        0044-003-01 User Guide.qxd
         Contents
1.                                                                 e Press  lt 4 in this menu to enter the Pass Code      Press x to put the system into Sleep    18    Menu Layout User Menu   Descriptions                               Controller parameters                      System Controller    System Controller  Software Version    Power Mode     Hi A    or    Lo A Status    Fire Delay                Fire Threshold          Received Signal Compensation Level  Percentage                         Detector parameters    Detector Status Temperature Distance Fault Delay    Info    Detector Software  8   50m or 50   100m    Version    Centigrade or Fahrenheit       19       Menu Layout Engineering Menu    tp  D  si    a    a     ADe Oue     OD ehbguke    Home Position Detector Settings LASER Targeting Beam Alignment Fire Threshold                 Controller Settings Software Utilities Fire Test Fire   Fault Delay    tr  Ei    ef d e  4D  h0G6  k uf   Deeoeae che    fD  amp holQue Ae GHGS        The Pass Code must be entered to access the Engineering Menu  e The menu is navigated by using   lt   gt  keys to move the cursor     Items are selected by using 74    e Pressing 3    exits this menu and returns the system to a    locked    state    20    Menu Layout Detector Settings       Default is Non Latched                      BSS   E a   7  fe       e en mae                                    Auto Optimise Motor  Movement On   Off    Set Distance Set Fire Latch   Reset       Set Dete
2.      0 3 Deg Range 1 to 255  Indicates the level of amplification  Receive Gain applied by the receiver  Set automatically by Auto Align    Operating Voltage    Operating Current     Low Power Mode       52 mA Power Mode    LOA       D  0    Operating Current     High Power Mode  Fire Threshold Range    Delay to Fire   Delay to Fault   Operating Distance between Detector and Reflector  Maximum angular misalignment of Detector    Maximum angular misalignment of Reflector   5 Deg    2999 Fire Threshold Range 10  to 60   Sets the amount of obscuration  850 nm required for the Detector to signal a Fire    Maximum angular movement of Detector head  o  Optical wavelength 35     Rapid obscuration Fault threshold 87  Range 2s to 30s  Sets the time the system needs to    Delay to Fire i      0    37 8 Deg C be below the Fire threshold before signalling a Fire  Range 2s to 30s  Sets the time the system needs to   10    55 Deg C be below the Fault threshold before a Fault is  Delay to Fault i   40    85 Deg C signalled  Note the signal needs to fall to  lt  13  within 2s    8   50m or 50   100m  Sets the distance between  IP54 Distance Detector and Reflector  Affects the initial transmit 8 50m  30V DC power at the start of Auto Align    100 mA Auto Optimise Disables or enables Auto Optimise  the automatic On  100 On Off beam movement function   m    Latched non  Sets if the system will latch Fire or automatically reset  Non   24   14 AWG latched Faults are always non latching  latching 
3.    English    IMPORTANT    PLEASE NOTE  The infrared beam path MUST be kept  clear of obstructions at all times     Failure to comply may result in the Detector initiating a  Fire or Fault signal        Oo           ON    12    13  14  15    16  17  18  20  21  22  23  24       Installation  General Information  Fitting the Product  Wiring Diagrams    Commissioning  Apply Power and Enter Pass Code  Select Power Mode and Distance  LASER Targeting     Auto    Alignment and    Set    0 100  Calibrate     In Use  Settings and Final Tests  Cleaning  Manual Fire and Fault Tests    Troubleshooting  Error Codes  LASER Not Visible  Home Position    System Information  LCD Icon Layout  Status Indicators  User Menu Layout  Engineering Menu Layout  Detector Settings Menu Layout  System Controller Settings Menu Layout  Operating Parameters and Dimensions  Approvals and Territory Specific Information    Installation General Information               50   100m   x4                18   50m   x1    50cm 8   18m   x1  ia Di 8 100m 7 Use Short Range Mask  Ensure clear line of sight Mount on solid surfaces  structural wall or girder     from Detector to Reflector         Check the beam spacing against local regulations    Position beam as high as possible  but with a minimum ve  distance of 0 5m from detector to ceiling    Mount Detector and Reflector directly opposite each  other    Do NOT position detector where personnel or objects    can enter the beam path f      x    Installation Fitting t
