        (Safety) Temperature limiter (Safety) Temperature monitor B
         Contents
1.              u 2442444 RR nennen  DIMENSIONS  2 laa aaa    Mounting on a standard rail  es A ee ehr    REMOVA ul a    Electrical connection   Installation notes        oooccoonncnconocnncnoncnononancnnnonanncnonanonononcnnnns  Connection diagram nn ee nen  Lead compensation siciliana    Function   Indication and controls     occcooncnccconoccncncncnnnnonanononaconononanones  O TUNCTION dba  S function ina    Starting up    Functional test   TSESUISQUGNCY  rr a  Testing STBs and STWs with O function   when thermocouples are connected     ooconcnnccncccconannnncnnno   Testing STBs and STWs with S function   when thermocouples are connected     ooconcnnccncccconannnncnnnn     Testing STBs and STWs with O  or  S function when connecting resistance thermometers         Test in the event of a fault  Technical data    25    1 Introduction    1 1 Description    The areas of application for  safety  temperature limiters or monitors    S TB or  S TW  are to be found wherever thermal processes have  to be monitored  and where the system must be set to a safe oper   ating condition in the event of a fault  If the permitted temperature  limit is reached  or a fault occurs within the permitted temperature  range  probe break short circuit  component defect  power failure    then the instrument switches off without delay  If the fault is no  longer present  then TB and STB must be reset manually  This can  be done by means of a reset pushbutton on the instrument  or by an  external reset bu
2.     Inductive components in the neighbourhood of the instrument   such as contactors or solenoid valves  must have RC  combinations fitted for interference suppression     The approval of the instrument to DIN 3440 is only valid if the  temperature probes marked with   in Chapter 8    Technical Data     are used   If temperature probes are used which are not marked or listed   then the approval of the instrument and probes must be  checked     12    3 Electrical connection    3 2    Connection diagram       A    The electrical connection  must only be carried out by  qualified personnel                       2 wire circuit    LAW  Lead compensation    resistor    Connection for   Terminals  Relay output 7    common   8 n o   make   230V 2A  9  n c   break   resistive load  Supply L1 line  as on label N neutral  External reset 5  pushbutton 6  Resistance 1 1 2  thermometer in 2       Thermocouple          RON      1  1    Thermocouple 1    Thermocouple 2          13       3 Electrical connection    3 3 Lead compensation    A lead resistance of 0 50 is allowed for internally as standard   10 10  300 or 500  extra Code  to special order     A lead compensation resistor LAW  10 Q  included in the delivery  package when the appropriate extra Code is ordered  is required for  the connection to Pt 100 resistance thermometers with a max   operating temperature of 700  C     Measurement  circuit with  internal comp     for lead  resistance  R    050107100   30 Q or 50 Q       Compensa
3.     Safety   Temperature limiter     Safety   Temperature monitor  to DIN 3440    B 70 1130    Operating Instructions  Version 1   8 98   00354358    Conformance symbol  The instrument conforms with the requirements of  DIN 3440     I cumo E    MESS  UND REGELTECHNIK       DIN 3440    SACHSEN ANHALT       ES If any servicing is required  the instrument must be  returned to the main factory   In accordance with the recommendations of  Germanische Lloyd  specific applications require  the availability of a replacement instrument     Please read these Operating Instructions before  commissioning the instrument  Keep the operating  instructions in a place which is accessible to all  users at all times     Please assist us to improve these operating  instructions  where necessary     We are always grateful for your suggestions     Phone in Germany  06 61  6003 727  from abroad   49 661 6003 0   Fax in Germany  06 61  60 03 5 08  from abroad   49  661 6003 607    Should any difficulties arise during start up  you are  asked not to carry out any unauthorised mani   pulations on the instrument  You could endanger  your rights under the warranty     Please contact the nearest JUMO office or the main  factory     1 1  1 2  1 3  1 4    2 1  2 2  2 3    2 4    3 1    3 2  3 3    4 1  4 2  4 3    6 1  6 2    6 3    6 4    Contents    Introduction   Description sen  Block Structfe cui ke  Type designation nase ee  Registration Number  es    Installation  Location and climatic conditions   
