Home
        Operating instructions EC controller - ebm
         Contents
1.            Control functsource                       Intemal             Control function           Cooling                  Control range II    P Fado o       1 1 86095                                 l Fado        1           008  3             Actualvaluesource 0           ED         OwOffspeed                       20b          Follow up times      Min  speed NN NNNM NNI  Max speed                  0               1098                   Remoeenble O J o OFF                                 Bostmde o OFF                       Manual mode activation J       OFF                            Manual mode source           Imema S            Man  mode Duty Cycle       OH N  Night limitation activation J       OFF o  Max  night duty cyce       1006      Minimum air shutdown OOP       Shutdown control deviation           00           Hysteresis o 000 o     1   Function K1 J Alfas          Active state K4 Jo opened S   a 0g       Page 83 of 92    Operating instructions     EC controller ebm Dd pst          Customer setting 2s  Drop out delay K1 NOK A  Function K2 Off   static EE  Active state K2     md AA  On delay K2  Drop out delay K2 HA  Screen display sensor fault E o  External fault input POF  Sensor    Type   Pressure sensor 0  30bar   gt  4  20mA  Connection   Input 0 4  20mA  1   terminal strip 3  terminals 6   10    Control     If the parameters are not changed  the following control behaviour results  P   controller      Duty Cycle  Al    100     0            p  Pa   12 Sbar
2.          20                      J  Switchover  setpoint 12 J       OFF       Setpoint2          280       Setpointreduction J ON      J                    Setpointreduct Start J       150          Setpointreduet End J                     Setpointatendpoint PO         Control functsource                         Intemal      Control function    Heatimg      Controlrange   000     P Fador O                     l Factor        1   80                              Actualvaluesource o EL               OwOffsped         4125       l               Folowuptime POs  Mi sped FH     Max speed          0        1095   j   Remoeenble J      OFF                     3    Boostmode                 OFF                            Manual mode activation J       OFF          4                      Manual mode source                    Intemal S            Man  mode Duty Cyce   OH  Night limitation activation J   OFF                 Max  night duty cyce           1006     Minimum airshutdown          OFF                            Shutdown control deviation J 0             Hysteresis o  o O   Function K1   Allfaudis                      jActivestateKi doo opened               ebmpapst    Page 80 of 92    Operating instructions     EC controller ebm Dd pst    Customer setting     po    On delay K1 0s    Drop out delay K1 EE O  FuncdinK2          static                        Active state K2 opened    On delay K2   0s      DropoutdelayK2 Oe G  Screen display sensorfaut   OFF             External fau
3.        If the Modbus function is inactive  the  Plant  menu  see 6 2  cannot be opened   The display  Bus inactive  appears there        Page 60 of 92    Operating instructions     EC controller ebm Dd pst    6 1 2 Initialization    After the Modbus function is activated and when requested by the user  an initialisation run of the control device is carried  out  During this process  the control device searches for fans in the configured address range  Each fan found is displayed in  the Plant menu  see 6 2   After 32 fans have been found  the search for more fans is cancelled  No more than these 32 fans  are displayed     After the initialisation run  only the fans that have been found are queried     1 After an initialisation run  none of the fans whose connection to the control device was interrupted  during the initialisation are displayed        6 1 2 1 Init range  gt  gt  gt  Modbus  gt  Configuration  gt  Init range    Init range    32  The initialisation range specifies the address range in which the search for fans takes place during an initialisation run     All addresses between 1 and the value specified in the parameter  Init range  are checked     The wider the Init range selected  the longer an initialisation run takes   At the maximum value  247  the initialisation run can take up to 70 seconds     During the initialisation run  the entire operation of the control device in the  Modbus  menu is  blocked  Therefore  select an Init range that is as small as possib
4.       5 2 4 3 Boost mode  gt    Settings  gt  Fan level A1  gt  Boost mode    Boost mode    OFF    With this parameter  a digital input can be selected which sets output A1 on the control device to boost mode  10V   provided  that this input is connected to ground     Boost Function      Possible values       always  Function  Boost mode  disabled    Digital input 1   open  Function  Boost mode  disabled   Digital input 1   GND  Function  Boost mode  enabled    Digital input 2   open  Function  Boost mode  disabled    Digital input 2   GND  Function  Boost mode  enabled    Digital input 3   open  Function  Boost mode  disabled  Digital input 3   GND  Function  Boost mode  enabled    Digital input 4   open  Function  Boost mode  disabled  Digital input 4   GND  Function  Boost mode  enabled       Page 47 of 92    Operating instructions     EC controller ebm papst    5 2 5 Manual mode 22  Settings  gt  Manual mode        Manual mode    OK  Manual mode  Activation See 5 2 5 1        Manual mode    Source See 5 2 5 2  Internal  Manual Mode  Speed See 5 2 5 3    0     5 2 5 1 Manual mode activation  gt    Settings  gt  Manual mode  gt  Manual mode activation    Manual mode    Activation  OFF       The parameter  Manual mode activation  switches the  Manual mode  function on and off     Possible values       Control to preset setpoint     Manual speed setting     Digital input D1   open   Control to configured setpoint  Digital input D1   GND   Manual speed setting     Digital inpu
5.      7000                            Control functsource                      Intemal      Control function   Cooing          Contolrange           OD               J      P Fado o 0      0  1    8095                             l Fado          1 1        008                             Actual value source   Ma EGE       OnOffspeed    A     Folowuptime PS  MESITA     Max speed   00H            Remote enabe J OFF                                 Bostmde OOP ol  Manual mode activation J       OFF     Manual mode source                    Imema S               Man  mode Duty Cycle           0      Night limitation activation J OFF       Max  night duty cyce   10                            Minimum airshutdown   OFF     Shutdown control deviation      000    Hysteresis TO  Function K1    Alfas          Active state K1  o opened     NE      On delay K1 0s       Page 86 of 92    Operating instructions     EC controller ebm Dd pst    Customer setting     Drop out delay K1    AN  Faon                       ofe                ao   ma A  On    K2  poega 05     1                  Screen display sensor fault       OFF                External fault input OE     Sensors     Type   Pressure sensor 0  30bar   gt  4  20mA  Connection   Input 0 4  20mA  1   terminal strip 3  terminals 6   10     Type   Pressure sensor 0  30bar   gt  4  20mA  Connection   Input 0 4  20mA  2   terminal strip 3  terminals 8   12     Control   The control behaviour corresponds to that of the simple condensers  see 7
6.     In the Information  menu  there is no  input option  i e  the  OK key  for input  is  disabled     4 2 1 Actual values    value 24 0  C    valuel 24 0  C  value2 23 2  C       Actual value E1     Select input E1 via the menu Settings  gt  Inputs  gt  Input E1  gt  Signal form E1  for details  refer to 5 2 1 2          Act value 24 0  C  Act valuel 24 0  C  Act value2    Setpoint 20 0  C  Setpointl 20 0  C  Setpoint2    Duty cycle 1 0   Control function    Digital inputs  D1 high D2 high    Relay K1  Relay K2 closed    Operating hours    y T     Software  46746V02    Date  25 03 09     gt  gt  Information  gt  Act values    Here the value is displayed which the sensor provides from the selected input     If the signal form for the  OFF  value is selected  the display       appears here     See 4 2 1    See 4 22    See 4 2 3    See 4 24    See 4 2 5    See 4 2 6    See 4 2 7    ebmpapst    Page 17 of 92    Operating instructions     EC controller ebm papst    Actual value E2     Select input E2 via the menu Settings  gt  Inputs  gt  Input E2  gt  Signal form E2  for details  refer to 5 2 1 2    Here the value is displayed which the sensor provides from the selected input     If the signal form for the  OFF  value is selected  the display       appears here     Actual value    Select via menu Settings  gt  Control  gt  Actual value source whether to use the actual value at Input E1 or at Input E2 as your  actual value  for details  refer to 5 2 3 5     Depending on the setti
7.     Two sensors can be connected to an 0  10V output     Terminal designation  Terminal strip 3  terminals 9 10  sensor 1   Terminal strip 3  terminals 11 12  sensor 2    Permitted sensor    Input resistor     2 4 5 Digital inputs    For switchover between functions  4 digital inputs are provided     Terminal designation  Terminal strip 3  terminals 17 18  input 1   terminal strip 3  Terminal strip 3  terminals 19 20  input 2  Terminal strip 3  terminals 21 22  input 3  Terminal strip 3  terminals 23 24  input 4    Switching  NO switch             Input resistor  14 7kQ    Page 8 of 92    Operating instructions     EC controller ebm papst    2 5 Outputs    2 5 1 Output 0  10V    The device has two 0  10V outputs  Here  the control inputs  0  10V  of  ebm papst EC motors can be connected     Terminal designation  Terminal strip 3  terminals 13 14  output 1   Terminal strip 3  terminals 15 16  output 2    Type of signal  0  10V x 3    Max  output current  10mA       2 5 2 Digital output  relay contact   The control device has 2 digital outputs  relay contacts    On the digital output  a reaction can be passed on to a connected unit     Terminal designation  Terminal strip 2  terminals 1 2  output 1   Terminal strip 2  terminals 3 4  output 2     Type of signal  Relay NO switch  Max  contact load  2A   250V AC       2 5 3 Power supply for sensors    The control device has two 24V outputs for supply of power to sensors     Terminal designation  Terminal strip 3  terminals 5 10  o
8.     ebmpapst    Page 78 of 92    Operating instructions     EC controller ebm Dd pst    Customer setting     Drop out delay K1 BEEN EN EE    FunctionK2           Off  static    qe A    On    K2   opaga 05     1                  Screen display sensor fault     OFF                     External fault input OFE     Sensor    Type   Pressure sensor 0  500Pa   gt  0  10V   Connection   Input 0  10V  1   terminal strip 3  terminals 9   10   Control     Using the     Factor the system controls pressure in such a way that the setpoint is always reached  Actual value   Setpoint    For this reason  it is not possible to depict the  Duty Cycle  as a function of the actual value     A setpoint of 250Pa is factory set   This means that the actual value in fully modulated status is also 250Pa     The control parameters are set to the following default values     P Factor  50      Factor   5     These values are sufficient for most applications     The  Control range  parameter as another display form for the P   Factor does not indicate anything since it is controlled by  the     Factor throughout this range     As a control function for this application  only the  Heating  setting  i e  positive operating    direction  is meaningful  The  Cooling  setting  negative operating direction  always culminates in    an unstable system        Modifications    a  Change in setpoint    Often the user requires a different setpoint to the standard one    After each change in setpoint  the device contr
9.    Pa JJ A  J                J    DecimalplacesE1                  20     Measuring range E1 min               0 N  Measuring range E1 mx   BOON  Sensor comparison check E1         0           SensortypeE2          Nosemsor      SignalformE2    UnitE2           Pa   9 Jj                Decimal places E2 o   o   0 J     MeaswingranpeE2mn J o 0    J               j    MeasuringrangeE2max               100        Sensor comparisoncheckE2     0              Setpoint              4230      Switchover  setpoint l2 J      OFF    Sepon2 OT 20 J  L    4   Setpoint reduction         OFF              A    Setpoint reduct Stat J      315   J       Setpointreduct End    Setpointatendpoint   N           Control funct source                 Intemal S   Control function      Heatiimg S   Contolrange _ 1   1 100           3           P Fado o   J   4LGlL      l Factor OH  Actual value source      OnlOfspeed   HP  Follow up time     2s                        Min  speed Owo   Max  speed   100   Remoteenable   CFF  Boostmode E O               J   Manual mode activation            OFF    Manual mode source       HE  Man  mode Duty Cycle   intemal      Night limitation activation   OFF o o  Max  night duty cycle J     1000     Minimum air shutdown J OFF  J        A     o    Shutdown control deviation                      0             J          o  Hysteresis   o N  FundionK  o   Alfas    ActivestateK1                         opned      OndeayKt       1  0s                                         
10.   5 3 1 2 Relay statuses  gt    Alarm functions  gt  Relays  gt  Relay K  gt  Active Status    Active state K1    opened       Using this parameter  a status for the relay contact can be assigned to the  Active state  of the relay  see 5 3 1 1      Possible values     opened   in active state  the relay contact is opened  closed   in active status  the relay contact is closed       The other status for the relay contact is therefore assigned to the inactive state     Application     For each function  you can configure whether the relay contact should be open or closed        5 3 1 3 Switching delay  gt    Alarm functions  gt  Relay  gt  Relay K  gt  On delay   Drop out delay    On delay K1 Drop out delay K1       0s Os  Using the  On delay  and  Drop out delay  parameters  a delay can be set for switching the relay contact   This time starts to run as soon as the condition selected in 5 3 1 1 Functions is satisfied  The contact is switched as soon as  the delay  i e  time lag  has elapsed     The  On delay  parameter is applicable here for closing the relay contact   The  Drop out delay  is applicable here for opening the relay contact     5 3 2 Sensor fault menu  gt    Alarm functions  gt  Screen display  gt  Sensor fault    Screen display    Sensor fault  OFF       Here you can select whether a Sensor fault should be output on the display while the standard display is still enabled     fault is not issued to the display during a standard display       If a fault occurs on 
