Home

5000 Series 8 zone installation manual

image

Contents

1. or all zones be assigned to control the Auxiliary Output While any of these zone s are unsecured the Auxiliary output will be turned on Thus all zones must be secured for the Auxiliary output to be turned off By using the keypad it is possible to over ride the zones controlling the output If the output is on press 9E and it will turn off Press 9E again and it will turn on Enter 9 END You cannot change the Auxiliary output while in the Program Memory or Exclude mode 15 TESTING AND TROUBLE SHOOTING To ensure the integrity of your security system it should be checked on a regular basis YOU can carry out any of the tests outlined below or engage a qualified Technician from a licensed Alarm Company to carry out a more technical assessment according to Australian Standards AS 2201 1 9 2 MAINTENANCE extract AS 2201 1 9 2 1 Routine maintenance 9 2 1 1 General Routine maintenance visits to the alarmed premises shall be made by an authorised representative of an alarm company at a minimum rate of twice per year with no more than 7 months between visits Remember If your system is connected to a Central Monitoring station please advise them prior to carrying out any of these tests SIREN TEST Enter 2 E Siren will sound To reset siren Enter CO
2. P 2 E 9765 E 9765 E 3 To CANCEL code 2 then enter P 2 E 09765 E 09765 E CSIR SORA SCOR COO CSCO OA CSO CSO A CORI CO OR CSR ACCOR GI SCOR OR COR CSCO OI CSCO I SCO OR CSO I SCOR ICO GR ICO ACCOR CSRS The Entry Delay Time is the time the Control Panel gives you to disarm the Panel after a delay zone is unsecured For maximum security the Entry Delay Time should be as short as possible The Entry Delay Time can be set to a minimum of 1 second up to a maximum of 99 seconds To VIEW the Entry Delay Time ENTER PROG 5 END 1 To view the current Entry Delay Time enter PSE 2 The value programmed will be displayed via the zone 1 8 battery 9 and mains 0 lights The display of the current value must be complete before a new value can be entered 3 To change the current value to say 10 seconds enter 10E Zone light will flash on for 1 second followed by the MAINS light 0 to indicate the new value To CHANGE the Entry Delay Time ENTER VALUE END EXIT DELAY TIME Sekoakakakokokokokokokokokokokokokakakakakokokokokokokokokokokakakakakakakokokokokokokokokokakakakakakakakokokokokokokokokokakakakakakokokokokokokokokokokokakakakakokokokokokokokokokokokokakakakakokokokok The Exit Delay Time is the time the Control Panel gives you to secure and depart the premises after the Panel is Armed The Exit Delay Time should be just long enough to allow
3. As explained elsewhere in this manual these zone lights are used to indicate other information in the Memory Exclude Monitor Installation and Client Program modes OR I SCOR A ICO ER CSO A CORI COO CSR ACCOR okk The program Mode is entered whenever programming options are to be changed IMPORTANT The Control Panel will automatically exit the Program Mode if no keys are pressed within a two minute period HOW TO PROGRAM TO ENTER PROGRAM MODE PRESS PROG MASTER CODE END The Program light will be illuminated EDGR SCSI CSIR CSO COR CSR CSCO OA CSR CSO A CORI COR CSR A SCOR COCOA ACCOR ISCO OR COR ACSC OI Programming the NESS 5000 SERIES 8 zone Control Panel is achieved via the keypad on the front Every time a button is pressed the panel responds with a very brief beep in acknowledgment Each button is used for three purposes a to enter a number eg 1 2 3 b to select a programming option to select a command eg ARM Note that programming options can only be selected whilst in PROGRAM mode Programming of options can be carried out in any order All Programming follows this pattern Select your option and VIEW the current value PROG OPTION END The PROG or P button is used in the selection of PROGRAM mode and thereafter in the selection of the option to be programmed
4. SETTING ZONES TO DELAY P1E LLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLDLLLLLLLDLLLLLLLLLLLLLLLLLLLLLDLLLLDLLLLLLL After expiry of the Exit Time a delay zone To set say zone 2 to be delayed enter becoming unsecured will cause an alarm at the end of Entry Time t the Panel has not been PIE 2E Disarmed The only zones that should be programmed for delay are point of entry zones DEFAULT ZONE 1 DELAY zone light 1 on To VIEW Delay option ENTER To ADD Delay zone s ENTER PROG 1 END ZONE NUMBER END SETTING ZONES TO HANDOVER P 2 E gt le s eie sk e sk oe ok oe o sese sese sese sese sie oF eee esee oR ok E oe oe oe fe k kkk kk kkk kkk Handover zone is a combination of a Delay Handover should be selected for all zones on zone and an Instant zone After Arming the the entry exit path that require an entry exit Handover zone is delayed to enable time to exit time Handover should not be selected for without triggering the alarm It then actual point of entry zones eg front or back automatically reverts to instant operation to door provide greater security for detectors on the delay path To set say zone 3 and zone 8 to be handover enter If a normal entry is first made through a Delay zone then all Handover zones will revert to P2E 3E 8E delayed operation again to enable time to enter and Disarm the Panel withou
5. others Disarmed The Control Panel housing and the metal covers over external sirens are protected by TAMPER switches to detect someone attempting to disable the security system Activation of these switches will cause an instant TAMPER ALARM If a detector becomes faulty you can EXCLUDE the associated zone so that it is totally ignored and cannot generate an alarm INCLUDING the zone will enable it to generate an alarm again The Control Panel is fitted with a STAND BY BATTERY to ensure your security system continues to operate it the MAINS POWER is interrupted This battery is checked every hour and whenever you Arm the Panel Whenever an alarm occurs it may be silenced by entering an ACCESS CODE otherwise it will reset at the end of RESET TIME All alarms are stored in MEMORY and may be retrieved at any time by entering MEMORY MODE Sekokakakokokokokokokokokokokokokakakakokokokokokokokokokokokakakakakakokokokokokokokokokokakakakakakokokokokokokokokokokakakakakakokokokokokokokokokokokakakakakokokokokokokokokokokakakakakakokokokok The 5000 SERIES 8 Zone Control Panel is one pan of an integrated range of equipment 4 Access codes Monitor mode partial Arming Simple operation allows selected zones to be Armed while others are ignored Ideal for monitoring doors and windows while you are safe inside Additional security is provided by the various programming options Arm via a code Exclude zones via a code
6. zone 2 light off To CHANGE Keypad option ENTER 2 END AUTO EXCLUSION OF ZONES P2IE eteeketteletokeletoetelotokeletlelokeletotokeletotoeleloloeleloleleletoleleletoleleletolelelotetelelotolelelotolelelotoleletotoleletol This selection is indicated by the zone 3 light On Arming all unsecured zones can be treated in the following ways a Automatically be Excluded at the end of exit time zone 3 light off NOTE any Auto Excluded zone will be Included when the zone becomes secured and will generate an alarm if it becomes unsecured b Cause the panel to ALARM at the end of EXIT TIME zone 3 light on To VIEW Auto exclusion option ENTER PROG 21 END Page 15 To view the option enter P 21 Then to change the option enter 3 DEFAULT AUTOMATIC EXCLUSION zone 3 light off To CHANGE Auto exclusion ENTER 3 END REA VE 5000 Series Dialler ENTRY WARNING BEEPS P21E 4 E b This selection is indicated by the zone 4 light To VIEW the option enter P 21 E Whenever a delay zone is unsecured and Entry Then to CHANGE the option enter 4 E Time begins the system s beeper may a Beep at one second intervals for entry time zone 4 light off b Remain silent for the duration of entry time DEFAULT BEEPS AT ONE SECOND zone 4 light On INTERVALS zone 4 light off To VIEW Entry Warning Option ENTER To CHANGE Entry Warning option ENTER PROG 21 END 4 END This selection is
7. Dialler 1 to send 8 alarm reports plus 15 Client 1 D s one client account number and then use Dialler 2 to send another 8 alarm reports via a second account number INSTALLATION The 5000 SERIES Dialler board is designed to plug into the 8 Zone Control Panel It cannot be used in conjunction with the 4 Zone Control Panel To install the Dialler remove the Control Panel board from the housing clip the Dialler into the third or fourth slot connect the 13 way ribbon cable between the dialler and the control panel Then re install the Control Panel board If a Zone Expander is being installed also the Dialler must be fitted to the third slot TESTING To test the Dialler after installation exit from Program mode Arm the Control Panel create one or more alarms and then check what data was received by the Monitoring Station The LINE EXPAND indicator will turn on when the Dialler seizes the line At the end of the call it will turn off if the call was successful or flash rapidly if the Kiss off tone was not received A line fault will always result in the LINE EXPAND indicator flashing slowly until the fault is corrected INPUTS The telephone line plugs into the socket in the top left hand corner of the Dialler board NOTE The 5000 SERIES Dialler uses a Mode 5 connection and not Mode 3 However the Mode 5 connection will work into any existing Mode 3 socket Page 2 REA LZ 5000 Series Dialler OUTPUTS Four plug in screw
8. Indication of zones that are unsecured when arming Special interface to allow the connection of NESS Remote Keypads which offer full programmability and operation of the panel from a remote location Unique keyswitch input to allow simple remote operation of the Control Panel Easy connection of the 5000 SERIES Satellite Siren to greatly increase the security of your system The Control Panel housing has 4 separate tamper systems Keypad Wall Lid and Panel impact The panel impact tamper system protects against control panel intrusion by heavy impacts These tampers are protected 24 hours a day Different siren sound for 24 hour alarms Outputs are separately fused Unique dynamic input system which will detect any component failure of the zone input circuitry and generates an alarm ALL inputs and outputs are heavily protected against lightning and high voltage power supply transients An earth terminal is provided for extra protection TRUE DYNAMIC BATTERY TEST under load every hour and when Arming the panel Your system will warn you in advance of possible battery failure Works irrespective of whether the mains is on or off A large 6 5 A H backup battery and a 1 4 amp plug pack transformer provides more than sufficient current to maintain the operation and security of the entire system even under full alarm conditions The mains input is constantly monitored A warning is given when the mains is
9. New Zealand style Decadic pulses Options 5 and 6 may be chosen in addition to the other options 7 Only transmit in Ademco Extended Format TIME to WAIT for ACKNOWLEDGE TONE BEFORE REDIAL P38E time E This option defaults to 15 seconds and should rarely need to be changed It may be set from 10 to 25 seconds MAXIMUM NUMBER of DIAL OUT ATTEMPTS P39E number E This option defaults to 6 dial attempts the maximum allowed by Telecom Australia and should rarely need to be changed It may be set from 1 to 6 attempts OUTPUT CONTROL and INDICATION OPTIONS P40E option E l Trigger the siren strobe for the Reset time on a Line Fault 2 Trigger siren strobe for Reset time Kiss off Note triggering is via the Keyswitch Panic input of the Panel 3 When the Kiss off tone is received beep the siren 3 times 4 When the Kiss off is received turn the strobe on for 3 seconds Turn the LINE EXPAND indicator on during a call page 2 6 Allow the client to program the Medical Alarm P53E Allow the client to program the Extra number P33E 8 Trigger the siren strobe for the reset time on a line fault only when armed Must be used with function 1 ie With 1 and 8 lights on line fault will cause an alarm only when armed None one or all of the above options may be chosen and the default is option 5 Page 7 REA LZ 5000 Series Dialler AUXILIARY OUTPUT DRIVE P41E option E 0 No Auxiliary drive l Turn Outpu
10. SCC A A A A A aka For ease of installation it is recommended that the following procedure be followed 1 Remove the cardboard terminal designation card 2 CAREFULLY remove the keypad ribbon from the circuit board and unclip the lid 3 Remove the rear tamper and battery terminal blocks from the circuit board Unclip and remove the circuit board by pushing the retainer clips up located just below the battery 4 Remove the battery 5 Mount the polycarbonate rear housing Wire the terminal blocks as per wiring instructions shown on the terminal designation card and as explained in this section 6 Replace Battery Clip in circuit board Plug in the terminal blocks except those for the Satellite and Battery 7 Replace lid and plug in keypad ribbon cable to the connector 8 Replace the Terminal Designation Card 9 Perform the Power up check 10 Program Installation Options 11 Carry out Test Procedure 12 Perform Check Before Entering Client Program Mode INPUTS k The Control Panel contains 10 separate monitored inputs 8 x fully programmable zones 1 x Tamper 1 x Panic Keyswitch inputs Each zone must be terminated with a 2200 ohm 2K2 End of Line resistor The Tamper input is wired in an identical manner to the zones Thus it must be fitted with a 2K2 end of line resistor If a Satellite siren is being used then the 2K2 resistor MUST BE substituted with the 820 ohm resistor supplied with the satel
11. from Monitor mode To CHANGE zones to be monitored ENTER ZONE NUMBER END EDGR A CSR CSO SCOR CSR CSCO OI ICS OR CSUR A CORI CO HR CSOSA CORI OR I SCOR OR CORIO I COO CSO CSO OR SCO GR CSO I SCOR COG CSO ACCOR OR CSRS The 8 Zone Control Panel provides an Auxiliary output which can be turned on and off by ANY selected zones or via the keypad This output can be used for a variety of applications Talk to your security installation company about your specific requirements A zone programmed for Auxiliary will cause the Auxiliary Output to turn on when it becomes unsecured regardless of whether the Panel is Armed or Disarmed To remove a zone from the selection re enter the zone number of the zone to be removed To VIEW Auxiliary Zones ENTER PROG 9 END PROGRAMMING SUMMARY To program say zones 4 6 and 8 to control the Auxiliary Output enter P9E 4E 6E 8E As each zone is programmed the corresponding zone light is illuminated if it was previously off If the zone light was previously on it will be extinguished thus de selecting that zone The output can also be turned on or off toggled by pressing 9 E while Disarmed or in Monitor mode To CHANGE Auxiliary Zone s ENTER ZONE NUMBER END CSR SOR I SCO OR CSR I SCOR A CSR CSO A CORI CO OR CSR ACCOR COCOA ACCOR I SCOR OR CORR ISCO I CSCO OI SCO OR CSO I SCOR D