4.   Switching differential Xgg         Satisfactory  range    OFF    Limit value   G       Response in normal operation       gt    G       temperature falls    gt  the relay drops out at U UG      Response after falling below the limit     U lt UG       temperature rises     gt  the relay pulls in automatically at       G Xsa  STW and TW    or has to be reset manually  STB and TB     Response in fault condition   In the event of a fault  probe break short circuit  faulty   electronics  supply failure  the relay drops out    When       the fault has been cleared     D0G Xsd     gt  then the relay pulls in automatically  STW and TW    STB and TB must be reset manually  Only in the event of a  short term power failure   lt  1 min  in the satisfactory range of  the system  will the instrument automatically be enabled  after the power has been restored     17    5 Starting up    The setting of the limit value  must not change by itself under  operating conditions  A clear  cover    which is lead sealable  is therefore provided to prevent  unintentional or unauthorised  adjustment          Swing the clear cover upwards and remove it       Set the required limit on the scale using the limit setting knob   The limit setting can easily be read  even when the clear cover is  in position  The start and end of the range are fixed by stops       After setting the limit  carry out the function test   gt  Chapter 6   and lead seal the clear cover     CS The safety circuit must be reset after
5.  1    96  creepage distances     mains to electronics and probe  gt 8mm  mains to relay  gt  3mm  relay to electronics and probe  gt  8mm    Instrument can be connected to SELV circuits     30    8 Technical data    Test voltages  to EN 60730 1    96 Tab  13 2    Electromagnetic compatibility  to EN 50081 1  EN 50082 2    Ambient conditions  to EN 60730 1  96 Para  2 12 6     normal       Operating conditions   The instrument is designed as a built in device according to     VDE 0160 5 5 1 3 5 88     VDE 0106 Part 100 3 83    Operating position unrestricted   Weight 250g approx   Dimensions  WxHxD  54mm x 70mm x 110mm  Casing   Plastic    Combustibility class VO    With extra Code    GL     The instrument meets Application Category C  according to the GL guideline     Temperature  0 to 55  C  Rel  humidity  not exceeding 100  r H   Vibration  not exceeding 0 7g    Standard accessories      Operating Instructions B 70 1130    2 fixing elements  only for GL version     LAW  only with extra Code 229  231  233  235     31    MEASUREMENT AND CONTROL    M K  JUCHHEIM GmbH  amp  Co  United Kingdom USA   36035 Fulda JUMO Instrument Co  Ltd  JUMO PROCESS CONTROL INC   Germany Temple Bank  Riverway 735 Fox Chase    Phone   49 6 61 60 03 0 GB Harlow  Coatesville  PA 19320   Fax    49661 6003 607 Essex CM20 2TT Phone 610 380 8002    Telex 49701 juf d Phone  0 12 79  63 55 33 800 554 JUMO    email JUMO_de e mail com Fax  0 12 79 63 5262 Fax 610 380 8009    
6.  Short circuit the reset button   Simulate a probe short circuit    O The LEDs S1 and S2 must light up    O The LEDs S1 and S2 must go out after approx  5 sec   Remove short circuit across the external reset button    O The LEDs S1 and S2 light up again    Remove the probe short circuit     O If the probe temperature is within the permitted temperature  range  i e  below the limit setting by the switching differential  for an O function  or above the limit setting by the switching  differential for an S function   then the two LEDs S1 and S2  must go out after approx  5 sec     O For an STW  the external fault indication must go out and the  safety circuit must close     26    6 Functional test    O For an STB  the external fault indication must continue to be  lit up and the safety circuit must remain open  It is only closed  again when the reset button is pressed     Check response after a power failure  STB   In the satisfactory range of the system     Switch off mains   O Wait approx  1 min    Switch on mains     O The LEDs S1 and S2 must light up for approx  5 sec and then  go out     O The external fault indication must go out after  approx   a fur   ther 2 sec and the safety circuit must close automatically     In the event of a fault      Simulate a probe break   O The LEDs S1 and S2 must light up      Remove the probe break   O The LEDs S1 and S2 must go out after approx  5 sec  O The safety circuit remains open      Switch off mains for at least 5 sec     Switch on 
