manuale di istruzioni all'utilizzatore installazione – uso
Contents
1. Fig B Fig C Close on rise and Open on rise and reopen on fall Recluse on fall 2 0 START UP Also the operations of starting up of instrument on process shall be made with the highest care just to avoid accidents to people and to things In particular we highly recommend to start very gradually the loading of instrument with the liquid to be controlled by paying the highest attention not to exceed the max values of Pressure and Temperature reported on the Project of system on the instrument Plate and on the specific Drawing accompanying the instrument This way the operator is in condition of immediately intervening in case of any mistake and thus avoid risks of damages to people and to things In any case water hammers on the instrument are absolutely to be avoided if too strong they might cause uncertain functions and in the most severe cases also a total blocking of it DOMIZI 10 MDLS During the normal function of plant we recommend To get near instrument very prudently it may contain very hot or very cold liquids and so may cause serious burns to people e To open drain and vent valves of instrument with much caution very dangerous liquids may come out as very hot very cold corrosive or under pressure and may cause damages to people and to things What happens in case of fire The instrument is composed mainly by metal and so cannot
2. DOMIZI Snc Tel 39 011 9457022 Via Polesine 15 Fax 39 011 9457021 D ni ZI 10020 CAMBIANO E mail sales domizi com Indicatori di livello Level indicators Interruttori di livello Level switches Strumenti pneumatici Pneumatic instruments TORINO ITALY www domizi com Manuale MDLS 12 05 MANUALE DI ISTRUZIONI ALL UTILIZZATORE INSTALLAZIONE USO PRECAUZIONI INSTRUCTION TO USER MANUAL MOUNTING OPERATING CAUTION INTERRUTTORE DI LIVELLO Mod DLS LEVEL SWITCHES Type DLS Lo strumento viene prodotto in base alle specifiche dell acquirente e nel pieno rispetto delle Norme nazio nali e internazionali sulla Qualit e Sicurezza Viene consegnato dalla fabbrica solo dopo aver superato i controlli intermedi ed il collaudo finale viene sempre accompagnato dal presente Manuale generale dal Disegno tecnico che ne elenca le prestazioni specifiche e dal Certificato di prova che ne attesta il collaudo individuale pertanto pronto per essere installato sul serbatoio Le operazioni di installazione e di manutenzione dovranno essere eseguite solo da personale adegua tamente preparato allo scopo Se vengono rispettati i dati riportati in questi documen ti lo strumento certamente in condizione di assicu rare prestazioni di alta qualit e di lunga durata Si consiglia perci di porre la massima attenzione alle Istruzioni che seguono integrandole con tutto ci che proviene dalla propria esperienza e dal buon
3. Category 1 2 Esplosive mixture Gas Nome e indirizzo del fabbricante nm NOTE In the case of Level Switch operating at temperatures such that may cause burns on persons an adjunctive plate is fixed on the instrument in order to caution about the possible risk DOMIZI 8 MDLS 1 INSTALLATION Every operations regarding receipt and installation of instrument even if assigned to long experienced personnel shall be made with the norm of the maximum security to avoid accidents to persons and things 1 1 Instrument unpacking Transport up to final destination case opening and picking up of instrument from the case shall be made always with the norm of protection and safety of persons and always with the help of proper lifting means of gloves glasses shoes and clothes recommended by Safety Standards Even if instruments have no protrusion or roughness able to cause wounds and abrasions it is recommended to handle everything with the highest care 1 2 Mechanical connections We recommend to operate always with the protection of gloves glasses shoes and clothes listed by Safety Standards and by using the most proper tools Every operations shall be made only by skilled personnel In particular to connect the instrument to vessel it is necessary to shut off the cocks in order to stop the flow from and to vessel to put the instrument forward the connection points of the system and to fix it we re
