Installation Manual

image

Contents

1. gt NX KNX WEB CONTROLLER gt 220V AC power cord gt KNX bus connector gt Ethernet network cable gt Manual TECHNICAL CHARACTERISTICS The main hardware characteristics of the product are outlined in the table below Dimensions 155 x 155 x 25mm Ports and Connections RS232 DB9 USB 2x Ethernet Network 2x KNX Interface Power Supply 7V 18V DC 220V AC Transformer supplied Operating Temperature 0 C 50 C NX KNX ELECTRICAL CONNECTIONS To use the NX KNX WEB CONTROLLER you must have the following connections gt Power supply using the transformer supplied v KNX bus using the specific connector supplied with the possibility of making enter exit connections Main data network on a LAN port for connecting secondary NetworX panels for Galileo series DVRs COM line for connecting to the main NetworX panel with the DB9 serial cable and the following PIN configuration NX 584 NX KNX 1 1 Orn oa gt n gt CENTRALE NX KNX IN OUT LAN ALIMENTAZIONE Connection to the KNX bus must respect the polarities indicated in the figure below PRELIMINARY CHECKS Before accessing the NX KNX pages it is a good idea to ensure that the following requirements have been met V A PC MAC with Ethernet network card you must have Administrator r
2. Zone status Reserved Zones snapshot Reserved Partition status Reserved Partitions snapshot Reserved Location 3 Programming command request activation Segment 1 Segment 2 Segment 3 Segment 4 1 Reserved 1 ON 1 ON 1 Reserved 2 ON 2 ON 2 ON 2 Reserved 3 Reserved 3 ON 3 ON 3 ON 4 ON 4 ON 4 ON 4 ON 5 ON 5 ON 5 ON 5 ON 6 ON 6 8 Reserved 6 ON 6 ON 7 ON 7 ON 7 ON 8 ON 8 ON 8 ON Location 4 Programming the LCD keypad address Enter the address of the keypad from where you would like the information to be collected Enter the value 192 Programming locations 3 4 in DL900 is as illustrated below 72 Automation module 1 Baud rate and transition enable Request enables Command request enables Reserved Interface configuration Reserved Zone name request Zone status request Zones snapshot request Partition status request Partitions snapshot request Program data request Program data command User info request with PIN User info request w o Set user code with PIN Set user code w o PIN Set user authority with PIN Set user authority w o PIN System status request Send X 10 message Log event request KP terminal mode request Reserved Reserved Reserved Reserved Reserved Store com event Set clock calender Primary KP function w PIN Primary KP function w o PIN Secondary KP function Zone bypass toggle LCD Keypad address NX 590 PROGRAMMING Loca
3. NX KNX ADMINISTRATION MENU The administration menu allows you to configure and customise every aspect of NX KNX The pages of this menu are structured in a table of icons and each icon allows you to call up a sub menu or a specific function The number and type of the icons available in the administration menu depends on the user who has logged into NX KNX Users with Administrator rights can access all the items in the menu but the power managers and basic users can only use a limited number of icons in accordance with the access rules of the respective user groups To edit these rules please see the section in this manual regarding user management pushing button SYSTEM CONFIGURATION This section allows you to set the main parameters of the controller This contains the following items gt NETWORK CONFIGURATION This allows you to set the NX KNX addresses and network card functions gt CONFIGURE DATE AND TIME This allows you to configure the date and time of the system and the time update criteria online and on the KNX bus gt MODULE AND LICENCE MANAGEMENT This allows you to enter or update the licences that belong to the various modules that make up the system and configure the main operating parameters e g communication ports gt USERS AND USER GROUPS This allows you to manage the system access accounts and their associated rights 24 NETWORK CONFIGURATION This page allows you to e
4. 210 Segment 1 Segment 2 1 Reserved 1 ON 2 ON 2 ON 3 Reserved 3 ON 4 Reserved 4 ON 5 ON 5 Reserved 6 ON 6 Reserved 7 ON 7 Reserved 8 ON 8 Reserved Programming locations 207 208 209 and 210 in DL900 is as illustrated below Advanced settings 1 Send Read Options Clock Display Download access Autotest and clock Auto arm Request enables System 1 System 2 Partition Auxiliary outputs Zone types Baud rate and transition enable Serial port enable amm Options ASCII Reserved Reserved Reserved Reserved Reserved Reserved Reserved Baud rate 9600 MS Transition enable Reserved System status Interface configuration X 10 message received Reserved Log event message Reserved Keypad message received Zone status Reserved Zones snapshot Reserved Partition status Reserved v Partitions snapshot Reserved 10 Location 211 Segment 1 Segment 2 Segment 3 Segment 4 1 Reserved 1 ON 1 ON 1 Reserved 2 ON 2 ON 2 ON 2 Reserved 3 Reserved 3 ON 3 ON 3 ON 4 ON 4 ON 4 ON 4 ON 5 ON 5 ON 5 ON 5 ON 6 ON 6 Reserved 6 ON 6 ON 7 ON 7 Reserved 7 ON 7 ON 8 ON 8 Reserved 8 ON 8 ON Location 212 Insert the keypad address 192 Programming locations 211 and 212 in DL900 is as illustrated below 2 Advanced settings 1 Sox Download access Autotest and clock Auto am Auxiliary outputs Zone types Baud rate a
5. In creating areas and zones you will be able to specify which panels they should refer to 27 CREATING NEW AREAS To configure one or more areas to monitor in NX KNX please follow the procedure below gt Access the homepage by pressing home in the main menu gt Select the item NX Areas gt In the panel at the start of the list select the item create a new object and then indicate the number of areas to create and choose NetworX NX Area You also have the option to specify whether the new objects need to be created in the current folder or in another folder see further down for creating folders gt Click on create and wait for a few seconds 47 T 0 SUL a lt ha Ie ie e hi Once the page has reloaded the new objects will appear The software automatically numbers the new objects progressively from number 1 uw m T T 112 eL 2 lt dich Je eo e ho z N ee NOTE if there are no further configuration operations to be performed follow the instructions given in the bottom panel to restart the communication services and set up NETWORX NX KNX WEB CONTROLLER for correct communication If there are further configuration operations ignore the message and continue with configuration only restarting after you have completed the last operation This indication applies to any operation that requires you to restart ser
