        LED Quickfit and Remote Powerpack Installation Manual
         Contents
1.  Trouble Shooting Guide Warranty Information    GREETINGS   Congratulations on choosing to use this Thomas  amp  Betts product  This document is designed to assist you during the installation of   this product  so for the safety of yourself and others  Thomas  amp  Betts recommends that you read this document  thoroughly before commencing installation    The Quickfit range of fittings as the name implies  are designed to be fitted quickly  These are advanced pieces of electronic equipment  and when treated with due care and maintained through regular and appropriate servicing  will perform without trouble for many years  to come        SAFETY WARNING   In Australia and New Zealand  only licensed electricians are permitted by law to work with 240 Volt electrical installations    Do not attempt to install or connect this product unless you are a licensed electrician    Turn off and isolate the electrical supply before connecting this fitting to the building wires    Do not touch the terminals of the terminal block when the light fitting is energised    The only user serviceable parts are the lamp s    Do not tamper with the fitting or the warranty will be void    As the installer  it is your responsibility to ensure compliance with all relevant building and safety codes   ie  AS3000  AS NZS2293    Refer to the applicable standards for data and mains cabling installation procedures and requirements     NEXUS LX  DATA CABLE SYSTEM    The Nexus range of light fitting are designed 
2.  are to be  connected to plastic weatherproof housing     12  Use hole plug set grommet provided to protect the remote power cable as it passes through cable entry hole in the Quickfit  mounting bracket  The cable entry into the housing must be sealed via a grommet  conduit bush or similar in order to maintain the  IP rating of the housing     13  Attach the LED Quickfit exit fitting to the mounting bracket by aligning the top left hand end of the unit  the end without the  protruding electrical connecting metal lugs  with the large cut away slot towards the left hand end of the bracket  Slip the left hand  end of the unit up into the slot in the left hand end of the bracket  Step  1  in Figure 1  and hold the unit horizontal to and parallel  with the bracket  It should be approximately 50mm to the right of its final destination  Simply slide the unit  Step  2  in 50mm to the  left along and into the bracket to engage the connections and the locking tab  Once in place  the exit unit cannot be removed from  the bracket without the use of a tool  a small screwdriver  to push in the locking tab at    D    in Figure 1  Ensure the correct pictograph  inserts have been attached to the diffuser assembly           Copyright 2013  Thomas  amp  Betts Australasia ABN  062 074 810 898  Rev  1 0 15April2013 2    Complete Solutions in Emergency Lighting STANILITE    Quickfit Insert here  Mounting to remove  Bracket    For Ceiling Mount  Screw through holes  labelled    A            For Wal
3.  do not install the unit and  notify the Thomas  amp  Betts Product Support Hotline in Australia on 1300 666 595     2  Ifall looks okay  proceed with the installation   3  Remove the power supply unit s cover  place the base against the wall and mark the position of the mounting screw holes     4  Determine the mains cable entry direction which can be from rear  side or top and remove the appropriate cable entry knock out   for LX fitting  remove the data cable   s knock out as well   For plastic enclosure  drill a 20mm hole at the middle of the base or side  to suit the mains cable entry  Remove all sharp edges or burrs around the hole     5  Secure the power supply base to the wall using appropriate fasteners to suit the building material  not provided due to the wide  variety of building construction materials      6  Run the mains and 10m power cable as appropriate through the cable access holes  Use the cable gland provided to protect the  4 core cable  supplied  to the remote exit sign  and use appropriate protection for the mains cable where it enters the nousing     7  Terminate the mains cable and remote 4 core cable to the mains and remote terminal blocks as labeled  Pay particular attention to  ensure that the remote cable pairs are correctly identified and terminated to the correct positions on the remote terminal block Be  careful with multi strand conductors that all of the strands are twisted together before insertion into the terminal  Any strand that  inadve