4. Lo strumento opera cosi quando il livello sale all altezza stabilita l aria compressa viene aperta ON e quando il livello ridiscende l aria viene richiusa OFF 1 Idue funzionamenti possono essere invertiti facilmente secondo le necessit dell impianto 1 5 Come invertire il funzionamento Per invertire il funzionamento bisogna seguire le seguenti fasi 1 Chiudere l alimentazione dell aria d ingresso allo strumento 2 Allentare la vite esagonale Fig C 5 e sfilare il porta flap Fig C 7 3 Svwitare le 2 viti a brucola Fig B 2 e sfilare delicatamente la base portarel Fig B 1 facendo attenzione a non smarrire i 4 O ring di tenuta presenti posteriormente 4 Ruotare di 180 la base porta rel Fig B 1 e rimontarla fissandola con le 2 viti a brucola Fig B 2 e gli O rings 5 Inserire il porta flap Fig C 7 ruotato di 180 e fissarlo con l apposita vite esagonale Fig C 5 cercando di posizionarlo il pi perpendicolare possibile all ugello Fig B 4 6 Infine seguire le fasi di taratura riportate di seguito DOMIZI 4 MDLS 1 6 Taratura Sia se fatta in una vasca di prova sia se fatta direttamente sull impianto assolutamente necessario che sia visibile il galleggiante immerso Chiusura in salita e riapertura in discesa l 2 3 4 5 Portare il livello del fluido a met galleggiante assicurandosi che l alimentazione dell aria sia aperta Allentare controdado Fig C 6 per permett
5. be primary source of fire and furthermore when requested by purchaser instruments are supplied in ATEX certified flame proof version But in the case that fire comes from outside environment the instrument does not suffer significant damages The instrument has been realized with wide safety margin so that can certainly assure the performances requested by purchaser to Domizi Snc even in the case of slight overloads in pressure and temperatures on condition that they come under the limits listed in the Test Instructions of ASME ANSI Standards In the usual cases two instruments are used on the same vessel so that the first one performs the normal control function e g High level operation and the second one operates instead of the first in case of breakdown and activates also an alarm High High level alarm But in the case of important mistakes in process management the instrument might be subject to sudden peaks of pressures and temperatures having values totally out of those communicated in the order to Domizi Snc and so it might be subject to structural damages just in order to avoid this damage and other much heavier effects on the remaining parts the plant designer realizes a proper and effective protection system 3 0 PERIODICAL MAINTENANCE Mechanical maintenance During the time a periodical cleaning of inside instrument from possible deposits may be necessary according to the type of liquids cleaning could be made about 1 2
6. la massima attenzione e controllare infine anche la tenuta dei collegamenti eseguiti allo scopo di evitare il rischio di successive perdite di liquidi in pressione corrosivi o caldi freddi e perci potenzialmente pericolosi per la salute umana e per l ambiente esplosioni e incendi 1 3 Collegamenti pneumatici Collegare i tubi dell aria ai connettori dello strumento che si trovano sulla base della custodia Bisogna impiegare solo aria strumenti cio aria filtrata e depurata da umidit ed olio Quest aria dovr entrare nel foro marcato IN ed uscire dal foro marcato OUT verso l utilizzatore il terzo foro situato nella parte posteriore della custodia serve per l eventuale recupero dell aria di sfiato i tre fori sono filettati 4 NPT F Alla fine bisogna anche controllare che non ci siano perdite d aria lungo i tubicini esterni alla custodia con l impiego ad es di acqua saponata Anche se non necessario in questa fase dei collegamenti possibile giungere alle parti interne della custodia aprendo il coperchio dopo aver sganciato l apposito dispositivo situato sul lato destro tra IN e OUT 1 4 Funzionamento dello strumento Lo strumento assicura i seguenti funzionamenti e Chiusura in salita e riapertura in discesa Lo strumento opera cosi quando il livello sale all altezza stabilita l aria compressa viene chiusa OFF e quando il livello ridiscende l aria viene riaperta ON Apertura in salita e richiusura in discesa
