5K online UPS Uninterruptible Power Supply System User Manual

image

Contents

1. Parameter 1 It s for program alternatives Refer to below table for detailed setting programs Parameter 2 and parameter 3 are the setting options or values for each program 00 Exit 01 Output voltage setting Parameter 3 Output voltage You may choose the following output voltage by pressing On Mute up key or Select down key button Then press enter key to confirm the selected output voltage 220 presents output voltage is 220Vac 230 presents output voltage is 230Vac 240 presents output voltage is 240Vac Parameter 2 amp Parameter 3 Set acceptable high voltage point and low voltage point for Line mode by pressing On Mute up key or Select down key button HLS High loss voltage in Line mode in parameter 3 For 220 230 240 VAC models the setting range is from 260V to 280V LLS Low loss voltage in Line mode in parameter 3 For 220 230 240 VAC models the setting range is from 170V to 190V 03 ECO enable disable Parameter 3 Enable or disable ECO function by pressing On Mute up key or Select down key button Then press enter key to confirm selection ENA ECO mode is enabled DIS ECO mode is disabled 04 ECO voltage range setting Parameter 2 amp Parameter 3 Set acceptable high voltage point and low voltage point for ECO mode by pressing On Mute up key or Select down key button HLS High loss voltage in ECO mode in parameter 3 For 220 230 240 VAC models the
2. 5K online UPS Uninterruptible Power Supply System Table of Contents 1 le ele e LHCE e Wal E 2 Eege ein Cd ET 2 EE e aO peer eee a eee een eer ere cere ete eee ee ee eee E ee H E ale e EE 2 Ee EIERE 3 1 5 Maintenance Service ANC FaUItS cccccccccucueucueucusususususeseseueueueuuueueuaueuaueueueueueuenanas 3 Ze T Stall tion and SOUND GE 4 SEENEN d e len E E d ele CL TEE 7 3 BE leg el E ele TT EE 7 5 27 LED Pane REN 7 GINS E ge EE 9 3 4 LED display WOrdINGS INGE TEEN 9 Bae YPS ln e EE 9 3 6 Operating Mode Description cccccsseusscuseusscuscusecuscusecuscusecuscusecueausecususecusansesues 12 3 Faults Reference CODE osad nad ad daaetadebhataad dha ieee haseiantadnoeen naan 13 370 Wal MING INGICALOF ENEE 13 4 StOrage and Maintenan Ce iiisisscesisiccncasnnnenvitusnanainansuensnsnccanseewardsnussguncduanieaeresnermeae 14 E elei ee TEEN 15 1 Important Safety Warning Please comply with all warnings and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety information and operating instructions carefully 1 1 Transportation Please transport the UPS system only in the original package to protect against shock and impact 1 2 Preparation Condensation may occur if the UPS system is moved directly from cold to warm environment The UPS system must be absolu
3. 95 up to 0 99 170 260Vac OUTPUT Output Voltage AC Voltage Regulation Batt Mode Frequency Range Synchronized Range Frequency Range Batt Mode Current Crest Ratio CF Harmonic Distortion THDU AC Mode to Batt Mode Transfer Time Inverter to Bypass Waveform Batt Mode Phase 220 230 240 VAC 1 47 53 Hz or 57 63 Hz 50 Hz 0 2 Hz or 60Hz 0 2 Hz 3 1 3 THD Linear load 6 THD Non linear Load Zero 4 ms Typical Pure Sinewave single phase L N G Terminal EFFICIENCY AC Mode Battery Mode 100 of full RCD load 92 peak 50 100 of full RCD load 90 peak during battery autonom BATTERY Battery Type Battery Voltage Backup Time Typical Recharging Time Li battery 102V 4 min 100 load 6 min 80 load 2 hours recovers to 90 capacity PHYSICAL Dimension D X W X H mm Net Weight kgs 600 x 438 x 88 2 ENVIRONMENT Humidity Noise Level 0 95 RH 5 40 C non condensing Less than 55dBA 1 Meter amp around UPS with less than 80 Load MANAGEMENT Smart RS 232 or USB Optional SNMP Supports Windows 2000 2003 XP Vista 2008 7 Linux Unix and MAC Power management from SNMP manager and web browser 15
4. button at least 2 seconds to turn off the UPS in battery mode UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency It will return back to default display when pausing for 10 seconds Setting mode Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in standby mode or bypass mode Down key Press this button to display next selection in UPS setting mode Switch to bypass mode When the main power is normal press ON Mute Select ON Mute and Select buttons simultaneously for 5 seconds Then UPS Button will enter to bypass mode This action will be ineffective when the input voltage is out of acceptable range OFF Enter Button Select Button 3 2 LCD Panel INPUTBATTTEMP CZ OUTPUTBATTLOAD zali C ae HLI A GCI ay He eet Display Function O O O S O Input Information INPUTBATTTEMP Indicates the AC input voltage AC input frequency battery zal VA voltage battery discharge charge current and ambient LI Hz temperature Setting programs error codes and backup time information Indicates the estimated backup time H hours M minute Indicates the setting programs and the detailed settings a