12. option ENTER PROG 20 END Page 14 once when the zone becomes unsecured but will not re alarm if the zone remains unsecured However it the zone re secures then at a later time unsecures the Panel will alarm again To set say zone 3 and 6 to lockout enter P20E 3E 6E zone light 3 amp 6 on To return zone 6 to Conditional lockout enter 6E again zone light 6 off DEFAULT ALL ZONES ARE CONDITIONAL LOCKOUT all zone lights off To CHANGE Lockout option ENTER ZONE NUMBER END AERA KEYSWITCH OPERATION P 21E1E This selection is indicated by the zone 1 light The keyswitch input can operate in two ways a Restricted operation for higher security A Delay one must be activated prior to operating the Keyswitch otherwise an alarm will occur zone 1 light off b At all times zone 1 light on To VIEW keyswitch option ENTER PROG 21 END 5000 Series Dialler To VIEW the option enter P 21 E Then to CHANGE the option enter 1 E DEFAULT RESTRICTED OPERATION zone I light off To CHANGE keyswitch option ENTER 1 END This selection is indicated by the zone 2 light There are two methods of Arming via a key pad a Single Digit Arming OE zone 2 light off B Arming via ACCESS CODE 0 code E zone 2 light on To VIEW Keypad Arming option ENTER PROG 21 END To VIEW the option enter P 21 E Then to CHANGE the option enter 2 E DEFAULT SINGLE DIGIT ARMING
13. protect the Central Station information If this code has not been programmed then all of the options are available to any installer for review and change If the Installer Access Code has been programmed then only the P30E and P98E options are available for use without the code To use any of the remaining options you must first enter the code ie in Installer Program mode press P Code E If the code is valid the Dialler will respond with 3 beeps and the LINE EXPAND indicator will turn on This indicator will remain on until the use of a programming option which does not belong to the Dialler Each time you enter the Installer Program mode you must use the Installer Access Code as above During programming numeric values are displayed via the 8 ZONE indicators the 9 BATTERY and the 0 MAINS indicators For your convenience single digit values remain displayed while multi digit values are flashed Out During the programming of the telephone numbers it is occasionally necessary to enter a special PAUSE digit To do so press and hold the button for at least second For example to programme a telephone number commencing with 0 PAUSE 4 press 0 long E 4 etc During the telephone number display the PAUSE digit is represented by the TAMPER SATELLITE indicator each PAUSE 2 5 seconds The programming data for the Dialler is stored in a special memory on Exit from the Installation Programming mode Thus if data is
14. terminals on the right hand side of the Dialler provide the following outputs COMMON ve LISTEN output AUXILIARY Output of Dialler 12 volt Output Connect any speaker between the LISTEN and COMMON terminals to listen in to the telephone line when the Dialler is making a call This simple procedure can be of tremendous assistance during fault finding The Dialler s own AUXILIARY Output is an open collector Output capable of sinking 300mA Via the 13 way ribbon cable the Dialler drives the LINE EXPAND indicator on the Control Panel This Dialler output is available for connection to remote equipment at the LINE LED INPUT OUTPUT terminal on the Control Panel centre of right hand side The 13 Molex pins on the right hand side of the Dialler are only provided for test purposes during production EARTH For maximum protection against lightning it is strongly recommended that the earth lug of the Dialler should be used by connecting it to the Earth lug of the Control Panel In lightning prone areas Telecom will provide on request and free of charge lightning arrestors for additional protection of the telephone line Page 3 REZ VEZ 5000 Series Dialler PROGRAMMING NOTE Programming the Dialler is virtually identical to programming the Control Panel simply plug the Dialler in and use the Installation options on the following pages However for security reasons the Dialler contains an optional Installer Access Code to
15. the Dialler will respond again with the above beeps to indicate the new status of the Control Panel or the Auxiliary output If you do not hang up within the next 5 seconds the Dialler will provide a simple Status report of the zone s in alarm This report consists of a 3 digit Dialler Identification plus 1 digit to indicate the zone in alarm Thus if the Dialler Identification is 642 and zone 3 had alarmed then the report will be 6423 1e 6 beeps pause 4 beeps pause 2 beeps pause 3 beeps A second zone in alarm results in the Dialler ID being repeated ie the report would be 6423 followed by 6428 if both zones 3 and 8 had alarmed MEDICAL FIRE PANIC Pressing the buttons 3 E will send a Panic normally personal attack alarm If required this can be made to be silent for hold up applications Pressing the buttons 2 E can send a Separate alarm to indicate Fire An optional RADIO PANIC BUTTON is available Pressing the buttons 1 E can send a separate alarm to indicate a Medical panic Alternatively it can be arranged to automatically send a Medical alarm if the buttons are not pressed within a preset time For example if the time is 24 hours then an alarm will be sent if you do not press 1 E on the panel every 24 hours In this case pressing E twice within a 6 minute period will send an alarm immediately Programming the Dialler is virtually identical to programming the Control Panel with one exception During the prog
16. x 8 ohm Ohm speakers not including Satellite sirens since they have a separate siren driver circuit 1 5 A at 12 V open collector fused With battery 12 V 1 5 A fused Resetting Alarm Output 1 5 A at 12 V open collector fused 24 hour Alarm Output 100 mA at 12 V open collector current limited Monitor Alarm Output 100 mA at 12 V open collector current limited Auxiliary Output 50 mA at 5 V emitter follower current limited CONTROLS AND INDICATIONS KEY PAD k kkk k The keypad consists of 12 buttons or keys Each button of the keypad is used for three purposes a to enter a number eg 1 2 3 b to select a client programming option marked in blue eg CODE 1 c to select a command marked in white eg ARM AUDIBLE INDICATIONS EDGR ACSA SOR CSO CSR CSO A CORI CO OR ICSI SCOR GR COCOA ACCOR ISCO OR COR ICSC ORI CORO ICO CSO I SCO GR CSO I SCHORR ICO CSCO OR CSRS Every time a button is pressed the Panel responds with a very brief beep In acknowledgment The beeper is also used to indicate whether the entry was valid or invalid For example whenever E is pressed all the buttons pressed before it are checked to see whether they are valid If they are valid the response will be 3 short beeps If they are invalid or incorrect the response will be 1 long beep and they will be ignored VISUAL INDICATIONS RDG CSIR SCSI OR CDG CSIR CSO SCOR ICS OR I SCOR I CSE CSO A COR
17. 12 V open collector fused 100 mA at 12 V open collector current limited 100 mA at 12 V open collector current limited 50 mA at 5 V emitter follower current limited Page 20 REA VE 5000 Series Dialler 5000 SERIES INSTALLATION PROGRAMMING SHEET X represents factory setting akko 1 2 3 4 5 6 7 8 INSTANT X X X X X X X PIE DELAY X P2E HANDOVER P3E SECOND DELAY P4E 24 HR AUDIBLE PSE 24 HR SILENT 1 2 3 4 5 6 7 8 PIOE 1 TRIGGER X X X X X X X X PILE 2 TRIGGER 12 19 VIBRATION 1 2 3 4 5 6 7 8 P20E LOCKOUT 1 2 3 4 9 6 7 8 P21E MISCELLANEOUS See page 15 to 17 P22E ALARM RESET TIME 10 Min Default In minutes X DEFAULT SETTING CLIENT PROGRAM SUMMARY See 5000 series user book for details TCHS AA CSR CSO I SCO A CSO ICAO COR CSR I SCOR CSR I SCOR OR COR COO CSCO SI ICO OR ICSC ICCA COR ICO ACCOR GI PIE MASTER CODE P2E USER CODE 2 P3E USER CODE 3 P4E USER CODE 4 PSE ENTRY DELAY TIME 20 Sec Default P6E EXIT DELAY TIME 60 Sec Default 7 1 4 P8E MONITOR ZONES POE AUX OUTPUT ZONES Page 21 5000 SERIES 8 ZONE INSTRUCTION MANUAL NESS SECURITY PRODUCTS 4 167 PROSPECT HIGHWAY SEVEN HILLS 2147 NSW AUSTRALIA SYDNEY Phone BRISBANE Phone MELBOURNE Phone PERTH Phone 02 8825 9222 07 3343 7744 03 9878 1022 08 9328 2511 Head Office To the best of our knowledge the information contained in this manual is correc
18. 9 Mains Fail 9 Test 9 9 Zone Excluded 9 Extended high Speed format allows 15 Client ID s to be sent via one Client Account Number The Dialler uses this feature and hence if Extended format is selected the 15 ID S are transmitted automatically Via Dialler 1 If Low Speed or High Speed formats are being used then it is not possible to transmit any Client I D s at this stage Page 11 INEZ INSTAL LATION PROGRAMMING OPTIONS SUMMARY Default value none code code 98 P3IE telephone 2 telephone telephone no E P34E numberE Alternate P35E optionE automatic P36E optionE automatic P37E optionE 15 seconds P38E time E 6 P39E number option 5 P4OE number none 41 optionE o seconds P42E time E 1 second P43E time E none P44E optionE 168 hours P45E time E o hours P46E time E 3 P47E number 5 P48E number 10 seconds P52E time seconds P53E time E none P57E channel E value E none P55E channel E value E none P59E channel E value E none P60E channel E value E none P61E channel E value E none P62E channel E value E none P63E channel E value E none P64E channel E value E none P65E channel E value E none P66E channel E value E none P67E channel E value E none P68E channel E value E none P69E channel E value E none P7OEchannel E
19. A CORR CSCO ACCOR GR ICO ACCOR I SCOR OR COO ACCOR I CORO ICSI CSO OI COO CSO I SCOR OR CORR ICO CSCO OR CSRS The PROG or P button is used to begin any programming sequence The END or E button is used in all cases to signify the end of the button sequence just pressed At other times the beeper will sound various warnings such as 10 beeps for a low battery When Arming the Panel 1 8 beeps will indicate that a zone is unsecured eg Zone 3 will be indicated by 3 long beeps A continuous tone on Arming indicates a Tamper or 24 Hour zone is unsecured During Entry time it indicates that an alarm has occurred The panel has 16 indicator lights surrounding the keypad Each light has three basic states to indicate function These are ON OFF FLASHING ARMED MONITOR ALARM MEMORY ZONE EXCLUDED PROGRAM BATTERY MAINS TAMPER SATELLITE LINE EXPAND ON The panel is Armed FLASHING The panel is in Monitor Mode ON Memory mode is selected FLASHING FAST An alarm has occurred ON The panel is in EXCLUDE mode FLASHING Zone s have been EXCLUDED OFF The panel is in normal operation mode FLASHING SLOW The panel is in installer program mode ON The panel battery is healthy ON The mains power is connected and turned on OFF The control panel and satellite siren tamper are secure and satellite siren battery is healthy OFF The dialler is inactive FLASHING SLOW The dialler senses a phone line fault or
20. ACK P 47 E number E This option defines the number of double rings needed to make the Dialler Call Back ie to make it send a Test Call immediately and hence before the time defined in P45E The number may be set from 1 to 13 and the default is 3 double rings Page 9 REA LZ 5000 Series Dialler DOUBLE RINGS NEEDED FOR AUTO ANSWER P 48 E number E This option defines the number of double rings needed to make the Dialler Auto Answer ie to answer an incoming call The number may be set from 1 to 15 The default is 3 double rings ABORT TIME DELAY for DELAYED DIALLING P 52 time E This Option defaults to 10 seconds but may be set from second to 120 minutes in the same manner as P42E To make use of the delay on an alarm the ABORT feature must be selected for that alarm MEDICAL ALARM TIME DELAY P 53 E time E This option defaults to 0 seconds which means that Medical Alarms from the panel 1 E are sent immediately if enabled in the Dialler P65E When the time is other than 0 then alarms are only sent by the Dialler if the Medical Alarms are NOT received within that time For example if the time is 24 hours then an alarm will be sent if the client does not press 1 E on the panel every 24 hours The time may be set from 1 to 250 which represents 0 1 to 250 hours In this situation an immediate alarm can still be sent by pressing E twice within a 6 minute period DIALLER 1 and 2 ALARM REPORTING P xx E channel E v
21. DE E SYSTEM CHECK ARM Panel 0E or O CODE E Wait for exit time to expire trigger any Instant zone and the siren should sound OR trigger a Delay zone wait for the entry time to expire and the siren should sound Reset the panel CODE E WALK TEST To check correct operation of all zones indicated by a 2 second siren and beeper warning NOTE Programming described in steps 14 are normal default values Therefore these steps may be bypassed if Monitor mode is not being used and has not been reprogrammed Enter Program mode P CODE E 2 Select Monitor mode 2 P7E 2E 3 Set all the zones to Monitor zones P 8E 1E 2E 3E 4E 5E 6E 7E 8E Select only those zones whose lights are not lit 4 Exit the client Program mode PE Ensure that all zones are secured and then 5 Select Monitor mode 8E Now move around your premises and unsecured each detector in turn The siren will operate for 2 seconds each time a detector is unsealed When you have tested all detectors check the control panel to ensure that all zone indicators are flashing ie all zones have been tested 6 EXIT FROM MONITOR MODE by disarming the panel 7 Don t forget to re program the Monitor mode type and Monitor zones back to their normal settings TROUBLE SHOOTING GUIDE 16 CSIR SOR I SCOR CSO CSCO OA ICO OR CSCO A CORI CO OR CSOSA SCOR COCOA ACCOR I SCOR OR COR ICSC OI COR OR CSCO OI SCO
22. ESCRIPTION OPTION Code 1 PIE code code E Code 2 P2E code E code E Code 3 P3E code E code E Code 4 P4E code E code E Entry Delay Time PSE time E Exit Delay Time P6E time E Monitor Type P7E type E Monitor Zones P6E zone E Aux Output Zones P9E zone E DEFAULT PROGRAMMED 20 secs 1 99 60 secs 1 99 2 1 4 All Zones 1 8 All Zones 1 8 10 OPERATION GENERAL INFORMATION SHR CSR CSUR SCOR CSR CSCO OA COR CSCO ACCOR I CHG ICSAC OI COR ACCOR I SCOR OR CORI SCOR OI COR ICO CSCO OI COO CSO I SCOR OR COR ICO CSCO OR CSRS This section describes the operation of a The Control Panel is normally operated via the typical Control Panel installation Keep in mind keypad on the front of the Panel or the optional that your installation may vary depending on Remote Keypad or the optional Intelligent the selected options and equipment Remote Keypad The operating instructions which follow will endeavour to cover the most common options If you have any doubts speak to your Installer OPERATING RULES SCSI ROSH CSIR SOR I SCO OR ICS OR CSCO A CS OR CSO A CORA ICO OR CSR ACCOR GR ICO ACCOR I SCOR OR CSR I CHRO CSCO CSO OI SCOR OR CSO I SCOR COR CSO ACCOR OR COGS The various operations that can be performed The optional keyswitch is operated by are indicated in white on the top of the relevant turning it clockwise until it stops buttons eg memory momentarily Generally t