7.  be reset  either manually or by means of a tool  when  the probe temperature has fallen below the limit value by the  amount of the switching differential     Safety temperature limiter STB     Safety temperature limiters are temperature limiters which  in addi   tion  comply with the requirements for enhanced safety according  to DIN 3440       Extract from DIN 3440    1 2 Block structure    Input        9  Fault indicator    O  8  System       1 Introduction    1 3 Type designation    701130       1   2   3   4                kx x   kx kk   kk                                         1  Basic type extensions                               0151 Temperature monitor with O function   0152 Temperature monitor with S function   0153 Temperature limiter with O function   0154 Temperature limiter with S function   0251 Safety temperature monitor with O function  0252 Safety temperature monitor with S function  0253 Safety temperature limiter with O function  0254 Safety temperature limiter with S function           2  Measurement inputs                         001 Resistance thermometer Pt100  in 2 wire circuit   037 W3Re W25Re   042 Fe Con L   043 NiCr Ni K   044 Pt10Rh Pt S   046 Pt30Rh Pt6Rh B             1 Introduction                 3  Supply   02 230V AC   10     15  48   63Hz  05 115V AC   10     15  48   63Hz  08 24V AC   10     15  48   63Hz           4  Extra Codes                                     202 Switching differential 3  C  only for Pt100    205 Switching differ
8.  every switch on or   break in the mains supply  by using the internal or exter   nal reset button  only for TB and STB    Only in the event of a short term power failure   lt  1 min   in the satisfactory range of the installation  will the  instrument automatically be enabled after the power has  been restored     For lead sealing  a hole is pro   vided on each side of the clear  cover  A wire is passed through  these holes to connect the  cover and the casing  The wire  ends are secured by a lead  seal        18    6 Functional test    6 1 Test frequency    The safety temperature monitors and limiters fulfil the requirements  made in Draft DIN 3440 A1 of September 1991     In addition  the instrument must undergo an annual functional test     ES Generally  the functional test always starts from the sat   isfactory range of the system  i e  the fault signal diodes  must not be lit up and the STBs must be reset     It is necessary to short circuit or open the measurement input cir   cuit s  for the functional test  The reset button must also be short   circuited during the test     For a rapid functional test it is therefore recommended that the but   tons    Il  and Ill are included in the measurement or reset circuits     ES When connecting themocouples and buttons it is impor   tant to ensure that no additional thermal e m f occurs   temperature differences at the terminals     When resistance thermometers and buttons are con   nected  it must be ensured that the contact r
9.  mains   O Wait for approx  1 min    Switch on mains     O The LEDs S1 and S2 must light up for approx  5 sec and then  go out    O The external fault indicator must go out after a further 2 sec  approx  and the safety circuit must close automatically     In the event of a fault      Simulate a probe break of the thermocouple 1   O The LEDs S1 and S2 must light up      Remove the probe break of thermocouple 1   O The LEDs S1 and S2 must go out after about 5 sec   O The safety circuit remains open     21    6 Functional test      Switch off mains for at least 5 sec     Switch on mains     O The LEDs S1 and S2 must light up for about 5 sec and then  go out     O The external fault indication continues to be lit up and the  safety circuit remains open  The safety circuit will only close  again  and the external fault indication will go out  when the  reset button is pressed     6 3 Testing STBs and STWs with S function  when thermocouples are connected                                  safety external Li N    circuit fault 230  indicator       ie external  ah reset button  1 probe 2    22         6 Functional test    Short circuit the reset button    Simulate a probe short circuit of thermocouple 1     O  O    O  O    The LEDs S1 and S2 must light up     The external fault indication must light up  The safety circuit  must be open     LEDs S1 and S2 must go out after approx  5 sec     The external fault indication remains lit and the safety circuit  remains open     Remove short 
