LED Flood Light Installation Manual
Contents
1. STANILITE Complete Solutions in Emergency Lighting Lamp Head Termination Lamp Head Earth Lug Connection 10 Position the enclosure s key way slots to the mounting screws slide it in place and tighten the screws to secure the unit to the wall 11 Plug the power cord to the power point For mains hard wiring remove the power cord strip 9mm insulation length from the mains cable connect and terminate wires to the terminal block Be careful with multi strand conductors that all the strands are twisted together before insertion into the terminal block Any stray strands that inadvertently come into contact with their neighboring terminal will cause undesirable results when fitting is powered Data connection for Nexus LX product installation The same colour wire from each data cables connects to the terminal marked The other colour wire from each of the data cables connects to the terminal marked No mains or mains carrying cables are to be connected to the data terminals or cables 12 Check operation of the unit to ensure that the installation was successful When powered up allow a few minutes to give the battery a small charge then press the manual test button located at the top right hand side edge of the unit Hold the test button in for a few seconds and observe the operation of the lamp switching from mains to the emergency mode If the lamp on emergency mode works momentarily that s okay Try again in a few more m
2. sending Flood Units for repairs make sure that the LED lamps are included TESTING PRECAUTIONS If the unit is to be left permanently connected to the mains supply from now on you will need to allow 24 hours for the battery to fully charge after which you must conduct a manual discharge test as per the requirements of AS NZS2293 2 Presently at the time of writing the standard requires that units operate in emergency mode for a period not less than 2 hours for their first test upon installation and for not less than 90 minutes thereafter once every 6 months You will need to keep the records for the initial test and enter them into the building emergency services logbook If the unit isn t permanently connected to mains supply at this time it is your responsibility to carry out the initial 2 hour test when you do connect it permanently to the mains supply Copyright 2013 Thomas amp Betts Australasia ABN 062 074 810 898 Rev 2 0 19November 2013 3
3. 00mm slack cable from the back of lamp to the enclosure s cable entry hole then tighten the cable gland in place Swing the lamp head around to make sure adequate wire length for movement re adjust the cable length if need to Nylock Nut SS Flat Washer Lamp Head Nylon Washer SS Flat Washer 6 Tiltthe lamp head parallel to the bracket This is an important step to avoid excessive lamp head tilt which may cause over shadow 7 Terminate the lamp cables into the terminal block make sure wire polarity is correct to each marked terminal block The lamp heads are provided with earth lug Locate earth stud marked with earth label near the termination point Remove nut and one earth washer only Drop both lamp head earth lugs earth washer and secure it with hex nut In no circumstances second locking nut should be accessed as it can cause earthing problem 8 Ifthe cable and data cable entry is from the side punch out the appropriate cable entry hole as required Remove all burrs and sharp edges after drilling 9 Run mains cable in the ceiling or wall space as appropriate or surface mounted in conduit slide the cable gland over the cable then feed the cable through the entry hole of the enclosure Allow adequate wire length to reach to the terminal block then secure the cable gland in place Repeat the process for Nexus LX data cable Copyright 2013 Thomas amp Betts Australasia ABN 062 074 810 898 Rev 2 0 19November 2013 2
4. STANILITE STANILITE Complete Solutions in Emergency Lighting CONSTRUCTION SITES Continuously switching on and off of the mains power supply that is connected to emergency light fittings during the installation process due to building works or for some other reason could cause affected emergency light fittings to discharge and charge their batteries many times over a short period this may shorten the life of the battery and may result in voiding of the battery warranty Thomas amp Betts does not recommend such practices and may not honour the warranty on batteries when they are subjected to such harsh operating conditions Emergency light fittings are designed to be regularly discharge tested once every 6 months as per AS NZS2293 2 deliberate repeated discharge testing over short periods of time is regarded as an abuse of the fittings Emergency Light LED Flash Patterns for Nexus Fittings LED Pattern Description LX Yellow flashing LX Yellow static LX RF Red static LX RF Red flashing LX Green Off flashing LX Red Yellow flashing LX RF Green on steady LX RF Off RF Green very slow flash RF Yellow flash 1 long 6 short RF Green flash with 2 red blinks RF Green flash with 3 red blinks RF Green flash with 4 red blinks Wink mode cable tracing is on Valid messages are being received by the unit Wink mode cable tracing has been turned off Unit has been commissioned battery is charging lamp filament is in
5. e space on either side of the enclosure to ensure adequate operation space for the LED push button when the unit is installed The mounting holes are indicated by keyway slots See Figure 1 for more details 69mm centre distance and smaller diameter 7mm Hold the enclosure against the wall use a pencil to mark the position of the screw holes and remove the enclosure Double check the holes centre distance make adjustment as required ensuring they are correct and level Mounting Tilt lamp head Holes for c parallel to bracket in place Fasteners f 2 A J Fitting are provided in a i Secure LED lamp lamp head box eee a r e N Rag ee an o TFT Lid Screw Test Switch Nexus Data Cable Entry if Figure 1 LED Flood Light Fitting Details 4 Fix two appropriate M6 screws to the wall due to the wide variety of building construction materials fasteners are not supplied Allow approx 10mm between wall and screw head for the enclosure to slide and drop into the position Make sure the mounting screws are fixed into solid material that is enough to support the weight of the unit approx 4kg Strengthen or support the mounting material if required 5 Install the LED lamps use fasteners provided from each box to secure the lamp head in place as shown in the image below Insert a Cable glade over each lamp cable then insert the cable into the flood unit housing Allow approx 1