23. Emitter follower switches positive 5 volts at 50 mA This output switches on whenever any programmed Auxiliary zone becomes unsecured It switches off when ALL Auxiliary zones are secured refer to Instruction manual for programming This output can also be toggled on or off via the Auxiliary Key 9 on the keypad The number of outputs can be expanded by 20 with the addition of 5000 SERIES Output Expander POWER e The Control Panel power terminals consist of AC INPUT TERMINALS For connection of the NESS plug pack or an AC source with the following characteristics 100mA load 17 to 23 VAC at 50 60 Hz 1 4A load 17 to 13 VAC at 50 60 Hz Page 7 12 VOLT OUTPUT TERMINALS D C regulated output for powering of detectors etc 13 8 Volts nominal fused via Fl 1 5 Amp BATTERY TERMINALS For connection of a rechargeable 12 volt sealed lead acid standby battery with a minimum capacity of 2 4Ah The charge current is limited to 450 mA maximum REA VE 5000 Series Dialler EAR THING o kkk EARTH TERMINALS For connection of the plug pack earth wire Thus the connection of an earth is strongly recommended Extensive testing in the field and rigorous testing in the laboratory has proven that a good earth dramatically improves the ability of the Control Panel s electronics to continue operating when its long cable runs aerials are subjected to induced high voltages ie lightning strikes POWE
24. G This Memory display may only be selected while the Panel is In the Disarmed Monitor or Armed modes for a primary alarm ie point of entry for a secondary alarm ie other zones entered by the intruder for a Panic or Code alarm for a Tamper alarm ie Siren Cover Satellite Siren etc for a low battery for a Mains failure for a Satellite low battery EXCLUDING ZONES 14 If a detector becomes faulty and cannot be secured when Arming the Panel then its zone may be excluded ie ignored by the system so that it does not generate false alarms Zones can only be excluded during the EXIT DELAY To enter the Exclude mode FIRST ARM THE PANEL and then press 7E 1 ARM the Panel 2 Press 7 END 3 Enter the zone s to EXCLUDED ZONE END ZONE END 4 To Exit and save Exclusion END All the lights will be turned off and then the Zone Excluded light will show a steady light You may now exclude zones To exclude say zones 4 and 8 after Arming TE SEE Zone lights 4 and 8 will turn on If you make a mistake enter the zones number again to remove it from your selection Zones which you exclude will be indicated by the relevant zone light Showing a steady light in the exclude mode Premises can achieve a higher level of security
25. It should be read in conjunction with the main 5000 SERIES Instruction Manual REGULAR CALLS To ensure the integrity of your security the Dialler will be installed to make regular calls to your Central Monitoring Station For industrial and commercial premises this will normally happen twice a day when the Control Panel is Disarmed and again when Armed Alternatively regular TEST calls can be sent from once every half hour to once a week The latter is often used for domestic premises Your security installer will advise you on the appropriate timing of the TEST calls for your premises LINE EXPAND INDICATOR The LINE EXPAND indicator is shared between the Dialler and the Zone Expander since each only uses it for a short time Normally the indicator will be off When the Dialler seizes the telephone line to make a call the indicator will turn on At the end of a successful call the indicator will turn off An unsuccessful call will leave the indicator flashing rapidly until the next call In certain high security applications the installer may inhibit the above operation of the LINE EXPAND indicator but not the fault indications described below Every few seconds the Dialler checks the telephone line for the existence of any faults eg the cutting of the telephone cable Whenever a fault is detected the LINE EXPAND indicator will flash slowly until the problem is corrected Should the LINE EXPAND indicator flash very rapidly
26. OR CSR kk This option causes a zone to trigger whenever To set say zone 5 zone 6 and zone 7 to it is unsecured for greater than 200 alarm on one trigger enter milliseconds PIOE 5E 6E 7E THIS IS THE NORMAL SELECTION FOR MOST DEVICES DEFAULT ALL ZONES ONE TRIGGER all zone lights on To VIEW one trigger option ENTER To ADD one Trigger zone s ENTER PROG 10 END ZONE NUMBER END SETTING ZONES TO TWO TRIGGER P 11 E LLLLLLLLLLLLLLLLLLLLLLLLLLLLLLDLLLLLLLLLLLLLLDLLLLDLLLDLLLLLLLLLLL LLL kkk This option causes a zone to trigger whenever it To set say zone 3 to alarm on two triggers is unsecured for greater than 200 milliseconds enter Twice within a 5 minute period or unsecured once for greater than 10 seconds P11 E3E An alarm will also occur if more than one two trigger zones are unsecured ONCE EACH DEFAULT NO ZONES TWO TRIGGER during this 5 minute period ie each trigger no zone lights on adds VIEW Two Trigger Option ENTER To ADD Two Trigger zone s ENTER PROG 11 END ZONE NUMBER END SETTING ZONES TO VIBRATION SENSITIVITIES P 12 E to P 19 E Sese e e ie oe ok oe le oe ok o oe oe se se sese sese sese sese sese oR eee R E eee oe oe oe oe oe oe fe oe se RO kkk kk kk k kk When using vibration sensors such as the To set say zone 5 to Medium sensitivity enter Nessensor any of the 8 zones can be programmed with individual sens
27. OUR SILENT P 5E LLLLLLLLLLLLLLLLLLLLLLLLLLLLLDLLLLLLLLLLLDLLLLDLLLDLLLLLLLLLLLLLLDLLLLL A 24 Hour Silent zone is a zone which triggers To set say zone 4 to be 24 Hour Silent enter instantly after it is unsecured This happens whether the panel is Armed or Disarmed PSE 4E The alarm is silent that is no sirens or noise of any description This is used for remote signalling of silent hold up alarms etc DEFAULT NO 24 HOUR SILENT ZONES no zone lights on To VIEW 24Hour Silent option ENTER To Add 24 hour Silent zone s ENTER PROG 5 END ZONE NUMBER END In addition to the selected ZONE OPTIONS instant delay 24 Hr etc each zone can be independently programmed to any ONE of the following ten sensitivities ONE trigger TWO trigger EIGHT Vibration Sensitivities Sensitivities cannot be deleted only changed by the selection of another sensitivity Example of a Zone Assignment ZONB DESCRIPTION ZONE OPTIONS SENSITIVITIES 1 Garage door Secondary delay One trigger long entry 2 Front door Delay One trigger short entry 3 Hallway detector Hand over Two trigger 4 Perimeter reeds Instant One trigger 5 PIR lounge room Instant Two trigger 6 Smoke detector 24HR Audible One trigger 7 Back door Delay One trigger short entry 8 Perimeter vibration sensors Instant Vibration medium sensitivity Page 12 REA VE 5000 Series Dialler SETTING ZONES TO ONE TRIGGER P 10 E EDGR ACSIA SSO CSO I CSIR CSO SCOR CSO CSO ACC
28. Output zone alarms to Dialler zone 7 light on To VIEW this option ENTER PROG 21 END To VIEW the option enter P 21 E Then to CHANGE the option enter 7 E DEFAULT NO MONITOR ALARMS TRIGGER THE DIALLER zone 7 light off To CHANGE this option ENTER 7 END This option sets the Audible Alarm s operating time The time is indicated by Its value being flashed via the zone mains battery lights eg 10 minutes zone light followed by mains 0 light The timer is programmable from 1 to 99 minutes in one minute increments To VIEW Siren Reset Time ENTER PROG 22 END To VIEW the programmed time enter P 22 E Then to CHANGE the time to say 11 minutes enter 11 E NOTE Whilst a time is being displayed the keypad is inoperable DEFAULT 10 MINUTES To CHANGE Siren Here Time ENTER TIME END In minutes CHECKS BEFORE ENTERING Client Program Mode s t eksoekookakookokopakoapakookakopaak pokok icc bosib chibi icr ices ek For security all 24Hr inputs are active during Client Program Mode Therefore after installation programming has been completed there are some basic checks that should be performed in order to save frustration and possible embarrassment 1 Check that the Tamper input is properly terminated with a 2K2 resistor 2 Check that the Keyswitch Panic input is also terminated with a 2K2 Resistor 820 ohm if a Satellite is used 3 Ensure rear panel
29. R CSO I SCOR SYMPTOM Zone light on or long beeps on Arming 10 beeps upon Arming Mains light flashing Battery light flashing 10 Beeps at any time mains battery light flashing 1 long beep during keypad entry Constant tone upon Arming 2 second siren at end of exit time Constant tone on entering premises External strobe light flash ing Siren sounding when sys tem disarmed Armed monitor light flash ing Zone Excluded light flash ing Tamper light flashing Alarm memory light flashing POSSIBLE CAUSE Zone detection device eg reed switch movement detector unsecured Number of beeps determine which zone is unsecured Mains power off Battery low as above Invalid keypad entry Tamper panic or 24 hour zone unsecured Zone unsecured before ex piry of exit time Alarm occurrence since last arming of panel Alarm occurrence since last arming of panel Tamper panic or 24 hour zone activated Monitor mode entered by mistake A zone has been excluded Tamper unsecured Alarm in memory CORRECTIVE ACTION Close door or window Find cause of movement Check plug pack is plugged in and power point on or call Installation Company as above Press END button and re enter Check panic button If in stalled or call Installation Company Re enter premises disarm system check zone isolate memory to determine zone Che
30. R UP CHECK This test is carried out purely to ensure the 1 Check for erroneous open or short circuits panel isn t subjected to short circuits which may using a multimeter cause damage when the battery is connected The AC supply is used in this test because it is 2 With the Control Panel lid open apply AC overload protected On failure of this test refer power If there are any sirens or piezo to the Trouble Shooting section page 33 alarms connected these should sound The Control Panel s beeper will also sound On completion of wiring 3 Disconnect AC power 4 Test complete You are now ready to commence programming CONTROLS AND INDICATIONS ettettkeleletotokeelelelototokoleleletotololelelelelotoleleleletototeleleletetototeleleletetoteleleleletoteteleleletototoleleletetototeleleletototolole KEYPAD The keypad consists of 12 buttons 16 status The PROG or P button is used to begin any lights and an internal beeper Each button is programming sequence used for four purposes a to enter a number eg 1 2 3 b to select an installation programming option eg POE C to select a client programming option marked in blue eg CODE 1 The END or E button is used in all cases to signify the end of the button sequence just pressed d to select a command marked in white eg ARM AUDIBLE INDICATIONS Every time a button is pressed the Panel responds with a very brief beep in At other times the b
31. REA VERA 5000 Series 8 Zone Panel Installation Manual NESS 5000 8 ZONE INSTALLATION MANUAL NESS SECURITY PRODUCTS SYDNEY Phone 02 8825 9222 Head office BRISBANE Phone 07 3343 7744 MELBOURNE Phone 03 9878 1022 PERTH Phone 08 9328 2511 Copyright by NESS SECURITY PRODUCTS December 1988 To the best of our knowledge the information contained in this manual is correct at the time of going to print NESS Security Products reserve the right to make changes to the features and specifications at any time and without notice in the course of product development CONTENTS INTRODUCTION 2 Terminology 2 Features 4 5000 SERIES Optional Equipment 5 INSTALLATION 6 Unpacking 6 Installation Procedure 6 Inputs 6 Outputs 7 Power 7 Earthing 8 Power Up Check 8 Wiring Diagram 8 CONTROLS AND INDICATIONS 8 Keypad 8 Audible Indications 8 Visual Indications 9 Zone Indications 9 INSTALLATION AND PROGRAMMING 10 Access to the Installation Program Mode 10 How to Program 10 ZONE OPTIONS 10 Setting Zones to Instant 11 Setting Zones to Delay 11 Setting zones to Handover 1 Setting Zones to Secondary Entry Delay 11 Setting Zones to 24 Hour Audible 12 Setting Zones to 24 Hour Silent 12 Zone Sensitivities 12 Setting Zones to One Trigger 13 Setting Zones to Two Trigger 13 Setting Zones to Vibration Sensitivities 13 Test Procedure 14 MISCELLANEOUS OPTIONS 14 Lockout and Conditional Lockout 14 keyswitch Operation 15 Keypad Arming 15 Auto Ex
32. RY RESETTING AN ALARM I SHIR CSIR CSO I SCOR CSR CSCO OA CO OR CSCO A CORI CO OR CSR ACCOR ICO ACCOR I SCOR OR COR ICSC GI COR CSCO I SCOR CSO I SCOR ICO GR ICO ACCOR COGS Your Panel can be reset and the alarm silenced by entering your CODE followed by the END button Alternatively if a keyswitch is installed the Panel may be reset by momentarily activating the keyswitch ALARM MEMORY If you arrive at your premises and find the strobe light flashing if installed reset the panel as below Refer to the description listed under ALARM MEMORY to help you interpret the flashing lights on the panel and what they mean Enter CODE END CSIR CSO I CO OR COR CSCO I ICO OR CSUR A CORI COO CSR ACCOR COO ACCOR ISCO OI COR ICSC OI COR ICO CSCO OR SCOR CSO I SCOR COG CSO ACCOR OR COGS The 8 Zone Control Panel contains a comprehensive Alarm Memory to show those alarms that occurred while the Panel was last armed To view the MEMORY display enter 5 The Panel will respond with 3 beeps ALARM MEMORY light will be illuminated and the other indicators will change to show the alarms if any 1 To View Memory press 5 END 2 Observe lights 3 To Exit press END The Indicators are used as follows ZONE LIGHTS FAST FLASH SLOW FLASH ARMED LIGHT FLASHING TAMPER LIGHT FLASHING BATTERY LIGHT FLASHING MAINS LIGHT FLASHING BATTERY amp TAMPER LIGHTS FLASHIN
33. The END or E button is used in all cases to signify the end of the button sequence just pressed Visual feedback of the options programmed is achieved by illuminating the zone indicator lights or flashing the BATTERY MAINS light The particular type of indications are described with the setting of each option in the following pages ENTER the new value s VALUE END One long beep indicates an invalid entry The control Panel may be programmed with up to 4 separate Access Codes Therefore each user may be allocated with their own unique code for higher security REMEMBER Access CODE 1 master code MUST be programmed All codes must contain a minimum of 3 digits toa maximum of 6 digits and must not begin with a zero Codes 2 3 and 4 are optional A code may be cancelled by beginning the code with zero As a security measure the existing code will not be displayed and the new code must be entered twice If the second entry differs from the first the existing code will remain unchanged To input Code ENTER PROG 1 END C END C END C Represents the numbers required as the code To input Code 2 ENTER PROG 2 END __ __ END END C Represents the numbers required as the code Access Codes 3 and 4 are programmed as above ENTRY DELAY TIME 1 To program code to be say 3456 then enter P 1 E 3456 3456 2 To program code 2 to be say 9765 then enter
