Home

USER MANUAL for digital indicator with U/I input

image

Contents

1. The unit is not equipped with an internal fuse or power supply circuit breaker Because of this an external time delay cut out fuse with minimal possible nominal current value must be used recommended bipolar max 2A and a power supply circuit breaker located near the unit In the case of using a monopolar fuse it must be mounted on the phase cable L The power supply network cable diameter must be selected in such a way that in the case of a short circuit of the cable from the side of the unit the cable shall be protected against destruction with an electrical installation fuse Wiring must meet appropriate standards and local regulations and laws In order to secure against accidental short circuit the connection cables must be terminated with appropriate insulated cable tips Tighten the clamping screws The recommended tightening torque is 0 5 Nm Loose screws can cause fire or defective operation Over tightening can lead to damaging the connections inside the units and breaking the thread In the case of the unit being fitted with separable clamps they should be inserted into appropriate connectors in the unit even if they are not used for any connections Unused clamps marked as n c must not be used for connecting any connecting cables e g as bridges because this can cause damage to the equipment or electric shock If the unit is equipped with housing covers and sealing packing protecting against wat
2. 10 2 TRANSMISSION ERRORS DESCRIPTION If an error occurs while write or read of single register then the device sends an error code according to Modbus RTU specifications example message no 1 Error codes 01h illegal function only functions 03h 06h and 10h are available 02h illegal register address 03h illegal data value 08h no write permission see mbAc parameter AOh exceed of upper border of input range 60h exceed of lower border of input range AOh and 60h codes can appear only during reg 01h is reading by 03h function read of a single register 10 3 EXAMPLES OF QUERY ANSWER FRAMES Examples apply for device with address 1 All values are represent hexadecimal Field description ADDR Device address on modbus network FUNC Function code REG H L Starting address address of first register to read write Hi and Lo byte COUNT H L No of registers to read write Hi and Lo byte BYTE C Data byte count in answer frame DATA H L Data byte Hi and Lo byte CRC LH CRC error check Hi and Lo byte 1 Read of the displayed value measurement WW 30 device address 01h ADDR FUNC REG H L COUNT HL CRC L H 01 03 00 01 00 01 D5 CA a The answer we assume that measurement is not out of range ADDR FUNC BYTE C DATA H L CRC LH 01 03 02 00 FF F8 04 DATA H L displayed value 255 no decimal point Decimal point positio
3. Pnt parameter menu inPt e User can not enter two points with the same value of X coordinate If user trays Gi to do it Err warning is displayed To modify any defined point use EdtP option e To distinguish X and Y coordinates if X coordinate is displayed an additional decimal point on utmost right position is displayed e If user defined characteristic is selected and if number of defined points is lower than 2 then warning Errc is displayed in measurement mode dELP this option allows user to delete any of the points of the user defined characteristic After selection current number of points of the user defined characteristic is displayed for about approx 1 5 sec After that device waits for selection of point being deleted by v buttons The short pressing of ENTER button causes by switching between X and Y value of the displayed point The long press press and hold at least 2 sec of ENTER button causes by displaying dEL ask If ENTER button is pressed again current point is deleted and new updated number of points of the user defined characteristic is displayed EdtP this option allows user to modify of particular point of the user defined characteristic After selection current number of points of the user defined characteristic is displayed for about approx 1 5 sec After that device waits for selection of point being edited by v buttons Th
4. 24 User manual for digital indicator with U I input WW 30 W 4I x Hi C Lo C LoC where W means the displayed value Showed above expression is not valid when normalized result is negative It is possible for 4 20 mode only In this case In lt 0 the displayed result is equal Lo C see graphs below Hic Loc 5 5 ER ED BS g3 aw Q 0 2 gt a gt a a Loc Hi C 0 4 8 12 16 20 0 4 8 12 16 20 Input current mA Input current mA Figure 9 3 Normal Lo C lt Hi C and inverted Lo C gt Hi C characteristic 9 1 4 User defined characteristic User defined characteristic is defined as set of X Y points Number of the points is variable and may be set from 2 to 20 points which make linear segments see graph and see Menu inPt Due to the normalized result the device computes specific segment e g for characteristic from figure below and I 0 65 the segment between points X 50 0 and X 70 0 will be chosen Let s mark those points as PL point low i PH point high in this example PL 50 0 and PH 70 0 and the normalized result for the point PL as in this example lp In PL 0 5 The displayed result is calculated accordingly to the expression Y PH Y PL W l 1 1 X TEH XPD X 100 Y PL where Y PH X PH Y PL X PL mean values of X and Y coordinates of PH i P
5. 4 20 1 5 or 2 10 mode only and determines lower border of the permissible range If input is set to 0 20 0 5 or 0 10 mode then lower border of the permissible range is always 0 For example if input is set to 4 20 mode then lower border is calculated due to expression Imin 4 MA 4 MA x Lor The Lo r value can be set from 0 to 99 9 Parameter Hi r determines the upper border of the permissible range accordingly to the expression for all modes For example if input is set to 4 20 mode then upper border is calculated due to expression Imax 20 mA 20 mA x Hi r The value of Hi r can be set from 0 to 19 9 In example no 1 of the DISPLAY VALUES CALCULATION paragraph the procedure of the permissible input range determining is presented in details displayed value exceeds range 999 9999 the warning Ov is displayed rather Gi If the measurement value do not exceeds permissible measurement range but than the calculated result 7 3 2 bri parameter This parameter allows user to set bright of the LED display bright can be set to conventional values from 1 to 8 19 User manual for digital indicator with U I input WW 30 7 3 3 HOLd menu This menu contains parameters connected with peak detection function See also full description of the peak detection function in paragraph DETECTION OF THE PEAK VALUES modE th
