1. Dimension HxWxD 224x297x52mm HxWxD 315x238x62mm Weight Approx 1 4 kg Approx 2 0 kg CE Approved BY From Panel Meets NEMA4 IP65 NEMA4 IP65 BA sottare Panel Master Easy Builder A 20 MT Series Revision 1 1 0515
2. MT Series Revision 1 1 0515 A 5 How to install the HMI Put the HMI to the cut hole and sew the lock screws at the four assembling holes on the HMI with average strength form the rear side Please do not sew too tight and without equational strength or it will damage the touch panel The operation of the Touch Panel A 6 MT Series Revision 1 1 0515 Industrial Touch Panel MT Installation manual MT080 104 is a kind of touch panel equipped with a VGA 640 H x 480 V size LCD display and an analog input touch panel The screen is a 40 x 30 chemically strengthened glass switches backing panel The shapes of touch keys should be rectangles with sizes from minimum 8 H x 8 V pixels to maximum 640 H x 480 V pixels MT084 121 is a kind of touch panel equipped with a super VGA 800 H x 600 V size LCD display and an analog input touch panel The screen is a 40 x 30 chemically strengthened glass switches backing panel The shapes of touch keys should be rectangles with sizes from minimum 8 H x 8 V pixels to maximum 800 H x 600 V pixels MT Series Revision 1 1 0515 A 7 FEATURES Oo oo Aa O Portrait 90 display amp normal horizontal display supported 100 quality test and industrial standard coating cases Adopts 32 bits high function high reliability and fan less ARM CPU Equipped with genuine 65535 true colors high brightness TFT modules Provides 3 RS232 422 485 communication ports available in
3. I can execute RUN AP Calibrate operation but cannot execute BIOS Download AP Clear SRAM operations When the users want to download new AP without password please set all DIP switches to off SW1 6 Off When turns on HMI again the HMI will display the clean all AP and old password screen After proceeding this procedure the HMI can be operated normally again A 10 MT Series Revision 1 1 0515 Industrial Touch Panel MT Installation manual Startup Test When turns on HMI it will display self testing screen After completed HMI will show the system menu HMI ROM BIOS VERSION B1 1 MAXTHERMO GMTA GROUP CORP N 084 140070006 Checking DIP SW SETING 5 1 11100 FigureA 1 The HMI startup self testing _normal When turns on HMI system will automatically execute hardware testing first to make sure hardware are normal or not The result will show on the screen Figure A 1 lf there are problems the HMI will not communicate with P L C normally When losing electricity during downloading or the PC breaks off downloading after restarting the HMI it will show Firmware Memory Checksum and Application Memory Checksum error It means there is an abnormal downloading To get a correct self testing result please execute a correct download AP procedure again If losing electricity during downloading or the PC breaks off downloading when upgrading OS it will surely cause download failure If you restart the HMI it wil
4. Industrial Touch Panel MT Installation manual MT080 084 104 121 Installation manual MT series Touch Panel such as MT080 VNT MT084 TNT MT104 VNT MT121 TNT are expert HMIs with high functions and reasonable price answer to the needs for most of the automation equipments and systems High coordination screen with plentiful colors relieve high speed and high quality The industrial standard design let MT products meets harsh environment and work for long and Steady Apart from the basic functions other HMIs may have it supports most PLC inverter and temperature controller drivers on the market Maxtech is laboring on the providing LAN function for standard models The ultimate patent design front panel inspired customers to make their own HMI membrane styles In addition to completely communication interfaces flexible hardware design enables Ethernet TCP IP operation The modernistic outward high brightness LCD with considerable memory let MT wins good reputations from users applying HMI in factory automation gt wise buildings and special tool machines MT Series Revision 1 1 0515 MT080 084 121 Specifications items MT080 VNT MT084 TNT MT104 VNT MT121 TNT Color mode TFT LCD Display Type 65536 colors Display Size 8 0 diagonal 8 4 diagonal 10 4 diagonal 12 1 diagonal Number of Pixels 640X480 800X600 640X480 800X600 Display Adjustment Contrast adjustable from touch screen CCFL Life time