34. The three special features are COMMON to both Diallers but may be changed while in the programme option for either one For example P71EI2E sets the Restore option for zone 1 on both Diallers while P171EDE would then reset the option for both Diallers The 22 alarms and their corresponding programming options are as follows Arm Disarm Open Close P66E Keypad Fire alarm Control Panel fail P67E Keypad Panic alarm Battery Fail P68E Keyswitch Panic alarm Satellite Battery fail P69E Duress alarm Mains fail P7OE Zone Excluded isolated Test Tamper alarm Zone alarm Keypad Code alarm to to Keypad Medical alarm P78E Zone 11 alarm If you wish to disable one of the 22 alarms so that it will never be reported then enter a channel number of 98 which will blank all the channel indicators ie 1 to 0 For example to disable Zone 1 so that it never reports press the buttons P7 E98E If you wish to use the Satellite Battery alarm you must enable it in POE by setting its channel to any value 0 to 9 Once enabled it is automatically combined with the main Battery Fail alarm P59E and sent with the channel number assigned to P59E To ensure correct alarm transmission in the various formats certain alarms MUST BE SET to specific channels as defined in the following table An indicates that any channel number may be used Low Speed High Speed Extended H S Arm Disarm 8 8 9 Battery Fail 0
35. This is a small hand held device which allows remote communication with the Auto Dialler via the telephone line It can be used to Arm the Control Panel operate an output or receive status reports Page 5 SECURITEL INTERFACE UNIT This is a plug in programmable device which offers similar features to the Auto Dialler but provides a higher level of security in that the telephone line is monitored at all times RADIO CONTROL EOUIPMENT A 4 channel Radio Control Receiver can be connected to the Panel to receive signals from the NESS hand held Emergency Panic buttons PRINTER REAL TIME EVENT RECORDER Records and or prints all activities of the Control Panel with a Time and Date Stamp OUTPUT EXPANDER A plug in device used for interfacing to Direct Line or other equipment Requiring no programming It provides 20 outputs such as individual alarms zone Excluded etc ZONE EXPANDER A plug in device that provides an extra 16 zones and is fully programmable from the Control Panel s keypad REA VE 5000 Series Dialler INSTALLATION Included in the 8 Zone Control Panel packaging is the following equipment 1 x 5000 SERIES 8 Zone Control Panel 1 x 12 Volt 6 5 A h Rechargeable Battery 1 x 17 Volt Plug pack 3 x Ten Way Terminal Blocks 12 x 2K2 Resistors 1 x Spare Fuse 1 5 Amp 1 x Allen Key 1 x Installation Manual 1 x Instruction Manual INSTALLATION PROCEDURE 1 OSS I A A I A A A A OO SSCS SCS
36. You should also use P604E to provide the 4 zones with a 24Hr Alarm Memory 2 The Control Panel programming determines whether the groups of expansion zones are Instant 24Hr Hand over etc 3 We strongly recommend that EXPAND 1 1 8 be connected to zone 1 of the Panel and EXPAND 2 9 16 to zone 2 of the panel This makes it much much easier for your client CLIENT OPERATION The following commands are available 4B to see the sealed unsealed state of EXPAND 1 ie the Expansion zones 1 8 6E to see the sealed unsealed state of EXPAND 2 ie the Expansion Zones 9 16 45E EXPAND 1 Alarm Memory 65E EXPAND 2 Alarm Memory NOTE indicators are STEADY only ON alarm 47E EXPAND 1 Excluding Including of zones 67E EXPAND 2 Excluding Including of zones NOTE zones can only be Excluded during Exit Time INSTALLATION PROGRAMMING The following programme options are available for the Zone Expander To use the indicators of the Control Panel each of the groups must have its own options EXPAND 1 Zones 1 8 P404E zone E P410E zone E P411E zone E P420E zone E P423E zone E P424E zone E P99B EXPAND 2 Zones 9 16 P604E zone E P610E zone E P611E zone E P620E zone E P623E zone E P624E zone E DESCRIPTION Provide the selected zones with a 24Hr Alarm Memory so that ifthey alarm while Disarmed the alarm will be stored in 45E or 65E use for 24Hr zones Selected zones will alarm on 1 tri
37. a failure to communicate with the base station OFF The panel is Disarmed OFF No alarms FLASHING SLOW An alarm is stored in memory OFF No zones are EXCLUDED ON The panel is in client program mode FLASHING FAST The program memory is faulty FLASHING The panel battery is low If flashing in unison with the satellite light the satellite battery is low FLASHING The mains power is disconnected or turned off FLASHING The panel or satellite siren tamper are unsecured If flashing in unison with the battery light the satellite battery is low ON The dialler has seized the phone line a dialler or zone expander option is selected FLASHING FAST The dialler or zone expander has a System fault or the dialler cannot store the information just programmed into it FLASHING at the incoming call rate The dialler is detecting an incoming call ZONE INDICATIONS OR CSUR CSCO A ICO OR CSO A CORI COR ICO ACCOR COO ACCOR I SCOR OI COR ICSI COR CSO CSCO OR SCO OR CSO I SCOR OR COR CSO ACCOR OR CSRS There are 8 Zone indicator lights above the keypad In normal operating mode they show the following states OFF Zone secured ON Zone unsecured HOW TO ENTER PROGRAM MODE PROGRAMMING FLASHING FAST Primary alarm ie indicates the first zone to become unsecured and cause the alarm FLASHING SLOW Secondary alarm ie indicates those zones that have become unsecured during the Alarm Reset time
38. alarms via your telephone line Dialler Remote Control This small hand held device allows com Output Expander Provides 20 additional outputs for interfacing to other equipment Zone Expander Provides an extra 16 Zones for the Panel munication and remote control between you at a remote telephone and your Control Panel Securitel is a Trademark of Telecom Australia Construction Dimensions mm Weight with 6 5 AH battery Plug pack Power supply Quiescent Current Operating Voltage Rechargeable Battery Battery Charge Current Dynamic Battery Test Dynamic Battery Test Low Voltage Fuses 5x20 mm Zone Inputs Remote Tamper Input Remote Keyswitch Panic Button Input Remote Keypads Inputs Intelligent Keypad Outputs Internal Siren Output External Siren Output Satellite Siren Output Maximum number of Sirens Latched Alarm Strobe Output Power Output for Optional Equipment 3mm Polycarbonate 233 wide x 300 high x 85 deep 3 3 kg Input 240V AC Output 17V AC at 1 4A 13 8 V DC at 1 25 Amps current limited Less than 80 mA 10 V to 15V DC 12 V 6 5AH 450 mA maximum current limited Every hour and when the Panel is Armed whether mains power is on or off 10 7 V with a 5A load 4 x 1 5A fast blow End of line resistor 2200 plus minus 900 ohms Same as zone input Same as zone input Proprietary Proprietary Open collector fused Open collector fused Proprietary 3
39. alue E The 8 Zone Control Panel produces the following 22 alarms which must be assigned to the 9 channels allowed in a transmission to a Central Monitoring Station The channel number can be from 0 to 9 and the current selection for an alarm is shown via the 8 ZONE indicators the 9 BATTERY and the 0 MAINS indicators Only one channel may be selected for an alarm at any one time One or more of the three special features explained below may be selected for each alarm and the current selection is shown via the indicators as follows Function Indicator Option ABORT TIME Arm Monitor 11 RESTORE Alarm Memory 12 MULTIPLE REPORTS Zone Excluded 13 Thus to set Zone 1 alarm to channel and select all of the three special features press the buttons P71E 6E 11E 12E 13E Ie P71E channel abort restore E multiple E Page 10 REA LZ 5000 Series Dialler 57 58 59 P60E P61E P62E P63E 64 65 P57E PS9E P6iE P62E P70E The following three features may be used to modify for each alarm the basic transmission procedure to a Central Station ABORT TIME Delay dialling until after this time If the Control Panel or the input is reset during the Abort Time the alarm is cancelled and no dialling takes place RESTORE When a alarm becomes sealed a restoral transmission is sent to the Central Station MULTIPLE REPORTS Each time an alarm occurs a transmission will be sent to the Central Station
40. an be up to 18 digits in length including any PAUSE digits mentioned above To program the number to be 12345678 first enter Program mode and then press the buttons P33E12345678E MEDICAL ALARM TIME DELAY This option defaults to 0 seconds which means that Medical Alarms from the panel 1E are sent immediately When the time is other than 0 then alarms are only sent by the Dialler if the Medical Alarms are NOT received within that time which may Set from 1 to 250 which represents 0 1 to 25 0 hours Thus to programme the time to be 24 hours first enter Program mode and then press the buttons P 20 E 240 NOTE Do not forget to change the time to 0 when you go on holidays AUTHORISATION TELECOM AUSTRALIA INSTRUCTIONS TO CUSTOMER Apparatus 5OOOD 5000 Series Dialler Communicator Authorisation No C87 3 94 Page 15 5000 ZONE EXPANDER Design Concepts The 5000 SERIES Zone Expander is intended as a low cost solution for those situations requiring more than 8 Zones Thus the expander uses the indicators of the 8 Zone Control Panel to provide many zones at a fraction of the cost of a large multi sector panels but at the same time offering increased security over the alternative of combining detectors to fit within the 8 Zones Installation In most instances the Zone Expander would be installed on the four inserts provided in the metal Expansion Box Connection to the 8 Zone Control Panel and Dialler if requ
41. ata is permanently stored in a non volatile EEPROM more secure than battery backed up memory Separate Installation and Client Programming modes The Control Panel housing has 4 separate tamper systems Keypad Wall Lid and Panel impact Tampers are monitored 24 hours a day Additional security is provided by the various programming options e Arm via a code Exclude zones via a code Partial Arming Monitor mode e Extra Delay zone to cater for long and short entry paths e Handover zones TRUE DYNAMIC BATTERY TEST every hour and upon Arming thus guaranteeing the system s integrity Comes complete with an a c plug pack and a 6 5 AH battery to maintain system security under all power supply conditions Outputs are separately fused Page 4 5000 Series Dialler Zone inputs can be split with two end of line resistors so that two pieces of equipment eg reed switches can both be monitored to provide maximum security ALL inputs and outputs are heavily protected against lightning and high voltage power supply transients An earth terminal is provided for extra protection Fail safe input system detects any component failure in the zone input circuitry and generates an alarm Detectors can be programmed to alarm on 1 or 2 triggers cheaper and more secure than using pulse count detectors Vibration sensors can be connected to any or all zones without additional hardware and can be programme
42. button to retain previously programmed data Enable option P21E 1E or ensure delay zone is being activated prior to operation of the Key switch This is normal operation AERA SYMPTOM Instant zones will not trigger after Arming the Panel Sirens Strobes or Detectors not working After Arming the beeper in the Control Panel Keypads and Keyswitches gives a constant beep until the end of Exit Time The internal and external sirens sound for two seconds at the end of exit time The Tamper light flashes always The Battery light is flashing SPECIFICATIONS Construction Dimensions mm Weight with 6 5 AH battery Plugpack Power supply Quiescent Current Operating Voltage Rechargeable Battery Battery Charge Current Dynamic Battery Test Dynamic Battery Test Low Voltage Fuses 5x20 mm Zone Inputs Remote Tamper Input Remote Keyswitch Panic Button Input Remote Keypads Inputs Intelligent Keypad Outputs Internal Siren Output External Siren Output Satellite Siren Output Maximum number of Sirens Latched Alarm Strobe Output Power Output for Optional Equipment Resetting Alarm Output 24 hour Alarm Output Monitor Alarm Output Auxiliary Output 5000 Series Dialler CAUSE All zones except 24Hr zones Are ignored during Exit Time after arming Blown Fuses A 24Hr Tamper or Panic input is unsecured The Panel has been Armed with zone unsecured Tamper circuits are un
43. by partially arming the control panel when people still occupy some areas To do this first Arm the Panel and then exclude those zones those zones and depart the premises The exit delay time will be automatically re enabled allowing them time to depart INCLUDING ZONES kE Akk CO OR CSO A CORI CO OR CSR ACCOR COO ACCOR I SCOR OR COR ICSC I CORO ICO CSCO GI SCOR CSO I SCOR OR COG CSO CSCO OR ICSE Zones which have been Excluded may be included while you are in the Armed Disarm or Monitor modes All Excluded zones are automatically Included when the panel is Disarmed Thus if a detector is still faulty it must be Excluded again 1 Press 7 END 2 Enter the zone s to be INCLUDED ZONE END ZONE END 3 To Exit and save Inclusion END The main reason for providing the capability to include zones is to allow an easy means for employees working back to include their own areas on leaving the premises The Exit Time will re start automatically Pressing 7E will light the zone lights for the zones that have been Excluded To Include say zones 4 and 8 press TE 4E SE E Zone lights 4 and 8 will turn off An attempt to include a zone which has not already been excluded will result in one long beep and the zone remains unchanged If you make a mistake selecting a zone to Include it is not possible to exclude that zone without returning to the Exclude Zone option AUXILIARY OUTPUT
44. changed and the power is turned off before Exit from this mode then the new data will be lost A number of the Installation Programming options are duplicated for the second Dialler and are accessed by adding 100 to the corresponding Dialler 1 option eg P34E Dialler 1 client account number P134E Dialler 2 client account number The options belonging to Dialler 2 are identified in the option s title which is also underlined Page 4 REA LZ 5000 Series Dialler SOFTWARE DATE INSTALLER PROGRAM ACCESS CODE P30E Code E Code E Pressing P30E will display the release date month and year only of the Software version currently installed in the Dialler To program your secret Installer Access Code enter it twice as shown above ie after the display of the date The only constraint for this code is that it must always be 4 digits in length For security reasons it is not displayed at any time See page 4 regarding the use of this Installer Access Code There is no default value for this code ie it is blank SET ALL OPTIONS to DEFAULT VALUES P98E Press P98E at any time in Installer Program mode to clear the Installer Access Code the telephone numbers and the Client Account Number as well as set all the other programming options to their default values Note If you need to reprogram the Dialler and do not know the Installer Access Code you must use P98E to clear everything as above before you can gain access to th
