1. 20 30 40 50 60 70 80 90 100 P 698 Relativ und Differenz Druckmodul Relative and differential pressure module Module de pression relative et diff rentielle 112669 Edition 01 2008 Ja T o sal s3 Je i 5 A npe sun um ww pa Poweron F4 m m poz3 D7 DS Rp1 Dan Dan A au Ba i ooo loool loo 4 5 6 78 9 10 SP2 SP l j external voltage English Francais Caution IN device is to be installed and removed by technicians only The applicable certified national safety regulations for the operation of pressure measuring devices shall be observed Devices in operation run on mains voltage depending on execution Please note that terminals 3 to 8 can still be under power even when power supply is disconnected or with low vo
2. 3 fs for linear versions and 40 100 fs for version with square root extraction The zero point and the end value have been adjusted in the factory and only need to be changed in exceptional cases Readjustment influences different sections of the pressure module such as output signal display and switching point Adjustment of limit values With display Press button S3 for SP1 or S4 for SP2 continuously The effective value os shown on the display Adjust the requested value with the potentiometer Rp3 for SP1 or Rp4 for SP2 Without display The limit values can be adjusted with the reference voltage on X4 Press button S3 for SP1 or S4 for SP2 continuosly and measure the voltage at the measuring point X4 Adjust the requested value with the potentiometer Rp3 for SP1 or Rp4 for SP2 Pmin Pmax gt 0 0 2 0 VDC Example 0 50 mbar Switching point 35 mbar corresponds to a voltage of 1 4 VDC Switching state The LED s show the actual switching state The led is lit in active switching state For SP1 D5 and D23 For SP2 D7 and D24 Connectors Q Z PL FF P2 OUT SP2 SP1 IN Attention AN Le montage et d montage de l appareil doivent tre r alis s exclusivement par un sp cialiste Les prescriptions de s curit en vigueur dans le pays doivent tre respect es lors de l utilisation d appareils de mesure de pres sion Pour certaines versions lors du fonctionnement
3. l appareil se trouve sous tension secteur est noter que lors de la coupure de la tension d alimentation ou pour des versions basse tension une tension secteur source externe peut se trouver sur les bornes 3 et 8 SP1 et SP2 Il ne doit pas tre r alis de liaison galvanique entre la sortie analogue et la tension d alimentation Raccord de pression P1 Manchon de raccordement en haut gauche pression plus lev e P2 Manchon de raccordement en bas droite pression plus basse Surpression max admissible selon plaque signal tique Embout pour tuyau Pour flexible de diam tre interne 4 7 mm Raccord rapide Pour flexible de diam tre interne 2 9 mm Connexions lectriques Valeurs selon plaque signal tique Sortie Interrupteur de valeurs limites SP2 Alimentation 1 OUT 3 Ligne d alimentation COM 9 IN 2 OUT 4 Contact de repos NC 10 IN 5 Contact de travail NO Interrupteur de valeurs limites SP1 6 Ligne d alimentation COM 7 Contact de repos NC 8 Contact de travail NO Choix par l utilisateur du type de signal de sortie Les appareils sont r gl s en usine avec le signal tension ou courant souhait et pour la position de montage comman d e Ils quittent ainsi l usine en tant pr ts l emploi Le si gnal de sortie peut tre s lectionn posteriori au moyen du commutateur DIP S5 Commutateur DIP S5 Signal de sortie tension 0 10V Commutateurs 1
