1. Ortsfeste Bleibatterien Stationary lead acid batteries Accumulateurs au plomb stationnaires Bater as estacionarias de plomo cido Batterie stazionarie al piombo acido Montageanleitung Installation instruction Instructions de montage Instrucciones de Instalaci n Istruzioni di installazione es 2 3 4 5 GNB INDUSTRIAL POWER 2 Montageanweisung fur station re Batterien Batterien Gestelle Schr nke e Gebrauchsanweisung beachten und am Ladeplatz sichtbar anbringen e Arbeiten an Batterien nur nach Unterweisung durch Fachpersonal Rauchen verboten Explosions und Brandgefahr DIN EN 50110 1 beachten 08 Keine offene Flamme Glut oder Funken in die N he der Batterie bringen da Bei Arbeiten an Batterien Schutzbrille und Schutzkleidung tragen Die Unfallverh tungsvorschriften sowie DIN EN 50 272 2 e S urespritzer im Auge oder auf der Haut mit viel klarem Wasser aus bzw ab spUlen Danach unverz glich einen Arzt aufsuchen e Kleidung mit Wasser auswaschen Elektrolyt ist stark tzend Vorsichtig behandeln Explosions und Brandgefahr Kurzschl sse vermeiden Elektrostatische Auf bzw Entladungen Funken sind zu vermeiden Blockbatterien Zellen haben ein hohes Gewicht Auf sichere Aufstellung achten Nur geeignete Transportmittel verwenden Block Zellengef Be sind empfindlich gegen mechanische Besch digungen Niemals Blockbatterien Zellen an den P
2. 4 Marcado CE Las bater as con una tensi n nominal a partir de 75 V requieren una declaraci n de conformidad CE de acuerdo con la directiva de baja tensi n 2006 95 EC sustituye a la 73 23 EEC lo que significa que se aplica el marcado CE a la bater a La empresa que instala la bater a es la responsable de suministrar la declaraci n y apli car el marcado CE ADVERTENCIA Antes de conectar la bater a al cargador aseg rese de que todo el trabajo de instala ci n se haya realizado debidamente Dibujo N mero de soportes 4 OPzV 200 6OPzV 300 3 piezas 5 OPzV 350 7OPzV 490 3 piezas 6 OPzV 600 12 OPzV 1200 4 piezas 15 OPzV 1500 24 OPzV 3000 4 piezas 40 mm min larguero 50 mm m x 10 Istruzioni di installazione GNB InDusTRIAL POWER per batterie stazionarie al piombo acido Batterie Scaffali Armadi e Seguire queste istruzioni e tenerle posizionate vicino alla batteria come riferimento futuro e lavori sulle batterie devono essere eseguiti soltanto da personale qualificato Non Fumare e Rischio di esplosione e di incendio Non usare fiamme libere o altre fonti di innesco Durante le operazioni sulle batterie indossare occhiali ed indumenti protettivi Osservare le norme di sicurezza EN 50 272 2 EN 50110 1 e le normative nazionali vigenti in materia di prevenzione degli infortuni e Gli schizzi di acido sulla pelle o negli occhi devono essere risciacquati immediatamente con molta acq
3. polari dad 2 4 Coloque las bater as o elementos en la estante r a unas tras otras asegurando su correcta polaridad Para elementos grandes es til empe zar instalando los elementos en el centro de la estanter a Alinear las bater as o elementos en para lelo La distancia entre las bater as o elementos deber ser aproximadamente de 10 mm como m nimo 5 mm Si fuese necesario limpiar las superficies de contacto de los terminales y conectores Colocar y atornillar los conectores entre monoblocs o elementos usando una llave dinamom trica aislada para el valor del par de apriete correcto compruebe las instruc ciones de funcionamiento de la bater a En su caso tenga en cuenta las instrucciones especiales con respecto a los conectores entre elementos Ej conectores soldados Coloque los conectores suministrados entre elementos filas o alturas y atorn llelos observando el valor del par de apriete Evite cortocircuitos Utilice cables de al menos 3 kv de tensi n disruptiva o manten ga una distancia a rea de aprox 10 mm entre los cables y piezas conductoras o aplique un aislamiento adicional a los conectores Evite aplicar fuerzas mec nicas en los polos de la bater a elementos Cuando corresponda retire los tapones de transporte y sustituya por otros operativos Compruebe el nivel de electrolito Tenga en cuenta las instrucciones de uso funcio namiento Mida la tensi n total tensi n nomin
4. Blockbatterien auf einwandfreien Zustand berpr fen visuell Polarit t 2 4 Zellen bzw Blockbatterien nacheinander pol richtig auf das Gestell stellen Bei groBen Zellen ist es zweckm ig mit der Zellenmontage in der Gestellmitte zu beginnen Zellen bzw Blockbatterien parallel ausrich ten Abstand zwischen Zellen oder Block batterien ca 10 mm mindestens jedoch 5 mm Falls erforderlich Kontaktfl chen der Pole und Verbinder s ubern Zellen bzw Blockverbinder auflegen und mit isoliertem Drehmomentschl ssel ver schrauben richtige Drehmomente laut Angaben der Batteriegebrauchsanweisung beachten Gegebenenfalls sind besondere Hinweise f r die Zellenverbinder zu beach ten z B SchweiBverbinder Mitgelieferte Reihen Stufen Etagen Verbinder auflegen und unter Beachtung der vorgegeben Drehmomente verschrau ben Dabei ist auf kurzschlussfeste Verlegung zu achten Das heiBt es sind Leitungsmateria lien mit mindestens 3 kV Durchschlagfestig keit zu verwenden oder es ist ein Luftabstand zwischen Leitungen und elek trisch leitf higen Teilen von ca 10 mm ein zuhalten oder es muss eine zus tzliche Isolation der Verbinder erfolgen Eine 3 3 1 mechanische Belastung der Zellen Batterie Pole ist zu vermeiden Alle Endableiter von Batterien welche Batterien untereinander mit Lasten Trennern oder Sicherungen ver binden m ssen kurzschlusssicher verlegt werden Transportstop
