Home
        Vacon 10 complete user manual.book
         Contents
1.      7 2 Display    The display has 14 segments and 7 segment blocks  arrowheads and clear text  symbols  The arrowheads  when visible  provide certain information about the drive   This information appears in the form of clear text on the overlay  numbers 1    14 in  the figure below   The arrowheads are divided into 3 groups with the following  meanings and text on the overlay  see figure 7 1      Group 1   5  Drive status  1   Drive is ready to run  READY   2   Drive is running  RUN   3   Drive has stopped  STOP   4   Alarm is activated  ALARM   5   Drive has stopped due to a fault  FAULT     Group 6   10  Control settings  6   Motor is rotating forwards  FWD   7   Motor is rotating backwards  REV      s  E S  1 0  Terminal block is selected control setting  de E S  1 0     9   Keypad is selected control setting  KEYPAD    10   Fieldbus is selected control setting  BUS   Group 11   14  Navigation menu   11   Reference menu  REF    12   Monitoring menu  MON    13   Parameter menu  PAR    14   Fault history menu  FLT     24 hour service 807 499 023 e e mail  vacon dvacon com       28   VACON CONTROL PANEL       1 2 3 4 5  READY RUN STOP ALARM FAULT        12  13  14  Navigation FWD REV gl O KEYPAD BUS  wheel  S ig p    10    t al  m tton    Figure 7 1  Vacon 10 control panel    7 3 Panel  The keypad section of the control panel consists of a navigation wheel and a fault  reset start up assistant button and a system identification button  see Figure 7 1    The navigation whee
2.     5Hz Field weakening point  par 3 7    Figure 10 4  Setting Minimum Load    TORQUE CURVE AT ZERO FREQUENCY   Torque limit can be set between 0 0 150 0   x TnMotor  This paramter  provides the minimum torque value permitted at zero frequency  See Figure  1 22     If the value of parameter 1 4 is changed  nominal motor current   this  parameter automatically resets to the default value     VACON   61       62    VACON PARAMETER DESCRIPTIONS       6 8    UNDERLOAD PROTECTION TIME LIMIT   This time can be set between 2 0 and 320 00 s    This is the maximum amount of time permitted in underload status  An  internal timer measures the time accumulated in underload status  If the  underload timer exceeds this limit  the protection will cause a fault as in  parameter 6 5  If the pump stops  the underload timer resets to zero  See  Figure 1 23     Underload timer        Par  6 8  Hit warning  par 6 5  Time  Underload          No underload zx  LI EE    Figure 10 5  Underload Timer Function    MOTOR THERMAL PROTECTION  PARAMETERS 6 9   6 11   Motorthermal protection is to protectthe motor from overheating  The Vacon  drive is capable of supplying higher than nominal current to the motor  If the  load requires this high current there is a risk that the motor will thermally  overheat  This is particularly the case at low frequencies  At low frequencies  the cooling effect of the motor is reduced as well as its capacity  If the motor  is equipped with an external fan the load reduction 
3.    motor     insulation failure in cables or  motor    w comBonsntfail  re Reset the fault and restart   System fault      He ti If the fault recurs  contact the  PASSO nearest distributor     Table 5 1  Fault codes       24 hour service 807 499 023 e email  vacon dvacon com       22   VACON    FAULT TRACING       Possible cause  code  DC link voltage has exceeded the  internal safety limit     most probable cause  too low  a supply voltage    frequency converter internal  fault    Power outages    Undervoltage    Frequency  converter low  temperature    IGBT switch temperature is below   109C    IGBT switch temperature is above  120  C  Overheating warning is  issued when IGBT switch  temperature exceeds 110  C     Frequency  converter  overheating    Motor overheating has been  detected by frequency converter  motor temperature model  Motor  is overloaded     Motor  overheating    Underload  EEPROM fault    Microcontroller  watchdog fault    The motor is underloaded   Eg  lack of input water     Parameter save fault    faulty operation    component failure      faulty operation    component failure    Analog input  lin    4 mA     selected signal  range 4 to 20  mA     Table 5 1  Fault codes    CX    Current at the analog input is     4mA    control cable is broken or  loose    signal source has failed    Correcting actions    In case of temporary supply  voltage break reset the fault  and restart the frequency  converter  Check the supply  voltage  If it is adequate  an  i
4.   Display contrast    S    1  Restores factory  Restore factory defaults defaults for all  parameters       Table 8 22  System parameters    NOTE  Parameters in bold are hidden  see P8 1     www vacon com       PARAMETER DESCRIPTIONS VRCON   51       10  PARAMETER DESCRIPTIONS    The following pages list the descriptions of certain parameters  Descriptions have  been arranged according to parameter group and number     GROUP 1  Quick setup parameters    1 7  AUTOCHANGE MODE  This parameter allows the user to select the autochange mode for the  system     Autochange is used to make pump wear more uniform     0   No autochange  Connection disconnection order of pumps will always  remain the same and the controller will regulate the speed of the first pump     1   Auxiliary autochange without interlocks  Controller regulates the speed  of the first pump and auxiliary pumps alternate  connecting and  disconnecting      2  Total autochange without interlocks  Controller alternates the regulation  of all pump speeds in the system     3   Auxilliary autochange with interlocks  Controller regulates the speed of  the first pump and auxiliary pumps alternate  connecting and  disconnecting   Interlocks are required to connect pumps     5   Total autochange with interlocks  Controller alternates regulation of the  speed of all the pumps in the system  Interlocks are required to connect  pumps     1 8   NUMBER OF AUXILIARY PUMPS  Auxiliary pumps assist the main pump   For example  a press
5.   the fault mode is activated  Otherwise  the fault is cleared after                                                                   the trial time has elapsed and the next fault starts the trial time count again  See  Figure 10 8   If one single fault remains during the trial time  fault mode is true   Wait time Wait time  Wait time   par 10 1 par 10 1 par 10 1  Fault trigger   i  Motor stop signal  Restart 1 Restart 2  Motor start signal  Supervision SENE i Trial time 7 E  par 10 2  Fault active  RESET   Fault reset             Autoreset function   Trials   2     Figure 10 8  Automatic restart    24 hour service 807 499 023 e e mail  vacon dvacon com       66    VACON PARAMETER DESCRIPTIONS       7 4 AUTOMATIC RESTART  TRIAL TIME    A binary code is inserted in this parameter to enable or disable automatic  restarts for some faults     Example    Bit 0   Undervoltage   Bit 1   Overvoltage   Bit 2   Overcurrent   Bit 3   Motor Overheating  Bit 4   Underload   Bit 5   User Error    Examples     1  If we only want to restart the controller when Undervoltage and  Overvoltage faults appear  we should set P7 4 to 3    2  If we only want to restart the controller when Undervoltage and  Overcurrent faults appear  we should set P7 4 to 5    3  If we only want to restart the controller when Overcurrent faults apper   we should set P7 4 to 4     www vacon com       TECHNICAL DATA VACON    67       11  TECHNICAL DATA  11 1 Vacon 10 technical data    WETS nput voltage Uin  connection 
6.  250Vac 2A or 250Vdc 0 4A       Pump 2 Control    Max  switching load   250Vac 2A or 250Vdc 0 4A       Table 6 10  PFC System preset I O connections and settings for Vacon 10       www vacon com    PFC SYSTEM INTERFACE VACON    25                         x VACON 10     moe la m E  i arr  3    mee mo   mU    spe  E D                m  on at af                               Figure 4  2 pump autochange systems  sample control diagram    movi       n VACON 10 a  PET os  3 po     s DI e 15 mi    sx    aA al s jay        ose iy Lan  a 7 a AE  to ef u e                                                                   N           p ml e wi    E                                           MiNacon Attimis Manacor mamans NiYacon Mais    Figure 5  3 pump autochange system  sample control diagram    24 hour service 807 499 023 e e mail  vacon dvacon com       26   VACON PFC SYSTEM INTERFACE                   PE       NX12k107 ds4                                  PE  NX12k104 ds           Mi    Figure 7  Example of 3 pump autochange  power diagram    www vacon com       CONTROL PANEL VACON    27       7  CONTROL PANEL    7 1 General    The panel is integrated into the drive and consists of the corresponding E S card and  cover with an overlay that contains the display and buttons     The Control panel consists of an LCD display with backlight and a keypad including  a navigation wheel  a green system identification button and a red fault reset start   up assistant button  see Figure 7 17 1 