6. KNX system all you need to do is edit the panel status to start the corresponding telegrams sending on the KNX bus and viceversa to start sending ON OFF commands from the KNX bus on the command addresses to pilot the intrusion detection system We suggest you use the ETS bus monitor to ensure that the gateway functions correctly in all operating conditions and to simulate telegram transmission 33 NOTIFICATIONS NX KNX allows you send messages to the user when a status change of objects relating to the Networx NX occurs You can configure two types of notifications gt SCREEN NOTIFICATIONS messages viewed on the web pages of the system that inform the user of an anomaly with the date time of the event gt EMAIL NOTIFICATIONS emails sent to one or more recipients when an event occurs NOTIFICATION CONFIGURATION You can associate notifications with all the objects for zone function area function and panel status which can be found in the sections KNX management NX zones KNX management NX areas and KNX management panel statuses respectively or by using the search engine as seen above Select one or more objects from the list with which you would like to associate a notification then click on create new event in the toolbar A page will appear where you can choose which action to perform at the status change of the selected objects In the create new object section select the type of notificatio
7. PARAMETERS On Administration menu we have two icons Configuration konnex comunicazione which contains gateway parameters Icon Export ETS configurstion allow to export gateway setup on a PC which has got an ETS application Declaration of Conformity HESA S p A Via Triboniano 25 20156 MILAN declares that the NX KNX equipment conforms to the essential requisites required by CE norms 2004 108 CEE The following regulatory documents were applied EN55022 2006 Class A EN50130 4 1995 A2 2003 EN61000 3 2 2006 EN61000 3 3 1995 A1 2001 A2 2005 C HESA s p Via Triboniano 25 20156 Milano Italy Tel 39 02 380361 Fax 39 02 38036701 www hesa com e mail hesa 9 hesa com H HESA DT02038HE1011R01 36
8. a command konnex address to let other konnex items to send commands to panel The second one is a status address to let other konnex items to read the status of the panel To fill in or modify konnex address simply write it on the filed in the x y z format where x and y are between 1 and 15 z is between 1 and 255 Then you will see that the button will change its color Now you are able to update your new configuration pushing button Make sure to restart services 23 Now you to setup konnex addresses for panel selecting Panel warnings KNX management T i ete tte lt h Subs Sy _ TA YCQU QTY P i memos NIC Stato contra bol CA 6 _ i 00 Ar 4 i 4 moa mim d 1 minm 8 bi 4 th hoy The first one is a command konnex address to let other konnex items to send commands to panel The second one is a status address to let other konnex items to read the status of the panel To fill in or modify konnex address simply write it on the filed in the x y z format where x and y are between 1 and 15 2 is between 1 and 255 Then you will see that the button will change its color Now you are able to update your new configuration 1 Make sure to restart services
9. integrated KNX port you must have internal interface selected and the device must be set to dev ttyS1 If you want to use an IP KNX gateway select the corresponding type and enter the parameters as set in the ETS software f Networx NX KNX a Melt NN group Maumem dl IU grove arabiat fer the MANAGE NX AREAS VIA KNX The individual functions associated with every area defined in NX KNX can be associated with one or more KNX group addresses based on the specific properties of each of them To do this access the page KNX management NX areas and identify the functions of the area in question in the list Alternatively search for the relevant objects using the search engine specifying Networx NX Area Function as the object type Once you have identified the object that you want to manage with KNX click on the arrow in the details column to open the relative box below the corresponding line In this box you can enter the address of the KNX group in 3 level format i e 0 0 1 on which you will receive the status change signal and for objects that can be controlled an address different to the status through which you can command the corresponding function from the KNX bus NOTE although the system allows it we strongly advise against using the same group address for different functions on different objects and on different operations status change and transmission performed
10. of the additional modules USER AND USER GROUP MANAGEMENT This section allows you to consult the list of users and user groups configured in the system and create new ones For a detailed description on user management please see the specific section in this manual To modify pre defined admin and user passwords please logon to gateway and connect to the following links for ADMIN http IP ADDRESS smartdomuspad modules system externalframe php url system editobject php id 15 for USER http IP ADDRESS smartdomuspad modules system externalframe php url system editobject php id 17 modifying IP ADDRESS with the real IP address of the gateway DATABASE MANAGEMENT This page allows you to perform operations in the database that contains the NX KNX configuration In particular you can gt EXPORT THE CURRENT DATABASE If you choose to export the current configuration when you press the finish button you will be asked to save the file containing the system configuration on your client computer or on the NX KNX if you are operating locally gt IMPORT A BACKUP By selecting the item import new database you will be given the possibility to choose a previously exported file When you click on the finish button the current configuration will be replaced with the configuration contained in the file itself gt RESTORE FACTORY SETTINGS This option allows you to restore factory settings on the NX KNX Note this oper