4.  0 5   1 5 mm    Operating Temperature  UL Approved   Operating Temperature  EN54 12 Approved     Storage temperature    Relative Humidity  non condensing  93   IP Rating   Relay Contact Voltage  Relay Contact Current    Maximum Cable Length  Controller to Detector              O O  N n  D     O O  J     Q  ok  N n    Cable Gauge    Housing Flammability rating UL94 VO Dimensions Width  in  mm  Height  in  mm  Depth  in  mm  Weight  Ib  kg     System Controller  including base 2 0  0 9   Detector  including  easy fit  base 1 1  0 5   Universal Bracket 0 4  0 2   Reflector  Single  0 2  0 1    Protective Cage   5 4    136  6 2  157  j  0 3  0 13        Approval Information       24    UL Approval Information    UL File Number  83417    Distance between Fire Threshold  Detector and Reflector Range    10   15m  32 8   49 2ft   22   40m  72 2   131 2ft     40   60m  131 2   196 8ft  35   50   60   100m  196 8   328 1ft     All installations should comply with NFPA72          Territory Specific Information    European Approval Information    CE    0832    Fire Fighting Enterprises Ltd  9 Hunting Gate  Hitchin   SG4 OTJ  UK    07  0832 CPD 0565    EN54 12    Line Detector using an Optical Beam  Fire Safety  Documentation  See doc  0044 003    Complies with EN54 12 for sensitivity levels between 25   and 35  with a maximum delay to fire of 20 seconds   Protective cage must be fitted to comply with EN54 12     Document Number  0044 003 05    
5. System Controller   to test the wiring to the Fire                      Confirm screen Fire screen    Control Panel Detector will signal Fire  System Controller signals  System Controller will    Fire    to Fire Control Panel  stay Normal    Press Yor X to  Press X to exit ayit  without performing the  test    11    Cleaning the System  Performing Manual Fire and Fault Tests       Cleaning the System    The system will automatically compensate for dust  build up by changing the Compensation Level     However  it is recommended that the Detector lenses  and the Reflector are cleaned periodically with a soft  lint free cloth     If the Compensation Level remains above 130 for  several days  this indicates that cleaning should take  place     The system should be isolated from the Fire Control  Panel before cleaning takes place     After cleaning  verify that the system is operating  normally     If the Signal Strength is between 90  and 110     leave the system to compensate back to 100    this should take no more than 12 hours     If the Signal Strength is above 110      reduce Compensation Level until Signal Strength  is 90   110   and wait for system to compensate  back to 100     If the Signal Strength is below 90     perform LASER Targeting  Auto Align  and Set     12    How to change Compensation Level                                                        Manual Fire and Fault Tests    After installation or cleaning  it is recommended that a  manual Fire and Fault test i
6. and Distance    3  Select Power Mode 4  Select Distance between Detector and Reflector    e All functions can be performed in    Lo A     10mA  e Select 8 50m  default  or 100m  mode  default     e Select    Hi A  50mA  to enable faster beam movement  during Auto Align and Laser Targeting    e After installation  set the system back to    Lo A                                        4                                                                   1  Use VO to move between 4  Use AY to  icons in the Engineering Menu  change selection    to highlight the icon shown       5  Press V  to accept  2  Press v   to select  Press K  to cancel    3  Use to move to            required item       Menu Navigation    Commissioning LASER Targeting    5  LASER Targeting    The system will signal Fault while in this mode                The LASER is used to align the Detector with the Reflector  It  is an approximate alignment tool only  After Auto Align the  LASER may not be aimed directly at the Reflector      Use  K   gt       v  to move the LASER as close to the  Reflector as possible   One press of an arrow key results in one movement of   the Detector head   Press    or X to turn off the LASER and return to the  Settings menu    Refer to User Guide page 14 for troubleshooting if LASER  is not visible    Commissioning                                           LASER RADIATION   AVOID  DIRECT EYE EXPOSURE    POWER OUTPUT  lt  5mW    CLASS Illa LASER  Wavelength 630   680 nm    Commissioni