7.  9 8 Hide parameters   9 9 System parameters  10 Parameter descriptions   10 1 Quick setup parameters   10 2 Advanced PFC settings   10 3 Motor Control   10 4 Analog Inputs   10 5 Output Signals   10 6 Protection   10 7 Automatic Restarts  11 Technical data   11 1 Vacon 10 technical data   11 2 Power ratings   11 2 1 Vacon 10   Mains voltage 115 V  11 2 2 Vacon 10   Mains voltage 208   240 V  11 2 3 Vacon 10   Mains voltage 380   480 V          36  36  39  40  41  42  44  45  46  47  48  49  49  51  51  52  55  59  60  61  65  67  67  69  69  69  70    www vacon com    4   VACON SarETY       1 SAFETY    ONLY A COMPETENT ELECTRICIAN IS ALLOWED TO CARRY  OUT THE ELECTRICAL INSTALLATION     This manual contains clearly marked cautions and warnings which are intended for  your personal safety and to avoid any unintentional damage to the product or  connected appliances     Please read the following safety information carefully       Dangerous voltage  Risk of death or severe injury               General warning  Risk of damage to the product or    connected appliances                   1 1 Warnings    The components of the power unit of the frequency converter are live when Vacon  10 is connected to the mains  Coming into contact with this voltage is extremely  dangerous and may cause death or severe injury  The control unit is isolated from  the mains     The motor terminals U  V  W  T1  T2  T3  and the possible brake resistor terminals       are live when Vacon 10 is connected 
8.  Input frequency 45   66 Hz    THD Line current    12095  Once per minute or less  normal case     newer  network that have a phase to ground  ort circuit current ee maximum short circuit current must be lower  MN CE MM    Connecting RSG    the motor Output current In estimated direct current at max  room  temperature   50  C  overload 1 5 x ly max  1 min   10 min     tarting current   torque x ly current for 2 s every 20s  pue  Torque depends on the motor   characteristics Open Loop Sensorless Vector Control    Braking torque 100  Ty with brake option   only for 400 V  gt  1 5 kW  30  Ty without brake  option       Table 11 1  Vacon 10 technical data    24 hour service 807 499 023 e e mail  vacon dvacon com       68   VACON TECHNICAL DATA       Ambient Operating ambient i 2 ADOC  load capacity  conditions temperature    ANETO    Relative humidity 0   95  RH  with no condensation  rust or  dripping water     Air qualit  hemical vapours IEC 721 3 3  unit in operation  class 3C2  IEC 721 3 3  unit in operation  class 352  100  load capacity  without reduction  of up to  1000 m  1  reduction per 100 m above 1000 m   max  2000 m     Vibration  3   150 Hz   EN60068 2 6 Shift range 1 spike  mm  at 3   15 8 Hz Max  range of acceleration  1 G at 15 8   150 Hz    Knocks  IEC 68 2 27 Storage and shipping  Max of 15 G  11 ms   with packaging     Type of enclosure  Complies with EN50082 1   2  EN61800 3    Emissions 230 V  Complies with EMC category C2  level H Vacon   With an internal R
9.  N and L3 of the frequency  converter and from the mains  Measure the insulation resistance of the mains cable  between each phase conductor as well as between each phase conductor and the  protective ground conductor  The insulation resistance must be   1MOhm   3  Motor insulation checks  Disconnect the motor cable from the motor and open the bridging connections in the  motor connection box  Measure the insulation resistance of each motor winding     The measurement voltage must equal at least the motor nominal voltage but not  exceed 1000 V  The insulation resistance must be   1MOhm     www vacon com       COMMISSIONING VACON    19       4  COMMISSIONING    Before commissioning  note the warnings and instructions listed in  Chapter 1     4 1 Commissioning steps of Vacon 10    Read the safety instructions in Chapter 1 carefully and follow them     After installation  make sure that     both the frequency converter and the motor are grounded    the mains and motor cables comply with the requirements given  in Chapter 3 2 3    the control cables are located as far as possible from the power  cables  see Chapter 3 2 4  step 2  and that the shields of the  shield cables are connected to protective ground    Check the quality and quantity of cooling air  Chapter 3 1 2   4 Check that all Start Stop switches connected to the 1 0 terminals are in  Stop position     5 Connect the frequency converter to mains    Note  The following steps are valid if you have an API Full or API Limit
10.  chapters 9 and 10     The following figure shows the parameter menu display        I3      alternates     L I l   Il l  I L    in the display LI  LIL           FWD REV IO KEYPAD BUS       2     gt   gt   gt    h  Browse Push to enter Change Push to  P1 1  gt  edit mode value confirm    Figure 7 5  Parameter menu    24 hour service 807 499 023 e e mail  vacon dvacon com       34   VACON CONTROL PANEL       7 4 5 Fault history menu                                                    READY RUN STOP ALARM FAULT EADY RUN STOP ALARM FAULT    E B dr qum  MON  MONI is  su  o      Fi  UU  Fura R4       SE REV Wo KEYPAD sus Push FWD REV IO KEYPAD BUS  Browse    faults 1 9  EADY RUN STOP ALARM FAUL EADY RUN STOP ALARM FAUL   REF   REF  M o   ud LEX T   LI Inn  ma   d  LUI   V ma   ILILILI  FLT    FLT    g  FWD REV WO KEYPAD BUS Fush FWD REV iO KEYPAD  Browse CA  for hours  H    minutes  M     and seconds  S   Figure 7 6  Fault history menu    You can browse through the last nine faults in the fault history menu  see Figure 7 6    If a fault is active  the corresponding fault reference  e g  F1 02  alternates in the  display with main menu  When you browse through the faults  the codes of active  faults flash  Active faults can be reset by pressing the stop button for 1 second  If  the fault cannot be reset  it will continue to flash  It is also possible to navigate  through the menu when there are active faults  but the display returns automatically  to the fault menu if no buttons or t
11.  has stopped working  you can reopen the pressure  unit intake and the equipment is ready to function     24 hour service 807 499 023 e e mail  vacon dvacon com       40   VACON PARAMETERS       9  SYSTEM PARAMETERS  On the next pages you will find the lists of parameters within their respective  parameter groups  The parameter descriptions are given in Chapter 10   NOTE  Some parameters can only be changed when the controller is in stop mode     Explanations     Code  Keypad Location  Shows the operator the monitoring value number of  current parameter number     Parameter  Parameter name or monitoring value    Min  Minimum value of parameter  Max  Maximum value of parameter  Unit  Unit of parameter value  given if available  Default  Factory preset value  ID  ID number of the parameter  used with fieldbus control   3 More information on this parameter available in chapter 10   Parameter    descriptions  and click on the name of the parameter     www vacon com       PARAMETERS VACON   41       9 1 Quick setup parameters     Pi Eee  getrarameterseg FAMI  Fees ipa alta E gres Note aient  Check specification plate on  110  the motor  111 Check specification plate on  the motor  o Default applies for a 4 pole  112  the motor motor   Nominal current Check specification plate on  the motor the motor    of  on    0   No Autochange   1   Aux  autochange   without interlocks   2   Autochange all without  Autochange Mode interlocks   3   Aux  autochange with   interlocks   4   Autocha
