PRT ATH1 Temperature and Humidity Sensor

image

Contents

1. The 12V N and N Communication input must be supplied from only ONE point Connections from more than one 12V supply may cause failure or damage to the reader expander or device supplying network power Under no circumstances should you power the locking devices that are connected to the PRT ATH1 from the N and N network communication power supply A separate power supply MUST be used to power the locking devices PRT ATH1 Sensor Installation Manual Page 9 ZONE INPUTS Introduction The Prot g Temperature and Humidity Sensor have no physical zone input connections The Temperature and Humidity Sensor monitors 8 trouble zones used to report trouble conditions A trouble zone is In most cases not physically connected with an input in to the Sensor rather it is related to a status condition within the system For example a module communication fault causes a trouble zone to open as a result of the communication failure Trouble Zone Inputs Each Temperature and Humidity Sensor can monitor up to 8 trouble zones Trouble zones are used to monitor the status of the Temperature and Humidity Sensor and in most cases are not physically connected to an external zone input For example trouble zone AE001 02 is used to monitor the analog supply voltage output and will generate an alarm if the voltage is low or fails The following table details the trouble zones that are configured in the system and the trouble type and group that they
2. Expansion Modules also adds 6 Zones and 8 Outputs to the Prot g System Some of the outputs on the PRT RDM2 have specific access control functions and can be used as zones in the Prot g alarm processing functions Analog 4 Channel Input Expansion Module PRT ADC4 Prot g allows the connection of the latest building automation technology and completely integrated building automation solutions Adds 4 Analog Inputs 4 20mA or 0 10V allowing the connection of numerous industrial automation sensors The Analog Input Expansion Modules also adds 4 PGM Outputs to the Prot g System Analog 4 Channel Output Expansion Module PRT DAC4 Prot g allows the connection of the latest building automation technology and completely integrated building automation solutions Adds 4 Analog Outputs 4 20mA or 0 10V allowing the connection of numerous industrial automation outputs including air damper and sun louver controls as well as analog flow valves The Analog Output Expansion Modules also adds 4 PGM Outputs to the Prot g System PRT ATH1 Sensor Installation Manual Page 7 INSTALLATION Package Contents When receiving the PRT ATH1 Prot g Temperature and Humidity Sensor you should find the kit contains the Items listed below The kit type is clearly labeled on the packaging and will tell you what your kit contains Please note that if you do not have the correct contents contact your distributor immediately PRT ATH1 Prot g Te
3. activate Zone Number Description_________ Type Group AEXxx 02 Power Supply Voltage Low Power Fault General Reserved None AEXxx 06 AEXxx 07 AExxx 08 Module Offline Module Offline Replace the xxx with the appropriate address of the Temperature and Humidity Sensor that you are programming Page 10 PRT ATH1 Sensor Installation Manual PROGRAMMABLE OUTPUTS Introduction The Prot g Temperature and Humidity Sensor have 4 Programmable Outputs PGM s The PGM s are used to activate a range of low current devices including relays PGM Outputs 1 To 2 The PGM outputs 1 2 on the Prot g Temperature and Humidity Sensor are low current relay outputs PGM Number Description Z S O AExxx 01 PGM Output 1 AExxx 02 PGM Output 2 Replace the xxx with the appropriate address of the Temperature and Humidity Sensor that you are programming 12V AUX 1K5 OHM UN Figure 3 Example LED Control from PGM 1 O The PGM outputs 1 to 2 can switch to a maximum capacity of 100mA each exceeding this amount will damage the PGM output LED Outputs PGM 3 and 4 The PGM outputs 3 and 4 on the Prot g Temperature and Humidity Sensor are internal LEDs that can be used for user display and warnings PGM Number Description i O AExxx 03 Square LED Output Center AExxx 04 Triangle LED Output Left PRT ATH1 Sensor Installation Manual Page 11 CONFIGURATION SWITCH Introductio