5. OS protection password to HMI then the HMI will request the users to enter BIOS password 2 If sets a login user password in AP when selects Run AP it will request the user to enter BIOS password MT Series Revision 1 1 0515 Download AP To download AP to HMI please make sure the download cable is connected properly During the operating or in startup menu the HMI is ready to receive AP data sent by PC automatically When download AP the SW2 ON Panel Setup Touch Panel fo bel hia i Receive Panel Data FigureA 5 The HMI downloading data from PC screens 1 Connect the PC COM1 or Com2 and HMI with a PC download cable HMI Connector PC RS232C HMI Connector PC Connector 9 pin Female 9 pin Female 9 pin Male 9 pin Female RAD RxD TAD SSS TAD 3 3 ae ne SG 5 CTS CTS i RTS E L D RTS a L d HMI COM2 PC COM HMI COM1 PC COM serious Caution Be sure turn off the power before connecting or it will damage the HMI communication components 2 The HMI will judge the data correctness during downloading AP When the PC sends AP data to HMI the HMI will show download AP screen and display related information automatically to receive data The HMI will show Incorrect Model when the Model No is not set correctly in the AP data Please select a correct Model No from the software then download it again If the HMI shows Incorrect User ID Code then the hardware and s
6. Remark New MT 080 VNT RISC 32 Bits CPU 8 TFT 65535 colors 350 cd m 450 cd m CCFL U type x1 50000hrs Under normal temperature 640X480 8 diagonal 16 MB 64MB Optional flash memory 128 KB 1 MB Optional 1 RS 232 HMI PC or HMI PLC 1 RS232 422 485 HMI PLC 1 RS232 422 485 HMI PLC Optional Profibus Module 2 USB Host Ver 2 0 Full Speed Ports 10 100 Ethernet Port HxWxD 176x233x50mm BMP JPG GIF Approx 0 9 kg Complies with FCC class A Yes 07 50 C 3229 120 F NEMA4 IP65 10 90 RH 50 C non condensing Panel Master MT 508 TV Intel PXA255 8 TFT 256 colors 400 cd m CCFLx1 40000hrs Under normal temperature 640X480 8 diagonal 2MB flash memory 128 KB 1 RS 232 HMI PC 1 RS232 485 HMI PLC 1 Printer Port none none Optional HxWxD 231x176x55mm BMP Approx 1 2 kg Complies with FCC class A Yes OF 45392413 F NEMA4 IP65 10 90 RH 40 C non condensing Easy Builder MT Series Revision 1 1 0515 A 19 RISC 32 Bits CPU RISC 32 Bits CPU Brightness 350 cd m 450 cd m 400 cd m Backlight life time 50000hrs Under normal temperature 50000hrs Under normal temperature Flash Memory 16 MB 64MB Optional flash memory 2MB flash memory 1 RS 232 HMI PC or HMI PLC 1 RS 232 HMI PC Communication Port 1 RS232 422 485 HMI PLC 1 RS232 485 HMI PLC 1 RS232 422 485 HMI PLC USB Port 2 USB Host Ver 2 0 Full Speed Ports none
7. e to run normally or even not be turned on the system due to the unstable electricity during operating With the two BIOS system customers need not send the damaged HMI back to the factory Customize logos and User ID codes are available Even for the small amount industrial products this function let the customers have their own operating panel to complete an integer design Automatically data download and communication ports COM1 COM2 detection No need to setup With BIOS recovery system while missing password can prevent system blocking due to missing password MT Series Revision 1 1 0515 A 9 DIP Switches setting MT080 MT084 MT104 MT121 DIP Switches setting Swi Not display system menu go to ON LINE communication after turns on Display system menu when turns on Not go to ON LINE communication E a l Emergency recovery the HMI BIOS to default value OFF version To execute HMI Communication testing program SW1 2 must set to Off To execute Key adjustment program or Touch adjustment program SW1 2 must set to Off To execute HMI application program Dee Pe l C a Extension Module amp Com port Selection Com3 Port enable Extension Module Enable a ee ee HMI operation mode Supports special functions for customized BIOS The MT080 084 104 121 has a BIOS password recovery system to prevent damage when missing password When you forget the password which has been set to the HMI this HM