11.   Min   Offset  20mA     I     4mA   Signal form  4 20mA    Actual value                       Max     Min    Min   Offset  16mA  Signal form  OFF     Actual value   0  This yields the following characteristic curve for the actual value   ME Resistor at input for  Temperature sensor  i  Tem Voltage at input  0  10V  i  A Current at input  0 4  20mA    Max              Maximum sensor value  Setpoint   Min               Minimum sensor value  Setpoint   Offset           Sensor comparison check  offset  Setpoint     If the applicable limit values for the signal form  1240  27900   0  10V  0  20mA  4  20mA  are exceeded  the corresponding       limit value is assumed to apply for calculating the relevant 2   limit value   Resistor 12400hm 27900hm  0 10V OV 10V  0 20mA OMA 20mA  4 20mA 4 mA 20 mA    For signal form  NTC   the actual value is calculated via a nonlinear table   For the curve  refer to the data sheet of the NTC 103AT     Page 35 of 92    Operating instructions     EC controller ebm Dd pst    5 2 2 Setpoints menu 22  Settings  gt  Setpoints    Setpoints Basic function Setpoint 1    See 5 2 2 1    250Pa       Switchover  Setpoint source 1 2    D1  A yp TA    Setpoint 2       200 Pa        Setpoint reduction Setpoint reduction    depending on E2 depending on E2 See 5 222       ON  y TA    Setpoint reduction    Start at  15 076    MEL    Setpoint reduction  End at   15 00    y Qa    Setpoint reduction          Setpoint at Endpoint  70Pa       5 2 2 1 Basic functions  gt  
12.   Settings  gt  Setpoints  gt  Basic function    Via the menu items  Setpoint 1  and  Setpoint 2   two different setpoints can be set for the control parameter     With  switchover setpoint source 1 2   a digital input can be selected which determines whether setpoint 1 or setpoint 2  should be used     If the value  OFF  is selected for  Switchover setpoint source 1 2   the system always uses    setpoint 1  for setpoint 2  no value appears       and there is also no input option        Page 36 of 92    Operating instructions     EC controller ebm papst    Possible settings for  Switchover  setpoint source 1 2       always  Setpoint 1    Digital input 1   open  Setpoint 1   Digital input 1   GND  Setpoint 2    Digital input 2   open  Setpoint 1    Digital input 2   GND  Setpoint 2    Digital input 3   open  Setpoint 1  Digital input 3   GND  Setpoint 2    Digital input 4   open  Setpoint 1  Digital input 4   GND  Setpoint 2       5 2 2 2 Setpoint reduction depending on E2 2   gt  Settings  gt  Setpoints  gt  Setpoint reduction depending on E2    a  Activation    Setpoint reduction  depending on E2  ON       With this parameter  the function  Setpoint reduction depending on E2  can be enabled and disabled     Possible values     OFF   Function disabled  setpoint corresponds to the setpoint of the basic function            ON   Function enabled  setpoint of basic function     is altered dependent upon actual value E2        Setpoint of the basic function is either setpoint 1 or
13.   so         o  P Fado        ooox      eos            OSS  Factor   10    00     LE   Actual value source              Ei OOMS ELE   onoffspeed o o QW MB II EI   Follow uptime   O          0s        Min speed            0x              4         Max speed EE   Remote enable   oF   OFF            SS   Boostmode                oF   oF     Manual mode acinaion   OFF    oF         Manual mode source   mema   memi                       o   Man modeDutyCyde        0    o   0         AS  atan de  oe ee A   Maxnghtduycyde       100    1006                         Minimum air shutdown              OFF   oF           o   Shutdown controldeviation           000   oo        ES   Hystersis  gt    00   oo                        Funcion k                   T Aitas   Alfas             Active statekt          opened   opened         D o  OvdeayKi          o   0s 0 O   I  IDropoutdelayKi         Os       o     Funcionk2   Of statie      Offisaio                         AcivestaleK2 opened   opened           D  oase   os TER       Drop outdelayke   o   o            Screen display sensora   OFF   OFF     ETE           OE  __oFF__     Page 27 of 92    Operating instructions     EC controller ebm Dd pst    5 1 2 Operating mode 2 22 gt  Operating mode  gt  Operating mode 2    Operating mode 2    Control  over 0 10V output       Possible operating modes     e Control over 0 10V output  e Control over Modbus output  e Plant monitoring over Modbus output       The following tables show how the device
14.   the value changes at a speed of 40 stages per second   If the keys are held down for longer than 6 seconds  the value changes at a speed of 200 stages per second     This means that any value across the entire range can be set within approx  100 seconds        Page 11 of 92    Operating instructions     EC controller ebm papst    3 2 Menu guidance    3 2 1 Overview       Page 12 of 92    Operating instructions     EC controller ebm papst       Page 13 of 92    Operating instructions     EC controller ebm Dd pst            ESC   OK          Language    Authorisation level    3 2 2 Main menu    After the device has been switched on  the first thing to appear on screen    ebmpapst for 5 seconds is information about the manufacturer and the device     EC Controller       Then the 1st point  standard display  on the main menu is displayed     Here the actual value of the sensor and the duty cycle on output A1 are  Act value 24 09    displayed  The standard display does not have any further sub menus and no  input options  The OK and ESC keys therefore do not function        Duty cycle A1    If the control device detects an error and this is also released to the display unit     the standard display appears in alternation with the error display   This alternating display only exists in this menu item        By pressing the W key  other points on the main menu can be called up     Page 14 of 92    Operating instructions     EC controller ebm papst    Overview of main menu     Act 
15.  1    Operating mode 1    Temperature ctrl T01  Standard       Possible operating modes     Temperature control  standard  Temperature control  NTC  Pressure control  ventilation systems    Pressure control  ambient temperature compensated  Pressure control  condensers  Pressure control  2 circuit condensers    ebmpapst       Page 25 of 92    Operating instructions     EC controller ebm Dd pst    The following tables show how the device is configured for the preset operating modes      Operating mode   TOY   T02    Sensor type E1 Temperature Temperature EE sensor EE sensor  KTY 10 6     NE     TOSAT     Decimal pias ET EE EE EE    Measuring range E1 min     300       430      0       0 J                     Measuring range E1 mx          700    900    amp X    50         50        Sensor comparison check E1   00       00      0 Jj      O0    J v        Sensor type E2 No sensor No sensor No sensor Temperature  sensor  KTY 10 6  SignalformE2 1   OFF   OFF    OFF    J PIC           Unte         Pa _   Pa   Pa    Cc J      DeimaplacesE2      0 JJ 0       O0 J  LDH 1 gd           MeasuringrangeE2min           0 JO  X     0 4  4 300      O   MeasuringrangeE2 mx       1000    100    4X  100   700        Sensor comparison checkE2       O          O0        0      00 s              Setpoint1            200   X 200   X250       X 250               Switchover  setpoint 1 2   OFF        OFF   OFF   OFF                          Sepon  O 0            Setpoint reduction OFF OFF OFF   Fseipo
16.  17  Control range    Modifications     a  Change in setpoint    Duty Cycle  Al    100        0     12 14 17 19 p  Pa     Page 84 of 92    Operating instructions     EC controller    b  Change in control range        Duty Cycle  Al  A oi id A      Control range   Sbar  0     12 17 20 p Pa     Factory pre settings must always be adapted by a specialist to suit prevailing    plant conditions     ebmpapst       Page 85 of 92    Operating instructions     EC controller ebm Dd pst    7 2 4 Pressure control  dual circuit condensers    Application   Pressure control for dual circuit condensers in refrigeration technology    Parameters     Customer setting es  Operating mode   002       Sensor type E1 Pressure sensor  0  30bar    SignalfomEt       420m N  UntET ar No  Decimal placesE1 o   2 4                     Measuring range Ef mn        Measuring range Ef mx              3000                  Sensor comparison check E1      0       Sensor type E2 Pressure sensor  0  30bar    Signal formE2   Am No  UntE2 a  DedmalpaesE2          2   34 J     Measuring range E2 min J    Measuring range E2 max BO                     Sensor comparisoncheckE2                0         Setpoint  o      2    34 12000    J L        J 4                 Switchover  setpoint 12 J OFF      1              Setpoint2 o 1200          Setpointreduction J   OFF            J        J    Setpoint reduct  Start           500                    Setpointreduet End        J      1500                    Setpointatendpoint
17.  2   The structure of  these menus is described beginning in 3 2     The setting options are only touched on briefly here  then described in greater detail in the following Chapters     The 4 input keys  see 3 1 2  have 2 different functions     e Switchover   changing over between the individual menu items  e Input   editing values    With the  Headings  menus  there is only the  Switchover  function   In the menus at the lowest level of  Values   both functions exist   With the  Input  function  the displayed value flashes    With the  Switchover  function  the value is displayed continuously     Page 10 of 92    Operating instructions     EC controller ebm Dd pst     Switchover  function     Key V   Move to next menu item on the same level  Key A   Move to previous menu item on the same level    ESC key    Move to higher level menu  one level higher   OK key   in  Headings  menu  move to lower level menu  one level lower   in  Values  menu  enable input function        Input  function        e KeyV   Reduce value by 1 stage   e KeyA   Increase value by 1 stage   e  ESCkey  Terminate input function  do not accept new value   e OKkey   Accept value  terminate input function       Fast forward     The value range for input can comprise up to 20 000 stages  For this reason  the W and A keys  have a Fast Forward function     If the keys are pressed and held down for less than 1 second  the value changes once by a single stage   If the keys are held down for longer than 1 second
18.  2 3     The difference is that the system has 2 sensors for establishing the actual value   It controls automatically to the higher actual value for pressure     Modifications     See 7 2 3    fi Factory pre settings must always be adapted by a specialist to suit prevailing  plant conditions        Page 87 of 92    26 Jo 9g eDeg    JOSU8S ON        vulc y p     C    vuloc 0    on eA  c3 SNIEJS Josuas  enjoy YE  23 9njeA jeny  i JLN WA 9  I  I  I  Old WA O  e F F    S c3 Woj Jeubis  SAGE  3 2 20  oNIEA jeny TER xe 333 T  Z 9 9 m     WWO  i S 23 EED  i E 205 JOSU8S ON  I    m  N    eoJnog  anjen  enjoy VWOZ y    ON eA VOE 0      3 anjen   enjoy  ENJOY 7010    L3 SN EJS Josueg  JIN WA     31d ga O    DY    E    yoeuo uosuedwos Josueg    I    3 Woj jeubis    L3 HUN    xew   3 abues BuunsealN  ul 13 e6ueJ BuunseaN    3 seoejd jewioeq    c ndul  VUIOT v 0    z Indul  AOL 0    y indu   Josuas eJnjeJeduje      z Indul  Josues eJnjeJeduje          ndul  VUIOT v 0      indu   NOL 0    e 1ndu   Josuas eJnjeJeduje        indu   Josues eJnjeJeduje      son eA  ENJJE SUDEJNOIJEJ  TS    19  01 U09 au  10  sueJDeip ynau Vog 8    jsded Lida SIOJOW 23 JO  aolAap  OJJUOD    ENUELU BuneJado    Z6 JO 68 3fed    indjno J9j 0J1u02    jsdeduiqo       10198        99Jnog  uonouny  01 U09  I  9oueleJIp xq   040002    xd    sa  lo 4u02  a  ld li     jeujSjui    DuneeH    80JNOS uonounj  0J1U02  uonounj  0J U02    Joyoe4   d    Bue  jojuo      julodjeS    anjen  enjoy    NO    110    uononpey   juiodje
19.  E1 Min   see 5 2 1 5  is displayed        If this input is at the same value as the Max  Value defined here   the value set in the  Measuring range E1 Max   see 5 2 1 5  is displayed         Intermediate values are then calculated in linear fashion   For the value  OFF   the actual value is always 0        For the sensor comparison check Offset   0  see 5 2 1 6     Page 32 of 92    Operating instructions     EC controller ebm Da pst    5 2 1 3 Unit  gt    Settings  gt  Inputs  gt  Input E1  gt  Unit    Unit El    de    The unit set here is used for all displays which refer to the sensor connected to this input   e g  actual value  setpoints         The following units are possible     5   temperature  bar   pressure    Pa   pressure  m h   air flow  m s   Speed         When unit  C is selected  temperature differences are displayed with the unit  K      5 2 1 4 Decimal places  gt    Settings  gt  Inputs  gt  Input E1  gt  Decimal places    Decimal places El    1       The  Decimal places  value defines the resolution and the value range for the display of all values referring to the sensor  connected to this input  e g  Actual value  setpoints        The following values are possible     AAA 9   999  999        Values outside the value range cannot be displayed and set        When the Decimal places are increased  it is possible that other values  e g  Actual value   setpoints     can no longer be displayed because they lie outside the value range     In this case  the displ
20.  Factor 0 0        Follow up time   Min  speed   Max  speed   Remote enable   Boost mode   Manual mode activation    Manual mode source   Man  mode Duty Cycle  Night limitation activation  Max  night duty cycle  Minimum air shutdown  Shutdown control deviation  Hysteresis    007  Function K1 All faults       ActivestateK1                     opened     On delay K1 0s   Drop out delay K1 0s   FuntinK2          amp                  Off  staie     Active state K2                       opend S   0s    On delay K2 N SS EE  DropoutdelayK2 Os N  Screen display sensor faut   OFF   S  External faultinput J OFF         Sensor     Type   Temperature sensor NTC 103AT  R25   10kO  Connection   Input for temperature sensor 3  terminal strip 3  terminals 29   30     The NTC 103AT has a larger component tolerance than the KTY10 6   If it is not necessary to use an NTC as the temperature sensor  we therefore recommend using  the KTY 10 6 as a sensor  Please refer to 7 1 1        Control     The control behaviour corresponds to that of the  Temperature control  standard  operating mode   For additional information  refer to 7 1 1     Page 77 of 92    Operating instructions     EC controller    7 2 Pressure control    7 2 1 Pressure control  ventilation systems    Application     Pressure control for ventilation systems in HVAC technology    Parameters      Opeaingmde POL o  Sensor type E1          amp       Pressuresensor0 500Pa     1 O Z o    Signal form E1 0 10V ME S S  UntE1          1 1   