6. menu rS Addr Device address 0 20 bAud Baud rate 9 6 20 mbAc Permission to changes of configuration registers on 21 rESP Additional delay of answer transmission Std 21 Configuration of numerical parameters edition Edit Numerical parameters edit mode dig 21 34 User manual for digital indicator with U I input WW 30 35 CIPLISEN gt APLISENS Sp z o o ul Morelowa 7 PL 03 192 Warszawa Poland tel 48 22 814 07 77 fax 48 22 814 07 78 http www aplisens com pl e mail aplisens aplisens pl
7. mode 70h5 Yes 999 1999 The value of Da coordinate of point no 1 of the user defined characteristic expressed in 0 1 71h5 Yes 999 9999 The value of A e coordinate of point no 1 of the user defined characteristic no decimal point included B 5 Further pairs of X Y coordinates of points no 2 19 of the user 72h 95h de defined characteristic 96h5 Yes 999 1999 The value of X coordinate of point no 20 of the user defined characteristic expressed in 0 1 97h5 Yes 999 9999 The value of P e coordinate of point no 20 of the user defined characteristic no decimal point included 2 after writing to register no 20h the device responds with an old address in the message 3 after writing to register no 22h the device responds with the new baud rate 4 the value of the mbAc parameter is also connected to write to this register so it is possible to block a writes but impossible to unblock writes via RS 485 interface The unblocking of the writes is possible from menu level only 5 the pairs of X Y coordinates may be defined for any free point The pair is free it means that particular point is not defined if X coordinate of this point is equal 8000h After writing both X and Y coordinate the point is defined and used in calculation of result The coordinates of any point can be changed at any time 30 User manual for digital indicator with U I input WW 30
8. be done for there different input currents from example 2 a lin 10 mA and h 0 375 Accordingly to expression on page 24 for linear characteristic sqrt 0 375 x 1200 300 919 and next the Lo C value is added to the result so the displayed value W 919 300 619 b lin 2 5 mA and I 0 0938 normalized result is negative so the displayed value is equal to Lo C parameter W Lo C 300 C ln 20 5 mA and 1 0313 W 1223 27 User manual for digital indicator with U I input WW 30 Example 6 The user defined characteristic Let the input mode 4 20 mA and the user selected the 10 segment characteristic To do this it is necessary to enter X and Y coordinates of 11 points see Menu inPt The calculations will be done for three different input currents from example 2 so in calculations some of the segments will be used only Let the following points will be given X1 00 0 Y1 50 0 X2 10 0 Y2 30 0 X6 30 0 Y6 30 0 X7 40 0 Y7 80 0 X10 90 0 Y10 900 0 X11 100 0 Y11 820 0 Additionally all other points must to be defined and stored in the device memory a ln 10 mA and h 0 375 The segment defined by X6 30 0 and X7 40 0 for this I will be selected Accordingly to expressions given for user defined characteristic see page 25 X6 PL 30 Y6 P
9. be set in range from O to 199 If the value O is set then device responds to frames with address 255 FFh bAud this parameter determines RS 485 interface baud rate It can be set to one of 8 possible values 1 2 2 4 4 8 79 6 19 2 38 4 757 6 7115 2 which respond to the baud rates of 1200 2400 4800 9600 19200 38400 57600 and 115200 bit s respectively 20 User manual for digital indicator with U I input WW 30 mbAc this parameter sets the access to the configuration registers of the device Possible values on configuration registers can be set via RS 485 interface oFF configuration registers can not be set via RS 485 interface rESP this parameter defines minimal additional delay between the Modbus message and the answer of the device received and sent via RS 485 interface This additional delay allows the device to work with poor RS converters which do not works properly on baud rates higher than 19200 This parameter can be set to one of values Std answer as quick as possible no additional delay 27 10c 20c answer delayed of 10 20 50 100 of 200 chars respectively where SE one character time depends on selected baud rate 200c In the most cases parameter rESP should be set to Std no additional delay Unfortunately for some third party RS converters rESP should be adjusted experimentally Table 7 1 cont
10. frame GW The device interprets the broadcast messages but then do not sends the answers 10 1 LIST OF REGISTERS Register Write Range Register description 01h No 999 9999 Measurement value no decimal point The status of the current measurement 0h data valid AOh top 02h No Oh AOh 60h border of the measurement range is exceeded 60h bottom border of the measurement range is exceeded Pnt parameter in InPt menu decimal point position 0 0 1 0 0 2 0 00 3 0 000 06h No 999 9999 Peak drop value no decimal point 03h Yes 0 3 tyPE parameter in InPt menu nominal input range 10h Yes 0 5 0 0 20 mA range 1 4 20 mA range 2 0 10 V range 3 2 10 V range 4 0 5 V range 5 1 5 V range CHAr parameter in InPt menu characteristic type a SES PAR 0 linear 1 square 2 square root 3 user defined 12h Yes 0 5 FiLt parameter in InPt menu measurement filtering rate 13h Yes 0 3 Pnt parameter in InPt menu the copy of 03h register decimal point position 0 0 1 0 0 2 0 00 3 0 000 14h Yes 999 9999 Lo C parameter in InPt menu no decimal point included 15h Yes 999 9999 Hi C parameter in InPt menu no decimal point included 16h Yes 0 999 Lo r parameter in InPt menu in 0 1 17h Yes 0 199 Hi r par
11. of measurement input control modes critical situations behaviour communication via RS 485 and access settings The meaning of the particular parameters is described in paragraph MENU DESCRIPTION 7 1 PROGRAMMING MENU To enter main menu being in the measurement mode operator must to press and hold at least 2 sec ESC MENU button If the user password is defined see parameter Scod operator have to enter correct one before proceeding to menu options Entering of the passwords is similar to the edition of numeric parameters see PARAMETERS EDITION however presently editing digit is showed nn only on the display other digits are replaced by sign After entering of last digit of the password first menu position will be displayed if the password is correct or warning Err in other case 14 User manual for digital indicator with U I input WW 30 Functions of the buttons while sub menu and parameters choice Selection of sub menu or parameter for editing Name of selected item sub menu or parameter is displayed Operation of ENTER button depend on present menu position e if the name of some sub menu is displayed enter this sub menu name of the first parameter or next level sub menu is displayed if the name of some parameter is displayed enter the edition of this parameter present value of the parameter is displayed ENTER ESC MENU button allow user to exit present menu le
