Operating Instructions Fire Alarm System EBL512

image

Contents

1. Menu Procedure according to chapter Access code for service maintenance H5 and H8 see page 110 S2 Re connect loop zone line input S3 Acknowledge SERVICE signal S4 Clear weekly average S5 Test of alarm devices S6 Safe shut down of control unit S7 Activate address in alarm mode S8 Synchronize the control units S9 Change code for service maintenance 10 Change code for PC communication Scroll to menu S3 S3 S3 Acknowledge SERVICE signal SERVICE signal as Sensor XXX XX This is a list in which you Technical number xxxxxx needs service can scroll The most recent service signal Senses YYY YY sensor is on top of the list Technical number yyyyyy needs service Use Y or A to select Sensor zzz zz a sensor the selected Technical number zzzzzz needs service sensor has a boarder around it Press lt to acknowledge the sensor 126 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x The service signal for the selected sensor is now Continue like above or acknowledged and the next sensor will be shown press ESC to menu S3 Sensor yyy yy Technical number yyyyyy needs service Sensor 2Zz 2z Technical number zzzzzz needs service S3 Acknowledge SERVICE signal Scroll to another menu or press ESC The Service symbol and the Service message will be turned off when all senso
2. H8 S1 Disconnect loop zone line input The access code was S Code for level 3A Re connect loop zone line input correct 4 digits Acknowledge SERVICE signal Press 4 or scroll to the Clear weekly average wanted menu and press Test of alarm devices H Safe shut down of control unit Activate address in alarm mode Synchronize the control units Change code for service maintenance S10 Change code for PC communication 110 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 28 2 Calibration of supervised outputs H5 A1 Supervised monitored outputs The voltage outputs SO S3 in each control unit The voltage outputs VOO VO1 in the COM loop output unit 3364 When all alarm devices sounders etc have been connected including required end of line devices and when the SSD is downloaded a calibration has to be done Function The calibrated range is 4K7 50K and 470 5x470 nF respectively If the actual value at any time differs from the calibrated value a small tolerance or if the calibrated value is outside the calibration range a fault will be generated NOTE Each output s logic is programmable via WinG3 i e normally low default or normally high 24V During the calibration the outputs have to be low i e a normally high output will be low a few seconds during the calibration Text in display Comments Menu According to chapter
3. Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 6 3 The information area priority order When the control unit system is in normal operation quiescent state i e no fire alarms no faults no disablements no service signals no zones in test mode no activated interlocking in outputs and or Alert Annunciation function not enabled only the LED Operation L5 should be lit and some system information is shown in the control unit display However the system information has the lowest priority and more important information suppresses less important In some cases also valid for the symbol area The priority order is is visible 5 Son A 6 Evacuate information Yes NOTE Fire alarms are Fire alarm Heavy smoke heat alarm Alert Annunciation AA alarm Key cabinet alarm The different type of events and the menu system are described in other parts of this document Regarding System information see 6 4 The AAF function is used in conjunction with an AAF Control which is available on the Australian market only gt Only valid for Belgian British Standard Hungarian Spanish and Ukrainian conventions 20 Panasonic Electric Works Nordic AB MEW01163 6 4 6 4 1 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x System information in the LCD EBL512 G3 control unit number date and time are displayed Th
4. This is valid for an external power supply unit 3366 connected on the COM loop The fault is activated after 1 300 minutes after Loss of mains i e no 230 V AC to the 3366 unit e Blown mains fuse e Fuse F1 blown on the charger board 3367 Fuse T5A L 5x20 mm HAULS M ltiple iemllics COM looo COMECOL Winwt xox Break cut off short circuit in more than one segment on the COM loop in control unit no xx FAULT No connection with the MMI board GOmerol UNLLE sx This fault message cannot be shown in the control unit display only via WinG3 or via Web server Fault in the MMI board 5011 software or the MMI board Check the cable between the boards This is a very serious fault Call for service personnel engineer immediately FAULT No reply expansion board x loop x Control unit sox This is valid for the I O Matrix board 4582 no x connected on COM loop x in the control unit no xx e Check the board s address i e the I O Matrix board no Jumpers JP1 JP2 and JP3 on the board Check if the board is disconnected from the loop FAULT No reply xxx xx Technical number xxxxxx In spite of the control unit is communicating on the COM loop in both directions the unit cannot be found xxx xx zone address e Check the unit s COM loop address with the programming tool 3314 56 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x e
5. Cold restart S W SSW Via RESET button on Main board FFD WASV SSD and MMI board respectively s w SSW Reset command via WinG3 or FFD WASV SSD TLON Manager s w SSW Automatically after download of site FFD WASV SSD 03 specific data SSD via a PC amp S W SSW WinG3 Warm restart Automatically after download of FFD WASV SSD 00 alt 03 S W and or text file via a PC amp s w SSW WinG3 Cold restart Automatically due to external FFD WASV SSD 01 02 alt disturbance Cold restart S W SSW 04 20 NOTE During the restart the fault alarm relay for Fault tx will be activated the supervised 24 V DC outputs S0 S3 will be not supervised and S0 S3 programmed as normally high will be low for a few seconds During the restart no fire alarm can be activated and the following is show in the display 3 Both rectifier mains and battery disconnected 4 First press the RESET button on Main board momentarily then the RESET button on MMI board momentarily 35 Tf in the middle of a process also the SSW might be deleted The old S W and or text file will be deleted 37 Tf this happens call for service personnel engineer 38 Depending on the restart reason also the SSW might be deleted 75 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x And after a few seconds if everything is all right else see
6. Re enable control unit Wo RO units control unit 00 R1 O high priority output 1 medium priority output Re enable CU io exp board 0 output O 2 low priority output CU 00 exp board 0 output 1 3 all 90 Panasonic Electric Works Nordic AB Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x MEW01163 Re enable output type 91 336 1 3364 4364 3377 3379 S R Expansion board Re enable another output or press ESC Scroll to another menu or press ESC Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 25 6 Disable re enable output type H2 B7 All outputs programmed as type control general fire ventilation and extinguishing system can for the type respectively be disabled all at the same time or all outputs of these types can be disabled all at the same time All outputs programmed as type interlocking can be disabled all at the same time Disabled control output means that even if the control expression trigger condition for the output respectively is fulfilled true the output will not be activated The outputs in one or more control units can be disabled or the outputs in all control units Disabled control outputs are indicated by LED Fault Disablements General disablements L10 and shown in menu H4 U1 from which it is possible to get a print out When all outputs
7. U3 Open doors U4 Sensor values U5 Sensors activating SERVICE signal U6 Event log U7 Information Scroll to menu U7 U7 Information 4 To change the convention in WinG3 Level 2 has to be selected which require a special password 107 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Main board version vvvvvvvvvvvv If printer 5058 is MMI board version vvvvvvvvvvvv mounted the soft key Alarm counter nnn Print will be visible Max number of allowed alarm points xxx else not Press Print Convention cccccccccc for a print out Serial number xxxxxxx SSSSSSSSSSSSSSSSSSSSSSSS YYYY MM DD hh mm Control unit NN U7 Information Scroll to another menu or press ESC 108 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 28 Service H5 When commissioning an installation and by maintenance e g when you power on and when you are programming a control unit system menu H5 can be used for certain information and help Only authorised personnel have access to the level 3A menus Access code for level 3A is required Via a PC and WinG3 access code for level 3B you can e download backup upload the site specific data SSD e create and download software S W settings configurations control unit and system properties e create and download the user definable text mes
8. built in or external or via menu H2 B1 B2 Automatic re enabling can be used e If there is an alarm organisation for the personnel on site the alert annunciation function can be used e Pre warning can be used as information before a fire alarm is activated 150 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 39 Information regarding radioactive radiation source The installation might contain old smoke sensors detectors of the ionization type They contain a small radioactive radiation source normally Americium 241 When the sensor detector gets dirty and when service signal has been activated in the system contact your local dealer for cleaning replacement of the sensors detectors Metal objects must absolutely not be stuck into the sensor detector Static electricity might destroy the detector Defective faulty discarded and replaced sensors detectors shall be taken care of as radioactive waste They shall be packed in chock absorbing material to make a stable parcel PLEASE NOTE Damaged sensors detectors shall also be packed in a sealed packet whose surface must not be contaminated that is not be soiled with loose radioactive dust National regulations have to be followed 151 Panasonic Electric Works Nordic AB MEWO01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 40 Revision history 152
9. 33K NOTE The calibrated value has to be in the range 4K7 50K FAULT TLON board 1590 Channel Control j FAULT 1590 Channel TLON connection board 1590 No communication connection with the TLON network The board for Channel 0 or 1 in control unit no xx has to be replaced FAULT Wrong type expansion board x LOCO x CONTLHOL Umie sox This is valid for the I O Matrix board 4582 no x connected on COM loop x in the control unit no xx Check the board type set with jumpers JP4 and JP5 on the I O Matrix board The type should be the same as programmed via WinG3 FAULT Wrong type expansion board x Control unit xx Valid for the 8 zones exp board 4580 the 8 relay outputs exp board 4581 and the Inputs and outputs exp board 4583 mounted in control unit no xx Check the type of board which should be the same as programmed via WinG3 FAULT Wrong type of unit xxx xx Technical number XXXXXX Check the type of unit which should be the same as programmed via WinG3 xxx xx zone address HAULS Boas Iain ainjowie some input x expansion Doar x CU xox 61 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Valid for the 8 zones exp board 4580 zone line input x Xxx xx zone address The board is mounted in control unit xx Break on the zone line wrong no end of line device short circuit if not programmed
10. High sensitivity 2 4 m amp Slow detection 35 s H 35 Low sensitivity 3 6 m amp Slow detection 35 s L 35 Heat algorithm Class Al Al Heat algorithm Class A2 S A2 Heat algorithm Class B S B Decision algorithm Dec Default is N 15 and A1 respectively Reset of a week average sensor value If a sensor analog smoke detector is replaced without having generated SERVICE signal its week average sensor value has to be cleared i e set to the default value If not the new clean sensor will inherit the old sensor s value It is possible to clear the week average sensor value for each sensor individually see chapter Clear weekly 44 If some other short name is wanted it can be changed in WinG3 Up to six characters can be used In the DBI Danish convention up to five characters 4 Low sensitivity and or slow detection 35 s might not fulfil the EN54 7 specifications Analog multi detector 4300 only 103 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x average H8 S4 page 128 See also chapter Acknowledge SERVICE signal H8 S3 page 126 NOTE Authorised service personnel only must do the reset to default value Used incorrectly it can cause nuisance fire alarms 104 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 27 5 Sensors activating
11. Operating Instructions Fire alarm system EBL512 G3 V1 0 x F Download software to control unit Software file Parts to download V Software E Text V No MMI board Communication 2 Set the Main board 5010 in boot mode i e hold the Boot button SW2 down and push the RESET button SW1 momentarily until the Main board 5010 is in boot mode indicated by the LED D24 turned off Start the download i e click Start LED Operation L5 will be turned off LED Fault Disablements General fault L9 is turned on indicating that EBL512 G3 is in the boot mode LED System fault L7 will be turned on If it is an EBL512 G3 type 5000 another dialog box opens r Set MMI board in boot mode and press OK Set the MMI board 5011 in boot mode i e hold the BOOT button SW2 down and push the RESET button SW1 momentarily until the MMI board 5011 is in boot mode indicated by the LED D18 turned off Click OK The download status is indicated by the progress bar When the progress bar has gone from red to green the download is completed and the following dialog box opens 71 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Download completed Restart control unit Click Yes and the control unit will restart Regarding the restart see also chapter Restart page 74 6 LED
12. TIES Momentary XX X m Weekly XX X m Perf factor X XX m Min XX X m If there are no sensors Algorithm X XX Max XX X m analog detectors when Momentary XX C Min XX C lt is pressed the list Algorithm XX Max XX C view will not open Print for a print out Sensor 001 03 technical address 000002 Momentary XX C Min XX C Algorithm XX Max XX C a Start sensor ooo00 Write another technical number and press 4 or press ESC ESC U4 Sensor values Scroll to another menu or press ESC 102 Panasonic Electric Works Nordic AB MEW01163 27 4 1 Operating Instructions Fire alarm system EBL512 G3 V1 0 x Regarding the Performance factor gt 0 00 The detector is mounted in a stable environment The momentary sensor values during the day are not differing a lot lt 2 55 The detector is mounted in an unstable environment The momentary sensor values during the day are differing a lot The Performance factor should normally be as low as possible See also Planning Instructions chapter Performance factor Table showing the algorithms and the shortenings respectively Algorithm Short name Normal sensitivity 3 m amp Normal detection 15 s N 15 High sensitivity 2 4 m amp Normal detection 15 s H 15 Low sensitivity 3 6 m amp Normal detection 15 s L 15 Normal sensitivity 3 m amp Slow detection 35 s N 35
13. all the installation programming created and downloaded via WinG3 S W Software i e the EBL512 G3 system program Safe shut down of control unit menu H8 S6 will save the SSW data except the week average sensor values in a Flash ROM before you power off de energize EBL512 G3 Before the first Safe shut down this memory is empty After each Safe shut down the latest SSW data is saved When EBL512 G3 is powered up the RAM working memory will after the restart read the SSW data saved in the Flash ROM The date amp time and alarm counter value is stored in the memory of the real time clock i e the value will be retained also after the c i e has been de energized NOTE After any restart a new week average sensor value will be calculated within two minutes for all the analog smoke detectors During these two minutes all fire alarms from analog smoke detectors will be suppressed Thereafter a new average sensor value will be calculated each week Here follows a table describing different reset alternatives and how the data respectively is affected 74 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Action Data etc Data etc Restart which will be which will be deleted not deleted Power down de energize and SSW SSD then power up again Cold restart FFD WASV S W Via menu H8 S6 Safe shut down of FFD WASV SSD 00 alt 03 control unit
14. comes with a printer The printer type number as a spare part is 5058 In Ext Fire Brigade Panel 1826 it is possible to mount an optional Printer 1535 Expansion boards In the control unit c i e it is possible to mount up to six expansion boards The following types are available Product type no Product name Note 4580 8 zones expansion board 4581 8 relay outputs expansion board 4583 Multipurpose I O expansion board Regarding the expansion boards see also the EBL512 G3 Planning Instructions and drawings Power supply The main power source is a built in rectifier 5037 230 V AC 24 V DC 6 5 A The second power source is a backup battery 2 x 12 V In the c ie is space for two 27 Ah batteries Larger batteries up to 65 Ah have to be placed outside the c i e The batteries and the rectifier are connected to the Main board 5010 which handles the charging of the batteries etc See the EBL512 G3 Planning Instructions chapter Power supply for more information 11 Panasonic Electric Works Nordic AB MEW01163 3 2 3 3 3 4 3 5 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x S W versions Due to continual development and improvement different S W versions can be found When installing a new control unit in a system with older control units you might have to update the S W in the old control units The same S W version is required in all control units Docume
15. 116 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 28 7 Display statistics for communication H5 A6 The statistics can be used during commissioning service etc Number of pollings is the number of pollings questions sent out by the control unit to all the units connected on the COM loop Parity fault is the received number of parity faults and faults in relation to pollings Number of bit faults is the received number of bit faults and faults in relation to pollings No answer is the received number of answer faults no answers and faults in relation to pollings Bit length fault is the received number of bit length faults and bit length faults in relation to the pollings The number of Parity faults Number of bit faults No answer and Bit length faults shall normally be 0 or as close to 0 as possible If not there are some communication problems that have to be investigated Check the COM loop connections and the loop units All values are set to 0 after restart and or after re connection of COM loop via menu H8 S2 Action Text in display Comments Menu According to chapter Access code for service maintenance H5 and H8 see page 110 A1 Calibration of supervised outputs A2 Sensitive fault detection mode A3 Service mode for COM loop A4 Display current consumption in unit A5 Display current consumption on COM loo