10.  the fixing elements into the guides on the sides      Insert the unit from above into the rail and swing it down until it  snaps into position  as above       Push the fixing elements up to the rail and tighten them evenly  with a spanner      see diagram on next page      10    2 Installation       2 4 Removal      Insert a screwdriver in the direction of the arrow under the clip       Press the clip down   and swing the unit up at the same time          11    3 Electrical connection    3 1 Installation notes    HM The requirements of VDE 0100    Regulations for the installation    of power equipment with rated voltages up to 1000V    or the  equivalent national regulations must be observed in the choice  of cable material  the installation and the electrical connection of  the equipment     The electrical connection must only be made by properly  qualified personnel     Isolate the instrument on both poles from the supply if there may  be contact with live parts during work     The electromagnetic compatibility  EMC  conforms to the  standards and regulations listed under Technical Data    gt  Chapter 8    Sensor  output or supply cables should be routed separately  from one another  and not laid in parallel     Sensor cables must be twisted and shielded  Avoid running  them close to current carrying components or cables     Do not connect any additional loads to the supply terminals of  the instrument     The instrument is not suitable for installation in hazardous areas 
11. circuit of reset button     O  O    The LEDs S1 and S2 light up again   The external fault indication remains on     Remove probe short circuit     O    If the probe temperature is within the permitted temperature  range  i e  above the limit setting by the switching differential   then the two LEDs S1 and S2 must go out after approx  5  sec     For an STW  the external fault indication must also disappear  and the safety circuit must close     For an STB  the external fault indication must continue to be  lit up and the safety circuit must remain open  It will only  close again when then reset button is pressed     Repeat the procedure for thermocouple 2     Check the response after power failure  STB only   In the satisfactory range of the system     Switch off mains     O    Wait for approx  1 min      Switch on mains   O The LEDs S1 and S2 must light up for approx  5 sec and then    go out     23    6 Functional test    O The external fault indication must go out after a further 2 sec   approx   and the safety circuit must close automatically     In the event of a fault      Simulate a probe short circuit of thermocouple 1   O The LEDs S1 and S2 must light up      Remove the probe short circuit of thermocouple 1  O The LEDs S1 and S2 must go out after approx  5 sec   O The safety circuit remains open      Switch off mains for at least 5 sec     Switch on mains     O The LEDs S1 and S2 must light up for approx  5 sec and then  go out     O The external fault indication con
12. ential 10  C   206 Switching differential 30  C   208 Switching differential 100  C   229 Lead resistance 1Q internally compensated  231 Lead resistance 100 internally compensated  233 Lead resistance 30Q internally compensated     235 Lead resistance 50Q internally compensated  245 Internal reset button  extra Code with TB only   062 GL         Lead compensation resistor LAW  10Q  is included in the delivery       Accessories       External reset button RT  Sales No  70 97097865       Mounting plate BS  Sales No  70 000591 72          Lead compensation resistor LAW  10Q   Sales No  70 00322800       1 4 Registration number  For Type 701130       TB TW STB STW 1091 97       2 Installation    2 1 Location and climatic conditions  The location and the climatic conditions must meet the    requirements defined in the specifications under Technical Data      Chapter 8      2 2 Dimensions                         7 110  119 5  Dimensions with lateral    fixing elements   only for GL version                                       mm inch   33 1 30   49 1 93   51 2 01   54 2 13   66 6 2 62   PERE  70   2 76    MY   A  119 5  4 70       2 Installation    2 3 Mounting on a standard rail  or a mounting plate    The instruments are designed as built in units and are protected to  IP20 as standard       Insert the instrument from above into the standard rail or into the  cut out of the mounting plate    and swing it down until it snaps  into position         Mounting the GL version     Push