5. cerca de la bater a para futuras referencias e Los trabajos en las bater as solo deber n llevarse a cabo por personal cualificado Prohibido fumar Peligro de incendio e explosi n EN 50110 1 No debe usar ninguna llama u otras fuentes de ignici n Durante cualquier manipulaci n de las bater as deber usar gafas y ropa de protecci n Observe atentamente las normativas de seguridad as como las normas EN 50 272 2 En caso de contacto del cido con los ojos o con la piel deber lavarse con abundante agua limpia inmediatamente A continuaci n acuda a un m dico e En caso de salpicaduras de cido en la ropa lavar con agua e Peligro de incendio e explosi n evite cortocircuitos e Evite cargas y descargas electroest ticas chispas El electrolito es fuertemente corrosivo En condiciones normales de trabajo el contacto con electrolito es imposible Si el recipiente del elemento o del bloc est da ado no toque el electrolito expuesto es corrosivo Los elementos blocs pesan mucho Aseg rese que est n instalados de forma segura Emplee solo medios apropiados para su transporte Los recipientes del elemento bloc son sensibles al da o mec nico Maneje con cuidado No levante ni tire de los elementos bloques por los polos Tensi n el ctrica peligrosa A Atenci n Las partes met licas de la bater a tienen tensi n constantemente por tanto no deposite herramient
6. ces mesures peuvent tre ex cut es seulement apr s la mise en service Les tensions de repos des l ments blocs ne doivent pas varier entre elles de plus que les valeurs autoris es suivant le tableau ci dessous Gamme de Max tol rance V produits plomb ouvert tanche El ments 2V 0 020 0 030 AV accumulateurs 0 028 0 042 monoblocs 6V accumulateurs 0 035 0 052 monoblocs 8V accumulateurs 0 040 0 060 monoblocs 10V accumulateurs 0 045 0 067 monoblocs 12V accumulateurs 0 049 0 073 monoblocs Demander conseil au fabricant lors d carts plus importants 2 Supports 2 1 La mise en place des supports dans les locaux doit correspondre aux dessins de montage Si un dessin de montage manque il convient de respecter les distances minimales suivantes vers le mur 100 mm tout autour en r f rence aux l ments ou accumulateurs monoblocs 50 mm pour les supports 1 5 m tre lors d une tension nominale ou d une tension partielle gt 120 V entre des raccords ou connecteurs non isol s et les composants reli s la terre par exemple les conduites d eau ou entre les p les ter minaux de l accumulateur Pendant le mon tage des accumulateurs il faut s assurer que la norme EN 50272 2 est respect e par exemple recouvrir les pi ces lectri quement conductrices de tapis isolants pour les largeurs de couloirs 1 5 x la largeur d l ment profondeur de monta
7. ed essere marcato di conseguenza Fare attenzione ai seguenti punti e Capacit di carico e natura del pavimento sia nei corridoi interessati al trasporto che nel locale batterie e Resistenza all elettrolito dell area prevista per l installazione della batteria Nessuna fonte di accensione fiamme vive sorgenti incandescenti interruttori elettrici deve essere posta a distanza ravvicinata dalle batterie e Ventilazione L installazione della batteria dovrebbe avvenire in modo tale che la differenza di temperatura tra le singole celle blocchi non sia superiore a 10 K per batterie acido libero e 3 K per batterie a regolate a valvola Per fare in modo che non ci siano problemi nell installazione coordinare pre ventivamente le modalit di installazione con il personale che si trova ad operare nella medesi ma area 1 2 Controllare al ricevimento della merce che i componenti siano completi ed integri Se neces sario pulire tutte le parti prima dell installazione 1 3 Seguire le istruzioni presenti nella documenta zione fornita es disegni per l installazione scaf fali ed armadi Far riferimento alle istruzioni d uso per la coppia di serraggio da applicare 1 4 Prima di rimuovere le vecchie batterie assicurar si sempre che tutti i collegamenti elettrici risulti no scollegati interruttori del carico sezionatori fusibili isolamenti Questo lavoro deve essere fatto solo da personale qual
8. mit anderen im gleichen Raum besch ftigten Personen erforderlich 1 2 Lieferumfang auf Vollst ndigkeit und eventuelle Besch digungen berpr fen Alle Teile falls erforderlich vor Zusammenbau s ubern 1 3 Mitgelieferte Dokumentationen befolgen z B Batterie Gestell Schrank Aufbauzeichnung F r anzuwendende Drehmomente siehe ent sprechende Gebrauchsanweisung 1 4 Bei der Erneuerung ist sicherzustellen dass vor Beginn der Demontage der alten Batterie die Zuleitungen freigeschaltet wurden Lasttrenner Sicherungen Schalter Dieses hat durch schalt berechtigtes Personal zu erfolgen GNB InDusTRIAL POWER ACHTUNG Keine eigenm chtigen Schaltungen durchf hren 1 5 Ruhespannungsmessungen der einzelnen Zel len bzw Blockbatterien Dabei ist gleichzeitig auf die richtige Polarit t zu achten Bei ungef ll ten und geladenen Batterien geschlossen k n nen diese Messungen erst nach der Inbetrieb setzung durchgef hrt werden Die Ruhespannungen der einzelnen Zellen Bl cke sollen untereinander nicht mehr als um die in der nachfolgenden Tabelle aufgelisteten Plus Minus Toleranzen Richtwerte vom gemessenen Mittelwert abweichen Max Toleranz V Einheit Geschlossene Verschlossene 2V Zelle 0 020 0 030 4V Block 0 028 0 042 6V Block 0 035 0 052 8V Block 0 040 0 060 10V Block 0 045 0 067 12V Block 0 049 0 073 Bei gr Beren als in der Tabelle gezeigten Abwei
9. POWER accumulateurs supports armoires e Suivez ces instructions et conservez les proximit de la batterie pour consultation ult rieure Seul du personnel qualifi pourra intervenir sur la batterie Interdiction de fumer Risque d explosion et d incendie 08 Ne pas utiliser de flamme nue ni d autres sources d inflammation Lors d interventions sur les batteries porter des lunettes et des v tements de protection En cas de connexions et d connexions d accumulateurs respecter les proc dures d finies par UTE C 18 510 port cran facial Respecter les r gles de pr vention des accidents ainsi que les normes NF EN 50272 2 NF EN 50110 1 et NF C15 100 e Toute projection d acide sur la peau ou les yeux doit tre aussit t abondamment rinc e l eau claire Consulter imm diatement un m decin Laver les V tements l eau a gt bbB e Attention Risque d incendie d explosion ou de br lures Ne pas d monter chauffer au del de 60 C ou jeter au feu Eviter les courts circuits s Eviter les tincelles les charges et d charges lectrostatiques L electrolyte est fortement corrosif Dans des conditions normales de fonctionnement le contact direct avec l lectrolyte est impossible Si le monobloc est endommag ne pas toucher l lectrolyte qui est tr s corrosif Les batteries ou les l ments sont lourds Toujours utiliser un mat riel de manutention ad quat pour le transp