11. the item Change default NX panel gt Change the name assigned to the panel to better identify it and the optional description given to it gt Type of communication specify if NX KNX has to connect to the panel via serial connection or via Internet gt Based on this choice specify which port to use for the connection in the event of serial USB connection or IP address and network port gt Enter the authentication code to use for connection to the panel The code must be valid to access the panel This code is used by NX KNX for operations that do not require users to enter codes gt Save the changes and restart the communication service as prompted by the message that will appear on the screen f fNetworx NX KNX Predetred NX pant Communication v ui gt Dem spect post eth pansi NOTE when the panel is saved for the first time picture icons are created that will allow you to view and manage the status and or alarm signals of the panel Once you have saved you can see these objects in the panel status section on the bottom in the panel card CONFIGURING MORE THAN ONE PANEL You can configure NX KNX to dialogue with more than one panel on different serial USB ports or via Internet To do this click on the item new NX panel in the NetworX NX section of the administration menu and enter the same information as above
12. where present TREE This allows you to browse quickly through the surveillance page structure The bottom panel contains the following icons ON SCREEN KEYPAD This brings up an on screen keypad to enter touchscreen text without a physical keyboard E MESSAGES This allows you to see a list of messages and notifications generated by the system In the pages that have an object list there is a toolbar at the beginning of the list that contains the buttons relating to possible actions to be performed in the page Some actions are available without selecting any object while others require you to select at least one object by checking the selection box in the first column The buttons available are BACK This allows you to return to the previous page the same as the back button on your browser NEW This allows you to create new objects as described in more detail below UPDATE This allows you to save the changes made on one or more objects in the list EDIT This allows you to access the detailed profile of an object to edit its properties REGROUP This allows you to put the selected objects into a folder REMOVE This allows you to remove the selected objects from the current folder ESI 23 E E 3 DELETE This permanently deletes the selected objects from the database Ea CREATE EVENT This allows you to associate an on screen or email not
13. NX KNX Cod NXKNX Konnex interface for NetworX panels Installation Manual HESA s p es Tel 39 02 380361 Fax 39 02 38036701 H HESA DT02038HE1011R01 GENERAL DESCRIPTION The NX KNX gateway is a completely fanless embedded controller without moving parts which can connect a NetworX NX V2 or NX 8E panel to a domotic system based on a Konnex protocol This gateway bidirectionally translates the statuses of the intrusion detection panels connected to it into Konnex events and also translates Konnex events into default actions for the intrusion detection panels The gateway can be connected to the intrusion detection panels of the NetworX family in the following way NX V2 connected to NX 584 domestic automation module which is in turn connected to the gateway via the serial port NX V2 connected to an NX 590 network module which is in turn connected to the gateway via the Ethernet socket gate NX 8E directly connected to the gateway via the serial port using the NXPO003 adaptor NX 8E connected to an NX 590 network module which is in turn connected to the gateway via the Ethernet socket port This Gateway is also able to stream Galileo series DVR videos on the web server With a user password you can also use the gateway to operate the NetworX panels using the web browser controls and view the Galileo DVR video streams PACKAGE CONTENT The package contains the following
14. SYSTEM This shuts down the Linux operating system on which NX KNX is based note this operation does not require the controller to shut down the system electrically gt RESTART THE SYSTEM This restarts the controller s operating system DIAGNOSTICS The diagnostics page allows you to see a summary of the machine configuration to identify any inconsistencies or configuration errrors that might compromise correct functioning LOG This page allows you to consult the system log that can contain error messages or notifications sent to the user that have been collected during device operation 26 OPTIONS This section allows you to set some parameters that determine the device s actions gt SYSTEM gt EMAIL This allows you to set the connection parameters to a SMTP server to send messages gt TVCC This allows you to specify pixels the width and height of the video stream viewed gt DYNDNS This allows you to configure the DYNDNS client integrated in the device This requires a valid account on www dyndns org The page also shows the outcome of the last update operation on the DYNDNS server ADVANCED COMMUNICATION WITH THE NETWORX PANEL When installed for the first time NX KNX already has a preconfigured NETWORX panel in its database To configure the parameters for this panel gt Access the administration menu and select the item Networx NX gt Select