4. for replacement Locked Device The Temperature and Humidity Sensor or system controller is a locked device and can not communicate on the network Return the unit to the distributor for replacement 7 Virtual Module This address has been reserved as a virtual module and therefore no module can register at this address This protects programming of zones and PGM that are used internally by programmable functions Page 14 PRT ATH1 Sensor Installation Manual ANALOG OUTPUT 0 10V Introduction The Prot g Temperature and Humidity Sensor also has a 0 10V analog output that follows the current value of the Temperature and Humidity input allowing the Sensor to interface to external control systems This output will be updated even when operating with the Prot g System The table below details what the voltages represent Analog Value 10V ETA Temperature Yellow 50 C 58 P 50 C 122 F Humidity Gray 100 Table 1 0 10V Analog Output Values Wiring The 0 10V outputs from the Prot g Temperature and Humidity Sensor can be directly wired into an analog input of a Programmable Logic Controller PLC or similar The example below Shows how to wire the temperature output into a PLC PLC Controller or Similar V AN1 AN2 V YELLOW BLACK Figure 5 0 10V Interface PRT ATH1 Sensor Installation Manual Page 15 STANDALONE CONFIGURATION Introduction The Prot g Temper
5. lt PROTEGE PRT ATH1 Temperature and Humidity Sensor Installation Manual PUBLICATION INFORMATION This manual covers firmware versions 1 40 or higher of the Prot g Temperature and Humidty Sensor when operating on hardware revision 208 4185 020 or higher Specifications may change without notice for updates visit the Integrated Control Technology website at www integratedcontroltechnology com COPYRIGHT NOTICE Integrated Control Technology has granted the following specific permissions for the electronic version of this manual 1 Permission is granted to retrieve print and store a single copy of this manual for personal use for the express purpose of servicing installing or maintaining products from Integrated Control Technology This permission does not extend to photocopying or producing copies in any form what so ever for other than personal use of the person creating the copy or making electronic copies available for retrieval by others in any form without prior permission in writing from an officer of Integrated Control Technology Except where over ridden by the specific permission above the standard copyright notice from Integrated Control Technology applies to the electronic version 1 Neither this manual nor any part may be reproduced or transmitted in any form or by any means electronic or mechanical including photocopying microfilming and recording or by any information storage or retrieval system without prio
6. result the specifications may change without notice It is recommended that you always consult www integratedcontroltechnology com for the latest documentation and product information Power Supply DC Input Voltage 12VDC 8 30VDC Operating Current 20mA Typical Sensors Temperature 40 C to 120 C 0 1 C 40 F to 250 F 0 2 F Humidity 0 to 100 3 0 Communication RS 485 Non Isolated Module Network Outputs PGM Outputs 2 100mA Max Relay Outputs LED Outputs 2 Configurable LED Indicators Inputs Trouble Zone 8 Dimensions Plastic 75mm x 118mm X 19mm 3 x 4 6 x 0 7 Temperature Operating 5 55 Celsius 41 131 Fahrenheit Humidity 0 85 Non Condensing Storage 10 85 Celsius 14 185 Fahrenheit PRT ATH1 Sensor Installation Manual Page 5 Prot g System Management Suite The Prot g System Management Suite is a Windows 2000 XP Professional Integrated Access Control and Alarm Management system designed for any configuration from single site single controller applications up to the global multi national corporations using multiple site multiple controller installations The Prot g System Management Suite application is ideal for the configuration and management of your Prot g installation Special built in features and the quick start kit will get your system up and running in minutes Prot g Modules The Prot g System can be expanded to accommodate large numbers
7. 1 02 67 Main Menu Temperature Humidity Dew Point Exit Selection gt 4 Select the a to modify the Temperature alarm b to modify the Humidity alarm and c to modify the Dew Point Alarm 5 Eachofthe three sensor inputs are configured independently as shown in the figure below Table 2 details each of the parameters that are programmed for each sensor PRT ATH1 Prot g Temperature and Humidity Sensor c Integrated Control Technology 2008 Version 1 02 67 Temperature Menu Alarm Above Set Point 20 Hysteresis 2 Output Relay 1 LED 1 Invert No x TEXTE Selection gt PRT ATH1 Sensor Installation Manual Page 19 Mode Alarm Above Alarm Below Set Point Output Page 20 T 40 to 100 H 0 100 DP 40 to 100 0 255 Relay 1 Relay 2 LED 1 LED 2 Relay 1 LED 1 Relay 2 LED 2 The mode determines when the output will be activated compared to the set point In this mode the output s will be activated when the set point is exceeded See the diagram below for more details ALARM ABOVE Set Point 20 Hysteresis 2 In alarm below mode the output s are activated when the temperature is below the set point See the diagram below for more details ALARM BELOW Set Point 4 Hysteresis 6 When operating in Alarm Above mode when the temperature exceeds this value the output s will be turned on When operating in Alarm Below mode when the t
