1. NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC d Mains power supply left to right earth neutral live Temperature sensor Battery Channel 1 relays left to right fire action fault Channel 2 relays left to right fire action fault o ww es NS External reset 5 FASD700 aspirated smoke detectors Installation manual WWW UKPANELS COM 2 2 Detector installation Up to two detectors may be installed For the FASD710 FASD712 panels conventional or analogue addressable detectors may be used not supplied For the FASD715 FASD717 panels laser detectors are supplied 2 2 1 Connecting detectors To connect the detector s 1 Remove the panel front cover 2 Connect the loop terminals of the detector s to the 2 way connector block s on the inner panel see Figure 3 Panel detector connection Figure 3 Panel detector connection 2 2 2 Configuration for analogue addressable detectors FASD710 FASD712 LR A flow fault is reported as a device fault on detector 1 Figure 4 FASD710 FASD712 analogue addressable detector connection To 24 VDC power supply 4 Relay contact Loop in to fire panel 5 To detector 1 Loop out to fire panel 6 To detector 2 FASD700 aspirated smoke detector Installation manual 6 WWW UKPANELS COM Note For detector connection details and for alarm end of line resistor values refer to the detector fire panel manual In the event of a fau
2. 1 1 Product description The FASD700 range of aspirated smoke detectors includes FASD710 and FASD712 panels conventional or analogue addressable detectors FASD715 and FASD717 panels laser detectors All panels are IP50 rated An optional IP65 rating is available to allow use in many harsh environments and where regular hosing is performed 1 1 1 FASD710 and FASD712 panels FASD710 and FASD712 panels have the following features Installation of up to two conventional or analogue addressable detectors not supplied providing the ability for failsafe redundancy or mixed detection strategies High performance aspirator and flow monitoring circuit The flow level is displayed on a 10 element bar graph with adjustments for high and low flow thresholds Flow failure is reported to the central panel as a device fault on the primary detector In line air filter to remove dust particles from the air sample This is housed in a removable transparent cartridge enabling rapid inspection and maintenance Closed loop sampling the exhausted air can be completely returned to the sampled area making in ideal for use in small spaces 1 1 2 FASD715 and FASD717 panels FASD715 and FASD717 panels have the following features Two laser detectors supplied in single or two channel configurations This gives a large monitored area using sampling holes in the place of point detectors The FASD717 has two pipes and can cover twice the area
3. the following additions Figure 6 FASD715 FASD717 front panel and display LEDs 0 OO 1 Alert alarm 4 Smoke detector fault 2 Action alarm 5 Isolate 3 Fire alarm 6 Reset 11 FASD700 aspirated smoke detectors Installation manual WWW UKPANELS COM 3 3 2 FASD715 FASD717 functions Access the required funtion as described in section 3 1 Selecting and programming functions The relevant LED will flash continuously to indicate the active function Table 2 FASD715 FASD717 functions Function Calibration mode Code entry See section 3 1 1 Code entry The Code entry LED flashes To RESET the panel press SELECT when the Reset LED is flashing Select Isolate channel The Isolate LEDs flash constant illumination when set Set fan speed The Power LED flashes Set sensitivity of bar graph to changes in airflow velocity The Flow OK LED flashes Select the bar graph LED segment above which the Flow HI LED will be illuminated The Flow HI LED flashes Select the bar graph LED segment below which the Flow LO LED will be illuminated The Flow LO LED flashes Set smoke detector ALERT alarm threshold The Alert LED flashes Set smoke detector ACTION alarm threshold The Action LED flashes 10 Set smoke detector FIRE alarm threshold The Fire LED flashes 11 Select Mains Battery fault detection The general Fault LED flashes Mains Battery LED flashes if sele
