Typ/Type 9160 Messumformerspeisegerät Transmitter

image

Contents

1. Technical data extract from the data sheet Power supply Nominal voltage Un Nominal current at Uy and Iamax 1 2 channels Power consumption at Uy and Iamax 1 2 channels LS input Supply voltage for transmitter Input signal range Output Range for load resistance Output signal range Ambient conditions Operating temperature Storage temperature Relative humidity no condensation 24 VDC 70 mA 125 mA 1 7W 3W 16 V 0 4 20 mA 600 Q 0 4 20 mA 20 60 70 C 40 80 C lt 95 Further technical information can be obtained from the current data sheet deviate from the standard operating conditions Please consult with the manufacturer before operating under conditions which 12 Transmitter Supply Unit Type 9160 english 5 Engineering 5 1 Max ambient temperatures Operating Instructions The IS pac isolators can be used over a wide temperature range Depending on the isolator version and installation method different maximum ambient temperatures may result Ventilation Installation aE unit DIN rail ee ee Type without ventilation pac Carrier horizontal o o vertical 9160 13 10 11 DE 9160 2 11 11 11 11 a Ventilation with ventilation DIN Schiene pac Carrier horizontal Installation Single unit Orientation any vertical Type Reise 11 11 on 10 11 9160 19 11 11 11 11 BE 10 11 BE 11 11 Channels 5 2
2. CE de type Qualitatssicherung Produktion Production Quality Assessment Assurance Qualit e Production Waldenburg 13 03 2003 Ort und Datum r Ing A Schimmele Place and date Leiter Marketing und Entwicklung EN 50014 1997 EN 50020 1994 EN 50284 1999 EN 50281 1 1 1998 EN 50021 1999 EN 61326 1 1997 DMT 03 ATEX E 010 X PTB 96 ATEX 0006 3 lieu et date Director Development and Engineering Direcior Quality management dept Directeur technique et d veloppement Directeur dept assurance de qualit 19 EG Baumusterpr fbescheinigung 20 EG Baumusterpr fbescheinigung Richtlinie 94 9 EG Ger te und Schutzsysteme zur bestimmungsgem en Verwendung in explosionsgef hrdeten Bereichen DMT 03 ATEX E 010 X Gerit Messumformerspeiseger t Typ 9160 1 11 Hersteller R STAHL Schaltger te GmbH Anschrift D 74638 Waldenburg Die Bauart dieses Ger tes sowie die verschiedenen zul ssigen Ausf hrungen sind in der Anlage zu dieser Baumusterpr fbescheinigung festgelegt Die Zertifizierungsstelle der Deutsche Montan Technologie GmbH benannte Stelle Nr 0158 gem Artikel 9 der Richtlinie 94 9 EG des Europ ischen Parlaments und des Rates vom 23 M rz 1994 bescheinigt dass das Ger t die grundlegenden Sicherheits und Gesundheitsanforderungen f r die Konzeption und den Bau von Ger ten und Schutzsystemen zur bestimmungsgem en Verwendung in explosionsgef hrdeten Bereichen gem Anhan
3. in denen keine h heren Spannungen als AC 250 V 50 Hz auftreten k nnen e Die sicherheitstechnischen Werte der des angeschlossenen Feldger te s m ssen mit den Angaben des Datenblattes bzw der EG Baumusterpr fbescheinigung bereinstimmen e Bei Zusammenschaltungen mehrerer aktiver Betriebsmittel in einem eigensicheren Stromkreis k nnen sich andere sicherheitstechnische Werte ergeben Hierbei kann die Eigensicherheit gef hrdet werden Die nationalen Sicherheits und Unfallverh tungsvorschriften Die allgemein anerkannten Regeln der Technik Die Sicherheitshinweise dieser Betriebsanleitung Besch digungen k nnen den Explosionsschutz aufheben Verwenden Sie das Ger t bestimmungsgem nur f r den zugelassenen Einsatzzweck siehe Funktion Fehlerhafter oder unzul ssiger Einsatz sowie das Nichtbeachten der Hinweise dieser Betriebsanleitung schlie en eine Gew hrleistung unsererseits aus Umbauten und Ver nderungen am Ger t die den Explosionsschutz beeintr chtigen sind nicht gestattet Das Ger t darf nur in unbesch digtem trockenem und sauberem Zustand eingebaut und betrieben werden 2 Normenkonformitat Die Messumformerspeisegerate Typen 9160 entsprechen den folgenden Normen bzw der folgenden Richtlinie e Richtlinie 94 9 EG e EN50 014 EN 50 020 e EN50021 Messumformerspeiseger t Typ 9160 3 Betriebsanleitung 3 Funktion deutsch Die Messumformerspeisegerate werden zum eigensicheren Bet
