Home
Bedienungsanleitung
Contents
1. appears 4 Testing 4 1 Function test You have to perform the function test in order to prepare the device for operation Step 1 Display test self test As long as the on off switch is pressed all display segments appear the 4 LEDs gleam and an acoustic signal occurs When you stop pressing the on off switch TEST appears in the display Step 2 Check ground connection and protective resistors Connect the universal clip to ground and contact the test electrode to ground The DSP 3HS36 is ready for operation when Rdy appears and the green LED gleams Attention If one of the displays fails during the self test the voltage tester may not be placed into operation and needs to be send to repair 4 2 Performing voltage tests Preparation and check within three steps 1 Establishing contact Firmly connect the contact clip with the ground potential preferably fixed ball point conductor rail 2 Function test Switch on the device press push button TEST as well as battery condition see 5 1 are indicated Press the test electrode to the ground potential Do not touch the clip when checking the connection between clip and ground The DSP 3HS36 is ready for operation when Rdy flashes and the green LED gleams Note In case the function test has not been sucessful check the following Is there a connection to ground potential Contact clip tightly connected Battery empty Test electrode s
2. Taste gedr ckt halten alle Displaysymbole und LEDs m ssen erscheinen Nach Loslassen des Tasters erscheint TEST auf der oberen Zeile der Anzeige F llt hierbei die Anzeige eines oder mehrerer Systeme aus darf das Ger t nicht mehr verwendet werden Funktionstest Pr felektrode ca 5 Sekunden mit Erde kontaktieren bis rdy erscheint Hierbei nicht die Klemme selbst antasten um die Verbindung Klemme Erde mit zu berpr fen Wenn die gr ne LED konstant leuchtet und in der Anzeige 000 V erscheint ist das Ger t betriebsbereit Falls der Funktionstest nicht erfolgreich war ist m glicherweise kein richtiger Kontakt zur Erde hergestellt Der Vorgang ist zu wiederholen Ist der Funktionstest nicht erfolgreich darf das Ger t nicht verwendet werden 3 e Spannung pr fen Achtung Funktionstest muss erfolgreich durchgef hrt worden sein gr ne LED muss leuchten Ger t nur unterhalb der achteckigen Griffbegrenzung anfassen Spitze nur oberhalb der roten Grenzmarke an Spannung f hren Anzeige Spannung vorhanden rote LEDs leuchten Anzeigewert erscheint auf beleuchtetem Display akustisches Signal ert nt Netzfrequenz in oberer Displayzeile Anzeige blinkend noch 10 s nach Spannungspr fung sichtbar spannungsfrei gr ne LED leuchtet Display bleibt dunkel Anzeige 000 V Sicherheitskontrolle 1 Elektrode richtig kontaktiert 2 Erdleitung fest angeschlossen Batteriezustandskontrolle volle Kapazitat noch viele Pr
3. 69 Tietzsch Bedienungsanleitung User Instructions MultiSafe DSP 3HS36 Hochspannungspr fer High Voltage Tester Rudolph Tietzsch GmbH amp Co KG Willringhauser Stra e 18 D 58256 Ennepetal Telefon 49 2333 75989 Telefax 49 2333 75257 info tietzsch de www tietzsch de DSP 3HS36_BA_03 2012 Pr felektrode rote Grenzmarke Pr fspitze Basisrohr Anzeigeeinheit Begrenzungsscheibe Handhabe Universalklemme zur Erdverbindung O ON A MN BPWN gt Verbindungsleitung Symbole auf dem Ger t A Achtung Bedienungsanleitung beachten EG Konformit tskennzeichnung ED Einschaltdauer f r Spannungspr fung A Ger t zum Arbeiten unter Spannung 1 Anwendung Der MultiSafe DSP 3HS36 ist ein zweipoliger Spannungspr fer f r Wechselspannungen und Gleichspan nungen bis 36 kV gegen Erde Er ist besonders geeignet um die Spannung an Kondensatorenbatterien und Umrichter mit Frequenzen von 0 200 Hz schnell und sicher festzustellen Die Spannung wird durch 3 rote LEDs signalisiert und der Wert digital auf dem Display angezeigt Gleichzeitig zeigt Ihnen die zweite Displayzeile die Netzfrequenz Eigentest und Funktionstest sind ein fach und schnell mit einer Taste durchzuf hren Die Bereitschaft und nicht vorhandene Spannung wer den durch eine gr ne LED angezeigt 2 Sicherheitshinweise Um den sicherheitstechnisch einwandfreien Zustand zu erhalten und die gefahrlose Anwendung sicherzu
