        Mitec RMS40 installation manual
         Contents
1.   Two of these can be used for  connecting communications and power     DESIGN Mitec RMS    No  of channels Power supply Galv  Isolation   Short   80 230 V 12V Cust   distance AC DC spec  This table shows the standard range of Mitec measuring stations  Different configurations are available   and the type of measuring sensors can always be freely selected                  mitec RMS40 21    Model program measu ri ng stations Mitec RMS40 and RMS31 measuring station    Power supply    Mitec RMS is powered by 230V 50 Hz or 110V 60 Hz  Power  consumption is approx  SW     Power is connected to the DIN rail mounted plinth  The system is  equipped with fuses and transient protection between phase and neutral   There is no main circuit breaker but the power can be cut by removing  the fuse holder     The instrument in Mitec RMS is equipped with a battery for backup of  the measuring system and data memory  If external power is cut   measuring will continue and measuring data will be saved in the  instrument   s memory     Communication will stop however  because the modem requires  external power  Measuring data will still be stored during the power cut  and the break will not be evident when power is reconnected  provided  that the external sensors have had continual power supply     The battery has sufficient capacity to operate for up to one month   gt  1  minute registration intervals and room temperature      Note that battery capacity is significantly reduced at lower temperatu
2.  3V with 4 mA and 4V with 20mA     Current is normally regulated by the loop   s transmitter  but a break in  the isolation amplifier   s secondary side can cause a voltage increase  that damages the amplifier  Power over 24V is therefore not recom   mended unless the input is protected with a Zener diode of 10 12V     10 mitec RMS40    Mitec RMS40 and RMS31 measuring station    Power supply  Mains power is connected to the separate terminal blocks   Protective earth is connected to the yellow green terminal block     NOTE  Ensure that power supply is disconnected during installation     Terminal block for  connecting protective earth Fey Fel Terminal black for    power supply       mitec RMS40       Installation    11    Insta llation Mitec RMS40 and RMS31 measuring station    GSM modem    Measuring stations are delivered with GSM modem and antenna  installed     Normally 1t is delivered with a subscription  SIM card  installed in the  modem     Mitec RMS with GSM modem and inbuilt antenna    Signal strength and antennas   The antenna is installed on the top of the measuring station with a  screw connector of type    TNC       Available as an accessory is a magnetic foot antenna with fiberglass rod  and 3 m cable with TNC connector  This has high amplification and is  recommended for places with difficult reception conditions     Check that there is GSM coverage at the location  A normal mobile  phone gives a good indication of signal strength  Consider that moving The stand
3.  All installation is to be performed by qualified personnel with  appropriate knowledge and training  This should be observed in  particular during installation of 110   230 V power supply     NOTE  Mains supply must be disconnected during all  installation work     The following is a general description of the installation for all Mitec  RMS models     Standard measuring station RMS40 with antenna     mitec RMS40    Insta llation Mitec RMS40 and RMS31 measuring station    Mechanical installation  The enclosure is equipped with four mounting lugs     Select a place where the equipment is not exposed to mechanical  factors or at risk of being affected by water or chemicals     Avoid places where vibration occurs     The recommended ambient temperature is 10   30  C  Operation can not  be guaranteed above 50  C or less than  15  C     Condensation must not occur     Wall mounting requires a free surface of approx  25 x 40 cm  w x h      With door open  a free width of approx  65 cm is required  The box  extends approx  20 cm from the wall        approx  50 cm                approx  65 cm    8 mitec RMS40    Mitec RMS40 and RMS31 measuring station Insta llation    Hole diameter  8 0       Layout for wall mounting of RMS40    mitec RMS40 9    Insta llation Mitec RMS40 and RMS31 measuring station    Connection of measuring sensors    Many different measuring sensors can be connected directly to Each measuring station is  RMS31 40  Connect sensors to the screw or clamp connection i