15. TOM PANEL If open this allows you to view alarm messages generated by the system or to plan regular checks on objects It can also contain an on screen keypad to assist in using the touchscreen gt SCROLL ARROWS These allow you to move around within the page if the content exceeds the view boundary of your browser The main menu contains the following icons REFRESH PAGE This refreshes your current page the same as the refresh function in your browser CHANGE CURRENT VIEW With these buttons you can choose the view list icons for the current page list HOME This takes you back to the default surveillance page ADMINISTRATION This allows you to access the administration menu CHANGE USER This logs you out of the system and the window for entering your access information appears once again SAVE ON FLASH This prompts you to save the configuration permanently on the disc before turning off the system QUICK SEARCH This allows you to search for one or more objects within the database CJ NOTE not all icons are visible on all pages of the software Users without Administrator rights may only view some icons as some operations are not permitted for end users 16 The side panel contains the following icons m DETAILS Default page of the side panel You can see additional page information such as the object category selector
16. ampi sottostanti fare click su Login per proseguire Accesso al sistema Username 3dmin Password leseee admin where you will need to enter admin as the login and admin as the password There is also a user password that will not let you edit the Konnex programming or the gateway configuration user as the login and user as the password 13 4 Networx NX KNX P P WEB CONTROLLER 1 jNetworx NX KNX P couTRILIER EMAIL SETTINGS 14 f Networx NX KNX P WEB CONTROLLER os SYSTEM OVERVIEW The NX KNX web pages are a fixed structure where it is possible to identify some elements that are always present in all sections of the software With reference to the figure below please note UNKU eL 2 lt 8 15 NAVIGATOR This shows you the position of the current page within the hierarchical structure of the system at any moment By clicking on its items you can quickly return to previously visited sections gt MAIN MENU This contains all the options required to change the default page view and for quick access to the main sections of the software and also has a quick search for objects in the database gt SIDE PANEL If open this contains additional information for browsing or configuring the objects within the surveillance project It can also be used as a fast project browser using the tree function gt BOT
17. ation does not change the IP address assigned to the network card 25 SOFTWARE UPDATE This page allows you to install updates or additional modules on your NX KNX that were not installed at the time of purchase To update software first make a backup of the configuration and then follow the guided instructions by uploading the file containing the update without decompressing it on your computer and ensuring that the update has completed correctly in the summary page If no error messages flash up in red click on the add file button to prepare the package for update Once the page has reloaded click on update to start the update procedure Wait for confirmation that the operation has been completed without performing any other action or closing the browser these actions might cause the device to malfunction Then restart if necessary NOTE this operation could take up to half an hour depending on the size of the update package EMPTY AND REFRESH CACHE This command empties all the temporary files generated by NX KNX during use in order to speed up browsing These files called caches can in some cases lead to a view that is not updated and not consistent with the configuration in the database especially if itis accessed contemporarily by different workstations and different users NOTE emptying the cache can cause a view error if you load a NX KNX page at the same time as another workstation If this happens reload
18. button to implement them NX KNX will restart with the new network parameters Please remember that BRIDGE mode requires a slightly longer set up time than the other configurations Remember to nat ports 80 and 443 to connect to gateway from WAN If access to NX KNX is anticipated via Internet you need to ensure that the default gateway address corresponds to the router that provides public access e g ADSL router If it does not you will not be able to reach the controller from outside the local network DATE TIME MANAGEMENT You can set the system clock in the configuration page with the same name on the side The clock can also be updated via Internet To do this you will need to specify the time server and the minute intervals of the update enter a value from 1 to 50 Finally this page allows you to plan any communication service restart at a given time on one or more days per week to be used for a particular system load to regularly free up the system resources MODULE AND LICENCE MANAGEMENT With this screen you can manage the configuration update and registration of system modules The software is provided with some pre installed modules and you can extend their function with optional additional modules For each module you can update and register the user licence and again through this page you can set the main operating parameters For more information please see the specific documentation in this manual or in the manuals