16. Access code for service maintenance H5 and H8 see page 110 Calibration in progress Please wait A1 Calibration of supervised outputs Calibration is ready Scroll to another menu or press ESC A2 Sensitive fault detection mode A3 Service mode for COM loop A4 Display current consumption in unit A5 Display current consumption on COM loop A6 Display statistics for communication A7 Activate address setting mode for DU NOTE After the calibration it is recommended do a Safe shutdown of the control unit see menu H8 S6 This will save the SSW data e g the calibration values in a Flash ROM see page 131 5 Control unit outputs SO S3 One end of line resistor 33K in the last unit or one resistor 33K in up to five units 3364 outputs VOO VO1 One end of line capacitor 470 nF in the last unit or one capacitor 470 nF in up to five units 111 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 28 3 Sensitive fault detection mode H5 A2 To increase the possibilities to detect faults during the commissioning it is possible to use the Sensitive fault detection mode The time delay for each fault will then be reduced i e you might find some faults now instead of in the future The Sensitive fault detection mode turned on is indicated by the LED Routing equipment Fault tx activated L13 and the Fault output for routing equipment
17. Australian market only for fan control In the Australian convention only an Alarm Acknowledgement Facility function can be used During the Acknowledgement Period and the Investigation Period respectively there will only be an indication in the c i e display Special hardware is required Regarding the different alarm types etc see the following chapters NOTE In the following chapters are all different alarm types described The figures in this document show the essential information and might not look exactly as shown in the display Pre warning Activation of Pre warning is an option that has to be enabled via WinG3 for the whole system An analog detector will generate a pre warning for a lower alarm level than the fire alarm level Pre warning can be used when an early alarm and or an early action is required e g a soft computer shut down Normal alarm devices output type Alarm devices routing equipment etc will not be activated In case of a pre warning the following happens e The buzzer in the c i e sounds 0 8 sec each 5 sec 0 8 5 sec e LEDs Fire L1 are blinking 0 4 0 4 sec 13 See EBL512 G3 Planning Instructions Any programmable input can also be used to activate a pre warning e g for a High Sensitivity Smoke Detector system 34 Panasonic Electric Works Nordic AB MEW01163 15 2 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x
18. Check the downloaded site specific data SSD e The unit might be faulty e The detector might be removed from its base e There might be a double break on the COM loop Note A single break gives the fault message FAULT Cut off FAULT No reply alert annunciation unit SOK COMeECOl UNLE Box FAULT No reply external presentation unit SO GOmuisoul ANOLE Alert Annunciation Unit 1735 1736 External Presentation Unit 1728 External Fire Brigade Panel 1826 1828 e The contact with the unit is interrupted Check the cable all connections etc Is correct complete SSD downloaded via WinG3 Check the address and SW mode settings If there is a program memory fault in the unit there will be a fault message in the unit s display Memory fault in program area n n 1 or 2 The unit will not work FAULT No reply expansion board x COMO unit Ox Valid for the 8 zones exp board 4580 the 8 relays exp board 4581 and the Inputs and outputs exp board 4583 mounted in the control unit no xx EBL512 G3 cannot communicate with the board Check change the address Check the cables connections FAULT Output x expansion board x Control unit xx A fault on the supervised output x on the expansion board 4583 with address x in control unit no xx If the output is programmed for sounders type Alarm devices it is also indicated by LED Fault Disablements Alarm devices L11 blinking
19. Esc menu 2 or ESC A3 Service mode for COM loop Scroll to another menu or press ESC 114 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 28 5 Display current consumption in unit H5 A4 The resolution is not very high i e the displayed values give only a rough idea of the current consumption Control unit The total current consumption including the charging current at 24V for the selected control unit c i e when it is connected to the mains 230 V AC i e this function is not working by battery backup Charging The battery charging current for the selected control unit c i e This is at 24 V i e before the DC DC converter for battery charging voltage etc Action Text in display Comments Menu According to chapter Access code for service maintenance H5 and H8 see page 110 no A1 Calibration of supervised outputs A2 Sensitive fault detection mode A3 Service mode for COM loop A4 Display current consumption in unit A5 Display current consumption on COM loop A6 Display statistics for communication A7 Activate address setting mode for DU Scroll to menu A4 ADI Waele dccTalmerolalsielanlolielamiamelalit Select control unit fo press lt Write control unit number and press lt l I No reply from control unit If the control unit don t exist or don t answer Current consumption in control un
20. If the output is programmed for fire brigade tx type Routing 57 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x equipment it is also indicated by LED Fault Disablements Fire brigade tx L12 blinking e Calibration not performed via menu H5 A1 Short circuit break on the connected cable equipment Blown fuse F1 Output 0 or F2 Output 1 on the 4583 board Fuse T200mA L 250V TR5 Connected equipment might be missing End of line resistor s missing or not correct value 1 5 resistors 33K NOTE The calibrated value has to be in the range 4K7 50K BAULES OUTIL SX technical number XXXXXX This fault message is valid for a COM loop output unit 3364 output If the output is programmed for sounders type Alarm devices it is also indicated by LED Fault Disablements Alarm devices L11 blinking If the output is programmed for fire brigade tx type Routing equipment it is also indicated by LED Fault Disablements Fire brigade tx L12 blinking Calibration not performed via menu H5 A1 Short circuit break on the connected cable equipment Connected equipment might be stolen End of line capacitor s missing or not correct value 1 5 capacitors 470 nF NOTE The calibrated value has to be in the range 470 nF 5 x 470 nF 2350 nF FAULT Read write site data SSW Control Unit xox SSW the data that is change
21. Memory fault below A fault will be generated and the following text message will be shown in the display and the buzzer will sound FAULT Restart control unit nn code xx address yyyyyy Regarding code xx and address yyyyyy see page 59 This fault is also indicated by LEDs Routing equipment Fault tx activated L13 and Fault Disablements General fault L9 After the fault is acknowledged via menu H6 the LEDs will be turned OFF if there are no other faults After a cold restart required disablements have to be done Memory fault In case of a fault in the Main board 5010 S W system program or the MMI board 5011 S W the following fault message might be shown This is also indicated by LED System fault L7 and the buzzer sounds steady continuous The Fault tx output is activated A new download of the S W system programs are required and or the Main board and or the MMI board have to be replaced NOTE After SSD download see chapter Programming SSD download page 68 the following messages might be shown FAULT Checksum fault in downloaded data Control unit will now restart After restart 76 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x FAULT Restart control unit nn code xx address yyyyyyyyy This means that the SSD have not been correctly downloaded A new SSD download has to be performed 7
22. OFF Yes Some national regulations also require a routine test of the routing equipment Press press 4 i e select No for no test If so the monthly test is completed see below or Press Y and lt i e select Yes to start such a test If so the following will happen in the system e The c i e Fault tx output will be de activated note that this output is activated in normal state indicated by the LED Fault tx activated L13 60 seconds count down starts e After 30 seconds also the c i e Fire brigade tx output and corresponding programmable outputs type routing equipment will be activated indicated by the LED Fire brigade tx delay L14 e After another 30 seconds the test will be ended and the outputs and LEDs will return to normal W and 4 Test of routing equipment in progress nn starts at 060 and will nnn seconds left count down to 000 Monthly test is completed Press J Scroll to another menu or 81 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x press ESC NOTE_1 During the test the following information will be shown in all other c i e displays Zones in test mode 001 002 003 004 NOTE_2 If an alarm point e g a manual call point is in alarm state when the test mode is ended there will not be a fire alarm activated Instead the alarm point will be disabled and has to be re enabled again via men
23. The lid protecting the screw terminals shall after the installation be correctly applied Replace the rectifier fuse F1 and the battery fuse F2 on the main board 5010 LED Operation L5 indicate that the 24 V DC power supply rectifier or battery is okay The c i e will now restart see chapter Restart page 74 The site specific data SSD created in WinG3 can now be downloaded see chapter Programming SSD download page 68 See also chapter Calibration of supervised outputs H5 A1 page 111 Control Units ina TLON network The EBL512 G3 system can be build up as a single TLON Network or a redundant TLON Network Cable tie shall be mounted to keep the mains wires well separated from the 24 V DC wires Follow National regulations 65 Panasonic Electric Works Nordic AB MEW01163 18 2 1 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x In the single TLON Network one TLON connection board 1590 has to be plugged in each control unit Network no 0 whereas in the redundant TLON Network two connection boards 1590 have to be plugged in each control unit The redundant TLON Network supports full functionality also in case of a network fault i e open circuit or short circuit in one of the TLON networks First install Network no 0 When the 1590 board is on place and the network cables are connected for each control unit do as for a single control un
24. Zones to be set in test mode Press lt to start the test e g 001 002 003 001 002 003 004 mode 004 Zones in test mode LED Test mode L8 001 002 003 004 End test will light up Perform the tests The zone s will stay in test mode until the test mode is ended but after 60 minutes or if you press Esc menu you will be logged out from menu H1 Perform the test as quickly as possible since the output s for routing equipment fire brigade tx are disabled also the parts of the zones in test mode not visible for the test personnel are disabled In order to shorten the testing time any time delay for the detectors zones in test mode will be disabled i e fire alarm will be detected faster than normally In the tested alarm point the LED will light up and the LEDs Fire L1 in the c i e will light up approx 10 seconds then the alarm point will be automatically reset The printer if available will print out every tested alarm point Zone xxx Address xx Time HH MM A sensor in test mode will not be able to activate fault After 60 minutes or Zones in test mode You are no longer in menu Esc Menu 001 002 003 004 End test 4 H1 but still in test mode NOTE See chapter The information area priority order page 20 regarding priority order When required Zones in test mode Press lt 4 to end test Menu code 001 002 003 004 End test Test of routing equipment The LED Test mode is turned
25. activated Ventilation yellow Output s for fire smoke ventilation equipment activated Or a programmable input type Ventilation is activated Fire brigade tx red Output Fire alarm for fire brigade tx routing equipment and or corresponding programmable output s of type Routing equipment is are activated Or a programmable input type Fire brigade tx is activated Test of routing equipment in progress see menu H1 Operation green The c i e is powered via the rectifier and or the battery Alarms queued 2 red More than one unit zone have activated fire alarm Use push button Alarms queued P8 to scroll amongst the alarm points or soft key Next zone P5 to scroll amongst the zones NOTE Fire alarms are Fire alarm incl test mode alarm Heavy smoke heat alarm Alert Annunciation AA alarm Key cabinet alarm 15 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Push buttons on the Fire Brigade Panel FBP Push button Operation function Silence buzzer yellow Used to silence the buzzer in the c i e P2 Silence Alarm devices Used to silence alarm devices sounders i e outputs for D red alarm devices will be de activated P3 Reset green Used to reset a Fire alarms see below Co incidence alarms if not automatically reset For more information see Alarm reset page 44 NOTE P3 has to be pressed for gt 0 5
26. addresses have to be re enabled via menu H4 B2 Menu According to chapter Access see page 78 Scroll to menu H2 H2 Disable or re enable Scroll to menu B2 B2 Disable zone address Disable zone loo address 00 press lt Write zone number and_ Disable zone 001 address of Press to disable the address e g 001 press lt and 01 a Disable zone address Disable output Re enable zone Re enable zone address Re enable output Disable re enable output type Disable re enable alarm devices Disable re enable routing equipment B10 De activate alert annunciation function Re enable time HH MM Press to disable without automatic re Yes enablement Default is current time 3 hours or Accept the time 3 hours or set another time max 24 hours select Yes and press 2 to disable with automatic re enablement 85 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Disable zone oo address 00 LED Fault press lt Disablements General disablements L10 will light up Disable another zone or press ESC Scroll to another menu or press ESC 86 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 25 3 Disable output H2 B3 Outputs can be individually disabled Disabled output will stay in or return to the normal condition for t
27. alarm zone 123 address 45 within zone 123 Co incidence alarm Zone Address T 23 45 SMOKE User definable alarm text for 123 45 If more than one Co incidence alarm not dependent on each other are activated the LEDs Alarms queued L6 are blinking and the Co incidence alarms will be automatically scrolled each 5 second If two or more zones or alarm points zone addresses dependent on each other are in alarm status at the same time normal fire alarm see above will be activated in the system The co incidence alarm function can be turned on off via a time channel 42 Panasonic Electric Works Nordic AB MEWO01163 15 7 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Quiet alarm One or more smoke detectors via WinG3 programmed for Quiet alarm have passed the fire alarm level Quiet alarm is used for fan control stop start depending on the type of fan Quiet alarm is normally used in conjunction with one I O Matrix board 4582 one application board for fan control and one I O unit 3361 for control of each fan Indications and actions LEDs Fire L1 are blinking 0 4 0 4 sec the buzzer sounds 0 8 5 sec and there is a Quiet alarm presentation in the display Programmable outputs for quiet alarm e g 3361 outputs controlling supply air fans and standard fans i e any output with a control expression containing the trigger conditions Quiet Alarm Zo
28. automatically 23 Panasonic Electric Works Nordic AB MEWO01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 7 3 Access level 2B J After the door has been opened Door open symbol in the symbol field the building occupier has access to level 2A and after access code for level 2B or 3A access to the following menus C2 Activate interlocking output 24 Panasonic Electric Works Nordic AB MEW01163 7 4 7 5 7 6 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Access level 3A After the door has been opened Door open symbol in the symbol field the service maintenance personnel have access to level 2A and after access code for level 3A access to the following menus Same menus as in access level 2B plus the following A1 Calibration of supervised outputs A3 Service mode for COM loop A4 Display current consumption in CU AS Display current consumption on COM loop A6 Display statistics for communication A2 Sensitive fault detection mode A7 Activate address setting mode for DU S1 Disconnect loop zone line input S3 Acknowledge SERVICE signal S2 Re connect loop zone line input S4 Clear weekly average S9 Change code for service maintenance S10 Change code for PC communication Access level 3B Used by Service maintenance commissioning engineers when a PC i e WinG3 is to be connected to EBL512 G3 for backup uploa
29. clock H3 Present system status H4 Disablement H4 U1 Disablement by time channel H4 U2 Open doors H4 U3 Sensor values H4 U4 27 4 1 Reset of a week average sensor value 46 46 47 48 63 65 65 65 66 67 67 67 68 68 68 69 69 70 70 72 73 73 74 78 80 83 84 85 87 88 89 90 92 94 96 97 98 99 99 100 101 102 103 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 27 5 Sensors activating SERVICE signal H4 US 105 27 6 Event log H4 U6 105 27 7 Show information H4 U7 106 28 Service H5 109 28 1 Access code for service maintenance H5 and H8 110 28 2 Calibration of supervised outputs H5 A1 111 28 3 Sensitive fault detection mode H5 A2 112 28 4 Service mode for COM loop H5 A3 113 28 5 Display current consumption in unit H5 A4 115 28 6 Display current consumption COM loop H5 A5 116 28 7 Display statistics for communication H5 A6 117 28 8 Activate address setting mode for DU H5 A7 119 29 FAULT Acknowledge H6 120 30 Perform ZONE TEST Test mode H7 121 31 Maintenance H8 123 31 1 Access code for service maintenance 123 31 2 Disconnect loop H8 S1 123 31 3 Re connect loop H8 S2 125 31 4 Acknowledge SERVICE signal H8 S3 126 31 5 Clear weekly average H8 S4 128 31 6 Test of alarm devices H8 S5 129 31 7 Safe shut down of control unit H8 S6 131 31 8 Activate address in alarm mode H8 S
30. e Outputs programmed for pre warning are activated e Inthe c i e display a presentation number zone address is shown for the first pre warning e Inthe c i e display a user definable text message the alarm text for fire alarm is shown if programmed Example pre warning zone 123 address 45 within zone 123 Pre warning Zone Address 123 49 sae User definable alarm text for 123 45 SMOKE after the presentation number is automatically added depending on the type of alarm point i e SMOKE HEAT MULTI or MCP NOTE The text Menu P4 is visible in the display only if the door in the CU is open If more than one pre warning is activated the LEDs Alarms queued L6 are blinking and the pre warnings will be automatically scrolled each five seconds Pre warnings are automatically reset see chapter Alarm reset page 44 Fire alarm The system can handle up to 15360 fire alarms but only 512 fire alarms can be shown in the c i e display If more than 512 fire alarms are activated no more fire alarms will be shown until one or more of the 512 fire alarms are reset Outputs programmed for General pre warning and outputs programmed for the activated pre warning s 35 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x See also chapter The information area priority order page 20 In accordance with the EN54 2 standard the fol