12. pressed again the changes are accepted stored in EEPROM end the edition process finished Pressing the key ESC after SEt causes in cancelling of made changes and returning to menu Functions of buttons when editing numeric and switching parameters While editing numeric parameter change of current flashing digit slide change of value acceleration deceleration direction change While editing switch parameter selection of switch parameter If numerical parameter is being edited a short press of ENTER button change edited position A long press of ENTER button at lest 2 sec causes of display a SEt ask which allow user to make sure if change of the parameter value is correct If switch parameter is being edited a short press of ENTER button causes of display a SEt ask When ENTER button is pressed again while SEt is displayed the new value of the parameter is stored in EEPROM memory ENTER Pressing this button operator can cancel the changes done up to now if they MENU were not approved by ENTER button after the SEt ask and come back to menu 16 User manual for digital indicator with U I input WW 30 7 3 MENU DESCRIPTION password checking If some password different from 0000 is set then every enter to main menu follows the entering of password If entered password is correct then first menu position will be displayed else warning Err and unit ret
13. r BS bei PEA i H Parameter i ln Scod Le edition timE F SS F lt Hdis I j a gt RB Parameter S ry Addr a Ge edition 4 H EJ Go zu ii re mbAc J H Parameter la rESP II Edit edition 7 E 4 digit special password entering r dEFS fa r Oe BR SEt Esc s 7 gt tYPE CHAr D lt FiLt t oi Pnt t bei LoC t bei HiC D o AddP t dELP h EdtP Y bei Lor D lt Hir Default settings restoring Parameter edition User manual for digital indicator with U I input WW 30 8 OVER CURRENT PROTECTION The current input of the device is equipped with over current protection circuit This circuit protects the standard resistor to damage Maximum input current is set to about 50 mA When temperature of the standard resistor falls the protection circuit will turn off himself automatically and the device will measure the input current again Due to thermal phenomenon in the standard resistor precision of the measurement may be lower during few minutes up to the standard resistor temperature will falls to the environment temperature 9 DISPLAYED VALUES CALCULATION For simplicity of examples it s assumed that current input is selected and all calculations are related to this input When voltage input is selected calculations are similar be sure of particular ranges and
14. APLISEN CN USER MANUAL for digital indicator with U l input type WW 30 firmware version 5 14 or higher CE Read the user s manual carefully before starting to use the unit Producer reserves the right to implement changes without prior notice 13 01 2009 V 2 01 User manual for digital indicator with U I input WW 30 CONTENTS 1 BASIC REQUIREMENTS AND USER SAFETY ssscsssssssessessensessesssensensensensenssassnscensnssensessenssessanavensaesensene 3 2 GENERAL CHARACTERISTICS sscssccerssssessenssnsenseassssensensenseassnseensensonsensonsenscausoncensonsensenssansseeasecnaseensass 4 3 TECHNICAL DATA EE 4 4 DEVICE INSTALLATION 6 4h UNPACKING ee 6 4 2 ASSEMBLY EE 6 4 3 CONNECTION METHOD vec a zada ay ay A ia AA AA 8 Ree RRE LEE 11 5 DESCRIPTION OF IR REMOTE CONTROLLER AND CONTROL SOFTWARE PUSH BUTTONS 12 6 PRINCIPLE OF OPERATION 1 cessssssssesssessersessensenssansonsonsensensenseanenssensonsensensenseensassesseasonseaseansoneassonsenensons 12 6 1 MEASUREMENT MODE 12 6 2 DETECTION OF THE PEAK VALUES 14 7 DEVICE PROGRAMMING 221 21 11 21 12222 11 14 7 1 PROGRAMMING MENU 14 7 2 PARAMETERS EOITION BE 7 2 1 Numeric parameters digit change model 7 2 2 Numeric parameters slide change mode Be Ee 7 2 3 Switch parameters LIST type KG 7 3 MENU DESCRIPTION BS be 7 3 1 inPt menu BEE 7 3 2 br
15. COUNT L_ the count of being read registers max 16 The answer ADDR FUNC BYTEC DATA H1 L1 DATA H2 L2 DATA H3 L3 CRC LH 01 03 06 00 0A 00 00 00 01 78 B4 DATA H1 L1 reg 01h 10 displayed value 1 0 DATA H2 L2 reg 02h O no errors DATA H3 L3 reg 03h 1 decimal point position 0 0 ED There is no full implementation of the Modbus Protocol in the device The functions presented above are available only User manual for digital indicator with U I input WW 30 11 DEFAULT AND USER S SETTINGS LIST Parameter Description Default value User s value geg Configuration of measurement input inPt menu tYPE Input mode 4 20 17 CHAr Conversion characteristic mode Lin 17 FiLt Filtering ratio 0 17 Pnt Decimal point position 0 0 17 LoC Minimum displayed value for nominal range 000 0 18 Hi C Maximum displayed value for nominal range 100 0 18 Lor Extension of the bottom of the nominal input range 5 0 18 Hi r Extension of the top of the nominal input range 5 0 18 Display parameters bri Display brightness bri6 19 Configuration of peaks detection function HOLd menu modE Kind of detected changes norm 20 PEA Minimum detected change 0 0 20 timE Maximum time of peak displaying 0 0 20 HdiS The type of displayed value HOLd 20 RS 485 interface configuration
16. L 30 X7 PH 40 Y7 PH 80 and lp 0 3 the displayed value W I I x X PH X PL 100 Y PL _ 80 30 m 0 375 0 3 x 40 30 100 30 67 b lin 2 5 mA and 0 0938 because of the normalized In value is lower than O the segment defined by X1 and X2 will be selected X1 PL 0 Y1 PL 50 X2 PH 10 Y2 PH 30 and 0 For these values the displayed value W 69 C lin 20 5 mA and 1 0313 because of the normalized value is higher than 1 the segment defined by X10 and X11 will be selected and X10 PL 90 Y10 PL 900 X11 PH 100 Y11 PH 820 and l 0 9 for these values the displayed value W 795 28 User manual for digital indicator with U I input WW 30 10 THE MODBUS PROTOCOL HANDLING Transmission parameters 1 start bit 8 data bits 1 or 2 stop bit 2 bits are send 1 and 2 bits are accepted when receive no parity control Baud rate selectable from 1200 to 115200 bits second Transmission protocol MODBUS RTU compatible The device parameters and display value are available via RS 485 interface as HOLDING type registers numeric values are given in U2 code of Modbus RTU protocol The registers or groups of the registers can be read by 03h function and wrote by 06h single registers or 10h group of the registers accordingly to Modbus RTU specification Maximum group size for 03h and 10h functions can not exceeds 16 registers for single