4. 1  on the front of the bracket towards the right hand end of the fitting  to ease   the locking tab into the fitting and away from the bracket  The unit is then free to slide to the right along the bracket for about 50mm  at  which time the slots line up and it can be lowered away from the bracket  allowing the two to separate  The unit will automatically switch  into emergency mode because it has been removed from the power supply  It will stay on emergency until such time as the battery cut   off threshold is reached or it is reconnected back onto the power supply  whichever happens first  When the unit is reconnected to the  supply  it will need time to recharge its battery before it will be capable of a full length discharge again  The ability of the unit to operate  on emergency is determined by the age  charge level  operating temperature conditions and environmental circumstances of the battery  in the unit     TESTING PRECAUTIONS   If the unit is to be left permanently connected to the mains supply from now on  you will need to allow it 24 hours to charge its battery and  then you will have to conduct a manual discharge test as per the requirements of AS NZS2293 2  Presently  at the time of writing   the  standard requires that units should operate in emergency mode for a period not less than 2 hours for their first test upon installation and  for not less than 90 minutes thereafter once every 6 months  You will need to keep the records for the initial test and enter 
5. Complete Solutions in Emergency Lighting STANILITE    CONSTRUCTION SITES   Continuously switching on and off of the unit   s mains supply during the installation process  due to building works or for some other  reason   could cause the unit s to discharge and charge their batteries many times over a short period  This may shorten the life of the  battery  Thomas  amp  Betts does not recommend such practices and may not honour any warranty on the life of the batteries or the lamps  when subjected to such harsh operating conditions  The unit s are designed to be regularly discharge tested once every 6 months as per  AS NZS2293 2  Deliberate consistent discharge testing is considered an abuse of the fittings     Emergency Light LED Flash Patterns for Nexus Fittings    LX  Yellow static   LX RF  Red static  LX RF  Red flashing   LX  Green   Off flashing  LX  Red   Yellow flashing       LX RF  Green on steady    TROUBLE SHOOTING GUIDE  If you ve installed and connected the unit as per the instructions listed earlier and it doesn   t work properly  use the following table as a  guide to fixing the problem  Look up the type of fault in the left column and check the possible causes from the right column        Unit not inserted into the base properly  or    1 Lamp and LED not lit AC mains supply not connected  or  Test switch damaged    AC mains supply turned off  or  2 Lamp not lit but LED is lit Lamp damaged  or  Battery incorrectly inserted    3 Lamp is lit but LED not lit Test s
6. l Mount  Screw through holes  labelled    B    via slot    C           ot Terminal Block  p   Cable Entry    To fit unit to Mounting  Bracket Insert at 1 then 2       Figure 1  Quickfit Insertion Diagram  amp  Internal View    14  Once powered up  the normal AC LED light source will energise and remain lit  The emergency function of the light fitting will only  operate when the normal lighting power supply fails or when somebody presses the manual test button located on the front of the  unit  Red LED indicates that the power is connected and the battery is charging     15  Check the exit fitting and power supply unit s battery operation to ensure that the installation was successful  When powered  up  allow five minutes to give the battery a small charge  then press the manual test button located at the front face of the power  supply unit  Hold the test button in for a few seconds and observe the operation of the LED light source switching from mains to  the emergency mode     16  Refer to the table on page 4 and the Nexus LX RF User  amp  Technical Guides for detailed descriptions of all possible LED patterns  and their meanings  If the exit unit does not work  refer to the trouble shooting guide for possible causes and remedy     17  If the commissioning test was successful  install the clear housing to the weatherproof unit and cover to the power supply unit     TO REMOVE THE UNIT FROM THE MOUNTING BRACKET   Insert a small screwdriver into the slot  at    D    in Figure 