31. fault is already serviced corrected Example Fault messages shown in the control unit display FAULT No reply zone 123 address 01 technical number 000025 2009 10 02 15 22 serviced FAULT No reply zone 123 address 03 technical number 000027 2009 10 06 09 25 FAULT No reply zone 234 address 01 technical number 002112 2009 11 06 15 25 Number of not ackn faults in system 5 e Login according to chapter Access page 78 e Use menu H6 access level 2B for fault acknowledge see chapter FAULT Acknowledge H6 page 120 Menu H6 is a list showing a maximum of 200 faults not acknow ledged faults and or acknowledged but not serviced corrected faults e All faults have to be individually acknowledged one by one by the key pad button e Use or w to scroll e Ifa fault has been corrected before it has been acknowledged the text Serviced is added after the time It still has to be acknowledged e When a fault is corrected serviced and acknowledged it will disappear from the list H6 4 Indicating that output for routing equipment Fault tx is activated 63 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x e When all faults have been acknowledged output s for routing equipment Fault tx is are reset i e the LED Routing equipment Fault tx activated L13 will be turned off e As long as there are faults i e not acknowle
32. for each unit set with the programming tool 3314 0 3 COM loop number 00 29 The control unit address number Don t have to be in sequence The connections to the TLON network don t have to be in sequence The address is set with a PC SW TLON Manager NOTE Totally 1020 COM loop addresses can be used for one control unit of which up to 512 COM loop addresses can be used for alarm points A brand new detector is factory set to COM loop address 000 Connected on the COM loop the detector LEDs will start blinking every second indicating that a COM loop address 001 255 has to be set before the detector will work IL Since address 000 cannot be used in fact the total number of addresses will be 4 x 255 1020 32 Panasonic Electric Works Nordic AB MEW01163 14 2 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Presentation number For each fire alarm point input zone a presentation number NNN NN has to be programmed The presentation number is shown in the c i e display and ext FBP display to identify the point zone activating fire alarm It is also used to disable re enable fire alarm points zones and as trigger conditions in control expressions to activate programmable outputs Together with the presentation number a user definable 40 characters text message alarm text can be displayed if programmed NNN NN 00 99 01 99 The ad
33. for fire alarm at short circuit PAUL S ZONG lirine mont KL technical number xxxxxx Valid for the Multipurpose I O unit 3361 monitored zone line input Z Break on the zone line or wrong no end of line capacitor 470 nF or short circuit if not programmed for fire alarm at short circuit No contact with main board Fault in the Main board 5010 software or the Main board Check the cable between the boards This is a very serious fault Call for service personnel engineer immediately User programmable text External fault Programmable input is connected to any external equipment s fault output User definable fault message programmed via WinG3 62 Panasonic Electric Works Nordic AB MEW01163 17 2 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Fault acknowledge The LEDs Routing equipment Fault tx activated L13 and Fault Disablements General fault L9 are turned on LEDs Fault Disablements Alarm devices L11 System fault L7 and or Fault Disablements Fire brigade tx L12 might be turned on as well Output s for routing equipment Fault tx is are activated Output s for general fault is are activated Output s for general charge fault might be activated One or more fault messages incl date and time are shown in the control unit display If Fault latching is selected in WinG3 default after the time might be shown Serviced the
34. have been re enabled The LED Fault Disablements General disablements L10 will be turned OFF if there are no other disablements in the system The outputs will be disabled until re enabled again via this menu Menu According to chapter Access see page 78 Scroll to menu H2 H2 Disable or re enable Disable zone 2 Disable zone address Disable output Re enable zone Re enable zone address Re enable output Disable re enable output type Disable re enable alarm devices Disable re enable routing equipment B10 De activate alert annunciation function Scroll to menu B7 B7 Disable re enable output type Including Addressable siren 3377 and Addressable sounder base 3379 4 Also the Extinguish equipment output on the German FBP interface board 4583 92 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Select output type Use VW or A to select extinguishing the output type in the list ventilation and press lt contr exting vent interlocking Select control unit io All Write the CU number or press P and select All Blank space all CUs Press Disable or Re enable Disable or Re Select control unit Wo All Disable or Re enable enable another output type Blank space control unit the procedure is similar for all types or press ESC Scroll to Suc DEEG ptemcqarclelis another menu or
35. indicators and push buttons page 15 The fire brigade personnel use the FBP to see which alarm point zone s having activated fire alarm and to take required operational control of the system In the graphical display the information in the upper part is depending on how many alarm points zones having generated fire alarm In the middle part a user definable text message alarm text is shown for each alarm point zone in alarm if programmed The CP is to communicate with the system i e for commissioning monthly tests maintenance etc Access codes for different access levels are required A keypad is used to get access to the system a menu tree with main and sub menus and for different manoeuvres The CP has several LEDs for system status 14 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 5 LED indicators and push buttons LEDs and push buttons can vary according to type and configuration convention country language See also Figure 2 page 14 LED Eee ee on the Fire Brigade Panel FBP LED LED indicator Indicating Fire 5 red Fire alarms see below Co incidence alarm Pre warning Quiet alarm normally Australia only Alarm Acknowledgement Facility AAF alarm Australia only See also chapter Alarm types page 34 Extinguishing red Output s for extinguishing equipment activated Ora programmable input type Extinguishing is
36. not ok another fault will be generated 2 After SSD download the control unit will restart A number of faults might then be generated e g due to not connected units This will cause heavy traffic on the network which might affect delay the SSD download to the other units 68 Panasonic Electric Works Nordic AB MEW01163 19 3 19 4 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x FAULT Site specific data SSD CU nn YYYY MM DD HH MM This text message means that the SSD have not been downloaded properly i e a new download has to be performed Control Units ina TLON network The SSD for all control units can be downloaded via a PC WinG3 connected to one control unit The download will be performed to the control units one at a time according to the chapter Single Control Unit above The download is performed in a consecutive order i e 0 1 2 3 4 29 amongst the selected control units but the control unit where the PC is connected will automatically be the last one to get the SSD downloaded When the SSD download to a control unit is completed that control unit will automatically restart see chapter Restart page 74 User definable text messages download When a fire alarm is activated e g an addressable alarm point the presentation number Zone Address will be shown in the control unit display as well as in the ext FBP 1826 1828 display There will also be sh
37. of the printer front to check the paper feed function and tear off the paper e Close the control unit door 146 Panasonic Electric Works Nordic AB MEWO01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 36 Replacing a TLON connection board and or the Main board By the TLON network programming some unique data will be stored in a memory on the 1590 TLON connection board and some will be stored in a memory on the 5010 main board Replacing a TLON connection board 1590 After replacing the board do Replace Update and Save in TLON Manager Replacing a TLON connection board 1590 and also the Main board 5010 After replacing the boards do Replace Update and Save in TLON Manager Replacing the Main board 5010 After replacing the board put back the TLON connection board s in the same position as on the replaced main board do Update and Save in TLON Manager 147 Panasonic Electric Works Nordic AB MEWO01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 37 Battery maintenance The batteries 2 x 12 V 28 Ah e g Panasonic LC P1228AP are placed inside the control unit Larger batteries lt 65 Ah have to be placed outside the control unit e g in a separate battery cabinet etc The control unit supervise and charge the batteries and a fault will be generated for any trouble with the batteries The batteries rechargeable Sealed Lead Acid batteries
38. press ESC 4l NOTE Outputs disabled for a specific control unit e g CU 03 can not be collectively re enabled via all CUs You have to re enable the outputs for the specific control unit s e g CU 03 93 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 25 7 Disable re enable alarm devices H2 B8 Outputs programmed as type alarm device sounder can be disabled all at the same time Disabled alarm devices means that even if the control expression trigger condition for the output respectively is fulfilled true the output will not be activated The outputs in one or more control units can be disabled or the outputs in all control units Disabled alarm devices are indicated by LEDs Fault Disablements Alarm devices L11 and General disablements L10 and shown in menu H4 U1 from which it is possible to get a print out When all outputs have been re enabled The LEDs Fault Disablements Alarm devices L11 and General disablements L10 will be turned OFF if there are no other disablements in the system The outputs will be disabled until re enabled again via this menu NOTE This function may may not be the same as push button we Silence alarm devices P2 see chapter Silence Alarm devices page 26 Menu According to chapter Access see page 78 Scroll to menu H2 H2 Disable or re enable
39. sounder base 3379 5 For the alarm devices 3377 and 3379 the tone with the highest priority level and type alarm device will be automatically selected 129 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Test of alarm devices in progress The test will continue for End test one hour if not stopped via this menu S5 or if a fire alarm is activated in the system Press lt to stop the test Test alarm devices control unit do All Continue like above to test alarm devices in other control units or press ESC S5 Test alarm devices Scroll to another menu or press ESC 130 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 31 7 Safe shut down of control unit H8 S6 It s not recommended to power off a control unit i e no 230 V AC and no battery without first doing a safe shut down of control unit Safe shut down will save the SSW and put the CPUs at rest See also chapter Restart page 74 It s recommended to do a safe shut down after commissioning the installation and after the calibration of supervised outputs change of access code etc in order to save the new values codes etc Safe shut down can be performed from any control unit and any control unit can be selected A control unit without a front has to be shut down from another control unit NOTE By restart and power o
40. the mr selected output Press Reset All to reset CEE all interlocking outputs Press ESC to menu C3 a a reset C3 Reset interlocking output Scroll to another menu or alt press ESC ESC 141 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 32 4 Disable interlocking output H9 C4 Interlocking outputs Type Interlocking can be individually disabled via this menu but not via menu H2 B3 All interlocking outputs can be collectively disabled via menu H2 B7 The Interlocking Combination Area Point is to be entered to disable the output Up to 200 interlocking outputs can be disabled Disabled interlocking outputs are listed in menu H4 U1 from which it is also possible to get a print out The LED Fault Disablements General disablements L10 is also indicating one or more disabled interlocking outputs Text in display Comments Menu According to chapter Access see page 78 Scroll to menu H9 H9 Interlocking outputs and inputs C2 Activate interlocking output C3 Reset interlocking output C4 Disable interlocking output C5 Re enable interlocking output Scroll to menu C4 C4 Disable interlocking output Disable interlocking output Write the area number and area oo point 00 point and press lt press If more interlocking outputs shall be disabled continue the same way Press ESC to menu C4 2 disabl
41. 2 Re connectloop SY a Re connect type m0109 Use A or WV to Zone line input select a type and press Addr zone interface pele a Re enable COM loop of control unit 00 Write the required data and Ty Le Depending on the press selected type the Re enable zone line input following will be Zone line input of exp board 0 control unit 00 shown Re enable addressable zone interface Input technical number flooo00 Re connect type e ieleleye Continue to re connect or Zone line input press ESC to menu S2 Addr zone interface ESC S2 Re connect loop Scroll to another menu or press ESC 125 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 31 4 Acknowledge SERVICE signal H8 S3 When SERVICE signal is generated in the system following symbol is shown in the display s symbol area 4 See also chapter Sensors activating SERVICE signal H4 U5 page 105 When service signal from a sensor is acknowledged the sensor is given a default sensor value same as for a new clean sensor i e first replace the sensor and then acknowledge the service signal as soon as possible The first week average sensor value after acknowledge will be calculated within one hour then each week NOTE If a sensor is replaced without having generated service signal it has to be reset to the default sensor value via menu H8 S4 page 128
42. 4 Alert Annunciation 45 16 5 Key cabinet alarm reset 45 Panasonic Electric Works Nordic AB MEW01163 Rev 16 6 16 7 17 17 1 17 2 18 18 1 18 2 Operating Instructions Fire alarm system EBL512 G3 V1 0 x Co incidence alarm Quiet alarm reset Fault Fault messages Fault acknowledge Commissioning an installation Single Control Unit Control Units in a TLON network 18 2 1 TLON network installation 18 3 18 4 18 5 19 19 1 19 2 19 3 19 4 20 20 1 20 2 21 21 1 22 23 24 25 25 1 25 2 25 3 Add a Control Unit in a TLON network Make two TLON networks one Delete a Control Unit in a TLON network Programming SSD download Check All Loop Units Single Control Unit Control Units in a TLON network User definable text messages download New system program S W version download __ Single control unit c i e Control Units in a TLON network Upgrade number of alarm points Control Units in a TLON network Restart Access Perform monthly test H1 Disable or re enable H2 Disable zone H2 B1 Disable zone address H2 B2 Disable output H2 B3 Re enable zone H2 B4 25 4 25 5 25 6 25 7 25 8 25 9 26 27 27 1 27 2 27 3 27 4 Re enable zone address H2 B5 Re enable output H2 B6 Disable re enable output type H2 B7 Disable re enable alarm devices H2 B8 Disable re enable routing equipment H2 B9 De activate Alert Annunciation function H2 B10 Set calendar and
43. 5 1736 Ext Presentation Unit 1728 Ext Fire Brigade Panel 1826 1828 There is no SSD Site Specific Data downloaded to the unit or something is wrong in the downloaded SSD PAUL S SbSrWLSScl OwrEjowlic x Control imi xx If the output is programmed for sounders type Alarm devices it is also indicated by LED Fault Disablements Alarm devices L11 blinking If the output is programmed for fire brigade tx type Routing equipment it is also indicated by LED Fault Disablements Fire brigade tx L12 blinking x 0 SO Short circuit break on the connected cable equipment and or blown fuse F4 on the main board 5010 x 1 S1 Short circuit break on the connected cable equipment and or blown fuse F5 on the main board 5010 x 2 S2 Short circuit break on the connected cable equipment and or blown fuse F6 on the main board 5010 gt NOTE The fault has to be acknowledged i e and it can last up to 10 minutes after the acknowledgement before the communication returns to communicate in the A direction only 60 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x x 3 S3 Short circuit break on the connected cable equipment and or blown fuse F7 on the main board 5010 Fuse T500mA L 250V TRS Calibration not performed via menu H5 A1 Connected equipment might be stolen Resistor s missing or not correct value 1 5 resistors
44. 5 1736 or an AA controller 1740 or in the c i e If more than one AA alarm is activated they will be reset all at a time NOTE Reset via an external unit is possible only during the investigation time and AA alarm s only not normal fire alarms Key cabinet alarm reset A key cabinet alarm has to be reset like the normal fire alarms 45 Panasonic Electric Works Nordic AB MEW01163 16 6 16 7 Operating Instructions Fire alarm system EBL512 G3 V1 0 x After reset a fault message is shown in the display to inform the user that the key cabinet has been opened FAULT Key cabinet control unit xx yyyy mm dd hh mm NOTE The date is in the Ukrainian and the Australian conventions shown as dd mm yyyy xx control unit number If the key cabinet is closed again the status information is changed to serviced This key cabinet fault message is to be acknowledged the same way as normal faults see chapter Fault acknowledge page 63 When the key cabinet fault is acknowledged the LED Fault Disablements General fault L9 will be turned off i e if the key cabinet is closed and if there are no other faults in the system Co incidence alarm A Co incidence alarm can be manually reset with the Reset button P3 on the c i e front or automatically reset after 5 minutes i e if the alarm point zone is no longer in alarm status See also chapter Co incidence alarm 2 address zone dependen
45. 7 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 23 Access To use the key pad in the control unit to get access to the menu tree it is necessary to logon with an access code for level 2B or 3A See also chapter Access levels page 22 Open the door in the control unit level 2A press the soft key Menu P4 and continue as follows EBL512 G3 Control Unit XX User definable text User definable text yyyy mm dd hh mm u Enter the code 4 digits Access code The digits are replaced by ve In the display NO ACCESS The access code was not correct Try again E The access code was i correct A main menu list is displayed Press lt to accept menu H1 or scroll Disable or re enable jump to the wanted menu Set calendar and clock H2 H10 and press Present system status Service FAULT Acknowledge Perform ZONE TEST Maintenance Interlocking outputs and inputs H10 Change access code for daily duties 78 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Explanations Action in the table use push button key e g Text in display in the table what is shown in the display in the control unit c 1 e Comments in the table Comments to the text in the Action and Text in display columns Use A and V to scroll between the main menus