4.  alkaline battery type LR6   indicates if the battery is in poor condition     Refer to the operation description above regarding battery power  supply     General information on settings    It is normally not necessary to perform any settings on site to start the  measuring station  This is carried out from the measuring server or via  Mitec   s measuring service     After power supply is switched on  the modem is initialised  automatically and the measuring station can be setup remotely from the    measuring server    Be  8 The measuring station is    normally started from the  measuring server but can also  be started manually     Registration interval  measuring interval and clock are also set from the  measuring server and measurement started     mitec RMS40 13    Sta rtup Mitec RMS40 and RMS31 measuring station    Manual settings  not normally needed     It is not normally necessary to adjust any settings before starting the Note  Normally measurement is  measuring station  this can be done from the measuring server or via started from the measuring  Mitec   s measuring service  server and no settings need to be    If desired  manual settings can be made following the description in this Made locally   chapter     1  Set the correct language    2  Set the clock  3  Check the start stop conditions  4  Set the registration interval    5  Initialise the modem    6  Start the measurement  Refer below for a step by step description of these settings     Remember  FUNC lights
5.  up the display   The instrument has two modes  Readings  F  and Settings  C      Go into Settings mode by simultaneously pressing the   and    buttons     Close Settings mode and go to Readings by simultaneously  pressing the   and   buttons     e Measuring must be stopped  F5  before settings can be adjusted     Display  The display has two rows with 16 characters   Buttons    FUNC switches between different functions  Fl to F5 are readings and  C1 to C13 are settings     ALT has sub alternatives for each function    SEL has sub alternatives for ALT      and   are used for settings    For full information read user manual for AT40   AT31        14 mitec RMS40    Mitec RMS40 and RMS31 measuring station    The following is a step by step description of the settings needed before  the system can start measurement  Refer AT40 and AT31 user manual     1   Set language C12    Following a battery exchange  the instrument   s language is set to  Swedish  The display can also show English  German and French   Change language using function C12    e Go to Settings    e Press FUNC repeatedly until C12 is shown in the display    e Press ALT to select language    e Return to Readings    2   Set dock C3    It is essential for correct measuring that the instrument   s clock is set  correctly  NOTE  always use winter time  not daylight saving time         e Goto Settings   e Press FUNC repeatedly until C3 is shown in the display  e Press ALT to enter the function    e Set the year using   
6. Measuring station RMS31 40    Installation manual    Measuring station RMS31 40    Installation manual    Mitec products are designed and manufactured by  Mitec Instrument AB i S  ffle    Copywrite for products  software and documentation  belongs exclusively to Mitec Elektronik AB    1992   2000   All rights to technical modifications are reserved   Document No  J10001 Rev  E    Mitec Instrument AB  V a Storgatan 18 661 30 S  ffle  0533 16050    www mitec se    Contents    eneral    pul   gt   u  a  E      Ss    lt   mie      5  na  Olaf    onnection of measuring sensors    a  o    urrent loop    Power suppl    mi  Ni    Signal strength and antennas    SM modem         N    eneral  urning on the power    J  py  pao          lt      rs                       m  wilo uju    eneral information on settings    P    anual settings  not normally needed     Set language C12     gt            nn      Set clock C3    Check start and stop conditions C4 and C5       Nn    E  p  Nn      Set registration interval C6  Initialise the modem C10  Start measuring F5       mm    Q  l  pad          j  N    esting    na  oo    heck sensors  heck communication             OO    CO    erify system function    eneral 20  odel program measuring stations 21  Main parts 21    nclosure       Ni    Power suppl    N  N    easuring and communication    N  N    easurin g sensors    Mitec RMS40 and RMS31 measuring station   nsta llation    Mitec RMS40 and RMS31  measuring station    Installation    General   