8. is i 30 000 hours CCFL Life time is 50 000 hours under 25 C and 85 RH Sac cigni under 25 C and humidity 85 RH humidity Analog resistive type Max Number of switches are 40x30 Chemically strengthened glass backing panel Over 1 million point activations Hard coat is resistant to most solvents and chemicals 24VDC 10 Isolation Under 30W COM1 9pin RS232 RS422 RS485 COM2 9pin RS232 COM2 Terminal 4Pin RS422 RS485 COM3 RS232 UB a T EE Touch Screen Communication Ports Ambient Humidity 20 90 RH non condensing Vibration Endurance 0 5mm displacement 10 55Hz 2hours per X Y and Z axis directions RFitesting O FCCP Cessa OOOO O O OO EN61000 4 2 1995 A1 1998 A 2 MT Series Revision 1 1 0515 ee ee er re eee Outlet and Cut out dimensions The outlet and cut out dimensions of MTO80 VNT MT084 TNT are shown as following 164 0 5mm cut out al i q N 285 5 0 5mm _ MT Series Revision 1 1 0515 A 3 The outlet and cut out dimensions of MT121 TNT are shown as following F 3 301 5 0 Smm A 4 MT Series Revision 1 1 0515 Industrial Touch Panel MT Installation manual Installation Before setup HMI please cut a hole according to the cutout dimension see below pictures for your installation reference MT080 VNT 221 5mmx164 0mm MT084 TNT 221 5mmx164 0mm MT104 VNT 285 5mmx210 5mm MT121 TNT 301 5mmx228 0mm
9. l not display normal screens or even cannot be turned on In that case please set the DIP SW2 to OFF restart the HMI to get a default BIOS version B then execute the upgrading OS program to get a correct OS version Set the DIP SW2 to ON then the HMI can be turned on normally MT Series Revision 1 1 0515 Startup Menu lf the DIP SW1 set to off after self testing the MT080 084 104 121 will show startup menu as following figures Situation 1 When SW2 OFF it will show the default startup BIOS o a FigureA 2 Startup BIOS_ Default Situation 2 When SW2 ON it will show the Panel Setup screen o o0 i eh a Real Time Clock Link 1 COM Link COM FigureA 3 Panel Setup_ Remove the USB Sticker Horizontal amp Vertical A 12 MT Series Revision 1 1 0515 Industrial Touch Panel MT Installation manual Situation 3 When SW2 ON and there is an USB sticker insert to rear USB port it will show the Panel Setup screen Panel Setup pot tom is Touch Panel Update from File Real Time Clock Link 1 COM Link 2 COM FigureA 4 Panel Setup_ Insert the USB Sticker Horizontal amp Vertical Download OS To receive new AP OS Ver from COM Port Copy to HMI To Copy AP to another HMI from COM1 2 Run AP Press Run AP or ENT to communicate with P L C Setting HMI keys and hardware functions testing Exit Press ESC to return HMI hardware self testing 1 If sets a BI
10. oftware might not fit each other Please check the brand name of the HMI to make sure you purchased a right hardware A 14 MT Series Revision 1 1 0515 Industrial Touch Panel MT Installation manual COM Ports Define The communication port COM1 of MT080 084 104 121 can use as RS232C gt RS422 and RS485 The COM2 of MT080 084 104 121 can use as RS232 RS422 and RS485 Please make the right connecting cable according to the specifications About the cable connecting figures of the HMI to other P L C please refer to the P L C manuals Communication port COM1 in HMI is a DB 9P Female COM1 pin definitions RS 422 TX and RS 485 RS 422 TX and RS 485 RS 232 TXD 18 RS 232 CTS 4 RS 422 RX 9 RS 422 RX Signal ground a l oe 4 RS Communication port COM2 in HMI is a DB 9P Male COM2 pin definitions Pin d RS485 RS 4B 3 RS 232TXD BT RS 232CTS ___ _ _ _ A So fO Optional5V output 5 Signalground S S COM2 4 pin definitions RS422 and RS485 AZ TAt R RX TH FLL 4g5 Communication port COM3 in HMI is a Round 6P Female for RS232 use only Com3 Pin Configuration MT Series Revision 1 1 0515 LCD Adjustment and IP Address Setting To adjust the LCD brightness TFT model can not be adjusted the brightness press General from MT Panel Setup screen or press LCD Testing from Settings in BIOS B From LCD Brightness press Increase Brightness to increase the b
11. rightness press Decrease Brightness to decrease brightness press Save Brightness to save Press OK to return to system screen When you wish to use the Ethernet please press General from MT Panel Setup screen and then you can set the IP Address You can press the IP Address number and use amp button to increase or decrease the IP Address number General Check Battery Mabe Sereen Saves Tineiminacs ol Enter Panel Setup Mode ENAME Communication Setting Default Start up Language P IP Address 166 LCD Brightness E pere peere see Figure A 6 Panel Setup screen_ LCD brightness adjustment amp IP Address Setting A 16 MT Series Revision 1 1 0515 Industrial Touch Panel MT Installation manual Power and Grounding Specifications Use DC24V as MT080 084 104 121 power input The power consumptions are as following table To ensure the MT080 084 104 121 hardware working properly to avoid outside electromagnetism noise please ground the power source properly MTO8O0 MT084 ltems Models MT104 VNT MT121 TNT an ae Power grounding caution The products are all equipped with power terminals and lock assembling sets The operating procedure is Screw off the power terminal 2 Peel the 24V wiring 1 25mm for 1 cm then plug in the power terminal 3 Use line screw driver to screw the power terminal tight Package content We are appreciated for your purchasing our product