19. dit the NX KNX network card parameters You can independently configure the two network ports identified as LAN and WAN respectively see the connection diagrams by entering the respective configuration parameters into the specific text boxes as illustrated in the figure on the side The LAN port cannot be deactivated and is considered the main port for access to NX KNX It can only be configured by entering a static IP address The WAN port can be activated by selecting the specific box and can be activated in both DHCP mode automatic address allocation and by manually entering the IP address Please note that in all cases the WAN port must be connected to sub network that is different from the LAN port and must therefore be configured with a different address allocation class otherwise the NX KNX will not work If you would like to use both network ports under the same sub network you can activate the Network Bridge by selecting the specific box In this case you must enter the IP address the network mask and the default gateway that will be adopted by both ports in HUB mode It is also possible to manually enter the addresses of the DNS servers used by NX KNX for access to the Internet In addition to these by selecting the appropriate box you can also select the automatic DNS address allocation from the DHCP server so that the WAN port is activated in DHCP mode Once the network settings have been modified click on the save
20. ects associated with the area and zone functions that are usually available in the side panel and insert them under free objects within folders to allow the user to access single functions directly f Networx NX KNX d Ib Ih RS a fh dh l Ih Eh P r Subew Cancel g i a VOD CC PR A 4 i e 1 inas AS n p E e je 4 JE JU ONE E EOE SW oT d U ra 8 O oo mclccIcm romeo 0 Aam memo 1 0 31 NETWORX PANEL MANAGEMENT VIA KONNEX INTRODUCTION NX KNX also allows you to manage the functions of the panel the areas and zones available on the web interface through telegrams that are sent or received on a KNX domotic bus Before attempting the configuration described in this chapter you will need to create a domotic project using ETS software creating a series of group addresses that will communicate with the device These addresses must be entered manually in NX KNX as described in the sections below KNX COMMUNICATION CONFIGURATION Before starting to configure the rules of bidirectional communication with the domotic system it is a good idea to ensure that KNX communication is correct To do this go to the administration menu select KNX and then configure KNX communication If you use the
21. ification with the selected objects described in more detail below 17 GATEWAY NX KNX SETUP Push Administration button 12 to have the following page a an OP iit 2M Vi int c 2 fc __ Mtg 10007SI vemaetdormorpad module cystem eitemalfiame php 7 4 vn f p Pu vetas Come i Ultime notie L Select Networx icon P LS an X fe 00225 module system etemalfiime php i P 2 notizie E We need to setup the user code Konnex will use to send request and commands to panel To do so press Modify defined panel 18 2 I m d 4 Ar as l l 4 I ny ns ow TES Fill in the code konnex will use to request and command the panel then press Save J i aM UL 2 lt E Piocehoed NX p Frfejefise3 patel Remember to setup an user with the same code on the panel 19 2 Push Click here to re start services and so apply modfifiations Setup the first area going back to the previous men 05 and selecting New NX partition 2 ES EE 718 i AD NEW PARTITION Press Save 20 If you press Click here to re start services Go on with the partition setup adding all parti
22. ights to configure the Internet connection and one of the following web browsers Mozilla Firefox Apple Safari Google Chrome Microsoft Internet Explorer We advise using Mozilla Firefox for configuration gt To configure KNX management you will need ETS Professional software installed on your computer and the ETC design for the domotic system with which you want to interact NX 584 AND NX 590 MODULE INSTALLATION The installation of NX 584 and NX 590 modules is described in the manuals of the specific modules themselves The programming procedures for these modules is provided below to simplify the installation process NX 584 PROGRAMMING Location 0 Programming the option indicators Option 1 off Binary Location 1 Frequency transmission table Segment 1 set to value 4 to have a transmission speed of 9600 baud Location 2 Activating variation send Segment 1 Segment 2 1 OFF 1 ON 2 ON 2 ON 3 4 Reserved 3 ON 5 ON 4 ON 6 ON 5 8 Reserved 7 ON 8 ON Programming locations 0 2 in DL900 is as illustrated below 72 Automation module 1 Send Read Options Display Baud rate and transition enable Request enables Options ASCII Reserved Reserved Reserved Reserved Reserved Reserved Reserved Baud rate 9600 Transition enable Reserved System status Interface configuration X 10 message received Reserved Reserved Keypad message received
23. ly from the list of objects of the folder in which you would like to insert the new video channel select new from the toolbar and specify Galileo channel as the type In the tab that pops up enter the following properties gt Name label associated with video signal gt Description optional field where you can insert a comment gt Image icon associated with the video camera gt Channel specify the video camera channel number in the DVR Galileo gt IP Address DVR network address gt Port network port on which the DVR provides the video signal default 80 gt Protocol communication protocol with the DVR default HTTP gt Width and height pixel size of the video signal when viewed in the web page gt Resolution video stream resolution requested to the DVR insert a valid resolution for the specific DVR gt Video format choose JPEG motion to view the images with the DVR native format photogram stream to regularly request the last photogram from the DVR for slow connections gt Activate PTZ this allows you to activate coordination of the video camera dome movement If activated this allows you to specify the parameters for coordinating camera movement and zoom 35 Once you have created the object by clicking on the relative icon a page will appear in which you can view the DVR video stream in real time KONNEX CONNECTION