45. ck Alarm memory to determine zone at fault Check Alarm memory to determine zone at fault Reset alarm by entering code or activating key switch check panic buttons if installed or call Install ation Company Exit monitor mode Check zone excluded memory Arm panel with all zones secured Call Installation Company Check alarm memory to see cause of alarm OPERATION SUMMARY 17 EDGR CSIR SSO CSO CSIR I SORA SCOR COUR CSCO I ICO OR CSR A CORI COO ICCA SA SCOR OI COO ACCOR I SCOR OR COR ICSC I CORO ICSI CSO OI COO CSO I SCHORR ICO ACCOR CSG ARM DISARM RESET ALARM MONITOR MODE Exit MONITOR MODE ALARM MEMORY Exit MEMORY EXCLUDE ZONES Exit EXCLUDE MODE INCLUDE ZONES Exit INCLUDE MODE PANIC ALARM CHANGE AUXILIARY OUTPUT ZONE SUMMARY 0Eor 0 CODE E CODE Eor Keyswitch CODE Eor Keyswitch 8E or Keyswitch CODE Eor OE 5 Keyswitch ARM as above then 7E zone zone etc E TE zone zone E 3E 9 ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 LOCATION REA Es 5000 Series Dialler NESS 5000 SERIES DIALLER INSTALLATION MANUAL This manual is designed to provide the installation instructions on the NESS SECURITY PRODUCT S 5000 SERIES Diall
46. clude Monitor Installation and Client Program modes REA VE 5000 Series Dialler INSTALLATION PROGRAMMING THE POWER UP CHECK ON PAGE 13 SHOULD BE CARRIED OUT PRIOR TO PROGRAMMING ACCESS TO THE INSTALLATION PROGRAM MODE The Installation Program Mode is entered b by depressing the E button on power up whenever programming options are to be the Panel will retain all previously changed by the installer It can be accessed in programmed values If no previous values three ways were programmed then the default values will be automatically selected a by depressing the P button on power up the Panel will be automatically programmed by entering POOOOOOE if the Panel is with the factory set default values as shown currently in the Client Program mode This in the summary at the end of this manual will silence any alarm HOW TO PROGRAM eeek Programming the NESS 5000 SERIES 8 zone The END or E button is used in all cases to Control Panel is achieved via the keypad signify the end of the button sequence lust Every time a button is pressed the panel pressed responds with a very brief beep in acknowledgment END The PROG or P button is used to begin any programming sequence Visual feedback of the value programmed is achieved by illuminating the zone mains or battery lights The particular type of indications are described for each option in the following pages The Numeric keys are used to enter Installation Programming
47. clusion of Zones 15 Entry Warning Beeps 16 Panic Alarms 16 Zone Tamper and Code Alarms 16 Monitor Alarms to Dialler 17 Siren Reset Time 17 Checks Before Entering Client Mode 17 TESTING 18 Testing 18 Troubleshooting 19 Specifications 20 Programming Sheet 21 AERA INTRODUCTION Thank you for purchasing the NESS 5000 SERIES 8 zone Control Panel The system was designed to provide you the installer with features and versatility never before offered in a Control Panel The high impact polycarbonate housing not only offers strength but is aesthetically pleasing and therefore easily marketable Both the main circuit board and the lid are removable which allows you to easily install the system Plug in terminal blocks eliminate the need to unscrew all connections before removing the board to provide ease of installation and service 5000 Series Dialler NESS Security Products over the years have always provided technically innovative quality products which have led to the 5000 SERIES being one of the most reliable on the market today NESS unparalleled technical support and service reinforces our commitment to the industry This manual will tell you all you need to know about installing and programming the system options For client programmable features and operating instructions refer to the INSTRUCTION MANUAL In order to fully understand the 5000 SERIES 8 Zone Panel you should become familiar with the terminology used
48. d 2 ENTER CODE EThe siren will stop ZONE EXPANDER FUNCTIONS a Audible Activates sirens and will transmit the alarm signal if monitored b Silent Will transmit the alarm signal if monitored remotely To activate emergency alarms MEDICAL enter 1E FIRE enter 2E PANIC enter 3E To SILENCE the siren you must enter CODE E Panic cannot be used while the Panel is in Program Memory or Exclude mode Tf you have the optional Remote Keyswitch press the separate panic button fitted above the keyswitch CSIR CSO I SCOR CSR ICS A A CORI COO CSCO ACCOR COR ACCOR ISCO OR COO CSCO OI CORO CSCO ICSC OR COO CSO I SCOR COG ICO CSCO OR CSRS These buttons are ONLY USED in conjunction with the NESS 5000 Series Zone Expander to address the sixteen additional zones 4 END Address first additional bank of 8 zone Address the second bank of 8 zones 13 Alarms may be caused by one of the following condition A Zone has been activated while the Panel was Armed A Tamper circuit has been activated A Panic button has been activated A 24 Hour Zone has been activated All of these can cause your sirens and strobe to operate Various visual indications relevant to the alarm will be retained in the memory If this occurs disarm your Control Panel which will silence and reset the alarm The cause of the alarm can be identified by entering the Alarm Memory Mode as described under ALARM MEMO
49. d to alarm on 1 of 8 sensitivities Separate Monitor alarm 24 Hour alarm and Auxiliary outputs Easy connection of the 5000 SERIES satellite siren to greatly increase the security of your system Special inputs to allow the connection of NESS Remote Keypads These keypads offer full programmability and operation of the Panel from a remote location Indication of unsecured zones while Arming AERA 5000 SERIES OPTIONAL EQUIPMENT 5000 Series Dialler The following optional 5000 SERIES equipment is available for use with the 8 Zone Control Panel REMOTE KEYPAD This Keypad is connected via 4 wires and can increase convenience of operation and security of the system It allows full programmability and operation with Audible feedback only INTELLIGENT REMOTE KEYPAD This Keypad is connected via 4 wires and allows full programmability and operation of the system with complete Visual and Audible feedback SATELLITE SIREN This Siren allows you to offer higher security for the installation It the system is attacked Connected via 4 wires It is fitted with It s own battery and electronics and operates independently of the Control Panel TELEPHONE AUTO DIALLER This is a plug in device and is fully programmable from the Control Panel s keypad It is capable of automatically communicating information to most common digital receivers and or to the client s home over a normal telephone line DIALLER REMOTE CONTROL
50. departure comfortably without rushing and making mistakes The Exit Delay Time can be set to a minimum of 1 second up to a maximum of 99 seconds To VIEW Exit Delay Time ENTER PROG 6 END MONITOR MODE TYPE 1 To view the current Exit Delay Time enter P6E 2 The value programmed will be displayed via the zone 1 8 battery 9 and mains 0 lights This display of the current value must be complete before a new value can be entered 3 To change the current value to say 80 seconds enter 80E Zone 8 light will flash on for 1 second followed by the MAINS light 0 to indicate the new value To CHANGE Exit Delay Time ENTER VALUE END EDGR CSR CSO OR SCOR CSR CSCO A CO OR CSO A CORSA CO OR CSCO ACCOR ICO ACCOR I SCOR OI COO ICSC OI CORR CSCO CSCO I SCOR CSO I SCOR COG CSO CSCO OR CSRS The 8 zone Control Panel provides an unique Monitor mode to ensure your security even while the Panel is disarmed and the premises are occupied Typically Monitor mode is used to monitor the perimeter zones doors windows of a house while the occupants are at home or to monitor entry through front doors or fire doors in shops and offices while the premises are in use You can program which zones are to be monitored as well as select of 4 different types of Monitor alarms To VIEW Monitor Mode Type ENTER PROG 7 END The 4 different types of Monitor mode alarms are 1 Beeper warning for the
51. disconnected Audible warnings to indicate trouble when Arming Comprehensive Memory Mode for easy retrieval of important events such as Primary Alarms Secondary Alarms Tamper Alarms Low Battery and Mains Fail All Programming data is permanently stored in secure non volatile EEPROM 5000 SERIES OPTIONAL EQUIPMENT The following optional 5000 SERIES equipment is available for use with the 8 zone Control Panel Remote Intelligent Keypad Remote or Intelligent Keypads can increase convenience of operation and security of your system Remote Keyswitch The Remote keyswitch will simplify the operation of the Control Panel it is required Satellite Siren Fitted with its own battery and electronics a Securitel Interface Unit Similar to the Telephone Auto Dialler but provides higher security Radio Control Equipment A Radio Control Receiver can be connected to the Panel to receive signals from Radio Trans mitters such as hand held panic emergency buttons Real Time Event Recorder Printer This device is connected to the Panel to RECORD and or PRINT when any activity takes place Satellite Siren will operate independently of the control panel if there is any interference to the system wiring Telephone Auto Dialler The Telephone Auto Dialler allows the 5000 SERIES Control Panel to communicate
52. duration of the panel entry time then full siren alarm Used for perimeter protection 2 Beeper and siren operate for 2 seconds only Use this for medium security warnings or as a walk test mode 3 Full siren alarm immediately Use this for high security such as monitoring fire doors etc 4 Zone number is beeped out only Use this for door opened warning To select say Monitor mode 3 enter 7 When the above option is programmed into the panel zone light 3 will flash on for 1 second Talk to your security installation company about your specific requirements To CHANGE Monitor Mode Type ENTER VALUE END ZONES TO BE MONITORED RSH CSIR CSIR I SOR OR SCOR CSR CSCO A ICO OR CSCO A CORI CO OR CSOSA SCOR COO ACCOR I SCOR OR CORR I SCOR GI COR ICO CSCO I COO CSO I SCOR COSI ICO ACCOR OR CSRS Any zone can be selected for operation in Monitor mode However do not select a zone that has been installed to generate a 24 hour alarm eg Fire Detector To remove a zone from the Monitor mode selection re enter the zone number To VIEW Zones to be monitored ENTER PROG 8 END ZONES TO CONTROL THE AUXILIARY OUTPUT To program say zones 3 and 4 to be Monitor zones enter 8 2E 4E As each zone is programmed the corresponding zone light is illuminated if it was previously off If the zone light was previously on it will be extinguished thus de selecting that zone
53. e programme options PRIMARY TELEPHONE NUMBER P31E Telephone no E The Primary Telephone number may be up to 18 digits in length If it is necessary to dial out through a PABX you may need a PAUSE within the telephone number to slow down the dialling To create a PAUSE see page 4 The default telephone number is a single digit 0 SECONDARY TELEPHONE NUMBER P32E Telephone no E The Secondary Telephone number may be up to 18 digits in length and defaults to 0 EXTRA TELEPHONE NUMBER P33E Telephone no E The Extra Telephone number may be up to 18 digits in length and defaults to 0 DIALLER 1 and 2 CLIENT ACCOUNT NUMBERS P34E number E Enter the 4 digit Client Account Number as above There are no other restrictions on what this number can be The default is 0 Page 5 REA LZ 5000 Series Dialler DIALLER 1 and 2 REPORTING P35E option E Do not use the Primary and Secondary telephone numbers at all ie only the Extra number can be used Alternate calls between Primary and Secondary telephone numbers if no Acknowledge tone is received Note if no Acknowledge tone is received for either number then no transmission will be made Use Primary number for half of the calls and then if no Acknowledge tone is received use the Secondary number for the remainder of the calls Transmit to the Primary number and when complete REPEAT all the data to the Secondary number Note this will only occur a successful if transmis
54. eas a rapid series of blows will do so 4 If the sensitivity needs to be changed re enter the desired level of Sensitivity and repeat step 3 Repeat for other zones 5 When adjustment is complete do not forget to set the zones back to their previous setting ie Delay Instant etc NOTE To avoid confusion you should only set one vibration sensor at a time to be 24 Hour MISCELLANEOUS OPTIONS Options P20E conditional I full lockout and P21E seven special options are programmed as the following rule An option is selected by entering its value and is de selected by entering its value again ie it toggles LOCKOUT AND CONDITIONAL LOCKOUT P 20 E eetkeetkeetetetetoeeletoeteleloleleloleleletoleletotolelelotokelelotolelelotoleletoteleletotoleletoteleletokole In order to ensure that alarm sirens reset at the end of Reset Time the zone that caused the alarm must be locked out Two options are provided for versatility Lockout and Conditional Lockout It is important to understand the difference If a zone is set to Lockout it will generate an alarm once and once only irrespective of whether a zone re secures and subsequently unsecures The zone will be locked out until the Panel is Disarmed Alternatively if a zone is set to Conditional Lockout the default selection it will alarm To VIEW Lockout
55. eeper will indicate various acknowledgment warnings such as 10 beeps for a low battery The beeper is also used to indicate whether the entry was valid or invalid For example whenever E is pressed all the buttons pressed before it are checked to see whether they are When Arming the Panel 1 3 beeps will indicate valid If they are valid the response will be 3 that a zone is unsecured eg Zone 3 will be short beeps indicated by 3 long beeps If they are invalid or incorrect the response A continuous tone on Arming indicates a will be 1 long beep and they will be ignored Tamper or 24 Hour zone is unsecured During Entry time it indicates that an alarm has occurred Page 8 REA VE 5000 Series Dialler VISUAL INDICATIONS The panel has 16 indicator lights rounding the keypad Each light has three basic states to indicate function These are ON OFF FLASHING ARMED ON The panel is Armed MONITOR FLASHING The panel is in Monitor Mode ALARM ON Memory mode is selected MEMORY FLASHING FAST An alarm has occurred ZONB ON The panel is in EXCLUDE mode EXCLUDED FLASHING Zone s have been EXCLUDED PROGRAM OFF The panel is in normal operation mode FLASHING SLOW The panel is in installer program mode BATTERY ON The panel battery is healthy MAINS ON The mains power is connected and turned on TAMPER OFF The control panel and satellite siren tamper SATELLITE are secure and satellite siren battery is healthy LINE OFF The dial