10. TTENZIONE prima di connettere la batteria al raddrizzato re assicurarsi che tutti i lavori di installazione siano stati dovutamente completati ve applicare ulteriori isolamenti elettrici ai monoblocchi connettori Evitare sforzi meccanici sui poli Disegno Numero di supporti 4 OPzV 200 6OPzV 300 3 pezzi 5 OPZV 350 7OPzV 490 3 pezzi 6OPzV 600 12 OPzV 1200 4 pezzi 15 OPZV 1500 24 OPzV 3000 4 pezzi 40 mm min travetto 50 mm max E 11 GNB INDUSTRIAL POWER Exide Technologies GmbH Im Thiergarten 63654 B dingen Germany Tel 49 0 60 42 81 544 Fax 49 0 60 42 81 398 www gnb com NXEXXAMPDF1113 Druckhaus Bechstein GNB InpustriaL POWER
11. al suma de tensiones de circuito abierto de los ele mentos o bater as individuales En caso necesario numere los elementos o bater as secuencialmente en un lugar visi ble entre el terminal positivo y el negativo de la bater a Aplique las se ales de polaridad a los ter minales de la bater a En caso necesario coloque cubiertas ais lantes para los terminales y conectores de los elementos monoblocs 3 3 1 Armarios con bater as incorporadas Armarios Instale el armario de bater as en el lugar asignado observando las normas preventi vas de accidentes Deje un espacio adicional de la pared para previstas o posibles entradas de cable Si fuese preciso elimine la protecci n de transporte incorporada de las bater as o elementos Compruebe que las bater as o elementos est n posicionados correctamente y que no tengan ning n da o mec nico 3 2 Armarios con bater as o elementos entregados por separado En los armarios solo se montaran bater as y o elementos que est n cargados y con cido abiertos de v lvula regulada Monte el armario coloque y alin elo en el lugar asignado observe las normas preven tivas de accidentes Coloque los elementos o bater as en el armario de acuerdo al plano de instalaci n conectar el ctricamente y colocar las iden tificaciones ver punto 2 4 En elementos o bater as instalados en horizontal la tapa nunca debe apoyar en un larguero ver dibujo
12. as u objetos sobre de la bater a Mantenga a los ni os alejados de las bater as El incumplimiento de las instrucciones de uso empleo de accesorios o recambios no originales en instalaciones e reparaciones o con accesorios y recambios no recomendados por el fabricante de la bater a o reparaciones echas sin autorizaci n Ej apertura de las v lvulas en bater as VRLA y uso de aditivos para los electr litos en bater as abiertas supuestos agentes de mejora invalidar la garant a 1 Condiciones de preparaci n e instalaci n 1 1 Antes de empezar con la instalaci n aseg rese que la sala de bater as est limpia y seca y que tiene una puerta con cerradura La sala de bater as debe cumplir con las normas EN 50 272 2 y marcada como tal Preste atenci n a los siguientes aspectos Tipo de suelo y capacidad de peso sopor table pasos y sala de bater as Resistencia electrol tica de la zona donde se va a instalar la bater a Ventilaci n La instalaci n de la bater a debe ser de tal modo que las diferencias de temperatura entre ele mentos no supere los 10K bater as abiertas o 3 K bater as VRLA Para garantizar una instala ci n sin problemas deber coordinarse con otras personas que trabajen en la misma zona Les 1 2 Comprobar el env o para que los componentes est n completos y en buen estado Si fuese necesario limpiar todas las piezas antes de su instalaci n 1 3 Siga las inst
13. chungen ist eine R cksprache mit dem Hersteller notwendig 2 Gestelle 2 1 Gestelle im Raum entsprechend der Aufstellungs zeichnung ausrichten Fehlt eine Aufstellungs zeichnung dann sind folgende Mindestabst nde einzuhalten Zur Wand 100 mm rundum bezogen auf das Gestell 1 5 Meter bei einer Nennspannung oder Teilspannung gt 120 V zwischen nichtisolier ten Anschl ssen oder Verbindern und geer deten Teilen z B Wasserleitungen bzw zwischen den Endpolen der Batterie W h rend der Montage von Batterien muss sichergestellt sein z B Abdecken von elek trisch leitf higen Teilen durch Isoliermatten dass DIN EN 50272 2 eingehalten wird Zu Gangbreiten 1 5 x Zellenbreite Einbau tiefe jedoch nicht kleiner als 600 mm 2 2 Gestelle unter Verwendung von Ausgleichsteilen oder verstellbaren Isolatoren horizontal ausrich ten Die Abst nde der Auflageschienen m ssen den Zellen bzw Blockbatterieabmessungen entsprechen Bei waagerechtem Einbau darauf achten dass der Block Zellendeckel frei nach vorne bersteht und nicht auf der Auflageschiene liegt siehe Abb oder anderweitig belastet wird z B durch Aufliegen auf vorstehender Deckel kante Anschlie end sind die Standfestigkeit der Gestelle sowie alle Schraub bzw Klemmverbin dungen auf festen Sitz zu pr fen Erdung des Gestelles bzw der Gestellteile falls vorgesehen Schraubverbindungen sind vor Korrosion zu sch tzen 2 3 Zellen bzw