4. crewed tightly Switch on the device for self test and put the universal clip to the contact electrode Firmly attach the clip with the ground potential if necessary clean the contact surface and repeat the function test If the function test fails the voltage tester may not be used 3 Testing voltage Attention The function test has to be performed successfully and the green LED must light up Hold the instrument only beneath its octagonal limiting disc The test probes may only be connected up to the red limiting mark to live or grounded plant compon ents With all other parts of the voltage tester the distance has to be kept as big as possible Connect the test electrode securely with the conductor to be tested Indication Voltage existent red LEDs light up value appears on the illuminated display acoustic signal is emitted mains frequency in the upper display line Zero potential green LED lights up display dark indication 000 V Security check 1 Electrode is connected properly 2 Grounding line firmly connected Note For about 10 seconds the flashing measurement value is indicated on the display so that the value can be read directly after the test procedure AC voltage tests can be peformed up to 36 000 V the measurement value is preceded with the symbol DC voltage tests can be peformed up to 36 000 V When you connect the test electrode to the positive pole of a direct voltage the indicated value is unsign
5. d L sen Sie beide gelben Schrauben entfernen Sie den Halteb gel und nehmen Sie das Anzeigeger t aus der Halterung heraus Batteriefachdeckel auf der Ger ter ckseite abschrauben Batterie aus der Schutzhaube gleiten lassen Batterieanschlusskontakte l sen Nach Anschlie en der neuen Batterie diese mit der Schutzhaube in das Batteriefach einsetzen und Deckel wieder festschrauben Die Anzeigeeinheit wieder auf dem Ger terohr montieren Setzen Sie das Anzeigeger t wieder in die Halterung ein schlie en Sie den Halteb gel und fixieren Sie beide gelben Schrauben Achtung Spannungspr fer d rfen bei ge ffnetem Batteriefach nicht benutzt werden Der MultiSafe DSP 3HS36 darf nur im montiertem Zustand auf dem Basisrohr zusammen mit der Pr fspitze verwendet werden 6 Pr felektrode wechseln Der MultiSafe DSP 3HS36 kann mit verschiedenen Pr felektroden ausgestattet werden Diese k nnen einfach auf die Hochspannungspr fspitze aufgeschraubt werden Danach ist der Funktionstest durch zuf hren Ausf hrungen der Pr felektroden F r den MultiSafe DSP 3HS36 werden folgende Pr felektroden angeboten HS36 i runde Elektrode Standard HS36 G spitze Elektrode mit 5 mm Gewinde HS36 Y gegabelte Elektrode l TT 7 Transport Der MultiSafe DSP 3HS36 kann f r den leichteren Transport geteilt werden Drehen Sie die Pr fspitze und das Basisrohr gegen den Uhrzeigersinn Nach ca 4 Umdrehunge
6. ed is it connected to minus the measurement value is preceded with the symbol Note At 37 kV or more the indicated value flashes and OL appears in the upper display line Then testing has to be stopped Frequency indication Simultaneously to voltage indication the upper display line indicates the mains frequency eon With direct voltage dc is indicated Voltage 20V S Application in moist environments The DSP 3HS36 is approved for indoor and outdoor applications In case of precipitation the device has to be wiped dry before usage Workings in case of dense fog and impaired visibility are not approved 5 Energy source 5 1 Check battery condition The battery condition is indicated by a battery