7. ctor Number                    Set TX Power    Set Compensation Level    Set RX Gain     Set Zero   100        Info      ONLY AVAILABLE ON MULTI DETECTOR UNIT    WARNING  ENGINEERING USE ONLY  ALTERING MAY CAUSE MALFUNCTION    21    Menu Layout System Controller Settings                                   Power Mode Units of Measurement    Change Pass Code       MANSINI e Units of Measurement  Changes between    Metric    and    Imperial     Care must be taken when  changing the Pass Code  e Change Pass Code  If the code is lost  the unit Use   lt     gt   to access each digit  cannot be unlocked and E  must be returned to the Use  wv   A  to change the digit    manufacturer  This is not  covered by the warranty     Press Y to save the new Pass Code and return to the settings menu  Press X to cancel the change and return to the Engineering menu       System Information Operating Parameters and Dimensions    Parameter Value Parameter Description Default    14   28V DC Pass code User Code required to access Engineering Menu 1234    8   12 mA    Hi A     System will operate at 50mA constant current  consumption     Lo A     System will operate at 10mA constant current    0 45   3 98 dB consumption  10   60  Range    50 to  205  Level of amplification applied to    SI compensate for dust build up and building movement  sani At 75 Auto Optimise is started    2   30 s T 1 Range 50 to 4095  Indicates the optical power output   ransmit power  8   100 m Set automatically by Auto Align 
8. he Product       Installation       Options for Detector wiring  orientation                                                                      LED indicator must face downward    Installation Wiring Diagrams    TO THE TO THE  DETECTOR DETECTOR       CON C                   ZONE   ZONE                SUPPLY    _  SUPPLY      P  EARTH SCREEN             Fire Resistor   Contact Fire Control Panel manufacturer e ALWAYS use a separate screened 2 core cable for  for values of Fire Resistor  each detector head  Some Zone and Switch Interface Modules do not need a    End Of Line     EOL     component is  Fire Resistor   replace Resistor with a short circuit  Refer to supplied by Fire Control Panel manufacturer    supplied CD IE reer information  l e CAUTION  For system monitoring     Do not use looped  e Check operation of Fire and Fault connection on wire under any terminals  Break wire run to provide  6 Fire Panel monitoring of connections     Commissioning Apply Power and Enter Pass Code    1  Apply power 2  Enter Pass Code to Access Engineering Menu    EZ T H 0    ADOOS g Press    for Pass Code screen     LILILIAI EME    Commissioning       e Default Pass Code  1 2 3 4  e AN  vV  Change digit   e   lt     gt   Move between digits  e lt  Accept    e An incorrect Pass Code will return the display to the  Pass Code entry screen    e Three incorrect attempts will lock access for three  minutes       Note   a commissioned  system will display        Commissioning Select Power Mode 
9. ligned to the Reflector  so repeat  Step 3      Perform    Auto    alignment  followed by    Set       Troubleshooting Home Position                                                       If it is not Known where the beam is pointing  use Home Position  to automatically steer the infrared beam to approximately the  centre of its range of movement     e Press Yor X to exit this function  e This will take up to 15 minutes to complete  e When complete the display will return to the Engineering Menu    Troubleshooting    15    Display and Indicators   LCD icon Layout    Seconds User Prompt    Feet  Latched   Reset Signal Strength Compensation Level    Detector Number Metres    Degrees Fire    Not Used    bp liansmit  Lee Shee Strength  Received     Ap 1000  tai IO N    Bar Graph     Set Home LASER Fire System Controller  Position Targeting Threshold Fire Test Settings    Detector Settings Beam Fire  Fault Software  Alignment Delay Utilities       16    Display and Indicators    Detector and System Controller Status Indicators    Detector  Indicator flashes every 10 seconds     NORMAL  GREEN  FAULT  YELLOW  FIRE  RED    System Controller  Indicators 1 to 4 show status for Detectors 1 to 4      NORMAL  No flash  FAULT  YELLOW    FIRE  RED    Indicator 5 flashes GREEN to indicate NORMAL  System Controller status   All indicators flash every 10 seconds       DETECTORS 2 TO 4 ONLY AVAILABLE ON MULTI HEAD SYSTEM          Info    17    Menu Layout User Menu    Controller parameters      