4. rail and tilt snap until it locks in Do not tilt at an angle to either side when snapping onto the pac Bus Note In order to prevent pole reversal during installation the pac Bus elements have been equipped with a keyed connection plug see photo The module is fitted with a matching slot Dismount as described below in b 15 Transmitter Supply Unit Type 9160 Operating Instructions english d Mounting in the pac Carrier Remove the black and green terminals Set the IS pac modules in place as described in a and b and completely tilt snap into the pac Carrier Close the red latching lever using gentle pressure The latching lever must engage completely To dismount use a screwdriver to open the latching mechanism as shown in the picture The module is nudged out of the slot and can be removed 7 Commissioning 7 1 Connections Hazardous Safe area area pac bus Types 9160 1 11 FNE F 2 OF OE EL Le 1 em SCH E G run Gest at OF O1 gef A ES with HART 1 Types 9160 19 1 11 one input two outputs 2 90 O thar ELILE Versions 9160 11 11 11 and 9160 21 11 11 do not pass HART signals Connection of power supply green terminal pin 9 7 Type of power supply Direct supply of the transmitter Green terminal PIN 9 and 7 supply unit Power supply via pac Bus See chapter 6 3 c 16 Transmitter Supply Uni
5. spac Typ Type 9160 Messumformerspeisegerat Transmitter Supply Unit Betriebsanleitung Operating Instructions Inhaltsverzeichnis 1 Sicherheitshinweisen ne ae dee 3 2 Weu DV eu Mel dun EE 3 3 PUN enee See A A Kennzeichnung und technische Daten ee 4 5 Projektierung ansehen 5 5 1 Maximal zul ssige Umgebungstemperaturen nenn 5 EE e EE 5 5 3 Projektierung der Verlustleistung in Gchaltschr nken seen 6 6 Anordnung und Montage EE 7 6 1 MaBZ6ICNNUNG eneren a a a a 7 62 _ Jostalation eneen a ed ec Wilde E Eet 7 6 3 Montage und Demontage 5 inca re ee 7 7 Inbetriebnahme 2 2 a2 aa i ea ET le 8 E WE UE 8 ZS Einstellungen san bee 9 8 Betrieb Und Betriebszust nde 20a 2 ar 10 9 Reparatur und Instandhaltung a ae ea 10 10 Zubeh r Und Ersatztelle ua ei 10 Contents 1 EES EE EE et 11 2 GOHIOFMIYIO SIANdarde unseren ee e een 11 3 ll edel EE 12 4 Marking and technical EE 12 5 nie nee ET 13 5 1 Engele le 13 5 2 POWErCISSIDATION EE 13 5 3 Engineering of the power dissipation in Cabinets cceceeeeeeeeeeeestteeeeeeeeeeeeeeees 14 6 Arrangement and TENG DEE 15 6 1 PRIME ISO ROTI Gs EE EE 15 6 2 2 istallato en Zee ee 15 6 3 Mounting and dismduntling ae ae aa 15 7 COMMISSIONE BE 16 71 CEDIES E Ee 16 Tar SCHUNG Sih tte ee ee re ee ae ee 17 8 Operation and operational States AA 18 9 Maintenance and repair sun een mu ee er 18 10 Accessories and spare P lts uu u 18 EG Konformit tserkl rung EC Dec
6. we nous R STAHL Schaltger te GmbH Am Bahnhof 30 D 74638 Waldenburg 9160 1 11 erkl ren in alleiniger Verantwortung dass das Produkt Messumformerspeiseger t hereby declare in our sole responsibility that the product Transmitter supply unit d ciarons de notre seule responsabilit que le produit Convertisseur MAMMA avec alimentation capteur auf das sich diese Erkl rung bezieht mit der den folgenden Norm en oder normativen Dokumenten bereinstimmt which is fhe subject of this declaration is in conformity with the following standard s or normative documents auquel cette d claration se rapporte est conforme aux norme s ou aux documents normatifs suivants Titel und oder Nr sowie Ausgabedatum der Norm title and or No and date of issue of the standard titre et ou No ainsi que date d mission des normes Bestimmungen der Richtlinie terms of the directive prescription de Ja directive 94 9 EG Gerate und Schutzsysteme zur bestimmungsgem en Verwendung in explosionsgef hrdeten Bereichen 94 Q EC Equipment and protective systems intended for use in potentially explosive atmospheres 94 9 CE Appareils et syst mes de protection destin s fr utilis s en atmosph res explosibies 89 336 EWG Elektromagnetische Vertr glichkeit 89 336 EEC Electromagnetic compatibility 89 336 CEE Compatibilite lectromagn tigue EG Baumusterprufbescheinigung EC Type Examination Certificate Attestation d examen