17. L points If the normalized result exceeds the user defined characteristic values then specific D utmost segment defined by two next points is used for calculations If characteristic from figure below is used and if Lei then segment defined by points X PL 90 0 X PH 100 0 will be used 25 User manual for digital indicator with U I input WW 30 Normalized measurement In for 0 20 mA range 0 0 2 0 35 0 5 0 7 0 9 1 5 elements characteristic i X PH 70 0 Displayed value 0 4 8 12 16 20 Input current mA Figure 9 4 Example of user defined characteristic 9 2 EXAMPLES OF CALCULATIONS Example 1 Selection of the permissible input range 4 20 mode If in 4 20 mode the user sets Lo r 20 0 and Hi r 10 0 then permissible input currents range will be equal 3 2 mA 22 mA Lower border of the range is the result of calculations 4 mA 4 mA x 20 and the higher 20 mA 20 mA x 10 Example 2 The normalized I result calculation Let the input mode 4 20 mA The normalized result is calculated accordingly to the expression on page 23 so if lin 10 mA then 10 mA 4 mA 6 mA and this result should be divided by the width of input range 16 mA Finally the normalized result In 6 16 0 375 In case when input current exceeds nominal measurement range calculations are similar For example if inpu
18. SIBLE DAMAGES This symbol denotes especially important characteristics of the unit Read any information regarding this symbol carefully 1 BASIC REQUIREMENTS AND USER SAFETY A The manufacturer is not responsible for any damages caused by inappropriate installation not maintaining the proper technical condition and using the unit against its destination Installation should be conducted by qualified personnel During installation all available safety requirements should be considered The fitter is responsible for executing the installation according to this manual local safety and EMC regulations The unit must be properly set up according to the application Incorrect configuration can cause defective operation which can lead to unit damage or an accident If in the case of a defect of unit operation there is a risk of a serious threat to the safety of people or property additional independent systems and solutions to prevent such a threat must be used The unit uses dangerous voltage that can cause a lethal accident The unit must be switched off and disconnected from the power supply prior to starting installation of troubleshooting in the case of malfunction Neighbouring and mating equipment must meet the requirements of appropriate standards and regulations concerning safety and be equipped with adequate anti overvoltage and anti interference filters Do not attempt to disassemble repair or modify
19. ains most frequently used values bAud parameter 38 4 57 6 115 2 rESP parameter 100 20c 50c Tab 7 1 Settings of rESP parameter 7 3 6 Edit parameter This parameter allows to change the edition mode of numerical parameters dig the change to by digit mode Slid slide change mode 7 3 7 dEFS parameter This setting allows to restore the factory settings of the device To get the access to this option special password is required 5465 next the device displays acknowledge question SEt Press ENTER to acknowledge the restoring of factory settings or ESC to cancel 7 3 8 SErv menu This menu contains the parameters for authorized service only To enter this menu proper service password must be entered Improper settings can causes of damage of the device 21 User manual for digital indicator with U I input WW 30 7 4 MENU STRUCTURE 22 r Measurement mode ESC ESC Y Eal Press and hold at least 2 seconds Yy 0 4 digit user password entering if it is different from 0000 inPt lt A MA SErv e bri L o E SE 7 em ec edition r So y EJ amp HoLa mode kees Dm 7
20. ameter in InPt menu in 0 1 20h Yes 0 199 Device address 21h No 20F2h Device identification code ID bAud parameter in rS menu baud rate 22h3 Yes 0 7 0 1200 baud 1 2400 baud 2 4800 baud 3 9600 baud 4 19200 baud 5 38400 baud 6 57600 baud 7 115200 baud 29 User manual for digital indicator with U I input WW 30 Register Write Range Register description 23h Yes 0 1 mbAc parameter in rS menu permission to write registers via j RS 485 interface 0 write denied 1 write allowed rESP parameter in rS menu additional response delay 25h Yes 0 5 0 no additional delay 1 10c option 2 20c option 3 50c option 4 100c option 5 200c option t bri parameter display brightness SCH Yes e 1 the lowest brightness 8 the highest brightness R Edit parameter numerical parameters edit mode SC JS Sec 0 dig mode 1 SLid mode 50h Ves 0 1 modE parameter in HOLd menu type of detected changes 0 peaks 1 drops 51h Yes 0 9999 PEA parameter in HOLd menu minimum detectable change no decimal point included 52h Yes 1 199 timE parameter in HOLd menu maximum peaks or drops display time expressed in seconds p HdiS parameter in HOLd menu SCH Nes 0 1 0 rEAL mode 1 HOLd
21. appropriate anti interference filters is recommended Bear in mind that the connection between the filter and the unit should be as short as possible and the metal housing of the filter must be connected to the earthing with largest possible surface The cables connected to the filter output must not run in parallel with cables with interference e g circuits controlling relays or contactors Connections of power supply voltage and measurement signals are executed using the screw connections on the back of the unit s housing Figure 4 4 Method of cable insulation replacing and cable terminals 0 1 5V 0 2 10V GND n c Power a DATA supply DATAt GND GND depending on version RS 485 0 20mA 4 20mA Figure 4 5 Terminals description A All connections must be made while power supply is disconnected User manual for digital indicator with U I input WW 30 a b L N FUSE FUSE L N 230V AC 24V DC Figure 4 6 Connection of power supply a for 230V AC version b for 24V DC version 24V DC Figure 4 8 Connection of 3 wire current converters 10 User manual for digital indicator with U I input WW 30 24V DC Figure 4 9 Connection of voltage converters 4 4 MAINTENANCE The unit does not have any internal replaceable or adjustable components availa