21.  SS A 10  3 1 3 Function of ITO inpul COUR ia 10   3 2 MED PES MIB W 6 m                                12  Sud QUOI T   T                                        E 12  22 DIN m RENE EE NE EE EE EE OE 14   d DISPLAYING VERE    ss dei see ses ee de aii 16  4 1 STANDARD DISPLAY titles De en Ge Oe eed 16  4 2 INFORMATION MENU TT              17  4 2 1 DI UM                       neat 17  4 2 2 SOUT II                                                                        YX N 18  4 2 3  5 520 47 7   E     Y                                  N 19  4 2 4 Iob EE OE EE N 19  4 2 5 PCY EE eae oo PA 20  4 2 6 Operatine KOUS COUP static 20  4 2 7 OA T TS O E ceca  20   4 3 ALARM INDICATION MENU ido E E ED CE 21  4 3 1 SYS  c                                                   22  4 3 2 A A 2  4 3 3  7                                                           N 23   o CONFIGURING VALUE Susan adi iii ici REDDE 24  5 1 OPERATING MOD E MENU esa JAS  A de ee CAE OWA 24  5 1 1 WII Mode Rc 2  5 1 2 Qu MV T 2                        26   5 2 SETTINGS MENO e a E E E ciar asia 29  Dd TIT FII E                                    U 30   SM A 3l   E A 22    Page 2 of 92    Operating instructions     EC controller ebm papst    o E RR EE EE EE EE EE N EE EE 33  S14  NE ie bot RE EE EE EE CU 33  24 15 Meisie SA 34  5 2 1 6 Sensor comparison check    sis Re ESE ER ia 34  2 17 Calculation  of the actual value aii od 35  3 2 2 SOPOTIS ad 36  AS  DASETUNENO   zes ci OOOO Dies obire S sue e Duro pO ee N Dieu ob
22.  Setpoint      Setpoint   Control range      20  C   30  C  across the range  Min  speed    Max  speed     25    100       For the actual value  lt  setpoint  the duty cycle corresponds to the min  speed value   25     If the control deviation drops below  3K  the duty cycle is set to 0    This is achieved at an actual value of 17 C   Control deviation   Actual value     Setpoint   17C 20C    3K  Cooling      The fan is switched back on  duty cycle   25   whenever the control deviation reaches this value  Control deviation   Shutdown with control deviation   Hysteresis      3K 1K    2K   This is the case with an actual value of 18  C     Special features  presupposing a pure P controller      If the  Shutdown with control deviation  parameter is positive  the system shuts down before the setpoint is reached   i e  still within the control range     If the  Shutdown with control deviation  parameter is negative  the system does not shut down until the setpoint is  reached    Hysteresis is only able to accept positive values  At a value of 0  the disengagement and engagement points are at one    and the same level    If the  Min  speed  parameter   0  the system always shuts down whenever the control deviation is negative   regardless of the parameters for minimum air shutdown    A negative switching point for the minimum air shutdown then has no effect    If the function is disabled   minimum air shutdown     OFF   the motor always continues running with a negative control  de
23.  The relay contact is connected to a digital input of the control device   Select this digital input in the  External fault input  menu   Then  when a relay contact is opened  a fault is signalled        Page 56 of 92    Operating instructions     EC controller ebm Dd pst    5 4 System menu         System Language See 5 4 1    English    Authorisation level  See 5 4 2    2    Password         See 5 4 2  1000       5 4 1 Language menu 22   System  gt  language    Language       English    Here  the language can be selected in which all displays appear     The following languages are possible     German  English  default   Swedish       54 2 Password function 2 2   System  gt  Authorisation level   Password    Authorisation level Password  2 1000    The password function controls write access to all parameters in the  Settings    Alarm functions    Modbus  and  System   menus  The password function consists of the parameters  Authorisation level  and  Password         Four authorisation levels are defined     Authorisation level   Write authorisation     0     No write authorisation   Write authorisation for Setpoint  gt  Basic function menu only  2 0    2 Write authorisation for all menus except  Holding Register  and  Rot direction source   Write authorisation for all menus       Page 57 of 92    Operating instructions     EC controller ebm Dd pst    The authorisation level configures write authorisation by default  Thus values can be changed even if the corresponding  passwo
24.  digital input     In this case  the parameters for manual mode must be configured as follows  see 5 2 5    e Manual mode activation  Select the same digital input as in Rot direction source   e Manual mode source  Internal   e Manual mode speed  Desired duty cycle for operation opposite the preferred direction       Page 63 of 92    Operating instructions     EC controller ebm Dd pst    6 1 4 Setpoint director 22   Modbus  gt  Configuration  gt  Setpoint director    Setpoint director    Controller       Possible values     e controller  e Manual       If you select  Controller   the duty cycle calculated by the controller is transmitted periodically to all fans via broadcast     If you select  Manual   you can specify the duty cycle for each fan individually     menu  Modbus  gt  Plant  gt  Fan  gt  Settings  gt  Setpoint  see 6 2 2 3    In doing so  the duty cycle is transmitted to the fan only once  when a new setpoint is entered    The duty cycle calculated by the controller is not transmitted to the fans  i e  the control function is inactive at that time    The control device then has a similar function to  EC Control   monitoring software for PC  or  Fan Control   monitoring  software for PDA   but with a greatly limited range of function compared to these programs     6 2 Plant menu  gt  gt  gt  Modbus  gt  Plant    ESC    Fan 32    Information Information See 6 2 1       V      Fan 1 Fan 32   Settings Settings See 6 2 2  Fan 1 Fan 32   i Holding Register i Holding Re
25.  instructions     EC controller ebm papst    With equations for the P share and the difference of the   share  see above   this results in        Controller output n      N xd n    SI Factor  dd NE   Max     Min D 100  Max     Min   Controller output              Controller output   ii to lineales Control deviation   P Factor AA P   Factor set on control device  see above      Factor                            Factor set on control device  see above    VELA Sensor measuring range maximum value  E1 Max or E2 Max    WIRE Sensor measuring range minimum value  E1 Min or E2 Min     This equation is carried out in real time by the control device     Through a process of reshaping  this can be transferred to the standard form of presentation for control functions     PF P Fact I Fact n   Controller output n    E E   A Y xd i   Max     Min Max  Min 100  n  P Factor I Factor Y   Controller output n                          xd n                         gt    xd i   PUO    n  100  2  o   with   Kp   P Factor  Max     Min   and   Ta      I Factor   Tn 100     the standard form of presentation for a Pl controller is created     Controller output n    io sda   0   N is    mH Proportional amplification factor  RE TE Readjustment time           sensing time    When required  the control device parameters can be converted using the following equations into the standard form of  presentation  and vice versa         Kp   P Factor or P Factor   Kp  Max     Min   Max     Min  0  Tn   A Sins or I 
26.  is configured for the preset operating modes     Operating mode Control Control Plant monitoring  over 0 10V output over Modbus output over Modbus a L    Modbus function       Page 28 of 92    Operating instructions     EC controller    5 2 Settings menu    This menu item has various sub menu items which are presented in this overview     OK  Settings Inputs SA    A    pei i  C       A    pem    ZEE     Fan level  Output Al  EZ    Manual mode   R  EZ    Night limitation    Minimum air        Shutdown       see 5 2 1  Input menu    see 5 22  Setpoints menu    see 5 2 3  Control menu    see 5 24  Fan level A1 menu    see 5 2 5  Manual mode menu    see 5 2 6  Night limitation menu    see 5 2 7  Minimum air  shutdown menu    ebmpapst    Page 29 of 92    Operating instructions     EC controller ebm Dd pst    5 2 1 Inputs menu 22  Settings  gt  Inputs  Inputs  OK  ESC  ESC  owe       Sensor type El Sensor type E2 See 5 2 1 1  Temperature Sensor No sensor MI  KTY 10 6       Signal form El Signal form E2    See 5 2 1 2  PTC  A  Unit El Unit E2  See 5 2 1 3  oC  De        Pa  p  E Ta    Decimal places El cimal places E2    See 5 2 1 4  1 0  Measuring range El Measuring range E2  Min Min See 5 2 1 5   30 0  C  Measuring range El         O Pa    Measuring range E2       sA TN See 5 2 1 5  70 09C 1000 Pa  SET p TA   Sensor adjustment El Sensor adjustment E2 See 5 2 1 6    0 0K 0 Pa       Page 30 of 92    Operating instructions     EC controller ebm Dd pst    5 2 1 1 Sensor type 22  Sett
27.  setpoint 2  see 5 2 2 1     b  Function    Setpoint reduction  Setpoint at Endpoint  70Pa    Setpoint reduction Setpoint reduction    Start at End at  15 09 C  15 0  C          For the function  Setpoint reduction depending on E2   3 parameters need to be set     e     Setpoint reduction Start at    e     Setpoint reduction End at  e Setpoint at endpoint       Page 37 of 92    Operating instructions     EC controller ebm Dd pst    With these parameters  a curve is defined which shows how the setpoint of the basic function changes in relation to the  actual value on input E2     Setpoint  E1        Seponti dele del EE EE EE EIE      Setpoint at endpoint  End at Start at Actual value E2  E2   For actual value E2  gt   Start at  is  Setpoint   Setpoint of basic function   For  End at   lt  Actual value E2  lt   Start at  becomes  Setpoint of basic function changed in linear fashion   For actual value E2  lt   End at  is  Setpoint   Setpoint at endpoint  Limitations     The parameter  Start at  must always be greater than or equal to the parameter  End at   Parameters outside  these limits cannot be set and are restricted automatically    The setpoint at endpoint must not be greater than the setpoint of the basic function    In this case  the setpoint for actual value E2  lt   Start at  is increased instead of reduced    If the function  Setpoint reduction depending on E2  is disabled  no value       appears beside any of the values   There is then no input option     The  Setpo
28. 00L  UOHEJNPOJ   y spA9 Ang    JejSUEJ    ap  o Ang  xq xq xq  I I l  e qeue ajoway UOqEANOY epoui  s00g  apou  ENUEJN   G MEG    jsded Lida SJOJOW 23 JO  80IA8p  0J1uoo   jenueu Dunejedo    26 JO 76 9Deg     2 66    00   noub puz  uonei ep  0002   oejuoo    e 9  xy z bl  syne  IN IEEE wa  i jlnej ue   0e U00   ne  ue  Aejoy AU pauado e indu   SB Ne  JeuJ9 X3    pasop    vq La     xQ    ne jeu19 x3  Net JeuJ9 X3    330 0       9 8 S oAnoy  O Z  F a  e E     23 Ine  Josuas  D i NE  Josueg  2     3 Ne  Josuas   lt   i  i  I     ones   HO 0     i    xy uonounJ     Z pue Ly SKelei uyoq 104   eo uap  si uoneAnoy    uoneAnos APA pg    jsded Lida SJOJOW 23 JO  80IA8p J0J1uoo   jenueu DuneadO    
29. 1 and E2  OK Sensor fault on E1 or E2  see 4 3 1  input  see 4 3 2       both sensors  on E1 and E2  OK Sensor fault on E1 or E2    and no faults on the external device or fault of the external device signalled via digital  and no fan fault input    or fault at fans connected via Modbus    Controller output    9596 Controller output   100     Applications and explanations about the functions     a  Off   static  This function is used   e for indicating in operation mode that the control device is switched on  In this case  the active status of the relay must be set to  opened   see 5 3 1 2   The relay contact  NO switch  is then  closed when the device is switched on  e For relays which are not required  In this case  the active state of the relay must be set to  closed   see 5 3 1 2   The relay contact  NO switch  always  remains open     b  Sensor fault   External fault   Fan fault   All faults  This function is used to signal the corresponding fault via the relay contact     C  2nd group   Using the relay contact  other fans can be engaged    The relay contact switches the 2 groups on whenever the controller output reaches a value of 100   i e  if maximum fan  power is not sufficient to reach the setpoint    Once the controller output drops back below 95   the 2nd group is switched off again    The switching operations can be delayed using the  On delay  and  Drop out delay  parameters  see 5 3 1 3      Page 54 of 92    Operating instructions     EC controller ebm Dd pst  
30. 28 30 32      LLL  17119121123125 27 29 31    y          D  amp  el   w e b a FI E E PI dd i u           ME EE    N L2  L1 PE    Relay K1  Relay K2  24 V   24 V  0 10V input 1  GND  GND  GND  GND  RSB  RSB    Power system  1 200 480V  50 60Hz  eu  uL y    Terminal strip 1 Terminal strip 2 Terminal strip 3    Temperature sensor 1  Temperature sensor 2  0 10V input 2  0  10V output A1  0  10V output A2  Temperature sensor 3  Temperature sensor 4    Page 7 of 92    Operating instructions     EC controller    2 3 Supply voltage    Terminal designation  Terminals 1 3  terminal strip 1     Nominal voltage  1   200 480V  Frequency  50 60Hz    ebmpapst       Power input     15VA  2 4 Inputs    2 4 1 PTC temperature sensors    Two temperature sensors can be connected     Terminal designation  Terminal strip 3  terminals 1 2  temperature sensor 1   Terminal strip 3  terminals 3 4  temperature sensor 2        Permitted sensor  KTY 10 6  R25   2kO    2 4 2 NTC temperature sensors    Two temperature sensors can be connected     Terminal designation  Terminal strip 3  terminals 29 30  temperature sensor 3   Terminal strips 3  terminals 31 32  temperature sensor 4        Permitted sensors  NTC 103AT  R25   10kO    2 4 3 Input 0 4  20mA    Two sensors can be connected to an 0  20mA  or 4  20mA output     Terminal designation  Terminal strip 3  terminals 610  sensor 1   Terminal strip 3  terminals 8 12  sensor 2   Permitted sensors  0  20mA  4  20mA  Input resistor  1000    2 4 4 Input 0  10V
31. 6 corresponds to a voltage of 10V at output A1     Page 50 of 92    Operating instructions     EC controller ebm papst    5 2 6 Night reduction mode        Settings  gt  Fan level A1  gt  Night limitation    Night limitation Night limitation    Activation Speed  OFF 100        With this parameter it is possible to place an upper limit on the duty cycle at output A1  and therefore the speed of the fan      This limitation can be enabled by means of the selected digital input   If the function is enabled  output A1 restricts the duty cycle  i e   speed   to the value shown in the  Night limitation   parameter     Possible values for  Night limitation activation         e OFF   always  No limitation  e D1   Digital input 1   open  No restriction   Digital input 1   GND  Restriction to  Night limitation speed   e  2   Digital input 2   open  No restriction   Digital input 2   GND  Restriction to  Night limitation speed   e D3   Digital input 3   open  No restriction   Digital input 3   GND  Restriction to  Night limitation speed   e D4   Digital input 4   open  No restriction   Digital input 4   GND  Restriction to  Night limitation speed        Application    This function is used for the night reduction mode    At the digital input selected in the  Night limitation  parameter  contact is made with a timeswitch  If this contact is closed  during the night by this timeswitch  the speed is limited to the value set in the  Night limitation speed  parameter     527 Minimum air shutd