8. andalone Mode uses Serial Port Settings PRT ATH1 Sensor Installation Manual Page 17 Standalone Mode uses DIP Switch ni Settings Table 3 Standalone DIP Switch Settings Programming Output Alarms For more complex systems that where the require setup can not be achieved using the DI P switch programming show above the Prot g Temperature and Humidity Sensor can be programmed using a serial connection from a PC Computer Both the Temperature and Humidity inputs have independently configurable set points that can activate the relay outputs when they are exceeded These are configured using Hyper Terminal or TeraTerm on a PC Computer 1 Using a RS 232 to RS 485 converter like the ACC 485 from Integrated Control Technology connect the Temperature and Humidity Sensor to a Serial Port 12V ACC 485 RS232 to RS485 Converter OV Figure 7 Wiring Connection for Serial Programming 2 Open Hyper Terminal and make a connection using a baud rate of 38400 8 data bits no parity bit 1 stop bit and no flow control 38400 8 n 1 3 Press ESC and the following screen will appear Because Dew Point measured in C is a function of Temperature and Humidity the Prot g Temperature and Humidity Sensor can also calculate this value This may be useful in some installations Page 18 PRT ATH1 Sensor Installation Manual PRI ATH1 Prot g Temperature and Humidity Sensor c Integrated Control Technology 2008 Version
9. ature and Humidity Sensor can also operate separate of the Prot g System and can activate the 4 onboard outputs based on internal settings or output the current temperature and humidity on a 0 10V analog output Configuring Standalone Mode By default the Prot g Temperature and Humidity Sensor will not operate in Standalone mode With the power off set DIP switch 8 on as shown in Figure 6 below AU Figure 6 Configuring Standalone Mode mi CI When the Temperature and Humidity Sensor is next turned on it will operate in a standalone mode In this mode the Power LED will not flash on start up but all 3 LEDs will activate for 5 seconds to confirm it is operating in the standalone mode DIP Switch Programming The Temperature and Humidity Sensor can be programmed from either the Serial interface or for simple applications the programming can be achieved using the DIP switch Temperature Setting setup Output Relay 1 LED 1 Table 1 Fixed Temperature Settings in DIP Switch Mode Setup Output Relay 2 LED 2 5 Hysteresis 5 Table 2 Fixed Humidity Settings in DIP Switch Mode Page 16 PRT ATH1 Sensor Installation Manual Switch Variable Action 1 2 Temperature Set Point 22 C 4 C 10 C 26 C 3 4 Humidity Set Point 60 40 50 70 Alarm Above Alarm Below None Invert Outputs Invert Alarm Mode 7 8 Standalone Mode Prot g Mode cs eee eee A ee H Tir St
10. conditions are exceeded to enable a prompt response to any problems Flexible module network architecture allows large numbers of modules to be connected to the RS 485 Module Network Up to 250 modules can be connected to the Prot g System in any combination to the network up to a distance of 900M 3000ft Communication beyond this distance requires the use of a RS 485 Module Network Repeater PRT MNR4 or the Slave Communication port of the PRT RDI 2 Intelligent Reader Expander Securing a network prevents the removal substitution or addition of modules to the module network effectively preventing any tampering with the system Features 40 C to 120 C Temperature Sensor 0 1 C 0 to 100 Humidity Sensor 3 0 Isolated Secure Encrypted RS 485 Module Communications Channel differentiate send on event per channel Channel deviation trigger level 2 Low Current PGM Outputs 2 Display LED PGM Outputs 8 30VDC Input Power Supply Online and Remote upgradeable firmware Page 4 PRT ATH1 Sensor Installation Manual Temperature and Humidity Sensor Specifications PRT ATH1 Prot g Temperature and Humidity Sensor Failure to adhere to the specifications will result in any warranty or guarantee that was provided becoming null and void The following specifications are important and vital to the correct operation of the Integrated Control Technology continually strives to increase the performance of its products and as a