14. delle batterie Durante l installazione delle batterie assicu ratevi che venga osservata la normativa EN 50 272 2 ad esempio ricoprendo elettrica mente le parti conduttive con materiali iso lanti Larghezza dei corridoi 1 5 x Larghezza dell elemento ma non meno di 600 mm 2 2 Bilanciare gli scaffali orizzontalmente usando eventuali spessori forniti o isolatori regolabili La distanza fra i profili di sostegno deve corri spondere alle dimensioni delle batterie Controllare che tutto sia stabile ben avvitato e fissato Per l installazione orizzontale di blocchi celle necessario assicurarsi che la contenitore coperchio non sia appoggiato su una trave asse vedi disegno e che il coperchio non venga sot toposto ad alcun carico ad esempio appoggian do sul bordo del coperchio Mettere a terra lo scaffale o parti dello scaffale se necessario Proteggere contro la corrosione le giunture avvi tate se richiesto dai materiali utilizzati 2 3 Controllare che gli elementi o i monoblocchi siano in perfette condizioni controllo visivo polarit 2 4 Mettere uno dopo l altro gli elementi o i mono blocchi sullo scaffale assicurandosi che la pola rit sia corretta Per gli elementi larghi utile iniziare ad installare gli elementi partendo da met scaffale Allineare gli elementi o i monoblocchi paral leli uno all altro La distanza tra gli elementi o i monoblocchi deve essere di 10mm ca o almen
15. ere dei coperchi isolan ti per i connettori ed i terminali degli ele menti monoblocchi 3 Armadi 3 1 Armadi con batteria incorporata Installare l armadio batteria nella posizione assegnata attenendosi alle regole di pre venzione infortuni Lasciare dell ulteriore spazio dal muro per eventuali entrate di cavi Se applicabile togliere la protezione per il trasporto dagli elementi o monoblocchi incorporati Controllare per il corretto posizionamento ogni eventuale danno agli elementi o ai 3 2 Armadi con elementi o monoblocchi inviati a parte Montare l armadio collocarlo ed allinearlo nella posizione assegnata attenersi alle regole di prevenzione infortuni Posizionare gli elementi o i monoblocchi nell armadio secondo il piano di installazio ne e le distanze definite fare le connessioni elettriche e applicare le marcature vedi punto 2 4 Per installazioni orizzontali di elementi o monoblocchi assicurarsi che il travetto di supporto non copra il tappo coperchio degli elementi monoblocchi 4 Marcatura CE Dal 1 Gennaio 1997 le batterie con tensione nominale superiore ai 75 V necessitano di una dichiarazione di conformit come da Direttiva Bassa Tensione 73 23 CE la quale comporta che la marcatura CE sia apposta sulla batteria La Societ che installa la batteria responsabile della emissione della dichiarazione di conformit e dell apposizione della marcatura CE A
16. fen ggf entfernen und Betriebsstopfen aufsetzen geschlossene Batterien Bei geschlossenen Batterien den Elektrolyt stand kontrollieren Gebrauchsanweisung Inbetriebsetzungsanweisung beachten Messung der Gesamtspannung Soll Summe der Ruhespannungen der einzelnen Zellen bzw Blockbatterien Falls erforderlich Zellen bzw Blockbatte rien an sichtbarer Stelle nicht auf den Ventil ffnungen mit einer durchlaufenden Nummerierung vom Pluspol der Batterie zum Minuspol versehen Polarit tsschilder f r die Batterieanschl sse anbringen Sicherheitskennzeichenschild Typschild und Gebrauchsanweisung sichtbar anbrin gen Gegebenenfalls sind Isolierabdeckungen f r Zellen Blockverbinder und Endpole zu montieren Schr nke Schr nke mit eingebauter Batterie Das Aufstellen des Batterieschrankes erfolgt unter Beachtung der Unfallverh tungsvorschriften am vorgesehenen Ort Zus tzliche Wandabst nde f r m gliche oder vorgesehene Kabeleinf hrungen ber cksichtigen Eventuelle Transportsicherungen an den ein gebauten Zellen bzw Blockbatterien entfer nen Zellen bzw Blockbatterien auf richtige Lage und mechanische Besch digungen kontrol lieren 3 2 Schr nke mit separat angelieferten Zellen bzw Blockbatterien Es werden nur gef llte und geladene Zellen bzw Blockbatterien geschlossen oder ver schlossen in Schr nke eingebaut Schrank montieren an seinem vorgesehe nen S
17. ge cepen dant pas moins de 600 mm 2 2 Installer les supports l horizontale en utilisant pi ces de compensation ou des isolateurs r glables Les distances entre les glissi res d appui doivent correspondre aux dimensions des accumulateurs monoblocs et l ments Pour les l ments install s en position horizon tale veillez ce que la liaison bac couvercle ne repose pas sur un longeron voir sch ma en bas de page et que le couvercle ne subit pas de contrainte m canique par ex un monobloc ou l ment ne doit pas reposer sur la partie protu b rante du couvercle Ensuite v rifier la stabilit des supports ainsi que la bonne mise en place de tous les raccords vis et borne Etablir la mise la terre des supports ou des parties du support si cela est pr vu Prot ger les raccords vis de la corrosion 2 3 Contr ler si les accumulateurs monoblocs ou les l ments sont en parfait tat visuellement pola rit 2 4 Poser les accumulateurs monoblocs ou les l ments l un apr s l autre sur les supports en veillant la polarit correcte Lors de grands l ments d accumulateur il est n cessaire de commencer par le montage des l ments au milieu du support Orienter les accumulateurs monoblocs ou les l ments parall lement Distance entre les accumulateurs monoblocs ou les l ments env 10 mm cependant au moins 5 mm ou en fonction de la longueur des connecteur
18. ificato ed autorizzato ad eseguire operazioni su circuiti elettrici ATTENZIONE non effettuare alcuna opera zione sui circuiti elettrici senza autorizzazio ne 1 5 Misurare la tensione a circuito aperto su ogni elemento o monoblocco verificando contempo raneamente la corretta connessione delle polari t Per quanto riguarda le batterie a carica secca si pu effettuare la misura solo dopo l attivazione e la messa in servizio La tensione a circuito aperto non deve differire tra un elemento e l altro pi di 0 02 V Per quanto riguarda i monoblocchi le tolleranze della tensio ne a circuito aperto sono come segue Max tolleranza V unit acido libero ermetiche Elementi da 2V 0 020 0 030 Monoblocchi da 4V 0 028 0 042 Monoblocchi da 6V 0 035 0 052 Monoblocchi da 8V 0 040 0 060 Monoblocchi da 10V 0 045 0 067 Monoblocchi da 12V 0 049 0 073 Se la variazione di temperatura risulta superiore contattare il fornitore 2 Scaffali 2 1 Individuare la posizione degli scaffali nel locale batterie secondo il piano di installazione Se non esiste un piano di installazione osservare le seguenti distanze minime Dal muro almeno 100 mm tutto attorno agli elementi ed ai monoblocchi o 50 mm tutto attorno agli scaffali Ad una tensione nominale o parziale gt 120 V 1500 mm tra i collegamenti non isolati e le parti messe a terra ad esempio le tuba ture d acqua e o i terminali