56. er For complete details on the warranty or the 5000 SERIES products please refer to our conditions of sale NESS SECURITY PRODUCTS 4 167 Prospect Hwy Seven Hills 2147 N S W Australia Head Office SYDNEY Phone 02 8825 9222 BRISBANE Phone 07 3343 7744 MELBOURNE Phone 03 9878 1022 PERTH Phone 08 9328 2511 Copyright by NESS SECURITY PRODUCTS July 1987 DESIGN CONCEPTS The 5000 SERIES Dialler is totally unique in that 2 separate diallers share the one Circuit board and telephone line It is not simply one dialler with two Client Account Numbers but 2 separate individually programmable diallers sharing the same hardware With this unique design and the many other features built into the 5000 SERIES Dialler NESS has been able to provide you with a product capable of meeting the diverse needs of virtually all installations In addition it provides a simple means of overcoming at no extra cost the 8 alarm channel limitation of most Central Station equipment Some of the unique capabilities of this Dialler are explained below EXTRA TELEPHONE NUMBER The Primary and Secondary telephone numbers are basically designed for reporting to the Main and Back up receivers of a Central Station An Extra telephone number which may be programmed by the client has been provided for added flexibility By setting option 4 of P35E the Extra number will be used in addition to the Primary Secondary numbers If both options 0 and 4 o
57. er to the lowest ohms range and check that the 4 fuses measure less than 0 5 ohms VOLTAGES All zone inputs the Tamper input and the Keyswitch panic inputs should be terminated with a 2K2 ohm end of line resistor When correctly secured the voltage reading across 5000 Series Dialler each zone input should be 2 5 volts or 0 2 volts If the voltage reading is above or below this reading check your detector wiring and cabling Check that the DC output to the detectors is 13 4 to 13 8 volts If a Satellite siren is installed the correct voltages across pos and neg should be 13 4 to 13 8 volts The voltage reading between the control and neg terminals must be in the range of 2 4 to 2 7 volts for reliable operation Ensure that an 820 ohm resistor has been substituted for the 2K2 ohm resistor in the External Tamper input of the 8 Zone When checking Tamper in put voltages or Satellite voltages ensure that all Tamper switches are secured including the lid tamper as all of these points are WIRED IN SERIES There are two simple methods of walk testing all zones Method B is the most convenient way of walk testing a system unless monitor mode options have been reprogrammed from the default values ie Monitor type 2 P7E 2E selected and all zones programmed to be monitor zones P8E all zone lights on METHOD A 1 Select Installation Program Mode 2 Program all zones to 24hr Audible PAE 1E to 8E 3 Un
58. extra security This is called a Dynamic Battery Test Page 2 AERA INPUTS A total of ten End of line Monitored Inputs are provided for connection to various devices One or more Defection Devices may be connected to any of the eight End of Line monitored zone inputs The inputs can be programmed to suit various applications A Movement Detector may require Two Trigger operation whereas a Reed Switch will require Normal One Trigger operation A Vibration Sensor would be programmed to one of eight Vibration Sensitivities Smoke Detectors and Holdup Switches are required to operate always and would therefore be programmed to 24 Hour operation The Control Panel housing external siren covers and many types of detectors are protected by Tamper switches designed to detect attempts to disable those devices The tamper switches are connected to the Tamper Input Activation of any tamper switch or its wiring will cause an immediate alarm at any time in all modes except Installation Program Mode The system may be controlled by a Remote Keyswitch connected to the Panic Keyswitch Input Panic Buttons may also be connected to the same input OUTPUTS Separately fused Siren outputs allow the connection of Internal and External Horn Speakers A Latched output is provided for Strobe lights and a Resetting output for miscellaneous alarm devices such as Piezo sirens Other outputs are provided for connection to optional 5000 SERIES equ
59. f P35E are set then only the Extra telephone number it used for either or both Diallers as required POCKET PAGER To indicate an alarm via a type pocket pager the Dialler only has to call a number and wait for a special Acknowledge tone It does not have to send any alarm reports This facility is available via option 5 of P36E COMMAND TONE An optional Tone Generator may be purchased to remotely control certain aspects of the Dialler if so programmed To use the facility call the Dialler and when it answers put the Tone Generator near the mouthpiece and press its button The Dialler will respond with a series of beeps depending on the options selected Page 1 REA LZ 5000 Series Dialler DIALLERS The enormous flexibility of the Dialler can be seen from a few of the possible combinations described below 1 Call the Primary number and if no Acknowledge tone call the Secondary number ie the Back up receiver 2 Call the Primary number and then repeat all alarms to the Secondary number 3 As in 1 or 2 and then repeat the alarms to the Extra number as well If no Acknowledge tone is received this will be in Audible format if so programmed or it could be a pocket pager 4 Split the 22 possible alarm reports between the 2 Diallers so that more than 8 can be reported by the use of 2 client account numbers 5 Send all alarm reports to both Diallers but only enable the Extra number on Dialler 2 6 Use
60. f the Exit Time the system will become fully Armed An Instant Zone becoming unsecured will cause an immediate alarm The alarm may be Silent it the system is monitored by a Central Station via a 5000 SERIES Dialler or a NESS Securitel Interface Unit or it can be Audible in which case the Sirens sound for the programmed Reset Time while the Strobe Lights will continue running until the Panel is Disarmed When the alarm Resets any zone that is still unsecured will be automatically Locked Out to prevent that zone from causing further alarms If the zone is programmed for Conditional Lockout the zone will become active again when the zone is secured so that it may cause further alarms whenever the zone becomes unsecured again All alarms are stored in Memory so that they can be recalled after the Panel is Disarmed The zone that caused the alarm is stored as a Primary Alarm and any zones that are Unsecured within the Reset Time are Secondary Alarms When the client enters the premises the Panel will ignore those zones that are programmed for Delay Secondary Delay or Handover for the duration of the relevant Entry Time Failure to Disarm the Panel within this time will cause an alarm AERA FEATURES Ultra modern and impact resistant housing 8 fully programmable zones plus tamper and panic inputs Fully programmable via Control Panel Keypad eliminates the need for expensive programmers or PROMs All Programming d
61. gger only Selected zones will alarm on 2 triggers If two 2 trigger expansion zones each trigger once then the panel will alarm Selected zones are set for Lockout indicator ON Conditional Lockout indicator OFF Selected zones are combined to drive the 1 8 output for connection to the Control Panel Selected zones are combined to drive the 9 16 output for Connection to the Control Panel Reset all Expander options to the default values ie both EXPAND 1 and 2 5000 Series Panel 8 Zone Version 3 INSTALLATION PROGRAMMING Program light flashing POE zone E PIE zone P2E zone E P3E zone E P4E zone E zone P10E zone P11E zone E P12E zone E to P19E zone E P20E zone E P21E option E P22E time E Exit Installation mode Instant Delay Handover Long Delay Entry time same as Exit time 24hr audible 24hr silent Single trigger zones 1 8 default Double trigger zones Vibration sensor Highest sensitivity Vibration sensor Lowest sensitivity Conditional lockout leds off Lockout leds on 1 Disable Keyswitch entry exit restriction 2 Enable Arm via Code 3 Disable Auto exclude full alarm at end of exit time 4 Disable entry warning beeps silent entry time 5 Enable silent Panic alarms 6 Enable silent other alarms except 24hr amp Fire 7 Enable Monitor modes 1 amp 3 to trigger dialler Siren run ti
62. he Panel will be in the Disarmed If you make a MISTAKE while entering any Armed or Monitor modes which provide codes press the END E button and start again different levels of security for your premises When you are required to enter your Access Three other temporary modes Program code you are given THREE opportunities to Memory and Exclude allow you to perform enter it correctly After the third invalid attempt various operations The Panel will automatically the alarm is activated requiring the correct exit from these temporary modes it you do not code to silence the alarm This prevents press any buttons on the keypad within a 2 anyone trying to guess your code by entering minute period random numbers ARMING THE CONTROL PANEL CSIR CSO I SCOR CSR CSCO A ICSE CSUR A CORA COR CSR ACCOR CSO ACCOR ISCO OI CORI SCOR OI COR OR ICSI CSCO OR COO CSO I SCHORR ICO CSCO OR CSRS The Control panel must be ARMED prior to There are three methods of Arming the Panel vacating the premises in order to detect intruders a Normally the panel is ARMED by entering on the keypad Ensure that the Panel is not in Program OE Memory or Exclude modes b However your Installer may have NOTE If the panel is already in alarm you programmed the Panel to require the entry of must first silence the alarm before you can a code to Arm the Panel Arm 0 CODE E c If the optional keyswitch is connected this is tur
63. indicated by the zone 5 light To VIEW the option enter P 21 E Keyswitch or keypad panics that are activated Then to CHANGE the option enter 5 E can be selected to be either a Audible Full siren and beeper zone 5 light off b Silent No siren and beeper for remote DEFAULT AUDIBLE PANIC signalling zone 5 light on zone 5 light off To VIEW Panic alarm option ENTER To CHANGE Panic Alarm option ENTER PROG 21 END 5 END ZONE TAMPER AND CODE ALARMS 21 6E This section is indicated by the zone 6 light To VIEW the option enter P 21 E Alarms that are caused by Zone Tamper or Then to CHANGE the option enter 0 E Code Alarm 3 incorrect attempts can be selected to be either a Audible Full siren and beeper zone 6 light off DEFAULT AUDIBLE ALARM b Silent No siren and beeper tor remote zone 6 light off signalling zone 6 light on To VIEW this option ENTER To CHANGE this option ENTER PROG 21 END 6 END Page 16 AERA 5000 Series Dialler MONITOR ALARMS TO DIALLER P21E 7E eetcteletoteletoeteletoketetotokeletotoleletotokelelotolelelotoleleloleleletoleleletolelelotoleleletotelelotelelelotoleletotolelel This selection is indicated by the zone 7 light During Monitor modes 1 and 3 audible alarms zones that cause an alarm can be programmed to a Not output zone alarms to Dialler zone 7 light off b
64. ipment Remote Keyswitches Standard Keypads and Intelligent Keypads can be located at remote points such as front or back doors to control the system and provide additional convenience and security Satellite Sirens ensure maximum security against attacks to the Control Panel Sirens or interconnecting cables It contains it s own battery and electronics to operate independently of the Control Panel OPERATION In Normal Operating Mode the Panel may be Armed ready to detect intruders It may be Disarmed when the premises are occupied or switched to Monitor Mode to allow only selected zones to be Armed simply Thus the Page 3 5000 Series Dialler Perimeter may be protected whilst the internal Zones are ignored Before Arming all zones should be Secured Activation of a detection device will cause the appropriate zone to become unsecured and may cause an alarm After Arming the Panel will ignore most detection devices for the duration of the Exit Time to allow departure from the premises During that time certain Audible Warnings may be sounded by the beeper eg a Low Battery Mains Fail or a Zone Unsecured warning At the end of Exit Time any zone that is still Unsecured may be Automatically Excluded If a detector becomes faulty the client may Manually Exclude the associated zone so that itis ignored and cannot generate an alarm Manually Including the zone will allow it to generate an alarm again After the expiry o
65. ired is via the 13 way strap If you wish to locate the expander within the Control Panel a short 13 way strap is available Each of the input terminals of the Expander can accept 2 separate zones which are identified by different End of line resistors EOLR The 2 zones may be wired using the following method ZONE 1 to 9 CONNECTION 2K2 RESISTOR ZONE 1 4K7 RESISTOR ZONE 9 COMMON CONNECTION EXPAND 1 Zones 1 8 2K2 EOLR Red Red Black Brown Brown EXPAND 2 Zones 9 16 4K7 EOLR Yellow Violet Black Brown Brown End of line resistors must be 1 The 16 expansion zones are normally grouped into two banks of eight Each group uses a zone of the Control Panel Do not forget to fit the panel s 2K2 End of line resistor ZONE EXPANDER 5000 8 ZONE CONTROL PANEL ALARM 1 8 e ZONEI ZONE2 ZONEEXPANDER ALARM 9 16 IMPORTANT NOTES 1 The default settings have Expansion Zones 1 8 and 9 16 driving their respective outputs Using P423E P623E and P424E 624 it is possible to change the 8 8 split For example suppose you want 12 PIRs as Instant zones and 4 others as 24 Hr zones then do the following use P423E to select all 8 Zones to drive the 1 8 output use P623E to select 4 zones to drive the 1 8 output The remaining 4 zones will drive the 9 16 output Connect the 1 8 output to the Panel and programme the panel as Instant Connect the 9 16 output to the Panel and programme the panel as 24Hr
66. itivities PISE 5E There are 8 sensitivities Refer to the following test procedure for testing the sensitivities P 12 maximum sensitivity through to P 19 minimum sensitivity DEFAULT NO ZONES VIBRATION SENSITIVITY no zone lights on To VIEW Vibration Sensitivities ENTER To ADD zones ENTER PROG 12 to 19 END ZONE NUMBER END Page 13 AERA TEST PROCEDURE A special test facility exists to test the operation of any zone without leaving the Installation Program mode This is especially useful for setting up and testing the sensitivity of the vibration sensors 1 Assign the zone which the vibration sensors are connected to to be a 24 Hour Audible zone P4E zone E 2 Set the vibration sensitivity as shown above to Medium sensitivity eg P 14 E or P 15 E for that zone 3 Locate the sensor and cause some high frequency vibration within its vicinity This is best achieved by using a solid object such as a screwdriver end NOTE Nessensors are very sensitive to high frequencies and insensitive to low frequencies Therefore it is not necessary to apply much force to the protected structure rather a very rapid succession of blows instead 5000 Series Dialler If sufficient vibration has been created to cause an alarm then the sirens will be activated for 2 seconds The sensitivity has been correctly adjusted when a single blow applied with a soft object eg by hand does not cause an alarm wher