7. rtently comes into contact with their neighboring terminal or the metal frame of the fitting will cause undesirable results when  the fitting is powered  Incorrect wiring will damage the unit  Ensure that the double insulation of the cable s passes complete into  the terminal block enclosure so that no single insulation is exposed     8  _ This step is for RF fittings only  mount the antenna to the side panel  Collect the MAC address by removing the peel off sticker  section and locating it on your floor plan or spreadsheet     9  This step is for LX fittings only  terminate the data cable to the two way terminal block marked    data     If looping data cable  ensure  that the screens are joined together     10  Run the 10m remote cable to the weatherproof enclosure  Follow instruction 29 01069 to mount the weatherproof unit in place and  drill the cable access hole to suit     11  Feed the remote cable into the weatherproof unit  double check the cable management and allow adequate length to the Quickfit  bracket   s termination block before trim the cable  Strip and connect wires to the Quickfit bracket   s terminal block as labeled and  wire colour coded  again paying particular attention to correctly identify the two pairs  Take care while stripping the twisted colored  pairs and double check the wiring  Incorrect wiring will damage the electronic components    Warning  Mains cable should be terminated to the remote power supply unit only  No mains or mains carrying cable
8. them into the  building emergency services logbook    If the unit isn   t permanently connected to mains supply at this time  you are responsible to give it the initial 2 hour test when you do  connect it permanently to the mains supply           Copyright 2013  Thomas  amp  Betts Australasia ABN  062 074 810 898  Rev  1 0 15April2013 3    
9. to be connected together into a special communication network over a Level 4  or higher   high speed data single twisted pair cable  The Nexus LX User  amp  Technical Guide describes all you need to know to successfully install  a Nexus project  Ask for it from your supervisor  from your employer or from your nearest Thomas  amp  Betts product supplier  The network  cabling of the building must be installed as per the procedure detailed in the Nexus LX User  amp  Technical Guide  No mains or mains  carrying cables are to be connected to the data terminals or cables     NEXUS RF  WIRELESS SYSTEM    The Nexus RF range of light fitting are designed to be connected together into a special RF communication network  The installation of  this product is no different to Standard product  The commissioning of the Nexus RF product is done by Thomas  amp  Betts service personal   please contact Product Support Hotline for more information in Australia on 1300 666 595           Copyright 2013  Thomas  amp  Betts Australasia ABN  062 074 810 898  Rev  1 0 15April2013 1    Complete Solutions in Emergency Lighting STANILITE    INSTALLATION INSTRUCTIONS    Note  These instructions are for the power supply unit s wiring only  For mounting instructions of Weatherproof Housing refer to Doc No   29 01069  Quickfit Weatherproof Exit   LED Quickfit Weatherproof Housing Installation Manual      1  Remove the unit from the packaging and inspect it for damage or imperfections  If any damage is found 
10. witch damaged  or  Battery not connected  4 The lamp doesn t switch to emergency mode when the Test switch damaged  test button is pressed    Battery not yet charged  allow up to 24 hours        5 The lamps works momentarily on emergency when the  d test button is pressed   the unit still doesn   t work after checking these possible causes  contact Thomas  amp  Betts Service in Australia on 1300 666 595  Monday  to Friday  8 30am to 4 30pm  AEST  and ask for help  Our trained service personnel will usually be able to take your call immediately and  assist you in resolving your difficulty  Thomas  amp  Betts is committed to providing valuable Through Life Support for its products           Copyright 2013  Thomas  amp  Betts Australasia ABN  062 074 810 898  Rev  1 0 15 April 2013 4       STANILITE    Doc No  29 01113    Thomas amp Betts       A Member of the ABB Group       Complete Solutions in Emergency Lighting    Thomas  amp  Betts Australasia  ABN 062 074 810 898  Head Office  Unit D3  3 29 Birnie Avenue  Lidcombe NSW 2141  Australia  Manufacturing  23a Nyrang Street  Lidcombe NSW 2141  Australia  Telephone    61  1300 666 595 Facsimile    61  1300 666 594    LED Quickfit and Remote Powerpack  Installation Manual  PSLED1W6  PSNRFLED1W6  PSNXSLED1W6   WPSLED1W6  WPSNRFLED1W6  WPSNXSLED1W6    What   s Inside the box  Electrical Safety Warning   Remote Powerpack for LED Quickfit  Installation Instructions 10 metre long Remote Cable    Testing Precautions Installation Manual 
    