32. 66  S8 NEN DC TUI DEAD AA DOTT 67  VN 2 speed  duty OOO NER           67  OE  RE                          67  02 1   ii  AAA EE ER RN MN M EARUM kd 68    A Opera  une NOUIS er een em eee nem t I Ui 68  6 2 2 NAAA ECCE EEE 69  A M A II A 69  0222    ER RE RE EE AE E 70    Page 3 of 92    Operating instructions     EC controller ebm papst    PAPA MEME  EE EE OE N S 71   6 2 3 ias AMA 71  6 2 4 MODUL RZS se o EE 72   7 PRESET OPERATING MODES                22202002000000000000000000000000000000000000000000000000000000000000000000000000 73  7 1 TEMPERATURE CONTROL  ase R iia 73  7 1 1 Temperatura CONTO SIMAO RE EE 73  24 2 NES GOO VT CORO sna EE EE OE IE EE N N OE EE N N 76   7 2 PRESSURE CONTROL Lanas 78  Z   4 Pressure control  ventilation systems       eie ees sees ese ee ee ee ee ee ee ee ee ee ee ee ee ee 78   gt  Pressure control  ambient temperature compensated               esses SU  7 2 3 Pressure control of condensers        ee ee ee ee ee ee ee 83  had Pressure control  dual circuit condensers SS SS ee 86   8 BLOCK CIRCUIT DIAGRAMS FOR THE CONTROLLER                  22 00 000 00000000000000000000 88  8 1 CALCULATING ACTUAL VALUE Sia ai 88  8 2 CALCULATING SETPOINTS   CONTROLLER          cccscecceccecceccececcecceceececcsceececscescaecncescuscsescescuss 89  8 3 CALCUEASTING DUTY    YC IGE aos 90  8 4 RELAY ACTIVATION SS 92    Page 4 of 92    Operating instructions     EC controller ebm Dd pst    1 Operating instructions       1 1 General instructions    To assure prope
33. Actual value  20  C 25  C    b  Change in control range    Duty Cycle  Al    100        0     Actval  20  C 25  C 30  C AE  Setpoint    c  Change in control function    Duty Cycle  Al    100        0   Act value    15 C 20  C 30  C  Setpoint    ebmpapst    Page 75 of 92    Operating instructions     EC controller    d  Change in Fan level A1  min  speed  max  speed     Duty Cycle  Al    A EE EE      C ME EE A             Min   0     30  Max   100         0   Act value    SK  Control range    20  C  Setpoint    25  C    7 1 2 NTC temperature control    Application     ebmpapst    Temperature control of air conditioning and refrigeration systems for applications that require an NTC as the temperature    sensor     Parameters     Parameter mea  lt  setting 2      Operating mode     o    Sensor type E1 SEE sensor  NTC 103AT    EE AE  Measuring RED I o  a S o OOOO O O O o    SignalfomE2   FF   UntE2 Pa  Decimal places E2 J o 0 S  Measuring range E2 min J        MeasuringrangeE2max       1000    Sensor comparison check E2           0      Sepon        200 J     Switchover  setpoint 12 f       OFF                         Setpoint2 d 200   J         Setpointreduction J   OFF                              Sesde ft  Setpoint reduct  End                    5 N     Setpointatendpoint J    700         Control functsource          Intemal    Control function   Coding             Page 76 of 92    Operating instructions     EC controller ebm Dd pst    Customer setting 2  po    2400  po       
34. Duty Cycle       The current speed of the fan and its duty cycle are displayed     6 2 1 3 Power       Modbus  gt  Plant  gt  Fan  gt  Information  gt  Power    Power 50W    The current power input of the fan is displayed     Page 67 of 92    Operating instructions     EC controller    6 2 1 4 Temperatures 22  Modbus  gt  Plant  gt  Fan  gt  Information  gt  Temperatures    Fan 1  T module    50  C  T motor    60  C       T electronic 30  C    Various temperatures of the fan are displayed   e    module    e    motor  e  electronic      Temperature of the output stage module    Temperature of the motor winding      Temperature of the electronics interior compartment    If the corresponding temperature sensor is not present in the fan  no value       is displayed for  this temperature        6 2 1 5 Operating hours 222  Modbus  gt  Plant  gt  Fan  gt  Information  gt  Operating hours    Fan 1    Operating hours       The operating hours of the Fan are displayed     Page 68 of 92    ebmpapst    Operating instructions     EC controller ebm Dd pst    6 2 20 Settings menu    Fan 1  Settings       22  Modbus  gt  Plant  gt  Fan  gt  Settings    Fan 1  Fan address See 6 2 2 1  See 6 2 2 2  See 6 2 2 3    Setpoint  0     In the  Settings  menu  the values can be both read and modified     If a value in the fan could not be modified correctly  the message  Write access error  is  displayed     Possible causes of the fault     6 2 2 1 Fan address    Fan 1    Fan address  1    The connec
35. Factor   OMS 100   I Factor Tn    Page 43 of 92    Operating instructions     EC controller ebm Dd pst    5 2 3 5 Actual value source 23   Settings  gt  Control  gt  Actual value source    Actual value source    El       The parameter  Actual value source  can be used to select which input should supply the actual value for the controller     Possible values          E1   Actual value from Input E1 is used   E E2   Actual value from Input E2 is used      Max E1 E2    The higher actual value for both inputs E1 and E2 is used   Applications     For the basic function  it is advisable to use input E1 as the Actual value source      If input E2 is used  other functions defined on input E2 cannot be used  e g  setpoint reduction  depending on E2         The Max E1 E2  setting is used for        Two circuit condensers  control to higher pressure  e Temperature control with 2 sensors  control to higher temperature    selecting  Max E1 E2   is logical only if   e Both sensors are active  Signal form E1     OFF  AND Signal form E2 7  OFF    e Both sensors have the same unit  Unit E1   Unit E2     Otherwise  selecting  Max  E1  E2   can cause undesirable effects    e  f only one active sensor was selected  the actual value 0 is assumed for the inactive sensor    e  fthe units of the two sensors are different  the unit of sensor E1 is always used for the actual  value     If the parameter  Actual value source  is changed  the P   Factor changes if a different measuring  range has been s
36. Operating instructions     EC controller ebm papst    Operating instructions  EC controller    Vor Offnen des Deckels Ger  t spannungstrei schalten      A Switch off the main supply before removing the cover    Togliere   a tensione prima di rimua i  coperchio      vere fi       Manufacturer  ebm papst  Mulfingen GmbH  amp  Co  KG    Bachm  hle 2   D 74673 Mulfingen  Germany  Phone   49 7938   81 0   Fax   49 7938   81 110   info1 Q  de ebmpapst com    www ebmpapst com    Page 1 of 92    Operating instructions     EC controller ebm papst    Table of contents    1  OPERATING INSTRUCTIONS issie sessie sed Res sisne Nes sd REEF PESE FERRE ed see Ge Ne Ge ke sek ke de ee ba be sad bei 5  2 LAYOUT CONNEC HO Ns 23309222 011 8 0800 od N ea ei ee N Ge Ao ed 6  2 1 MECHANICAL LA VOE CPP 6  2 CONNECTION TERMINAL oe Gee ee oos Ee Ge Ee EKO EPL iwo EEG DM M OE A EE 7  2 3 SUPPLY WOETS EE nuevos aisl   ollo 8  2 4 NOUS PP eo RP o PS II III A IIA 8  2 4 1 PITE Jen DOPO OS CIS OVS EE EE EE ER EE N 8  2 4 2 NTC temperature sensors    ee aaa aaa aaa aaa aaa aaa aaa aaa aaa aaa ee ee sess sse nnn nennen nnns     2 4 3 DTU Me A 8  2 4 4 A AE EE eo e     Ie 8  2 4 5 BE                                Y                       amp    2 5 GOAL ONECIE EEC 9  2  EN   ne 9  2 3 2 Pie al OUI  relay COMA o ciao 9  PARE  TOW CI SUI TOF SWS OKO N 9   2 6 BUS CONNECTION PAPER 9   3 OPERAS TION EE EE EE 00269  is 10  3 1 AA o A e UU O O A 10  3 1 1 Dy     9                                               10  12
37. Using the Modbus interface  up to 32 ebm papst fans can be connected to the control device   The configuration and data exchange with the fans are carried out in the sub menu items of  Modbus      Modbus       See 6 1  See 6 2  6 1 Configuration menu       Modbus  gt  Configuration  OK  Configuration Modbus function See 6 1 1       Init range See 6 1 2 1  32  AN    Init status          Scanned  See 6 1 2 2  Initialisation  See 6 1 2 3  NO    TA  Rot direction source See 6 13  OFF    TA  Preferred direction  See 6 1 3  clockwise  Setpoint director See 6 14    controller       Page 59 of 92    Operating instructions     EC controller ebm Dd pst    6 1 1 Modbus function       Modbus  gt  Configuration  gt  Modbus function    Modbus function    ON       The  Modbus function  parameter switches all communication via Modbus on and off   Possible values     E ON   Bus function disabled  e OFF   Bus function enabled    owitching on the Modbus function has the following effects    e Automatic initialisation run  immediately after switching on and after every reset of the device    e The duty cycle is sent to all fans via broadcast    e The fault status of all fans found during the initialisation run is checked via a circular query     If the bus function is not required  i e  the fans are triggered via 0 10V signal   the Modbus  function should be switched off so as not to use up unnecessary computing capacity in the  control device     Then  no signals are output at the Modbus output
38. authorisation level 2     Authorisation level can be adjusted in the range 0   2  Enter the password for authorisation level 3     Authorisation level can be adjusted in the range 0   3    This authorisation procedure ensures the following   e The password does not have to be entered for each write access if this was not desired   e No write access is possible that was not permitted by an authorised person     e  he preset authorisation level cannot be downgraded accidentally without knowing the password   otherwise  write access would no longer be possible      If the input menus on the control device do not respond to the  OK  key being pressed  i e  the    display does not start to flash   write protection is enabled     In this case  the correct password must be entered in order to enable the input function        Recommended procedures for setting the password function        e Desired function  Each user is to have write access  Leave authorisation level at  2    factory setting     e Desired function  Write authorisation is to exist only if the correct password is entered  Enter password for authorisation level 2  Change authorisation level to 0  Delete password  enter 1000     e Desired function  Write access to parameter  Rot direction source  or Holding Register required  Request password for authorisation level 3 from ebm papst and enter password  Change authorisation level to 3    Page 58 of 92    Operating instructions     EC controller ebm Dd pst    6 Modbus    
39. ay for these values is as follows     MAX for a value greater than the value range      MIN for a value less than the value range    In this case  it is advisable to check all values in the  Settings  menu for compliance with the  value range and  if necessary  to reconfigure them        Page 33 of 92    Operating instructions     EC controller ebm Dd pst    5 2 1 5 Measuring range 22   Settings  gt  Inputs  gt  Input E1  gt  Measuring range    Measuring range El Measuring range El    Min Max   30 09C 70  DE       Here  you should enter the measuring range for the sensor     These values directly influence the calculation of the actual value        5 2 1 6 Sensor comparison check 2   gt  Settings  gt  Inputs  gt  Input E1  gt  Sensor comparison check    Sensor adjustment El    0 0K       Here the output value of the sensor can be changed subsequently to compensate for deviations in the output signal   The value set here is added to the value established     Page 34 of 92    Operating instructions     EC controller ebm papst    5 2 1 7 Calculation of the actual value    The parameters described in Chapter 5 2 1 Menu inputs determine how the actual value is calculated  depending on the  signal form selected  as follows        R    1260Q       signal form  PTC    Actual value                       Max     Min    Min   Offset  15300    U  Signal form  0 10V    Actual value            Max     Min    Min   Offset  LOF  I  Signal form  0 20mA    Actual value            Max     Min  
40. ayKi       o       o   o   o     Funcionk        Of stwic   Offistaio   Of  staie    Oflstio     Active state KA   opened   opened   opened  opened     on delayka          o   o   o J o     Drop outdelayka           0s   o   o   o       Screen display sensora              OFF   OFF   OFF     oF         Extemafadtinpt_                  OFF   OFF   _oFF   OFF  S    Page 26 of 92    Operating instructions     EC controller ebm Dd pst       Operating mde           ca     X C02       DESI HRS TA  0  30bar 0  30bar   SignalformE1            4 20m       420mA FC   Unit E1    Bar    bar   Decimal places E1   2       BS    Measuring range E1 min  de A 3   4  Measuring range E1 max 30 00 30 00           ensor comparison check ET   0o   o    po  ET type E2 No sensor Pressure sensor  0  30bar  AAA    Signal form E2     4 20mA    Unit E2                                      DecimalplacesE2          o          2       LE   Measuring range E2 min       0       o            o   Measuring range E2max       1000   Re   Sensor compart chec   0   6 tt  Setpoint    1200 BE    Swichoverseponti         o   oF      O   ES   Sepont2   1200   ro     Setpoint reduction   OFF   oF     Setpoint reduct  Stat _   15   1800      O    o    O   Soo SoS   Setpoint reduct End              15   BY   Setpoint at endpoint       7000   7000                            Control funct source       Internal   ntem                            Control function     Cooling   Cooling                  SSS   Controlrange   so 
41. comparison check   0 0   00   00       09          9           0   200Pa 0  500Pa 0  1000Pa 0   30 bar  Unit     po Pa    _Pa          Pa   Pa   Pa    DeimaplcesET         0      0   0o AO   MeasuringrangeEtmin   0             0 0 00   30     Sensor comparison check   0   0   0 00   J  O         The selection option of  No sensor  is provided for open inputs  e g  if only one sensor is used  In the display for the  corresponding actual value in this instance  no value appears         For processing purposes  the value 0 is assigned to the corresponding actual value     Once a sensor is connected which is not available in the above list of preconfigurable sensors  you must choose the   Individual  selection option    In this instance  all parameters in the  Input E  or  Input E2  are adapted to suit the sensor in order to assure that each  sensor parameter is displayed correctly     Page 31 of 92    Operating instructions     EC controller ebm Dd pst    5 2 1 2 Signal form     22   Settings  gt  Inputs  gt  Input E1  gt  Signal form    Signal form El    PTC       Here  the form of sensor output signal is entered     Possible values        The sensor must be connected to the intended input on the control device     0 20mA 0 4  20mA  4 20mA 0 4  20mA  Dr   ARA    qe Jem ee        see 24  For calculation of the actual value  the signal from the input selected here is used     If this input is at the same value as the Min  Value defined here   the value set in the  Measuring range