4. Deutsch 1 2 3 4 56 7 8 1l 0 100 mbar DCE max 300 mbar 10T60 IP64 IN 230 V 50 Hz 4 VA 698 11203000100 OUT 0 10 V gt 2 kOhm 07 03 118 0633 74 pE our P2 spz sP1 in 7 2 11 12 3 1314 Leistungsschild 1 Artikelnummer 2 Ausgang Speisung Druckbereich Einseitig zul ssige berlast Maximale Leistungsaufnahme Umgebungstemperatur 10 60 C 9 0 O U1 WW Doppelte Isolierung CE konform 10 Schutzart 11 Druckanschluss P1 h here Druck P2 tieferer Druck 12 Grenzwertschalter 230V 6A Wechselkontakt 13 B rde 14 Produktionsdatum JJ MM Achtung IN Ein und Ausbau des Ger tes ist nur von Fachperso nal vorzunehmen Es sind die geltenden l nderspe zifischen harmonisierten Sicherheitsbestimmungen f r den Be trieb von Druckmessger ten einzuhalten Das Ger t steht im Betrieb je nach Ausf hrung unter Netzspannung Zu beachten ist zudem dass auch bei unterbrochener Speisespannung oder bei Kleinspannungsaus f hrungen Netzspannung Fremdspannung an den An schlussklemmen 3 bis 8 anliegen kann SP1 und SP2 Bei einer Festinstallation muss der Stromkreis mit 10A tr ge abgesichert werden Zus tzlich ist ein gekennzeichneter und gut erreichbarer Schalter f r die Unterbrechung der Stromzu fuhr in der N he des Drucksensors anzubringen Es darf keine galvanische Verbindung zwische
5. et 2 sur ON Commutateurs 3 et 4 sur OFF ON A A 3 4 Signal de sortie courant 0 20 mA Commutateur 3 sur ON Commutateurs 1 2 et 4 sur OFF ON 1 2 3 4 Signal de sortie courant 4 20 mA Commutateurs 3 et 4 sur ON Commutateurs 1 et 2 sur OFF ON 1 2 3 4 Ajustement par le client R glage du point z ro Le point z ro s ajuste avec le potentiom tre Rp1 3 E M R glage de la valeur de fin d chelle Apr s r glage du point z ro la valeur de fin d chelle peut tre ajust e au moyen du potentiom tre RP2 en fonction de a pression en entr e 3 pour la version lin aire et 40 100 pour la Version extraction de racine R glage de la valeur finale R glage de la valeur finale apr s r glage du point z ro la valeur finale de la plage de mesure peut tre align e avec le potentiom tre P2 la pression admise correspondante FR Un ajustage aura un effet sur l ensemble du module de pres sion Le signal de sortie l affichage et les seuils de commu ation seront influenc s Point z ro et valeur finale sont r gl s en usine et ne doivent tre qu exceptionnellement r ajust s R glage des seuils de commutation Avec affichage Appuyer sur la touche S3 pour SP1 ou sur S4 pour SP2 La valeur pr c demment r gl e appara t Au moyen du poten tiom tre Rp3 pour SP1 ou Rp4 pour SP2 r gler la valeur de seuil souhait e Sans affichage Les seuils de com
6. ltage executions SP1 and SP2 Ohmic contacts between analogue output and power supply are not allowed Pressure connection P1 Connection branch top left higher pressure P2 Connection branch down right lower pressure max admissible overpressure acc to rating plate Hose connector For tube with internal diameter 4 7 mm Quick fitting For tube with internal diameter 2 9 mm Electrical connections Values acc to rating plate Output Limit value switch SP2 Power supply 1 OUT 3 Feeder COM 9 IN 2OUT 4 NC contact 10 IN 5 NO contact Limit value switch SP1 6 Feeder COM 7 NC contact 8 NO contact Customer specific choice of output signal Requested power and voltage output signal in the requested mounting position are factory set The product leaves the factory ready for connection In order to change the output signal use the DIP switch S5 DIP Switch S5 Voltage output 0 10V Switch 1 and 2 ON Switch 3 and 4 OFF ON a 2 3 4 ON 3 2 3 4 ON 1 2 3 4 Current output 0 20 mA Switch 3 ON Switch 1 2 and 4 OFF Current output 4 20 mA Switch 3 and 4 ON Switch 1 and 2 OFF Adjustment by customer Zero point adjustment The zero point can be adjusted with potentiometer Rp1 3 fs End value adjustment After zero point has been adjusted the measurement range end value can be set with potentiometer Rp2 by applying the appropriate pressure