46. 7 133 31 9 Synchronize the control units H8 S8 135 31 10 Change code for service maintenance H8 S9 137 31 11 Change code for PC communication H8 S10 138 32 Interlocking outputs and inputs H9 139 32 1 Activated interlocking outputs inputs H9 C1 139 32 2 Activate interlocking output H9 C2 140 32 3 Reset interlocking output H9 C3 141 32 4 Disable interlocking output H9 C4 142 32 5 Re enable interlocking output H9 C5 143 33 Change access code for daily duties H10 144 34 Annual control 145 35 How to change paper in the printer 146 36 Replacing a TLON connection board and or the Main board 147 37 Battery maintenance 148 38 How to avoid unnecessary nuisance fire alarms 149 39 Information regarding radioactive radiation source151 40 Revision history 152 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 1 Introduction EBL512 G3 Operating Instructions is a document intended to be used by the end user and the fire brigade personnel as well as service commissioning engineers Due to continual development and improvement different S W versions are to be found This document is valid for S W version 1 0 x On the date rev date of this document x 0 Since the EBL512 G3 control unit c i e is produced for many countries the look the texts the functions etc might vary Products Consists of one or more parts HW according to a Product Parts Lis
47. 73 01 Scroll to another menu or press ESC 89 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 25 5 Re enable output H2 B6 Disabled outputs are listed in menu H4 U1 from which it is possible to get a print out When all outputs have been re enabled The LED Fault Disablements General disablements L10 will be turned OFF if there are no other disablements in the system Menu According to chapter Access see page 78 Scroll to menu H2 H2 Disable or re enable n lt n Disable zone address Disable output Re enable zone Re enable zone address Re enable output Disable re enable output type Disable re enable alarm devices Disable re enable routing equipment B10 De activate alert annunciation function Scroll to menu B6 B6 Re enable output madj Re enable output type 361 3364 4364 Select output type 3377 3379 S CU voltage output S0 S S3 R R CU relay output RO R1 Expansion board Press lt to accept a Re enable loooo1 output 0 If there are no outputs to Depending on the 000001 output 1 re enable menu B6 will be selected type the following will be shown h in Re enable of 0001 priority 0 shown again 010001 priority 3 Use Y or A to select the output in the list and Re enable control unit lo SO ress 4 Regarding the control unit 00 S1 P garding 3377 ASI amp 3379 ASB
48. 8 H2 Disable or re enable B2 Disable zone address Disable output Re enable zone Re enable zone address Re enable output Disable re enable output type Disable re enable alarm devices Disable re enable routing equipment B10 De activate alert annunciation function Disable zone loo press lt Disable zone o1 Press lt to disable press lt Re enable time H MM Press to disable without automatic re Yes enablement Default is current time 3 hours or Accept the time 3 hours or set another time max 24 hours select Yes and press 2 to disable with automatic re enablement Disable zone loo LED Fault press lt Disablements General disablements L10 will light up Disable another zone or press ESC Scroll to another menu or press ESC 84 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 25 2 Disable zone address H2 B2 Addressable alarm points also addressable manual call points connected to the COM loop can be individually disabled Disabled alarm points zone addresses are listed in menu H4 U1 from which it is also possible to get a print out Regarding disabled analog smoke detector The sensor values will not be saved i e only the values saved before and after the disablement will be used when calculating the week average sensor value Disabled alarm points zone
49. AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Re enable zone H2 B4 Disabled zones are listed in menu H4 U1 from which it is also possible to get a print out Re enabling via this menu has higher priority than automatic re enabling When all zones have been re enabled The LED Fault Disablements General disablements L10 will be turned OFF if there are no other disablements in the system NOTE It is not possible to collectively re enable a number of alarm points zone address that are individually disabled via menu H2 B2 Menu According to chapter Access see page 78 Scroll to menu H2 H2 Disable or re enable Disable zone Disable zone address Disable output Re enable zone Re enable zone address Re enable output Disable re enable output type Disable re enable alarm devices Disable re enable routing equipment B10 De activate alert annunciation function Scroll to menu B4 B4 Re enable zone Re enable zone lo If there are no zones to re zone 002 enable menu B4 will be zone 006 shown again The disabled zone 073 zones will be shown in a list Use Y or A to select the zone and press a Re enable zone loz Re enable another zone or zone 006 press ESC Scroll to zone 073 another menu or press ESC 88 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 25 4 Re enable zo
50. BL512 G3 V1 0 x 2 Interlocking log only interlocking events 3 General event log all events except alarm and interlocking events Menu According to chapter Access see page 78 Scroll to menu H4 H4 Present system status U1 Disablement U2 Disablement by time channel U3 Open doors U4 Sensor values U5 Sensors activating SERVICE signal U6 Event log Information Scroll to menu U6 U6 Event fs Eventiog D Select event log Use Y or A to select Interlocking log a log E g the Alarm General event log log When lt is pressed the events will be shown in the A list in which you can display The most recent event is on top of the list scroll with Y or A Some examples are shown below If printer 5058 is mounted Command Reset all alarms the soft key Print will be 2009 12 03 09 25 visible else not Press Print for a print out of FIRE ALARM zone 123 address 45 the three events shown in 2009 12 03 09 09 the display Scroll with Y or A to view three FIRE ALARM zone 123 address 46 more events and press 2009 12 03 09 07 Print for a new print out If there are no events in the list when is pressed the list view will not open ESC U6 Event log Scroll to another menu or press ESC 7 7 Show information H4 U7 Menu H4 U7 can be used to show the following information for that specific control unit Main board version The S W system program version of the Main
51. Disable zone Disable zone address Disable output Re enable zone Re enable zone address Re enable output Disable re enable output type Disable re enable alarm devices Disable re enable routing equipment B10 De activate alert annunciation function Scroll to menu B8 B8 Disable re enable alarm devices 94 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Select control unit lo All Write the CU number or press gt and select All Blank space all CUs Press Disable or Re enable Disable or Re Select control unit lo All Disable or Re enable alarm enable devices in another control Blank space unit or press ESC Scroll to another menu or press ESC 4 NOTE Alarm devices disabled for a specific control unit e g CU 03 can not be collectively re enabled via all CUs You have to re enable the outputs for the specific control unit s e g CU 03 95 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 25 8 Disable re enable routing equipment H2 B9 Disabled outputs are listed in menu H4 U1 from which it is possible to get a print out Outputs for routing equipment fire brigade tx fault tx can be disabled and re enabled via this menu Can be useful during an installation and test period when only local alarms are required Disabled output is indicated by LE
52. Ds Fault Disablements General disablements L10 and Fire brigade tx L12 Disabled output will stay disabled until re enabled again via this menu Menu According to chapter Access see page 78 Scroll to menu H2 H2 Disable or re enable Disable zone Disable zone address Disable output Re enable zone Re enable zone address Re enable output Disable re enable output type Disable re enable alarm devices Disable re enable routing equipment B10 De activate alert annunciation function Scroll to menu B9 B9 Disable Re enable routing equipment Routing equipment for Fire Use Y or A to select Fault output type s Se Aei Press Disable or Re enable Blank space Disable or Re Routing equipment for BIG Disable or Re enable enable Fault another output type or Fire and fault press ESC Scroll to another menu or press Blank space ESC 96 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 25 9 De activate Alert Annunciation function H2 B10 Normal function For alarm points zones programmed for Alert Annunciation via WinG3 is normally the AA function enabled via a time channel e g enabled daytime during working hours and disabled night time As an alternative the AA function can be continuously enabled Off Via this menu H2 B10 it is possible to de activate disable the AA function i e the AA
53. EW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 31 Maintenance H8 31 1 Access code for service maintenance Access code to level 3A is required for menu H8 31 2 Disconnect loop H8 S1 Before physical connection disconnection of loop units etc the loop or zone line shall be disconnected disabled i e there will be no voltage on the loop to avoid damage on the units and the c i e Zone line input requires an 8 zones expansion board 1580 in the control unit or an Addressable multipurpose I O unit 3361 connected on a COM loop Menu Procedure according to chapter Access code for service maintenance H5 and H8 see page 110 S1 Disconnect loop zone line input S2 Re connect loop zone line input S3 Acknowledge SERVICE signal Clear weekly average S5 Test of alarm devices S6 Safe shut down of control unit S7 Activate address in alarm mode S8 Synchronize the control units S9 Change code for service maintenance 10 Change code for PC communication mon Disconnect type 0 mlele o Use A or VW to Zone line input select a type and press Addr zone interface ae Disconnect COM loop Write the required data and Depending on the COM loop of control unit 00 press 4 selected type the Disconnect zone line input following will be Zone line input of exp board 0 control unit 00 shown i Disconnect addressable zone interface Input technical number flooo00 a Disc
54. H1 H10 Use Enter to accept Some main menus have sub menus Use A and V to scroll between the sub menus e g B1 B9 Use to accept NOTE The menus are circular i e if you scroll with Y and the last menu is reached the first menu comes up next Quick jump can be used within each menu e g in menu H1 press 6 for a quick jump to menu H6 1 and then 0 within 1 sec 10 In some cases a cursor appearse g Disable zone Ho 0 It is then possible to type in digits with the numeric keys 0 9 Use lt 4 gt A and VW to move the cursor in a menu Use ESC to return from a sub menu to the main menu H1 H10 Use ESC or the soft key Esc menu to log off from a main menu H1 H10 Use the soft key Esc menu to log off It is always possible to log off whenever the soft key Esc menu is available There will be an automatic log off 60 minutes after the last action i e if the key pad or a push button has not been used for 60 min and also when you close the door NOTE In the following chapters are all the menus described The Text in display column shows the essential text and might not look exactly as shown in the display 79 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 24 Perform monthly test H1 The control unit and the installation shall be tested on a regular basis If one twelfth of the a
55. I nn describes between which Short Circuit Isolators 4313 the short circuit is located nn A B 00 01 02 03 04 05 06 07 15 A amp B is the built in isolator in the EBL512 G3 c 1 e A direction and B direction respectively If no SCI is used the information will always be SCI A lt gt SCI B If one SCI no 0 is used the information will be SCI A lt gt SCIOO or SCIOO lt gt SCI B and so on There will also be a FAULT No reply message for each unit not found by the c i e If there are several short circuits on the loop the message shows the isolator just before the break in the A direction incl the following isolator There will also be shown FAULT Multiple 59 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x faults ic NOTE Each 10 minute a check is performed if all short circuits are corrected repaired If so the communication automatically returns to communicate in the A direction only HAULS Site specie darca SSD GOMcwOl GNL sox The Site Specific Data SSD in control unit no xx is not downloaded correctly a checksum fault etc A new SSD download via WinG3 is required FAULT Site specifie Ceca al WMACLAELOM Aane SX COCO ite specific data external tiron WME xX ComcicOl Unit xox CS SjOSCwiclS daca Lre brigade COmaaO xx Alert Annunciation Unit 173
56. Operation L5 will be turned on and the other LEDs will be turned off 7 Close X the Download dialog box Follow the same procedure in each control unit 20 2 Control Units ina TLON network All control units connected to a TLON network shall have the same software version For download of new software in each control unit follow the procedure described above Since some control units do not have contact with some control units during the downloading the following faults might be generated FAULT Control unit xx has no contact with control unit xx network x yyyy mm dd hh mm FAULT CU xx has wrong information yyyy mm dd hh mm The faults have to be acknowledged 72 Panasonic Electric Works Nordic AB MEW01163 21 Operating Instructions Fire alarm system EBL512 G3 V1 0 x Upgrade number of alarm points 21 1 All EBL512 G3 settings are normally factory downloaded before the delivery It is however possible to do the following on site e Upgrade the maximum number of alarm points 128 gt 256 gt 512 NOTE The maximum number of COM loop addresses is always 1020 i e address 1 255 on each COM loop If you wish to upgrade the number of alarm points a PC and WinG3 are used Before download the PC has to be connected to the USB connector 1 Logon to the control unit 2 In the control unit icon pop up menu select Upgrade number of alarm points and a dialog box opens all Upgrad
57. Panasonic Operating Instructions MEW01163 Revision Fire Alarm System EBL512 G3 V1 0 x Author Jan Pettersson Date of issue 2010 04 27 Date of rev This page has deliberately been left blank Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Table of contents 1 Introduction 2 Definitions Explanations 2 1 PEWN AB 2 2 Alarm points 2 2 1 Smoke detector 2 2 2 Sensor 2 2 3 Analog detector 2 2 4 Analog Sensor Base ASB 2 2 5 Conventional detector 2 2 6 Conventional Detector Base CDB 22 7 Addressable 2 2 8 Conventional zone line input External line 2 3 Output unit 2 4 Output Control output 2 5 Short circuit isolator ISO 2 6 Display unit DU Dil COM loop 2 8 Control Unit C U C LE 2 9 Fire Brigade Panel FBP 2 10 Control panel CP 2 11 System 2 12 Network TLON LonWorks Echelon Node TLON Conn board Gateway Sub net Backbone net Router Repeater 9 2 13 LED 9 o0 o0 o0 o0 O O NA N NNN NNN NN A 2 14 External Indicator LED 9 2 15 Display LCD 9 2 16 Door open Door Key switch 9 2 17 Site Specific Data SSD 9 2 18 Software S W System program 10 3 Overview 11 3 1 The EBL512 G3 system 11 3 1 1 Printer 11 3 1 2 Expansion boards 11 3 1 3 Power supply 11 3 2 S W versions 12 3 3 Documents 12 3 4 Applications 12 3 5 PCS W 12 4 Control Unit 13 5 LED indicators and push buttons 15 6 Th
58. Quiet alarm 0 8 5 sec Fault continuous Disablements and Faults 1 sec directly after the door to the c i e is closed Activated interlocking input 0 8 0 8 sec if this option is selected via WinG3 Press Silence buzzer P1 to silence the buzzer In case of a new alarm pre warning co incidence alarm etc or if the push button Silence buzzer is pressed again the buzzer will automatically sound again Silence buzzer by open door In WinG3 can the function Silence Buzzer by Door Switch be selected The buzzer will then be turned off as long as the control unit door is open This function is a violation to the EN54 2 standard EBL512 G3 c i e type no 5001 This unit has no front and no built in buzzer 8 Incl Heavy smoke heat alarm AA alarm Key cabinet alarm and Acknowledged alarm New Zealand only 28 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 11 Disable Re enable all control extinguishing and ventilation outputs All control outputs programmed as type e Control general e Fire ventilation e Extinguishing system can via menu H2 B7 be collective disabled for one several or all control units This is indicated by LED Fault Disablements General disablements L10 They will remain disabled until they are re enabled again via menu H2 B7 See also chapter Disable re enable output type H2 B7
59. SERVICE signal H4 U5 When SERVICE signal is generated in the system following symbol is shown in the display s symbol area Lp Regarding the SERVICE signal levels see Planning Instructions chapter SERVICE signal Menu H4 US is a list of the sensor s activating SERVICE signal NOTE SERVICE signal is only information that the sensor has to be replaced with a new clean sensor soon The SERVICE signal has to be acknowledged see chapter Acknowledge SERVICE signal H8 S3 page 126 Menu According to chapter Access see page 78 Scroll to menu H4 H4 Present system status U1 Disablement U2 Disablement by time channel U3 Open doors U4 Sensor values U5 Sensors activating SERVICE signal U6 Event log U7 Information Scroll to menu US U5 Sensors activating SERVICE signal Sensor ZZZ AA technical address xxxxxx needs A list in which you can service scroll with VW or A asi If printer 5058 is a mounted the soft key Print will be visible else not Press Print for a print out If there are no sensors having generated SERVICE signal when is pressed the list view will not open ESC U5 Sensors activating SERVICE signal Scroll to another menu or press ESC 7 6 Event log H4 U6 Three event logs are available 1 Alarm log only alarm events e g fire alarm fire alarm reset etc 105 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system E
60. Scroll to menu H10 H10 Change access code for daily duties nn Access code l New code Verify KKK Enter the old code the Access code The digits are replaced by new code and the new New code Verify ah in the display code again Incorrect access code NO change MEORE EKE ACInOT correct Try again H10 Change access code for daily duties The access code was correct and is now changed to the new code Scroll to another menu or press ESC X NOTE After change of access code it is recommended do Safe shutdown of the control unit see menu H8 S8 This will save the SSW data e g the new code in a Flash ROM see page 131 If the valid access code is unknown a back door code is available 144 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 34 Annual control The building occupier is highly recommended once a year to do some tests beside the monthly tests To avoid the Fault tx output s to be activated they can be disabled via menu H2 B9 or via an open door se chapter Open door page 31 Regarding the fault condition see chapters Fault page 47 and Fault messages page 48 NOTE Most of the faults have a delay Each control unit should be tested as follows e Perform monthly test menu H1 e Remove one battery fuse e g F2 on the Main board 5010 The following fault message is to be shown FAULT Batt
61. This page has deliberately been left blank Panasonic Panasonic Electric Works Nordic AB Jungmansgatan 12 SE 211 19 Malm Sweden Tel 46 0 40 697 70 00 Fax 46 0 40 697 70 99 info fste eu pewg panasonic com www panasonic fire security com ISO 9001 NATIONAL AOCREDITATION OFCERTIFCATION BODES