5. still can charge batteries 12 3 7 Faults Reference Code Bus startfail 01 Ly Inverter voltage Lon 13 x Busover 02 x Inverter output short 14 x Bus under 03 x Battery voltage too high 27 _ x Battery voltage too low Inverter soft start fail Over temperature Inverter voltage high reon posing O dees A Sounding every second ER second Sounding every second 3 8 Warning indicator 13 4 Storage and Maintenance Operation The UPS system contains no user serviceable parts If the battery service life 3 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer S Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material Storage Before storing charge the UPS 2 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 30 C Every 4 months 30 C 45 C Every 1 month 14 5 Specifications Capacity 5000VA 4500W INPUT Low Line Transfer Low Line Comeback Voltage Range l High Line Transfer High Line Comeback Frequency Range Phase Power Factor 170VAC 45 180VAC 5 280VAC 5 Ou 270VAC 5 40 70 Hz Auto sensing single phase L N G Terminal 0
6. ble programmable outlets ENA Programmable outlets are enabled DIS Programmable outlets are disabled Parameter 3 Set up backup time limits for programmable outlets 0 999 setting the backup time limits in minutes from 0 999 for programmable outlets which connect to non critical devices on battery mode 11 10 Backup time setting for outlets Parameter 3 Set up backup time on battery mode for general outlets 0 999 setting the backup time in minutes from 0 999 for general outlets on battery mode 0 When setting as 0 the backup time will be only 10 seconds 999 When setting as 999 the backup time setting will be disabled 3 6 Operating Mode Description Mperating mods LCD display Online mode When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at online mode ECO mode Energy saving mode When the input voltage is within voltage regulation range UPS will bypass voltage to output for energy Saving Battery mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptable range but UPS is overload UPS will enter bypass mode or bypass mode can be set by front panel Alarm is sounding every 10 second Standby mode UPS is powered off and no output supply power but
7. ective earthing of the UPS system and of all connected loads The UPS system features its own internal current source batteries The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet In order to fully disconnect the UPS system first press the OFF Enter button to disconnect the mains Prevent no fluids or other foreign objects from inside of the UPS system 1 5 Maintenance service and faults The UPS system operates with hazardous voltages Repairs may be carried out only by qualified maintenance personnel Caution risk of electric shock Even after the unit is disconnected from the mains building wiring outlet components inside the UPS system are still connected to the battery and electrically live and dangerous Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please v
8. erify that no voltage is present Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any other measures necessary when working with batteries remove wristwatches rings and other metal objects use only tools with insulated grips and handles When changing batteries install the same number and same type of batteries Do not attempt to dispose of batteries by burning them This could cause battery explosion Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic Please replace the fuse only with the same type and amperage in order to avoid fire hazards Do not dismantle the UPS system 2 Installation and setup NOTE Before installation please inspect the unit Be sure that nothing inside the package is damaged Please keep the original package in a safe place for future use 2 1 Rear panel view Programmable outlets connect to non critical loads Output terminal Input terminal Network Fax Modem surge protection USB communication port RS 232 communication port Intelligent slot Emergency power off function connector EPO CON O WO BR LA N e 2 2 Install the UPS For safety consideration the UPS is shipped out from factory with the main switch off Before installing the UPS please follow below steps to activate the UPS first Step 1 Step 2 Pres
9. re listed in section 4 Indicates warning and fault codes and detailed codes are listed in section 7 and 8 Output information OUTPUTBATTLOAD Indicate the output voltage output frequency load level load Fa E om KW 8 a E VA in VA and load in Watt AB a Van Hz Indicates battery level by 0 24 25 49 50 74 and 75 100 charging status and battery type by SLA Li SLA sealed lead acid battery Li Li battery Load information Indicates overload Bloe Indicates the load level by 0 24 25 50 50 74 and 3 75 100 o m Mode operation information Indicates the UPS connects to the mains Indicates the bypass circuit is working Indicates the ECO mode is enabled Indicates the PFC circuit is working Indicates the inverter circuit is working Indicates that the UPS alarm is disabled Programmable outlets information J Indicates that programmable outlets are working 8 3 3 Audible Alarm Battery Mode Sounding every 4 seconds Low Battery Sounding every second Sounding twice every second Continuously sounding Bypass Mode Sounding every 10 seconds 3 4 LCD display wordings index To CHO Be Battery fate O O Oooo a Battery replace on D 0 Cru IT ct ll kee or IL a III V L C0 Ee Lm tn ENA DIS ESC HLS LLS EP TP CH ez Hs o mM 3 5 UPS Setting Parameter 2 Parameter 1 Parameter 3 There are three parameters to set up the UPS