13. esistance is  not too high   0 4Q   1  C error      o Carry out a functional test after every malfunction     19    6 Functional test    6 2 Testing STBs and STWs with O function  when thermocouples are connected          safety external Li N  circuit fault 230V   indicator       Lenna external  reset button        1 probe 2      Short circuit the reset button    Simulate a probe break of thermocouple 1   O The LEDs S1 and S2 must light up     O The external fault indicator must light up  The safety circuit  must be opened     O The LEDs S1 and S2 must go out after about 5 sec     O The external fault indicator remains lit up and the safety cir   cuit remains open     20    6 Functional test      Remove the short circuit across the reset button   O The LEDs S1 and S2 light up again   O The external fault indicator remains on      Remove the probe break     O If the probe temperature is within the permitted temperature  range    e  below the limit setting by the switching differential   then the two LED S1 and S2 must go out after approx  5 sec     O For an STW  the external fault indication must also disappear  and the safety circuit must close     O For an STB  the external fault indication must continue to be  lit up and the safety circuit must remain open  The safety cir   cuit is only closed again when the reset button is pressed       Repeat the procedure for thermocouple 2     Check response on power failure  STB    In the satisfactory range of the system     Switch off
14. mains     O The LEDs S1 and S2 must light up for approx  5 sec and then  go out     O The external fault indication continues to be lit up and the  safety circuit remains open  Only when the reset button is  pressed  will the safety circuit close and the external fault  indication go out     27    7 Test in the event of a fault    In the event of a system fault  the instrument switches off the sys   tem  This condition is indicated by LED S1 lighting up  S1 and S2  on instruments with enhanced safety   The fault is signalled simulta   neously by the external fault indication  In this condition  the relay of  the temperature limiting device  STB  TB  STW  TW  is not operated     Initial condition  STB has switched off the system        Fault indicators are lit    Fault indicators are off       The fault is still present in the  system   over undertemperature  probe  break short circuit       Press the reset button  at  least 5 sec  until S1 and S2  go out    If the safety circuit remains    open  the system and the  probe circuit have to be  checked             Press the reset button    If the instrument remains inhib   ited after pressing the reset  button  the replacement instru   ment must be installed and the  functional test carried out        28       8 Technical data    Inputs    Resistance thermometer  Pt100 in 2 wire circuit  0   120  C    0   300  C    0   400  C    0   600  C    200   500 C    Ambient temperature error  0 8  C 10  C  Lead compensation   A lead resis
15. tance of 0 5Q is allowed for internally as standard   10  109  30Q or 50Q on request  A lead compensation resistor  LAW  100  is required for connection to resistance thermometers  with a max  operating temperature of 700 C     Double thermocouples    NiCr Ni K  200    600 C   400    800 C   600   1000 C   800   1200  C  Pt10Rh Pt S  400    800  C     800   1200  C   1000   1400  C  1200   1600  C    Pt30Rh Pt6Rh B  800   1200 C   1000   1400 C   1200   1600 C  1400   1800 C    Fe Con L  50    450  C   200    600  C   500    900  C  W3Re W25Re  1600    2000  C    Ambient temperature error  2 0  C 10  C      For temperature probes used in accordance with DIN 3440  the  max  limit temperature of the instrument is determined by the  upper meas  temperature of the selected temperature probe     29    8 Technical data    Outputs    Relay  with floating changeover contact    Switching capacity  2 A 230 V AC  resistive load  protected by fuse 2A M    Contact life  100 000 switching operations at rated load    General data  Switching point accuracy  2  of span    Switching differential 3  C  for Pt100 only    10  C  30  C or 100  C    Supply  230V AC   10     15  48   63Hz  115V AC   10     15  48   63Hz  24V AC   10     15  48 63Hz  Power consumption 4 VA approx     Permissable ambient temperature 0 to  55   C  Permissable storage temperature  40 to  80   C  Climatic conditions rel  humidity 75  max   no condensation    Protection IP20  to EN 60529     Electrical safety  to EN 60730