7. senso generale Indice degli argomenti e Funzionamento e Targhe Pag 23 Installazione montaggio Pag 4 Taratura ob xt amp oe e we yw Rage 9 Messainfunzione Pag 5 e Manutenzione smontaggio montaggio Pag 6 Problemi e soluzioni 20 Pag 6 Disegno specifico dello strumento Allegato The instrument is manufactured on the basis of the purchaser s specifications and in the total conformity of national and international standards about Quality and Safety It is delivered by the factory only after having passed positively intermediate and final tests it is always accompanied by the present general Manual by the technical Drawing listing the specific performances of it and by the Test certificate stating the individual final test of it Consequently it is ready to be installed on the vessel All the installing and maintenance operations shall be made only by skilled personnel If purchaser effects the technical data reported in these documents the instrument is certainly in condition of assuring high quality and long life performances We recommend to pay the max attention to the following instruction integrating them with all that may come from your own experience and general good sense Table of contents Operation and Plates Page 7 Installation assembling Page 9 Calibration Pagel0 e Startup 2 s s s s 5 Pagel e Maintenance dismantling
8. times a year It is recommended to proceed in the various steps with the highest care to avoid risks for health of people burns poisonings etc and for environment protection fires explosions etc In any case after having put on gloves glasses and suitable clothes would you please Shut off the inlet and outlet cocks in order to block the liquid to and from the instrument to be checked f necessary wait until the instrument come back to environmental temperature f present on the instrument open with much prudence the top vent valve and the bottom drain valve taking care to avoid splashes of inner liquid because potentially corrosive and dangerous Unscrew the nuts from connection flanges and remove the instrument from system with much care Make the inner cleaning of instrument with jets of compressed air of steam etc and at then re assemble everything by proceeding in the above sequence but on the contrary Fill very prudentially the instrument with the liquid and start up it 3 2 Pneumatic maintenance In order to avoid dangers to people and to pneumatic system we recommend to shut off the compressed air circuit In the case of impurities e g oil water etc in the air feeding it may happen that after time the relay stops working act with the max attention and dismantle the entire pneumatic device clean it with care and assemble it exactly as before 4 0 PROBLEMS AND SOLUTIONS The liquid does not push flo
9. ES ON LEVEL SWITCHES When the Level Switches are certified ATEX 94 9 CE European directive establishing the rules to get safety as maximum as possible by equipments intended for areas with potentially explosive atmospheres they have the following plates MEANING F LEVEL SWITCH oe e d uc INTERRUTTORE DI LIVELLO v duo assieme by purchaser j Vei iii Serial No of instrument Year of production bun i te i Max pressure of fluid SerialNo A Productionyear Operative pressure of fluid OTR Pressure Max bar Temperature of Process and Ambient RE Pressure Oper bar Specific gravity of fluid M Proc T min max C Pneumatic feed n Amb T min max C t Specific gravity of fluid kg m OB maik Ai switch 2 bar 0496 Notified body supervising the production i Attention Per invertire la funzione ruotare la base porta rel di 180 seguendo il Manuale di Istruzioni To inverse the function rotate the relay holder base of 180 as per the Instruction Manual E European standards c Apparatus safety housing CE 0496 n2 Ge T6 IIC Gas group T6 Temperature class E 2 KEMA 05 ATEX 2126 Kema Notified body 2005 Certificate year Ccertificate No pO Demy www domizi com sales domizi com Via Polesine 15 o 10020 Cambiano Torino Italia o Tel 39 011 945 70 22 Fax 39 011 945 70 21 Equipment for areas with explosive atmospheres Group II
10. anche la funzione contraria Intervento in discesa e Ripristino in salita Un differenziale cos piccolo ottenibile agendo sulla combinazione tra volume e peso del galleggiante e lunghezza del braccio che sostiene il galleggiante APPLICAZIONI Controllo di livello su serbatoi di vari liquidi industriali in impianti petroliferi su piattaforme e su terra ferma L interruttore DLS pu controllare il livello di liquidi con pressione fino a 500 Bar con temperature fino a 300 C e con pesi specifici da 500 kg m in su PRINCIPIO DI FUNZIONAMENTO Interruttori con montaggio di Lato Il MANOMETRO IN MANOMETRO DUT X DOMIZI 2 MDLS TARGA SUGLI INTERRUTTORI Quando gli Interruttori di Livello sono certificati ATEX 94 9 CE Direttiva europea che stabilisce le regole per ottenere la massima sicurezza possibile dagli apparecchi destinati ad operare in zone con miscele di gas potenzialmente esplosive essi presentano le seguenti targhe SIGNIFICATO Codice dello strumento e Sigla assegnata dall acquirente Num serie dello strumento Anno di produzione Pressione massima del fluido M Pressione operativa del fluido v e Temperatura di Processo e Ambiente Peso specifico del fluido v Alimentazione pneumatica Marchio CE Ente Notificato che sorveglia la produzione Apparecchio per zone con atmosfera potenzia