11. eeh fe ale e 16 Configuring Standalone lee EEN 16 BI engl Geelen Ui rana 16 Programi ning OUtPUE ARMS iS AAA A aad 18 Ordering Information 22 Page 2 PRT ATH1 Sensor Installation Manual PROG UE COS a ti cd de eins e al e 22 Warranty CRW 23 Introduction A A usa neu O E sns lt aden wettest ane a tae Alea ck bene 23 PRT ATH1 Sensor Installation Manual Page 3 PROT G SYSTEM Introduction The Prot g System is a powerful integrated alarm and access control management system designed to provide integration with building automation apartment complex control and HVAC in one flexible package Communicating through a proprietary high speed protocol across an encrypted RS 485 network using modular based hardware design system installers have the flexibility to accommodate any installation from small or large residential or commercial Temperature and Humidity Sensor The PRT ATH1 Prot g Temperature and Humidity Sensor extends the Prot g System by providing Temperature Humidity and Dew Point readings that can be used for building automation and control or environmental alarms The Prot g Temperature and Humidity Sensor can monitor the environmental conditions of highly critical server rooms this data can be used to control the air conditioning in the room to maintain regulated conditions Prot g can also use the data to trigger reportable alarms when normal operating
12. emperature drops below this value the output s will be turned on When operating in Alarm Above when the temperature drops below the Set point minus the hysteresis the output s will be turned off When operating in Alarm Below mode when the temperature exceeds the Set point plus the hysteresis the output s will be turned off Select the output that is activated when the sensor goes into an alarm condition by pressing d until the output required is displayed PRT ATH1 Sensor Installation Manual Invert The state of the output s can be inverted when this option is set to Yes Press e to select the required option When the invert option is selected the output will be turned off when the sensor is in alarm Table 2 Standalone Programming Options 6 Once the programming is complete press x to return to the main menu and program the other sensors PRT ATH1 Sensor Installation Manual Page 21 ORDERING INFORMATION Product Codes Please use the following product codes when placing an order for the Prot g Temperature and Humidity Sensor PRT ATH1 PCB Prot g Temperature and Humidity Sensor Includes Accessory Bag Manuals and literature are avallable at the Integrated Control Technology website in the documentation section If you require manuals on CD ROM please request a literature CD ROM from the website Page 22 PRT ATH1 Sensor Installation Manual WARRANTY Introd
13. includes extensive diagnostic indicators that can aid the installer in diagnostic faults and conditions In some cases an indicator may have multiple meanings depending on the status indicator display at the time Power Indicator The Power Indicator is located at the top right and indicates the status of the Prot g Temperature and Humidity Sensor If the Prot g Temperature and Humidity Sensor is operating normally the LED will indicate this by FLASHI NG at 1 second intervals FLASHING rapidly at 250ms intervals indicates that the Temperature and Humidity Sensor is attempting to register with the system controller or that communication has failed and the Temperature and Humidity Sensor is retrying the request Figure 4 Power LED Location If the power LED is not flashing at a regular interval there is a fault condition refer to Error Code I ndication on page 14 below PRT ATH1 Sensor Installation Manual Page 13 ERROR CODE INDICATION Introduction When the Temperature and Humidity Sensor attempts to register or communicate with the system controller a registration error can be generated indicating that it was not successful Error Code Display The following table is only valid if the FAULT indicator is ON and the STATUS indicator is FLASHING If the fault indicator is FLASHING the Temperature and Humidity Sensor requires a firmware update or is currently in firmware update mode The status indicator will FLASH wi
