1. Setting 12 16 8 24 33 6 V Default 14 4 28 4 Description When battery voltage is above setting controller displays high DC volt warning Weak Batt Detect Setting Disable Enable Default Enable Description Activates weak battery protection W Batt Set Point Setting 4 8 8 4 9 6 16 8 V Default 8 4 9 6 Description When battery voltage is below setting controller displays battery warning Charge failed Setting 9 6 14 4 19 2 28 8 V Default 12 6 22 6V Description When voltage is out of range controller displays charge fail 17 9 AC Voltage 1 System AC Volt Setting 110 120 190 208 220 380V 440 480 660 3300 4 160 6600 7620 11400 Default 380V Description Setup Genset AC voltage Hi ACV Protect Setting Disable Enable Default Enable Description Activates high voltage protection Hi ACV Protection Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default 3 Description Setup the action when high voltage occurs Hi ACV Set Point Setting 110 132 120 144 190 228 208 250 220 264 380 456 V Default 122 122 210 242 242 418 Description When AC voltage is above the setting the controller outputs trip signal Hi ACV Delay Setting 0 5 5 Seconds Default 2 5 Description When high voltage occurred timer starts before activating protection Low ACV Detect Setting Disable Enable Default Enable Description Activates low voltage protection Low ACV Protection Setting 1 W
2. 3 Trip 4 Stop Default 4 Description Setup the action when service reminder reaches setting Maintain Code 0 Setting 0 99 Default 12 Description Setup first two digits of service password Maintain Code 1 Setting 0 99 Default 15 Description Setup remaining digits of service password Maintain DnCount Setting 0 1275 hour Default 250 Description Setup the duration between each service 15 Reverse Power 1 ReversePower Det Setting Disable Enable Description Activates Reverse power detection R P Protect Setting 1 Warning 2 Alarm 3 Trip 4 Stop Description Setup the action when reverse power occured R P Set point Setting 0 1084 0 KW Description Setup the reverse power upper limit Uppder limit changes with AC voltage setting and CT ratio R P Delay Setting 1 20 Seconds Description When reverse power reaches setting timer starts before activating protection 16 Others 1 Protect Pending Setting 1 30 seconds Default 10 Description Time delay for displaying warning or error messages after engine starts 25 2 Language Setting English Chinese Default English Description Choose between English or Chinese language 3 Comm Address Setting 0 255 00H FFH Default FFH Description Multiple Genset networking via RS 485 requires individual address for each controller 4 Not in AUTO Mode Setting Disable Enable Description When GTR 220 is
3. Pre fuel is activated the fuel outputs before crank procedure 2 AUTO Inthe Auto mode the GTR 600 starts the engine by ATS signal and then the LCD shows preheat if pre heat function is enabled After pre heat the engine starts to crank If engine fails to start the system returns to the pre heat state and then start to crank the engine again For example if the conditions and parameter settings are given as follows l stop duration is 10 seconds crank attempt is 3 times The engine cranks for 10 seconds and then rest for 10 seconds after 3 attempts the LCD shows the over crank and triggers the alarm 3 OFF Switch to OFF stops the engine and then stop appears on the LCD The idle also appears on the LCD if the idle function is enabled After 10 seconds of delay depends on the setting the engine stops completely and idle icon disappears E Rear connectors Pin Description Code 2 Battery B 3 Battery B 4 Ground GND 5 Crank output Crank 6 Fuel pump output Fuel 7 Stop output Stop 8 Output 3 Out 3 9 Output 2 Out 2 10 Output 1 Out 1 11 Output 1 12 Output 0 Out 0 13 Output 0 18 Input 4 IN 4 19 Input 3 IN 3 20 Input 2 IN 2 21 Input 1 IN 1 22 ATS input ATS 23 Input 0 IN O 24 Low oil pressure switch L O P 25 High water tempera