symbol in the display as follows EST full capacity still many measurements possible replace the battery soon few measurements possible Battery symbol flashing no further measurements admissible Battery change The device works with a 9 V block IEC 6LR61 alkali manganese Remove the display unit from the basic pipe see picture Unscrew the two yellow screws Remove the holding bracket and pull the device out of its holder Unscrew the cover ofthe battery compartment on the back ofthe device Let the battery slide out of the CAT IV protection cover Release battery connecting contacts After connecting the new battery use the CAT IV protection cover to insert the battery into the battery compart
7. eigt um auch direkt nach der Spannungspr fung den Wert ablesen zu k nnen Wechselspannungspr fungen k nnen bis 36 000 V durchgef hrt werden und werden durch das Symbol vor dem angezeigten Wert dargestellt Gleichspannungspr fungen k nnen bis 36 000 V durchgef hrt werden Bei Anlegen der Pr felektrode an den Pluspol einer Gleich spannung erscheint kein Vorzeichen liegt dort Minus an erscheint vor dem angezeigten Wert Hinweis Ab 37 kV blinkt der angezeigte Wert und es erscheint OL in der oberen Displayzeile Die Pr fung muss in diesem Fall abgebrochen werden Frequenzanzeige In der oberen Displayzeile wird gleichzeitig zur Spannung die Netzfrequenz in Hz angezeigt we Bei Gleichspannung wird dc signalisiert Anwendung in feuchter Umgebung Der DSP 3HS36 ist zur Verwendung im Freien und f r Innenraumanlagen zugelassen Bei Niederschlag ist der Pr fer vor dem Gebrauch trocken zu wischen Arbeiten bei starkem Nebel der die Sicht beeintr chtigt sind nicht zugelassen 5 Energiequelle 5 1 Batteriezustandkontrolle Der Batteriezustand wird durch das Batterie Symbol auf dem LCD wie folgt dargestellt CN volle Kapazitat noch viele Pr fungen m glich Batterie ersetzen Pr fung noch m glich Symbol blinkend Keine Pr fungen mehr zul ssig Batterie wechseln Das Ger t arbeitet mit einer 9 V Blockbatterie IEC 6 LR61 Alkali Mangan Die Anzeigeeinheit vom Ger terohr demontieren Bil
8. emme Erde mit zu berpr fen Wenn Rdy blinkt und die gr ne LED leuchtet ist der DSP 3HS36 einsatzbereit Hinweis Falls der Funktionstest nicht erfolgreich war ist folgendes zu berpr fen Verbindung zu Erdpotential Erdungsklemme fest verbunden Batterie leer Pr felektrode fest aufgeschraubt Zum Eigentest Einschalten und Universalklemme auf Kontaktelektrode setzen Klemme wieder fest mit Erdpotential verbinden Kontaktfl che ggf s ubern und Funktionstest wiederholen Wird der Funktionstest nicht bestanden darf der Spannungspr fer nicht verwendet werden 3 Spannung pr fen Achtung Funktionstest muss erfolgreich durchgef hrt worden sein gr ne LED muss leuchten Ger t nur unterhalb der achteckigen Begrenzungsscheibe anfassen Die Pr fspitze darf nur oberhalb der roten Grenzmarke an spannungsf hrende oder geerdete Anlagenteile gebracht werden mit allen anderen Teilen des Spannungspr fers muss ein m glichst gro er Abstand eingehalten werden Pr felektrode sicher auf den zu pr fenden Leiter setzen Anzeige Spannung vorhanden rote LEDs leuchten Anzeigewert erscheint auf beleuchtetem Display akustisches Signal ert nt Netzfrequenz in oberer Displayzeile spannungsfrei gr ne LED leuchtet Display dunkel Anzeige 000 V Sicherheitskontrolle 1 Elektrode richtig kontaktiert 2 Erdleitung fest angeschlossen Hinweis Der Messwert wird noch ca 10 s lang nach der Spannungspr fung blinkend angez