14. mperature and Humidity Sensor Temperature and Humidity Sensor 10 Way Wiring Loom Wire Loom Colour Coding The Prot g Temperature and Humidity Sensor is supplied with a wire loom attachment and are connected using a keyed 10 position snap lock connector The 10 way wiring loom connection uses the following colour coding Page 8 BLUE WHITE ORANGE 0 E AJ V m m BROWN GREEN f YELLOW HL vi NO RLY1 COM RLY2 NO RLY2 COM TEMP 0 10V HUMI 0 10V Figure 1 Wiring Loom Colour Coding PRT ATH1 Sensor Installation Manual Encrypted Module Network The Prot g Temperature and Humidity Sensor incorporate encrypted RS 485 communications technology Connection of the communications should be performed according to the diagram shown in Figure 2 It is important that the N Network Communications Power be supplied from an independent battery backed power supply unit or a networked module capable of supplying the required voltage to all of the network powered devices on the RS485 network Always connect the modules NA and NB terminals to the NA and NB terminals of the communication network The N and N must go to a 12V power supply source as shown in the following diagram and connected at ONLY one 12V power source MODULE OR CONTROLLER SUPPLYING POWER TO NETWORKED DEVICES NEXT MODULES ON NETWORK N N NA NB gE deen ELI Figure 2 Network Power Supplied By Network Module
15. n The addressing of the Prot g Temperature and Humidity Sensor allows up to 128 devices to be connected to the Prot g System Controller The CONFIG configuration DIP switch allows each Temperature and Humidity Sensor to have a unique address Address Configuration The switch positions 1 to 7 select the device address from 1 to 128 When setting an address the Temperature and Humidity Sensor must be powered down and restarted for the new address to take affect When changing the address the Temperature and Humidity Sensor will automatically default the internal configuration and require a network update See the Prot g System reference manual for information on performing a module update ADDRESS 1 ADDRESS 2 ADDRESS 4 ADDRESS 8 ADDRESS 16 ADDRESS 32 ADDRESS 64 ADDRESS 128 Figure 13 Temperature and Humidity Sensor CONFIG Switch Functions The device address is determined by adding the value of each switch that is selected in the ON position and then adding 1 to this value In the example below the address 024 results in 16 4 2 1 1 024 Setting all address switches to OFF results in the default address of 001 ADDRESS 1 ADDRESS 2 ADDRESS 4 ADDRESS 8 ADDRESS 16 ADDRESS 32 ADDRESS 64 ADDRESS 128 Figure 14 Temperature and Humidity Sensor Configured For Address 024 Page 12 PRT ATH1 Sensor Installation Manual STATUS INDI CATION Introduction The Prot g Temperature and Humidity Sensor
16. of modules using the encrypted RS 485 network Modules that are currently available are listed below Visit the Integrated Control Technology website www integratedcontroltechnology com for the latest Prot g module and product information Alphanumeric LCD User Interface PRT KLCD The Prot g LCD User Interface Keypad is the interface between the user and the Prot g System All programming and end user functions can be performed using the LCD Keypad The 32 character alphanumeric display uses easy to read messages and menus to guide users through the systems operation The LCD Keypad also adds two zones four zones in multiple zone configuration and one PGM to the Prot g System 16 Zone Expansion Module PRT ZX16 Extends the Prot g System with the addition of 16 Zones and 4 Programmable Outputs PGM s Operates from 16VAC with onboard power supply and isolated communication interface 16 Zone Standard Expansion Module PRT ZXS16 Extends the Prot g System with the addition of 16 Zones and 1 Programmable Output PGM Operates from 12VDC network connection No onboard power supply 16 PGM Expansion Module PRT PX16 Extends the Prot g System with the addition of 16 Programmable Outputs PGM s 16 7A FORM C Relays The PRT PX16 can be connected to the slave communications interface of the PRT RDI2 2 Reader Expansion Module for FULL monitored elevator control with the addition of the PRT DRI Destination Reporting Interface O
17. ptical Input Module 16 PGM Standard Expansion Module PRT PXS16 Extends the Prot g System with the addition of 16 Programmable Outputs PGM s 16 20mA Open Collector Outputs Operates from 12VDC network connection No onboard power supply Ethernet Intelligent 2 Reader Expansion Module PRT RDE2 Communicating over a high speed interface using 10 100 Ethernet interface connection for two card readers either Wiegand or Magnetic Stripe formats Four Wiegand Card Readers can be connected in Multiple Card mode The 2 Reader Ethernet Expansion Module also adds 8 Zones and 8 Outputs to the Prot g System Some of the outputs on the PRT RDE2 have specific access control functions and can be used as zones in the Prot g alarm processing functions Intelligent 2 Reader Expansion Module PRT RDI 2 Page 6 PRT ATH1 Sensor Installation Manual Adds the interface connection for two card readers either Wiegand or Magnetic Stripe formats Four Wiegand Card Readers can be connected in Multiple Card mode The 2 Reader Expansion Modules also adds 8 Zones and 8 Outputs to the Prot g System Some of the outputs on the PRT RDI2 have specific access control functions and can be used as zones in the Prot g alarm processing functions Mini 2 Reader Expansion Module PRT RDM2 Adds the interface connection for two card readers either Wiegand or Magnetic Stripe formats Four Wiegand Card Readers can be connected in Multiple Card mode The 2 Reader
