en los orificios inferiores de la cubierta abajo Presione hacia arriba para liberar la tapa Fig 2 Tire desde abajo hacia fuera hasta retirar la tapa Cierre Gire la llave en sentido antihorario hasta su tope izquierdo Fig 6 Coloque la leng eta superior de la cubierta sobre las ranuras del m dulo del pulsador y presione hasta encajar la cubierta en su posici n S mbolo Abra la car
6. g screen i i Apertura caja sellado Open the housing seal gt o Fig 3 Etiqueta de identificaci n Fig 3 Identification label Fig 6 Colocar l mina Fig 6 Replace screen 132 0 gt O E gt Fig 7 Caja de superficie Ref 704985 Fig 7 Back box for surface mounting Part No 704985 Sistema System IQ8Control FlexES control Fig 8 Marco de montaje empotrado Ref 704967 Fig 8 Universal installation frame incl cover Part No 704967 Fig 9 Cubierta frontal junta y prensaestopas para cable 1 4 Ref 704965 Fig 9 Hinged cover incl washers Part No 704965 and cable entries 1 4 Contacto contact 804867 804867 804867 Observe la fuerza de a
7. ing sequence for the loop e Terminals 1 4 ULi Input UL our Output e Use designated communication cable l Y St Y n x 2 x 0 8 mm or fire alarm cable e Connection of the cable shield to the ground terminal protects the signal cables against interference e Install inlying cable with a dripping bend to protect the device from dampness e Before connecting inductive loads and alarm devices ensure for each connected device if the supplied diode type 1N4007 is required for a proper wiring 1 Additional and updated Informations The product specification relate to the date of issue and may differ due to modifications and or amended Standards and Regulations from the given information For updated information and declaration of conformity refer to www esser systems de Refer to the Fire Alarm System Catalogue for additional accessories esserbus and essernet are registered trademarks in Germany Importante Lea detenidamente estas instrucciones antes de instalar Se declina toda responsabilidad y garant a sobre da os derivados por no seguir estas instrucciones de instalaci n No se aceptar responsabilidad alguna por cualquier p rdida o da o Informaci n de seguridad NUNCA conecte el IQ8FCT directamente a 220Vac Instale en ambientes dentro el rango de temperatura especificado Solo t cnicos cualificados que est n familiarizados con los riesgos espec ficos y las normativas correspondientes
8. iring Fig 10 The IQ8FCT are connected terminals 1 4 to the loop of the System 1Q8Control FlexES control fire alarm control panel Zone isolator The zone isolators ensure that the system continues to function even if a segment of the loop circuit fails due to a short circuit When a short circuit occurs the zone isolators before and after the short circuit open disconnecting the section of the loop between the isolators Simple wire breaks do not affect the functionality of the loop circuit Contact The total cable length of the external contact should not exceed 500 meters wiring example Fig 11 If no external contact is connected the 10 KOhm 5 terminating resistor must be installed directly to terminals 7 8 Fig 10 Contact response Operating mode The dry contacts of a relay are available on terminals 5 6 Fig 10 The relay is operated as NO contact by factory settings The relay output can be programmed as a control zone in the customer data of the fire alarm control panel and the NC normally closed operating mode must be programmed with the programming software tools 8000 Maximum contact rating 30 VWDC 1Aor30VAC 1A Specifications 8 V DC to 42 V DC approx 45 yA O 19 V DC Power supply Quiescent current Alarm current approx 9 mA pulsed No of call points max 127 IQ8FCT per loop Alarm indicator red LED Operation indicator green LED Connection terminals max 2 5 mm AWG 26 14 Application tem