7. mutation peuvent tre lus par la tension de r f rence au bornes X4 Appuyer sur la touche S3 pour SP1 ou sur S4 pour SP2 et mesurer la tension sur les bornes X4 Au moyen du potentiom tre Rp3 pour SP1 ou Rp4 pour SP2 r gler la valeur de seuil souhait e Pmin Pmax gt 0 0 2 0 VDC Exemple pour une amp tendue de mesure de 0 50 mbar Un seuil de 35 mbar correspond une tension de 1 4 VDC Etat de commutation Les LEDs indiquent l tat de commutation effectif Dans l tat actif la LED correspondante est allum e Pour SP1 D5 et D23 Pour SP2 D7 et D24 Bornes Q 6 7 8 910 Mo P2 OUT SP2 SP1 IN 1 2 3 4 56 78910 _ 698 11203000100 eig 10T60 IP64 0 100 mbar max 300 mbar IN 230 V 50 Hz 4 VA OUT 0 10 V gt 2 kOhm 07 03 O 118 0833 R73 Em our P sp sp1 in 2 11 12 3 1314 Label W SON E s Se 2 3 14 2 3 4 5 6 7 8 9 1 1 0 1 12 13 14 Article number Output Power supply Pressure range Tolerable over load on one side ax power consumption Ambient temperature 10 60 C Double isolation CE conformity Protection standard Pressure connection P1 higher pressure P2 lower pressure Limit value switch 230V 6A Changeover switch Load Production date YY MM Circuit extraction de racine C
8. n Analogaus gang und Speisung herstellt werden Druckanschluss P1 Anschlussstutzen oben links h herer Druck P2 Anschlussstutzen unten rechts tieferer Druck max zul ssiger berdruck gem ss Leistungsschild Schlauchstutzen F r Schlauch mit Innendurchmesser 4 7 mm Schnellverschraubung F r Schlauch mit Innendurchmesser 2 9 mm Elektrische Anschl sse Werte gem ss Leistungsschild Ausgang Grenzwertschalter SP2 Speisung 1 OUT 3 Zuleitung COM 9 IN 2 OUT 4 Ruhekontakt ffner 10 IN 5 Arbeitskontakt Schliesser Grenzwertschalter SP1 6 Zuleitung COM 7 Ruhekontakt ffner 8 Arbeitskontakt Schliesser Kundenseitige Wahl des Ausgangssignals Die Ger te werden werkseitig auf das gew nschte Strom oder Spannungsausgangssignal und in der bestellten Einbaulage ab geglichen Sie verlassen somit das Werk anschlussfertig Das Ausgangssignal kann nachtr glich mittels DIP Schalter S5 um gestellt werden DIP Schalter S5 Spannungsausgang 0 10V Schalter 1 und 2 auf ON Schalter 3 und 4 auf OFF ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 Stromausgang 0 20 mA Schalter 3 auf ON Schalter 1 2 und 4 auf OFF Stromausgang 4 20 mA Schalter 3 und 4 auf ON Schalter 1 und 2 auf OFF Kundenseitiger Abgleich Nullpunkteinstellung Mit Potentiometer Rp1 kann der Nullpunkt justiert werden 3 FS Endwerteinstellung Mit Potentiometer Rp2 kann nach erfolgte
9. ode article Sortie Alimentation Plage de pression Surpression unilat rale admissible Consommation maximale de courant Temp rature ambiante 10 60 C Double isolation Conforme CE ndice de protection Raccord de pression P1 pressio la plus base P2 pression la plus elev e nterrupteur de valeurs limites 230V 6A Contact inverseur Charge Date de production AA MM
10. r Nullpunkteinstel lung mit entsprechend beaufschlagtem Druck der Messbe reichsendwert abgeglichen werden 3 FS bei der linearen Version und 40 100 FS bei der radizierten Version Nullpunkt und Endwert sind werkseitig justiert und m ssen nur in Ausnahmef llen nachgeregelt werden Eine Nachrege lung hat Einfluss auf das gesamte Druckmodul Es werden da mit das Ausgangssignal die Anzeige und die Schaltpunkte beeinflusst Einstellen der Grenzwerte it Display Taster S3 f r SP1 oder S4 f r SP2 gedr ckt halten Der aktuelle Wert wird auf dem Display angezeigt Mittels des Potentiometers Rp3 f r SP1 oder Rp4 f r SP2 den ge w nschten Wert einstellen Ohne Display Die Grenzwerte k nnen ber die Referenzspannung an X4 eingestellt werden Taster S3 f r SP1 oder S4 f r SP2 gedr ckt halten und am esspunkt X4 die Spannung messen Mittels des Potentiome ers Rp3 f r SP1 oder Rp4 f r SP2 den gew nschten Wert einstellen Pmin Pmax gt 0 0 2 0 VDC Beispiel 0 50 mbar Schaltpunkt bei 35 mbar entspricht einer Spannung von 1 4 VDC Schaltzustand Die LEDs zeigen den aktuellen Schaltzustand im aktiven Zustand leuchtet das entsprechende LED F r SP1 D5 und D23 F r SP2 D7 und D24 Anschlussklemmen Radizierschaltung Square root extraction circuit Circuit extraction de racine Out 100 90 80 70 60 50 40 30 20 Out 100 e 2