12.  of transport damages to the  product and that the delivery is complete  compare the type designation of the  product to the code below      If the drive is damaged during shipping  please contact the shipper s insurance  company or the carrier     If the delivery does not correspond to your order  contact the supplier immediately   2 1 Type designation code    Vacon 0010   1L   0001   4 Machinery  IPN1  SMO2    Changes to default setup    SMO01   API RS 485    API Full   EMC2   EMC C4   gt  EMC C2       Version    Voltage rating  2   208 240Vac  4   380 480Vac       Current rating          Input phase       Product range       Figure 2 1  Vacon 10 type designation code    2 2 Storage    If the frequency converter is to be kept in store before use make sure that ambient  conditions are acceptable     Storage temperature 40    70  C  Relative humidity  lt  95   no condensation    2 3 Maintenance    In normal operating conditions  Vacon 10 frequency converters are maintenance   free     24 hour service 807 499 023 e e mail  vacon dvacon com       8   VACON RECEIPT OF DELIVERY       2 4 Warranty    Only manufacturing defects are covered by the warranty  The manufacturer  assumes no responsibility for damages caused during or resulting from transport   receipt of the delivery  installation  commissioning or use     The manufacturer shall in no event and under no circumstances be held responsible  for damages and failures resulting from misuse  wrong installation  unacceptable  am
13.  to measuring the motor or the motor cable  disconnect  the motor cable from the frequency converter     Do not open the cover of Vacon 10  Static voltage discharge  from your fingers may damage the components  Opening the  cover may also damage the device  If the cover of Vacon 10 is  opened  warranty becomes void     PPPPP    1 3 Grounding and ground fault protection    The Vacon 10 frequency converter must always be grounded with a ground  conductor connected to the grounding terminal  See figure below        e The ground fault protection inside the frequency converter  protects only the converter itself against ground faults     e  f ground fault current protective switches are used  they must be  tested on the drive with ground fault currents that may arise in  fault situations     24 hour service 807 499 023 e e mail  vacon dvacon com       6   VACON SarETY       1 4 Before running the motor  Checklist     Before running the motor  check it is correctly installed and  make sure that the machine it is connected to allows the  motor to be started     Set the maximum motor speed  frequency  according to the  motor and the machine connected to it     Before reversing the motor shaft rotation direction make sure  that this can be done safely     Make sure that no power correction capacitors are connected  to the motor cable      gt  o pep    www vacon com       RECEIPT OF DELIVERY VACON   7       2  RECEIPT OF DELIVERY    After unpacking the product  check there are no signs
14. 3 8  Open the cover           Control cable  tightening  torque  0 4 Nm       Strip the plastic  cable coating for  360   earthing    Figure 3 9  Install the control cables  See chapter 6     24 hour service 807 499 023 e e mail  vacon dvacon com       16    VACON INSTALLATION       3 2 3 Cable and fuse specifications    Use cables with at least  70 C heat resistance  Cables and fuses must be  dimensioned according to the tables below  Installation of cables according to UL  regulations is presented in Chapter 3 2 6    The fuses also act as cable overload protection    These instructions apply only to cases with one motor and one cable connection from  the frequency converter to the motor  In any other case  ask the factory for more  information     LevalN  1 1    Motor cable pes  Control cable pes    Table 3 4  Cable types required to meet standards  EMC levels are described in  Chapter 3 1 3     Power cable intended for fixed installation and the specific mains voltage   Shielded cable not required    NKCABLES MCMK or similar recommended   Power cable equipped with concentric protection wire and intended for  specific mains voltage    NKCABLES  MCMK or similar recommended     d       specific mains voltage     NKCABLES  MCCMK  SAB   ZCUY J or similar recommended      360  grounding of both motor and FC connection required to meet the standard  creened cable equipped with compact low impedance shield  NKCAB   Jamak  SAB OZCuY 0 or similar      Table 3 5  Cable type descripti
15. 48    VACON PARAMETERS       9 7 Automatic restarts    QC IC  win  Wer  LT I         we     3     Delay before automatic  restart after a fault  disappears    Defines the time before  the frequency converter  P7 2 Trial time 90 00 attempts to automatically  restart the motor after a  fault has disappeared    0 Ramp  P7 3 Start mode 1   Flying start  2  As in P3 2  see e  ee  code    Table 8 20  Automatic restarts       www vacon com       PARAMETERS VACON    49       9 8 Hide parameters    PESA ES E ed    n 0   Parameters visible  5    1  Do Dems    Table 8 21  Hide parameters       9 9 System parameters    EGG eo deli A eci a A AE    Software information  MENU PAR   gt  S1     ET memos   p p Pep 7     API Firmware interface  Application ID    Application revision    Format  XX yyy xx     0   64  Number   of error messages   yyy   0   999  Number  of correct messages       0 FB disabled  EJ Fieldbus protocol 1   Modbus    Slave address    52 2   S  0 300  1 600  2 1200    S2 4 Baud rate 5 5 811   3 2400  4 4800   5 9600    S    2 7    2 8    S  Number of stop bits  Parity type    0   Not used   Communication time out 121 second   2   2 seconds  etc     Reset communication 815   1   Reset torque 52 1  status    Total counters  MENU PAR     S3        Table 8 22  System parameters    24 hour service 807 499 023 e e mail  vacon dvacon com       50   VACON PARAMETERS        code  Parameter  WR   sr meer                4 2    S  S    Power on days  Power on hours    User se    541 
16. FI filter  400V  Complies with EMC category C2  level H Vacon   With an internal RFI filter  Both  Without protection against EMC emissions  level N Vacon   Without RFI filter    For EMC  EN61800 3   For safety  ULS08C  EN61800 5    Certificates  and For safety  CB  CE  UL  cUL    For EMC  CE  CB  c tick  manufacturer       declarations of see drive nameplate for more detailed   E information   conformity    Table 11 1  Vacon 10 technical data    Standards          WWW Vacon com       TECHNICAL DATA VACON    69       11 2 Power ratings  11 2 1 Vacon 10   Mains voltage 115 V    Mains voltage 115 V  50 60 Hz  1  series    Rated loadability M minal  Mechanical  Ishaft input Isize and  power current weight  kg    100  direct 150  overload P A   currently  A       current  A   kw    15    3307   15  577        Table 11 2    Vacon 10 rated loadability  115 V       11 2 2 Vacon 10   Mains voltage 208   240 V    Mains voltage 208 240 V  50 60 Hz  1  series    Rated loadability Motor Mechanical  size and  power weight  kg     100  direct 150  overload P  currently  A   current  A   kw      009 5   2      58 T ams    09 38 L1      22   788  50      Table 11 3  Vacon 10 power ratings  208   240 V       Maximum Vacon 10 operating ambient temperature    24 hour service 807 499 023 e e mail  vacon dvacon com       70   VACON TECHNICAL DATA       Mechanical  size and  weight  kg     100  direct  current Iy  A     Table 11 4  Vacon 10 power ratings  208   240 V  3        11 2 3 Vacon 10   Ma
17. PAD BUS  Press to change value     Program nominal motor    current and press to  confirm value    i They alternate    I    on the display n y    REA RUN STOP RM FAULT READY RUN STOP ALARM FAULT          REF  REF  MO     MOI  PAR    PAR     FLT  FLT   FWD REV I O KEYPAD BUS FWD REV W O KEYPAD BUS    p     Program the type of autochange and  press to confirm value       O Press to change value    0 No autochange   1 Auxiliary autochange   2 Autochange of all   3 Auxiliary autochange with interlocks  4 Autochange of all with interlocks    24 hour service 807 499 023 e e mail  vacon dvacon com       VACON   38       START UP  i a They alternate I  I  on the display i  REANY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT  A       FWD REV WO KEYPAD BUS    Press to change value Program the number of    auxiliary pumps and  press to confirm value       i grey alternate      J  7  I  on the display q LJ       VO KEYPAD BUS    Press to change value Program desired work    pressure in Kg and press to  confirm value    WWW vacon es       START UP VACON    39       8 2 System identifcation function    In order to identify the pump  we must follow the steps listed below     1  Completely close the pressure unit discharge to prevent water intake   Pressure must be 0 bars    2  Press the green  START  button for 5 seconds to start the pump and  begin to carry out identification Identification takes around 60s   approximately         READY RUM S    Press for 5 seconds       3  Once the pump