19. ing on batteries wear protective eye glasses and clothing Observe the accident prevention rules as well as EN 50 272 2 e Any acid splashes on the skin or in the eyes must be flushed with plenty of water immediately Then seek medical assistance Spillages on clothing should be rinsed out with water items or tools on the battery oP PPB Explosion and fire hazard avoid short circuits e Avoid electrostatic charges and discharges sparks Electrolyte is very corrosive In normal working conditions the contact with the electolyte is impossible If the cell or monoblock container is damaged do not touch the exposed electrolyte because it is corrosive Cells and blocks are heavy Make sure they are installed securely Only use suitable handling equipment for transportation Handle with care because cells blocks are sensitive to mechanical shock Do not lift or pull up blocks cells on the poles e Caution Metal parts of the battery are always alive therefore do not place Keep children away from batteries Non compliance with installation instruction installations or repairs made with other than original accessories and spare parts or with accessories and spare parts not recommended by the battery manufacturer or repairs made without authorization e g opening of valves on VRLA batteries and use of additives for the electrolytes on flooded batteries alleged enhancing agents render the warranty void 1 Installatio
20. monoblock batte ries Check cells or monoblock batteries for cor rect positioning and for any mechanical damage 3 2 Cabinets with separately delivered cells or monoblock batteries Only filled and charged cells and or monoblock batteries vented or valve regu lated are built into cabinets Assemble cabinet place and align at the assigned location observe the accident prevention rules Place cells or monoblock batteries in the cabinet in accordance with the installation plan connect electrically and apply mark ings see point 2 4 For horizontal installation of blocks cells please ensure that the beam does not support the lid cover of blocks cells see drawing 4 CE marking Batteries with a nominal voltage from 75 V onwards require an EC conformity declaration according to the low voltage directive 2006 95 EC replaces 73 23 EEC which entails that the CE marking is applied to the battery The company installing the battery is responsible for supplying the declaration and applying the CE marking WARNING Prior to connecting the battery to the char ger ensure that all installation work has been duly completed Drawing Number of supports 4 OPzV 200 6OPzV 300 3 pieces 5 OPzV 350 7OPzV 490 3 pieces 6 OPzV 600 12 OPzV 1200 4 pieces 15 OPzV 1500 24 OPzV 3000 4 pieces 40 mm min beam 50 mm max Instructions de montage pour les accumulateurs stationnaires InDusTRIAL
21. n preconditions and preparations 1 1 Prior to commencing installation ensure that the battery room is clean and dry and that it has a lockable door The battery room must meet the requirements in accordance with EN 50 272 2 and be marked as such Pay attention to the following aspects Load bearing capacity and nature of the floor transport paths and battery room Electrolytic resistance of the area where the battery is to be installed Ventilation Battery installation should be made such that temperature differences between individual cells blocks do not exceed gt 10 K vented batte ries respectively gt 3K valve regulated batteries To ensure trouble free installation coordination should be made with other personnel working in the same area 1 2 Check delivery for complete and undamaged components If necessary clean all parts prior to installation 1 3 Follow instructions in the documentation sup plied e g installation drawings for battery stand cabinet See equivalent Operating instructions for tor ques to be applied 1 4 Prior to removing old batteries always ensure that all of the leads have been disconnected load break switches fuses insulations This must be carried out only by personnel author ised to perform circuit operations WARNING Do not carry out any unauthorised circuit operation InDusTRIAL POWER 1 5 Carry out open circuit voltage measurements on the i
22. ndividual cells or monoblock batteries At the same time ensure that they are connected in the correct polarity As for unfilled and charged bat teries these measurements can only be taken after commissioning The open circuit voltage of the individual cells blocks should not vary themselves from the measured average value by more than the plus minus tolerances listed in the table below guide values Max tolerance V Unit Vented VRLA 2V celle 0 020 0 030 4V block 0 028 0 042 6V block 0 035 0 052 8V block 0 040 0 060 10V block 0 045 0 067 12V block 0 049 0 073 If the deviation is any higher than shown in the table contact the supplier 2 Stands 2 1 Locate the stands racks within the battery room in accordance with the installation plan If an installation plan does not exist observe the fol lowing minimum distances From the wall 100 mm all around with regard to cells or monoblocks or 50 mm concerning of the stands Ata nominal voltage or partial voltage gt 120 V 1 5 metres between non insulated leads or connectors and grounded parts e g water pipes and or between the battery terminals During the installation of the bat teries ensure that EN 50 272 2 part 2 is observed e g by covering electrically con ductive parts with insulating mats Width of aisles 1 5 x cell width built in depth but not less than 600 mm 2 2 Balance battery stands hori