22. ble to the user Pay attention to the ambient temperature in the room where the unit is operating Excessively high temperatures cause faster ageing of the internal components and shorten the fault free time of unit operation In cases where the unit gets dirty do not clean with solvents For cleaning use warm water with small amount of detergent or in the case of more significant contamination ethyl or isopropyl alcohol AN Using any other agents can cause permanent damage to the housing Sa Product marked with this symbol should not be placed in municipal waste Please CAS check local regulations for disposal and electronic products v a 11 User manual for digital indicator with U I input WW 30 5 DESCRIPTION OF IR REMOTE CONTROLLER AND CONTROL SOFTWARE PUSH BUTTONS infra red gess transmitter programming pushbuttons Symbols and functions of push buttons Symbol used in the manual ESC MENU MENU Functions e Enter to main menu press and hold by at least 2 sec Exit the current level and Enter to previous menu or measure mode Cancel the changes made in parameter being edited Symbol used in the manual ENTER Functions e Start to edit the parameter e Enter to the sub menu e Confirmation of changes made in parameter being edited Symbol used in the manual v Functions e Change of the present menu e Modification of the parameter value e Change of the display m
23. c Pnt decimal point position It can be set to one of Di 0 73 0 0 Di 0 00 0 000 Decimal point position is changed by A v buttons 17 User manual for digital indicator with U I input WW 30 Lo C These parameters describe the values displayed for minimum and maximum input Hi C current For example if input type is set to 4 20 mA Lo C parameter defines the value displayed when input current is equal 4 mA and Hi C parameter defines the value displayed for 20 mA of input current Available range for these parameters 999 9999 Negative values can be set by entering sign on the first position by use of 4 v buttons If user defined characteristic is selected parameter CHA USEr the GD parameters Lo C and Hi C are not available for modification due to their values are calculated from defined characteristic AddP this menu allow user to add single point to the user defined characteristic After selection of this option device waits for X and Y coordinates of new point Modification of the coordinates is done accordingly to numerical parameters edition Coordinate X defines the percentage ratio of input current to selected current range The X range 99 9 199 9 Coordinate Y defines displayed value for particular X value The Y value can be changed in range 999 9999 decimal point position depend on
24. e short pressing of ENTER button causes by switching between X and Y value of the displayed point The long press press and hold at least 2 sec of ENTER button causes by entering to edit the selected coordinate of the point Modification of the coordinates is done accordingly to numerical parameters edition AddP dELP and EdtP options are available only if the user defined GD characteristic is used it means when parameter CHAr USEr Lo r Hi r these parameters define the expansion of nominal range in percent They 18 User manual for digital indicator with U I input WW 30 determine the permissible range of input signal Figure 7 1 The permissible range allow user to exceed the nominal range of input signal If input value is contained in the permissible range a proper result is displayed If input signal exceeds this range defined by Lo r and Hi r Lo or Hi warning is displayed depend on input signal value Lo r 75 0 3 mA Hi r 5 0 1 mA Ki nominal measurement range 4 20mA a permissible measurement range Ka SH measurement result is displayed d display regardless on nominal range exceeding display message Lo message Hi Figure 7 1 Example of definition of permissible range of input signal Lo r and Hi r parameters 4 20 mode The Lo r parameter is important if input is set to
25. e type of detected changes of the input signal can be set to values norm peaks peak and next drop of the input signal of value equal at least PEA inv drops drop and next peak of the input signal of value equal at least PEA PEA minimal detected signal change classified as peak or drop see Figure 6 3 timE maximum time of displaying of the peak drop value can be set from 0 1 to 19 9 sec with 0 1 sec resolution HdiS type of displayed values rEAL current value is displayed HOLd peak drop value is displayed 7 3 4 Scod parameter This parameter defines user password 4 digits number If this parameter is set at value 0000 user password is turned off If the user do not remember his password the access to the menu is possible by the one use password To get this password please contact with Marketing Division Single use password can be used only one time after that it is destroyed Entering this password causes in clearing of user password it means sets the user password to 0000 The one use password can be used ONE TIME ONLY it is impossible to use it again The one use password can be restored by Service Division only 7 3 5 rS menu This menu is connected with RS 485 interface and sets his properties Addr this parameter defines the address of the device accordingly to Modbus protocol It can
26. er intrusion pay special attention to their correct tightening or clamping In the case of any doubt consider using additional preventive measures covers roofing seals etc Carelessly executed assembly can increase the risk of electric shock After the installation is completed do not touch the unit s connections when it is switched on because it carries the risk of electrical shock Due to possible significant interference in industrial installations appropriate measures assuring correct operation of the unit must be applied To avoid the unit of improper indications keep recommendations listed below Avoid common parallel leading of signal cables and transmission cables together with power supply cables and cables controlling induction loads e g contactors Such cables should cross at a right angle Contactor coils and induction loads should be equipped with anti interference protection systems e g RC type User manual for digital indicator with U I input WW 30 _ Use of screened signal cables is recommended Signal cable screens should be connected to the earthing only at one of the ends of the screened cable In the case of magnetically induced interference the use of twisted couples of signal cables so called spirals is recommended The spiral best if shielded must be used with RS 485 serial transmission connections In the case of interference from the power supply side the use of