18. SURE IN SNOOZE MODE  Overpressure that takes place in the installation when the system goes into  snooze mode     REFERENCE FREQUENCY SELECTION  PI DISABLED   DI3   Parameter that allows the user to select the source of the reference  frequency  when PI has been disabled using DI3    0   Panel   1 AI1    REFERENCE PRESSURE SELECTION   Parameter that allows the user to select the source of work pressure   0   Panel  P1 9 P2 1    1 All    www vacon com       PARAMETER DESCRIPTIONS VACON    55       GROUP 3  Motor Control    3 2 START MODE  The user can select two start modes for Vacon 10 with this parameter     0   Ramp start   The frequency converter starts from 0 Hz and accelerates to the set  frequency reference within the set acceleration time  P4 2    Load inertia or  initial friction may lengthen acceleration times      1   Flying start    The frequency converter is also able to start running a motor by applying a  smalltorque to it and searching for the frequency that matches the speed the  motor is running at  Searching starts at maximum frequency and works  downwards until the correct frequency is detected  Therefore  output  frequency will be increased decreased to the set reference value according  to the set acceleration deceleration parameters  Use this mode if the motor  is rotating when the start command is given  A flying start makes it possible  to ride through short interruptions in mains voltage    3 3 STOP MODE  Two stop modes can be selected in this applica
19. VACON 10    AC DRIVES    VACON 10 PFC USER MANUAL       VACON    DRIVEN BY DRIVES    Document code  DPD00343A  Edited  29 4 2010    4  4  5  5  6  7  7  7  7  8  9  9    1 Safety   1 1 Warnings   1 2 Safety instructions   1 3 Grounding and ground fault protection  1 4 Before running the motor   2 Receipt of delivery   2 1 Type designation code   2 2 Storage   2 3 Maintenance   2 4 Warranty   3 Installation   3 1 Mechanical installation   3 1 1 Vacon 10 dimensions   3 1 2 Cooling   3 1 3 EMC levels   3 1 4 Changing the EMC protection class from H or L to T  3 2 Cabling and connections   3 2 1 Power cabling   3 2 2 Control cabling   3 2 3 Cable and fuse specifications   3 2 4 General cabling rules   3 2 5 Stripping lengths of motor and power cables  3 2 6 Cable installation and the UL standards  3 2 7 Cable and motor insulation checks  4 Commissioning   4 1 Commissioning steps of Vacon 10  5 Fault tracing   6 PFC system interface   6 1 1 0 Control   7 Control panel   7 1 General   7 2 Display   7 3 Panel   7 4 Navigating on the Vacon 10 control panel  7 4 1 Main menu   7 4 2 Reference menu   7 4 3 Monitoring menu   7 4 4 Parameter menu   7 4 5 Fault history menu    24 hour service 807 499 023 e e mail  vacon dvacon com       8 Start up   8 1 Quick start up wizard   8 2 System identifcation function  9 System Parameters   9 1 Quick setup parameters   9 2 Advanced PFC settings   9 3 Motor control   9 4 Analog inputs   9 5 Output signals   9 6 Protection   9 7 Automatic restarts  
20. analog signal     CUSTOMER MIN     CUSTOMER MAX   These parameters make it possible to scale input current from 0 to 20 mA     MINIMUM SCALING    MAXIMUM SCALING  Set maximum minimum scaling to current Value        60   VACON PARAMETER DESCRIPTIONS           Scaled input signal    100                         Par  4 6   30   Par  4 7   80        Analogue  input      80  0 T 100     0 3 6 80 100V  0 68 16 0 20 0mV  4 8 8 16 8 20 0 mV    Figure 10 3  Example of signal scaling    GROUP 5  Output Signals  5 1 RELAY 2  RO2   0   Pump 2 Control  1   Ready  2 Run  3   Fault    5 2 DIGITAL OUTPUT  DO     Pump 3 Control  Ready   Run   Fault              WNn  o       5 3 DIGITAL OUTPUT  AO     Ready   Run   Fault   Fault Inverted            0  1  2  3         www vacon com       PARAMETER DESCRIPTIONS       GROUP 6  Protection    6 5    6 6    24 hour service 807 499 023 e e mail  vacon dvacon com    UNDERLOAD PROTECTION    0   No response  1   Warning  2   Fault  stop mode after fault as in parameter 3 3    Pump is underloaded  Check  that pump suction is not obstructed or blocked   that the pump has enough water     If the pumping is working properly  you should set parameters P6 6 and P6 7   Underload protection  field weakening area load  Torque limit can be set between 0 0 150 0   x TnMotor     This parameter provides the minimum torque value permitted when output  frequency is above the field weakening point  See Figure 1 22     Pare  Liz              Par  6 6    Underload zone   
21. at low speeds is small   Motor thermal protection is based on a calibrated model and uses the output  current of the drive to determine the load on the motor    Motor thermal protection can be adjusted with parameters  The thermal  current IT specifies the load current above which the motor will be  overloaded  This current threshold is a function of the output frequency     CAUTION  The calibrated model does not protect the motor if    the air intake grill is blocked and reduces the airflow to the  motor     www vacon com       PARAMETER DESCRIPTIONS VACON    63       6 9    6 10    6 11    24 hour service 807 499 023 e e mail  vacon dvacon com    THERMAL PROTECTION OF THE MOTOR   0   No response   1   Warning   2   Fault  stop mode after an error as in parameter 3 3    If tripping is selected  the drive will stop and activate the fault phase  Al  Disable protection  that is  by setting the parameter to 0   the thermal  model of the motor is reset to 0      MOTOR AMBIENT TEMPERATURE   When motor ambient temperature should be taken into account  the user  should change this parameter  Values can range   from  20 to 100 degrees Celsius     MOTOR COOLING FACTOR AT ZERO SPEED  Cooling power can be set between 0 150 0  x cooling power at nominal    frequency  See Figure 10 6     Pooling  A       Overload area  100  A    par 9 9 40           0 f f    Figure 10 6  Motor cooling power       64   VACON PARAMETER DESCRIPTIONS       9 12 MOTOR THERMAL TIME CONSTANT  This time can be se
22. bient temperature  dust  corrosive substances or operation outside the rated  specifications  Neither can the manufacturer be held responsible for consequential  damages     The Manufacturer s time of warranty is 18 months from the delivery or 12 months  from commissioning  whichever expires first  General Conditions NL92 Orgalime  S92      The local distributor may grant a warranty time different from the above  This  warranty time shall be specified in the distributor s sales and warranty terms  Vacon  assumes no responsibility for any other warranties than that granted by Vacon  itself           In all matters concerning the warranty  please contact your distributor     www vacon com       INSTALLATION VACON    9       3  INSTALLATION    3 1 Mechanical installation    There are two ways of mounting Vacon 10 on the wall  screw mounting or DIN rail  mounting  Mounting dimensions are listed on the back of the unit and on the  following page     M1 MI2 3    Q     v5  X    diio  1 2    Figure 3 3  DIN rail mounting              Figure 3 2  Screw mounting    24 hour service 807 499 023 e e mail  vacon dvacon com       10    VACON INSTALLATION       3 1 1 Vacon 10 dimensions    D2                                                ur   1373   55   378      7 3973   585   378   25     55  e   m 1 73   8257  2575    55    Table 3 1  Vacon 10 dimensions in millimetres       www vacon com       INSTALLATION VACON    11       3 1 2 Cooling    All Vacon 10 drives use forced air flow coolin
23. but not  changed  Monitoring values are listed in Table 7 13     Pressing the navigation wheel once in this menu takes the user to the next level   where the monitoring value  e g  M1 11 and the value are displayed  see Figure 7 2    Monitoring values can be examined by rotating the navigation wheel clockwise  as  shown in Figure 7 4     24 hour service 807 499 023 e e mail  vacon dvacon com       32   VACON CONTROL PANEL       oie T Monitoring sat Lust T5 T sese             3   Output frequency Frequency to the motor  Fewer eren       Re A                       Motor speed Rated motor speed  Motor torque Rated torque  nominal real   Esiste power Tomine el    M7   Motor voltage   v       Motor voltage  DC link voltage Measured DC link voltage  Unit temperature   co   8  Measured temperature   Analog input 1 Value of AI1 in V  Analog input 2 Value of AI2 in mA  DI1  DI2  DI3      Run   Ref PI2   Undo PI    M1 13   D14  DIS  DIE   fe  a 1 Interlock 2   Interlock        17  Output statuses  Digital output  AO  SES     of max  process reference    of max  current value    of max  error value    of max  output value    Table 7 13  Monitoring values    616  Current pressure in Kg       www vacon com       CONTROL PANEL VACON    33       7 4 4 Parameter menu    Parameter menu only shows the quick setup parameter list by default  By giving the  right value to parameter 8 1  it is possible to access the other advanced parameter  groups  Parameter lists and descriptions can be found in