6. g must be installed as per the procedure detailed in the Nexus LX User amp Technical Guide No mains or mains carrying cables are to be connected to the data terminals or cables NEXUS RF WIRELESS SYSTEM The Nexus RF range of emergency light fitting are designed to be connected together via a proprietary radio frequency RF communication network The installation of a Nexus RF emergency light fitting is no different from the installation of a standard non monitored product with the exception that the MAC address of the Nexus RF fitting must to be noted along with the SPUID at the time of installation in order for commissioning to be performed Commissioning of Nexus RF product is done by Thomas amp Betts service personal please contact Product Support Hotline for more information in Australia on 1300 666 595 Copyright 2013 Thomas amp Betts Australasia ABN 062 074 810 898 Rev 2 0 19November 2013 1 STANILITE Complete Solutions in Emergency Lighting INSTALLATION INSTRUCTIONS 1 Remove the unit from the packing box and inspect it for damage or imperfections If any damage is found do not install the unit but replace it carefully into the packing box and notify the Thomas amp Betts Product Support Hotline in Australia on 1300 666 595 2 Ifall looks okay installation can proceed Remove the lid by unscrewing 4 screws on each side 3 Determine the mounting and mains cable entry direction allow at least 100mm of clearanc
7. inutes in case battery is completely discharged it may take a little time to charge up enough to operate even momentarily After this time press the test button again and if the lamp doesn t work at all check the supply the connections and the trouble shooting guide at the end of this document 13 This step is for Nexus LX or Nexus RF unit only Once manually checked it is ready for the commissioning into the Nexus network Keep the information details of this Flood Unit including exact location description DB distribution board and CB circuit breaker numbering channel and router numbering plan number and cross referencing information as all of this will be required for entry into the database during commissioning Refer to the Nexus LX User amp Technical Guide for full details As the installer it is your responsibility to conduct the initial discharge testing of the installed unit Refer to AS NZS 2293 14 If the installation is successful secure the lid to the enclosure 15 While the lamp heads are on check the lamp head tilt final position and make sure there is no over shadow Adjust lamp head position as required REMOVAL INSTRUCTIONS 1 Before removing the installed unit switch off the mains supply to the fitting 2 Remove the lid disconnect the mains and data for Nexus only cable connection from the terminal block using suitable size screw driver 3 Undo the mounting screws and remove the unit from wall Note When
8. m AEST and ask for help Our trained service personnel will usually be able to take your call immediately and assist you in resolving your difficulty Thomas amp Betts is committed to providing valuable Through Life Support for its products Copyright 2013 Thomas amp Betts Australasia ABN 062 074 810 898 Rev 2 0 19November 2013 4 Complete Solutions in Emergency Lighting Doc No 29 00134 Thomas 8etts A Member of the ABB Group Thomas amp Betts Australasia ABN 062 074 810 898 Head Office Unit D3 3 29 Birnie Avenue Lidcombe NSW 2141 Australia Manufacturing 23a Nyrang Street Lidcombe NSW 2141 Australia Telephone 61 1300 666 595 Facsimile 61 1300 666 594 Website www tnbaust com LED Flood Light Installation Manual FL210LED FLNXS210LED FLNRF210LED What s Inside the box Flood Unit A LED Lamps 2 Contents Electrical Safety Warning Installation Instructions Accessory Kit Installation Manual Warranty Information d Removal Instructions Testing Precautions Trouble Shooting Guide GREETINGS Congratulations on choosing to use this Thomas amp Betts product covered by our unique Through Life Support system This document is designed to assist you during the installation of this product for the safety of yourself and others Thomas amp Betts recommends that you read this document thoroughly before commencing installation The fittings are designed for easy installation They a
9. re advanced pieces of electronic equipment which when treated with care and maintained through regular and appropriate servicing will perform reliably for many years to come SAFETY WARNING In Australia and New Zealand only licensed electricians are permitted by law to work with 240 Volt electrical installations Do not attempt to install or connect this product unless you are a licensed electrician Turn off and isolate the electrical supply before connecting this fitting to the building wires Do not touch the terminals of the terminal block when the light fitting is energised The only user serviceable parts are fluorescent or halogen lamp s LED light sources are not user servicable Do not tamper with the fitting or the warranty will be void As the installer it is your responsibility to ensure compliance with all relevant building and safety codes ie AS3000 AS NZS2293 Refer to the applicable standards for data and mains cabling installation procedures and requirements NEXUS LX DATA CABLE SYSTEM The Nexus range of emergency light fitting are designed to be connected together into a special communication network over a Level 4 or higher high speed single twisted pair data cable The Nexus LX User amp Technical Guide describes all you need to know to successfully install a Nexus project Ask for it from your supervisor from your employer or from your nearest Thomas amp Betts product supplier The network cabling of the buildin
10. tact Unit is under test Unit uncommissioned otherwise normal Unit PID is not nefw003b Unit uncommissioned otherwise normal Unit PID is nefw003b Okay when button pressed or unit faulty when button is not pressed Fitting is not powered or battery is not charging Unconfigured Configured and in flash yellow mode for identification Configured and hardware okay but unit uncommissioned and no RF network connection Configured and hardware okay and RF network connection okay but unit uncommissioned Configured commissioned and hardware okay but no RF network connection TROUBLE SHOOTING GUIDE If you ve installed and connected the unit as per the instructions listed earlier and it doesn t function correctly use the following table as a guide to fixing the problem Look up the type of fault in the left column and check the possible causes from the right column 1 Red LED not lit AC supply not connected or AC supply turned off or Test switch damaged 2 Red LED is lit but lamp doesn t come on when test switch Lamp damaged or Lamp not connected properly or Battery pack damaged or Test switch damaged 3 Lamp is lit momentarily when test switch is pressed or Battery not fully charged or When mains fail Battery pack damaged is pressed If the unit still doesn t work after checking these possible causes contact Thomas amp Betts Service in Australia on 1300 666 595 Monday to Friday 8 30am to 4 30p