7. 4 20 mA 600 Q 0 4 20 mA 20 60 70 C 40 80 C lt 95 Weitere technische Daten sind dem aktuellen Datenblatt zu entnehmen bitte RUcksprache mit dem Hersteller Bei anderen vom Standard abweichenden Betriebsbedingungen nehmen Sie 4 Messumformerspeiseger t Typ 9160 deutsch Betriebsanleitung 5 Projektierung 5 1 Maximal zul ssige Umgebungstemperaturen Die Ger te der Reihe IS pac sind ber einen weiten Temperaturbereich einsetzbar Je nach Ger teausf hrung und Einbaubedingung ergeben sich unterschiedliche maximal zul ssige Umgebungstemperaturen Bel ftung Installation Einzelger t DIN Schiene pac Tr ger Einbaulage beliebig vertikal horizontal lt SH aan B 9160 2 11 11 Bel ftung DIN Schiene pac Tr ger horizontal vertikal Horizontal Typ 5 2 Verlustleistung In den Datenblattern wird die max Verlustleistung im Nennbetrieb Ausgang 20 mA Hilfsenergie 24 V DC Last 250 Q angegeben Da in der Praxis nicht alle Gerate gleichzeitig unter Volllast betrieben werden erfolgt die Projektierung Ublicherweise mit einer durchschnittlichen Verlustleistung von 70 P70 Typ Kan le max Verlustleistung 70 Verlustleistung 9160 13 10 11 9160 1 11 11 i GA EYY 9160 19 10 11 9160 19 11 11 be SE VE 9160 23 10 11 Messumformerspeisegerat Typ 9160 5 Betriebsanleitung deutsch 5 3 Projektierung der Verlustleistung in Sch
8. Power dissipation vertical horizontal Data sheets are describing the maximum power dissipation in standard operation output 20 mA power supply 24 V DC load 250 Q In practice not all isolators are working with full load Therefore engineering is done typically with an average power dissipation of 70 P70 Type Channels max power dissipation 70 power dissipation 9160 13 10 11 9160 1 11 11 as 9160 19 10 11 9160 19 11 11 an 9160 23 10 11 17W 9160 2 11 11 Transmitter Supply Unit Type 9160 13 Operating Instructions english 5 3 Engineering of the power dissipation in cabinets When electronic devices are integrated in cabinets free air movement is restricted and the temperature rises To minimise the temperature rise it is important to optimise the power dissipation as well as the elimination of the produced heat inside a cabinet a Natural Convection in closed cabinets e _ Application when the dissipated power is moderate and when the system operates in a dusty or harsh environment D Calculation of the maximum allowed power dissipation Pmax At S K Pmax W max allowed power dissipation in the cabinet At C max allowed temperature rise S m free heat emitting surface of the cabinet K W m C thermal emitting coefficient K 5 5 for painted steel sheets The calculated value for Pmax has to be smaller than the total average power dissipation 70 of max power dissip
9. Umgebung oder die hohe Verlustleistung keine nat rliche Konvektion erlauben e Funktion ein W rmetauscher mit L fter saugt Luft in den Schrank und dr ckt sie in die W rmetauscherplatten die durch einen zweiten L fter mit Umgebungsluft gek hlt werden e Ergebnis Je nach Ausf hrung kann die 5 bis 6 fache zul ssige Verlustleistung wie unter a erreicht werden d Erzwungene Bel ftung in offenen Schr nken e Funktion Ein oder mehrere L fter erzeugen einen Luftstrom von der unteren Schrank ffnung an den Ger ten vorbei durch die obere Schrank ffnung hinaus e Berechnung des notwendigen Luftstroms Q 3 1 3 Pos At Q mh notwendiger Luftstrom P70 W entstehende Verlustleistung 70 der max Verlustleistung At C zul ssige Temperaturerh hung im Schaltschrank e Klimaanlage e Anwendung bei hei em Klima eine Schranktemperatur gleich gro oder geringer als die Umgebungstemperatur ist erreichbar e Funktion Nutzung eines spezifisches K ltemaschinen Systems oder des existierenden Klimasystems f r die Schrankk hlung 6 Messumformerspeiseger t Typ 9160 deutsch Betriebsanleitung 6 Anordnung und Montage 6 1 Ma zeichnung a MaB X Schraubklemmen 108 mm Federzugklemmen Schneid Klemm Technik 6 2 Installation Das Messumformerspeiseger t ist in der Zone 2 oder au erhalb exp