27. eristic of conversion decimal point position and measure filtering ratio are user configurable parameters All accessible parameters can be changed by entering the menu see DEVICE PROGRAMMING Use the local keyboard or the remote controller to do it Note all parameters can be remote changed via RS 485 interface Configuration of the device via menu or RS 485 interface do not stops measures 13 User manual for digital indicator with U I input WW 30 6 2 DETECTION OF THE PEAK VALUES The WW 30 controller is equipped with peaks detection function It can detect a peaks of the input signal and display their values Presets connected with this function are placed in HOLd menu see description of HOLd menu The detection of the peak can be done if the measured signal raises and drops of value at least equal to parameter BEAT Detected peaks are displayed during the time defined by parameter timE If a new peak will be detected while one is displayed this new peak will be displayed and display time counter will be cleared Figure 6 3 If no peaks are detected while time timE elapses device starts to show the current value of input signal again a measure timE timE PEA Y J PEAY real measurement result time display value Figure 6 3 Process of peaks detection 7 DEVICE PROGRAMMING The device menu allow user to set all parameters connected to operation
28. gital indicator with U I input WW 30 the normalized results is equal 1 then value Hi C is displayed Expression presented below shows the manner of result calculation W 1 X Hi C Lo C LoC where W means the displayed value The value of the Lo C parameter can be higher than the value of Hi C G parameter In such a case for an increasing value of input current the displayed value decreases Hi C Displayed value r o a l 0 4 8 12 16 Input current mA 20 r o a Displayed value l 4 8 12 16 20 Input current mA Figure 9 1 Normal Lo C lt Hi C and inverted Lo C gt Hi C characteristic 9 1 2 Square characteristic The normalized result is squared and further conversion is done as for linear characteristic Conversion is made accordingly with the expression W I x Hi C Lo C where W means the displayed value Hi C Displayed value Loc p 0 4 8 12 16 20 Input current mA 9 1 3 Square root characteristic Displayed value LoC 4 8 12 16 20 Input current mA Figure 9 2 Normal Lo C lt Hi C and inverted Lo C gt Hi C characteristic The normalized result is rooted and further conversion is done as for linear characteristic Conversion is made accordingly with the expression
29. i parameter 7 3 3 HOLA menu 20 7 3 4 Scod parameter 20 7 3 5 1S MENU 11 21111 20 7 3 6 Edit parameter sad 7 3 7 dEFS parameter t 2a 7 3 8 SErv menu 2i 7 4 MENU STRUCTURE wee 8 OVER CURRENT PROTECTION ee 9 DISPLAYED VALUES CALCULATION 1 ssssscssssscssssesserssssssssssssnssesssssssssssssnssenenees 23 9 1 ADDITIONAL CALCULATIONS USED CONVERSION CHARACTERISTIC 1 28 9 1 1 Linear characteriStiC eesuuaa aaa aaa aaa aaa aaa aaa aa aana aaa aaaaaaazaaasaazaazaace 28 9 1 2 Square characteristic 24 9 1 3 Square root characteristic 9 1 4 User defined characteristic 9 2 EXAMPLES OF CALCULATIONS 220 10 THE MODBUS PROTOCOL HANDLING 29 10 1 USTOER GISTERS A 220 10 2 TRANSMISSION ERRORS DESCRIPTION BECK 10 3 EXAMPLES OF QUERY ANSWER FRAMES 11 DEFAULT AND USER S SETTINGS LIST sssssssssssseesessenssensensensensensenssasenscensensensenseasenseansoseensonsenseneass 34 User manual for digital indicator with U I input WW 30 Explanation of symbols used in the manual operation of the device Not complying with the guidelines denoted by this symbol 1 This symbol denotes especially important guidelines concerning the installation and may cause an accident damage or equipment destruction IF THE DEVICE IS NOT USED ACCORDING TO THE MANUAL THE USER IS RESPONSIBLE FOR POS
30. lows user to select a conversion characteristic of several kinds linear square square root and user defined max 20 points length Result is showed on 4 digit LED display Displayed values range can be selected by user from 999 to 9999 plus decimal point Device WW 30 is equipped with RS 485 Modbus RTU communication interface The measurement range active input and other parameters can be selected while ordering The device can be configured via IR remote controller or optionally by PC via RS 485 interface or using simple RS 232 to IR converter Moreover communication interface RS 485 enables data transmission in any monitoring system equipped witch Modbus RTU protocol Easy assembling small dimensions precision and reliability are the basic trumps of WW 30 indicators IR remote controller is not a part of the WW 30 and must be ordered separately 3 TECHNICAL DATA Power supply voltage 230V AC 10 50 60 Hz depending on version or 110V AC 10 50 60 Hz or 24V DC not separated External fuse required T type max 2A Power consumption max 1 5 VA 230V AC and 110V AC max 1W 24V DC Current input 0 20 mA 4 20 mA overload protected maximum input current about 50 mA Current measurement accuracy 0 25 one digit for 0 20 mA range Current input resistance 502 Voltage input 0 5 V 1 5 V 0 10 V 2 10 V 4 User manual for digital indicator with U I input WW 30 Voltage measurement accuracy V
31. n can be read from reg 03h 31 User manual for digital indicator with U I input WW 30 b The answer if an error occur ADDR FUNC ERROR CRC LH 01 83 60 41 18 ERROR error code 60h bottom border of the measurement range is exceeded 2 Read of device ID code ADDR FUNC REG H L COUNT HL CRC L H 01 03 00 21 00 01 D4 00 The answer ADDR FUNC BYTEC DATA H L CRC L H 01 03 02 20 F2 20 01 DATA identification code 20F2h 3 Change of the device address from 1 to 2 write to reg 20h ADDR FUNC REG H L DATA H L CRC LH 01 06 00 20 00 02 09 C1 DATA H 0 DATA L new device address 2 The answer the same as the message ADDR FUNC REG H L DATA H L CRC LH 01 06 00 20 00 02 09 C1 4 Change of baud rate of all devices connected to the net BROADCAST message ADDR FUNC REG H L COUNT HE CRC L H 00 06 00 22 00 04 29 D2 DATA H 0 DATA L 4 new baud rate 19200 baud Gi Device do not reply to BROADCAST type messages 32 User manual for digital indicator with U I input WW 30 5 Read of the registers 1 2 and 3 in one message example of reading a number of registries in one frame ADDR FUNC REG H L COUNT HL CRC LH 01 03 00 01 00 03 54 0B