4. FASD7OO aspirated smoke detectors Installation manual WWW UKPANELS COM 3 2 2 FASD710 FASD712 functions Access the required funtion as described in section 3 1 Selecting and programming functions The relevant LED will flash continuously to indicate the active function Table 1 FASD710 FASD712 functions Function Description Code entry See section 3 1 1 Code entry The Code entry LED flashes Set fan speed The Power LED flashes Set sensitivity of bar graph to changes in airflow velocity The Flow OK LED flashes Select the bar graph LED segment above which the Flow HI LED will be illuminated The Flow HI LED flashes Select the bar graph LED segment below which the Flow LO LED will be illuminated The Flow LO LED flashes Select Mains Battery fault detection The general Fault LED flashes Mains Battery LED flashes if selected Calibrate flow sensors at zero and selected airflow speed The Fan fault LED flashes Fan and Power LEDs flash during calibration Exit function selection and return to normal mode A 20 second time out function will also exit calibration mode 3 2 3 Unit alarms Airflow or Power fault 1 relay FASD700 aspirated smoke detector Installation manual 10 WWW UKPANELS COM 3 3 FASD715 FASD717 operation 3 3 1 Display LEDs The FASD715 FASD717 panels use the same interface and LEDs as the FASD710 FASD712 panels see Figure 5 with
5. FM 15 FASD700 aspirated smoke detectors Installation manual WWW UKPANELS COM Ce 1052955 WWW UKPANELS COM
6. GE Security FASD700 aspirated smoke detector installation manual version 3 0 january 2005 GE imagination at work WWW UKPANELS COM http www geindustrial com ge interlogix emea 2005 GE Interlogix B V All rights reserved GE Interlogix B V grants the right to reprint this manual for internal use only GE Interlogix B V reserves the right to change information without notice WWW UKPANELS COM CONTENTS 1 Ntro dUCtiON Et 4 1 4 ProductdesScriptlOh A Sita 4 2 Installation enia oceans LS Ici nl 5 2 1 J Electrical conriectioris oot A A he e eee iot es Steeles aad egere Tee eee 5 2 2 Detector installato sa a e eeu os tale ta arta tu ae ta itv iD 6 23 Panel installation yer recede EE e a e e ur estos ed tere 7 2 4 Pipeunstallation 3 A inve dl oe e eat teat edhe tu etta odes eset tune 7 2 5 External conhectiloris erc i eee sesh hitters eis mua ve muris AAA evi ee ate Rea oT Rte dens 7 3 User QUIE pm 8 3 1 Selecting and programming functions ssssse een emm rr 8 3 2 FASD710 FASD712 operation cccccccceceeeceeeecncce cece ee teeeceaeeeeceeeeeeeeeaaeeeceeeeeseeeeeaneeeeeeeeeeeneees 9 3 9 FASD715 FASD7T1 operatlon inert eit A A a bd 11 4 Maintenance cx0cciiii ete decide deett etsi acct ected alo Era 14 5 Technical specificatlons 5 eiie as Ere Deeds 15 3 FASD700 aspirated smoke detectors Installation manual WWW UKPANELS COM 1 INTRODUCTION
7. cted 12 Calibrate flow sensors at zero and selected airflow speed The Fan fault LED flashes Fan and Power LEDs flash during calibration 13 Exit function selection and return to normal mode A 20 second time out function will also exit calibration mode Smoke detector level displayed as cumulative bar graph on each display 3 3 3 Unit alarms CH1 FIRE CH1 ACTION CH2 FIRE CH2 ACTION 4 relays CH1 smoke detector airflow or power Fault 1 relay CH2 smoke detector airflow or power Fault 1 relay FASD700 aspirated smoke detector Installation manual WWW UKPANELS COM 12 3 3 4 Bar graph levels 13 The bar graph on the front panel indicates the level of smoke being detected Table 3 shows how the levels on the bar graph correspond to the smoke levels being detected These are also the levels at which the alarms can be set Table 3 Bar graph levels Bar graph LED Obscuration metre 1 0 065 0 098 0 164 0 327 0 655 1 637 3 273 4 887 Oooo INIO ay AJOJN 6 516 FASD700 aspirated smoke detectors Installation manual WWW UKPANELS COM 4 MAINTENANCE The filter should be inspected every six months This is housed in a removable transparent cartridge enabling rapid inspection and maintenance The lifespan of the filter will depend on the installation environment A dirty filter will reduce airflow and lower
8. keys located on the side of the unit 1 Press and hold the SELECT and CHANGE keys simultaneously for 1 second to initialise function selection 2 Press and hold the SELECT key to step through each function Each LED on the front panel will be illuminated sequentially Keep the SELECT key pressed until the LED for the function you wish to change is selected 3 Press and hold the CHANGE key to modify the setting A complete list of available functions for each panel is available in sections ES 3 2 2 FASD710 FASD712 functions and 3 3 2 FASD715 FASD717 functions 3 1 1 Code entry The code 510 must be entered to allow any function change To enter the code 1 Initialise function selection see above and select the Code entry LED Press change The Code entry LED will flash 2 Press and hold the CHANGE key until the number 5 LED on the bar graph is illuminated Press the SELECT key 4 Repeat steps 1 to 3 until the complete access code 510 has been entered The Unlocked LED will flash when the code has been entered correctly FASD700 aspirated smoke detector Installation manual 8 WWW UKPANELS COM 3 2 FASD710 FASD712 operation 3 2 1 Display LEDs Figure 5 FASD710 FASD712 front panel and display LEDs 009 oo 0 0000000000 1 Power 6 Fan fault 2 General fault 7 Bar graph of airflow speed 3 Mains fault 8 Code entry 4 Battery low 9 Unlocked 5 Airflow ok high low 9