9. er aktiviert werden TEST erscheint auf dem Display Achtung Der Funktionstest ist durchzuf hren um das Ger t in den betriebsbereiten Zustand zu bringen Ausschalten Ein Aus Taster dr cken bis oFF erscheint 3 4 Priifen 4 1 Funktionstest Der Funktionstest ist vor jedem Einsatz durchzuf hren um die Betriebsbereitschaft sicherzustellen Schritt 1 Test der Anzeige Eigentest Solange der Ein Aus Taster beim Einschalten gedr ckt wird werden alle Segmente des Displays sowie 4 LEDs zur Anzeige gebracht und es ert nt ein akustisches Signal Nach Loslassen der Taste erscheint TEST in der Anzeige Schritt 2 Test der Erdverbindung und Schutzwiderst nde Universalklemme mit Erde verbinden und die Pr felektrode an Erde kontaktieren Wenn Rdy und die gr ne LED leuchtet ist der MultiSafe DSP 3HS36 einsatzbereit Achtung Falls bei einem dieserTests die Anzeige nicht vollst ndig erscheint darf das Ger t nicht verwendet werden und ist zur Reparatur einzusenden 4 2 Durchf hren der Spannungspr fung Die Vorbereitung und Pr fung erfolgt in 3 Schritten 1 Verbindung mit Erde herstellen Verbinden Sie die Erdungsklemme fest mit Erdpotential vorzugsweise Kugelfestpunkt Stromschiene 2 Funktionstest Ger t einschalten Taster dr cken TEST sowie der Batteriestatus siehe 5 1 wird angezeigt Pr felektrode an Erdpotential dr cken Hierbei nicht die Klemme selbst antasten um die Verbindung Kl
10. fungen m glich Jah Batterie bald ersetzen Symbol blinkend keine Pr fungen mehr zul ssig 69 Tietzsch User Instructions MultiSafe DSP 3HS36 High Voltage Tester Rudolph Tietzsch GmbH amp Co KG Willringhauser Stra e 18 D 58256 Ennepetal Fon 49 2333 75989 Fax 49 2333 75257 info tietzsch de www tietzsch de DSP 3HS36_BA_03 2012 Test electrode Red limiting mark Test probe Basic pipe Display Limiting disc Handle Universal clip for ground connection Connecting lead CP MNAMNRWHN a Symbols on the instrument A Attention Observe user instructions EC conformity E D On time for voltage testing A Device for live working 1 Application The MultiSafe DSP 3HS36 is a two pole voltage tester for a c and d c voltages up to 36 kV against ground It is particularly suitable to detect voltages at capacitor banks and rail con verter systems with frequencies between 0 200 Hz quickly and securely Voltage is signalised by three red LEDs and the value is indicated digital on the LCD Simultaneously the upper display line indicates the mains frequency With one push button self test and function test are easily and quickly performed Stand by and abscence of voltage are signalised by a green LED 2 Safety Precautions In order to maintain flawless technical safety conditions and to assure safe use it is imperative that you read these operating instructions thoroughly and carefu
11. he test probes may only be connected up to the red limiting mark to live or grounded plant components Indication Voltage existent red LEDs light up value appears on the illuminated display acoustic signal is emitted mains frequency in the upper display line indication flashing still for 10 seconds after testing readible Zero potential green LED lights up display dark indication 000 V Security check 1 Electrode is connected properly 2 Grounding line firmly connected Check battery condition Ue ti full capacity still many measurements possible replace battery few measurements possible flashing symbol no further measurements admissible 19
12. ion for everyday use In order to assure safe operation observe the entire user instruction of the MultiSafe DSP 3HS36 Follow the safety regulations otherwise there is danger of life 1 Establishing contact Before application the DSP 3HS36 has to be completely moounted test electrode basic pipe test probe display unit Firmly connect the contact clip with the ground potential preferably fixed ball point conductor rail Function test Attention Perform the function test before each voltage test Display test self test As long as the on off switch is pressed all display segments appear When you stop pressing the on off switch TEST appears in the display If the display of one or several systems fails in the course of checking the instrument must not be used again Function test Press the