32. n such cases the user can be requested to use appropriate preventive measures User manual for digital indicator with U I input WW 30 4 DEVICE INSTALLATION The unit has been designed and manufactured in a way assuring a high level of user safety and resistance to interference occurring in a typical industrial environment In order to take full advantage of these characteristics installation of the unit must be conducted correctly and according to the local regulations A Read the basic safety requirements on page 3 prior to starting the installation Ensure that the power supply network voltage corresponds to the nominal voltage stated on the unit s identification label The load must correspond to the requirements listed in the technical data All installation works must be conducted with a disconnected power supply Protecting the power supply clamps against unauthorized persons must be taken into consideration 4 1 UNPACKING After removing the unit from the protective packaging check for transportation damage Any transportation damage must be immediately reported to the carrier Also write down the unit serial number on the housing and report the damage to the manufacturer Attached with the unit please find user s manual warranty assembly brackets 2 pieces 4 2 ASSEMBLY AN The unit is designed for mounting indoor inside housings control panel switchboard assuring appropria
33. ng button v can be used If v is pressed shortly and button is still pressed increasing slow down for a moment only if v is pressed and held while button 4 is still pressed the increasing slow down and will be kept on lower speed To decrease edited value press or press and hold v button only The decreasing became quickest as long as button v is pressed To slow down the decreasing button can be used If 4 is pressed shortly and button v is still pressed decreasing slow down for a moment only if is pressed and held while button v is still pressed the decreasing slow down and will be kept on lower speed Press ENTER at least 2 seconds to accept the changes after that question SEt is displayed and user must to confirm or cancel the changes To conform changes and story it 15 User manual for digital indicator with U I input WW 30 in EEPROM press ENTER button shortly after SEt is displayed To cancel the changes press ESC button shortly after SEt is displayed After that device returns to the menu 7 2 3 Switch parameters LIST type Switch parameters can be described as a sets of values a lists out of which only one of the options available on the list can be selected for the given parameter Options of switching parameter are selected using 4 v keys Short pressing of ENTER causes in displaying of the acknowledge question SEt If key ENTER is
34. ode ENTER 6 PRINCIPLE OF OPERATION After turning the power supply on device ID and software version are showed on the display next the controller goes to the measurement mode 6 1 MEASUREMENT MODE In the measure mode the measurement results converted over selected characteristic are displayed on the LED display The measurement range equal to the nominal range is called nominal measurement range and the measurement range equal to the extended nominal range is called permissible measurement range Figure 6 1 6 2 12 User manual for digital indicator with U I input WW 30 Lo r parameter Hi r parameter N nominal measurement range ra R gt var 4mA 20 mA permissible measurement range Figure 6 1 Definitions of measurement ranges in mode 4 20mA If the result of measurement exceeds the permissible measurement range warning Hi or Lois displayed rather than input signal depends on exceeded value see description of Lo r i Hi r parameters paragraph inPt menu Hi r parameter nominal measurement range eg Za 0 mA 20 mA permissible measurement range Figure 6 2 Definitions of measurement ranges in mode 0 20mA If the measurement value do not exceeds permissible measurement range but displayed value exceeds range 999 9999 the warning Ov is displayed rather than the calculated result Input type range of displaying values charact
35. oltage input resistance Display range Accepted prolonged input overload Communication interface Baud rate Display Data memory Protection level Housing type Housing material Housing dimensions Mounting hole Assembly depth Panel thickness Operating temperature depending on version Storage temperature depending on version Humidity Altitude Screws tightening max torque Max connection leads diameter Safety requirements EMC 0 25 one digit for 0 10 V range 100 kQ 999 9999 plus decimal point 20 RS 485 8N1 and 8N2 Modbus RTU not separated 1200 bit s 115200 bit s LED 4 digit 13mm height red non volatile memory EEPROM type IP 40 from front IP 20 housing and connection clips panel NORYL UL94V 0 for 24V DC version 72 x 36 x 77 mm for 230V AC version 72 x 36 x 94 mm 67 x 32 5 mm for 24V DC version min 78 mm for 230V AC version min 95 mm max 5mm 0 C to 50 C or 20 C to 50 C 10 C to 70 C or 20 C to 70 C 5 to 90 no condensation up to 2000 meters above sea level 0 5 Nm 2 5 mm according to PN EN 61010 1 installation category II pollution degree 2 voltage in relation to ground 300V AC insulation resistance gt 20MQ insulation strength between power supply and input output terminal 1min 2300V according to PN EN 61326 This is a class A unit In housing or a similar area it can cause radio frequency interference I
36. t current is equal 2 5 mA then I 2 5 4 16 0 0938 and if input current is equal 20 5 mA then I 20 5 4 16 1 0313 Example 3 The linear characteristic Let the input mode 4 20 mA and parameters Lo C and Hi C equal to 300 and 1200 respectively The calculations will be done for there different input currents from example 2 26 User manual for digital indicator with U I input WW 30 a lin 10 mA and h 0 375 Accordingly to expression on page 24 for linear characteristic 0 375 x 1200 300 562 and next the Lo C value is added to the result so the displayed value W 562 300 262 b lin 2 5 mA and In 0 0938 W 441 C ln 20 5 mA and h 1 0313 W 1247 Example 4 The square characteristic Let the input mode 4 20 mA and parameters Lo C and Hi C equal to 300 and 1200 respectively The calculations will be done for there different input currents from example 2 a lin 10 mA and h 0 375 Accordingly to expression on page 24 for linear characteristic 0 375 x 1200 300 211 and next the Lo C value is added to the result so the displayed value W 211 300 89 b lin 2 5 mA and I 0 0938 W 287 C ln 20 5 mA and h 1 0313 W 1295 Example 5 The square root characteristic Let the input mode 4 20 mA and parameters Lo C and Hi C equal to 300 and 1200 respectively The calculations will