24. converters can be changed from H  or L to T by removing the EMC capacitator disconnection screw  See figure below   Note  Do not attempt to change the EMC level back to class H or L  Even if the  procedure above is reversed  the frequency converter will no longer fulfil the EMC  requirements of class H L     Vacon 10 frequency converters are divided into five classes according to the level of  electromagnetic disturbances emitted  the requirements of a power system network  and the installation environment  see below   The EMC class of each product is  defined in the type designation code     www vacon com       INSTALLATION VACON    13       3 2 Cabling and connections  3 2 1 Power cabling  Note  Tightening torque for power cables is 0 5   0 6 Nm    gee    Strip the  plastic cable  coating for    MAINS 360   earthing MOTOR       Figure 3 5  Vacon 10 power connections  MI1             3   400V   Exti I brak  1   230V      resistor  400V   Motor out  L1L2 N L3 R  R UT1 V T2 WIT3      ipi a ja ipi Bp  EN  RN y  Strip the  plastic  cable A    coating I y o S YA    Figure 3 6  Vacon 10 power connections  MI2   MI3    24 hour service 807 499 023 e e mail  vacon dvacon com       14   VACON INSTALLATION       3 2 2 Control cabling    e e 9        Attach the support  AFTER installing  the power cables    Attach this plate  BEFORE installing  the power cables    Figure 3 7  Mount the PE  plate and API cable support    www vacon com       INSTALLATION VACON    15                Figure 
25. de  Stop mode    Current    threshold    weakening  points    Voltage at  field  weakening    U f  optimization  Switching  frequency    Table 8 16  Motor control       www vacon com       PARAMETERS VACON   45       9 4 Analog inputs     ras T  AI1 Hysteresis   0 000  9 000    P4 2   Al2 Signal Range   2      AI1 Sensitivity  2 0 20mA  3 4 20mA  0   not filtered    EJ  E    389   E 0 0   Not scaled    100 0   Not scaled      100 0      0   Not scaled    Value       Maximum  scaling Current 96 100 0 337   100 0   Not scaled    Table 8 17  Analog inputs    24 hour service 807 499 023 e e mail  vacon dvacon com       46    VACON PARAMETERS       9 5 Output signals    0  Ctrl  Pump 2  1  Ready   2  Run   3   Fault    0 Ctrl  Pump 3  Digital Output 1   Ready    2 Run  3   Fault  0   Ready  Digital Output 1 Run   A0  2   Fault  3   Fault inverted       Table 8 18  Output signals    www vacon com       PARAMETERS    VACON    47       9 6 Protection    Response to fault  4mA    Response  undervoltage fault  Ground fault  protection    Low freq  protection    Under  protection  Torque curve at  zero frequency    v    Torque curve a  nominal frequency  Underload  protection time  limit  Motor thermal  protection    Motor ambien   temperature   Motor cooling  factor a zero speed    Motor thermal  me constant  Motor stall current    Table 8 19  Protection    v  ES  co    24 hour service 807 499 023 e e mail  vacon dvacon com    0   No response    Warning  2   Fault  stop as in          
26. e has not  been closed properly     The pump is unable to rotate at  system desired speed due to high  consumption or to the mains  power supply being too low        24 hour service 807 499 023 e email  vacon dvacon com    Correcting actions    Check the programming  and the device indicated by  the external fault  information  Also the  cabling of this device     Check installation    If installation is correct  contact the nearest Vacon  distributor     Use the monitoring menu   M1 14  to check the state of  digital inputs D14  D15 and  D16 and also check their  cabling     Check that the pressure  unit discharge opens and  closes correctly     Check the controller power  supply and that the pump is  not blocked or the  discharge piping dirty        24   VACON PFC SYSTEM INTERFACE       6  PFC system interface    6 11 0 Control    R  lerminal       Signal     Preset factory value                                                          24Ncc 50mA    Ref  voltage output    Maximum load 10 mA                                                          Programmable in P5 2 pumps Contre     Th Frequency Reference 0     10 VRi  200 kQ  min    20    max  load 50 mA     Pa 0   30V Ri   12 kQ min  i   2 thread transducer    014   20 mA  Pressure input 0 4    20 mA  Ri   2000  4 20mA  0    30 V Ri  12kQ min  y  0  10v  0 20mA  Ri 500Q  10Vcc 20mA Programmable in P5 3  Digital output Discharge open  max  load    148 Vcc 50 mA       Relay output 1  Pump 1 Control    Max  switching load  
27. ed  Application Interface in your Vacon 10     Set the parameters of group 1 according to the requirements of your  application  At least the following parameters should be set      motor nominal voltage  par  1 1      motor nominal frequency  par  1 2      motor nominal speed  par  1 3      motor nominal current  par  1 4   You will find the values needed for the parameters on the motor  specification plate     Perform test run without motor  Perform Test A     A  Control from the 1 0 terminals   Activate digital inputs DI1  8  and D13  10      Change the frequency reference  potentiometer     Check in the Monitoring Menu that output frequency changes  according to the change in frequency reference     Turn the Start Stop switch  DI1  to OFF position        24 hour service 807 499 023 e e mail  vacon dvacon com       20   VACON COMMISSIONING       Run the no load tests without the motor being connected to the process   if possible  If this is not possible  ensure the safety of each test prior to  running it  Inform your co workers of the tests   Switch off the supply voltage and wait until the drive has stopped   Connect the motor cable to the motor and to the motor cable  terminals of the frequency converter   Make sure that all Start Stop switches are in Stop positions   Switch the mains ON  Repeat test 7A     Connect the motor to the process  if the no load test was run without the  motor being connected      Before running the tests  make sure that this can be done safel
28. ed below the field weakening  point and produces less torque  power losses and electromechanical noise   The U f ratio can be used in applications in which load torque is proportional  to squared speed     www vacon com       PARAMETER DESCRIPTIONS VACON   57       A UV     Un eee      sia  par 1 11  Default  Nominal  voltage of the motor           Field weakening     point    Linear    Squared Default  Nominal    Hrequency of the  motor ftHz   par  1 14  gt           Figure 10 1  Linear and motor voltage change    2   Programmable U f curve    The U f curve can be programmed with three different points   Programmable U f curve can be used if the other settings do not  satisfy the needs of the application    Un   k   3    225  2      Default  Nominal  Par 1 11   voltage of the motor    Field weakening  point             Par  1 13  D  E Pena a e  Par  1 14   Def  0 096   ait ua  Par  1 12 Par  1 10     Def  1096     Figure 10 2  Programmable U f curve    24 hour service 807 499 023 e e mail  vacon dvacon com       58    VACON PARAMETER DESCRIPTIONS       3 7    3 8    3 9    3 10    FIELD WEAKENING POINT  The field weakening point is the output frequency at which the output voltage  reaches the value set with parameter 3 8     VOLTAGE AT FIELD WEAKENING POINT  The field weakening point is the output frequency at which the output voltage  reaches the value set with parameter 3 8     3 8 Voltage at field weakening point   Above the frequency at the field weakening point  the out