42. dbus  gt  Plant  gt  Fan  gt  Information    Fan 1    Fan 1  Information Failure status See 6 2 1 1  OK    Duty Cycle 30   See 6 2 1 3  Fan  T module  T motor See 6 2 1 4  T electronic  Operating hours See 6 2 1 5       In the Information menu  there is no write access to the data   The values can be displayed only     Page 66 of 92    Operating instructions     EC controller ebm Dd pst    6 2 1 1 Failure status  gt  gt  gt  Modbus  gt  Plant  gt  Fan  gt  Information  gt  Failure status    Fan 1    Failure status  OK       The failure status specifies the status of the respective fan and a possible cause of the fault     Possible values     OK   Phase failure   Power module overheated   Internal comm error  communication error between the microcontrollers in the fan   Motor overheated   Hall sensor failure   Locked motor   Electronics overheated   Overvoltage   Undervoltage   Reversed operation  external drive in reversed operation at high speed for longer period   Not connected  RS 485 connection between control device and fan is interrupted     If an error is displayed without further information   Error No           it was not yet defined at the  time the control device was developed and thus cannot be output in plain text    If this display appears  refer to the corresponding  Modbus parameter specification  of the fan to  determine the cause of the fault        6 2 1 2 Speed   duty cycle 22   Modbus  gt  Plant  gt  Fan  gt  Information  gt  Speed   Duty Cycle    Speed  
43. dress to the value  2   The fan is then no longer accessible  question mark appears in the display   You do not need to carry out another initialisation run for the time being   e Connect the next fan to the network and switch it on  This fan also has fan address 1 and can be reached at this  address  To obtain a valid display  you have to exit the  Fan address  menu briefly   Change the fan address to the value of  3   After this procedure  connect one fan after another to the network  When doing so  increase the fan address by 1 for  each fan     e Connect the last fan to the network  You can leave this fan at the address  1    e Start the initialisation run  All fans appear in the  Plant  menu   6 2 22 Reset 2  Modbus  gt  Plant  gt  Fan  gt  Settings  gt  Reset    Reset  NO    If the value is changed to  YES   a reset in the fan is triggered  This causes a defined restart of the firmware in the fan  After  the reset process in the fan is finished  the value is set to  NO  automatically   Application     If there is a fault in the fan  see 6 2 1 1   it can be cleared by a reset only  The fan cannot restart  until the fault has been reset     If the cause of the fault is not eliminated  the fault can reappear immediately after the reset        Page 70 of 92    Operating instructions     EC controller ebm Dd pst    6 2 2 3 Setpoint       Modbus  gt  Plant  gt  Fan  gt  Settings  gt  Setpoint    Fan 1    Setpoint  0        Here  you can assign each fan an individual setpoint 
44. e in setpoint     Often the user requires a different setpoint to the standard one   After each change in setpoint  the device controls the actual value to the new setting     The setpoint curve is dependent on ambient temperature and changes as follows   Setpoint  Pa        P NM A NE OE ET AE ER AE    70     15 15 T C     b  Change in parameter for ambient temperature compensation   Setpoint  Pa     250    70 PO       15  5 10 15 T C     Setpoint  Pa     250    150      Setpoint at endpoint   70Pa  70 l     15 15 T C     Page 82 of 92    Operating instructions     EC controller ebm Dd pst    7 2 3 Pressure control of condensers    Application     Pressure control for condensers in refrigeration technology    Parameters     Customer rss E    g  Operating mode    Sensor type E1 Pressure sensor  0  30bar    HEER    1 1                    Measuringrange Et min f      0  3        Measuring range Ef max              3000      Sensor comparison chekEl                0      SensortypeE2               Nosesr                        SignalformE2   OFF J        A             DedmalpaesE2            0 N              Measuring range E2 min              0     Measuring range E2 max           100                    Sensor comparisoncheckE2              0 N  Setpoint        2  1900     Switchover  setpoint 1 2 J     OFF      Setpoint2 S 1200          Setpointreduction J    OFF                               Ses EL o  Setpointreduet End     J          15 N  Setpoint atendpoint       7000      
45. e used while in perfect condition     Page 5 of 92    Operating instructions     EC controller ebm papst    2  Layout  connection    2 1 Mechanical layout    Befestigungspunkte   mounting points   100          Page 6 of 92    Operating instructions     EC controller ebm papst    2 2 Connection terminals    Terminal strip 1 Terminal strip 2 Terminal strip 3             a    gt   x   a  o   EJEA       pols           Ei           E           oaj o  ale  N  CO      N  o       STS      N  N N  B  N   N N  Oj      NIS  TJ   CO  N  CO  EE           x  T  m         A2 output 0   10V               GND  A    or2  GND    Input 0 10V  GND    Input 0 10V    A1 output 0   10V   GND    GND    S  Temperature sensor 4    or 1  ebm Bus RSB  RSA    Relay 1  Relay 2  GND  R     24V    Input 0 20mA   24V    power supply  1 200 480V  50 60Hz    Input 0 20mA    Temperature sens   Temperature sens  Digial input 1  Digital input 2  Digital input 3  Digital input 4    RS485     Temperature sensor 3    The power supply of the control device is connected to terminal strip 1  Compatible cross section  0 08     2 5mm   Two relay outputs are connected to terminal strip 2  Compatible cross section  0 5     1 5mm   The remaining inputs and outputs are attached to terminal strip 3  Compatible cross section  0 5     1 5mm     0  20mA input 1  0   20mA input 2  Digital input D1  Digital input D2  Digital input D3  Digital input D4    GND  GND  GND  GND  GND  GND  RSA   RSA   GND  GND          n  18 20 22 24 26 
46. elected for the sensors  Max  Min    If necessary  the P   Factor must be corrected subsequently        Page 44 of 92    Operating instructions     EC controller ebm Dd pst    5 2 3 6 On Off speed and follow up time 22  Settings  gt  Control  gt  On Off speed   Follow up time    ON OFF speed Follow up time    0  Os       If the duty cycle reaches the value  On Off speed   the time set in  Follow up time   remains at the value of the  On Off  speed     If the duty cycle does not rise again on completion of the follow up time     e  if it still has a value of  On Off speed      the duty  cycle is set to a minimum level from this time onwards of  Min  speed     The duty cycle remains at this value until the control deviation becomes positive again     The maximum value for the follow up time is 254s  If the value is increased even more using the A button     s appears in  the display  This means the value  infinite   i e  the duty cycle never falls below the value for  On Off speed      Application     The 0  10V input for ebm papst fans is defined in such a way that the fan stops whenever the allowed value drops below 1V  or comes to rest at that level     Through favourable setting of these parameters it is possible to prevent the output signal from the control device dropping  below 10  and the fan therefore shutting down briefly in response to a negative setpoint jump  specifying a lower setpoint   and an l share  gt  0  until such time as the actual value drops back below t
47. for the duty cycle     This menu is active only if the value  Manual  is configured in the Setpoint director menu  see  6 1 4   Otherwise  no value       appears and there is also no input option        6 2 3 Holding Register  gt  gt  gt  Modbus  gt  Plant  gt  Fan  gt  Holding Register    Fan 1  Holding Register  Address DOOO  Data 0000    Fan 1  Fan 1 Holding Register  Holding Register Address D100  Data 0001    Holding Register  Address DFFF  Data P       In the  Holding Register  menu item  the values of all Holding Registers of a fan can be displayed and modified in a range  between D000 and DFFF  This is the address range in which all Holding Registers of ebm papst fans typically lie  All values  are displayed in hexadecimal format     Because the control device displays only very few Holding Registers of a fan in plain text  Fan address  Reset  Setpoint   this  menu provides an opportunity to check the configuration of the fan and change it if necessary     The Holding Register area contains a total of 4096 sub menus  one for each Holding Register address between D000 and    DFFF   To enable quick toggling between the individual menu items  the address of the individual menu items can be  changed quickly by holding the W or A button  similar to the fast mode function when editing data      Page 71 of 92    Operating instructions     EC controller ebm Dd pst    For the function of the Holding Registers  refer to the  Modbus parameter specification for ebm standard serie
48. gister See 6 2 3  Fan 1 Fan 32   See 6 2 4    Input Register Input Register             Page 64 of 92    Operating instructions     EC controller ebm Dd pst    The Plant menu contains a menu item for each fan found during the initialisation run  specifying the address of the  respective fan   Thus the number of menu items can vary between 0 and 32     If no fan was found during the initialisation run  the following display appears in the Plant menu     Plant    No fan found    The fan menus can then not be activated     If the Modbus function is inactive  see 6 1 1   the following display appears in the Plant menu     Plant    Bus inactive    The fan menus can then not be activated     All values in the  Plant  menu are stored in the corresponding fan only   If the connection between the control device and fan is interrupted  a question mark     appears  instead of the value     For all connected fans  ensure that the configuration of their Modbus parameters is configured to  the control device   Otherwise  the proper interaction between the control device and fan is not guaranteed     opecifically  ensure that the following Holding Registers are set correctly    e D101 Setpoint source Value  0001  RS485    e D103 Save setpoint Value  0000  do not save setpoint   e D106 Daytime operating mode Value  0002  control    e D107 Nighttime operating mode Value  0002  control        Page 65 of 92    Operating instructions     EC controller ebm papst    6 2 1 Information Menu S gt  Mo
49. hat of the setpoint   in unfavourable cases  this  shutdown can cause the controller to vibrate      With PI controllers   share  gt  0   it is therefore necessary to note the following points     The On Off speed should be set to a value substantially above that of the engagement threshold  of the fan  e g  with the ebm papst catalogue fan 12      The value for the follow up time is dependent on the control system  The maximum time period  needs to be established during which the controller output remains at the value  On Off speed  in  response to negative setpoint jumps  The follow up time must be greater than this period of time     Comment     If the fan shuts down briefly in response to negative setpoint jumps  you must  1  Set the  On Off speed  to a value greater than the engagement threshold  2  Increase the  Follow up time  until the fan ceases to shut down        Page 45 of 92    Operating instructions     EC controller ebm papst    5 2 4 Menu for Fan level Al 22  Settings  gt  Fan level A1    Fan level in   Output A1 oee 5 24 1    Max  speed        See 5 2 4 1  100   TELS  Remote enable See 5242  B t d  ee ee See 5 2 4 3  OFF  5 2 4 1 Min  speed and max  speed  gt     Settings  gt  Fan level A1  gt  Min  speed   Max  speed       The two parameters  Min  speed  and  Max  speed  determine the function which assigns a duty cycle to the controller  output    With a controller output of 0   the duty cycle quoted at output A1 for  Min  speed  is issued    With a control
50. he initialisation via Modbus  see 6 1 2    The number of menu items depends on the number of fans found  i e  up to 32   For differentiation  the specific fan address  is specified  If no fan has been found  this display is omitted     Possible values     OK   Phase failure   Power module overheated   Internal comm error  communication error between the microcontrollers in the fan   Motor overheated   Hall sensor failure   Locked motor   Electronics overheated   Overvoltage   Undervoltage   Reversed operation  external drive in reversed operation at high speed for longer period   Not connected  RS 485 connection between control device and fan is interrupted     If an error is displayed without further information   Error No           it was not yet defined at the  time the control device was developed and thus cannot be output in plain text    If this display appears  refer to the corresponding  Modbus parameter specification  of the fan to  determine the cause of the error        Page 23 of 92    Operating instructions     EC controller ebm Dd pst    5 Configuring values    The menu items  Operating mode    Settings    Alarm functions  and  System  of the main menu contain values that are both  displayed and modified  These are parameters that can be used to configure the function of the control device     5 1 Operating mode menu    Operating mode Operating mode 1  Temperature ctrl TO1 See 5 1 1  Standard    Operating mode 2  Control See 5 1 2  over 0 10V Output       Easy i
51. ing instructions     EC controller ebm Dd pst    7 Preset operating modes    A simple installation of the control device can be achieved by selected pre programmed operating modes  Selection is made  via the menu item Operating mode  gt  Operating mode 1    When selecting application specific operating modes  configuration of the  Settings  and  Alarm functions  menus is  performed automatically  i e  all values in these menus are overwritten with the preset values    The factory pre settings for each operating mode are based on experiential figures compiled over many years and suitable  for many different applications  In exceptional cases  these can be adapted individually by manually changing the figures in  the  Settings  and  Alarm functions  menus     7 1 Temperature control    7 1 1 Temperature control  standard    Application     Temperature control  climate and refrigeration technology     Parameters     IL setting  Operating mode    Sensor type E1 Temperature sensor  KTY 10 6    Signal form E1    DIT DEINER NNNM A KONA  Measuring range E1 mn           300 N  Measuring enge e t    SinafomE2        1 1 1        OFF          UntE2         1   Pa       A4                   Decimal placesE2   0 N  h              MeasuringrangeE2min J    Measuring range E2 max               100       j     Sensor comparison chekE2           0      Setpoint  o  02320 0   32 20         B    v    Switchover  setpoint 12           OFF      Setpoint2             200           2 47  Setpointred