62. V1 0 x eS eG Fire Alarm Zone 002 Address 03 SMOKE YY MM DD hh mm User definable alarm text if progr Reset of the fire alarms see chapter Alarm reset page 44 15 2 1 Enter the menu during fire alarm By pressing the soft key Menu P4 during fire alarm you will get access to the menu system see Access page 78 In this case a part of the display s alarm window will be temporarily suppressed to permit the display of the menu system First alarm 002 03 Alarm number 1 of 10 Latest alarm 003 11 4 zones in alarm menu H2 Disable or re enable H3 Set calendar and clock H4 Present system H5 Service H6 FAULT acknowledge H7 Perform zone test Test mode H8 Maintenance H9 Interlocking outputs and inputs H10 Change access code for daily duties Esc menu Next zone The normal alarm window will be automatically displayed again after the menu system is escaped or 20 seconds after the latest manoeuvre in the menu system The alarm window will also be automatically displayed again if any of the soft keys Esc menu P4 or Next zone P5 is pressed or push button Alarms queued P8 38 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 15 3 Heavy smoke alarm Heavy heat alarm An analog detector can activate a heavy smoke heat alarm for a higher alarm level than the normal fire alarm level i e a normal fire alarm is al
63. able interlocking output Scroll to menu C2 C2 Activate interlocking output a Activate interlocking output Write the area number and area oo point 00 point d press Press a C2 Activate interlocking output Scroll to another menu or press ESC 140 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 32 3 Reset interlocking output H9 C3 All activated interlocking outputs are listed in this menu If the interlocking output is activated via its programmed control expression and with latching output selected in WinG3 the output has to be reset via this menu If the interlocking output is activated via its programmed control expression and with latching output not selected the output can be reset via this menu If the interlocking output is activated via menu H9 C2 the output has to be reset via this menu Text in display Comments Menu According to chapter Access see page 78 Scroll to menu H9 H9 Interlocking outputs and inputs a C2 Activate interlocking output C3 Reset interlocking output C4 Disable interlocking output C5 Re enable interlocking output Scroll to menu C3 C3 Reset interlocking output Ya Reset interlocking output Menu C3 is a list in which area Mot point 10 you cn scroll If there are no activated outputs menu area 001 point 11 baa area 001 point 12 Meor Open 66 Press 4 to reset
64. access code and to accept a menu and accept input of data Left right keys are used to move the cursor in a menu Up down keys are used to scroll between the menus Numeric keys for the figures 0 9 Used to clear delete just written data Used to stop input of data leave a menu one step up and to 18 Panasonic Electric Works Nordic AB MEWO01163 6 Operating Instructions Fire alarm system EBL512 G3 V1 0 x The display LCD 6 1 Symbol area Information area Soft key area 6 2 Areas in the display Next zone The display is divided in three areas e The symbol area Some events are indicated with symbols see 6 2 below e The information area General area for all kind of information and the menu system e The soft key area The function of a soft key is shown in this area The function of a soft key may vary depending on the situation If nothing is shown the soft key has no function for the moment The symbol area The symbol area is at the top of the display see 6 1 above The symbol area Symbol Indicating Door open Any c i e door in the system is opened See also page 31 Also valid for ext FBPs Loss of mains Any c i e or ext power supply in the system is out of 230 V AC The week average sensor value is over the service level for one or more analog smoke detectors in the system See also page 105 Note that the symbol area may be suppressed see 6 3 19
65. be nS visible else not Press ree Print for a print out If there are no open doors when lt is pressed the Soen th list view will not open ESC U3 Open doors Scroll to another menu or press ESC 101 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 27 4 Sensor values H4 U4 The very first week average sensor value is calculated within 2 minutes after SSD download amp restart During these 2 minutes can no fire alarm be activated and the sensor value 000 will be shown The Performance factor and Min Max values are updated each night 00 00 i e the values shown are from the previous day Menu According to chapter Access see page 78 Scroll to menu H4 H4 Present system status wa U1 Disablement U2 Disablement by time channel U3 Open doors U4 Sensor values U5 Sensors activating SERVICE signal U6 Event log U7 Information Scroll to menu U4 U4 Sensor values Wl n Start sensor fooo00 Write the technical number and or press lt to start as from sensor 000001 a When lt is pressed the sensor values will be shown in the A list in which you can display An examples which shows the values from an analog scroll with Y or A multi detector 4300 and an analog heat detector 3308 If printer 5058 is mounted the soft key Print will be Sensor 001 01 technical address 000001 visible clecmict
66. board 5010 106 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x MMI board version The S W system program version of the MMI board 5011 Alarm counter The alarm counter is increased with 1 every time the c i e enters a real fire alarm condition Fire alarm indication in the display LEDs Fire are lit and the c i e buzzer is sounding i e not for zones in test mode It starts on 000 and goes to 999 It can be reset to 000 via WinG3 Control unit menu Reset alarm counter It is stored in an EEPROM i e the value will be retained also after the c i e has been de energized Max number of allowed alarm points that can be used in this control unit i e 128 256 or 512 Note that max number of COM loop addresses is always 1020 Convention Different countries have different conventions i e country specific functions default settings etc The convention is set in conjunction with the installation of WinG3 The convention can if required be changed via WinG3 Serial number The manufacturer s serial number year month number Installation name As written in the WinG3 dialog box System Properties Name Date and time when the site specific data SSD was downloaded Control unit number 00 29 Menu According to chapter Access see page 78 Scroll to menu H4 H4 Present system status U1 Disablement U2 Disablement by time channel
67. c Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 31 6 Test of alarm devices H8 S5 The programmable outputs of type Alarm device can be collectively activated via this menu H8 S5 which makes it possible to test the alarm devices The test cannot be started if a fire alarm already is activated in the system One or all control units can be selected When the test starts the alarm devices will sound continuously steady for approx 5 seconds be silent for approx 25 seconds sound for approx 5 seconds and so 53 on NOTE Also disabled and silenced alarm devices will be tested The test will continue for one hour if not stopped via this menu H8 S5 or if a fire alarm is activated in the system Menu Procedure according to chapter Access code for service maintenance H5 and H8 see page 110 S2 Re connect loop zone line input S3 Acknowledge SERVICE signal S4 Clear weekly average S5 Test of alarm devices S6 Safe shut down of control unit S7 Activate address in alarm mode S8 Synchronize the control units S9 Change code for service maintenance 10 Change code for PC communication Scroll to menu S5 S5 S5 Test alarm devices 222 alarm devices ee Test alarm devices control unit Ho All Write control unit number or press P i e select AJl Press lt to start the test Including Addressable siren 3377 and Addressable
68. c Electric Works Nordic AB MEWO01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 4 Control Unit Figure 1 EBL512 G3 Control Unit 5000 with printer The look _ might vary according to configuration country etc Depending on country convention configuration etc the look language and functions might vary Figure 1 shows an EBL512 G3 with an English front EBL512 G3 is housed in a grey metal cabinet The door has a Plexiglas ahead of the front and display see Figure 1 A key is required to open the door to get full access to the push buttons on the front i e the Fire Brigade Panel FBP and the Control Panel CP 13 Panasonic Electric Works Nordic AB MEWO01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Fire LI gt e L2 gt L Enouening je P1 Silence L3 gt a Ventilation aad am lt L4 Do Febr gt brigade be Silence alarm devices Ls gt a gt ol lt L6 en Taree P4 P7 a P8 Alarms queued Panasonic Fire Alarm Technology L7 L8 gt H System fault z Testmode E I L9 L10 gt F General fault Ll 1 L12 gt CH Alarm devices General disablements ESEA HA L13 L14 gt of rannan H Femen COEL o Esc _ Figure 2 The EBL512 G3 front with display FBP upper part and CP lower part The look might vary according to language An English front is shown in the figure See also chapter LED
69. can take place The PC has to be connected to the USB port type B in a control unit Start WinG3 Log on to the control unit access code for level 3B shall be entered via the PC WinG3 In WinG3 menu Tools Download SSD you select the unit s to which the SSD shall be downloaded For security reasons the SSD i e the installation will be automatically saved after the download Check All Loop Units In the WinG3 COM loop icon pop up menu select Check Loop This function can be used after or before the download of SSD The function is as follows The control unit will find all units that are connected on the COM loop The addresses 1 255 will be reported to WinG3 For all units the address and the type of unit will be reported All differences compared to the WinG3 SSD will be listed in WinG3 and can be saved and or printed out NOTE During this check the COM loop will be disconnected disabled and no alarms or faults can be activated Disconnected COM loop is indicated by the LED Fault Disablements General disablements L10 Single Control Unit Start the downloading from WinG3 A text message will be shown in the control unit display Downloading SSD When the download is completed the control unit will restart see chapter Restart page 74 After the restart another text message will be shown in the display FAULT Restart control unit nn code 03 YYYY MM DD HH MM If the download was
70. ce Smoke detectors sensors are influenced by their environment and become dirty In an analog system like EBL512 G3 a Service signal is given when it is time to exchange the smoke detectors sensors to new ones The alternative is to exchange detectors at given periods to be on the safe side Change in activities or wrong choice of detector If the activities in the premises are altered the detector choice might also need to be altered Due to special environments see above an in appropriate detector type might have been chosen from the beginning and thus cause unnecessary alarms Miscellaneous Choosing another type of detector can solve certain problems Bear also in mind that the coverage area can be different for different types of detectors It is however not always the best action to change detector type Here is a list of other actions programmed via WinG3 which can be used e Another alarm algorithm can be used e g during working hours e Alarm delay for smoke detectors sensors can be used e Two zone or two unit dependent co incidence fire alarm activation can be used e Inan installation with addressable detectors sensors e g EBL512 G3 the affected detectors can be individually disabled or whole zones for temporary work in the premises Bear in mind that the smoke spreads and consideration must be taken to adjacent detectors zones Disablements can be done automatically via a time channel
71. ce page 42 Quiet alarm reset Quiet alarms are non latching i e they will be automatically reset when the alarm point zone is no longer above alarm level Outputs activated by quiet alarm will be de activated In some cases after a programmable delay time 46 Panasonic Electric Works Nordic AB MEWO01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 17 Fault All faults are delayed in order not to generate any unnecessarily faults e g for COM loop and zone line input faults the delay time is approx 45 seconds In case of a fault condition the following will happen in the control unit e The buzzer in the c i e will sound continuously steady e The fault condition output for routing equipment Fault tx will be activated e Programmable output s for general fault will be activated and output s for general charge fault might be activated e LED Routing equipment Fault tx activated L13 will be turned on indicating that the fault condition output for routing equipment Fault tx is activated e LED Fault Disablements General fault L9 will be turned on e LEDs Fault Disablements Alarm devices L11 System fault L7 and or Fault Disablements Fire brigade tx L12 might be turned on as well e A fault message incl date time and status will be shown in the c i e display Example fault message FAULT No reply zone xxx address xx technical number xxx
72. cess code for service maintenance H5 and H8 see page 110 a A2 Sensitive fault detection mode A3 Service mode for COM loop A4 Display current consumption in unit A5 Display current consumption on COM loop A6 Display statistics for communication A7 Activate address setting mode for DU Scroll to menu A7 A7 Activate address setting mode for DU a Activate address setting mode for DU Write control unit number Control unit o0 display unit 00 All and the unit s address or select press P All i e all display units on the selected control unit a Scroll to another menu or press ESC The address is thereafter edited in the display unit DU respectively 119 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 29 FAULT Acknowledge H6 Regarding fault indication etc see chapter Fault page 47 See also chapter Fault acknowledge page 63 All faults i e not acknowledged faults acknowledged faults and corrected faults are stored in the event log and can be listed see chapter Event log H4 U6 page 105 In menu H6 can up to 300 faults not acknowledged and not corrected faults be listed Menu According to chapter Access see page 78 Scroll to menu H6 H6 Acknowledge FAULTS f Some examples of fault messages This is a list in which you can scroll The most FAULT Low battery capacity control unit oe Poe 00 ms H
73. ch outside switch is turned on in control unit no xx i e from not activated to activated state FAULT Fire brigade panel xx COMCOIL UNIE sox FBP 1826 1828 Ext Fire Brigade Panel The ext FBP xx connected to control unit no xx is programmed as another type in the SSD or a fault in the unit FAULEs Puse on COMO Ooms Control unit xx Blown fuse F15 Loop 0 F16 Loop 1 F17 Loop 2 or F14 Loop 3 on the main board 5010 in control unit no xx Fuse T1 6A L 250V TR5 NOTE The fuse shall not be replaced The main board 5010 shall be replaced since more components are broken as well PAULUS Tapt x COMICIe O l wMLE xx A fault on the supervised input x in control unit xx Check the cables connections cut off or short circuit 53 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x FAULT Input x expansion board x Control unii A fault on the supervised input x on the expansion board 4583 with address x in control unit no xx Check the cables connections cut off or short circuit FAULT Interlocking input AAA PP An interlocking input is not activated within the time set for fault activation 5 255 seconds The time is counted from the activation of the output in the interlocking combination area AAA point PP PAUL S Internal short Circuit COM looa x COMEZOL wmit xox Short circuit on the connection ribbo
74. ctivated fire alarm is reset when it still is in alarm status it will activate a new fire alarm within 20 seconds In accordance with the EN54 2 standard When Single with automatic disablement reset is performed an alarm point or zone still in alarm status will not only be reset but also disabled i e it will not activate a new fire alarm within 20 seconds It has to be re enabled via menu H2 B5 before it can activate a new fire alarm This function set via WinG3 is a violation to the EN54 2 standard LED Fault Disablements General disablements L10 is indicating one or more disablements in the system NOTE When All or Single reset is used automatic disablement encapsulation function can be used by pressing Reset P3 and approx 0 1 sec later also press Alarms queued P8 and hold them pressed for gt 0 5 sec The alarm point or the whole zone conventional currently shown in the middle of display with large digits will be reset and disabled Heavy smoke heat alarm reset If a heavy smoke heat alarm has been activated it will be reset at the same time as the corresponding fire alarm is reset Also the output s will be reset i e de activated Alert Annunciation Regarding the function see chapter Alert Annunciation alarm AA alarm page 40 and EBL512 G3 Planning Instructions chapter Alert annunciation Reset of the AA alarm s can be done via push button Reset on an AA unit 173
75. ctric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x PAULUS CoOimcwOl Umi x lhucgia CwiceSinic consumption The control unit current consumption is gt 3 3A gt 6 5A in alarm state and because of this the battery charging is turned off and will be so until the current consumption has decreased to lt 3 3A lt 6 5 A again PAUL S Cirte Oitic loop x Control walt xx SCL iy lt gt SCI in This fault is indicating a cut off break on COM loop x or the COM loop voltage is too low at the end of the loop i e lt 12 V DC SCI n lt gt SCI n describes between which Short Circuit Isolators 4313 the cut off is located n A B 0 1 2 3 4 5 6o0r7 A amp B is the built in isolator in the EBL512 G3 A direction and B direction respectively i e if no SCI is used the information will always be SCI A lt gt SCI B If only one SCI is used i e 4313 no 0 the information will be SCI A lt gt SCI 0 or SCI O lt gt SCI B and so on If it is a single break cut off on the loop there will be no other fault messages If there are several breaks on the loop the message shows the last isolator before the break in the A direction incl the following isolator There will also be a FAULT No reply message for each unit that EBL512 G3 cannot find and FAULT Several faults NOTE Each 10 minute a new attempt is made to communicate in one directio
76. d download of site specific data and or download of software Access level 4 Used by manufacturer or by personnel authorised by the manufacturer when a PC is to be connected to the control unit i e when WinG3 is to be used for re initialisation of the alarm counter change software configurations on line status checking etc 25 Panasonic Electric Works Nordic AB MEWO01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 8 Silence Alarm devices In the control unit front the FBP part there is a push button Silence alarm devices P2 When the alarm devices are activated sounding and the push button Silence alarm devices is pressed the following will happen e The activated outputs programmed for sounders type Alarm devices will be turned OFF de activated If the push button Silence alarm devices is pressed again the sounders will automatically sound again In case of a new alarm Fire alarm Co incidence alarm or Pre warning the sounders will automatically sound again In WinG3 the function Silence Switch Disables Alarm Devices can be selected In this case the button Silence alarm devices P2 will have the same function as the menu Disable re enable alarm devices H2 B8 See also chapter Disable Re enable alarm devices page 27 System Name System User definable text Paget Paez Ss V Latch Faults Silence B