12. round the equipment Ground resistance must be less than 100 2 class3 Note that the ground cable must not be connected to the same ground point as the power circuit Installation Mount the HMI from the front of a suitable preserved hole Attached the brackets behind Fasten the screw of the brackets with proper force Tightening too much may cause damage to the structure of the unit Input and Output signal lines must be separated from the power cables for operational circuits Use shielded cables or it may cause unpredictable problems Do not allow cut wires filling or shavings to fall inside a unit or block when drilling holes or connecting cables lines Environment Do not install in areas subject to excessive dust oily mist conductive dust corrosive gas or flammable gas Do not mount in areas subject to shock or vibration Do not mount in areas subject to high temperature moisture or rain Pa Indicated loss of life severe personal injury or substantial property damage will result if proper precautions are not taken A 18 MT Series Revision 1 1 0515 MT Installation manual Remark Product Information CPU Display Brightness Backlight Backlight life time Resolution Flash Memory Battery Backup Communication Port Extension Port USB Port Ethernet Dimension Graphics Weight EMI CE Approved Operating temperature Front Panel Meets Relative humidity Software
13. s Our standard package should be equipped with 5 items as following Please check after receiving it If there s any shortage please refer to the suppliers MT080 MT084 MT104 MT121 unit x 1 HMI Hardware Power terminal x 1 power terminal Communication terminal x 1 4 pin communication connector MT080 MT084 Installation screw nuts x 4 Lock for assemble with screws MT104 MT121 Installation screw nuts x 8 Lock for assemble with screws MT080 MT084 MT104 MT121 Installation Guide x 1 Installation manual Cautions lf this product is used in a house radio wave interference might occur to other devices In the case that it does occur the user is requested to try a variety of remedies to solve the problem MT Series Revision 1 1 0515 Power source MT080 084 104 121 is equipped with DC24V input power If the supply power is other than DC24V whatever less or excess it will severely damage the HMI Therefore check the switching power supply supporting the DC power regularly To avoid electronic shock be sure the Power Cable is unplugged from the power outlet when connecting the cable to the HMI Grounding From the FG terminal at the rear side of HMI please make sure the grounding is made exclusively When the FG terminal is connect be sure the wire is grounded Without grounding the operation of HMI may be severely affected by excess external noise levels and vibrations Use a cable at 2 mm AWG 14 to g
14. standard models The standard 128KB backup memory which can expend up to 1MB allows storing Alarm Recipe and historical data Supports multi languages Windows build in Fonts BMP and JPG graphics and GIF animations Provides transparent communication for designers to save their program adjustment time The ultimate patent front panel design inspired customers to make their own HMI membrane styles 10 The expansion bus expends various customize devices such as motion control temperature control communication module and I O module etc 11 High speed Ethernet port supports upload and download remote Communication 12 Provides accommodative Software PanelMaster A 8 MT Series Revision 1 1 0515 Industrial Touch Panel MT Installation manual ADVANTAGE FUNCTIONS MT080 084 104 121 are all compact HMIs with BIOS password protected function This special function can be used to prevent the inside application data from being stolen or destroyed The BIOS password is not set as a default situation With BIOS upgrade function wherever in the world whenever the HMI needs to be updated new functions this function supports upgrading without sending back to the factory With serial number in the BIOS as an ID number of the HMI Supports checking the serial number from the HMI to assure a complete after service The unique 2 BIOS systems patent design In our past experiences the HMI will not be abl