10. altschranken Beim Einbau von Ger ten innerhalb von Schaltschranken wird der freie Luftstrom begrenzt und die Temperatur steigt Um die Temperaturerh hung zu minimieren ist es wichtig die Verlustleistung sowie die produzierte W rme innerhalb des Schrankes zu optimieren a Nat rliche Konvektion in geschlossenen Schr nken e Anwendung bei geringer Verlustleistung und wenn das System in einer staubigen oder rauen Umgebung installiert ist e Berechnung der maximal zul ssigen Verlustleistung Pmax At S K Pmax W max zul ssige Verlustleistung im Schaltschrank At C max zul ssige Temperaturerh hung S m freie warme emittierende Oberfl che des Schaltschrankes K W m C thermischer Leitf higkeitskoeffizient lackierter Stahl K 5 5 Der errechnete Wert Pmax muss kleiner als die Summe der durchschnittlichen Verlust leistungen 70 der max Verlustleistung der eingebauten Ger te sein Pmax lt amp P70 b Nat rliche Konvektion in offenen Schr nken e Funktion die W rme wird mittels k hler Luftstr me zwischen den Ger ten verdr ngt e Voraussetzungen Luftein und auslass ffnungen an den unteren und oberen Enden des Schrankes der Weg des Luftstroms muss frei von Hindernissen gehalten werden e Ergebnis Je nach Ausf hrung kann die doppelte zul ssige Verlustleistung wie unter a erreicht werden c Erzwungene Bel ftung mit W rmetauscher in geschlossenen Schr nken e Anwendung wenn entweder die
11. ate relates only to the design examination and tests of the specified equipment in accordance to Directive 94 9 EC Further requirements of the Directive apply to the manufacturing process and supply of this equipment These are not covered by this certificate The marking of the equipment shall include the following e 1 GD IEEX ia IICHTB and 3G EExnACHT4 Deutsche Montan Technologie GmbH Essen dated 05 February 2003 Signed Jockers Signed Eickhoff DMT Certification body Head of special services unit Page of 3 to DMT 03 ATEX E010 X This certificate may only be reproduced in its entirety and without change Am Technologiepark 1 45307 Essen Telefon 0201 172 1416 Telefax 0201 172 1716 21 23 R STAHL Schaltgerate GmbH Am Bahnhof 30 74638 Waldenburg W rtt Germany www stahl de ID Nr 91 606 01 310 S BA 9160 006 de en 08 2006
12. ation of the installed isolators Pmax lt 3 P70 b Natural convection in open cabinets e Function the heat is removed by cool air flowing through the devices e Requirements inlet and outlet ports in the lower and upper ends of the cabinet the air flow path must be kept free from obstacles e Result Depending on the engineering the improvement can reach a two times higher power dissipation as with a c Forced ventilation with heat exchanger in closed cabinets e Application when either the harsh environment or the high dissipated power do not allow natural convection e Function a heat exchanger with a fan pulls the air into the cabinet and pushes it into the heat exchanger plates that are cooled by the external ambient air moved by a second fan e Result Depending on the engineering the improvement can reach a 5 or 6 times higher power dissipation as with a d Forced ventilation in open cabinets e Function the filtered air is taken from the bottom cabinet openings by one or more fans flows through the devices and finally exits at the top of the cabinet e Calculation of the required air flow Q 3 1 P7o At Q m h required air flow P70 W dissipated power 70 of max power dissipation At C allowed temperature rise in the cabinet e Air conditioned cabinets e Application for hot climates it is possible to reach a cabinet temperature equal or even lower than the ambient temperature e Fun
13. ction a specific refrigerating system or the existing air conditioning system can be used for cabinet conditioning 14 Transmitter Supply Unit Type 9160 english Operating Instructions 6 Arrangement and fitting 6 1 Dimension drawing x Size X Screw terminals 108 mm Spring clamp terminals Insulation displacement 131 mm connectors 122 14 5 Ld 14 EC N HH 6 2 Installation The transmitter supply units may be installed in Zone 2 Zone 22 or outside hazardous areas In the case of operation in Zone 2 or Zone 22 the transmitter supply unit must be fitted in an enclosure which complies with the requirements of EN 50 021 or EN 50 281 e g in an enclosure type 8146 from the R STAHL Schaltger te GmbH company 6 3 Mounting and dismounting a Detachable terminals All devices are provided with detachable terminals A screwdriver is needed to remove the terminals as shown in the picture b Mounting on DIN rails in accordance with EN 50 022 Set the device on the DIN rail and tilt snap onto the rail as depicted Do not set at an angle For removal pull the base latch out a little with a screwdriver and remove the module c Mounting on DIN rails with an already installed pac Bus As depicted in the photo set the device in position on the pac Bus already mounted on the DIN