9. perature 20 C to 70 C Storage temperature 30 C to 75 C Protection rating IP 43 in housing IP 55 with option Housing PC ASA plastic Colour grey similar RAL 7035 Weight approx 110g Housing dimensions w x h x d 88 x 88 x 21 mm Dimensions with back box 88 x 88 x 57 mm EN 54 17 2005 18 2005 G 20138 0786 CPD 20792 Specification VdS approval CE certificate CE Opciones Etiquetas transparentes con letra blanca 10 Uds Tapa transparente frontal M y juntas para aumentar el grado de protecci n de IP 43 hasta IP 55 Llaves de recambio 10 Uds Marco de montaje empotrado rojo blanco 132 x 132 x 8 mm Caja de superficie de color gris similar a RAL 7035 Montage Mounting Fig 1 Dimensiones en mm Fig 1 Dimensions in mm Kuniisiofachebe Plastic screen o Top li iJ WM Fig 4 Indicaci n de alarma y LED lamina de pl stico Fig 4 Alarm indicator and LED plastic screen Art Nr 704961 704965 704966 704967 704985 Label transparent with whit printing differing from standard icons 10 pieces Options Hinged cover M and washers to increase the protection rating from IP 43 up to IP 55 Replacement key 10 pieces Frame incl cover red white 132 x 132 x 8 mm Back box for surface mounting grey similar to RAL 7035 Part No 704961 704965 704966 704967 704985 Fig 2 Fig 2 Fig 5 Sustituir l mina Fig 5 Removin
10. priete de los pe SN E A Sa SN terminales de conexi n 0 4 Nm M x ej ojoj ejoj o o o ejeje eo ejeje e alo eo ol 5 EN BEN PEN PEN PE TETE E AAA jil l Observe permitted torque Caos Gasbesss DIEIIS max 0 4 Nm of the terminals AS E OO e 0 INOIO DA ar uo Ss DL 5 5 lt Ago SGEE J saj 3333 gej 3333 ael jasa 341 l5 s5 gt 37 s73 3g 2593 n z N s Y ES Ed Us o o gt lt gt lt O e Pa L 3 e pS Ring Modul Loop Module T RA A pra NECE E pd contacto reposo a T UE normal mode Mins erre rr rar ua a ET ios Mr es contacto activado HE iA active mode Fig 10 Cableado de lazo anal gico y rel Fig 10 Wiring loop and relay Fig 11 Ejemplo de cableado Fig 11 Wiring example
11. s Un solo corte o cortocircuito no afecta al funcionamiento del lazo Entrada de contacto La longitud total del la l nea de entrada no puede exceder los 500 metros ejemplo de cableado Fig 11 Si no se ha conectado contacto externo debe instalarse una resistencia final de l nea de 10 KOhm 5 entre los terminales 7 8 Fig 10 Rel Funcionamiento Los terminales del rel seco se encuentran entre los terminales 5 6 Fig 10 El rel por defecto funciona como NA Normalmente Abierto La activaci n de la salida de rel puede configurarse en la programaci n del panel de control y modo de funcionamiento NC Normalmente Cerrado del contacto debe configurarse con el software de programaci n tools 8000 Consumo m ximo por el contacto 30 Vcc 1A030Vac 1A Caracter sticas T cnicas 8 Vdc a 42 Vdc 45 uA aprox 19 Vdc Alimentaci n Consumo reposo 19 V DC 9 mA aprox pulsante m x 127 IQ8FCT por lazo LED rojo LED verde m x 2 5 mm AWG 26 14 20 C a 70 C 30 C a 75 C IP 43 en caja Consumo alarma N mero Equipos Indicaci n alarma Indicador funcionamiento Terminales Temperatura trabajo Temperatura almacenamiento Grado de protecci n IP 55 con opci n Caja PC ASA pl stico Color Gris similar RAL 7035 Peso 110 g aprox Dimensiones a x h x f 88 x 88 x 21 mm 88 x 88 x 57 mm EN 54 17 2005 18 2005 G 20138 0786 CPD 20792 Diemnansiones con caja sup

Download Pdf Manuals

image

Related Search

Related Contents

  Samsung WA11J5710SG/HC دليل المستخدم    digital, variable, high voltage, insulation test meter.  Manual de introducción a la plataforma en línea del  Dynaflex Elastomeric Flexible Couplings LCR User's Manual  =ーNAX ==田野「 tuiーet  Datamax I-4208 Printer User Manual  Veranda 73024515 Installation Guide  Système RackCooler™ de Liebert  