77. d during operation i e week average sensor values access codes calibration values and event logs in control unit no xx e If the C U was made powerless i e mains and battery disconnected without first doing a Safe shut down of control unit via menu H8 S6 see page 131 this fault might be generated when the C U is powered again After fault acknowledge the SSW will get default values and the fault will be corrected serviced Supervised outputs have to be calibrated via menu H5 A1 e Some external influence has caused a fault in the SSW This is very serious Call for service personnel engineer 58 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x FAULT IRAGIEBIEIE COiMewol unic ina code xx address yyyyyyyyyy Control unit restart has occurred in control unit no nn See also page 74 xx 00 Power up Restart Power supply connected xx 01 Watchdog Reset xx 02 Accidental jump to reset vector xx 03 Restart after SSD Software text file download xx 04 19 Unexpected interrupt xx 20 S W monitoring fault NOTE xx 00 and 03 are normal Acknowledge the fault xx 01 02 or 04 20 appearing often call for service personnel engineer yy y memory address before restart Write down the address and inform the service personnel engineer BAULUS Shore Cirouit loco x Concrol unit xx SCInn lt gt SCInn SCI nn lt gt SC
78. d output will stay in or return to the normal condition for the output respectively Disabled outputs via menus H2 B7 B9 are not limited and must not be counted Up to 200 Interlocking outputs can be individually disabled via menu H9 C4 It is not possible to exceed the limits A warning will be shown Max disablements reached Disablement not performed Don t forget to re enable via menus H2 B4 B9 H8 S3 H9 C5 or use automatic re enablement for zones and alarm points Disablements are indicated by LED Fault Disablements General disablements L10 and are also shown in the display An example Zone 001 is disabled Zone 002 is disabled More is indicating more disablements NOTE See chapter The information area priority order page 20 regarding priority order Disablements and faults are indicated by a 2 sec beep when you close the control unit door 83 Panasonic Electric Works Nordic AB MEW01163 25 1 Menu Scroll to menu H2 n lt n Write the zone number e g 001 n lt n Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Disable zone H2 B1 When a whole zone is disabled all alarm points within the zone are disabled except the addressable manual call points This function can depend on convention country Disabled zones are listed in menu H4 U1 from which it is also possible to get a print out According to chapter Access see page 7
79. de tx delay L14 the indications print outs actions etc are the same as for a normal fire alarm see above except for the c i e output for routing equipment fire brigade tx which will not be activated The AA alarm has to be acknowledged within an acknowledge time and reset within an investigation time otherwise the output s for routing equipment fire brigade tx will be activated See EBL512 G3 Planning Instructions for more information regarding the AA function Acknowledgement and reset of the AA alarm can be done on an AA unit 1735 1736 or an AA controller 1740 See also chapter Alarm reset page 44 40 Panasonic Electric Works Nordic AB MEW01163 15 5 15 5 1 15 5 2 15 5 2 1 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Key cabinet alarm The fire brigade uses a key cabinet to store a key to the building One programmable input per c i e can be used to connect a key cabinet Key cabinet opened before a fire alarm If the key cabinet is opened before a fire alarm e g if somebody illegally breaks into the key cabinet a key cabinet alarm will be activated Example Key cabinet alarm xx Control Unit number 00 29 First alarm 000 00 Alarm number 1 of 1 Alarm from key cabinet control unit XX When printer is available the Key cabinet alarm will be printed like a normal fire alarm see above Key cabinet alarm is reset like a normal fire alarm see chapter Fir
80. dge SERVICE signal S4 Clear weekly average S5 Test of alarm devices S6 Safe shut down of control unit S7 Activate address in alarm mode S8 Synchronize the control units S9 Change code for service maintenance 10 Change code for PC communication Scroll to menu S9 s9 S9 Change code for service maintenance code for service maintenance o Access code l New code Enter the old code the Access code The digits are replaced by new code and the new New code Verify aa in the display code again Incorrect access code NO change The access code was not correct Try again ERC ChOCUC MAU CUruCc mE rhe access code was correct and is now changed to the new code Scroll to another menu or press ESC NOTE After change of access code it is recommended do Safe shutdown of the control unit see menu H8 S6 This will save the SSW data e g the new code in a Flash ROM see page 131 If the valid access code is unknown a back door code is available 137 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 31 11 Change code for PC communication H8 S10 As a protection against unauthorised personnel programming the system via WinG3 an access code level 3B amp 4 for PC connection is required For security reasons the default code should be changed NOTE This code requires eight 8 digits Text in display Comments Menu Pr
81. dged faults and or acknowledged but not corrected faults the LED Fault Disablements General fault L9 will be lit and general fault and maybe general charge fault output s are activated e Faults corrected faults and acknowledged faults are shown in the General event log menu H4 U6 64 Panasonic Electric Works Nordic AB MEW01163 18 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Commissioning an installation 18 1 18 2 Before you connect the power supply to a control unit all other cable connections shall be made Check once more that they are correct Single Control Unit 1 Take away the rectifier fuse F1 and the battery fuse F2 on the main board 5010 Connect the batteries to the main board 5010 terminal block J2 NOTE There shall be an in line fuses F on the cable between the batteries see drawing 512 G3 21 CAUTION RISK OF EXPLOSION IF BATTERY IS REPLACED BY INCORRECT TYPE DISPOSE USED BATTERIES ACCORDING TO THE INSTRUCTIONS Connect the rectifier to the mains 230 V AC NOTE It shall be connected to a household removable fuse for the fire alarm c i e only via a two way circuit breaker The mains cable shall be securely clamped and the wires shall be as Short as possible The mains safety earth ground shall however be longer than the other wires to ensure that it is the last to be disconnected if the mains cable clamp should fail
82. dress within the zone 00 Only the zone number will be displayed e g used for conventional zone line inputs 001 999 Zone number NOTE Zone numbers 001 999 can be used but not more than 512 alarm points and or zones can be used per c i e This is in accordance with the EN54 2 standard 12 Also in the Alert Annunciation Units and Presentation Units Display Units The presentation number or a user definable 40 characters text message can also be shown in the old type of display units connected to the COM loops 33 Panasonic Electric Works Nordic AB MEW01163 15 Operating Instructions Fire alarm system EBL512 G3 V1 0 x Alarm types 15 1 In case of a fire analog detectors sensors conventional smoke and or heat detectors manual call points and programmable inputs can activate fire alarm If somebody illegally breaks into a key cabinet this will also activate a fire alarm i e a key cabinet alarm A fire alarm could be an Alert Annunciation alarm i e the activation of the routing equipment fire brigade tx is delayed during an acknowledgement time and an investigation time respectively The analog detectors can also activate two other types of alarm i e Pre warning and Heavy smoke alarm Heavy heat alarm Two unit dependent addressable alarm points normally only smoke detectors and 2 zone dependent zones can activate a Co incidence alarm Quiet alarm is normally used on the
83. e Serial number Set number of alarm points 128 v Enter password Reed Wie 3 Click Read to get the data for the control unit you are connected to 4 Report the serial number to the producer in order to get the password 5 Write the new number of alarm points and the received password in the field respectively and click Write Follow the same procedure in each control unit Control Units in a TLON network All control units connected to a TLON network do not have to have the same max number of alarm points set 32 To upgrade the maximum number of alarm points a separate password is required The password will be unique for every upgrade and downgrade This password will be available from the producer after you have reported the serial number A special PC program with a hardware lock has to be used 73 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 22 Restart A restart will delete or not delete the data in EBL512 G3 Here follows an explanation of the different data abbreviations and a table showing how the data respectively is affected cold or warm restart FF Fire alarms and Faults D Disablements FFD Fire alarms Faults and Disablements SSW Sensor values access codes supervised output calibration values and event logs WASV Week Average Sensor Values SSD Site Specific Data i e
84. e C4 Disable interlocking output Scroll to another menu or alt press ESC ESC 142 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 32 5 Re enable interlocking output H9 C5 Disabled interlocking outputs are listed in menu H4 U1 from which it is also possible to get a print out Interlocking outputs Type Interlocking can be re enabled via this menu but not via menu H2 B6 If all interlocking outputs have been collectively disabled via H2 B7 they have to be re enabled via H2 B7 er Access see page 78 Tae C2 Activate interlocking output C3 Reset interlocking output C4 Disable interlocking output C5 Re enable interlocking output Scroll to menu CS C5 Re enable interlocking output Re enable interlocking output This is a list in which you aren ot point 01 can scroll If there are no area 004 point 01 disabled outputs menu C5 will not open Press lt to re enable the selected output Press ESC to menu C5 a a Re enable interlocking output Scroll to another menu or alt press ESC area 004 point 01 ESC 0 p 143 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 33 Change access code for daily duties H10 For security reasons the default code should be changed Access According to chapter Access see page 78
85. e alarm reset page 44 This alarm will also generate a fault message see chapter Key cabinet alarm reset page 45 It is indicated by LED Fault L9 NOTE The Fault tx output s will not be activated by this fault Key cabinet opened in conjunction with a fire alarm The fire brigade personnel can open the key cabinet if a normal fire alarm already is activated in the c i e without activating any key cabinet alarm or fault Restoring the key after a fire alarm When all fire alarms in the system are reset see chapter Alarm reset page 44 the key has to be restored into the key cabinet within 5 minutes If not a fault will be generated see chapter Key cabinet alarm reset page 45 41 Panasonic Electric Works Nordic AB MEW01163 15 6 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Co incidence alarm 2 address zone dependence The co incidence alarm function is programmed via WinG3 for the alarm points zones in question When only one zone or one zone address alarm point is in alarm status the c i e buzzer sounds 0 8 5 sec and there is a Co incidence alarm presentation in the display Note that LEDs Fire L1 are not indicating a co incidence alarm The co incidence alarm will be automatically Reset after 5 minutes i e if the zone alarm point is no longer in alarm status or via the Reset button P3 See chapter Alarm reset page 44 Example Co incidence
86. e exact look is convention language dependent One example EBL512 G3 Control Unit XX yyyy mm dd hh mm yyyy mm dd Date Year Month Day Control Unit XX 00 29 hh mm Time hour minute User definable system information User definable system installation information created and downloaded via WinG3 can be displayed in the middle of the display Two rows a 40 characters are available This information is shown in all control units in the system One example EBL512 G3 Control Unit XX Panasonic Electric Works Fire amp Security Technology Europe AB yyyy mm dd hh mm 21 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 7 Access levels EBL512 G3 has different access levels 1 4 for different kind of users Access levels 2 and 3 are divided in sub levels A B Access Access code Required action Users Action level password 1 N A Anybody Scroll browse Door closed through the queued alarms 2A N A Fire brigade key Fire brigade Fire alarm handling personnel 2B PERE Fire brigade key Building Installation handling access code for level occupier daily duties e g 2B or 3A installation monthly tests dis owner ablements etc 3A nae Fire brigade key Service Service access code for level maintenance maintenance 3A personnel commissioning etc 3B eke PC WinG3 Service Service connected PC
87. e display LCD 19 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 6 1 Areas in the display 19 6 2 The symbol area 19 6 3 The information area priority order 20 6 4 System information in the LCD 21 6 4 1 User definable system information 21 7 Access levels 22 7 1 Access level 1 23 7 2 Access level 2A 23 7 3 Access level 2B 24 71 4 Access level 3A 25 7 5 Access level 3B 25 7 6 Access level 4 25 8 Silence Alarm devices 26 9 Disable Re enable alarm devices 27 10 Silence buzzer 28 11 Disable Re enable all control extinguishing and ventilation outputs 29 12 Evacuate 30 13 Open door 31 13 1 Outputs for routing equipment Fire brigade tx and Fault tx 31 14 Technical number Presentation number 32 14 1 Technical number for COM loop units 32 14 2 Presentation number 33 15 Alarm types 34 15 1 Pre warning 34 15 2 Fire alarm 35 15 2 1 Enter the menu during fire alarm 38 15 3 Heavy smoke alarm Heavy heat alarm 39 15 4 Alert Annunciation alarm AA alarm 40 15 5 Key cabinet alarm 41 15 5 1 Key cabinet opened before a fire alarm 41 15 5 2 Key cabinet opened in conjunction with a fire alarm __ 41 15 6 Co incidence alarm 2 address zone dependence 42 15 7 Quiet alarm 43 16 Alarm reset 44 16 1 Pre warning reset 44 16 2 Fire alarm reset 44 16 2 1 All eee 16 2 2 Single 44 16 2 3 Single with automatic disablement 45 16 3 Heavy smoke heat alarm reset 45 16
88. e synchronised NOTE If you don t want to change anything press ESC instead of lt to return to menu H3 Menu According to chapter Access see page 78 Scroll to menu H3 WEER Eao Koo a YYWy MM DD hh mm The date amp time shown Tuesday was valid when this menu Wednesday was opened When Thursday required change the date Friday time and or weekday Saturday press Y or A to Sunday select the weekday The clock starts again as from the date time etc shown in the display when you press lt If no changes shall be done press ESC instead of van H3 Set calendar and clock Scroll to another menu or press ESC 4 The capacitor can supply the RTC for a couple of days When the power has been turned off it is recommended to check set the date and time in menu H3 98 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 27 Present system status H4 If printer 5058 an option for control unit 5000 is mounted it is possible to get a print out from menu U1 U7 respectively In this case the soft key Print P5 shall be used 27 1 Disablement H4 U1 This is a list of all disablements in the system Also alarm point s and or zones disabled via Single reset with automatic disablement encapsulation function see page 45 are shown in the list In this case a zone will be displayed as ZZZ 00 i e a zone numbe
89. ed Test mode fire alarm will be presented in all control Zone Address unit displays and all ext FBP displays and indicated 1 2 3 4 5 by the LEDs Fire L1 SMOKE and Fire brigade tx L4 This manually activated fire alarm has to be reset by the push button Reset P 1 zone in alarm Ea 134 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 31 9 Synchronize the control units H8 S8 After any control unit restart synchronization will start automatically Synchronization can also be started via WinG3 and via this menu H8 S8 The control units have to be synchronized when the following fault message is shown FAULT Control unit xx has wrong information During the synchronization there will be information displayed for all control units in the system U rotating clockwise Synchronization in progress for the control unit CU v Synchronization completed successfully for the control unit CU lt Blank gt Synchronization failed for the control unit CU Menu Procedure according to chapter Access code for service maintenance H5 and H8 see page 110 S2 Re connect loop zone line input S3 Acknowledge SERVICE signal S4 Clear weekly average S5 Test of alarm devices S6 Safe shut down of control unit S7 Activate address in alarm mode S8 Synchronize the control units S9 Change code for service maintenance S10 Change c
90. ensive tobacco smoking in conjunction with bad ventilation can cause a fire alarm Welding grinding cutting sawing amp drilling These kind of jobs cause smoke Carpet welding Welding of plastic carpets causes a smoke that can be almost invisible but it still influences the smoke detectors sensors Cooking fumes toasting amp candles It is not only normal smoke that influences smoke detectors sensors It is all kinds of combustion products caused by cooking frying grilling toasting etc Warning Be careful when smoke detectors sensors are mounted near close to such activities Special environments In certain premises a special environment can exist which can influence smoke detectors sensors and cause alarm It can be ions from plastics flour dust oil haze aerosols strong perfumes strong ventilation insecticides disinfecting sprays etc If many odd and unnecessary alarms occur the environment must be examined and perhaps other detector types have to be chosen Steam hot air Smoke and heat detectors are influenced by steam and hot air e g from an oven dry blower heater etc 149 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Exhausts Exhausts from cars trucks lift trucks lawn mowers etc influences smoke detectors sensors If windows and doors are open exhausts can slip in that way Lack of maintenan
91. er A SEa fault is indicated by serviced yon daha An acknowledged fault is FAULT No reply zone 045 address 06 indicated by acknow technical number 000005 ledged yyyy mm dd hhmm serviced To acknowledge a fault FAULT No reply zone 021 address 05 select it and press lt 4 technical number 000114 The selected fault has yyyy mm dd hh mm acknowledged a boarder around it FAULT Low battery capacity control unit A corrected serviced Ma 00 fault that is acknow yyyy mm dd hh mm acknowledged ledged will disappear from this list FAULT No reply zone 021 address 05 technical number 000114 yyyy mm dd hh mm acknowledged ESC H6 Acknowledge FAULTS Scroll to another menu or press ESC l When the list is empty i e when all faults are acknowledged and corrected you will automatically return to menu H6 120 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 30 Perform ZONE TEST Test mode H7 Normally zones are tested during the monthly test via menu H1 Via this menu H7 it is possible to perform the zone test solely In test mode only the alarm points are tested i e no outputs no sounders will be activated during the test Alarm devices can be tested via menu H8 S5 If a real fire alarm is activated by an alarm point not in test mode the normal fire alarm functions will be activated i e fire alarm presentation ou