14. ctions english 8 Operation and operational states Before commissioning the device please ensure that e the device has been installed in the correct slot and in accordance with the standards e the device is not damaged e the cables are properly connected In case of detected line faults Output signal input signal 9 Maintenance and repair It is recommended that all repairs to our devices be carried out by R Stahl In exceptional cases repair may be performed by approved third parties The devices are maintenance free Troubleshooting chart Error detection Cause of error Corrective action PWR LED not lit Power supply failure or device fuse is Check power supply defective If device fuse is defective send device in for repair If the procedure described above does not obtain the desired result please contact your local R STAHL sales and service representative In order to quickly process your request please provide us with the following information Type and serial number Purchase date s Description of the error Application description particularly the configuration of the input output circuitry 10 Accessories and spare parts Use only original accessories and spare parts from R STAHL Schaltgerate GmbH 18 Transmitter Supply Unit Type 9160 EG Konformitatserklarung EC Declaration of Conformity EG Konformitatserklarung EC Declaration of Conformity CE D claration de Conformite Wir
15. e devices or components impairing their explosion protection are permitted The device may only be fitted and used if it is in an undamaged dry and clean state 2 Conformity to standards The Type 9160 transmitter power supply devices comply with the following standards and directives e Directive 94 9 EC e EN 50 014 EN 50 020 e DIN EN 50 021 Transmitter Supply Unit Type 9160 11 Operating Instructions 3 Function english The transmitter supply units are used in the operation of 2 wire and 3 wire transmitters or to connect to intrinsically safe mA current sources The 2 wire and 3 wire transmitters are supplied with power by the transmitter power supply unit The devices bidirectionally transfer a superimposed HART communications signal 4 Marking and technical data Manufacturer Type designation CE marking Ex marking Explosion protection marking and Testing authority and certificate number Ambient temperature range Safety data Max voltage U Max current Max power P Internal capacitance C inductance Li Max connectable capacitance C IIC IIB Max connectable inductance L IIC IIB Insulation voltage Un R STAHL 9160 1 1 L Ee amp IL 1 G D EEx ia IIC IIB 113 G EEx nAC II T4 DMT 03 ATEX E 010 X 20 C 60 70 C 27V 88 mA 576 mW negligible 90 nF 705 nF 2 3 mH 14 mH 250 V See EC type examination certificate for further information and value combinations
16. ehlersuchplan Fehlererkennung Fehlerursache Fehlerbehebung LED PWR erloschen Hilfsenergie ausgefallen oder Hilfsenergieversorgung kontrollieren Ger tesicherung defekt Bei defekter Sicherung das Ger t zur Reparatur geben F hren die beschriebenen Vorgehensweisen nicht zum gew nschten Erfolg wenden Sie sich bitte an unsere n chste Vertriebsniederlassung Zur schnellen Bearbeitung ben tigt diese von Ihnen folgende Angaben e Typ und Seriennummer e Kaufdaten e Fehlerbeschreibung e Einsatzzweck insbesondere Eingangs Ausgangsbeschaltung 10 Zubehor und Ersatzteile Verwenden Sie nur Original Zubeh r sowie Original Ersatzteile der Fa R STAHL Schaltger te GmbH 10 Messumformerspeiseger t Typ 9160 english Operating Instructions 1 Safety instructions The most important safety instructions are summarised in this chapter It is intended to supplement the relevant regulations which must be studied by the personnel responsible When working in hazardous areas the safety of personnel and plant depends on complying with all relevant safety regulations Assembly and maintenance staff working on installations therefore have a particular responsibility The precondition for this is an accurate knowledge of the applicable regulations and provisions When installing and operating the device the following are to be observed H The national installation and assembly regulations e g EN 60079 14 apply e The transmitte