67. ler is inactive EXPAND FLASHING SLOW The dialler senses a phone line fault or a failure to communicate with the base station FLASHING at the incoming call rate The dialler is detecting an incoming call ZONE INDICATIONS There are 8 Zone indicator lights above the keypad In normal operating mode they show alarm the following states OFF Zone secured ON Zone unsecured Page 9 OFF The panel is Disarmed OFF No alarms FLASHING SLOW An alarm is stored in memory OFF No zones are EXCLUDED ON The panel is in client program mode FLASHING FAST The program memory is faulty FLASHING The panel battery is low If flashing in unison with the satellite light the satellite battery is low FLASHING The mains power is disconnected or turned off FLASHING The panel or satellite siren tamper are unsecured If flashing in unison with the battery light the satellite battery is low ON The dialler has seized the phone line a dialler or zone expander option is selected FLASHING FAST The dialler or zone expander has a System fault or the dialler cannot store the information just programmed into it FLASHING FAST Primary alarm ie indicates the first zone to become unsecured and cause the FLASHING SLOW Secondary alarm ie indicates those zones that have become unsecured during the Alarm Reset time As explained elsewhere in this manual these zone lights are used to indicate other information in the Memory Ex
68. lite For wiring details for the Remote Keypads Keyswitches Panic Buttons and Satellite sirens see the terminal designation card Additional keypads may be connected in parallel Page 6 AERA 5000 Series Dialler The 8 Zone Control Panel contains the following outputs SIREN A Oscillating output fused via F3 1 5A for connection of TWO 8 ohm horn speakers MAXIMUM SIREN B Oscillating output fused via F4 1 5A for connection of TWO 8 ohm horn speakers MAXIMUM NOTE An absolute maximum of three horn speakers only can be connected to SIREN A and SIREN B outputs ie 2 speakers on siren A and 1 on siren B or vice versa STROBE Latched 12 Volt alarm output fused via F2 1 5 A RESET OUTPUT Resetting 12 Volt alarm output fused via F2 1 5A NOTE A TOTAL current of 1 5 Amps only is available from the STROBE and RESET OUTPUTS SATELLITE SIREN Four wire connection to NESS 5000 SERIES SATELLITE ONLY The satellite s battery charging circuit is fused via F2 1 5A The other terminals are current limited 24 HOUR LATCHED ALARM OUTPUT PINS Open collector switched negative sinks 100mA This output is switched on when a 24 hour alarm occurs ie 24 Hr zones Tamper and Panic MONITOR LATCHED ALARM OUTPUT PINS Open collector switched negative sinks 100mA This output is switched on when a Monitor zone alarms refer to Instruction manual for programming AUXILIARY OUTPUT TERMINAL
69. lose 11 Battery fail iv Mains fail and v Zone exclude It is not permitted to send Zone reports down this channel Zone Tamper Panic and Duress etc can only report on channels 1 8 It is possible however to allow 2 or more different Zones to report on one channel P71E 12E channel E Zone 1 assigned to a channel choose 1 8 P72E 12E channel E Zone 2 assigned to a channel choose 1 8 P73E 12E channel E Zone 3 assigned to a channel choose 1 8 P74E 12E channel E Zone 4 assigned to a channel choose 1 8 P75E 12E channel Zone 5 assigned to a channel choose 1 8 P76E 12E channel E Zone 6 assigned to a channel choose 1 8 P77E 12E channel E Zone 7 assigned to a channel choose 1 8 P78E 12E channel E Zone 8 assigned to a channel choose 1 8 P63E channel E Tamper report choose 1 8 P98E Clears dialler to factory default settings will also clear user codes 05 to 015
70. me in minutes 1 99 PE CLIENT PROGRAMMING Program light on steady PIE code code P2E code E code E P3E code E code E P4E code E code E Code 1 Master Code Code 2 Code 3 Code 4 Codes can be 3 6 digits in length but cannot start with a 0 PSE time E Entry time in seconds 1 99 P6E time E Exit time in seconds 1 99 P7E option E 1 Entry delay the full alarm 2 2 seconds siren and sonalert 3 Immediate full alarm 4 Zone number pulsed via sonalert 8 zone E Monitor zones P9E zone E Auxiliary zones Exit Client mode PE To re enter Client program mode P Master Code E To re enter Installation mode P 000000 E Note Entry to Installer mode can only be made while in Client mode Normal operating mode Battery and Mains light ON 5000 Series Dialler Programming Typical program for Central Station Communication P31E telephone number E P32E telephone number E P34E client account number E P36E 3E Selects Ademco H S Format P44E 1E 2E Allows test calls P45E hours E Time between test calls usually 168 P46E hours E Time before first test call P57E 9E Open Close reports enabled P59E 9E Battery fail selected P61E 9E Mains fail with abort time selected P62E 9E Test call report enabled P70E 9E Zone exclude reports enabled Note Ademco High Speed format has certain fixed reporting requirements These are as follows Channel 9 can only be used for 5 alarm reports These are 1 Test calls Open C
71. mode either a Press 8E OR b If you are using a Remote Keyswitch first Arm the Panel by turning the keyswitch once then turn the keyswitch twice within 2 seconds The Control Panel will respond with 3 beeps and the Armed Monitor indicator will FLASH to indicate that you are in Monitor mode Monitor mode cannot be selected while in Program memory or Exclude modes To EXIT from monitor mode either a Enter CODE E to DISARM OR b Activate the keyswitch momentarily to DISARM OR c Enter OE or 0 CODE E to ARM the Panel NOTE If an alarm occurs while in Monitor mode silence the alarm by entering CODE E or activate the keyswitch If an alarm does occur in Monitor mode the zone light will remain flashing as a memory until you exit Monitor mode EMERGENCY FUNCTIONS 12 ADH HCH SOR CSO kkkhh kkk kkk For personal protection the Control Panel contains an INSTANT panic feature Panic can be used to Scare away intruders inside or outside your premises Summon help from friends or neighbours Test the operation of the siren Three Emergency functions exist MEDICAL A silent alarm that is only used if the Alarm system is monitored remotely eg Central Station FIRE An audible alarm that activates sirens and will transmit the alarm signal if monitored remotely eg Central Station PANIC This function may have been programmed to be either EMERGENCY 1 ENTER 3E The siren will soun
72. ned momentarily to ARM the Panel 1 CHECK that all windows and doors are securely locked 2 Enter 0 END or 0 CODE END 3 The ARMED light should be ON and the keypad should beep 3 times 4 Leave the premises within your Exit Delay Time 5 At the end of the Exit Delay Time three beeps will indicate successful Arming If something is wrong when Arming the control panel the normal 3 beeps will be replaced by other warnings 10 BEEPS Indicates either a Mains fault Control Panel Battery fault or Satellite Siren Battery fault LONG BEEPS Warn that a zone is unsecured Eg 4 long beeps if zone 4 is unsecured CONSTANT TONE Indicates a 24 hour zone is unsecured Tamper Panic or 24 hour zone 11 SIREN WARNING At the end of the Exit Time all zones should be secured If any are unsecured the siren will sound as a warning to indicate that those zones have been automatically Excluded For maximum security you should return DISARM check the premises and then ARM again Continual warnings could mean that a detector is faulty and may have to be manually Excluded If the Auto Exclude option is disabled the siren will sound continuously if a zone is unsecured at the end of Exit Time DISARMING THE CONTROL PANEL SOR I SCOR CSR CSCO I COE CSCO A CORI COO ICSE A SCOR COO ACCOR I SCOR OR COR ISCO OI COO CSCO OI SCO OR CSO I SCOR COSI ICO CSCO OR CSRS Upon entering the protected premises th
73. options can be a Programming options carried out in any sequence All programming operations follow the pattern b Programmed Values shown below Select your option and view the current value PROG Option END enter the new value Value END Value END One long beep indicates an invalid entry Each zone can be independently programmed to any ONE of the six following options Instant Delay Handover Secondary Delay 24 Hour Audible 24 Hour Silent ULULULULU Options cannot be deleted only changed by the selection of another option If more than one zone is required to be programmed for a particular option say zone 2 zone 3 and zone 4 then enter P option E 2E 3E 4E As each zone is programmed the corresponding zone light is illuminated Page 10 REA VE 5000 Series Dialler SETTING A ZONE TO INSTANT P 0 E Sese e e ie e e ok oe ok oe E oe se oe sese sese sere sese sese k 9 R eese e oe oe oe oe oe oe oe oe R R k R eee oe oe oe oe oe ole oe OR HE An Instant Zone triggers an alarm the moment To set say zone 1 and zone 3 to be instant the zone is unsecured This can only occur enter when the Panel is Armed and the Exit Time has expired POE 1E DEFAULT ZONES 2 to 8 INSTANT zone lights 2 8 on TO VIEW Instant option ENTER To ADD Instant zone s ENTER PROG 0 END ZONE NUMBER END
74. ramming of the telephone numbers it is occasionally necessary to enter a special PAUSE digit To do so press and hold the E button for at least I second For example to programme a telephone number commencing with 0 PAUSE 4 press 0 long E 4 etc During the telephone number display the PAUSE digit is represented by the TAMPER SATELLITE indicator NOTE each PAUSE z 2 5 seconds Page 14 REA LZ 5000 Series Dialler EXTRA CODES The Dialler provides 11 extra codes which can be used in exactly the same manner as the first four of the Control Panel To programme say Code 5 to be 446 first enter the PROGRAM mode and then press the buttons 5 4 4 6E4E6E Similarly to programme Code 15 press the buttons P 01 5 E code code E Note the leading 0 for the option number of these codes EXTRA TELEPHONE NUMBER An extra telephone number has been provided for your use if so required Using this number it is possible to have the Dialler ring the Central Monitoring Station and then to ring you at home It can even give you an audible status report to tell you whether the Control Panel is Armed or Disarmed and what zones have alarmed Alternatively the number can be used to call a beeper type pocket pager to tell you that an alarm has occurred Your installer will advise you of exactly how the Dialler can be used to meet your needs If necessary the installer can allow you to change this extra telephone number which c
75. rough a delay zone the Control Panel responds with BEEPS AT ONE SECOND INTERVALS as a reminder to Disarm You then have your programmed Entry Delay Time to Disarm the Panel by either a Entering one of your access codes and END OR b Activating the keyswitch If the Panel is not Disarmed by the end of the Entry Delay Time an alarm will occur You may still enter your code to silence the alarm 1 ENTER the protected premises via a DELAY ZONE 2 LISTEN for the beeps coming from the panel 3 Enter CODE END 4 The ARMED light should now be extinguished A Continuous beep on entry is a warning that an alarm occurred while the Control Panel was Armed the external strobe light If fitted will also be flashing as a reminder If one of your codes is say 7676 then to Disarm enter 7676 E If you make a mistake in entering your code then you must press E and start again Three incorrect entries will cause an alarm The 1 second entry beeps not the continuous warning can be disabled as a function of the installation options MONITOR etttettetkeoeletotoeleletotokeletototeleletetojoleletotojoleletotoleleletotoleleletotoleleletotoleleletotoleletototoleletotojeleletotejeleletoteleleletoteleleletotolelelototolelelotoleleletotol Monitor mode allows you to ARM selected zones while others are ignored Typically Perimeter zones doors and windows can be Monitored while the occupants are at home To select MONITOR
76. secure each zone in turn the buzzer and all sirens will sound for two seconds each time a zone is triggered 4 Reprogram each zone to their correct type after completion of the walk test Page 18 METHOD B 1 Select normal operating mode 2 Select Monitor Mode 8E 3 Un secure each zone in turn the buzzer and all the sirens will sound for two seconds each time a zone is triggered 4 Return to the Panel and ensure all zone lights are flashing to indicate that they have been triggered AERA 5000 Series Dialler SYMPTOM Control Panel not Starting up when AC voltage is applied Starts up Armed and in alarm with finger on the P or E button The Control Panel alarms on exit from Installation Program mode Cannot exit from Client Program mode using PE Panel automatically exits Client Program mode Program light flashes rapidly after exiting Client Program mode Programmed values are not retained in memory when power is removed from the control Panel and then re applied The Panel goes into alarm when Disarming the Panel with a 5000 SERIES keyswitch The Heat Sink is warm to touch CAUSE Excessive load connected to the Power supply Current limit protection operating Keypad tail connected incorrectly or the keypad is faulty 24Hr zone Tamper or Keyswitch Panic inputs unsecured Client Code 1 Master Code not programmed For security Client Program mode automatically exits
77. secured The Panel has been powered up initially on AC and has not yet been Armed the battery is not connected or the battery is flat 3mm Polycarbonate 233 wide x 300 high x 85 deep 3 3 kg Input 240V a c Less than 80 mA 10 V to 15V d c 12 V 6 5AH 450 mA maximum current limited Every hour and when the Panel is Armed whether mains power is on or off 10 7 V with a 5A load 4x1 5A fast bow REMEDY Trigger the zones after Exit Time Check for short circuits on outputs and replace blown fuses Ensure a 2K2 ohm is fitted to the keyswitch Panic input and that all tamper and 24Hr zones are secured Disarm secure the unsecured zone and re arm Check the rear Panel Tamper front Panel Tamper and External Tamper switches are all secured with the relevant values of resistors All Tampers are wired in series as far as the Panel is concerned Arm and Disarm the Panel which will cause a dynamic battery test to be carried out Connect the battery or replace the battery Output 17Va c at 1 4A 13 8 V d c at 1 25 Amps current limited End of line resistor 2200 plus minus 900 ohms Same as zone input Same as zone input Proprietary Proprietary Open collector fused Open collector fused Proprietary 3x 8 ohm ohm speakers not including Satellite sirens since they have a separate siren driver circuit 1 5 Aat 12 V open collector fused With battery 12 V 1 5 A fused 1 5 A at
78. sion was made to the Primary telephone number within 5 calls Only one of the above options is allowed and the default is 1 Allow the Extra telephone number to be used Disable the Test Status Reports when the Dialler Auto Answers see P44 Options 4 and 5 may be chosen in addition to the other options DIALLER 1 and 2 TRANSMISSION FORMAT P36E option E If no acknowledge tone is received transmit in the NESS Audible format If transmitting in Low Speed format old alarms which are still active are to be included in the transmission If a high speed acknowledge tone is received transmit using the Ademco Extended format Invert 8 9 for Open Close in Low speed format If an acknowledge tone is received from a beeper type pocket pager system do not transmit any alarm reports None one or all of the above options may be chosen and the default is none The Dialler always transmits in the format identified by the Acknowledge tone but this may be modified by the above Page 6 REA LZ 5000 Series Dialler TYPE of DIALLING P37E option E l Use Decadic or Touch Tone dialling depending on the type of dial tone received First call only 2 Use Decadic dialling only 3 Use Touch Tone dialling only 4 Use Touch Tone dialling only and dial using Telecom Australia s EASY DIAL facility Only one of the above options is allowed and the default is 1 5 Dial as above even if a Dial tone is not received 6 Use