52. ings  gt  Inputs  gt  Input E1  gt  Sensor type    sensor type El    Temperature sensor  KTY 10 6       Here  a sensor from the ebm papst range can be selected     Possible values        Individual   Temperature sensor KTY 10 6  Temperature sensor NTC 103AT  Temperature sensor 50003 1 0174    output 0  10V  Temperature sensor 50005 1 0174  output 0  10V     R25   2kQ            Pressure sensor 0   100Pa  output 0  10V                R25   10kQ     Pressure sensor 0   500Pa output 0  10V  Pressure sensor 0  1000Pa  Pressure sensor 0  30bar  No sensor             Pressure sensor 0   200Pa output 0  10V           output 0  10V  output 4  20mA     If a sensor proposed by ebm papst is chosen  value 7  Individual    the properties of the sensor   i e  remaining values in the  Input E1  or  Input E2  menu  are automatically adapted to reflect  the choice of sensor and overwritten with the preset values     When a sensor proposed by ebm papst is selected  the input option for the remaining values in the   Input E1  or  Input E2  menu is blocked  with the exception of the sensor comparison check         The following values are assigned to the sensors proposed by ebm papst     Sensor type Temperature Temperature Temperature Temperature Pressure sensor  sensor sensor sensor sensor 0   100Pa  KTY 10 6 NTC 103AT 50003 1 0174 50005 1 0174    Unit S   ba AAA    Measuring range E1 mn      300      300   __60___    3 200 JO     Measuring range ET max   700   800   450   800   109     Sensor 
53. int reduction  function should be enabled only if sensor E2 is active   Signal form E2     OFF      Otherwise  the value 0 is used as the actual value E2        Application     This function is preferably used for pressure control or air flow control with ambient temperature compensation    At input E1  a pressure or air flow rate sensor is then required    At input E2  a temperature sensor is connected    The pressure or air flow rate setpoint is reduced in linear fashion as a function of the measured  ambient  temperature as  soon as ambient temperature drops below the  Start at  level    Below an ambient temperature of  End at   the setpoint    Setpoint at endpoint      Page 38 of 92    Operating instructions     EC controller    5 2 3 Control menu      gt  Settings  gt  Control  OK  Control Control funct source  Esc  Internal       y t     Control function    cooling  WEZ    Control range          5 0K  y TA    P   Factor    2000   ET     I   Factor       0 0     y TA             Actual value source    El  MEL    ON OFF speed    0   y TA    Follow up time    Os       See 5 2 3 1    See 5 2 3 1    See 5 2 3 2    See 5 2 3 2    See 5 2 3 3    See 5 2 3 5    See 5 2 3 6    See 5 2 3 6    ebmpapst    Page 39 of 92    Operating instructions     EC controller ebm papst    5 2 3 1 Control function  gt    Settings  gt  Control  gt  Control function    a  Control funct source    Control funct source    Internal       Using the parameter  Control funct source   you select which sou
54. intreduct Stat ts                45     Bo   86    Setpoint reduct  End         1 15      15   15          150      Setpoint at endpoint   700    X 700      7     Controlfunctsource        Intemal   Internal   Internal     Inteml      Control function               Cooling   Cooling _   Heating _     Heating    Control range    50      50   1000       1000        3               P Factor o o   20006   24006 4  50      50       l Factor o o 1   00    00     506    J  50       Actual value source   E      Et   El   Et    j           9      On Off speed         0    0     1      X 12      Follow up time    0s   Os        20       205           Min speed              0    0    0 6     2  0  J                  Max  speed       1005   1006   100    100  N S  Remote enable         OFF   OFF   OFF   OFF            Boostmode   X OFF   OFF   OFF   OFF    j               Manual mode activation                 OFF          OFF   OFF 1  oF   o      Manual mode source           Internal   Internal   Internal     Internal     Man  mode Duty Cycle    Night limitation active         OFF   OFF   OFF    OFF                    Max  night duty cycle            100    100    100    100      Minimum air shutdown       OFF   OFF      OF   OF                 00 j  00   0   20       Shutdown control deviation    Hysteresis      oo   00 1     0   oS O  Funcion K     Al aus    Alfauts   Allfauts   Aitas    LAcivestateKi   opened   opened   opened  opened    On delay K  ts     os       0s   o     Drpoude
55. ire Uo  36  5 2 2 2 Setpoint reduction depending on E2                          EE Ee EE EE EE 37  9 223 A             E              39  SAN EE rero BUT TC NOST TEE 40  12 32 COntol ranpexdnd P  Faclor EE t to  41  HAS  EE ie EE RE OR OE 42  A o A R E etit mE eius UE M 0 42  3205 Acal Valle SOHO  ss de Daetete AO oe Re 44  5 2 3 6 On Off speed and follow up time                       eese eene 45  5 2 4 Mena TOP Ponle AE N EE OE N GE EE IE 46  3241 Min Speed and Max speed  aanse ee ei tie 46  2224 2  A A A 47  24  ao ol A On Pe EG E EA Ee 47  5 25  MIODU MODE MT EE eS o OO   O  E 48  5 2 5 1  Manual mode AAA 48  05202 Manual mode SONCE AAA O UU bed ee enire 49  22 5 Manual modes Deodato ateo 50  5 2 6 NTE ele oe N eo EE EE AOC OE OCE 51  2 227 Minimum air Shutdown    zazna aaa aaa aaa ee ee ee ee aaa aaa nora nn nan nn nene esee sess ee ee ee nn 51  5 3 ALARM EUNCNON  MENU uns AE OO ge Ge Ed 53  5 3 1 ROA II                              33  A AA mcn 54  F AE nu o     od N ER 55  A o A                                     M 55  3 9 2 SMS OF  21710 0 14023 117 RR RN T 55  5 3 3 AA 56  5 4 SPI m np m                                        57  5 4 1 LR CUATE ME estas 57  5 4 2 SIS ORE A A OE EN 7  O MODBUS sumen iio ticas 59  6 1 CONFIGURATION MENU esca nico 59  6 1 1 o DRE 60  6 1 2 Jo nme A EO EE OE EO EE EN 61  S NN ME FC eau Rc 6l  A a en 62  6 12 3  Manualimtalz adan ii 62  6 1 3 Direcional A OE OE ES EE EE OE 63  6 1 4 No A 64  6 2 PLANT MENO asa oa oia 64  6 2 1 JI 021 AA 
56. le in order to minimise the time  for an initialisation run        Page 61 of 92    Operating instructions     EC controller ebm Dd pst    6 1 2 2 Init status  gt  gt  gt  Modbus  gt  Configuration  gt  Init status    Init status    Scanned   Found        The initialisation status  Init status  specifies how many fan addresses have been queried during an initialisation run and  how many fans have been found   No input option exists in this menu item       In the entire  Modbus  menu  only the menu item  Init Status  is displayed during an initialisation    run  The control device cannot be operated during this time        6 1 23 Manual initialization  gt  gt  gt  Modbus  gt  Configuration  gt  Initialization    Initialization       NO    Possible values     NO   No manual initialisation       YES   Trigger manual initialisation    Changing the value to  YES  triggers a manual initialisation     The search for fans takes place in the configured initialisation range  see 6 1 2 1   Only the fans found during this operation  are displayed after the initialisation run     After the initialisation process is finished  the value is reset to  NO  automatically     Page 62 of 92    Operating instructions     EC controller ebm Dd pst    6 1 3 Direction of rotation 22   Modbus  gt  Configuration  gt  Rot direction source   Preferred direction    Rot direction source Preferred direction    Di clockwise       The direction of rotation of the fans is configured using the parameters  Rot di
57. ler output of 100   the duty cycle quoted at output A1 for  Max  speed  is issued    Between these points  the response characteristics are linear  i e the value range for the duty cycle    Min  speed      Max  speed  are assigned to the value range of the controller output  0 to 100       A duty cycle of 0  corresponds to a voltage of OV at output A1   A duty cycle of 100  corresponds to a voltage of 10V at output A1     This relationship is depicted by the following graphic     Modulation  level  96     Max   speed    Min   speed       Controller  output        0  100     With these parameters  it is possible to set a restriction on the duty cycle  minimum or maximum level      Page 46 of 92    Operating instructions     EC controller ebm papst    5 2 4 2 Remote enable  gt    Settings  gt  Fan level A1  gt  Remote enable    Remote enable    OFF       With this parameter  a digital input can be selected which releases and or blocks output A1 on the control device   If output A1 was blocked  a voltage of OV is then issued permanently at this output     Possible values       always  Output A1 released     Digital input 1   open  output A1 blocked  70V   Digital input 1   GND  output A1 released     Digital input 2   open  output A1 blocked  70V     Digital input 2   GND  output A1 released     Digital input 3   open  output A1 blocked  70V   Digital input 3   GND  output A1 released     Digital input 4   open  output A1 blocked  70V   Digital input 4   GND  output A1 released 
58. lt input OR     Sensors    Type   Pressure sensor 0  500Pa   gt  0  10V   Connection   Input 0  10V  1   terminal strip 3  terminals 9   10    Type   Temperature sensor KTY 10 6  R25   2k0   Connection   Input for temperature sensor 2  terminal strip 3  terminals 3   4     Setpoint adjustment dependent upon ambient temperature   The factory configured setpoint of 250Pa is adjusted in accordance with the ambient temperature in the following manner   Setpoint  Pa        P Nee EE OE N EE OR AE AR    70     15 15 T    C    For T  gt  15  C   Setpoint   250Pa   For  15  C  lt  T  lt  15  C   Setpoint of basic function is altered in linear fashion within range  70Pa   250Pa   For T  lt   15  C   Setpoint   70Pa    Control     Control is identical to 7 2 1 Pressure control of ventilation systems   Operating method  refer to this Chapter     Modifications   a  Change in control parameters    If the control system starts to oscillate with the standard values  the control parameters should  be reduced  The setpoint is then reached more slowly and the feedback control function is more  stable     If the control system does not modulate the value fast enough  then the control parameters should be  increased    The setpoint is reached faster  However  in this case  there is a higher probability of unstable  behaviour occurring        The optimum setting is always dependent on the control path  user system      Page 81 of 92    Operating instructions     EC controller ebm papst    b  Chang
59. n    100  Control deviation                     Max     Min   P Factor    Following a change in measuring range  Max  Min   the    control range remains unchanged  The P   Factor changes accordingly        5 2 3 3     Factor 23   Settings  gt  Control  gt      Factor    I   Factor    0 0        The     Factor determines the integral share  share of totals of all deviations  for the Pl controller     The     Factor is standardised on the measuring range of the selected sensor  E1 Min   E1 Max  or    E2 Min   E2 Max   and the P   Factor  The  Actual value source  parameter decides which of these two sensors  E1 or E2  is  used for this purpose    With an     Factor and a P   Factor of 100  and a control deviation of  Max   Min   a value of 100  is obtained for changes  to the l share    General     Alshare   I Factor L Factor Control deviation    100  Max     Min    For the     Factor   0   the   share is always   0   This then involves a proportional controller   P controller      5 2 3 4 Control behaviour    The following equations enable the control behaviour of the control device to be demonstrated   The controller output comprises a P share and an l share     Controller output   P share  1 share    The controller output always has a value range of 0 to 100    The controller output must not be confused with the duty cycle  see 5 2 4 1    The controller output at time T   n   Ta is then    Controller output n     Pshare n   Y A I share i     i 0    Page 42 of 92    Operating
60. ng of this parameter  the value from  Actual value E1  or  Actual value E2  is copied to the  Actual  value      This actual value then forms the actual value for the controller   The displayed value is the same as the one on the standard display     4 2 2  Setpoints 23   Information  gt  Setpoints    Setpoint 20 090    Setpointl 20 09     Setpoint2 25 0       Setpoint 1     Here  the setpoint configured in this menu sequence is displayed  Settings  gt  Setpoints  gt  Basic function  gt  Setpoint 1     Setpoint 2     Here  the setpoint configured in this menu sequence is displayed  Settings  gt  Setpoints  gt  Basic function  gt  Setpoint 2   If the switchover to the 2nd setpoint has been disabled  Settings  gt  Setpoints  gt  Basic function  gt  Switchover between  setpoints 1 2   no value       is displayed here     Setpoint     Here the setpoint for the control device is displayed    In the basic function  this corresponds to Setpoint 1 or to Setpoint 2   Selection is made through parameter Settings  gt  Setpoints  gt  Basic function  gt  Switchover between setpoints 1 2 and the  status of the digital input selected here     For details  refer to 5 2 2 1      In the extended function  the parameters Settings  gt  Setpoints  gt  Setpoint reduction depending on E2 are also incorporated in    the calculation of the setpoint   In this case  the setpoint can differ from Setpoint 1 and Setpoint 2  for details  refer to 5 2 2 2     Page 18 of 92    Operating instructions     EC c
61. nstallation of the control device is possible by selecting preprogrammed operating modes  for additional information   refer to 7      When selecting an application in the Operating mode 1 menu  the  Settings  and  Alarm functions  menus are configured  automatically  i e  all values of these menus are overwritten with the default values     When selecting an application in the Operating mode 2 menu  the  Modbus  menu is configured automatically  i e  all values  of this menu are overwritten with the default values     The factory pre settings for each operating mode are based on experiential figures compiled over many years and suitable  for many different applications  In exceptional cases  these can be adapted individually by changing the numbers manually in  the  Settings  and  Alarm functions  or  Modbus  menus     If  in the Operating mode 1 or   Operating mode 2 menu  an input is confirmed Change mode    with OK  another confirmation prompt appears All values will be  before the value is taken over  overwritten  NO    If the value is changed from  NO  to  YES  during the security check and is confirmed with the  OK key  all parameters containing the standard value for this operating mode are overwritten     By cancelling with the ESC key or by entering  NO   it is still possible to cancel changes to the  operating mode at this point        Page 24 of 92    Operating instructions     EC controller    5 1 1 Operating mode I  gt  gt  gt  Operating mode  gt  Operating mode