11. assembling Pagell Problems and solutions Pagell Specific drawing of instrument Attached 1 M DLS PRINCIPIO DI FUNZIONAMENTO In questa pagina viene illustrato il principio di funzionamento dello strumento solamente in modo generico mentre nel Disegno tecnico allegato viene mostrato lo strumento specifico richiesto dall acquirente con tutte le caratteristiche e le prestazioni nominali che chiamato a realizzare Come illustrato nello schizzo e nella Fig A pi sotto gli interruttori DLS sono montati sul fianco di serbatoi piuttosto stretti Il livello del liquido viene controllato da un galleggiante solidale con un tubetto metallico molto flessibile entro il tubetto si trova un tondino fissato ad una sola estremit la spinta idrostatica proveniente dal galleggiante provoca una flessione del tubetto esterno e di conseguenza una spinta laterale del tondino interno che fa scattare il dispositivo d uscita all interno della custodia Quando il livello sale oltre il punto prestabilito il galleggiante fa scattare il dispositivo pneumatico posto dentro la custodia intervento in salita poi quando il livello ridiscende al di sotto di tale punto il galleggiante riporta il dispositivo allo stato di partenza ripristino in discesa tra i punti di intervento e di ripristino vi un differenziale di circa 5 10mm L intervento avviene quando il liquido raggiunge all incirca la linea mediana del galleggiante disponibile
12. at upwards or sink it Maybe the instrument should be placed at a different height on vessel or is not perfectly vertical The liquid is at sufficient level but does not push the float Maybe the float is damaged cracked or deformed it should be replaced The Level switch operates on the contrary Inverse the operation position as per above para 1 5 After the function inversing a malfunction of the Switch and some air lacking happen Verify that the four O ring are correctly placed on the rear of relay holder as per above para 1 5 Ifa repair is necessary would you please contact the seat of Domizi Snc directly 11 MDLS outid
13. commend to install it so that housing remains in horizontal position It is necessary to use tie rods nuts gaskets and other components absolutely suitable for the performances requested by the system named process too and to tighten tie rods on flanges with a dynamometric wrench correctly calibrated according to the instructions of flange s manufacturer It is also necessary to operate with the max attention and to check the seal of these mechanical connections in order to absolutely avoid the risk of subsequent liquid leaks they may be under pressure or corrosive or too cold hot and so may be potentially dangerous for human health and environment fires and explosions 1 3 Pneumatic connections Connect the air pipes to the instrument connectors placed on the outside base of housing It is necessary to use only instruments air that is air already filtered and purified from moisture and oil The air shall go in through the IN union and go out through the QUT union towards the user the third hole placed on the rear of housing is for the possible recovery of vent air unless it is differently indicated in the specific drawing of instrument the three holes are 4 NPT F threaded At the end it is also necessary to check that there is no air leak along the outside pipes by wetting them for example with soapy water Even if not necessary on this stage it is possible to reach the inner parts of housing by releasing the device placed on