4. 0 A 200 1000 A 240 1200 A 300 1500 A 320 1600 A 400 2000 A 500 2500 A 600 3000 A 640 3200 A 800 4000 A 1000 5000 A Description When current is above the setting controller outputs trip signal setup range is related to the CT ration setup 9 Short Delay Setting 0 1 1 0 Second Default 0 2 Description When AC short occurres timer starts before activating protection 20 11 RPM 1 RPM Mul Factor Setting 1 200 Default 60 Description Please use value calculated in next parameter setting RPM Div Factor Setting 1 200 Default 40 Description The R P M Mul and Div are the ratio of engine revolution versus total number of fly wheel teeth or the RPM of fly wheel versus the RPM of alternator charger For example Set up the RPM numerator and the denominator to 1 to find input pulse from the LCD A Ifthe engine revolution is 1800 and alternator revolution is 460 input pulse the R P M numerator could be set to 90 gt 1800 20 and R P M denominator could be set to 23 gt 46020 Solution 1800 460 3 913 The R P M calculation formula is as below R P M Input pulse RPM numerator RPM denominator 1800 460 90 23 B If the engine revolution is 1500 and total count of fly wheel teeth in one second is 4437 input pulse the R P M numerator should be set to 45 and R P M denominator should be set to 133 Solution 1500 4437 0 338 The R P M calculation formula is as
5. 3 Charge fail 4 Low voltage 4 Under voltage 5 High frequency 6 Low frequency 8 36 VDC Max 24 W 0 S500VAC 40 2 O0O 5A CT ratio 0 2 0 80 Hz 0 02 10 A 30 VDC Output 3 Max 1A Communication protocol A Power environment Communication protocol Working temperature Dimension W H D Opening W H Weight B Modbus master Communication protocol 10 C 60 C 216 mm 144 mm 89 mm 210 mm 138 mm 1 Kg A Genset Info Display generator inforamtion B Event Record Display operation history C Parameter Modify 1 Crank Settings 1 Detect Frequency Setting Disable Enable Default Enable Description Check frequency value before cranking the engine 2 Detect oil press Setting Disable Enable Default Enable Description Check oil pressure before cranking the engine 3 Crank interval Setting 5 40 seconds Default 10 Description Set the duration of each crank 4 Crank attempts Setting 1 10 Default 3 Description Set total number of crank attempts 5 Escape up limit Setting 15 30 Hz Default 20 Description When frequency reaches setting starter motor disconnects from engine 6 Engage low limit Setting 15 30 Hz Default 20 Description If frequency is below setting allows crank procedure 7 OP build up time Setting 0 2 2 0 Seconds Default 0 6 Description Time delay before disconnecting starter motor after oil pressure swit
6. GTR 600 User manual is WO monicon TEL 04 2238 0698 FAX 04 2238 0891 Web Site http www monicon com tw E mail sales monicon com tw 1 Introduction A Panel descriptions B Circuit Breaker status LED Indication of circuit breaker status Genset Indicators When ATS transfers load from Mains to the Genset the LED turns ON if connector 26 detects signal from ATS switch 2 C Setup Keypad 1 In password entry mode this keypad switches to next digit 2 Under PARAMETER setting this keypad switches to the next parameter 1 In password entry mode this keypad switches to previous digit 2 Under PARAMETER setting this keypad switches to previous parameter 1 In CODE entry mode this keypad increases the value 2 Under PARAMETER setting this keypad increases the setting value 1 In CODE entry mode this keypad decreases the value 2 Under the PARAMETER setting mode this keypad decreases the setting value Enter or exit the parameter setting mode Confirm and save the settings N These keypads alternately change the display of Genset information evenlog 03 and error code Press reset to clear error and deactivates alarm e8 000 0 D Rotary Switch 1 Manual In manual mode the LCD shows pre heat function after pre heat engine starts immediately If engine fails to start the GTR 600 returns to the OFF mode The pre heat state may not perform if parameter setting is disabled If