9. lt on the FASD710 FASD712 panel the relay on the main PCB will open the fault monitor line DET1 This will give the fault signal on the fire panel 2 3 Panel installation The panel should be secured to a suitable surface using the 4 corner fixing points 2 4 Pipe installation ES For pipe installation guidelines refer to the FHSD700 Ducts Installation manual Note the following A ABS UPVC copper or stainless steel pipe may be used Pipe with an outer diameter of 25 mm or 26 7 mm may be used An adapter is required for used with 25 mm pipe Pipe lengths are cut as required and joined by sockets permanent solvent welded or socket unions removable Smoke tests should be performed before planning and installing the pipe network CAUTION Do not use T joints in low pressure wide bore systems These make pipe design and air flow calculation difficult to predict accurately 2 5 External connections The panels allow the following external connections 2 5 1 FASD710 FASD712 panels Mains supply 24 VDC External loop disconnect alarm relay optional I O module optional 2 5 2 FASD715 FASD717 panels Mains supply 24 VDC Alarm relays RS232 Isolate External loop disconnect alarm relay optional I O module optional FASD700 aspirated smoke detectors Installation manual WWW UKPANELS COM 3 1 Selecting and programming functions Panels are programmed using the SELECT and CHANGE
10. of the FASD715 High performance aspirator and flow monitoring circuit to ensure a constant monitored flow level which can be displayed on a 10 element bar graph with adjustments for high and low flow thresholds Three alarm levels give warnings at their pre set levels In line air filters to remove dust particles from the air samples These are housed in removable transparent cartridges enabling rapid inspection and maintenance RS232 Modbus port to download all the data that is logged within the unit This can then be used to look at events or trends over a period of time In addition to the above FASD715 panels also have the following features Closed loop sampling whereby the exhausted air can be completely returned to the sampled area Can be configured to require both detectors to go into alarm to avoid false discharges of suppression systems By using two independent detectors this removes the need for two separate systems FASD700 aspirated smoke detector Installation manual 4 WWW UKPANELS COM 2 INSTALLATION 2 1 Electrical connections A X WARNING 7he power supply should not be connected until all other Z connections have been completed To access the PCB connectors the inner cover of the panel must be removed Figure 1 PCB connectors for FASD710 FASD712 panels 24V ov Battery Fault relay Loop in Bo me Loop out Figure 2 PCB connectors for FASD715 FASD717 panels QO GQ
11. the accuracy of smoke detection To change the filter 1 Remove the panel cover 2 Remove the filter from the acrylic housing 3 Insert the new filter 4 Replace the panel cover FASD700 aspirated smoke detector Installation manual 14 WWW UKPANELS COM 5 TECHNICAL SPECIFICATIONS Dimensions FASD710 l EASDT12 y te thee e rale et iet tides 254 x 180 x 165 mm Dimensions FASD 7 15 FASDT17 y imet tee Fiere eis 254 x 180 x 112 mm Maxim rm number of detectors reete tia does abbecele illes 2 Filtration E Cartridge dust particle filter Flow monitoring Thermal device hi lo thresholds 10 element indication loop fault reporting Supply VORIGE tcm ED T M Pi RR 24 VDC Supply current without aspirating pipe eene nennen nennen 460 mA Supply current Dependant on fan speed pipe length sssssssssee See Table 4 Maximum pipe length per channel enm een rr 100 m lacune IP50 IP65 optional Operating Temperature ceci ette ode eter ee utr ome red etie etat ae 10 to 60 C Operating hu rnidity ecce tecti rit eoe dicc be Eae c Minceur heo 10 to 9596 RH non condensing Table 4 Fan speed supply current with 20 m pipe length and 6 mm end hole Fan speed Supply current mA 9 330 8 260 7 200 6 160 5 125 4 100 3 75 2 60 1 50 0 50 Figure 7 Static Pressure and CFM graph for fan at 2600 rpm and 3600 rpm mm H O C