29. g   Enough free space shall be left above and below the frequency converter to ensure  sufficient air circulation and cooling  You will find the required dimensions for free  space in the table below     Type Dimensions  mm   A  50      09  __         Table 3 3  Cooling air required    3 1 3 EMC levels    Category C1  Vacon EMC class C   Frequency converters of this class comply with  the requirements of category C1 of the product standard EN 61800 3  2004    Category C1 ensures the best EMC characteristics and it includes converters the  rated voltage of which is less than 1000V and which are intended for use in the 1st  environment  NOTE  The requirements of class C are fulfilled only as far as the  conducted emissions are concerned     Category C2  Vacon EMC class H   Frequency converters of this class comply with  the requirements of category C2 of the product standard EN 61800 3  2004    Category C2 includes converters in fixed installations the rated voltage of which is  less than 1000 V  Class H frequency converters can be used in both the 1st and 2nd  environment     Category C3  Vacon EMC class L   Frequency converters of this class comply with  the requirements of category C3 of the product standard EN 61800 3  2004    Category C3 includes converters the rated voltage of which is less than 1000V and  which are intended for use in the second environment only     Category C4  Vacon EMC class N   The drives of this class do not provide EMC  emission protection  These k
30. he navigation wheel are pressed or the navigation  wheel is not rotated  The operating hour  minute and second when the fault occurs  are shown in the value menu  operating hours   display reading x 1000 h      Note  The entire fault history can be deleted by  pressing stop button for 5 seconds  when the drive    has stopped and the fault history menu on the  display has been selected     See Chapter 5 for fault descriptions     www vacon com       VACON   36 START UP       8  START UP    8 1 Quick start up wizard    Note  You should only use the wizard when starting up the  controller  since parameters are reset to their factory default  values every time it is used  If you need to change a particular    value  you are recommended to go to the specific parameter  see  page 11         READY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT      2 a  REF REF  MON   4     MONA   PAR PARI  n   gt  e     FWD REV lO KEYPAD BUS FWD REV WO KEYPAD BUS  Press twice until left Press STOP for  cursor flashes 5 seconds    i They alternate WI  I  J on the display EE    READY RUN STOP ALARM FAULT  a          eai    x   FWD REV W O KEYPAD BUS FWD REV IO KEYPAD BUS   Press to change value Program nominal motor  speed and press to confirm  value    WWW vacon es       START UP VACON    37       ILJ 4 Theyalternate   3 47     on the display DE LI  default value depends on the size  of the convertor     REABY RUN STOP ALAR  AULT READY RUN STOP ALARM FAULT       y  FWD REV WO KEYPAD BUS FWD via KEY
31. inds of drives are mounted in enclosures  NOTE  An  external EMC filter is usually required to fulfil the EMC emission requirements     24 hour service 807 499 023 e e mail  vacon dvacon com       12    VACON INSTALLATION       Category C4 for IT networks  Vacon EMC class T   Frequency converters of this  class fulfil the product standard EN 61800 3  2004  if intended to be used in IT  systems  In IT systems  the networks are isolated from ground  or connected to  ground through high impedance to achieve a low leakage current  NOTE  if  converters are used with other supplies  no EMC requirements are complied with     Environments in product standard EN 61800 3  2004     First environment  Environment that includes domestic premises  It also includes  establishments directly connected without intermediate transformers to a low   voltage power supply network which supplies buildings used for domestic purposes     NOTE  houses  apartments  commercial premises or offices in a residential building  are examples of first environment locations     Second environment  Environment that includes all establishments other than  those directly connected to a low voltage power supply network which supplies  buildings used for domestic purposes    NOTE  industrial areas  technical areas of any building fed from a dedicated  transformer are examples of second environment locations     3 1 4 Changing the EMC protection class from H or L to T    The EMC protection class of Vacon 10 frequency 
32. ins voltage 380   480 V  Mains voltage 380 480 V  50 60 Hz  3  series    Rated loadability Nominal Mechanical   size and  100  direct 150  overload upply  current Iy  A    current  A      im 535   Ss   s    Table 11 5  Vacon 10 power ratings  380   480 V    A   T NUS   8  s  mmn     put   95      5       Note 1  The input currents are values calculated with a 100 kVA line transformer  supply     Note 2  The mechanical dimensions of the drives are given in Chapter 3 1 1     www vacon com       VACON    DRIVEN BY DRIVES    Find your nearest Vacon office  on the Internet at     www vacon com       
33. l is used for navigating on the panel display  but also works as a    reference potentiometer when DI3 has been enabled and P2 22 has been set to 0   The wheel has two different functions       rotating the wheel  for example  to change parameter values    12 steps rotation       pressing the wheel  for example  to accept the new value      www vacon com       CONTROL PANEL    VACON    29       7 4 Navigating on the Vacon 10 control panel  This chapter provides information on navigating the menus on Vacon 10 and editing    parameter values     7 4 1 Main menu    The Vacon 10 control menu consists of a main menu and various submenus   Navigation in the main menu is shown below     READY RUN STOP ALARM FAULT    READY RUN STOP ALARM FAULT                                                                                                 REFERENCE va A      tenn Rete ee inno  Displays the MON  MON    keypad reference MIO   es P PAR PAR ni    regardless ol PUSH  the selected FLT    e FT   gt   control place  FWD REV IO KEYPAD BUS FWD REV IO KEYPAD BUS  l e ROTATE  READY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT  pu        MONITORING pep    REF mi  In this menu MON  4   MON  4  you can N a td  browse the PAR PAR    monitorin  values  T RT m PUSH FLT v v  FWD REV VO KEYPAD BUS FWD REV VO KEYPAD BUS       ROTATE  READY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT  PARAMETER a a ES a  MENU REF REF O   I  In this menu MON MON  ou can Y I       rowse and PARja  PAR       edit the  
34. mponents of the unit      If an external brake resistor  option  is used  connect its cable to  the appropriate terminal      Check the connection of the ground cable to the motor and the  frequency converter terminals marked with      Connect the shield of the motor cable  to the ground of the frequency converter  motor and supply  centre        24 hour service 807 499 023 e e mail  vacon dvacon com       18    VACON INSTALLATION       3 2 5 Stripping lengths of motor and power cables    Earth conductor  8 mm     f  I    35 mm 20 mm    8 mm    NON                                      Figure 3 10  Stripping of cables    Note  Strip also the plastic cover of the cables for 360 degree grounding  See Figures  3 5  3 6 and 3 9    3 2 6 Cable installation and the UL standards  To meet the UL  Underwriters Laboratories  regulations  a UL approved copper  cable with a minimum heat resistance of  60 75 C must be used    3 2 7 Cable and motor insulation checks  These checks can be performed as follows if motor or cable insulations are  suspected to be faulty   1  Motor cable insulation checks  Disconnect the motor cable from terminals U T1  V T2 and W T3 of the frequency  converter and from the motor  Measure the insulation resistance of the motor cable  between each phase conductor as well as between each phase conductor and the  protective ground conductor   The insulation resistance must be   1MOhm   2  Mains cable insulation checks  Disconnect the mains cable from terminals L1  L2
35. nge all with   interlocks    Number of Auxiliary pumps in the  P1 8 ie 3  Auxiliary Pumps system  pressure Kg    Table 8 14  Quick setup parameters       24 hour service 807 499 023 e e mail  vacon dvacon com       42    VACON PARAMETERS       9 2 Advanced PFC settings    EPA Maxi A gefautt EA    Second pressure  P2 Work pressure 2 P1 P2 20 Kg 5 0 1617  reference   Activated using DI2  Acceleration time from  Acceleration 3000 0 0 Hz to maximum  frequency  Deceleration time  Deceleration 3000 0 104   from maximum  frequency to 0 Hz    EJE   Not inverted  1   Inverted    puo 0   Test 40 s   3000 0 1604  Autochange time  elapsed  Autochange  Autochange level for  Maxumum No of 1605  auxiliary pump  Auxiliaries connection  Autochange  1606 Controller output  cee frequency level for  Frequency limit  autochange  Auxiliary running  pes   320 09  frequency       Table 8 15  Advanced PFC settings    www vacon com       PARAMETERS VACON    43       e  Auxiliary stop delay    0   Wake up below level   P2 16   1   Wake up above level   P2 16   2   Wake up below level   P1 9   3   Wake up above level  ae 9     Wake up Function    P2 18 PI Hysteresis 161  61    Pressure  Frequency    Selection  disable  PI   DI3       0   Panel  P1 9   reat  menocrun  aino  o   1  __      1411S ony in sion mode    Table 8 15  Advanced PFC settings    T    0   Navigation wheel  1 AM       24 hour service 807 499 023 e e mail  vacon dvacon com       44   VACON PARAMETERS       9 3 Motor control    Start mo