10. ng    Auto    Alignment and    Set    0 100  Calibrate        6     Auto    Alignment                                                         e Select    Auto    to automatically  align the infrared beam    e Signal Strength will be shown   LOA  18 minutes  during Alignment HiA  15 minutes    d     Al  OR GRE  amp        10    7         Set    0 100  Calibrate                                                           When    Set    is displayed press Y  When    S 00    is displayed  cover the Reflector with a non   reflective material and leave covered  then press  lt       When    S 01    is displayed  uncover the Reflector and  leave uncovered  then press    8  System is Aligned    It is recommended to set the system back to    Lo A mode    Green LED on Detector will flash every 10 seconds  and  Signal Strength should be between 99  and 101   Default values  35  Fire Threshold  10 second delay to  Fire and Fault  Non Latching mode   Refer to User Guide page 11   12 to change settings  and for Fire and Fault Test    In Use Settings and Final Tests    Fire Threshold   How to change the  threshold at which the  Detector will detect a Fire                                        Fire   Fault Delay   How to change the delay  the System Controller  uses before signalling a  Fire or Fault to the Fire  Control Panel                               F       Delay 1  Fire  Delay 2  Fault                            In Use                   Fire Test   How to perform a Fire Test  from the 
11. s not uncovered  during    S 01        e Ensure Reflector was  uncovered when    S 01    was  selected       Reflector Not Found     Detector could not align with  Reflector    e Ensure correct distance has  been set    e Ensure correct Reflector type  has been used      Ensure clear line of sight to  Reflector    e Re align beam using LASER  and Auto Align       Centre    Stage of Alignment  Failed    Detector is too far from the centre  of the Reflector    Troubleshooting      Ensure clear line of sight to  Reflector    e Ensure correct distance  between beam path and roof  structures    13    Troubleshooting LASER Not Visible    14                                                       If it is not possible to see the LASER because of  the installation environment  for example  if you  cannot see the Reflector from the System  Controller or there is high ambient light  then use     Hand    Alignment  This option displays the signal  strength value returned by the Detector  and  allows the user to move the beam    al    Start    Auto    Alignment and press X  after two seconds to exit   this will  maximise infrared power       Select    Hand    alignment  Use   lt     gt    A   v  to steer the beam until    the signal strength is above 800  There is  no auto repeat function on any key  To  move the motor in any given direction  more than once  press the key multiple  times      Cover the Reflector  If the Signal Strength    does not drop by more than half  the beam  is not a
12. s performed     Fire Test  Cover the Reflector slowly so that it takes  longer than 2 seconds to cover  The System Controller  will signal Fire to the Fire Control Panel     Fault Test  Cover the reflector completely within 2  seconds  The System Controller will signal Fault back  to the Fire Control Panel     Troubleshooting    Error Codes       Detector Not Found    System Controller could not  find Detector  Also displayed during  power up     e Wait 45 seconds for  system to power up    e Check wiring between System  Controller and Detector  Voltage  to Detector should be 11   13V        Auto Align Failed    e Ensure correct distance between  Reflector and roof structures      Ensure clear line of sight to  Reflector    e Re align Detector using  Auto Align    Compensation Level Not Zero    Compensation must equal zero  when    Set    is selected     e Re align beam using Auto Align       Cannot Zero During    S 00    in    Set       The Reflector was not covered or  the Detector was not aligned onto  the Reflector     e Ensure Reflector was  completely covered with a non   reflective material    e Re align Detector using  Auto Align    Signal Strength Out of Range     Signal Strength is too low or too high  after Auto Align     e Ensure correct distance has been  set    e Ensure correct Reflector type has  been used      Ensure clear line of sight to  Reflector    e Re align beam using LASER and  Auto Align       No Signal During    S 01    in    Set     The Reflector wa
    