24. n menu Base users cannot change this view as they are restricted to the default view established by the person configuring the system jNetworx NX KNX Me AAAI gt lt am nm a P Lou PUTTING OBJECTS INTO FOLDERS You can put various types of objects into folders starting with other folders to create a type of hierarchical tree for navigation 30 The areas or zones created previously can be put into one or more folders To do this all you need to do is access the page NX areas or NX zones respectively select the areas zones of interest and click on the regroup button on the panel Then select the destination folder and confirm with the run button NOTE a copy IS NOT made when an object if put into a folder unlike the file of a disc Instead a relationship is created in the database between the object and the folder You can then always remove the association between the object and folder by pressing remove on the panel without this action deleting the object which you can then take out of other folders it is in Operations on objects can also be performed by the search engine which can be accessed by using the specific box on the top right of the main menu All you need to do is enter one or more keywords to obtain a list of all the objects that respond to those keywords on which you can perform operations such as edit regroup delete etc The search engine also lets you recover the sub obj
25. n to create If more than one object is selected choose yes in the create multiple object item to create a notification associated with each of the panel objects Click on new to continue On the next page for each of the objects selected you will be asked which status must trigger a notification Choose the desired status in the drop down menu then confirm to implement the changes If you leave at every change of value the notification will be sent every time the object of reference changes value On the contrary by choosing a specific status among those provided only this event will trigger the notification f fNetworx NX KNX u 2 a fae Mo Mahe Ma Me 34 Quando Gourd fauk assume ilvalare ON Quards mene taut assure 11 ON Costrrusicatioe taut maums 1 valor ON EMAIL PARAMETER CONFIGURATION To correctly send emails NX KNX must be connected to the Internet and suitably configured with the SMTP server parameters it is supported on Enter the required information in the email options page in the maintenance section of the administration menu as illustrated above INTRODUCTION NX KNX allows you to monitor video streams by one or more GALILEO DVR videos GALILEO CHANNEL CONFIGURATION To configure a new channel video camera of a GALILEO DVR go to the administration menu select the item video surveillance and click on new Galileo channel Alternative
26. nables Reserved System status request Interface configuration Send X 10 message Reserved Log event request Zone name request Send Keypad text Zone status request KP terminal mode request Zones snapshot request Reserved Partition status request Reserved Partitions snapshot request Reserved Program data request Reserved Program data command Reserved User info request with PIN Store com event User info request w o PIN Set clock calender Set user code with PIN Primary KP function w PIN Set user code w o PIN Primary KP function w o PIN Set user authority with PIN Secondary KP function Set user authority w o PIN Zone bypass toggle LCD Keypad address 192 I lt lt lt lt lt PROGRAMMING THE NX 8E PANEL To connect the NX 8E panel to the NX KNX gateway you will need to use the adaptor that can be bought separately from the panel so that the serial output presents as a classic COM 9 PIN connector If you want to create it yourself the pinouts are outlined below IDC 2x5 PIN Connector COM DB9 male Connection Table The red cable PIN IDC PIN DB9 on PIN 1 3 TX 8 CTS 2RX 7 RTS 5 GND OM ok Instructions for programming the panel for serial connection to the NX KNX gateway are provided below Location 207 Programme the value 1 Location 208 Programme the value 2 to set the speed at 9600 Baud Location 209 Leave this location in OFF state Location
27. nd transition enable Request enables System 1 System2 Partition Overides Command request enables Reserved System status request Interface configuration Send X 10 message Reserved Log event request Zone name request Send Keypad text Zone status request KP terminal mode request Zones snapshot request Reserved Partition status request Reserved v Partitions snapshot request Reserved Program data request Reserved Program data command Reserved User info request with PIN Store com event User info request w o PIN Set clock calender Set user code with PIN Primary KP function w PIN Set user code w o PIN Primary KP function w o PIN Set user authority with PIN Secondary KP function Set user authority w o PIN v Zone bypass toggle LCD Keypad address 192 11 ACCESS TO NX KNX GATEWAY To configure the NX KNX gateway you will first need to connect your computer to the network with the controller The gateway can connect in two ways gt Connecting NX KNX with the LAN network to which the computer is already connected gt Directly connecting NX KNX to your computer using a CROSS OVER network cable In both cases you will need to configure even if only temporarily your computer s network so that you can dialogue with the NX KNX gateway whose default address is 192 168 0 110 To do this dependi
28. ng on your operating system if the factory address is not compatible with your network proceed in the following way gt Manually set your computer s IP address using the first three numbers of the NX KNX address and assigning a value of between 1 and 254 to the fourth number ensuring that it is not already in use and not using 110 E g 192 168 0 100 Propriet Connessione alla rete locale LAN JK Generale NETS Connetti tramite Propriet Protocollo Internet Scheda Ethene Geneale possibile otfenere l assegnazione autemalica delle mpostazioni IP se la reke supporta tole caratherishoa In caso cantieri sar necessari al amministralore d le impostazioni IP comette La connessione utilizza 1 component sequent vi Sl Cieni per reti El Condvisione stampanti par v JE uita di piarilicaziarie pacchetti o3 IE Protocollo Interest C Other sutomaticamenie un indirizzo IP Ce Utilizza d sequente indrizza ndinzzo 192 168 100 Subst mack 255 26S ee 0 Instala Preoriek Gakeway 192 168 0 110 Descrizione Protocolo predetiniio per le WAN che permette la comunicazione dwerse reti interconnesse RM E Ce Utilizza i seguenti indirizzi server DNS Server OHS prefento C Mosta un icona sul area di n