7. I Betung User Define Description Setup fuel sensor brand Check before start Setting Disable Enable Default Disable Description Setup the system to check sensors during controller boot up Cel Or Feh Setting F C Default C Description Setup water temperature unit in Fahrenheit or Celsius 23 15 P S I or Bar Setting BAR PSI Default PSI Description Setup oil pressure unit in Bar or PSI 13 Exerciser funct 1 Exercise Funct Setting Disable Enable Default Enable Description Activates exerciser function Date week Depend Setting Date Week Default Date Description Setup monthly exercise by date or week Date set point Setting 1 31 date Default 28 Description Setup date of monthly exercise Week set point Setting Sunday Monday Tuesday Wednesday Thursday Friday saturday Default Sunday Description Setup week of monthly exercise Hour set point Setting 0 23 hour Default 12 Description Setup the starting hour of the exercise Minute set point Setting 0 59 minute Default 0 Description Setup the starting minute of the exercise Running Interval Setting 0 510 minute Default 4 Description Setup the duration of each exercise 14 Maintain 1 Maintain Funct Setting Disable Enable Default Disable 24 Description Activates service reminder function Maintain Protect Setting 1 Warning 2 Alarm
8. arning 2 Alarm 3 Trip 4 Stop Default 3 Description Setup the action when low voltage occurs Low ACV set point Setting 78 110 84 120 134 190 146 208 154 220 266 380 V Default 108 108 172 198 198 342 Description When AC voltage is below setting controller outputs trip signal Low ACV delay Setting 0 5 5 Seconds Default 2 5 Description When low voltage occurred timer starts before activating protection 18 10 Mini ACV Detect Setting Disable Enable Default Enable Description Activates extreme low voltage protection 11 Mini ACV setpoint Setting 34 88 36 96 58 152 62 166 66 176 114 304 V Default 56 60 96 110 110 198 Description When sudden drop of AC voltage blows setting low voltage protection is disabled 12 ACV Escape Motor Setting Disable Enable Description Disconnect starter motor by Genset voltage 13 Esc ACV Setpoint Setting 44 100 48 108 76 172 84 188 88 198 152 342 V Default 72 72 124 124 132 228 Description Disconnect starter motor when AC Voltage reaches disconnecting setting 10 AC Ampere 1 Current Ratio Range 1 31 5 5 10 5 15 5 20 5 30 5 40 5 50 5 60 5 75 5 80 5 100 5 150 5 200 5 250 5 300 5 400 5 500 5 600 5 700 5 800 5 900 5 1000 5 1200 5 1500 5 1600 5 2000 5 2500 5 3000 5 3200 5 4000 5 5000 5 Default 500 5 Description Setup the current transformer ratio 2 Over load Detect Setting Disable E
9. below R P M Input pulse revolution numerator revolution denominator 1500 4437 45 133 C If the teeth count of engine flywheel is 118 Assume the rated rpm of Gen set is 1500 rpm Then the 1500 rpm 50hz gt 30 rpms per second also generate 30 x 118 3540 electronic signals Then 1500 3540 0 423 75 177 0 423 set the R P M numerator to 75 and R P M denominator to 177 RPM Escape motor Setting Disable Enable Default Disable Description Disconnect starter motor by RPM setting RPM Esc Set point Setting 300 900 RPM Default 480 Description Disconnect starter motor when RPM reaches setting RPM Disp Source Setting Alternator Frequency Default Freq 21 Description Converts the RPM from frequency or alternator speed O S Detection Setting Disable Enable Default Enable Description Activates over speed protection O S set point Setting 1350 2100 RPM Default 1980 Description If engine speed is higher than setting controller shuts down the engine only if over speed is enabled Over speed delay Setting 1 10 Second Default 1 Description When over speed occurres timer starts before activating protection 12 Sensors 1 LFL Value Alarm Setting Disable Enable Default Enable Description Activates low fuel warning LFL set point Setting 6 55 Default 45 Default When fuel level is below setting controller displays warning message HFL se
10. ch activates Detect oil press must be enabled 8 Idle interval Setting 0 600 Seconds Default 0 Description Duration of engine idle 2 Engine Settings 1 PreAdd Fuel Time Setting 0 0 5 0 seconds Default 3 Description Activates fuel pump before initiating crank procedure Pre Heat Time Setting 0 20 Seconds Default 0 Description Duration of Preheat before crank Energied to Stop Setting 1 30 seconds Default 10 Description Output duration for stop solenoid to shut down the engine Failed to stop Setting 1 10 Seconds Default 2 Description Time delay before triggering engine shutdown failed alarm Trip then shut Setting Disable Enable Default Enable Description When error occurred timer starts before shutdown the engine Trip duration Setting 30 900 Seconds Default 30 Description When error occurred controller outputs error signal if error is not cleared within setting system initiates Genset shutdown Cooling time Setting 0 1250 Seconds Default 30 Description Set engine cooling time for normal Genset shutdown Engine cooling time is disabled during malfunction shutdown Freq versus RPM Setting 0 200 Default 30 Description To conver RPM from frequency divide RPM by frequency 1800rpm 60HZ 30 30 is the ratio for this setting 9 Man Inst Stop Setting Disable Enable Default Enable Description Manua