23. noblocs ou l ments individuels Si n cessaire apposer des num ros cons cutifs sur les accumulateurs monoblocs ou sur les l ments un endroit visible du p le positif de l accumulateur vers le p le n gatif en vitant les soupapes Accrocher les pictogrammes de polarit pour les raccords d accumulateur Apposer de mani re visible la plaquette avec le label de s curit la plaque signal tique et le mode d emploi Si n cessaire monter des couvercles iso lants pour les connecteurs d l ments de blocs et les p les terminaux 3 Armoires 3 1 Armoires avec accumulateur int gr Monter l armoire d accumulateur l endroit pr vu sous le respect des consignes de pr vention d accidents Tenir compte des distances murales sup pl mentaires pour des passages de cable possibles ou pr vus Enlever les ventuels dispositifs de s curit pendant le transport mis en place sur les accumulateurs monoblocs ou l ments int gr s Contr ler si les accumulateurs monoblocs ou les l ments sont positionn s correcte ment et pr sentent des endommagements m caniques 3 2 Armoires avec accumulateurs monoblocs ou l ments livr s s par ment Monter dans les armoires uniquement des accumulateurs monoblocs ou l ments ouverts ou tanches qui sont remplis et charg s Monter l armoire la placer l endroit pr vu et l orienter obser
24. o di 5 mm Se necessario pulire le superfici di contatto dei terminali e dei connettori Posizionare ed avvitare le connessioni degli elementi o dei monoblocchi usando una chiave dinamometrica isolata per la coppia di serraggio fare riferimento alle istruzioni operative della batteria Se necessario osservare le istruzioni speciali per quanto riguarda le connessioni es connessioni saldate Creare i collegamenti in serie utilizzando i materiali forniti ed avvitandoli insieme rispettando le coppie di serraggio nominali Evitare corto circuiti Usare cavi con tensio ne di isolamento superiore a 3 KVolt man tenere una distanza d aria di circa 10 mm tra i cavi e le parti elettricamente condutti Se applicabile rimuovere i tappi di traspor to e rimpiazzarli con tappi di funzionamento standard Controllare il livello di elettrolito fare riferi mento alle istruzioni operative o di attivazio ne Misurare la tensione totale tensione nomi nale somma della tensione a circuito aper to di ogni singolo elemento o monoblocco Se necessario numerare in modo sequen ziale tra il terminale positivo ed il terminale negativo della batteria ciascun elemento o monoblocco in un punto visibile Applicare i segnali di polarit sui cablaggi delle batterie Applicare i segnali di sicurezza le etichette con i dati tecnici e le istruzioni operative in posizione visibile Se necessario mett
25. oit se trouver proximit des ouvertures des l ments d accumulateur e conditions de ventilation La batterie doit tre install e de mani re ce que la diff rence de temperature entre les mono fr blocs ou l ments ne depasse pas 3 C batterie tanche ou 10 C batterie plomb ouvert Pour assurer un d roulement sans probl me il convient de s accorder avec les autres per sonnes qui exercent leurs activit s dans les m mes locaux 1 2 V rifier si le contenu de la livraison est complet et pr sente d ventuels dommages Si n ces saire nettoyer toutes les pi ces avant l assem blage 1 3 Suivre les instructions figurant dans la documen tation jointe la livraison par exemple les des sins de montage de l accumulateur du support et de l armoire Les couples de serrage appliquer sont indi qu s sur la notice d utilisation 1 4 Lors du remplacement s assurer avant de com mencer le d montage de l ancienne batterie que les cables d alimentation ont t d connect s sectionneurs coupure en charge fusibles commutateurs Cela doit tre ex cut par un personnel autoris pour ces t ches ATTENTION ne proc der aucune mise en circuit de propre r gie 1 5 Mesures de la tension de repos des accumula teurs individuels monoblocs ou l ments Veiller alors par la m me occasion a la polarit correcte Lors d accumulateurs charg s non remplis ferm s
26. olen anheben oder hochziehen ab PPP e Gef hrliche elektrische Spannung Achtung Metallteile der Batteriezellen stehen immer unter Spannung deshalb keine fremden Gegenst nde oder Werkzeuge auf der Batterie ablegen Kinder von Batterien fernhalten Bei Nichtbeachtung der Montageanweisung bei Installation oder Reparatur mit nicht originalen bzw vom Batteriehersteller nicht empfohlenen Zubeh r bzw Ersatzteilen eigenm chtigen Eingriffen Anwedung von Zus tzen zum Elektrolyten angebliche Aufbesserungsmittel erlischt der Garantieanspruch 1 Montagevoraussetzungen und vorbereitungen 1 1 Vor Beginn der Montage muss sichergestellt sein dass der Batterieraum sauber und trocken ist und ber eine abschlie bare T r verf gt Der Batterieraum muss entsprechend der DIN EN 50272 2 beschaffen und gekennzeichnet sein Dabei sind insbesondere zu beachten e Bodenbelastbarkeit und beschaffenheit Transportwege und Batterieraum e Elektrolytbest ndigkeit der Batterieaufstell fl che e Keine Z ndquellen z B offene Flammen Gl hk rper elektrische Schalter im Nah bereich der Zellen ffnungen e Bel ftungsbedingungen Die Batterie ist so aufzustellen dass zwischen den einzelnen Zellen Bl cken eine umgebungs bedingte Temperaturdifferenz von gt 10K geschlossene Batterien bzw gt 3 K verschlos sene Batterien nicht auftreten kann Zur Sicherstellung eines reibungslosen Ablaufes ist eine Abstimmung