7. and   buttons    e Switch to Month using the SEL button and set using   and    buttons  Set the complete date and time using SEL and        e Return to Readings    3   Check start and stop conditions C4 and C5    For continuous measurement  the start condition should be Manual and  the stop condition be None     e Goto Settings   e Press FUNC repeatedly until C4 is shown in the display   e Check that the start condition is Manual  Change if needed  e Proceed to C5 using FUNC   e Check that the stop condition is None  Change if needed    e Return to Readings    4   Set registration interval C6  mitec RMS40    Startup    NOTE  This description of  settings refers to RMS40  Refer  to AT31 user manual for usage  in RMS31    15    Sta rtup Mitec RMS40 and RMS31 measuring station    The registration interval is the time between storage of measuring data  in the memory of the measuring interface  An interval between 1  second and 24 hours can be freely selected  The normal interval for  logistics and industrial service is between 1 minute and 1 hour  Select  the longest possible time to minimise the quantity of data    e Goto Settings   e Press FUNC repeatedly until C6 is shown in the display   e Press ALT    e Set the interval using the   and   buttons    e Return to Readings    5   Initialise the modem C10    The registration interal is the time between saving measuring data in the  measuring interface   s memory     e Goto Settings   e Press FUNC repeatedly until C10 is shown in 
8. ard antenna can be    the antenna very slightly can make a big difference  screwed off the cabinet and  Place the antenna high and free  and avoid placing it near electrical replaced with the extra   equipment that may cause interference  antenna   s cable connector     12 mitec RMS40    Mitec RMS40 and RMS31 measuring station Sta rtup    Startup    General    Mitec RMS is delivered from the factory with all equipment installed  and tested  Following installation the full system must however be  tested to verify the operation of measuring sensors and communication     Any external influencing factors should also be checked     Mitec RMS is based on Mitec   s measuring instruments AT40 or AT31   The function and operation of RMS is essentially the same as these  instruments  Refer to AT40 and AT31 user manuals     Tuming on the power    External power supply  Connect power supply to RMS     Different types of power supply units are used depending on the design  and some types are equipped with indicator lamps for power  Check  that this lights up     Check that indicator lamps in the modem are lit  If not  check that the  modem is switched on     Battery backup   The instrument in RMS is equipped with a battery for backup of the  measuring system and data memory  Check that the battery is installed  and that it has sufficient capacity     The easiest way is to turn off the external power supply and check that  the display lights up when the FUNC button is pressed  An alarm Use
9. hone     Ring the installation   s telephone number and check that it replies and  that a carrier signal can be heard     When a GSM telephone is installed its Data number is used for dialling   Refer to the documentation accompanying the subscription     Wavecom WMOD2 is installed as the standard modem in Mitec  measuring stations  It has a red LED indicator with the following  functions     e Slow blink  Contact with GSM network   e Fast blink  Contact with GSM network  communication active     e Steady light  The modem is switched on but there is no contact  with the GSM network     Additional checks can then be made using a PC and Mitec Monitor  software     Verify system function    The final verification of the system   s function is made from the  measuring server and Mitec Monitor program     The measuring system is configured and test dialled from the  measuring server     18 mitec RMS40    Mitec RMS40 and RMS31 measuring station Testi ng    Settings in measuring server Mitec Monitor under     Measurement  Configuration             RMS40 and RMS31 always select Family     31 40 series     For RMS40 select logger     AT40      For RMS31 select logger     AT31      Enter serial number  Indicated on the measuring station        Enter telephone number  Refer subscription information     mitec RMS40 19    G eneral Mitec RMS40 and RMS31 measuring station    General    Measuring stations in the RMS series are part of Mitec   s system for  GSM monitoring    RMS is a universa