14. e dello strumento per liberarle da eventuali depositi lasciati dal liquido sotto controllo tale pulizia pu essere eseguita indicativamente 1 2 volte all anno a seconda del tipo di liquido Si dovr procedere nelle varie fasi con la massima attenzione per evitare di correre rischi per la salute delle persone scottature intossicazioni etc e per la salvaguardia dell ambiente esplosioni incendi etc In ogni caso dopo aver indossato guanti occhiali e vestiti adeguati bisogna smontare lo strumento con queste fasi e Chiudere le valvole che intercettano l entrata e l uscita del liquido dallo strumento Se necessario attendere che l intero strumento sia tornato alla temperatura ambientale per evitare scottature Se sono presenti sullo strumento aprire con molta cautela la valvola di sfiato superiore e quella di drenaggio inferiore badando a ripararsi da eventuali spruzzi del liquido interno perch pu essere corrosivo e pericoloso e Svitare i dadi dai tiranti delle flange e staccare con delicatezza lo strumento dall impianto Effettuare la pulizia interna dello strumento con getti d aria compressa di vapore etc Alla fine rimontare il tutto adoperando nuove guarnizioni sulle flange e procedendo nelle sequenza di sopra ma naturalmente in senso inverso Riempire lo strumento nuovamente con il liquido da controllare e rimettere in funzione lo strumento 3 2 Manutenzione pneumatica Per evitare pericoli al
15. ere la regolazione del flap Fig B 3 Svitare manualmente il flap Fig B 3 fino a chiudere l uscita dell aria dall ugello del rel Fig B 4 Perfezionare la regolazione in questo modo abbassare il livello del fluido fino a provocare la riapertura del rel e fare in modo che in tale condizione il galleggiante non sia totalmente fuori dal fluido ma che abbia una piccola parte ancora immersa in tal modo si avr un buon margine di sicurezza Stringere il controdado Fig C 6 per fissare la taratura eseguita Apertura in salita e chiusura in discesa l W 2 0 Portare il livello del fluido leggermente oltre la met galleggiante assicurandosi che l alimentazione dell aria sia aperta Allentare controdado Fig C 6 per permettere la regolazione del flap Fig B 3 Avvitare manualmente il flap Fig B 3 fino ad aprire l uscita dell aria dall ugello del rel Fig B 4 Perfezionare la regolazione in questo modo abbassare il livello del fluido fino a provocare la chiusura del rel e fare in modo che in tale condizione il galleggiante non sia totalmente fuori dal fluido ma che abbia una piccola parte ancora immersa in tal modo si avr un buon margine di sicurezza Stringere il controdado Fig C 6 per fissare la taratura eseguita Fig B Fig C Chiu
16. la persona ed all impianto pneumatico si raccomanda di chiudere la condotta dell aria compressa dell alimentatore del circuito Nel caso di sporcizia presente nell alimentazione dell aria si pu verificare nel tempo il blocco del rel In tal caso procedere con molta attenzione smontando tutta la parte pneumatica pulirla e rimontarla esattamente come prima 4 0 PROBLEMI E SOLUZIONI Il liquido non solleva il galleggiante oppure lo sommerge Forse lo strumento va sistemato ad un altezza diversa sul serbatoio oppure non perfettamente orizzontale Il liquido a livello sufficiente ma non aziona il galleggiante Forse il galleggiante danneggiato deformato occorre sostituirlo e L Interruttore opera al contrario di quello desiderato Invertire la posizione di lavoro ved Punto 1 5 di questo Manuale d istruzione Dopo aver effettuato l inversione del funzionamento si verifica un mal funzionamento e delle perdite d aria Verificare che non si siano smarriti i quattro O ring presenti dietro la base porta rel ved Punto 1 5 di questo Manuale d istruzione ncaso di necessit di una riparazione preghiamo interpellare direttamente la sede della Domizi Snc DOMIZI 6 MDLS OPERATION PRINCIPLE In this page only the generic operation principle is shown while the function regarding the specific instrument requested by purchaser is shown in the enclosed Technical Drawing with all the nominal specificatio
17. llo strumento Il trasporto fino alla destinazione finale l apertura della cassa di imballo ed il prelievo dello strumento dalla cassa deve avvenire sempre con il criterio della salvaguardia dell incolumit e sicurezza delle persone e sempre e con l ausilio di appropriati mezzi di sollevamento di guanti occhiali scarpe e vestiti previsti dalle Norme di Sicurezza Anche se lo strumento non presenta sporgenze o ruvidit tali da provocare tagli ed abrasioni normale prudenza maneggiare tutto con molta cura e attenzione 1 2 Collegamenti meccanici Si raccomanda di operare sempre con la protezione di guanti occhiali scarpe e vestiti previsti dalle apposite Norme di Sicurezza e di usare sempre gli utensili pi adeguati allo scopo Tutte le operazioni dovranno essere eseguite solo da personale adeguatamente preparato allo scopo In particolare per collegare lo strumento al serbatoio bisogna chiudere le valvole di intercettazione in modo da interrompere il flusso del liquido da e verso il serbatoio affacciare lo strumento ai punti di collegamento dell impianto e poi fissarlo si raccomanda di installarlo in modo che la custodia rimanga in posizione orizzontale Bisogna adoperare tiranti dadi guarnizioni ed altri componenti di tipo adeguato alle prestazioni richieste dall impianto e serrare 1 tiranti sulle flange con chiave dinamometrica opportunamente tarata a seconda di quanto richiesto dal costruttore delle flange Bisogna operare con