16. tinues to be lit up and the  safety circuit remains open  Only when the reset button is  pressed  will the safety circuit close and the external fault  indication go out     24    6 Functional test    6 4 Testing STBs and STWs with O  or  S function when connecting resistance  thermometers                external LI N  circuit fault 230V   indicator             external  Pt 100 reset button      Short circuit the reset button    Simulate a probe break   O The LEDs S1 and S2 must light up     O The external fault indication must light up  The safety circuit  must be open     O The LEDs S1 and S2 must go out after approx  5 sec     25    6 Functional test    O The external fault indication continues to be lit up and the  safety circuit remains open     Remove the short circuit across the reset button   O The LEDs S1 and S2 light up again    O The external fault indication remains on   Remove the probe break     O If the probe temperature is within the permitted temperature  range  i e  below the limit setting by the switching differential  for an O function  or above the limit setting by the switching  differential for an S function   then the two LEDS S1 and S2  go out after approx  5 sec     O For an STW  the external fault indication must also go out and  the safety circuit must close     For an STB  the external fault indication must continue to be lit  up and the safety circuit must remain open  The safety circuit will  only close again when the reset button is pressed    
17. tion condition  RL   Reomp   RLF    RL internally compensated lead resistance of the  measuring circuit    Rcomp resistance of the lead compensation resistor LAW  RLF resistance of the probe leads    14    4 1    4 Function    Indication and controls             Screw terminals  max  2 5mm        Reset button  extra Code with TB only        Limit setting knob       Limit scale          0000    Fault indicator for channel 1  S1  and channel 2  S2   S2 only for STB and STW       Q    Lead sealable clear cover             Plastic casing       15       4 Function    4 2 O function    Relay Switching differential Xg y  ON    Satisfactory  range       OFF  Limit value Ue       Response in normal operation    U lt OG       temperature rises    gt  the relay drops out at    UG      Response after rising above the limit     O gt dg       temperature falls     gt  the relay pulls in automatically at 0 O0G    Xgq  STW and TW    or has to be reset manually  STB and TB     Response in fault condition   In the event of a fault  probe break short circuit  faulty   electronics  supply failure  the relay drops out    When       the fault has been cleared     DS dag     gt  then the relay pulls in automatically  STW and TW    STB and TB must be reset manually  Only in the event of a  short term power failure   lt  1 min  in the satisfactory range of  the system  will the instrument automatically be enabled after  the power has been restored     16    4 Function    4 3 S function    Relay  ON  
18. tton  The flow of energy is only enabled again when  the temperature is lower  O function  or higher  S function  than the  preset limit temperature by the amount of the switching differential   In the event of a short term power failure   lt  1 min  within the satis   factory range of the system  the instrument is enabled automatically  after the power has been restored  The amount of the switching dif   ferential is 3  C  10  C  30  C or 100  C     The analogue limit setting knob for the limit temperature is mounted  on the front panel  An unintentional or unauthorised adjustment of  the limit setting is prevented by a clear cover which can be lead   sealed  The instruments are intended for use as built in units for fix   ing onto standard rails to EN 50022 35  The screw terminals for the  electrical connection  max  conductor cross section 2 5mm   are on  one wiring level     The instruments function over defined temperature ranges between  0 and 2000   C     Temperature monitor TW     Temperature monitors are devices which  after cutting out  are auto   matically reset when the probe temperature has fallen below the  preset limit value by the amount of the switching differential     Safety temperature monitor STW     Safety temperature monitors are temperature monitors which  in  addition  meet the requirements for enhanced safety to DIN 3440     1 Introduction    Temperature limiter TB     Temperature limiters are devices which are locked out after cutting  out  They can
    