11. cy error if high frequency protection is enable Hi Freq Delay Setting 1 9 Seconds Default 1 Description When high frequency occurres timer starts before activating protection Low frequency Detect Setting Disable Enable Default Enable Description Activates low frequency protection L F Protection Setting 1 Warning 2 Alarm 3 Trip 4 shutdown Default 2 Description Setup the action when low frequency occurs L F Set Point Setting 40 50 48 60 Hz Default 45 55Hz Description When AC frequency is lower than setting controller outputs trip signal Low Freq Delay Setting 1 9 seconds Default 3 Description When low frequency occurres timer starts before activating protection 16 10 Mini Freq Det Setting Disable Enable Default Enable Description Activates minimum low frequency protection M F set point Setting 30 48 Hz Default 36 Description When sudden drop of frequency belows setting low frequency protection automatically disables and engine operates at idle speed Battery 1 System DC volt Setting 12 24 V Default 12 Description Setup DC voltage in 12V or 24V Batt Fault Alarm Setting Disable Enable Default Enable Description Activates battery error protections L batt Set Point Setting 8 4 12 16 8 24 V Default 10 8 20 Description When battery voltage is below setting controller displays low DC volt warning H batt Set Point
12. e initiating crank procedure InputO Detect Setting Disable Enable Default Enable Description Activates Input 0 function Input 0 Name Setting 1 Emergency Stop 2 User Define 3 Low battery Voltage 4 System fault 5 High fuel level 6 System trip 7 Insulation Fail 8 Cooling failure 9 Malfunction warning 10 Charge fail 11 Over load 12 Low water temperature 13 Preheat Default Preheat Description Define the function for input 0 InO Protection Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default Stop Description Setup the action when input 0 activates InO Switch Type Setting NC NO Default Normal Close Description Setup input 0 to normally close or normally open InputO Delay Setting 0 2 5 0 Seconds Default 0 2 Description When input0 activates timer starts before activating protection Input 1 Detect Setting Disable Enable 12 10 11 12 13 14 15 Default Enable Description Activates input function Input Name 1 Emergency Start 2 User Define 3 Low battery Voltage 4 System fault 5 High fuel level 6 System trip 7 Insulation Fail 8 Cooling failure 9 Malfunction warning 10 Charge fail 11 Over load 12 Low water temperature 13 Preheat Default 4 Description Define function for input 1 In1 Protection Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default Stop Description Setup the action when input activates Inl Switch Type Setting NC NO Default Normal Open Descriptio
13. equency 14 Low oil 15 High water 16 High AC voltage pressure switch temperature switch 17 Low AC voltage 18 Overload 19 Short circuit 20 Low battery voltage 21 High battery voltage 22 Input 0 activate 23 Inputlactivate 24 Input 2 activate 25 Input 3 activate 26 Sensor fault 27 High water temp 28 Low oil pressure 29 Low fuel level 30 High fuel level 31 System notin AUTO 32 System in AUTO 33 Manual Start 34 AUTO Start 35 Standby mode 36 Pre heat 37 Pre fuel 38 Cranking 39 Crank cycle 40 System normal 41 System Alarm 42 System Trip 43 Engine shutdown 44 Engine Cooling 45 Reverse power Default 36 Description Setup the function for output 0 2 Output 1 function Setting 1 45 Default 1 Description Setup the function for output 1 3 Output 2 function Setting 1 45 Default 5 Description Setup the function for output 2 4 Output 3 function Setting 1 45 Default 42 Description Setup the function for output 3 7 Frequency 1 System Frequency Setting 50 60 Hz Default 60 Description Setup Genset frequency in 50Hz or 60Hz Hi Freq Detect Setting Disable Enable Default Enable Description Activates high frequency protection H F set point Setting 50 60 60 72 Hz Default 55 66Hz Description When AC frequency is higher than setting controller shuts down the engine and display high frequen