27. ort Manipuler avec pr caution car les monoblocs sont sensibles aux chocs m caniques Port des chaussures de s curit obligatoire Ne jamais tirer ou soulever l accumulateur par les bornes e Attention Les parties m talliques de la batterie sont toujours actives en cons quence ne pas poser de pi ce ou d outil non isol s sur la batterie e Garder les accumulateurs hors de port e des enfants Le non respect des instructions d utilisation les installations ou les r parations effectu es avec des pi ces autres que celles d origine ou avec des pi ces non recommand es par le fabricant ou des r parations faites sans autorisation par ex l ouverture des soupapes pourront entra ner l annulation de la garantie 1 Conditions de montage et travaux pr paratifs pour le montage 1 1 Avant de commencer le montage il faut s assu rer que le compartiment d accumulateur est propre et sec et qu il est quip d une porte pouvant tre verrouill e Le compartiment d ac cumulateur doit tre am nag et caract ris selon la norme NF EN 50272 2 Il convient alors en particulier d observer les points suivants e capacit de portance et structure du sol chemin de transport et compartiment d ac cumulateur e resistance de la surface d implantation de l accumulateur envers l lectrolyte e aucune source d allumage par exemple flammes vives objets incandescents com mutateurs lectriques ne d
28. rucciones de la documentaci n faci litada Ej esquemas de instalaci n de la bater a estantes armarios Ver equivalente Instrucci n de trabajo para los torques a aplicar 1 4 Antes de sacar las bater as usadas aseg rese siempre que todos los cables se hayan desco nectado disyuntores fusibles aislamientos Esto deber llevarse a cabo solo por personal autorizado para realizar operaciones de riesgo el ctrico ADVERTENCIA No llevar a cabo ninguna operaci n el ctrica no autorizada 1 5 Tomar las medidas de tensi n de circuito abierto de las bater as o elementos Al mismo tiempo aseg rese que est n conectadas en la polaridad correcta En cuanto a las bater as sin rellenar y cargadas estas mediciones solo se podr n lle var a cabo despu s de la puesta en marcha Las tensiones del circuito abierto de los blocs elementos individuales no deber a variar en valor medio medido en mas que las tolerancias que figuran en la tabla de abajo valores de referencia Tolerancia m x M Unidad Abierto VRLA Elemento 2V 0 020 0 030 Monobloc 4V 0 028 0 042 Monobloc 6V 0 035 0 052 Monobloc 8V 0 040 0 060 Monobloc 10V 0 045 0 067 Monobloc 12V 0 049 0 073 Si la desviaci n es mas alta que lo mostrado en la tabla contacte con el proveedor 2 Estantes 2 1 Busque los estantes bancadas dentro de la sala de baterias de acuerdo con el plano de instala ci n Si no exis
29. s contenus dans la livraison Si n cessaire nettoyer les surfaces de contact des p les et des connecteurs Poser les connecteurs de blocs ou d l ments et les visser avec une cl dynamo m trique isol e respecter les couples de serrage corrects selon les indications figu rant dans le mode d emploi de l accumula teur Le cas ch ant il est imp ratif d ob server les remarques particuli res concer nant les connecteurs d l ments par exemple les connecteurs soud s Mettre en place les connecteurs en s rie gradins et tages contenus dans la livrai son et les visser en respectant les couples de serrage prescrits Veiller alors ce que la pose r siste aux courts circuits C est dire il faut utiliser des mat riaux de c ble avec une r sistance di lectrique d au moins 3 kV ou maintenir une distance d env 10 mm entre les c bles et les pi ces lectriquement conductrices ou appliquer une isolation suppl mentaire sur les connecteurs Eviter de solliciter m caniquement les l ments et les p les de l accumulateur Le cas ch ant enlever les bouchons de transport et placer des bouchons de service accumulateurs ferm s Contr ler le niveau d lectrolyte dans les accumulateurs ferm s observer le mode d emploi et les instructions de mise en ser vice Mesure de la tension totale valeur de consigne somme des tensions de repos des accumulateurs mo
30. tandort aufstellen und ausrichten unter Beachtung der UVV Zellen bzw Blockbatterien gem Einbau plan in den Schrank einsetzen elektrisch verschalten und kennzeichnen siehe Pkt 2 4 Bei waagerechtem Einbau darauf achten dass der Block Zellendeckel frei nach vorne bersteht und nicht auf der Auflageschiene liegt siehe Abb 4 CE Kennzeichnung Bei Batterien ab 75 V Nennspannung ist eine EG Konformit tserkl rung gem der Nieder spannungsrichtlinie 2006 95 EG ersetzt 73 23 EWG mit der entsprechenden CE Kennzeich nung der Batterie erforderlich F r die Ausstel lung der Erkl rung und die Anbringung der CE Kennzeichnung ist der Errichter der Batterie anlage zust ndig ACHTUNG Vor dem Anschluss an das Ladeger t muss sichergestellt sein dass alle Montagearbei ten ordnungsgem abgeschlossen wurden Abb Anzahl der Auflagen 40PzV 200 6OPzV 300 3 St ck 5 OPzV 350 7OPzV 490 3 St ck 6OPzV 600 12 OPzV 1200 4 St ck 15 OPzV 1500 24 OPzV 3000 4 St ck 40 mm min Gestellbalken 50 mm max Installation instruction for stationary lead acid batteries Batteries Stands Cabinets Observe these Instructions and keep them located near the battery for future reference Work on the battery should only be carried out by qualified e personnel Do not smoke e Risk of explosion and fire 08 EN 50110 1 e Do not use any naked flame or other sources of ignition While work
31. te ning n plano de instalaci n observe las distancias m nimas siguientes Dela pared 100 mm por todas partes en lo que se refiere a elementos o blocs o a 50 mm en lo que se refiere a los estantes Con una tensi n nominal o parcial gt 120 V 1 5 metros entre puntos no aislados o conectores y partes de tierra Ej tuber as de agua y o entre los terminales de la bater a Durante la instalaci n de las bater as aseg rese de que se cumpla la norma EN 50 272 2 parte 2 Ej cubriendo las partes conductoras de electricidad con elementos aislantes Anchura de los pasillos 1 5 x ancho de elemento profundidad total pero no menos de 500 mm 2 2 Equilibre las bancadas horizontalmente usando piezas por compensation o los aislantes ajusta bles Las distancias de los largueros deben coincidir con las dimensiones de las bater as o elementos Para la instalaci n de los elementos blocs en posici n horizontal aseg rese de que el larguero no se apoya en la tapa de los elemen tos bater a v ase dibujo o la tapa no est car gada de forma diferente por ejemplo cargando el borde saliente de la tapa Compruebe la esta bilidad de las bancadas y que todas las uniones atornilladas y a presi n queden firmes Si fuese preciso conectar a tierra la bancada Las uniones atornilladas deber n estar protegidas contra la corrosi n 2 3 Compruebe que las bater as o elementos est n en perfectas condiciones Control visual