test electrode about 5 seconds to the ground potential until Rdy appears Do not touch the clip when checking the connection between clip and ground When the green LED gleams constantly and 000 V is indicated the device is ready for operation In case the function test has not been successful check the connection to ground Repeat the procedure In case once again the function test has not been successful the device must not be used Testing voltage Attention The function test has to be performed successfully and the green LED must light up Hold the instrument only beneath its octagonal limiting disc T
13. lf test function test If the display of one or several systems fails in the course of checking the instrument must not be used again gt The maximum on time of the DSP 3HS36 is 15 minutes gt The voltage tester may only be dismantled by authorized personel gt Voltage testers must be kept dry and clean gt Do not use the device when damages can be identified visual inspection basic pipe test probe electrode display connecting line universal clip gt Arepeated examiniation has to be carried out at least every 6 years 3 General information In order to save on battery the device switches off automatically after approximately 120 seconds when no measurement is taken The LCD backlight switches off automatically after 5 seconds OL out of limit on the display means that the measurement value is higher than the rated measurent range You need to change the battery of the device before continuing with testing when the empty battery symbol on the display flashes Before application the DSP 3HS36 has to be completely moounted test electrode basic pipe test probe display Switch on Switch off The DSP 3HS36 does not switch on automatically For self tests and voltage test the device needs to be activated with the on off switch TEST appears on the display Attention You have to perform the function test in order to prepare the device for operation Switch off Press the on off switch until oFF
14. lly before placing your instrument into service and that you follow all instructions contained therein otherwise there is danger of life Please observe the following safety precautions gt Only qualified personnel with appropriate protective equipment may do these workings Observe the minimum object distance to other plant components that are energized or earthed and use personal protective equipment as specified by national accident prevention regulations in Germany BGV A3 or VDE 0105 100 gt The voltages indicated on the DSP 3HS36 are rated voltages The voltage tester may only be used in systems working with those rated voltage ranges gt Faultless indication of display values is only guaranteed between 10 C and 55 C gt Establish and check safe connection to ground gt Hold the instrument only beneath its octagonal limiting dics do not touch test probes and test electrodes gt The test probes may only be connected up to the red limiting mark to live or grounded plant components With all other parts of the voltage tester the distance has to be kept as big as possible gt The contact clip has to be securely attached to the ground potential e g fixed ball point The grounding line must not cross live plant components Just before they are used and as possible afterwards as well voltage testers need to be checked to ensure they function correctly Check the instrument at a known voltage source by performing the se