14. in OFF mode controller triggers alarm 5 Contrast Adjust Setting 1 19 Description Adjust contrast of LCD screen D Error Record Display Malfunction history E Miscellaneous 1 Time setting Description Setup real time clock 2 User Code Description Reset user password 3 Maintain Code Description Reset engineer password 4 Crank information Description a Total count Display total number of crank attempts b Fail count Display total number of crank fail c Succeed count Display total number of successful cranks d Reset counters Clears crank information Password required
15. l shutdown the Genset without cooling down the engine 3 Hour Meters l 3 4 Acc Seconds Setting 0 59 Seconds Default 0 Description Set the hour meter in seconds Acc Minutes Setting 0 59 Minutes Default 0 Description Set the hour meter in minutes Acc Hour Setting 0 99 Hour Default 0 Description Set the hour meter in hours Acc Hour 100 Setting 0 99 100 Default 0 Description Set the hour meter in 100 hours scale 4 Sensors Switches 1 3 4 H W T Detection Setting Disable Enable Default Enable Description Activates high water temperature protection H T Sw Type Setting NC NO Default Normal Open Description Setup the switch to normally close or normally open H W T Sw Delay Setting 1 9 5 Seconds Default 1 5 Description When high water temperature occurres timer starts before initiating shutdown L O P Detection Setting Disable Enable Default Enable 11 6 5 Description Activates low oil pressure protection O P Sw Type Setting NC NO Default Norma close Description Setup the switch to normally close or normally open L O P Sw Delay Setting 0 2 6 0 Seconds Default 1 Description When low oil pressure occurres timer starts before initiating shutdown Auxiliary Input 1 Auto input delay Setting 0 2 5 seconds Default 1 Description Time delay for ATS input befor
16. n Define inputl type to normally close or normally open In1 delay Setting 0 2 5 0 Seconds Default 2 0 Description When input activates timer starts before activating protection Input 2 Detect Setting Disable Enable Default Enable Description Activates input2 function Input 2 Name Setting 1 Low coolant level 2 User Define 3 Low battery Voltage 4 System fault 5 High fuel level 6 System trip 7 Insulation Fail 8 Cooling Fan failure 9 Malfunction warning 10 Charge fail 11 Over load 12 Low water temperature 13 Preheat Default 8 Description Define function for input 2 In2 Protection Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default 2 Description Setup the action when In2 activates In2 switch type Setting NC NO Default Normal Open Description Setup input2 to normally close or normally open 16 17 18 19 20 21 22 23 24 Input2 Delay Setting 0 2 5 0 Seconds Default 0 4 Description When input2 activates timer starts before activating protection Input3 Detect Setting Disable Enable Default Enable Description Activates input3 function Input 3 Name Setting 1 Low fuel level 2 User Define 3 Low battery Voltage 4 System fault 5 High fuel level 6 System trip 7 Insulation Fail 8 Cooling Fan failure 9 Malfunction warning 10 Charge fail 11 Over load 12 Low water temperature 13 Preheat Default 6 Description Define function for AUX 3 I
17. n3 Protection Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default 4 Description Setup the action when input 3 activates In3 Switch Type Setting NC NO Default Normal Open Description Setup Input 3 to normally close or normally open Input3 Delay Setting 0 2 5 0 Seconds Default 2 Description When input 3 activates timer starts before activating protection Input4 Detect Setting Disable Enable Default Enable Description Activates input4 function Input4 Name Setting 1 Low fuel level 2 User Define 3 Low battery Voltage 4 System fault 5 High fuel level 6 System trip 7 Insulation Fail 8 Cooling Fan failure 9 Malfunction warning 10 Charge fail 11 Over load 12 Low water temperature 13 Preheat Default 5 Description Define function for input4 In4 Protection Setting 1 Warning 2 Alarm 3 Trip 4 Stop 14 Default 2 Description Setup the action when input 4 activates 25 In4 Switch Type Setting NC NO Default Normal Open Description Setup Input 4 to normally close or normally open 26 Input4 Delay Setting 0 2 5 0 Seconds Default 0 4 Description When input 4 activates timer starts before activating protection 6 Auxiliary Output 1 Output 0 function Setting 1 45 1 All errors 2 Trip 3 Preheat 4 Idle 5 Reset 6 Main breaker On 7 Main breaker hold 8 Genset power normal 9 Engine running 10 Over crank 11 Over speed 12 Over frequency 13 Low fr