17. g II der Richtlinie erf llt Die Ergebnisse der Pr fung sind in dem Pr fprotokoll BVS PP 03 2005 EG niedergelegt Die grundlegenden Sicherheits und Gesundheitsanforderungen werden erf llt durch bereinstimmung mit EN 50014 1997 Al A2 Allgemeine Bestimmungen EN 50020 1994 Eigensicherheit i EN 50284 1999 Ger tegruppe II Kategorie 1G EN 50281 1 1 1998 Staubexplosionsschutz EN 50021 1999 Z ndschutzart n Falls das Zeichen X hinter der Bescheinigungsnummer steht wird in der Anlage zu dieser Bescheinigung auf besondere Bedingungen f r die sichere Anwendung des Ger tes hingewiesen Diese EG Baumusterpr fbescheinigung bezieht sich nur auf die Konzeption und die Baumusterpr fung des beschriebenen Ger tes in bereinstimmung mit der Richtlinie 94 9 EG F r Herstellung und Inverkehrbringen des Ger tes sind weitere Anforderungen der Richtlinie zu erf llen die nicht durch diese Bescheinigung abgedeckt sind Die Kennzeichnung des Ger tes muss die folgenden Angaben enthalten II 1 GD EEx ia IIC IIB und 3G EEx nAC II T4 Deutsche Montan Technologie GmbH Essen den 05 Februar 2003 Fachbereichsleiter Seite 1 von 3 zu DMT 03 ATEX E 010 X Dieses Zertifikat darf nur unver ndert weiterverbreitet werden Am Technologiepark 1 45307 Essen Telefon 0201 172 1416 Telefax 0201 172 1716 EC Type Examination Certificate A DMT Translation EC Type Examination Certificate Directive 94 9 EC Equ
18. ipment and protective systems intended for use in potentially explosive atmospheres DMT 03 ATEX E 010 X Equipment Transmitter Supply Unit type 9160 1 11 Manufacturer ER STAHL Schaltger te GmbH Address D 74638 Waldenburg The design and construction of this equipment and any acceptable variation thereto are specified in the schedule to this type examination certificate The certification body of Deutsche Montan Technologie GmbH notified body no 0158 in accordance with Article 9 of the Directive 94 9 EC of the European Parliament and the Council of 23 March 1994 certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of equipment and protective systems intended for use in potentially explosive atmospheres given in Annex II to the Directive The examination and test results are recorded in the test and assessment report BVS PP 03 2005 EG The Essential Health and Safety Requirements are assured by compliance with EN 50014 1997 A1 A2 General requirements EN 50020 1994 Intrinsic safety i EN 50284 1999 Equipment Group II Category 1G EN 50281 1 1 1998 Dust explosion protection EN 50021 1999 Type of protection n If the sign X is placed after the certificate number it indicates that the equipment is subject to special conditions for safe use specified in the schedule to this certificate This EC Type Examination Certific
19. laration of Conformity 244440ssssnnnnnnnnnnnnnnnnennn 19 EG Baumusterpriifbescheintgumg nn 20 EC Type Examinatlon GeritiGate area a en 21 deutsch Betriebsanleitung 1 Sicherheitshinweise In diesem Kapitel sind die wichtigsten SicherheitsmaBnahmen zusammengefasst Es erganzt die entsprechenden Vorschriften zu deren Studium das verantwortliche Personal verpflichtet ist Bei Arbeiten in explosionsgefahrdeten Bereichen hangt die Sicherheit von Personen und Anlagen von der Einhaltung aller relevanten Sicherheitsvorschriften ab Das Montage und Wartungspersonal tr gt deshalb eine besondere Verantwortung Die Voraussetzung daf r ist die genaue Kenntnis der geltenden Vorschriften und Bestimmungen Bei Errichtung und Betrieb ist Folgendes zu beachten e Es gelten die nationalen Montage und Errichtungsvorschriften z B EN 60079 14 e Das Messumformerspeiseger t ist in Zone 2 Zone 22 oder au erhalb explosionsgef hrdeter Bereiche zu installieren e Bei Einsatz in Zone 2 ist das Messumformerspeiseger t in ein Geh use einzubauen das den Anforderungen der EN 50 021 gen gt e Bei Einsatz in Zone 22 ist das Messumformerspeisegerat in ein Geh use einzubauen das den Anforderungen der EN 50 281 gen gt Bei Einsatz in Zone 2 und Zone 22 d rfen an die eigensicheren Eingangsstromkreise eigensichere Ger te der Zonen 1 0 21 und 20 angeschlossen werden Das Messumformerspeiseger t darf nur an Ger te angeschlossen werden