79. t ON when a Line Fault is detected 2 Turn output ON when a Kiss off tone is not received 3 Turn output ON when a Kiss off tone is received 4 Turn output ON when a Command tone is received If this option and Arm via Command Tone P44E are both selected then receipt of the tone will operate both the Auxiliary output and Arm the panel simultaneously 5 Turn output ON when the panel is Disarmed Only one of the above drive options is allowed and the default is 0 6 Output follows the drive condition 7 Output toggles on each occurrence of the drive condition 8 Output will Pulse on each occurrence of the drive condition Only one of the options 6 7 and 5 is allowed in addition to one of the other options TIME DELAY BEFORE PULSING the AUXILIARY OUTPUT ON P 42 E time E The Auxiliary output may be delayed by this preset time if the option 8 Pulse is chosen in P41E above The default time is 0 seconds but it may be set from 0 seconds to 120 minutes as follows 0 to 100 0 to 100 seconds 101 to 220 1 to 120 minutes TIME PERIOD of the AUXILIARY OUTPUT PULSE P 43 E time E The Auxiliary output will stay on for this preset time if option 8 Pulse is chosen in above The default time is 1 second but it may be set from 0 seconds to 120 minutes in the same manner as P42E Page 8 REA LZ 5000 Series Dialler RING DETECT and TEST CALL OPTIONS P 44 E option E Enable Auto Test calls when Armed Enable Auto Tes
80. t at the time of going to print NESS Security Products reserve the right to make changes so the features and specifications at any time and without notice in the course of product development TABLE OF CONTENTS INTRODUCTION Terminology Features 5000 SERIES Optional Equipment Specifications CONTROLS AND INDICATIONS Keypad Audible Indications Visual Indications Zone Indications PROGRAMMING How to Enter Program Mode How to Program Access Codes Entry Delay Time Exit Delay Time Monitor Mode Type Zones to be Monitored Zones to Control the Auxiliary Output Programming Summary Nn ON UA Q tA NO XO 1 100 OPERATION General Information 10 Operating Rules 10 Arming the Control Panel 10 Disarming the Control Panel 11 Monitor Mode 11 Emergency Functions 12 Zone Expander Functions 12 Alarms 13 Resetting an Alarm 13 Alarm Memory 13 Excluding Zones 14 Including Zones 14 Auxiliary Output 14 TESTING AND TROUBLESHOOTING Testing 15 Troubleshooting Guide 16 Operation and Zone Summary 17 Thank you for purchasing a NESS 5000 SERIES Control Panel Please do not be frightened by its apparent complexity The Panel is very powerful but also very easy to use and you only need to use as many or as few features as you require At the very least you need only know how to ARM and DISARM the Panel plus have a basic understanding of the indicators Please take the time to read this manual so that yo
81. t calls when Disarmed Enable Call Back calls when Armed Enable Call Back calla when Disarmed Enable Auto Answer capability when Armed Enable Auto Answer capability when Disarmed Enable the panel to be Armed on receipt of the Command tone If already Armed the tone will be ignored unless it has been programmed to drive the Auxiliary output as well See P41E option 4 None one or all of the above options may be chosen and the default is none Select both options 1 and 2 to enable Auto Test calls always TIME BETWEEN AUTOMATIC TEST CALLS P 45 E time E Automatic Test Calls are identified as such at the Central Station and are used to check the integrity of the Dialler and the telephone line To use the facility the Test alarm P62E must be enabled by assigning it a channel number Then set the time between Test Calls using this option This time defaults to 168 hours but may be set from half hourly to 250 hours A conversion table of hours to days is shown below 0 half hourly 24 1 day 120 2 5 days 1 hour 48 2 days 144 6 days 2 2 hours 72 3 days 168 7 days 9 9 hours 96 4 days 240 10 days TIME REMAINING BEFORE FIRSI TEST CALL P 46 E time E After installation set this time to position the first Automatic Test Call at the required time This option defaults to 0 hours but may be set from 1 to 250 hours The time commences on Exit from installation Programme mode DOUBLE RINGS NEEDED FOR CALL B
82. t triggering an DEFAULT NO HANDOVER ZONES alarm no zone lights on To VIEW Handover option ENTER To ADD Handover zone s ENTER PROG 2 END ZONE NUMBER END SETTING ZONES TO SECONDARY ENTRY DELAY P 3 E LLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLDLLLLLLLLLLLLLLDLLLLLLLLLLLDLLLLLLLDLLLLLLLDLLLL LLL LLL LLL A Secondary delay zone is essentially the same The garage door may be programmed for a as a normal delay zone except that its Entry Secondary Delay where both the entry and exit Time is equal to the programmed Exit Time It times equal the programmed exit time say 60 can be used to provide additional entry time for seconds a second entry path eg garage door To set say zone 4 to be a secondary delay Thus a front door may be programmed for an Exit Time of say 60 seconds and an Entry Time P3E 4E of 20 seconds for high security DEFAULT NO SECONDARY DELAY ZONES Page 11 REA VE 5000 Series Dialler SETTING ZONES TO 24 HOUR AUDIBLE P4 24 Hour Audible zone is a zone which triggers To set say zone 7 and zone 8 to be 24 Hour instantly after ft is unsecured whether the panel Audible enter is Armed or Disarmed P4E 7E 8E The alarm is audible and therefore the sirens and internal noise makers are activated DEFAULT NO 24 HOUR AUDIBLE ZONES no zone lights on To VIEW 24 hour Audible option ENTER To Add 24 hour Audible zone s ENTER PROG 4 END ZONE NUMBER END SETTING ZONES TO 24 H
83. tamper is secured 4 Close the lid of the Control Panel FAILURE TO COMPLETE THESE TASKS WILL RESULT IN THE CONTROL PANEL GOING INTO ALARM AS SOON AS INSTALLATION PROGRAM MODE IS EXITED You are now ready to exit the Installation Program Mode and enter the Client Program Mode This is done by entering P E Page 17 Upon entering the Client program mode the PROGRAM light will stop flashing and will be constantly illuminated NOTE It is important that you enter the master code at this point Client Program mode will automatically be exited if a button is not pressed within 2 minutes 1 1 code code Entering master code will allow you to re enter the Client program mode if the panel has entered the normal operating mode SEE THE INSTRUCTION MANUAL FOR FURTHER INFORMATION NOTE All the programmed information is not stored to memory until the panel has exited Client Program mode into normal operating mode Therefore It power is disconnected during Installation or Client Program modes all NEW programmed information will be lost AERA TESTING AND TROUBLESHOOTING To ensure reliable operation of any system correct testing procedures should be carried out prior to handing the competed installation over to the customer Using a digital multimeter the following procedures are recommended for testing a 5000 SERIES 8 Zone system FUSES With the power removed from the Panel set your met
84. then either the Dialler or the Zone Expander is faulty and should be repaired as soon as possible OPTIONAL FEATURES Your installer can provide one or more of the following simple features if required to help you maintain maximum security Operate the siren and strobe on detection of a telephone line fault Operate the siren and strobe after an unsuccessful series of calls to the Central Monitoring Station Indicate a successful call to a Central Monitoring Station by beeping the siren 3 times used when Arming Indicate a successful call to a Central Monitoring Station by operating the strobe for 3 seconds used when Arming Operate the Dialler s AUXILIARY output on detection of a line fault after a successful call or after an unsuccessful call Page 13 REA LZ 5000 Series Dialler REMOTE CONTROL STATUS REPORT An optional REMOTE CONTROL device may be purchased to either Arm the Control Panel via the Dialler or to operate the Dialler s AUXILIARY output from a remote location These features can only be enabled by your installer To use the unique Remote Control features ring your Dialler and wait for it to answer as follows 1 long beep Control Panel DISARMED Auxiliary output OFF 7 short beeps Control Panel ARMED Auxiliary output ON You then have 5 seconds to place the Remote Control device near the mouthpiece of the telephone and press the button to send a special tone to the Dialler Once this tone is received
85. throughout this manual The following is a brief system description GENERAL The 8 Zone Panel is constructed of Polycarbonate which is a material used in many high security applications such as bullet proof glass The panel is designed to meet or exceed Australian Standard AS 2201 Many features are provided to ensure Ease of installation and service eg removable lid clip in PC boards and plug in terminal blocks Flexibility eg full Programmability via the inbuilt Keypad System Integrity eg Dynamic Battery Test High Security eg inbuilt Vibration Tamper MODES OF OPERATION The Panel may be operated in 3 modes 1 Installation Program Mode enables system parameters such as Zone types Delay Instant Handover etc to be programmed or reprogrammed by the installer 2 Client Program Mode allows a client with a Master Code the capability of programming User Codes Monitor Zones Entry and Exit times etc 3 Normal Operating Mode allows day to day operation by one or more clients POWER A C power is supplied from the mains to the panel via a Plug pack transformer which also provides an Earth connection to improve the Lightning Protection A Stand by Battery is fitted to ensure that the system continues to operate it mains power is interrupted The A C power is checked continuously while the battery is checked every hour and whenever the system is Armed Battery testing is performed under load for
86. u understand the full benefits of the 5000 SERIES Control Panel TERMINOLOGY eetttettctioletotooeletototoeletotokoleletotojoleleletoleleletotoleleletotoleleletotoleleletotoleletetotoleletetojoleletotojoleletetejeleletotoleleletotoleletetotoleletetotoleletol The microcomputer based 8 Zone CONTROL PANEL forms the heart of your security system and connects to all other equipment Each ZONE of the Panel will be connected to one or more detection devices to protect an area such as the front door hallway windows etc The Panel is said to be ARMED when it is set to detect an intruder At other times it is DISARMED Normally a zone is considered SECURED Activation of a detector will cause the zone to be UNSECURED and may cause an alarm Detectors such as fire detectors and panic buttons must be able to generate an alarm at all times regardless of the Panel setting A zone with this assignment is called a 24 HOUR ZONE Before leaving the premises you must ARM the Panel to enable it to detect intruders and generate an alarm After ARMING the Panel will ignore most detectors for the EXIT DELAY TIME to enable you to depart without triggering an alarm When you enter the premises the Panel will ignore selected zones for the ENTRY DELAY TIME and will not alarm unless you fail to DISARM the panel during this allowed time If you wish to protect one area while you occupy another MONITOR MODE allows selected zones to be Armed while leaving
87. value E none P71E channel E value E to none P78E channel E value E 5000 Series Dialler Installer Access Code Set all options to default Primary telephone no Secondary telephone no Extra telephone no Dialler 1 Client Account no Dialler 1 Reporting options Dialler 1 Transmission format Type of dialling Time to wait for Acknowledge tone Number of dial out attempts Output control and indication options Auxiliary output drive Time before Auxiliary output pulse Time period of Auxiliary output pulse Ring Detect and Test Call options Time between automatic Test Calls Time before first Test Call Double rings for Call Back Double rings for Auto Answer Abort Time Delay Time delay for Medical alarm Arm I Disarm Open Close Control Panel fail Battery fail Satellite Battery fail Mains fail Test Tamper alarm Keypad Code alarm Keypad Medical alarm Keypad Fire alarm Keypad Panic alarm Keyswitch Panic alarm Duress alarm Zone Excluded partial Seal Zone 1 alarm to Zone 8 alarm Page 12 REA VE 5000 Series Dialler INSTRUCTION MANUAL DIALLER OPERATION If you have a 5000 SERIES Dialler fitted to your 8 ZONE Control Panel you are provided with many additional features as well as the capability to transmit alarms to a Central Monitoring station This manual is designed to provide instructions on those Dialler features which may be under your control
88. when no keys are pressed within a two minute period Access Code 1 Master Code not programmed and panel has automatically exited Client Program mode OR Program memory faulty hence Panel cannot save data in the EEPROM Power removed prior to exiting Client program modes All programming is stored to memory on he exiting of Client Program mode OR The system has been powered up into Installation program mode using the P button thus re loading all default values Entry zone has not been activated prior to using the Keyswitch if the Entry restriction on the Keyswitch has not been disabled 21E 1E Normal operation Page 19 REMEDY Check for short circuits and excessive load on the power supply outputs Check Keypad connection or replace For security all 24Hr Tamper and Panic circuits operate in Client program mode Ensure they are secured before entering Client program mode Program Access Code 1 prior to exiting Client Program mode Avoid leaving the Panel in program mode without pressing buttons for long periods of time Program Master Code as soon as possible after entering Client Program mode Power down and Power up using the End Key and exit both Installer and Client program modes again If the light still flashes return Panel for service Exit user program mode to operation mode Do not remove power during any programming Enter Installer Program mode by powering up with E

Download Pdf Manuals

image

Related Search

Related Contents

greenwood deck - Materials plus  Agilent 8453 UV-Vis Spektrosokopie-System  Kingpin Screens Velvet Framed Screen  GUIDE DE L`UTILISATEUR  IQBoard ET & PS V7.0 User Manual  MANUAL DE INSTRUCCIONES  Swingline Precision Pro  CMU 100 - WORK PRO Audio  「国立女性教育会館宿泊室用椅子」入札公告【PDF】  Edimax EW-7415PDn  

Copyright © All rights reserved.
Failed to retrieve file