18. lmente esplosiva Gruppo II Categoria 1 2 Miscela esplosiva Gas E Norme europee armonizzate c Custodia a sicurezza costruttiva IIC Gruppo dei gas T Classi di temperature KEMA Ente Notificato 2005Anno di certificazione Numero di certificazione Nome e indirizzo del fabbricante LEVEL SWITCH INTERRUTTORE DI LIVELLO Code Tag Serial No gt Pressure Max bar Production year Pressure Oper bar Proc T min max C Amb T min max C Specific gravity of fluid kg m Pneumatic switch 2 bar Attention Per invertire la funzione ruotare la base porta rel di 180 seguendo il Manuale di Istruzioni To inverse the function rotate the relay holder base of 180 as per the Instruction Manual CA CE 0496 E 1 2 Gc T6 KEMA 05 ATEX 2126 DOMIT Via Polesine 15 10020 Cambiano Torino Italia o Tel 39 011 945 70 22 Fax 39 011 945 70 21 www domizi com sales domizi com NOTA Nel caso di Indicatore di Livello operante a temperature tali da costituire pericolo di scottature per la persona viene aggiunta una targa di avvertimento sullo strumento DOMIZI 3 MDLS 1 INSTALLAZIONE Tutte le operazioni di ricezione e installazione dello strumento devono essere affidate a personale di lunga esperienza e devono essere eseguite con i criteri della massima sicurezza per evitare incidenti alle persone ed alle cose 1 1 Disimballo de
19. ns and perfor mances of it As shown in the below Fig A the Level switches DLS are mounted on a side of vessels even if very narrow The liquid level is checked by a float integral with a small and very flexible tube within this tube there is a rod fixed on only an end the lift coming from float causes a bending on the outer tube and consequently a side thrust on the inner rod that makes the output device trip trip on rise then when the level comes down again and exceeds the preset point the float makes the output device come back to the initial point reset on fall between the set and the reset points there is always a small gap named differential of about 5 10mm The trip happens when level reaches about the median line of the float The inverse function is available too Trip on fall and Reset on rise A so small differential can be obtained thanks to the combination between volume and weight of float and length of the arm supporting the float APPLICATIONS Level control on vessels containing various types of industrial liquids in off shore and in shore oil plants The Switch can operate with liquids having pressures up to 500 Bar temp up to 120 C and specific gravity from 500kg m up PRINCIPIO DI FUNZIONAMENTO Interruttori con montaggio di Lato MANOMETRO IN MANOMETRO pute NIN UN DOMIZI DUT DOMITI 7 MDLS PLAT
20. nto non pu essere fonte primaria di incendio ed inoltre quando richiesto dall acquirente vengono forniti strumenti in versione certificata ATEX antideflagrante Nel caso per che l incendio provenisse dall ambiente esterno lo strumento in s non subisce danni significativi Lo strumento stato realizzato con ampi margini di sicurezza in modo che possa svolgere egregiamente i compiti comunicati dal committente alla Domizi Snc anche in caso di lievi sovraccarichi in pressione e temperature purch rientranti nei limiti previsti dalle Istruzioni di Collaudo delle Norme ASME ANSI Di norma si prevede la messa in opera sul serbatoio di due strumenti in modo che il primo esegua il normale lavoro di controllo ad es intervento per Livello Alto ed il secondo intervenga al posto del primo in caso di avaria e faccia scattare anche un allarme ad es allarme per Livello Altissimo Se pero in seguito ad errori di manovra nella gestione dell impianto lo strumento venisse sottoposto a colpi improv visi di pressioni e di temperature con valori totalmente al di fuori di quelli previsti dalle Norme ASME ANSI potrebbe nascere il rischio di un suo cedimento strutturale per evitare questo cedimento ed altre conseguenze ancora pi gravi al resto il progettista dell impianto realizza un adeguato sistema di protezione 3 0 MANUTENZIONE PERIODICA 3 1 Manutenzione meccanica Nel tempo pu rendersi necessaria la pulizia periodica delle parti intern