20. losionsgef hrdeter Bereiche zu installieren Bei Betrieb in Zone 2 ist das Messumformerspeiseger t in ein Geh use einzubauen das den Anforderungen der EN 50 021 gen gt z B in ein Geh use Typ 8146 der Fa R STAHL Schaltger te GmbH 6 3 Montage und Demontage a Die abziehbaren Klemmen Alle Ger te sind mit abziehbaren Klemmen versehen Zum Abziehen die Klemmen mit z B einem Schraubendreher wie im Bild dargestellt l sen b Montage auf DIN Schienen nach EN 50 022 Ger te wie im Foto dargestellt ansetzen und auf die DIN Schiene aufschwenken Dabei nicht verkanten Zur Demontage den Fu riegel mit einem Schraubendreher etwas herausziehen und das Modul entnehmen c Montage auf Hutschienen mit installiertem pac Bus Ger te wie im Foto oben dargestellt ansetzen und auf die DIN Schiene mit dem pac Bus aufschwenken Dabei nicht verkanten Hinweis um eine Verpolung bei der Installation zu Verhindern sind die pac Bus Elemente mit einer Codierleiste siehe Foto und die Module mit dem entsprechendem Codierschlitz versehen Demontage wie unter b beschrieben 7 Messumformerspeiseger t Typ 9160 Betriebsanleitung deutsch d Montage im pac Trager Schwarze und gr ne Klemmen entfernen Die IS pac Module wie unter a und b beschrieben ansetzen und in den pac Tr ger vollst ndig einschwenken Den roten Rasthebel mit leichtem Druck schlie en Der Rasthebel muss vollst ndig eingerastet sein Zur Demontage de
21. n Rastmechanismus mit einem Schraubendreher wie im Bild dargestellt ffnen Das Modul wird aus dem Steckplatz geschoben und kann entnommen werden 7 Inbetriebnahme 7 1 Anschl sse Ex Bereich Sicherer Bereich pac bus oo 24 V DC 2 oi oO Ls mit HART 2 A D amp him Typen 9160 1 11 Gest at 1 ei OF Ciy I GL 7 D I THT A Typen 9160 19 1 11 ein Eingang zwei Ausg nge Varianten 9160 11 11 11 und 9160 21 11 11 komplett ohne HART bertragung Anschluss der Speisung Gr ne Klemme 9 7 Art der Versorgung Wo schlie t man an Direkte Versorgung des Mess Gr ne Klemme mit den PIN s 9 und 7 umformerspeiseger tes Versorgung ber pac Bus Siehe Kapitel 6 3 Punkt c 8 Messumformerspeiseger t Typ 9160 Eingangsbeschaltung blaue Klemmen mit den PINs 10 11 12 und 13 14 15 6 Zwei Leiter Drei Leiter mA Quelle Messumformer Messumformer 4 Leiter MU Kanal 2 Kanal 1 Hinweis F r eine funktionierende HART Kommunikation im Ausgangsstromkreis ist ein Lastwiderstand z B Eingangswiderstand der Eingangsbaugruppe von mindestens 250 Q notwendig Steht dieser nicht zur Verf gung kann zus tzlich der interne 221 Q Widerstand verwendet werden Der Anschluss muss dann an den Klemmen 3 2 bzw 4 6 erfolgen Die maximale Ausgangslast verringe
22. r supply unit may be installed in Zone 2 Zone 22 or outside the explosion hazard areas e In the case of operation in Zone 2 the transmitter power supply unit must be fitted in an enclosure which complies with the requirements of EN 50 021 e In the case of operation in Zone 22 the transmitter power supply unit must be fitted in an enclosure which complies with the requirements of EN 50 281 e When used in Zone 2 and Zone 22 intrinsically safe devices of Zones 1 0 21 and 20 may be connected to the intrinsically safe input circuits e _ The transmitter power supply unit may only be connected to devices which will not be subjected to voltages higher than AC 250 V 50 Hz e The safe maximum values of the connected field device s must correspond to the values of the data sheet or the EC type examination certificate e Interconnecting several active devices in an intrinsic safety circuit may result in other safe maximum values This could endanger the intrinsic safety e National safety and accident prevention regulations e _ The generally recognised technical regulations e _ The safety guidelines in these operating instructions e Any damage can compromise and even neutralise the explosion protection Use the device in accordance with the regulations and for its intended purpose only see Function Incorrect or impermissible use or non compliance with these instructions invalidates our warranty provision No changes to th