29. nlifica quando connesso M atifisa in caso di carniettisat liritala assente Server D MS akermalia Avanzabes ok Amus gt If required specify 255 255 255 0 as network mask Once you have modified your network configuration ensure that you are correctly communicating with the NX KNX gateway by opening the COMMAND PROMPT window in Windows for other operating systems please see the relevant manuals and enter the command ping 168 0 110 12 ensuring that the communication has been made correctly as in the figure below ox COWINDOWS system 3 172 168 8 11H Esecuzione di Ping 192 168 808 118 con 32 byte di dati da 192 168 868 110 byte 32 durata 1ms TTL 127 da 172 168 BH 118 byte 32 durata 1ms TTL 127 isposta da 192 168 6 118 byte 32 durata 42me TIL i27 1 da 172 168 BH 118 byte 32 durata 1ms TTL 127 Pacchetti Trasmessi 4 Ricevuti 4 Fersi persi empo approssimativo percorsi andata pPitopno in millisecondi Minimo ims Massimo 2ms Medio ims If the ping command receives a positive response as in the example open a web browser recommended MOZILLA not recommended INTERNET EXPLORER and enter the following address http 192 168 0 110 You will then get connected to the following webpage Login Utente E necessario inserire un nome utente ed una password per poter accedere al sistema Compilare i c
30. on the same object Only use this type of configuration in special cases and carefully ensure that the gateway functions correctly 32 Once you have inserted the addresses for all the functions ensuring not to change page in the meantime save the changes by pressing the update button in the panel at the start of the list Follow the same procedure for any additional objects and then restart the communication service to implement the changes zNetworx NX KNX corrsocus u CSS 21 lt Sle JU f us vecccnocc o taste aay group address Dh ooo 001 Stay 3 le MANAGE NX ZONES VIA KNX In a similar way you can associate the status transmission of the NX zones on the KNX bus by identifying the corresponding functions in the KNX management NX zones page and by inserting the KNX address in the detail box of where you want to transmit the status or by using the search engine MANAGE NX PANEL STATUSES VIA KNX In a similar way you can associate the status transmission of the NX zones on the KNX bus by identifying the corresponding functions in the KNX management panel statuses page and by inserting the KNX address in the detail box of where you want to transmit the status or by using the search engine TEST THE KNX GATEWAY Once you have configured the bidirectional exchange rules between the Networx NX and the
31. t edit from the panel You will see the detailed profile where you can also specify in addition to the name the description and icon to which panel communication section it belongs if you are configuring more than one panel In addition this profile also shows the folders in which the area is located see below and the functions available for that area with regard to the panel CREATING AND EDITING A ZONE In the same way as the areas you can create new zones by accessing the specific page from the homepage Zone NX and selecting new then specifying how many objects to create ensuring that you specify Networx NX zone as the type of object to create In this case again the system will automatically number the new zones progressively starting from the last zone found in the database or from 1 if this is a new configuration By clicking on the icon of a zone in the actions column you will see a list of the statuses as provided by the panel in real time When this is on the screen you cannot perform interactive actions Similarly to areas you can edit zone names directly on the list and detail all the properties by accessing the relative profile and proceeding in the same way as described for areas ff Networx NX KNX IN Hu CREATING A NEW FOLDER NX KNX allows you to monitor areas and zones of the Networx NX panels by organising them into folders and sub folders in an absolutely arbitrary way Usually through
32. t 1 Segment 2 1 Reserved 1 ON 2 ON 2 ON 3 Reserved 3 ON 4 Reserved 4 ON 5 ON 5 Reserved 6 ON 6 Reserved 7 ON 7 Reserved 8 ON 8 Reserved Programming location 89 in DL900 is as illustrated below li 79 NX 590E 1 m Read Send Options Display Options Partition event enables Names Ports andtimers Account numbers Transition enables Command Request enables Serial port enable m Options ASCII Reserved Reserved Reserved Reserved Reserved Reserved Reserved Transition enable Reserved System status Interface configuration X 10 message received Reserved Log event message Reserved Keypad message received Zone status Reserved Zones snapshot Reserved Partition status Reserved Partitions snapshot Reserved Location 90 Segment 1 Segment 2 Segment 3 Segment 4 1 Reserved 1 ON 1 ON 1 Reserved 2 ON 2 ON 2 ON 2 Reserved 3 Reserved 3 ON 3 ON 3 ON 4 ON 4 ON 4 ON 4 ON 5 ON 5 ON 5 ON 5 ON 6 ON 6 Reserved 6 ON 6 ON 7 ON 7 Reserved 7 ON 7 ON 8 ON 8 Reserved 8 ON 8 ON Location 91 Enter the address 192 of the keypad that contains the labels Programming locations 90 and 91 in DL900 is as illustrated below 79 NX 590E 1 VL dM com Send Read Options Display Options Partition event enables Names Portsandtimers Account numbers Transition enables Command Request enables Command request e