92. ery not connected CU xx NOTE xx is depending on control unit xx 00 29 e Put back the fuse and acknowledge the fault menu H6 e Remove fuse F4 on the Main board 5010 The following fault message is to be shown FAULT Supervised output 0 CU xx NOTE xx is depending on control unit xx 00 29 e Put back the fuse and acknowledge the fault e Check the manual call points the glass Take required measures Use the manual call point test key to activate fire alarm e Check some control outputs Are they activated according to programmed control expressions 145 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 35 How to change paper in the printer When the paper roll is almost empty a red line appears on one edge of the paper Change the paper roll before it is completely empty Always have a spare paper roll on site paper width 58 mm Change the paper roll as follows e Read all instructions before changing the paper roll e Open the control unit door e Open the printer cover i e press the green illuminated release button in the middle on top of the printer front e Remove the remains of the old paper roll e Place the new paper roll in the printer Make sure that it unrolls in the proper direction like the old one e Pull out 50 mm paper and close the cover e Tear off the paper then press the Paper feed button to the right on top
93. et one by one NOTE This function is available only if it is set in WinG3 Press Reset P3 to reset the fire alarm currently shown in the middle of the display with large digits NOTE The push button has to be pressed for min 0 5 sec Output s programmed for that fire alarm alarm point zone will be reset i e de activated If more than one fire alarm is activated i e LEDs Alarms queued L6 are lit the next fire alarm in the queue will be shown in the middle of the display It has to be reset the same way as the first one When all fire alarms are reset LEDs Fire L1 and Alarms queued L6 are turned off If there are other conditions e g a fault condition the corresponding information will be shown e g a fault message for the priority order see chapter The information area priority order page 20 44 Panasonic Electric Works Nordic AB MEW01163 16 2 3 16 3 16 4 16 5 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x All outputs for fire alarm are reset i e de activated If a key cabinet is installed the key to the building has to be put back into the key cabinet within 5 minutes If not a fault will be generated and a fault message will be shown in the display see chapter Key cabinet alarm reset page 45 Single with automatic disablement Like Single reset but incl the so called encapsulation function Normally when an alarm point or zone having a
94. external power supply equipment which has a fault output connected to a programmable input in control unit Xx FAULT Extinguishing system Cr Ea Ea The fault is to be found in the extinguishing system which has a fault output connected to a programmable supervised input in the EBL512 G3 system in control unit no xx Also check the input connections FAULTS PaCtorty Sectings CONC rOL Unie zx The factory settings have been changed in control unit no xx e g because of some external disturbance The main board has to be replaced 52 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x FAUT Ean xx COiMEwOI wine xx The LED Fault is lit on a fan control module connected to control unit xx Fan no xx has been activated but the corresponding I O unit 3361 input has not been activated within 30 seconds Check the fan and the cables connections FAULT Fault warning routing equipment Control wins The fault is to be found in the Fault warning routing equipment A routing equipment fault output is connected to a programmable supervised input in the EBL512 G3 system in control unit no xx Check the input connections as well Normally used for German routing equipment connected to an expansion board 4583 input 0 FAULT FB Silence switch active Conco aLe sox Only valid in the New Zealand convention New Zealand FB Silence swit
95. ff the Fault tx output s will be activated Menu Procedure according to chapter Access code for service maintenance H5 and H8 see page 110 S2 Re connect loop zone line input S3 Acknowledge SERVICE signal S4 Clear weekly average S5 Test of alarm devices S6 Safe shut down of control unit S7 Activate address in alarm mode S8 Synchronize the control units S9 Change code for service maintenance S10 Change code for PC communication Scroll to menu S6 S6 S6 Safe shut down of control unit sd shut down of control unit ans Shut down control unit do Write control unit number Yes and press W i e select Yes i fe Ready for shut down break the power The SSW is now saved and a Automatic restart within xxx seconds the Main board and MMI board CPUs are at rest xxx will start at 300 seconds and countdown to 000 before You can now power off the the control unit will restart automatically control unit If not the control unit will restart automatically after 5 minutes 300 seconds Tf not a fault FAULT Read write site data SSW CU xx might be generated when you power up the control unit again 131 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Power off Power on FAULT Restart control unit nn code xx After a restart power on or address yyyyyyyyyy see page 74 there will after 5 min yyyy mm dd hh mm always be a faul
96. function will be disabled for the alarm points zones programmed for Alert Annunciation in spite of the time channel is on or if they are programmed to be continuously enabled The AA function will stay de activated disabled until re activated re enabled again via this menu Menu According to chapter Access see page 78 Scroll to menu H2 H2 Disable or re enable n lt n Disable zone address Disable output Re enable zone Re enable zone address Re enable output Disable re enable output type Disable re enable alarm devices Disable re enable routing equipment B10 De activate alert annunciation function Scroll to menu B10 B10 De activate alert annunciation function na Alert annunciation function NOMMEL Select Normal or Off Off B10 De activate alert annunciation function Scroll to another menu or press ESC 97 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 26 Set calendar and clock H3 The RTC component has a capacitor as a backup power supply Normally date day of the week and time only have to be set when the power is turned on the control unit for the first time If required the clock might be corrected so that the time stamps for fire alarms faults etc will be correct The calendar and clock can be set in any c i e for the whole system Every day at midnight the calendar and clock will b
97. h the rectifier voltage due to the battery condition backup duration etc The Service mode for COM loop is indicated by LED Fault Disablements General disablements L10 If you log off this menu the Service mode for COM loop will be terminated automatically NOTE If short circuit is detected when a COM loop is in service mode the loop will be disabled and a fault message will be displayed loop x Comitwol uni Eee SimOict Cieewict SCL A lt gt SCL B Independent of where on the loop the short circuit is situated Text in display Comments Menu According to chapter Access code for service maintenance H5 and H8 see page 110 ml A1 Calibration of supervised outputs Sensitive fault detection mode Service mode for COM loop Display current consumption in unit Display current consumption on COM loop Display statistics for communication Activate address setting mode for DU Scroll to menu A3 RESIA O CROAS al Service mode for COM loop 0 CU 00 Write COM loop number B Direction and control unit number Both then select A direction B direction or Both Press lt 4 113 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x E g COM loop 3 Service mode for control unit 03 COM loop 3 Press 4 ESC or Esc CU 03 and A Supplied from A direction only menu to terminate the direction service mode Maun
98. he alarm point will be automatically reset The printer if available will print out every tested alarm point Zone xxx Address xx Time HH MM A sensor in test mode will not be able to activate fault After 60 minutes or Zones in test mode You are no longer in menu 121 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Esc Menu 001 002 003 004 End test H7 but still in test mode NOTE See chapter The information area priority order page 20 regarding priority order When required Zones in test mode Press 4 to end test n n Menu code Scroll to menu H7 001 002 003 004 End test lt ESC H7 Perform ZONE TEST The LED Test mode L8 is turned OFF If more zones are to be tested continue as above If not scroll to another menu or press ESC NOTE_1 During the test the following information will be shown in all other c i e displays Zones in test mode 001 002 003 004 NOTE_2 If an alarm point e g a manual call point is in alarm state when the test mode is ended there will not be a fire alarm activated Instead the alarm point will be disabled and has to be re enabled again via menu H2 B5 NOTE_3 When the Fire door closing function is used the fire door will be closed when the detectors controlling the door are tested in test mode 122 Panasonic Electric Works Nordic AB M
99. he output respectively Disabled outputs are listed in menu H4 U1 from which it is also possible to get a print out Menu According to chapter Access see page 78 Scroll to menu H2 H2 Disable or re enable B2 Disable zone address Disable output Re enable zone Re enable zone address Re enable output Disable re enable output type Disable re enable alarm devices Disable re enable routing equipment B10 De activate alert annunciation function Scroll to menu B3 B3 Disable output a a Disable output type SRIAIRRIZ ILEI Select output type 3377 3379 S CU voltage output S0 S3 S R CU relay output RO R1 R Press lt to accept Expansion board a i Disable ooo output 0 Write the data for the Depending on the press lt output respectively selected type the P 7 Press lt 4 to accept i Disable 000000 priority output high h following will be 0 P YORE i m Regarding the 3377 AST amp shown ea 3379 ASB units Priority all output all will disable the high medium and low Disable CU do S 0 priority outputs for the press lt selected unit LED Fault Disab t Disable CU io R 0 OE R General disablements press Pon L10 will light up Disable control unit do exp board 0 output 0 Disable output type 361 3364 4364 Disable another output or 3377 3379 press ESC Scroll to S another menu or press R ESC Expansion board 87 Panasonic Electric Works Nordic
100. hould normally be replaced NOTE The battery check is performed every 12 hour i e it can take up to 12 hours until the fault status will be corrected FAULT Low voltage control unit xx System voltage lt 21 V DC in control unit no xx Check the power supply rectifier 5037 output voltage which shall be 24 V DC Replace 5037 if required FAULT Low voltage technical number xxxxxx System voltage lt 21 V DC in the external power supply unit 3366 Check the power supply rectifier 1537 output voltage which shall be 24 V DC Replace 1537 if required EPAUILIS Mains Control unit sox The fault is activated 1 300 minutes after e Loss of mains i e no 230 V AC Blown mains fuse Blown fuse F1 on main board 5010 Fuse T6 3A H 250V 5x20 mm ceramic FAULT Mains external power supply COnTrOL WMC Box This is valid for an external power supply equipment which has a fault output connected to a programmable input in the EBL512 G3 system The fault is activated 1 300 minutes after e Loss of mains i e no 230 V AC to the ext power supply equipment 2 The time is programmable via WinG3 Max 30 min according to the EN54 2 standard Default value depending convention 55 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x e Blown mains fuse e Check the programmable input connections FAULT Mains technical number xxxxxx
101. is activated NOTE Don t forget to turn off this mode after the commissioning Text in display Comments Menu According to chapter Access code for service maintenance H5 and H8 see page 110 ma A2 Sensitive fault detection mode A3 Service mode for COM loop A4 Display current consumption in unit A5 Display current consumption on COM loop A6 Display statistics for communication A7 Activate address setting mode for DU Scroll to menu A2 A2 Sensitive fault detection mode a Sensitive fault detection mode Oji Press lt to turn off or On select On and press lt to turn on the sensitive fault detection mode On A2 Sensitive fault detection mode Scroll to another menu or Taag press ESC 112 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 28 4 Service mode for COM loop H5 A3 This mode can be used when commissioning an installation and by maintenance The COM loop communication polling will be turned off but there is still voltage 24 V DC on the loop in the A direction only in the B direction only or in both directions at the same time A volt meter can be used e g to check the voltage voltage drop on different places on the loop or to find a single break on the loop It is recommended to do this check also when EBL512 G3 is power supplied via the backup battery only since the voltage can be up to 3 V lower compared wit
102. it see 1 6 above When all control units are powered the TLON network installation have to take place before the site specific data SSD can be downloaded see chapter Programming SSD download page 68 If you know that one or more of the control units are to be started up later do as follows In WinG3 create the SSD only for the control units that shall be connected now Wait to download the SSD until the TLON Network installation is ready In TLON Manager do the TLON Network programming for the project i e only the control units that shall be connected now When the TLON Network installation is ready download the SSD Later when one or more control units shall be added to the TLON Network Open the project in TLON Manager add the control unit s and install download it according to the separate TLON network documentation Open the SSD in WinG3 and add the control unit s and download the SSD to all control units TLON network installation A project a system with two or more control units is created in the PC program TLON Manager or has been created earlier A PC is connected to the modular connector J10 Network no 0 in the control unit main board 5010 Open the project in TLON Manager and install download the project see separate TLON network documentation In case of a redundant TLON system a PC is connected to the modular connector J11 Network no 1 and the same procedure is repeated fo
103. it 00 From rectifier xxxx mA Charging xxxx mA battery temperature xx C 2 or ESC A4 Display current consumption in unit Scroll to another menu or press ESC 115 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 28 6 Display current consumption COM loop H5 A5 The resolution is not very high i e the displayed values give only a rough idea of the current consumption The current consumption an average value for each COM loop can be displayed NOTE No or very small current consumption can not be presented correctly precisely Text in display Comments Menu According to chapter Access code for service maintenance H5 and H8 see page 110 a A2 Sensitive fault detection mode A3 Service mode for COM loop A4 Display current consumption in unit A5 Display current consumption on COM loop A6 Display statistics for communication A7 Activate address setting mode for DU Scroll to menu A5 A5 Display current consumption on COM loop a Display current consumption on Write loop number and COM loop a control unit 00 control unit number and press lt press lt 4 If the control unit don t exist or don t answer i Current consumption on COM loop 0 control unit The current consumption 00 is xxxx mA accuracy is 5 mA 2 or ESC A5 Display current consumption on COM loop Scroll to another menu or press ESC
104. it the control units etc from the other system If it is known from the beginning that two systems shall be one in the future it is possible to give the control units in the system respectively the final control unit numbers right from the beginning in order to get the correct technical numbers in the system documents NOTE Two or more presentation numbers Zone Address in the systems must not be the same Delete a Control Unit in a TLON network Physically disconnect the control unit This action will generate faults in the other control units Acknowledge the faults Open the current project in TLON Manager delete the control unit according to the separate TLON network documentation Open the SSD for the current system via WinG3 Delete the control unit and the units connected to it and download the new SSD according to chapter Programming SSD download page 68 8 It is not possible to merge two TLON Networks into one or copy one system and paste into another system 67 Panasonic Electric Works Nordic AB MEW01163 19 Operating Instructions Fire alarm system EBL512 G3 V1 0 x Programming SSD download 19 1 19 2 The PC program WinG3 is used for programming of the site specific data SSD and to download it into the EBL512 G3 control unit s and or 1728 1735 1736 1826 amp 1828 units When the units are running i e the power is turned on and the TLON network is running the SSD download
105. larm points are tested each month the whole installation will be tested after one year In test mode only the alarm points are tested i e no outputs no sounders will be activated during the test Alarm devices can be tested via menu H8 S5 If a real fire alarm is activated for example by an alarm point not in test mode the normal fire alarm functions will be activated i e fire alarm presentation outputs sounders activated routing equipment fire brigade tx activated etc See also chapter The information area priority order page 20 NOTE If the control unit door is left open the output s for routing equipment fire brigade tx might be disabled if set so in WinG3 There will be an automatic ending of the test mode one hour after the latest tested alarm point zone See also chapter Perform ZONE TEST Test mode H7 page 121 Menu According to chapter Access see page 78 PF H1 Perform monthly test Check that all LEDs light up Press J The buzzer in the C U sounds and all dots in the display are shown All All dots are lit up LEDs light up incl LEDs in units connected via I O Matrix board 4582 If printer 5058 an option for control unit 5000 is mounted it will print out Zones to be set in test mode 2 222 227 222 Start test 80 Panasonic Electric Works Nordic AB MEWO01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Write zone numbers
106. lowing happens in case of a fire alarm e The buzzer in the c i e sounds 0 4 sec each 0 4 sec 0 4 0 4 sec e LEDs Fire L1 are blinking 0 4 0 4 sec e Output for routing equipment Fire brigade tx and outputs type Routing equipment are activated e Outputs for fire alarm are activated e Inthe c i e display a presentation number zone address is shown for the first fire alarm e Inthe c i e display a user definable text message alarm text is shown if programmed e Inthe c i e display is also some additional information presented One alarm point activating fire alarm Example fire alarm zone 002 address 03 within zone 002 First alarm 002 03 Alarm number 1 of 1 Zone Address 002 03 svo User definable alarm text for 002 03 SMOKE after the presentation number is automatically added depending on the type of alarm point i e SMOKE HEAT MULTI or MCP S Outputs programmed for General fire alarm and outputs programmed for the activated fire alarm s 36 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x More than one alarm point activating fire alarm Example fire alarm zone 002 address 03 within zone 002 and nine other fire alarms in four different zones First alarm 002 03 Alarm number 1 of 10 Zone Address 002 03 svo User definable alarm text for 002 03 Latest alarm 003 11 4 zone