23. rieb von 2 und 3 Leiter Messumformern oder zum Anschluss an eigensichere mA Quellen eingesetzt Die 2 und 3 Leiter Messumformer werden vom Messumformerspeisegerat mit Hilfsenergie versorgt Die Ger te bertragen ein berlagertes HART Kommunikationssignal bidirektional 4 Kennzeichnung und technische Daten Hersteller Typbezeichnung CE Kennzeichnung Ex Kennzeichnung Kennzeichnung Explosionsschutz und Pr fstelle und Bescheinigungsnummer Umgebungstemperaturbereich Sicherheitstechnische Daten max Spannung U max Strom Io max Leistung Po innere Kapazit t C Induktivit t L max anschlie bare Kapazit t C IIC IIB max anschlieBbare Induktivit t Lo IIC IIB Isolationsspannung Um R STAHL 9160 1 1 Lac amp IL 1 G D EEx ia IIC IIB 113 G EEx nAC II T4 DMT 03 ATEX E 010 X 20 60 70 C 27V 88 mA 576 mW vernachlassigbar 90 nF 705 nF 2 3 MH 14 mH 250 V Weitere Angaben und Wertekombinationen siehe EG Baumusterpr fbescheinigung Technische Daten Auszug aus dem Datenblatt Hilfsenergie Nennspannung Un Nennstrom bei Uy und Iamax 1 2 Kan le Leistungsaufnahme bei Uy und Iamax 1 2 Kan le Ex i Eingang Speisespannung f r Messumformer Eingangssignalbereich Ausgang Bereich f r Lastwiderstand B rde Ausgangssignalbereich Umgebungsbedingungen Betriebstemperatur Lagertemperatur relative Feuchte keine Betauung 24 VDC 70 mA 125 mA 1 7W 3W 16 V 0
24. rt sich auf 479 Q Die Varianten 9160 11 11 11 und 9160 21 11 11 verf gen nicht ber eine HART Kommunikation 7 2 Einstellungen Leitungsfehlererkennung LF Deaktiviert Aktiviert Standardeinstellung bei Auslieferung Bitte beachten Die Leitungsfehlererkennung bezieht den Eingang und Ausgang mit ein Bei der Ger tevariante 9160 19 bezieht sich die Fehlererkennung auf den gemeinsamen Eingang und den entsprechenden Ausgangskanal Offene Ausg nge f hren deshalb zu einer Fehlermeldung Nicht genutzte aktive Ausg nge sollten mit einem 250 Ohm Widerstand beschaltet werden Die nderung der DIP Schalter Einstellungen ist im Betrieb auch in der Zone 2 und bei angeschlossenen eigensicheren Eingangssignalen zul ssig Betriebsanleitung deutsch 8 Betrieb und Betriebszustande Bevor Sie das Ger t in Betrieb nehmen stellen Sie sicher dass e das Ger t vorschriftsm ig im korrekten Steckplatz installiert wurde e das Ger t nicht besch digt ist e die Kabel ordnungsgem angeschlossen sind Bei detektierten Leitungsfehler ist Ausgangssignal gleich dem Eingangssignal 9 Reparatur und Instandhaltung Es wird empfohlen Reparaturen an unseren Ger ten ausschlie lich durch uns durchf hren zu lassen In Ausnahmef llen kann die Reparatur auch durch eine andere zugelassene Stelle erfolgen Die Ger te sind wartungsfrei F
25. t Type 9160 Input connections blue terminals PIN 10 11 12 and 13 14 15 Two wire Three wire mA source transmitter transmitter Channel 2 Channle 1 Channel 2 Channel 1 Note A working HART communication requires a minimum load resistance e g input resistance of input card of 250 Q in the output circuit Is this not available the internal 221 Q resistance can be used Then the connection has to be done on terminals 3 2 or 4 6 The maximum output load is reduced to 479 Q The Versions 9160 11 11 11 and 9160 21 11 11 do not support HART communication 7 2 Settings Line Fault detection LF Deactivated Activated E E l LF2 5 LF2 Channel 2 2 Default factory setting Please note The line fault detection is applied for the input and output circuits The version 9160 19 offers an one input two output structure The line fault detection monitors the common input channel and the according output channel An open output without load leads to fault indication Please connect a load of 250 Ohm to the unused output The DIP switch settings may be changed during operation in Zone 2 as well and in the case of connected intrinsically safe input signals Operating Instru