15. ment Screw tight the cover Erect the display unit on the basic pipe Put the device back into the holder close the mounting bracket and fasten the screws Attention Voltage testers may not be used with open battery box Only use the erected MultiSafe DSP 3HS36 on the basic pipe in connection with the test probe 6 Change test electrodes The MultiSafe DSP 3HS36 can be equipped with different test electrodes Those can be easily screwed onto the high tension test probes After this perform the self test Design of electrodes The following test electrodes are available for the MultiSafe DSP 3HS36 HS36 i semicircular electrode standard HS36 G peaked electrode with5 mm thread HS36 Y bifurcated electrode TT 7 Transportion The MultiSafe DSP 3HS36 can be demounted for transportation Turn the test probe and the basic pipe counterclockwise After about 4 turns you can pull the test electrode from the basic pipe For safe transport fix the universal clip at the ball point Note The device may only be used when completely mounted and after successfully performed self test 8 Maintenance The MultiSafe DSP 3HS36 needs to be kept dry and clean The casing and the test probes can be cleaned with clear water without detergents or with a cloth dampened with isopropyl alcohol Make sure regularly that the battery does not leak In case it does you have to replace the electrolyte com
16. n k nnen Sie die Pr fspitze vom Basisrohr abziehen Die Universalklemme l sst sich an der Kugel zur Transportsicherung fixieren Hinweis Das Ger t kann nur im vollst ndig montiertem Zustand und nach durchgef hrtem Eigentest verwendet werden 8 Wartung Der MultiSafe DSP 3HS36 ist stets in trockenem und sauberen Zustand m glichst in einem festen Be h ltnis aufzubewahren Das Geh use einschlie lich der Pr fspitzen kann mit einem mit klarem Wasser ohne Reinigungsmittel befeuchteten Tuch gereinigt werden berzeugen Sie sich in regelm igen Abst nden dass die Batterie ihres Ger tes nicht ausgelaufen ist Bei ausgelaufener Batterie m ssen Sie den Batterie Elektrolyt vollst ndig entfernen und eine neue Bat terie einsetzen Wir empfehlen die Batterie bei l ngerem Nichtgebrauch aus dem Ger t zu entnehmen 8 1 Wiederholungspr fung Die Frist f r die Wiederholungspr fung beim DSP 3HS36 darf 6 Jahre nicht berschreiten je nach Einsatz bedingungen und H ufigkeit der Benutzung kann eine fr here Pr fung empfehlenswert sein Das letzte Pr fdatum befindet sich auf einer Pr fplakette seitlich am Anzeigeteil Das Herstelldatum xxxxx Nr Woche Woche Jahr Jahr ist auf der R ckseite des Anzeigeteils eingepr gt Beispiel 2 27 11 Ger tenummer Woche Jahr Zur Wiederholungspr fung muss das Ger t an den Hersteller eingesandt werden 8 2 Reparatur berpr fung Eine Reparatur ist nur durch den Hersteller ode
17. pletely and insert a new battery During longer disuse we recommend to remove the battery from the device 8 1 Repeated examination Repeated examinations with the DSP3 HS36 may not exceed the time limit of 6 years Depending on operation conditions and frequency a previous inspection may be recommendable The date of the last repeated examination is marked on the test label at the side of the display unit The date of manufacturing xxxxx Nr Week Week Year Year is imprinted on the back side of the device Example 2 27 11 device number Week Year For repeated examination the device has to be send to the manufacturer 8 2 Repair Inspection Repair is only allowed by the manufacturer or explicitly authorised repair shops In case of damages failure of the self test or for detailed inspection calibration please contact service tietzsch de or send the device back to the manufacturer with a description of failure 9 Accessories We recommend a solid casing for transportation and secure storage A une Zi Solid box with aluminium frame 124 x 27 x 12 cm Art No 84330 10 Technical Data Rated Voltage Indication Indicator group 50 36000 V AC DC 3 red LEDs for voltage gt 50 V green LED for standby two line LC display with backlight for indication of voltage frequency type of voltage and battery condition acoustic signal gt 50 V AC 120 V DC land Ill Measurement ranges Accuracy Freq