32. ua Cercare in seguito l assistenza medica e Eventuali schizzi sugli indumenti devono essere risciacquati con acqua L elettrolito molto corrosivo Tensione elettrica pericolosa Tenere bambini lontani dale batterie ab gt Pericolo di esplosione e di incendio evitare corto circuiti Evitare cariche e scariche elettrostatiche scintille Gli elementi ed i monoblocchi sono molto pesanti Usare sempre attrezzature adeguate per il trasporto Maneggiare con cura perch gli elementi ed i monoblocchi sono sensibili agli shock meccanici Non alzare o estrarre gli elementi monoblocchi dai poli e Attenzione Le parti metalliche della batteria sono sempre sensibili aicontatti elettrici di conseguenza non posizionare alcun oggetto o attrezzo sulla batteria La garanzie da considerarsi annullata se non conformit con le istruzione di installazione installazioni o riparazioni effettuate con accessori e ricambi non originali o con accessori e pezzi di ricambio non raccomandati dal produttore delle batterie riparazioni effettuate senza autorizzazione es apertura di valvole sulle batterie VRLA l uso di additivi per gli elettroliti delle batterie ad acido libero 1 Precondizioni di installazione e preparativi Prima di iniziare l installazione assicurarsi che il locale batteria sia pulito ed asciutto e che abbia una porta chiudibile a chiave Il locale batteria deve soddisfare i requisiti della EN 50 272 2
33. ue values Avoid short circuits Use leads of at least 3 kV breakdown voltage or keep an air distance of approx 10 mm between the leads and electrically conductive parts or apply additional insulation to the connec tors Avoid applying any mechanical force on the cell battery poles All end connectors of batteries which connect batteries among each other with the load the disconnector or fuses must be installed inherently short circuit proof 3 3 1 If applicable remove transport plugs and replace by operational plugs Check electrolyte level Observe operating instructions commissioning instructions Measure total voltage nominal voltage sum of open circuit voltages of the individu al cells or monoblock batteries If necessary sequentially number the cells or monoblock batteries in a visible place not on the valves between the positive terminal of the battery and the negative terminal of the battery Apply polarity signs for the battery leads Attach safety marking type lable and oper ating instructions in a visible place If necessary fit insulating covers for cell monoblock connectors and terminals Cabinets Cabinets with built in battery Install the battery cabinet at the location assigned observing the accident preven tion rules Leave additional space from the wall for possible or planned cable entries If applicable remove transport protection from the built in cells or
34. ver les consignes de pr vention d accidents Poser les accumulateurs monoblocs ou les l ments dans l armoire conform ment au plan de montage et aux distances pre scrites Ensuite les mettre en circuit lectri quement et les mettre en vidence voir au paragraphe 2 4 Dans le cas d l ments ou monoblocs install s en position horizontale la jonction bac couvercle ne doit jamais reposer sur une longrine sch ma ci des SOUS 4 Estampille de la CE Une d claration de conformit de la CE confor m ment la directive de basse tension 2006 95 CE remplace 73 23 CEE portant l estampille correspondante de la CE est n cessaire pour Paccumulateur lors d accumulateurs partir d une tension nominale de 75 V C est le responsable du montage de l installation qui est comp tent pour la d position de la d claration et l apposition de l estampille de la CE ATTENTION Avant le branchement au chargeur il faut s assurer que tous les travaux de montage ont t achev s en bonne et due forme Schema Nombre de longrines 40PzV 200 6OPzV 300 3 pi ces 5 OPzV 350 7OPzV 490 3 pi ces 6 OPzV 600 12 OPzV 1200 4 pi ces 15 OPzV 1500 24 OPzV 3000 4 pi ces 40 mm min longrine 50 mm max Instrucciones de Instalaci n GNB InDusTRIAL POWER para bater as estacionarias de plomo cido Bater as Estantes Armarios e Siga atentamente estas instrucciones y mant ngalas expuestas
35. zontally using balan ce parts or adjustable insulators The distances of the base rails must correspond to the dimen sions of the cells or monoblock batteries For horizontal installation of blocks cells please ensure that the box lid bond is not resting on a beam see drawing and the lid is not stressed in any way e g by laying the cell block on the pro truding edge of the lid Check the stands for stability and all screwed and clamped joints for firm connection Earth ground the stand or parts of the stand if required Screwed joints must be protected against corrosion 2 3 Check cells or monoblock batteries for perfect condition visual check polarity 2 4 Place cells or monoblock batteries on the stand one after another ensuring correct polarity For large cells it is useful to start installing the cells in the middle of the stand Align cells or monoblock batteries parallel to each other Distance between cells or monoblock batteries approx 10 mm at least 5 mm If necessary clean the contacting surfaces of the terminals and connectors Place and screw intercell or monoblock connectors using an insulated torque wrench for correct torque value refer to battery operating instructions If applicable observe special instructions with regard to the intercell connectors e g welded con nectors Place the series step or tier connectors supplied and screw them together observ ing the given torq