21. sura in salita e Apertura in salita e riapertura in discesa richiusura in discesa MESSA IN FUNZIONE Anche la messa in funzione dello strumento sull impianto deve essere eseguita con la massima attenzione sempre per evitare incidenti alle persone e danni alle cose Avviare con molta gradualit il riempimento dello strumento con il liquido da controllare facendo la max attenzione a non superare i valori di Pressione e di Temperatura indicati nel progetto dell impianto e riportati nei dati di Targa dello strumento e nel Disegno specifico che lo accompagna In tal modo si avr la possibilit di intervenire in tempo nel caso di qualche svista nei collegamenti e di evitare quindi rischi di danni a persone ed a cose Sono comunque da evitare colpi di ariete sullo strumento perch se fossero molto forti potrebbero provocare malfunzionamenti e nei casi limite il blocco completo dello strumento Durante il normale funzionamento dell impianto si raccomanda di DOMIZI 5 MDLS Avvicinarsi con molta cautela allo strumento pu contenere liquidi molto caldi o molto freddi e quindi pu cau sare delle serie scottature alle persone Aprire con cautela le valvole di spurgo e di sfiato dello strumento possono uscire liquidi corrosivi molto caldi o molto freddi oppure sotto pressione e quindi potenzialmente pericolosi per l uomo e per l ambiente Cosa capita in caso di incendio Lo strumento costituito principalmente di metallo e perta
22. tem it is necessary that the dipped float is well visible Close on rise and reopen on fall I 2 3 4 5 Fill the fluid up to half height of float and verify that air feeding is open Loosen the counter nut Fig C 6 in order to allow the calibration of the flap Fig B 3 Unscrew the flap by hand Fig B 3 up to close the air from the relay nozzle Fig B 4 Make perfect the calibration this way empty out the fluid up to cause the reopening of air from the relay and act so that in this condition the float is not totally out of fluid but a small part of it is still dipped this way you will have a good safety margin Tighten the counter nut again Fig C 6 to fix the calibration Open on rise and reclose on fall l 2 3 4 Fill the fluid up to a little bit more than the half height of float and verify that air feeding is open Loosen the counter nut Fig C 6 in order to allow the calibration of the flap Fig B 3 Unscrew the flap by hand Fig B 3 up to open the air from the relay nozzle Fig B 4 Make perfect the calibration this way empty out the fluid up to cause the reclosing of air from the relay and act so that in this condition the float is not totally out of fluid but a small part of it is still dipped this way you will have a good safety margin Tighten the counter nut again Fig C 6 to fix the calibration
23. the cover between IN and OUT marks 1 4 How the instrument operates The instrument performs the following functions Close on rise and reopen on fall It operates as follows when level rises up to the preset height the compressed air is closed OFF and when comes down again the air is reopened ON Openon rise and reclose on fall It operates as follows when level rises up to the preset height the compressed air is opened ON and when comes down again the air is reclosed OFF The two functions can be easily reversed according to the needs of the system 1 5 How to reverse the function on the instrument If you wish to invert the function the following steps are necessary 1 Close the compressed air feeding to the instrument 2 Loosen the hexagonal screw Fig C 5 and remove the flap holder Fig C 7 3 Loosen the 2 socket head cap screws Fig B 2 and gently remove the base of relay holder Fig B 1 by caring not to lose the 4 sealing O rings placed on the rear 4 Rotate of 180 the above base of relay holder Fig B 1 and fix it again by the 2 screw and the 4 O rings 5 Insert the flap holder Fig C 7 already rotated of 180 and fix it by the proper hexagonal screw Fig C 5 by caring to place it as perpendicular as possible to the nozzle Fig B 4 6 Atthe end follow the calibrating steps described as follows POMIZI 9 MDLS 1 6 Calibration Both if made in a test basin and if made directly on the sys
Download Pdf Manuals
Related Search
Related Contents
Philips myVision 871829112757400 energy-saving lamp Load500 Serial Communication Software for the CP500 Cinema ACTA DE CONSTITUCIÓN DEL GTBySP DE LA U.G.C. DE Toshiba Satellite Z30-A-12R User Manual Richtlinie GH-868 Security Video and DVR Integration System User Manual Bedienungsanleitung Plantronics schnurloses DECT Headset Moen T6110 User's Manual "取扱説明書" Copyright © All rights reserved.