18. r durch vom Hersteller ausdr cklich erm chtigte Werk st tten zul ssig Bei Besch digung des Ger tes Ausfall des Eigentests oder zur detaillierten berpr fung Kalibrierung wenden Sie sich bitte an service tietzsch de oder senden Sie das Ger t mit Fehlerbeschreibung an den Hersteller 9 Zubeh r F r den Transport und die sichere Aufbewahrung wird ein festes Beh ltnis empfohlen ee u Stabiler Koffer mit Alu Rahmen 124 x 27x 12 cm Art Nr 84330 10 Technische Daten Nennspannung Anzeige Anzeige Gruppe Messbereiche Genauigkeit Frequenzbereich Eingangswiderstand Strom Scheitelwert Einschaltdauer Eigentest Sto spannungsfestigeit Bauform Betriebstemperatur Energiequelle Aufbau Normen Pr fplakette Gewicht Ma e 50 36000 VAC DC 3 rote LEDs f r Spannung gt 50 V eine gr ne LED f r Bereitschaft zweizeiliges LC Display mit Hintergrundbeleuchtung f r die Anzeige von Spannung Frequenz Spannungsart Batteriestatus akustisches Signal ab gt 50 V AC 120 V DC l und Ill 40 1000 V AC DC 5 10 Digits Aufl sung 1 V 1 00 9 99 kV AC DC 5 10 Digits Aufl sung 10 V 10 0 36 0 kV AC DC 5 10 Digits Aufl sung 100 V automatische Bereichsumschaltung 0 200 Hz 119 MO lt 0 4 mA bei 36000 V 15 min Funktion Erdung und Schutzwiderst nde gt 300kV VDE Pr fbericht liegt vor f r Innen Aussenraum Anlagen IP 65 Ger
19. stellen ist es unerl sslich dass Sie vor dem Einsatz Ihres Ger tes diese Bedienungsanlei tung vollst ndig lesen und diese in allen Punkten befolgen sonst besteht Lebensgefahr Bitte beachten Sie folgende Sicherheitsvorkehrungen gt Nur eingewiesenes Fachpersonal mit entsprechender Schutzausr stung darf diese Arbeiten aus f hren Beachten Sie die Mindestabst nde zu anderen unter Spannung stehenden oder geerdeten Anlagenteilen und verwenden Sie pers nliche Schutzausr stung gem den landesspezifischen Unfallverh tungsvorschriften in Deutschland BGV A3 oder VDE 0105 100 gt Die Spannungsangaben auf dem DSP 3HS36 sind Nennwerte Der Spannungspr fer darf nur in Anlagen mit dem angegebenen Nennspannungsbereich benutzt werden gt Eine einwandfreie Anzeige ist nur im Temperaturbereich von 10 C bis 55 C sichergestellt gt Sichere Verbindung zu Erde herstellen und kontrollieren gt Ger t nur unterhalb der achteckigen Begrenzungsscheibe anfassen Pr fspitze und Pr felektrode nicht ber hren gt Die Pr fspitze darf nur oberhalb der roten Grenzmarke an spannungsf hrende oder geerdete Anlagenteile gebracht werden mit allen anderen Teilen des Spannungspr fers muss ein m glichst gro er Abstand gehalten werden gt Die Erdungklemme muss fest mit Erdpotential verbunden sein z B Kugelfestpunkt Die Erdleitung darf keine unter Spannung stehenden Anlagenteile kreuzen gt Spannungspr fer m ssen kurz vor dem Einsat
20. t bei Niederschlag verwendbar 10 C 55 9 V Block IEC 6LR61 Alkali Mangan Anzeige des Batteriestatus Zweipoliger Spannungspr fer mit Festanschluss an Erde zweiteilige Hochspannungspr fspitze zusammenschraubbar aus doppelwandigem GFK Rohr mit vergossener Widerstandsdekade Anzeigeteil im schlagfestem staubdichtem Kunstoffgeh use IP 65 mit unzerbrechlicher Anzeigeabdeckung 10 m Leitung PUR mit Universalklemme f r Stromschienen und Kugelfestpunkte bis 25 mm EN IEC 61243 2 Hochspannungspr fer EN IEC 60071 Sto spannungsfestigkeit weitere angewandte Normen EN IEC 61010 und VDE 0105 100 weiteres siehe Risikoanalyse der letzten berpr fung auf dem Ger t 2 1 kg ca 1430 x 100 x 100 mm Transportl nge demontiert 900 mm Kurzanleitung MultiSafe DSP 3HS36 Achtung Dies ist eine verk rzte Anleitung f r den t glichen Gebrauch Zur Sicherheit ist die gesamte Bedie nungsanleitung des MultiSafe DSP 3HS36 ist in allen Punkten zu befolgen Die Sicherheitsvorschriften sind zu beachten sonst besteht Lebensgefahr 1 e Verbindung mit Erde herstellen Vor Verwendung muss der DSP 3HS36 vollst ndig montiert sein Pr felektrode Basisrohr Spitze Anzeigeeinheit Die Universalklemme fest mit Erde z B Kugelfestpunkt oder Stromschiene verbinden 2 e Funktionstest Achtung Funktionstest vor jeder Pr fung durchf hren um das Ger t in den betriebsbereiten Zustand zu bringen Displaytest Eigentest Ein Aus