62. ntact closed  Relay K2    The status of relay K2 is displayed    Possible values    Opened   Relay dropped  contact opened  Closed   Relay raised  contact closed    4 2 6 Operating hours counter    Operating hours       4 2 7 Software Version    46746V02  25 03 09    Software     Date              Information  gt  Operating hours counter    The number of full hours is displayed during which the control device was  switched on    Only full hours are counted  If the control device is switched off  any incomplete  hours are discounted      gt  gt  Information  gt  Software version    Displays the software version with which the control device is running   The second line contains the relevant release date for this software date     Page 20 of 92    Operating instructions     EC controller ebm Dd pst    4 3 Alarm indication menu    In the Alarm indication menu  there is no input option  i e  the OK key  for input  is disabled  The Alarm indication alternates  in menu item  Standard display  with the standard display if an alarm is present and has been released to the display   see 4 1           OK          Alarm indication Sensor E1  See 4 3 1  OK  AA  Sensor E2  See 4 3 1  OK  y TA  External device  See 4 3 2  See 4 3 3    The  Fan  menu item is displayed for each fan found in the initialisation via Modbus  see 6 1 2    The number of menu items depends on the number of fans found  i e  up to 32   For    differentiation  the specific fan address is specified  If no fan has been f
63. ols the actual value to the new setting   b  Change to control parameters    If the control system starts to oscillate with the standard values  the control parameters should be reduced  The setpoint is  then reached more slowly and the feedback control function is more stable     If the control system does not modulate the value fast enough  then the control parameters should be increased   The setpoint is reached faster  However  in this case  there is a higher probability of unstable behaviour occurring     The optimum setting is always dependent on the control path  user system      Page 79 of 92    Operating instructions     EC controller    7 2 2 Pressure control  ambient temperature compensated    Application     Pressure control for ventilation systems in HVAC technology   The setpoint is altered proportionally to the ambient temperature     Parameters     Operating mode                   P02      Sensor type E1     _      Pressure sensor 0  500Pa           5 o    Signal form E1 0 10V ME S S  Unit E1 Pa    Decimal places E1   N  Measuring range Ef min           000 N  Measuring range Ef mx           00     SensorcomparisoncheckE1              0        Sensor type E2 Temperature sensor  KTY 10 6      oignal form E2   PTC      LIO  E M                  Unit E2  Decimal places E2    Measuring range E2 min               300     1          MeasuingrangeE2mx     J 1 700            j   Sensor comparison cheek               09                               Setpoint           
64. ontroller ebm papst    4 2 3 Controller data 22  Information  gt  Controller data    Duty cycle 1 0     Control function  cooling       Duty Cycle A1     Here the duty cycle at output A1 is displayed     0  indicates an output voltage of OV  100  indicates an output voltage of 10V    The displayed value is the same as the one on the standard display     Control function     This is where the currently used control function is displayed  This is dependent on the following parameters     e Settings  gt  Control  gt  Control funct source    e for internal  Settings  gt  Control  gt  Control function  e otherwise  Status at selected digital input       Possible values     Heating  Control function positive  i e  control deviation   Setpoint   Actual value  Cooling  Control function negative  i e  control deviation   Actual value   Setpoint       4 2 4 Digital inputs 22   Information  gt  Digital inputs    Digital inputs  D1 high D2 low  D3 low D4 high       The status of digital inputs D1  D2  D3 and D4 is displayed     Possible values     Low   Digital input is bridged to GND  i e  contact at input is closed    High       Digital input is open  i e  contact at input is open       Page 19 of 92    Operating instructions     EC controller    4 2 5 Relay    Closed  Closed    Relay K1    Relay K2       Relay K1     The status of relay K1 is displayed     Possible values     ebmpapst    D gt  Information  gt  Relays    Opened   Relay dropped  contact opened  Closed   Relay raised  co
65. ound  this menu item is  omitted   For the sake of simplicity  only one menu item is displayed here        Page 21 of 92    Operating instructions     EC controller ebm Dd pst    4 3   Sensors 22   Alarm indication  gt  Sensor E1  Sensor El Sensor E2  OK OK  Sensors     The status of the sensor at Input E1 or at Input E2 and any possible errors occurring on the sensor are displayed     Possible values     OK  No error  Cable break  sensor is not connected  Short circuit  Short circuit on sensor    Errors can be recorded for signal forms  PTC    NTC  and  4  20mA  only   With other signal forms  the full range of values is valid     With actual values smaller than the minimum value to be recorded by the sensor  this display  appears   Short circuit     With actual values larger than the maximum value to be recorded by the sensor  this display  appears        Cable break     4 3 2 External device 22   Alarm indication  gt  External device    External device    OK       The status is displayed for the external device whose fault output is connected to the selected digital input on the control  device    The digital input is selected via menu Alarm functions  gt  External fault  gt  Input    For details  refer to 5 3 3      Possible values     OK   No fault on the external device  Fault   Fault on the external device    Page 22 of 92    Operating instructions     EC controller ebm Dd pst    4 33 Fan 22   Alarm indication  gt  Fan    The status is displayed for each fan found in t
66. own 2   Settings  gt  Fan level A1  gt  Minimum air shutdown          Minimum alr Shutdown with Hysteresis  shutdown control deviation  ON  3 0K 1 0K    The  Minimum air shutdown  function is used primarily when using the device as a pure P controller     Activation   This function is enabled by the  Minimum air shutdown  parameter     Possible values     e OFF   Function disabled  e ON   Function enabled  Function     If the control deviation drops below the value set in the  Shutdown with control deviation  parameter  a voltage of OV is  issued at output A1  This shuts down the connected fan  The fan is not switched back on again until the control deviation  exceeds the value for  Shutdown with control deviation     Hysteresis      Page 51 of 92    Operating instructions     EC controller ebm papst    Example     This function should be made clearer in the following example     The relevant parameters have the following values     Minimum air shutdown   ON  Shutdown with control deviation    9 0K  Hysteresis   1 0K  Setpoint 1   20 0  C  Control range   10K  Control function   Cooling  Min  speed   25   Max  speed   100   Duty Cycle  Al  T00  ls Nod PA RA                       ZADRA em    9606  lo     LA                              e  gt  Actual value  1 0K     10 0K     Hysteresis   4                     control range     3 0K   Shutdown at  control  E deviation l  17  C 20  C 30  C  Setpoint    The duty cycle is changed in linear fashion for an actual value in the range 
67. r usage  we ask you to read these operating instructions carefully before installation and  commissioning of the control device     Dissemination and reproduction of these operating instructions  commercial use and communication of its contents are  prohibited unless specifically authorised  All infringements will lead to demands for compensation  All rights associated with  the granting of patents or trademark entry are reserved     O ebm papst Mulfingen GmbH  amp  Co  KG    We reserve the right to make changes to the contents of this documentation in the light of technical progress and its impact  on our products    All rights reserved  This documentation has been produced and checked carefully  ebm papst Mulfingen will not accept any  liability for any errors it may contain     This operating manual only refers to the control device described in this documentation and    does not apply to any associated equipment   devices        1 2 Safety instructions    Attention     Only specialist personnel with specialist knowledge of electrical engineering are authorised  to work on electrical components   assemblies     Attention     Before opening up the device  first isolate it from its power supply     Danger from electrical current or voltage       All connections must be plugged while electrical power is switched off       Always ensure that no one is able to come into contact with electrically live components while  the equipment is in operation          The device can only b
68. rce the control function is established from   With  Internal   the value set for the  Control function    parameter is adopted   If a digital input is selected  the status of that digital input determines the control function     Possible values     Internal    Control function    Control function  parameter  D1   Digital input 1   open  Control function   Heating    Digital input 1   GND  Control function   Cooling    D2   Digital input 2   open  Control function   Heating    Digital input 2   GND  Control function   Cooling    D3   Digital input 3   open  Control function   Heating    Digital input 3   GND  Control function   Cooling    D4   Digital input 4   open  Control function   Heating    Digital input 4   GND  Control function   Cooling         b   Control function  internal     Control  function    cooling       Here the operating direction of the controller can be set provided that the  Control funct source  parameter is set to  Internal      Possible values        Heating        Cooling        Heating  Control function positive i e  control deviation   setpoint   actual value      Cooling  Control function negative i e  control deviation   actual value   setpoint    Page 40 of 92    Operating instructions     EC controller ebm papst    5 2 3 2  Control range and P   Factor 2   gt  Settings  gt  Control  gt  Control range   P   Factor    Control range P   Factor    5 0K 2000        Control range and P   Factor are different ways of depicting the same value   Both 
69. rd has not been entered     In factory condition  Authorisation level 2 is the default  This allows write authorisation for almost all parameters     Each authorisation level is assigned a password  The passwords themselves do not form part of this document  These must  be requested separately from ebm papst    After entering the correct password for an authorisation level  you also obtain the write authorisation for the corresponding  authorisation level  However  this does not change the  Authorisation level  parameter     The additional authorisation via the password input is taken back as soon as a password is entered without authorisation   e g  1000      If no key is pressed on the control device for a 4 minute period  the additional authorisation obtained  by the password is withdrawn automatically   If necessary  re enter the password then     Once the menu item password has been selected  the value  1000  always appears  even if a  different password has been set  This ensures that unauthorised users are unable to query the  correct password from this menu item        To be able to modify the  Authorisation level  parameter  the password for at least the configured authorisation level must be  entered  The  Authorisation level  parameter can then be set no higher than that for which the password is valid     Example   Authorisation level 2 is configured    Enter the password for authorisation level 1     Authorisation level cannot be modified  Enter the password for 
70. rection source  and  Preferred direction        Possible values for  Preferred direction    E counter clockwise   e clockwise   Possible values for  Rot direction source      OFF   Fans rotate in the direction programmed in the fan  no direction specified by control device  Preferred    Fans rotate in preferred direction  D1   Digital input D1   open   Fans rotate in preferred direction  Digital input D1   GND   Fans rotate opposite to the preferred direction  D2   Digital input D2 7 open   Fans rotate in preferred direction  Digital input D2   GND   Fans rotate opposite to the preferred direction  D3   Digital input D3 7 open   Fans rotate in preferred direction  Digital input D3   GND   Fans rotate opposite to the preferred direction  D4   Digital input D4   open   Fans rotate in preferred direction  Digital input D4   GND   Fans rotate opposite to the preferred direction    If the specified direction of rotation changes  by changing one of these parameters or by a status  change at a digital input   the duty cycle is first set to 0  for 30 seconds to give the fans time   to stop    Then  the direction of rotation of the fans is changed and they are restarted     Modifying the parameter  Rot direction source  requires authorisation level 3     For some applications  it is helpful when during operation opposite the preferred direction  a fixed  duty cycle is always specified by the control device   The prerequisite for this is that the direction of rotation is switched via a
71. s       Z3 enje   enjoy  c3 enjeA jeny    jutodpue jurodjes  uononpai jurodjas  1e puy uononpa  jurodjas    e ues vononpa  jurodjas    uononpey     Judas              uodes      lurodjaS    xQ       Z     yulodyas  JOAOUDIIMS    19  0 9U09   sjurod3jos UNIE T R    SIO OW 23 JO  80IA8p  oJ uoo     enuew BuneJedo    26 10 06 3fed    op    Anq  J9JSUeJ             I HO   UO    siseJejs  u VINE  1   paads peedg   i HIP 104 U09 YIN i UW l juBiu Xen   I I   I   uoneep o4uo            ind  eunsseid  I I 0 I p UIN     ulu   y  enssi uau   uos    NO i     SWI  dn MOJJOJ  lt    i jndino J9  0J UO 2     i 1   104 440  NO Peeds  fo Ang  I l 0  ejo  o   mp 1911489 y oje no eo   I I    uone uo uny 9p  Ain       do     xQ    UONeyuI  UO UNY PAS Ana   I     lo vopenwi     nuew UMOPINUS i   UIN       Jie    ull   i euin dn MOJ O y             x     UMOPINYS    IE WINUWIUIN i   uonejui  JUBIN   E 2   c                                                      a                                              D 2         Hed    AI Ajynp SUDEJNOJED cg    jsded Lida SJOJOW 23 JO  80IA8p  0J1uoo   jenueu DuneadO    26 10 16 abed                  epow   ENUEJN  I  i p    ds   indu   i  EUIS U    pow  enuelN YvWOc 7 LA  gt  VUIOG P 0  VUIOZ 0 LH       indu   vwo  13 vwo0c r 0  julodjoS vw0c 0 13  8 O  ENUEJ   ue  Jeujo z indu   i AOL 0 dd   AOL 0  vO     Je  OI JUOD     UONelNDON 440   indu   o on    i i  5 85 0013 A01 0  ac 2    uonounJ i  SNAPON 10 98 1p JUlodjas 80JNOS  apou  ENUEJN  Ly ndino C      ma  