18. nable Default Enable Description Activates overload protection 3 Over load Protection Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default 3 Description Setup the action when overload occurs 19 4 O L Set Point Range 1 31 0 1 20 0 A 0 1 30 0 A 0 1 40 0 A 0 1 50 0 A 0 1 60 0 A 0 1 75 0 A 0 1 80 0 A 0 2 100 0 A 0 3 150 0 A 0 4 200 0 A 5 0 250 0 A 6 0 300 0 A 8 0 400 0 A 10 0 500 0 A 12 0 600 0 A 14 700 0 A 15 0 750 0 A 16 0 800 0 A 18 0 900 0 A 20 0 1000 0 A 24 0 1200 0 A 30 0 1500 0 A 32 0 1600 0 A 40 0 2000 0 A 50 0 2500 0 A 60 0 3000 0 A 64 0 3200 0 A 80 0 4000 0 A 100 0 5000 0 A 120 6000 A Description When current is above setting the controller outputs trip signal setup range is related to the CT ratio 5 Overload Delay Setting 10 300 Second Default 40 Description When overload occurres timer starts before activating protection 6 Short Detect Setting Disable Enable Default Enable Description Activates AC short protection 7 Short protect Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default 4 Description Setup the action when AC short occurs 8 Short Set Point Setting 1 31 1 5 A 2 10 A 3 15 A 4 20 A 6 30 A 8 40 A 10 50 A 12 60 A 15 75 A 16 80 A 20 100 A 30 150 A 40 200 A 50 250 A 60 300 A 80 400 A 100 500 A 120 600 A 150 750 A 160 800 A 180 90
19. t point Setting 35 99 Default 95 Description When fuel level is above setting controller displays warning message LOP value alarm Setting Disable Enable Default Enable Description Activates low oil pressure warning LOP set point Setting 15 60 PSD Default 15 Description When oil pressure is below setting controller displays warning message HWT Value Alarm Setting Disable Enable Default Enable 22 10 11 12 13 14 Description Activates high water temperature protection HWT set point Setting 85 110 C Default 105 Description When water temperature is above setting controller displays warning message OP Escape motor Setting Disable Enable Default Disable Description Disconnect starter motor when oil pressure reaches setting Esc OP Set point Setting 25 65 PSD Default 45 Description Disconnect starter motor when oil pressure reaches setting OP Sensor Brand Setting VDO 10 Bar KD 10 Bar YG 962 N 010 B2 KL 3967251 MHI 10 Bar DATCON 10 Bar SUSUKI10 Bar VDO 5 Bar KP 6 Bar KAMAZ Betung Weichai Betung 3317 EPT Description Setup oil pressure sensor brand WT sensor Brand Setting VDO 120 KD 120 WGI 900131 KP130 YB 054 KL 3967250 MHI 98 SUSUKI PRO SCD Betung User Define Description Setup water temperature sensor brand FL sensor Brand Setting SUSUK
20. ture switch H W T 26 Genset breaker status input G switch 27 N A 28 Pickup RPM Pick up 29 Pickup RPM Pick up 49 CT 1 input Il 50 CT 2 input R 51 CT3 input B 52 CT Common input Com 53 Sensor V output Sensor V 54 Sensor Common GND input Common 55 Oil pressure sensor input Oil Press 56 Oil temperature sensor input Oil Temp 57 Water temperature sensor input Coolant Temp 58 AUX sensor input Auxiliary U__ Generator U input U V Generator V input V W Generator W input W N Generator N input N 2 Dimension 81 mm 144 mm 209 mm 156mm 216 mm 6 3 Specification A Display CON DAR WN S 11 12 Mains OFF warning Fuel level Frequency AC voltage current RPM Engine parameter settings Battery voltage Weekly monthly exerciser Water temperature Oil pressure 1024 Event log 64 Error record B Remote access 1 2 3 4 Start stop and reset Parameter settings Genset monitoring Error records C Front panel 1 2 3 4 Manual Auto ATS OFF Reset D Protections Engine 1 High water temperature 2 Low oil pressure 3 Low coolant 4 Over crank 5 Over speed 6 Low fuel E Specification DC input Power consumption Voltage measurement Current measurement Frequency measurement Relay output Generator Battery 1 Over load 1 Low voltage 2 Short 2 High voltage 3 High voltage