21. uency range Input resistance Current peak value On time Self test Sto spannungsfestigeit Construction Operating temperature Power supply Design Standards Test label Dimensions weight 40 1000 V AC DC 5 10 digits resolution 1 V 1 00 9 99 kV AC DC 5 10 digits resolution 10 V 10 0 36 0 kV AC DC 5 10 digits resolution 100 V automatic range switching 0 200 Hz 119 MO lt 0 4 mA at 36000 V 15 min function grounding and protective resistors gt 300 kV VDE test report available for indoor and outdoor installations IP 65 device can be used in moist environments 10 C 55 9V block IEC 6 LR61 alkali manganese indication of battery condition two pole voltage tester with fixed connection to ground two piece high tension test probes screwable made of double walled GRP tube with moulded resistor decade display part made of impact resistant dust proof plastic casing IP 65 with unbreakable display cover 10 m PUR cable with universal clip for condutor bars and fixed ball points up to 25 mm EN IEC 61243 2 high voltage tester EN IEC 60071 surge voltage strength further applied standards EN IEC 61010 and VDE 0105 100 further details see risk analysis of the last examination on the device 2 1 kg approx 1430 x 100 x 100 mm Transportation length demounted 900 mm Brief instructions MultiSafe DSP 3HS36 Attention This is a shortened user instruct
22. z und m glichst auch danach auf Funktion gepr ft werden berpr fen Sie das Ger t an einer bekannten Spannungsquelle und mit dem Eigentest Funktionstest F llt hierbei die Anzeige eines oder mehrerer Systeme aus darf das Ger t nicht mehr verwendet werden gt Die maximal zul ssige Einschaltdauer des DSP 3HS36 betr gt 15 min gt Unbefugte d rfen den Spannungspr fer nicht zerlegen gt Spannungspr fger te m ssen trocken und sauber sein Bei Niederschlag ist das Ger t vor dem Einsatz trocken zu wischen gt Das Ger t darf nicht verwendet werden wenn Besch digungen zu erkennen sind Sichtpr fung Basisrohr Pr fspitze Elektrode Anzeigeeinheit Verbindungsleitung Universalklemme gt Sp testens alle 6 Jahre ist eine Wiederholungspr fung durchf hren zu lassen 3 Allgemeines Um die Batterie zu schonen schaltet sich das Ger t automatisch nach etwa 120s aus wenn keine Messung erfolgt Die Hintergrundbeleuchtung schaltet sich nach 5 s aus OL out of limit auf der Anzeige bedeutet dass der Messwert au erhalb des Messbereiches liegt Blinkt das leere Batteriesymbol auf der Anzeige ist die Batterie vor weiterer Anwendung zu wechseln Vor Verwendung muss der DSP 3HS36 vollst ndig montiert sein Pr felektrode Basisrohr Pr fspitze Anzeigeeinheit Einschalten Ausschalten Der DSP 3HS36 schaltet sich nicht automatisch ein F r Eigentest und Spannungspr fungen muss das Ger t mit dem Ein Aus Tast
Download Pdf Manuals
Related Search
Bedienungsanleitung bedienungsanleitung bedienungsanleitung sky receiver hd bedienungsanleitungen pdf bedienungsanleitung englisch bedienungsanleitung deutsch bedienungsanleitung samsung bedienungsanleitung vw bedienungsanleitung samsung a16 5g bedienungsanleitung jabra evolve2 65 bedienungsanleitung philips fernseher bedienungsanleitung delonghi magnifica s bedienungsanleitung smart watch deutsch bedienungsanleitung deutsch saro hd 200 bedienungsanleitungen englisch bedienungsanleitung auf englisch bedienungsanleitung opel astra l bedienungsanleitung delonghi magnifica evo bedienungsanleitung philips kaffeevollautomat bedienungsanleitung erstellen bedienungsanleitung iphone bedienungsanleitung panasonic tv bedienungsanleitung zeitschaltuhr bedienungsanleitung samsung fernseher bedienungsanleitungen kostenlos in deutsch bedienungsanleitung delonghi dinamica