10. s the main switch to activate the UPS Remove front panel Press the main switch to activate Press again to inactivate the UPS the UPS Step 3 Put the front panel back to the unit Rack mount Installation Step 1 Step 2 Tower Installation Step 1 Step 2 Step 1 UPS input connection Plug the UPS into a two pole three wire and grounded receptacle only Please do not use extension cords The input plug is 12 3C Step 2 UPS output connection Simply plug devices to output sockets During power failure UPS will provide power to connected devices Step 3 Communication connection Intelligent slot This model is equipped with intelligent slot perfect for SNMP RS 232 USB or AS 400 card When installing with these communication card in the UPS it will provide advanced communication and monitoring options NBG w We mg Al w SA ZZ f lt Ki CG w i ei N G A X NA ra SY i Ak NY Cee a2 Oh Ki j Ba WAN L hi S ec Inn 8 ge el ep D AJ ee Loo H Step 2 s Remove cover of intelligent Insert communication card Screw card tightly and Slot into the slot complete installation Step 4 Turn on the UPS Be sure to press the main switch to activate the UPS first before turning on the UPS Then press the ON Mute button on the front panel for two seconds to power on the UPS Important Only operate main switch for initial usage or long term storage Note The bat
11. setting range is from 7V to 24V of the nominal voltage LLS Low loss voltage in ECO mode in parameter 3 For 220 230 240 VAC models the setting range is from 7V to 24V of the nominal voltage 05 Bypass mode enable disable when UPS is off Parameter 3 Bypass mode enable disable when UPS is off and the mains is ok ENA Bypass mode is enabled and there is output from UPS even though the UPS is off but the mains is ok DIS Bypass mode is disabled and there is no output from UPS even though the mains is ok Parameter 2 amp Parameter 3 Set acceptable high voltage point and low voltage point for bypass mode by pressing On Mute up key or Select down key button HLS High loss voltage in Bypass mode in parameter 3 For 220 230 240 VAC models the setting range is from 230Vac to 264Vac LLS Low loss voltage in Bypass mode in parameter 3 For 220 230 240 VAC models the setting range is from 170Vac to 220Vac 07 Bypass frequency range setting Parameter 2 amp Parameter 3 Set acceptable high frequency point and low frequency point for Bypass mode by pressing On Mute up key or Select Down key button HLS High frequency point in Bypass mode in parameter 3 For 50Hz models the setting range is from 51 0Hz to 55 0Hz LLS Low frequency point in Bypass mode in parameter 3 For 50Hz models the setting range is from 45 0Hz to 49 0Hz 08 Programmable outlets enable disable Parameter 3 Enable or disa
12. tely dry before being installed Please allow at least two hours for the UPS system to acclimate the environment Do not install the UPS system near water or in moist environments Do not install the UPS system where it would be exposed to direct sunlight or near heater Do not block ventilation holes in the UPS housing 1 3 Installation To guarantee UPS normal operation before connecting devices to the UPS please verify that ground and neural lines of the connected devices are not short circuited see figure 1 ES NEUTRAL GND Devices Figure 1 Arr neutral line and ground line are short circuited please add isolation transformer between UPS and devices see figure 2 Er eegg f went DI A NEUTRAL isolation NEUTRAL transformer GND Device Figure 2 Do not connect appliances or devices which would overload the UPS system e g laser printers to the UPS output sockets Place cables in such a way that no one can step on or trip over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system 1 4 Operation Do not disconnect the mains cable on the UPS system or the building wiring outlet shockproof socket outlet during operations since this would cancel the prot
13. tery charges fully during the first five hours of normal operation Do not expect full battery run capability during this initial charge period Step 5 Install software For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown You may insert provided CD into CD ROM to install the monitoring software If not please follow steps below to download and install monitoring software from the internet 1 Go to the website http www power software download com 2 Click ViewPower software icon and then choose your required OS to download the software 3 Follow the on screen instructions to install the software 4 When your computer restarts the monitoring software will appear as an orange plug icon located in the system tray near the clock 3 Operations 3 1 Button operation E C CGC ON Mute Select OFF Enter gt Turn on the UPS Press and hold ON Mute button for at least 2 seconds to turn on the UPS gt Mute the alarm After the UPS is turned on in battery mode press and hold this button for at least 5 seconds to disable or enable the alarm system But its not applied to the situations when warnings or ON Mute Button errors occur Up key Press this button to display previous selection in UPS setting mode Switch to UPS self test mode Press ON Mute buttons simultaneously for 5 seconds to enter UPS self testing while in AC mode or converter mode Turn off the UPS Press and hold this