10. l measuring and communications unit with all  functionality required for use with different measuring sensors and  communication methods    A number of different sensors for measuring pressure  temperature   flow  level  energy etc can be connected to RMS  Communication can  take place via GSM telephone  radio  private network or the public  telephone network    Measuring occurs automatically using a selectable time interval and  information packets are transferred on request to the system   s  measuring central     Mitec RMS is available in different designs     SMS alarm  and data    as  apgr    sr  Y  Sensors          533332 N    Wireless  Internet    E mail alarm       GSM measuing    stations i Internet    Measuring server It sensors    The Mitec measuring system    20 mitec RMS40    Mitec RMS40 and RMS31 measuring station Model program measu ri ng stations    Model program measuring stations    Main parts   Mitec RMS can be delivered in different designs depending on the  application  Refer table below  The main parts of Mitec RMS are   e Power pack   e GSM modem  normal modem as option    e Measuring and communication interface    e Terminal blocks  galvanic isolation optional     Endosure    Mitec RMS has a weatherproof enclosure class IP65 in metal and has a  door with simple lock arrangement     The box can be mounted using the four mounting plates with screw  holes     Ten conduit entries of type PC9 for cable diameter up to 8mm are  mounted on the standard product
11. n the delivered with an individual  box  One to eight sensors can be connected at the same time  Refer plinth description     markings on respective terminal blocks for polarisation     The connection can later be tested using the inbuilt display     Terminal block with  fuses for connecting  power supply    Terminal block or isolation     amplifier for connecting  sensors  Measuring channel 1    to the left   II 1 213  4 15 7       Current loop    One ofthe most common connections is a current loop with 0 20mA or  4 20mA  Connection can be made to the measuring station directly or  via isolation amplifiers     Direct connection    Inputs on the measuring station are not galvanically isolated from each  other or from the measuring system   s earth  minus on the power supply  unit   When an external current loop is connected directly  this will thus  be galvanically connected to the minus on the power supply unit     In this way  multiple current loops that are connected to the measuring  station will be connected together and have the same earth potential   The internal resistance in this case is 50 ohm  1V at 20mA   The  maximum allowable current is 50mA     Isolation amplifiers 4 20 mA  When a connection is made using isolation amplifiers such as Inor  CL122  inputs will be isolated from each other and from earth potential     The recommended power supply in the loop is 24 VDC  The maximum  allowable power across the inputs is 15 VDC  The potential drop in the  loop will be
12. res  and that power consumption increases significantly when registration  intervals more frequent than one minute are used     Measuring and communication    For data communication  measuring and operator communication  there  is an electronic unit mounted in the inner panel of the case  Four or  eight measuring sensors are connected to this  For data collection and  settings  there are buttons and a display  Refer user manual Mitec AT40  and AT 31     For communication with the Mitec measuring central there is a standard  modem or a GSM modem  depending on the option chosen     Measuring sensors    Measuring sensors are connected via the terminal block  A number of  different sensors can be used  Refer www mitec se for selection     For connection of process signals  4 20mA is standard     Measuring sensors are scaled automatically and the measuring signal  can be shown on the local display     22 mitec RMS40    
13. the display  e Press ALT   e Set the modem type using   and   buttons   e Press ALT   e Set the Baud rate using   and   buttons    e Return to Readings     Telephone modem SRT   Select Modem 3       GSM modem Siemens M20T   Select Modem 3       GSM modem Wavecom WMOD2  Select Modem 3       Baud rate for above modems   Select 9600 bps          16 mitec RMS40    Mitec RMS40 and RMS31 measuring station Sta rtup    6   Start measuring F5    After the above installation is done the system is ready to go into  operation  It is first necessary for the measurement to be started  which is done under the Readings function FS   e Press FUNC repeatedly until F5 is shown in the display  e Press ALT    e Start using the   button    e Press the   button again to confirm the start    If any of the above settings need to be changed  the measurement must  first be stopped  This is also done under F5     mitec RMS40 17    Testi ng Mitec RMS40 and RMS31 measuring station    Testing    When the installation is completed and settings made  it is time to  check the operation of the unit     Check sensors    The sensors output signal can be simply checked on the measuring  station   s display     e Press FUNC so the display lights up   e Press ALT and read the value from sensor 1     e Show sensors 1 8 by pressing the   button     Check that the values displayed from the sensors appear reasonable     Check communication    A simple check can be carried out directly in the field using a mobile  telep
    