37. te protection against electric impulse waves Metal housing must be connected to the grounding in a way complying with the governing regulations Disconnect the power supply prior to starting assembly Check the correctness of the performed connections prior to switching the unit on prepared The thickness of the material of which the panel is made must not exceed 5mm Place the unit in the mounting hole inserting it from the front side of the panel and then fix it using the brackets Figure 4 2 The minimum distances between assembly holes axes due to the thermal and mechanical conditions of operation are 91 mm x 57mm Figure 4 3 1 In order to assembly the unit a 67 x 32 5 mm mounting hole Figure 4 1 must be User manual for digital indicator with U I input WW 30 66 5 mm 32 5 mm 1 10 Figure 4 1 Mounting hole dimensions 92 mm SEH REN Figure 4 2 Installing of brackets and dimensions of connectors CHE GEZ Figure 4 3 Minimum distances when assembly of a number of units 57mm User manual for digital indicator with U I input WW 30 4 3 CONNECTION METHOD Caution AN Installation should be conducted by qualified personnel During installation all available safety requirements should be considered The fitter is responsible for executing the installation according to this manual local safety and EMC regulations
38. the unit yourself The unit has no user serviceable parts Units in which a defect was stated must be disconnected and submitted for repairs at an authorized service centre AN In order to minimize fire or electric shock hazard the unit must be protected against atmospheric precipitation and excessive humidity Do not use the unit in areas threatened with excessive shocks vibrations dust humidity corrosive gasses and oils Do not use the unit in explosion hazard areas User manual for digital indicator with U I input WW 30 A Do not use the unit in areas with significant temperature variations exposed to condensation or icing Do not use the unit in areas exposed to direct sunlight Make sure that the ambient temperature e g inside the control box does not exceed the recommended values In such cases forced cooling of the unit must be considered e g by using a ventilator The unit is designed for operation in an industrial environment and must not be used in a household environment or similar 2 GENERAL CHARACTERISTICS The WW 30 is a simple digital panel indicator equipped with two measurement inputs One current input 0 20 4 20mA and one voltage input 0 5 1 5 0 10 2 10V Current input has additionally overcurrent protection circuit which protects standard resistor The selection of active input is realised by software and selected input can be changed at any time Additionally the WW 30 al
39. units The first step to compute the result of measure is the calculation of the normalized result it means result of 0 1 range To do it the begin of the input range 0 mA for 0 20mA range and 4mA for 4 20mA range must be subtracted from measured value Next received result must be divided by the width of the input range it means 20mA for 0 20mA range and 16mA for 4 20mA range So normalized result can be expressed by expressions ER 4 BEA for 4 20mA range L inp Va for 0 20mA range where lip Means input current in mA and ln normalized result not exceed the permissible input range then received normalized result will exceed 0 1 range e g input range 4 20 mA input current 3 mA the normalized result is equal 0 0625 and for input current 22 mA the normalized result is equal 1 125 In such cases presented expressions are still correct D If measured value exceeds the nominal input range 0 20mA or 4 20mA and do 9 1 ADDITIONAL CALCULATIONS USED CONVERSION CHARACTERISTIC The manner of the additional computation of the displayed result depends on selected conversion characteristic All presented charts are connected with the input range 4 20 mA 9 1 1 Linear characteristic The normalized result is converted by fixed coefficients determined by Lo C and Hi C parameters when the normalized results is equal 0 then value Lo C is displayed and when 23 User manual for di
40. urns to measurement mode Due to problem with direct displaying of m letter it is exchanged with special sign o Independently in user manual letter m is used to make it more readable example modE 7 3 1 inPt menu This menu presets the measurement input tYPE type of the input sensor This parameter can be set to values 0 20 4 20 current inputs 0 10 2 10 0 5 1 5 voltage inputs Displayed values are defined by parameters LoC HiC or by user defined characteristic points and parameter Pnt CHA this option presets type of the conversion characteristic and can be set to Lin linear Sqr square When one of those characteristics is chosen display Sqrt square root range is defined by Lo C and Hi C USEr user defined characteristic Maximal length 20 points Every point is defined by user Adding Editing and Deleting of points is done by options AddP EdtP dELP InPt menu respectively ED If user defined characteristic is selected and if number of defined points is lower than 2 then warning Errc is displayed in measurement mode The process of displayed result calculation is described in details in DISPLAY VALUES CALCULATION paragraph ELO this parameter sets filtration rate It can be set to values from 0 no filtration to 5 strongest filtration time window about 2 se
41. vel and goes to upper MENU level menu or measurement mode E After about 1 min since last use of the buttons device exits the menu mode and returns to the measurement mode only if no parameters are in editing mode 7 2 PARAMETERS EDITION To start edition of any parameter user should select name of desired one using Vv buttons and then press ENTER 7 2 1 Numeric parameters digit change mode Numerical parameters are displayed as decimal numbers The mode of its new value entering depends on chosen edit method see parameter Edit In mode by digit Edit dig pressing one of the keys or v causes change of current position flashing digit or the sign Short pressing of the ENTER button causes change of the position digit Press ENTER at least 2 seconds to accept the changes after that question SEt is displayed and user must to confirm or cancel the changes To conform changes and story it in EEPROM press ENTER button shortly after SEt is displayed To cancel the changes press ESC button shortly after SEt is displayed After that device returns to the menu 7 2 2 Numeric parameters slide change mode In slide change mode Edit Slid buttons and v has different functions To increase edited value press or press and hold button only the increasing became quickest as long as button is pressed To slow down the increasi

Download Pdf Manuals

image

Related Search

Related Contents

Smeg WMI14C7 washing machine  

Copyright © All rights reserved.
Failed to retrieve file