36. nternal failure has occurred   Contact the nearest  distributor     Check ambient temperature     Check that the cooling air flow  is not blocked    Check ambient temperature   Make sure that the switching  frequency is not too high in  relation to ambient  temperature and motor load      Motor stato   stalled Motor stall protection has been Gheckeni  t  r   Motor statea   ivaa     Decrease the motor load    If no motor overload exists   check the temperature model  parameters     Check the load and  parameters related to  underload detection  P6 5   P6 8     Contact the nearest  distributor     Reset the fault and restart   If the fault recurs  contact  the nearest distributor     Internal bus Ambient interference or defective   If the fault recurs  contact  communication   hardware your nearest distributor    Contact the nearest  System fault System does not work distributor     Check the sensor and  sensor cable        www vacon com    FAULT TRACING    VACON    23       External fault    Fieldbus fault    Interlock alarm    System  identification  fault    Output  frequency  lt   Reference  frequency    Table 5 1  Fault codes    Possible cause    Digital input fault  Digital input  has been programmed as an  external fault input and this input  is active     The data connection between the  fieldbus Master and the fieldbus  of the drive has broken     An autochange with interlocks   P1 7  has been selected and the  controller fails to detect them     Pressure unit discharg
37. ons       gustas setis Main Ground Control Relay    Culmm     terminat   terminat   terminal   terminal  Imm   Imm   Imm     Imm    vr 007 0002 FTSE  0005 0007    RAZZE   wr ww   e  x Tes  188 355     Table 3 6  Cable and fuse sizes for Vacon 10  208   240 V       www vacon com       INSTALLATION VACON    17    Terminal cable size  min max   Type       Mains cable    0001 0004 3 1 5 1 5  MI2   0005 0006 3 1 5 1 5    MI3   0008 0012  Table 3 7  Cable and fuse sizes for Vacon 10  380   480V       3 2 4 General cabling rules    Place the motor cables far enough from other cables      Avoid placing the motor cables in long parallel lines with other  cables      If the motor cable runs in parallel with the other cables  the  minimum distance between the motor cable and the other  cables is 0 3 m      The given distance also applies between the motor cables and  signal cables of other systems      The maximum length of the motor cables is 30 m     The motor cables should cross other cables at an angle of 90  degrees     Connecting the cables      Strip the motor and mains cables as advised in Figure 3 10      Connect the mains  motor and control cables into their respective  terminals   See figures 3 5   3 9       Note the tightening torques of power cables and control cables  givenin page 13and page 15      For information on cable installation according to UL regulations  see Chapter 3 2 6       Make sure that the control cable wires do not come in contact  with the electronic co
38. parameters  Er   PUSH FLT    x  FWD REV VO KEYPAD BUS FWD REV JO KEYPAD BUS  i    ROTATE  READY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT  FAULT HISTORY REF    a RE      MENU  1 ni  Here you will MON MON E j I I  be able IL   fo brews PAR PAR l  L i   through the Furia     PUSH rir     faults occurred  NY y x    FWD REV VO KEYPAD BUS FWD REV IO KEYPAD BUS    Figure 7 2  Vacon 10 main menu    24 hour service 807 499 023 e e mail  vacon dvacon com       30   VACON CONTROL PANEL       7 4 2 Reference menu      READY RUN STOP ALARM FAULT       are anno     6 LILI    PAR ve  Hz   FLT  X  E  FWD REV IO KEYPAD BUS                Push to enter Change Push to  edit mode value confirm             Figure 7 3  Reference menu display    Move to the reference menu using the navigation wheel  see Figure 7 2   The  reference value can be changed using the navigation wheel as shown in Figure 7 3   The reference value follows the rotation continuously    without accepting the new  value      www vacon com       CONTROL PANEL VACON    31       7 4 3 Monitoring menu    M       4       Alternates _      Alternat fil  ll   I    in the display LI I Il    READY  RUN STOP A M FAULT  A  p  REE     RI   lt          MON   PAR  FLT    Hz  v v    FWD REV I O KEYPAD BUS          N  Browse  M1 1   M1 20    Figure 7 4  Monitoring menu display    Monitoring values are made up of the actual values of signals measured as well as  the status of some control settings  They can be visualised on the display  
39. put voltage  remains at the value set with this parameter  Below the   frequency at field weakening point  the output voltage depends on the  setting of the U f curve parameters     When parameters 1 1 and 1 2  nominal voltage and nominal frequency   of the motor  are set  parameters 3 7 and 3 8 are given   the corresponding values automatically  If you need different values for the  field weakening point and voltage  change these   parameters after setting parameters 1 1 and 1 2     U F OPTIMIZATION  0 Not used    1 Automatic Torque Boost    The voltage to the motor changes automatically which makes the motor  produce sufficient torque to start and run at low frequencies  The increase in  voltage depends on motor type and power  Automatic torque boost can be  used in applications with high start torque due to friction  e g  in conveyor  belts     SWITCHING FREQUENCY  Motor noise can be minimised using a high switching frequency  Increasing  the switching frequency reduces the capacity of the frequency converter unit     Switching frequency for Vacon 10  1 5   16 Hz     www vacon com       PARAMETER DESCRIPTIONS VACON    59       GROUP 4  Analog Inputs    4 1    4 2    4 3    4 4    4 5    4 6    4 7    24 hour service 807 499 023 e e mail  vacon dvacon com    AI1 HYSTERESIS  Analog Input Sensitivity    AI2 SIGNAL RANGE  2 0 20mA  3 4 20mA    AI2 FILTER TIME  This parameter  given a value greater than 0  activates the function that  filters out disturbances from the incoming 
40. ry pump is disconnected  when the  controlled pump is at its minimum level of output     2 14 SNOOZE FREQUENCY    Frequency converter cuts out automatically if running frequency drops below the  snooze level  set by this parameter  for a longer period of time than established  in parameter 2 15  While Stopped  the PI controller changes the frequency  converter to Start mode when the current value drops below or exceeds  see  parameter 2 17  the wake up Level set in parameter 2 16     2 15 SNOOZE DELAY    The minimum amount of time that frequency should remain below the  snooze Level before the frequency converter cuts out     24 hour service 807 499 023 e e mail  vacon dvacon com       54   VACON PARAMETER DESCRIPTIONS       2 16    2 17    2 18    2 19    2 20    2 21    2 22    2 23    WAKE UP LEVEL  The wake up level defines the level that the current value must drop below  or exceed before the Start mode of the frequency converter is restored     WAKE UP FUNCTION  This parameter defines whether Start mode is restored when the signal of  the current value drops below or exceeds wake up Level  parameter 2 16      PI HYSTERESIS   n installations where the level of noise produced by the transducer may not  allow the system to ever go into snooze mode  this parameter can help offset  this effect        REFERENCE INCREASE START PI  Delay time before the pressure reference reaches 10096     PRESSURE TRANSDUCER SCALE  Maximum pressure permitted by pressure transducer     OVERPRES