18. r permission in writing from the publisher 2 The consent of Integrated Control Technology does not extend to copying for general distribution for promotion for creating new works or for resale Specific permission must be obtained in writing from an officer of Integrated Control Technology for such copying PRT ATH1 Sensor Installation Manual Page 1 CONTENTS e UC Ce Protege System a Neige el tegen EE 4 Temperature and Humidity Sensor cnn cnn rn 4 FOIOS ri ia Laan ere N enna nana 4 Temperature and Humidity Sensor Gpecfications cece cc rr 5 Prot g System Management Suite nale ito 6 Protege Modules eras iaa alare ona 6 DESEN 3 Package colliei EE 8 vire Loom ColourEodingLisb lira rA 8 Encrypted Module Network 9 Zone LEE LO INLFOOUCHO Nail 10 Poupie Zone Ka e E ns en cw mee ea 10 Programmable Outputs CRW 11 IATOOU CON iS SS i 11 POM OUMU LETONIA ta en apap a enone 11 ED Oytputs POM 2 inte 4 ulyuy uu u ida 11 Configuration Switch NENA AAA nn 12 ATO T C Onu nais RR iodo 12 Adaress e eiert Lelleg e Te DEE uyu uku aksa a suka aaa aap aaa ia 12 Status Indication suwmumummumunmunnunananananmananmana 13 tro ALCAN a a isis 13 POWer LINGICAEOR EE 13 Error Code Indication NENA AAA Anna An 14 Wake gore Sled oliva 14 Emor Code E e VE 14 Analog Output 0 10V CRW 15 INTO UCM Ss 15 WII ea ea 15 Standalone Configuration CRW 16 Kee
19. th the error code number The error code number is shown with a 250ms ON and OFF period duty cycle with a delay of 1 5 seconds between each display cycle FLASH ERROR DESCRIPTION Unknown Error Code The error code returned by the system controller could not be understood by the Analog Expander Contact Integrated Control Technology Firmware Version The firmware version on the Temperature and Humidity Sensor is not compatible with the system controller To clear this error update the module using the module update application Address Too High The Temperature and Humidity Sensor address is above the maximum number of Analog Expanders available on the system controller To clear this error change the address to one within the range set on the system controller restart the Temperature and Humidity Sensor by disconnecting the power Address In Use The Address is already in use by another Analog Expander To clear this error set the address to one that is currently not occupied by a Analog Expander Use the view network status command to list the attached devices or the network update command to refresh the registered device list Controller Secured Registration Not Allowed Controller is not accepting any module registrations To allow module registrations use the network secure command to change the secure setting to not secured Serial Number Fault The serial number in the device is not valid Return the unit to the distributor
20. uction The Prot g Temperature and Humidity Sensor are covered under the Integrated Control Technology standard terms and warranty agreement This document can be downloaded from the Integrated Control Technology web site or obtained by return fax Contact Integrated Control Technology welcomes all feedback Please visit our website or use the information below Integrated Control Technology P O Box 302 340 North Harbour Post Centre Auckland New Zealand Phone 64 9 476 7124 Fax 64 9 476 7128 www integratedcontroltechnology com PRT ATH1 Sensor Installation Manual Unit C 6 Ascension Place Mairangi Bay Auckland New Zealand Page 23 Page 24 PRT ATH1 Sensor Installation Manual PRT ATH1 Sensor Installation Manual Page 25 ict Unit C 6 Ascension Place Mairangi Bay P O Box 302 340 North Harbour Auckland New Zealand Phone 64 9 476 7124 Fax 64 9 476 7128 www integratedcontroltechnology com

Download Pdf Manuals

image

Related Search

Related Contents

dryer user instructions instrucciones para el usuario de la secadora  Electro-Voice PL5 User's Manual  ASUS M M11BB-NL001S PC  Philips GC3390 Steam iron  High Contrast Ratio Enhanced Colour Wheel Design I  COMMON RAIL SYSTEM (CRS) SERVICE MANUAL: General Edition  Anleitung Raumtemperaturregler    取扱説明書  QuickCam® Orbit™  