72. s      A   Modifying the data of a Holding Register requires authorisation level 3     changed only if the required password value has been entered previously in the  Password     Holding Registers for which the Modbus authorisation  Customer  or  ebm papst  is necessary can be  A  D002   D004  Holding Register  Otherwise  write access is denied        6 2 4 Input Register 2  Modbus  gt  Plant  gt  Fan  gt  Input Register    Fan 1  Fan 1 Input Register    Input Register address D000  Data 0002    Fan 1  Input Register  address DFFF  Data         In the  Input Register  menu item  the values of all Input Registers of a fan can be displayed and modified in a range  between D000 and DFFF  This is the address range in which all Input Registers of ebm papst fans typically lie  All values are  displayed in hexadecimal format     Because the control device displays only very few Input Registers of a fan in plain text  this menu provides an opportunity to  check the configuration of the fan and change it if necessary     The Input Register area contains a total of 4096 sub menus  one for each Input Register address between D000 and DFFF    To enable quick toggling between the individual menu items  the address of the individual menu items can be changed  quickly by holding the Y or A button  similar to the fast mode function when editing data      For the function of the Input Registers  refer to the  Modbus parameter specification for eom standard series      Page 72 of 92    Operat
73. t D2   open   Control to configured setpoint    Digital input D2   GND   Manual speed setting     Digital input D3   open   Control to configured setpoint  Digital input D3   GND   Manual speed setting     Digital input D4   open   Control to configured setpoint  Digital input D4   GND   Manual speed setting       If the  Manual mode  function is disabled  OFF   the signal at output A1 is always modulated to the configured setpoint   When manual mode is enabled  ON   the signal selected via manual mode source is output  see 5 2 5 2   In addition  by  selecting a digital input  you have the option to activate manual mode using an external switch     Page 48 of 92    Operating instructions     EC controller ebm papst    5 2 5 2 Manual mode source  gt    gt  Settings  gt  Manual mode  gt  Manual mode source    Manual mode    Source  Internal       Possible values   Internal   Duty cycle is determined by the  Manual mode speed  parameter  E10 10V   Duty cycle is determined by the signal at 0  10V input 1  E20 10V   Duty cycle is determined by the signal at 0  10V input 2    E10 20mA   Duty cycle is determined by signal at 0  20mA input 1  E2 0 20mA   Duty cycle is determined by signal at 0   20mA input 2  E14 20mA   Duty cycle is determined by signal at 4  20mA input 1  E24 20mA   Duty cycle is determined by signal at 4  20mA input 2       This parameter is effective only if the  Manual mode  function is activated  see 5 2 5 1     For  Manual mode source     Internal   the value 
74. that appears in the  Manual mode speed  parameter is output  see 5 2 5 3    For all other values  the duty cycle is calculated from the signal of the selected input and the parameters  Minimum speed   and  Maximum speed   see 5 2 4 1      The control range of the specific input is mapped in linear form to the range defined by the parameters  Minimum speed  and   Maximum speed      E10 10V Dutycycle   V    nMax     nMin    nMin  E2 0 10V Duty cycle   P    nMax     nMin    nMin  E1 0 20mA Duty cycle   Hayy   nMax     nMin    nMin  20mA  E2 0 20mA Duty cycle   A       nMax     nMin    nMin  20mA  E1 4 20mA Duty cycle   ATA    nMax     nMin    nMin  16mA  El 4 20mA Duty cycle   O    nMax     nMin    nMin  16mA  MINA ie cortes Minimum speed NMAX AAA Maximum speed  HET  rod Voltage at 0 10V input 1 U E   AA Voltage at 0 10V input 2   RE Current at 0 4 20mA input 1 NE   AAA Current at 0 4 20mA input 2    Page 49 of 92    ebmpapst    Operating instructions     EC controller    The following illustration shows the relationships in graphic form        Modulation  level      Max   speed  Min   speed  OV 6 ae  0 mA 20mA ALI  4mA 20mA    X gt  Settings  gt  Manual mode  gt  Manual mode speed    5 2 5 3 Manual mode speed    Manual mode    speed  0        This parameter defines the duty cycle that is output when manual mode is switched on  see 5 2 5 1  and  Manual mode  source    internal  see 5 2 5 2      A duty cycle of 0  corresponds to a voltage of OV at output A1   A duty cycle of 1009
75. the sensor  it appears alternately on screen beside the standard display     Page 55 of 92    Operating instructions     EC controller ebm Dd pst    5 3 3 External fault input menu 22  Alarm functions  gt  External fault  gt  Input    External fault External fault    Input  OFF       Here  you can select a digital input at which the fault output of an external device is connected     If no external device is connected to the control device  select the  OFF  setting here  In this case  the value  OK  is always  displayed on the Alarm indication  gt  Motor menu     If a digital input was selected  an error is signalled in the Alarm indication  gt  Motor menu whenever the fault output of the  external device connected to it connected to it is opened  7 high impedance   In this case  the digital input on the control  device is open     The error is displayed simultaneously and alternately together with the standard display   This display cannot be switched off using an additional menu item  If no error is displayed  the function needs to be disabled  using the  OFF  setting     Possible values       no fault output of an external device connected     Fault output of external device connected to digital input 1    Fault output of external device connected to digital input 2    Fault output of external device connected to digital input 3    Fault output of external device connected to digital input 4    This function can be used to evaluate the fault relay of an ebm papst motor    
76. tion between the control device and fan is interrupted    Faults on the bus line    The fan power supply is interrupted    When the fan address is changed  A fan with the desired address already exists in the  network        92  Modbus  gt  Plant  gt  Fan  gt  Settings  gt  Fan address       You can change the Modbus address of the fan here     After a fan address is changed  the fan can no longer be reached at its old address  Therefore  no  more values can be displayed in any of the fan s menu items  Instead of the values  a question  mark     appears     An initialisation run is required to display the fan  see 6 1 2   After the initialisation run  the fan  appears under its new address in the  Plant  menu        Page 69 of 92    Operating instructions     EC controller ebm Dd pst    Only fan addresses that do not already exist in the network may be selected   A    If  despite this  you select an address that is already assigned in the network  the  Write access    error  message is displayed  The fan address is not changed        Procedure for setting up a plant        All ebm papst fans are delivered from the factory with the fan address 1  Therefore  when connecting multiple fans to a  control device  the fan address must be reassigned for each fan     We recommend following this procedure   e Connect one fan to the network and switch it on   e Start the initialisation run on the control device  In the Plant menu  a fan appears with the address  1    e Change the fan ad
77. uction J   OFF                         See EL o  Setpointreduet End J MB     Setpoint atendpoint      700     Control functsource                          Intemal                   Follow up time EE o   Mi sped PH       Page 73 of 92    Operating instructions     EC controller    Customer setting 2  100  IS    Remote enable OE ol    Boost mode  Manual mode activation OFF      Manual mode source   Internal      Man  mode Duty Cycle    Night limitation activation            OFF                    O  Max  night duty cycle            1006    Minimum air shutdown _              OFF                     O  Shutdown control deviation       00 N          Hysteresis O  Function K1               Alfalis       Cs  Active state K4                1  opened         TOO o E    Do   out delay K1 0s    EN EN  Function K2     OOflstlic           Active state K2 opened N  SELA N EN EE  Drop outdelayK2___________ _0s    Screen display sensor fault   OFF        External faultinput d CF       Sensor     Type   Temperature sensor KTY 10 6  R25   2k0       ebmpapst       Connection       Input temperature sensor 1  terminal strip 3  terminal 1   2     Control     If the parameters are not changed  the following control behaviour results  P   controller    Duty Cycle  Al    100     0          Actual value  5K      20  C Control range 25  C    Setpoint    Page 74 of 92    Operating instructions     EC controller    Frequent modifications     a  Change in setpoint     Duty Cycle  A     100     0        
78. utput 1   Terminal strip 3  terminals 7 12  output 2     Type of signal  24V   20   Max  output current  120mA       2 6 Bus connection    The control device has a bus connection for communication with ebm papst motors  Each of the two connections  RSB and RSA  are connected internally    Terminal designation  Terminal strip 3  terminals 25 27  RSB   26 28  RSA        Type of signal  RS485  MODBUS RTU    Page 9 of 92    Operating instructions     EC controller ebm papst    3 Operation    3 1 Controls    3 1 1 Display  For display purposes and to change values  the control device has a screen display   Type  LCD display    STN blue mode  negative screen display       Size  4 lines  each of 20 characters    The display is menu driven  The various menus and their arrangement are described in  Chapter 3 2 Menu guide   The display switches to standby mode after 4 minutes  Press any key to reactivate it        3 1 2 Input keys  The control device has 4 input keys for selecting the various display menu item and to alter values        Lower      Higher         Exit      Accept        3 1 3 Function of the input keys  These various menus are structured into several levels  A distinction is made between    e  Headings    these menus have sub menu items and no values are displayed      Values    these are located on the lowest level of the menu  values can be displayed and edited here    To change between these individual menu items and to edit values  the 4 input keys are used  see 3 1
79. value    Duty cycle 1  Vy T   OK    Information see 4 2  Information menu       see 4 3  Alarm indication menu    see 5 1  Operating mode menu    see 5 2  Settings menu    see 5 3  Alarm functions menu       Modbus OK    yy See 6  Modbus menu    Vy DA    System OK    see 5 4  System menu    Page 15 of 92    Operating instructions     EC controller    4 Displaying values    ebmpapst    The first 3 menu items of the main menu   Standard display    Information    Alarm indication   are used to display the    following   e Input and output signals on the control device  e Important values for the control  taken from  Settings  menu   e Fault signals    There is no input option in these menus    4 1 Standard display    Act value 24 0  C    Duty cycle A1       Actual value E1    Here the value is displayed which the sensor provides from the selected input   The input is selected via the menus Settings  gt  Control  gt  Actual value source and  Settings  gt  Inputs  gt  Input E1 2  gt  Signal form E1 2    For details  refer to 5 2 3 5  5 2 1 2      Duty Cycle A1   Here the duty cycle at output A1 is displayed     0  indicates an output voltage of OV  10096 indicates an output voltage of 10V    If the control device detects a fault  this is displayed in alternation with the standard display     The fault display corresponds to the form shown in the  Alarm indication  menu  see 4 3         Page 16 of 92    Operating instructions     EC controller    4 2 Information Menu    Information
80. values determine the P share  share of absolute deviation  of the PI controller   If one of these values changes  the other value also changes automatically     Control range     The presentation via this control range is intended for use as a P controller  i e  the     Factor is set to 0    The control range then indicates the control deviation figure for which the controller output changes from 0 to 100    This relationship is depicted by the following diagram        Controller  Output  100   0   0 Control range Control  deviation  P   Factor     If an     Factor is set  gt  0   the control range cannot be depicted meaningfully in a diagram  For this case  the screen display  of P   Factor is provided     The P   Factor is standardised to the measuring range of the sensor  E1 Min   E1 Max  or  E2 Min   E2 Max   The  Actual  value source  parameter decides which of these two sensors  E1 or E2  is used for this purpose     With a P   Factor of 100  and a control deviations of  Max   Min   the resultant P share is a value of 100    General     Control deviation    P share   P Factor    Max     Min  Max              Sensor measuring range maximum value  E1 Max or E2 Max   Min               Sensor measuring range minimum value  E1 Min or E2 Min     Page 41 of 92    Operating instructions     EC controller ebm Dd pst    The display as P   Factor and as Control range can be converted in either direction using the following equations     P Factor   A  Max     Min   Control deviatio
81. viation at  Min  speed   The system only shuts down for  Min  speed    0        Page 52 of 92    Operating instructions     EC controller ebm Dd pst    5 3 Alarm functions menu    Alarm functions see 5 3 1    Relay menu    see 5 3 2  Display menu    External fault see 5 3 3    External fault menu       53 1 Relay menu       Alarm functions  gt  Relays    OK  ESC    ESC  Ko Ig  A    Function K1 Function K2    See 5 3 1 1  All faults OLE   static         Active State K1 Active State K2    I See 5 3 1 2  opened opened  Pick up delay K1 i Pick up delay K2    P d   See 5 3 1 3  i Drop out delay K1 i Drop out delay K2 See 5 3 13            Os Os    The menu items for relays K1 and K2 are identical in terms of layout  Here  by way of example  is a description of the menu  items from relay K1  For the menu items of relay K2  the following applies     Page 53 of 92    Operating instructions     EC controller ebm papst    5 3 1 1 Functions  3   Alarm functions  gt  Relays   Relay K  gt  Function    Function K1    All faults       Various functions can be assigned to these relays   Every function has an enabled or  active  status and a disabled or  inactive  status   A switching status for the relay contact is assigned to each of these statuses in the  Active state  menu item  see 5 3 1 2      The following table shows the conditions for inactive and active state for each of the functions that can be set     Off   static always satisfied never satisfied   Sensor fault both sensors  on E
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
mantenimiento por parte del usuario diese anleitung  I. Purpose The purpose of this Appendix is to provide a summary of  Disfraces por pocos pesos  MAGLEV: Magnetic Levitation Plant User Manual  Origin Storage AC Adapter ( PA-17 )    MATERIEL NECESSAIRE : Kit GPI-C 4 cylindres Fichier  Bedienungsanleitung Klapprad    LG 55UB820T 55 Inch 139cm 4K Ultra HD    Copyright © All rights reserved. 
   Failed to retrieve file