41. s enabled only if Start Stop request is activated       Timing is reset after autochange takes place or when the Start request is  removed     www vacon com       PARAMETER DESCRIPTIONS VACON    53       2 8   MAXIMUM NUMBER OF AUXILIARY START UPS AND    2 9 AUTOCHANGE  INTERVAL LIMIT  These parameters set the maximum load for autochange to take place    This level is defined as follows      Autochange can take place if the number of auxiliary pumps running  is lower than the value in parameter 2 89  autochange may take place      Autochange can take place if the number of auxiliary pumps running  is equivalent to the value in parameter 2 8 and controlled drive  frequency is lower than the value in parameter 2 9      Ifthe value in parameter 2 9 is 0 0 Hz  autochange can only take place  when on standby  Stop and Snooze  regardless of the value in  parameter 2 8     2 10 AUXILIARY PUMP START FREQUENCY  When the pump controlled at this output frequency  or higher  and the time  set in P2 11 has elapsed  an auxiliary pump will be connected     2 11 AUXILIARY PUMP START DELAY  The time that must elapse before an auxiliary pump is connected when the  main pump is at its maximum level of output  if required by the system     2 12 AUXILIARY PUMP FREQUENCY  When the controlled pump runs at this output frequency  or a lower value   and the time set in P2 13 has elapsed  an auxiliary pump will be  disconnected     2 13 AUXILIARY PUMP STOP DELAY  Time that must elapse before an auxilia
42. t between 1 and 200 minutes     This is the thermal time constant of the motor  The larger the motor  the  longer the time constant  The time constant is the time within which the  calibrated thermal model has reached 63  of its final value     Motor thermal time is specific to motor design and varies from one motor  manufacturer to another     If the motor t   time  t   is the time in seconds the motor can safely operate at  sixtimes the rated current  is known  given by the motor manufacturer   it can  be used as a basis for setting the time constant parameter  As a rule of thumb   the motor thermal time constant in minutes is equal to 2xt6  If the drive is in  stop mode  the time constant is internally increased to three times the set  parameter value  See also Figure 10 7     A  Motor temperature      Trip area            105     x E    Motor    current      fA e       Mr    Faultwarning  par  9 7                         Nu  py N      Time constant T          T    Motor temperature Q    1 17   x  1 e T  Time          Changes by motor size and  adjusted with parameter 9 10    Figure 10 7  Motor temperature calculation    www vacon com       PARAMETER DESCRIPTIONS VACON    65       GROUP 7  Automatic Restarts    7 2 AUTOMATIC RESTART  TRIAL TIME  The automatic restart function restarts the frequency converter when the faults  have disappeared and waiting time has elapsed     The time count starts from the first autorestart  If more than three faults occur  during trial time
43. tion     0   Coasting   The motor coasts to a halt without control from the frequency converter after  the Stop command     1  Ramp stop    After the Stop command  the speed of the motor is decelerated according to  the set deceleration parameters    If regenerated energy is high  it may be necessary to use an external braking  resistor to decelerate the motor in acceptable time     24 hour service 807 499 023 e e mail  vacon dvacon com       56    VACON PARAMETER DESCRIPTIONS       3 5    3 6    MOTOR CONTROL  With this parameter the user can select the motor control mode  The options  are     0   Frequency Control   1 0 terminal references are frequency references and the frequency  converter controls output frequency  output frequency resolution   0 01 Hz     1   Speed Control   1 0 terminal references are speed references and the frequency converter  controls motor speed     U F RATIO  The options for this parameter are     0   Linear    Motor voltage changes linearly with the frequency in the constant flux area  from 0 Hz to the field weakening point where nominal voltage is supplied to  the motor    Linear U f ratio should be used in constant torque applications  See Figure  9 17    This default setting should be used if no other adjustment is necessary     1   Squared    Motor voltage changes following a squared curve form with the frequency in  the area from 0 Hz to the field weakening point where nominal voltage is also  supplied to the motor  The motor runs magnetis
44. to the mains  even if the motor is not  running    The control unit I O terminals are isolated from the mains  However  the relay  output terminals may have a dangerous control voltage present even when Vacon  10 is disconnected from the mains     Ground leakage current of Vacon 10 frequency converters exceeds 3 5mA AC   According to standard EN61800 5 1  a reinforced protective ground connection  must be ensured     If the frequency converter is used as a part of a machine  the machine  manufacturer is responsible for providing the machine with a main switch  EN  60204 1      If Vacon 10 is disconnected from the mains while running the motor  it remains live  if the motor is energized by the process  In this case the motor functions as a  generator feeding energy to the frequency converter    After disconnecting the frequency converter from the mains  wait until the fan stops  and the indicators on the display disappear  Wait 5 more minutes before doing any  work on Vacon 10 connections     The motor can start automatically after a fault if the automatic restart function has  been enabled     A  A  A  A  A  A  A  A    www vacon com       SAFETY VACON    5       1 2 Safety instructions    The Vacon 10 frequency converter is intended for fixed  installations only     Do not perform any measurements when the frequency  converter is connected to the mains     Do not perform any insulation tests on any part of Vacon 10   Product safety has undergone full factory testing     Prior
45. ure unit with a total of 3 pumps has 2 auxiliary pumps   Number of Auxiliary Pumps   N   of pumps   1     24 hour service 807 499 023 e e mail  vacon dvacon com       52    VACON PARAMETER DESCRIPTIONS       GROUP 2  Advanced PFC settings    2 1    2 2    2 3    2 5    2 6    2 7    WORK PRESSURE 2  By enabling digital input DI2  you can work with the pressure inserted in this  parameter     ACCELERATION  Acceleration time from OHz to maximum frequency     DECELERATION  Deceleration time from maximum frequency to OHz     PI CONTROLLER GAIN   This parameter defines the gain of the PI controller  If this parameter is set  to 100   a 10  change in the error value results in a 10  change in  controller output     PI CONTROLLER I TIME   This parameter defines the integration time of the PI controller  If this  parameter is set to 1 00 second  controller output changes by a value  corresponding to the output caused by the gain every second   Gain Error  s     PID ERROR VALUE INVERSION  This parameter enables users to invert the PID controller error value  and  therefore PID controller operations      0 Not inverted  1 Inverted    AUTOCHANGE INTERVAL   After the time set by this parameter has elapsed  autochange takes place if  the load used is less than the level set in parameters P2 9  autochange  interval limit  and 2 8  Maximum number of auxiliary pumps   If the load  exceeds the value in parameter 2 9  autochange will not occur until the load  is below this limit       Timing i
46. y     Inform your co workers of the tests     Repeattest 7A        www vacon com       FAULT TRACING VACON    21       5  FAULT TRACING    Note  The fault codes listed in this chapter are visible if the Application Interface has  a display  like e g  in API FULL or API LIMITED or if a personal computer has been  connected to the drive     When a fault is detected by the frequency converter control electronics  the drive is  stopped and the symbol F together with the ordinal number of the fault and the fault  code appear on the display in the following format  e g     F102     S Fault code  02   overvoltage     Fault ordinal number  F1   latest fault     The fault can be reset by pressing the stop button on the control keypad  The faults  with time labels are stored in the Fault history menu which can be browsed  The  different fault codes  their causes and correcting actions are presented in the table  below     Este   catrame   rete   Hoe  code    Frequency converter has detected  too high a current   gt 4 Iy  in the Check loading   Overc  rrerit motor cable   Check motor size   e sudden heavy load increase Check cables     short circuit in motor cables    unsuitable motor    DC link voltage has exceed the  internal safety limit  i  MET Increase the deceleration  Overvoltage   too short a deceleration time        ds time  P 4 3     high overvoltage spikes in  mains  Current measurement has  detected extra leakage current at Chedkomatercabl  sishd  Ground fault   start   a   
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Elite-7x Manuel d`utilisation  Sony CRX320EE User's Manual  ツト レヴウッドタイ プ  Fujitsu ESPRIMO E420  セットアップガイド - Dynabook        Copyright © All rights reserved. 
   Failed to retrieve file