33. the page using the specific browser command SAVE DATA ON DISC During normal functioning NX KNX uses a dynamic copy of its database held in the RAM memory volatile to minimise access times to data and the number of scripts on the flash memory When you change the project configuration the data does not get immediately transferred onto the flash memory permanent Instead a procedure is activated that saves the data permanently within the next 5 minutes Any data to be written permanently onto the flash memory is highlighted by an icon in the main menu that turns red when the RAM memory configuration is not aligned with the disc If you need to save data permanently to the disc immediately such as to switch of NX KNX you can click on this icon which will immediately save all the data permanently COMMUNICATION SERVICES MANAGEMENT This section allows you to interact with the system by performing one of the operations reported below In normal circumstances you do not need to intervene in these but in some cases it might be useful to force a restart or reload of communication services on which NX KNX is based or of the entire controller operating system gt RESTART COMMUNICATION SERVICES This operation restarts services based on NX KNX functioning This operation is not usually necessary or it is requested after operations that require it but it can be a good idea in some cases to restart the application gt SHUT DOWN THE
34. these folders the end user can navigate within environments in which the building is structured To do this there is an environment item on the system homepage When you access this folder you can create sub folders by clicking on new on the panel and indicating how many folders to create ensuring that you specify folder as the type of object In the same way as for areas and zones you can create as many sub folders as you want in the current folder You can edit the name and the icon of each of the sub folders by entering the new name and selecting a new icon from the library then confirming it by pressing update You can detail the properties of a folder by accessing its profile gt Name label associated with the folder gt Description optional field where you can enter a comment gt Image picture icon associated with the folder selected from the library available in the side panel gt default view you can decide whether the folder content is shown in list or icon form as shown in the figure on the side Alternatively you can choose the popup view which will show the folder content in a side panel when the corresponding icon is chosen 29 bi b T UL 2 lt lt 77 CT e 5 em 79 NOTE The Administrator can temporarily change the view of a folder from list to icons using the corresponding buttons available in the mai
35. tion 0 5 ON Programming location 0 in DL900 is as illustrated below 192 79 NX 590E 1 jm Send Read Options Display Account numbers Transition enables Command Request enables Options Partition event enables Names Ports and timers Use control as backup Site initiated downloading SIA Remote init downloading Use receiver 2 as backup DHCP DNS Reserved Download at test time Reserved Polling enable Email authentication Reserved Reserved Reserved Reserved Reserved Reserved Reserved Location 87 Enter the IP address of the NX KNX gateway Location 88 Enter the user port of the Ethernet socket you want to use to connect to the NX KNX gateway Programming locations 58 and 88 DL900 is as illustrated below li 79 NX 590E 1 XP XT Send Read Options Display Account numbers Transition enables Command Request enables Options Partition event enables Names Ports and timers TCP IP Addresses Automation system 0 0 0 0 i Rec alarm port E 9999 Email port Rec download port 9 9998 omation pot fnn 31 1 2 Account number 00001 000 Receiver number 0001 Line number 0001 Timers and counters Network attempts 2 Reserved Time for attempts 30 Reserved ho 2 Polling time 10 Reserved 57600 Y Location 89 Segmen
36. tions used and managed in konnex Setup now NetworX zones pushing New NX zone 3 gt Fill in name and description of the zone 2 Go on with the setup of the next zones Now you can save setup pressing to save modification to flash 21 4 4 Now it is important to re start services tworx NX KNX MRNA IIL To do so press Click here Now we should setup konnex addresses To do so go to main menu and select Manage NX partitions Now you have along list of states Press arrow gt you will find out where knonnex address are located ca 44 uc Mle SES lt Je Ia ia GCTIUESI MN NN LL p The first is command konnex address to let other konnex items to send commands to panel The second one is a status address to let other konnex items to read the status of the panel To fill in or modify konnex address simply write it on the filed in the x y z format where x and y are between 1 and 15 z is between 1 and 255 Then you will see that the button will change its color Now you are able to update your new configuration V pushing button Make sure to restart services 27 Now you can move to setup konnex addresses for zones selecting NX zones KNX management X NX KNX 2 amea a A RN UCET HN NEN The first one is
37. vices By clicking on the icon in the last column on the right you will see a side panel normally closed but you can view it by clicking the open close arrow at the top right containing all the functions of the area that can be managed The status of the icons is aligned with the panel in real time 28 Some of the icons in the panel can be controlled If you click on one of them a virtual keypad will pop up where you can enter the activation code by selecting the corresponding numeric keys or by directly entering with the keypad This code is the same as the code used for real keypad operations If the code is correct the function will be enabled and the icon will change status after a few seconds If it does not become enabled the icon will return to its original status and you will see an error message EDIT AREA PROPERTIES You can edit the name assigned to an area by simply entering the new name in the corresponding text box You can also edit the icon associated with that area by clicking on it and selecting an icon among those available in the library from the side panel Once you have made the changes and after checking that the selection box first column of the list corresponding to the modified areas is highlighted blue click on update on the panel to implement the changes After a few seconds the page will reload To edit other properties of an area select the area with its selection box first column and then selec