107. maintenance maintenance access code for level commissioning commissioning etc 3B engineer via WinG3 4 wees PC WinG3 Manufacturer Changing factory connected PC settings access code for level 3B and level 4 The access codes can be changed To change a code you have to use the valid code or use a code for a higher access level Retailers are informed regarding the default access code respectively 4 The c i e door is closed but the Plexiglas in the door is provided with a hole for access to the Alarms queued button P8 see Figure 1 page 14 Normally a person on site trained in order to perform monthly tests dis ablements etc 22 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 7 1 Access level 1 With the door closed anybody has access to the push button Alarms queued P8 to scroll browse through the queued alarms 7 2 Access level 2A A After the door has been opened Door open symbol E in the symbol field the user fire brigade personnel have access to the push buttons keypad to do the following Push Operation function button P Silence the buzzer in the c i e i P2 Silence all alarm devices sounders P3 Reset fire alarms see below NOTE Fire alarms are Fire alarm incl heavy smoke heat alarm Alert Annunciation AA alarm Key cabinet alarm Co incidence alarm if not reset
108. messages programmable outputs etc are created in the PC program WinG3 and also downloaded in EBL512 G3 with WinG3 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 2 18 Software S W System program The S W makes the control unit the microprocessor work It is factory downloaded but a new version can be downloaded in EBL512 G3 on site 10 Panasonic Electric Works Nordic AB MEW01163 3 Operating Instructions Fire alarm system EBL512 G3 V1 0 x Overview 3 1 3 1 1 The EBL512 G3 system EBL512 G3 is a microprocessor controlled intelligent fire alarm system intended for analog addressable smoke detectors as well as conventional detectors and manual call points Programmable control outputs and output units are available Up to 1020 addresses of which up to 512 can be alarm points can be connected to each control unit c i e EBL512 G3 is available in several types versions and configurations It can be connected to a TLON network a system with up to 30 control units Each control unit has access to all information Product type no Product name 5000 EBL512 G3 c 1 e with front and display 5001 EBL512 G3 c i e without front and display EBL512 G3 is designed according to the European standard EN54 part 2 and 4 The Swedish front conforms to SS3654 Printer The control unit EBL512 G3 type 5000 with PRN included in the article number
109. n c i e door is being closed Fault messages Below follows a list of all fault messages in alphabetical order There is also an explanation to each fault FAULT 24V for external equipment output x CGO MceeOl WALE X x l 4 xx 00 29 Check fuses F9 F10 F11 and F12 on the Main board 5010 in control unit no xx Fuse T4A L 250V TR5 PAULA S ZaW for roucing equilonent Control Check fuse F8 on the main board 5010 in control unit no xx Also indicated by LED Fault Disablement Fire brigade tx L12 blinking Fuse T500mA L 250V TR5 FAUCETS ZAV Obie OMIEOUNE WALE KR This is valid for the external power supply 3366 connected on the COM loop The output might be turned off or the current output limit 4A is exceeded FAULT AAU Sox CONL LOL UNIL XS AAU 1735 1736 Alert Annunciation Unit The AAU unit xx connected to control unit no xx is programmed as another type in the SSD or a fault in the unit PAULA 3 ASE COM LOCS x COMmceOl unie xx 48 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x ASF Addressable short circuit isolator 4313 This message is only shown when the control unit works in Sensitive fault detection mode menu H5 A2 Short circuit on the COM loop shorter faster than the normal time delay for a fault has occurred Can be used for commissioning maintenance purposes FAULT Battery charging C
110. n cable to or between the expansion boards 458x in the control unit xx EBL512 G3 HAULS Key Cabinet Control Unit sox The key cabinet has been opened without a prior fire alarm i e if somebody has opened the key cabinet illegally or The key cabinet has not been closed within 5 minutes after reset of all fire alarms in the system BAVERO OL O Technical number XXXXXX The unit xxx xx zone address is not all right i e the unit is out of order faulty The detector s built in self verification function has reported a fault status The unit has to be replaced FAULT Low battery capacity CGOmcerOl unie xx Battery in control unit no xx internal resistance gt 0 6 Q The battery might be too old Cables fuses etc for externally placed batteries might cause a voltage drop Check adjust the rectifier power supply voltage 24 V DC Check the charging voltage over the battery respectively 13 5 13 8 depending on the actual charging step 54 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x e Check the voltage over a disconnected battery fully charged gt 13 V e Inthe New Zealand convention only The battery charging is turned off 60 minutes every 24 hour A battery voltage lt 24 4 V during these 60 minutes will generate a fault If a fault is generated it will automatically be Serviced after these 60 minutes The battery s
111. n only When all breaks are repaired corrected the communication automatically returns to communicate in one direction only PAULE TSE Earth fault is detected in control unit no xx System voltage is normally 24 V DC 24 V to earth is normally 12 5 V O V to earth is normally 11 5 V Voltage to earth lt 3 4 V Earth fault minus Voltage to earth gt 18 3 V Earth fault plus Check all cables for damage etc The function of the control unit cannot be guaranteed Call for service personnel engineer 51 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x AUIS iaieicla ican Technical number xxxxxx Check all cables for damage etc connected to the unit FAUL EPU Sex CONCrOL Unit xox EPU 1728 Ext Presentation Unit The EPU xx connected to control unit no xx is programmed as another type in the SSD or a fault in the unit FAULT Expansion board x oaa aE O sox This is valid for the I O Matrix board 4582 no x connected on COM loop x 0 3 in the control unit no xx There is some internal fault on the board which has to be replaced FAULT External fuses control unit xx The fault is to be found in the external power supply equipment which has a fuse fault output connected to a programmable input in control unit no xx FAULT External power supply Control unit xx The fault is to be found in the
112. n the following symbol is shown in the Set H display s symbol area See also chapter Open doors H4 U3 page 101 Outputs for routing equipment Fire brigade tx and Fault tx Via WinG3 the following can be programmed default settings shown Disable routing equipment by door switch None Open door in a C U or an ext FBP will not disable the output s for routing equipment Fire brigade tx and fault tx O Any control unit door Open door in any C U will disable the output s for routing equipment Fire brigade tx and fault tx in all C U s O Any door Open door in any C U or any ext FBP will disable the output s for routing equipment Fire brigade tx and fault tx in all C U s Disabled outputs for routing equipment are indicated by the LEDs Fault Disablements General disablements L10 and Fire brigade tx L12 and listed in menu H4 U1 31 Panasonic Electric Works Nordic AB MEW01163 14 Operating Instructions Fire alarm system EBL512 G3 V1 0 x Technical number Presentation number 14 1 Technical number for COM loop units The technical number NNNNNN is used when programming all units connected to the COM loops Technical number is also used to identify which unit has generated a fault NN N NNN 001 255 The address on the COM loop The addresses don t have to be in sequence The connections on the COM loop don t have to be in sequence The address is
113. ne address H2 B5 Disabled alarm points zone addresses are listed in menu H4 U1 from which it is also possible to get a print out Alarm point s and or zones disabled via the Single reset with automatic disablement encapsulation function see page 45 have to be re enabled via this menu A zone will be displayed as ZZZ 00 i e zone number and address 00 Re enabling via this menu has higher priority than automatic re enabling When all zone addresses have been re enabled The LED Fault Disablements General disablements L10 will be turned OFF if there are no other disablements in the system Menu According to chapter Access see page 78 Scroll to menu H2 H2 Disable or re enable a Scroll to menu B5 B2 Disable zone address Disable output Re enable zone Re enable zone address Re enable output Disable re enable output type Disable re enable alarm devices Disable re enable routing equipment B10 De activate alert annunciation function B5 Re enable zone address Re enable zone address lo 02 If there are no zone zone address 002 01 addresses to re enable zone address 006 03 menu B5 will be shown zone address 073 01 again The disabled zone addresses will be shown in alist Use Y or A to select the zone address and press lt Re enable zone address 02 01 Re enable another zone zone address 006 03 address or press ESC zone address 0
114. ne or Quiet Alarm Zone Address The Fan control panel 4593 can be used for control of up to eight fans 43 Panasonic Electric Works Nordic AB MEW01163 16 Operating Instructions Fire alarm system EBL512 G3 V1 0 x Alarm reset 16 1 16 2 16 2 1 16 2 2 Pre warning reset Pre warning is automatically reset Fire alarm reset NOTE The detectors having activated fire alarm shall after reset be inspected tested and replaced when required One of the following alarm reset alternatives is valid This is selected via WinG3 All is default All All activated fire alarms alarm points zones will be reset by pressing Reset P3 once This is in accordance with the EN54 2 standard NOTE The push button has to be pressed for min 0 5 sec When all fire alarms are reset LEDs Fire L1 and Alarms queued L6 are turned off If there are other conditions e g a fault condition the corresponding information will be shown e g a fault message for the priority order see chapter The information area priority order page 20 All outputs for fire alarm are reset i e de activated If a key cabinet is installed the key to the building has to be put back into the key cabinet within 5 minutes If not a fault will be generated and a fault message will be shown in the display see chapter Key cabinet alarm reset page 45 Single Each fire alarm alarm point zone has to be res
115. nts The following documents except this document are available e Planning instructions e Drawings Normally information found in one document is not to be found in another document i e the documents complement each other Applications The EBL512 G3 system is intended for small medium and large installations The intelligent control units offer the system designer and end user a technically sophisticated range of facilities and functions Programming PC S W WinG3 and TLON Manager and commissioning of the control unit system is very easy Start with one control unit and then when required add more units The TLON network makes it possible to install the control units in one building or in many buildings PC S W WinG3 is used for programming and commissioning of one or more control units e create download backup upload of site specific data SSD e download of S W settings conventions configurations C U amp system properties etc e create download the user definable text messages alarm texts shown in the display in the C U and ext FBP Display units WinG3 shall have the same or higher version number as the EBL512 G3 S W version number e g 1 0 x and 1 0 x respectively Backup require the same version number in WinG3 and in EBL512 G3 Old files can be opened and saved in a newer version of WinG3 and thereafter downloaded TLON Manager is used for the network programming 12 Panasoni
116. ocedure according to chapter Access code for service maintenance H5 and H8 see page 110 a S2 Re connect loop zone line input S3 Acknowledge SERVICE signal S4 Clear weekly average Test of alarm devices Safe shut down of control unit S7 Activate address in alarm mode Synchronize the control units Change code for service maintenance 10 Change code for PC communication Scroll to menu S10 S10 Change code for PC communication a Access code New code Verify Enter the old code the Access code The digits are replaced by new code and the new New code Verify seared xxx in the display code again Incorrect access code NO change The access code was not correct Try again S10 Change code for PC communication The access code was correct and is now changed to the new code Scroll to another menu or press ESC NOTE After change of access code it is recommended do Safe shutdown of the control unit see menu H8 S6 This will save the SSW data e g the new code in a Flash ROM see page 131 138 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 32 Interlocking outputs and inputs H9 32 1 Activated interlocking outputs inputs H9 C1 Text in display Comments Menu According to chapter Access see page 78 Scroll to menu H9 H9 Interlocking outputs and inputs ta C2 Activate interlocking ou
117. ode for PC communication Scroll to menu S8 S8 IS8 Synchronize the control units si the control units Start synchronization Press Y i e select Yes Yes Press lt 4 to start the synchronization 135 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Synchronization in progress CU00 CU10 CU01 CU11 U CU02 CU12U CU03 CU13 U CU04 CU14U CU05 CU06 CU07 CU08 CU09 After a few minutes Synchronization completed yyyy mm dd hh mm CU00 v CU10 v CU01 v CU11 v CU02 v CU12 v CU03 v CU13 v CU04 v CU14 v CU05 v CU06 v CU07 v CU08 v CU09 v During the synchronization the progress symbol for each control unit is shown In the example are CU15 amp CU16 not programmed Date and time for the latest completed synchronization The symbol v means that the synchronization succeeded If the symbol v is missing the synchronization has failed ESC S8 Synchronize the control units Scroll to another menu or press ESC 136 Panasonic Electric Works Nordic AB MEWO01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 31 10 Change code for service maintenance H8 S9 For security reasons the default code should be changed Menu Procedure according to chapter Access code for service maintenance H5 and H8 see page 110 S2 Re connect loop zone line input S3 Acknowle
118. og U7 Information Scroll to menu U2 U2 Disablement by time channel When lt is pressed the disablements will be shown in the A list in which you can display Some examples scroll with Y or A Zone XXX address XX disabled by time channel If printer 5058 is mounted Zone XXX address XX disabled by time channel the soft key Print will be abe visible else not Press see Print for a print out If there are no disablements when lt is pressed the list view will not open ESC U2 Disablement by time channel Scroll to another menu or press ESC 100 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 27 3 Open doors H4 U3 If any door in the system is open the following symbol is shown in the al display s symbol area a See also chapter Open door page 31 This menu is a list of all open doors in the system Menu According to chapter Access see page 78 Scroll to menu H4 H4 Present system status Mal U1 Disablement U2 Disablement by time channel U3 Open doors U4 Sensor values U5 Sensors activating SERVICE signal U6 Event log U7 Information Scroll to menu U3 U3 Open doors E When lt 4 is pressed the disablements will be shown in the A list in which you can display Some examples scroll with Y or A Door open control unit 00 If printer 5058 is mounted Door open FBP x CU xx the soft key Print will
119. onnect type Continue to disconnect or Zone line input press ESC to menu S1 Addr zone interface ESC LED Fault Disablements General disablements L10 will light up 123 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Scroll to another menu or press ESC Don t forget to re connect the loop zone line again via menu H8 S2 124 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 31 3 Re connect loop H8 S2 Disconnected disabled loops zone lines via menu H8 S1 are indicated by LED Fault Disablements General disablements L10 and listed in menu H4 U1 NOTE When you re connect a COM loop all the statistics shown in menu H5 A7 will be erased and set to 0 When all loops zone lines have been re enabled The LED Fault Disablements General disablements L10 will be turned OFF if there are no other disablements in the system Menu Procedure according to chapter Access code for service maintenance H5 and H8 see page 110 S2 Re connect loop zone line input S3 Acknowledge SERVICE signal S4 Clear weekly average S5 Test of alarm devices S6 Safe shut down of control unit S7 Activate address in alarm mode S8 Synchronize the control units S9 Change code for service maintenance 10 Change code for PC communication Scroll to menu S2 S2 Re connect S
120. ontrol unit xx The battery charging function is not OK The main board 5010 may have to be replaced FAULT Battery not connected CONTEOL WALE zx Battery voltage is below 18 9 V Batteries 2 x 12 V are missing or not connected correctly Fuse F2 on the Main board 5010 is blown Other battery fuse is blown This check is done every 14 minute i e after correcting the fault it might take up to 14 min until it disappears from the fault list Fuse T6 3A H 250V 5x20 mm ceramic FAULT Cables mixed COM loop x Control unit xx The two wires L SA and C SB for COM loop no x 0 3 in control unit no xx have been mixed alternated Check correct the wire connections FAULT Charging external power supply Control unit xx The fault is to be found in the external power supply equipment which has a charging fault output connected to a programmable input in control unit no xx FAULT Charging technical number xxxxxx The charging function in the external power supply 3366 connected on the COM loop The unit is not OK The p c b has to be replaced 49 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x FAULT Checksum fault in downloaded data Control unit will now restart A fault in the downloaded Site Specific Data SSD After the restart a new fault will be generated FAULT Site Specific Data SSD control unit xx A new SSD d
121. own a user definable alarm text if programmed See page 36 Each alarm point can have a unique text message Each zone can have a unique text message Each zone line input can have a unique text message The user definable text messages will be printed out when a printer is available See also chapter Fire alarm page 35 All user definable text messages up to 40 alphanumeric characters each are created and downloaded via WinG3 See Planning Instructions chapter User definable text messages 3 This is also valid for the Ext Presentation unit 1728 and the Alert Annunciation units 1735 1736 69 Panasonic Electric Works Nordic AB MEW01163 20 Operating Instructions Fire alarm system EBL512 G3 V1 0 x New system program S W version download 20 1 The latest software S W version of the EBL512 G3 system program is factory downloaded before the delivery Due to continual development and improvement different S W versions can be found The valid S W version for the Main board 5010 and the MMI board 5011 respectively can be read in menu H4 U7 system information or via WinG3 On site new S W can be downloaded via WinG3 See also the WinG3 help chapter help topic Download Software EBLS512 G3 type 5000 has both a Main board 5010 and an MMI board 5011 EBL512 G3 type 5001 has only a Main board 5010 On site new S W for the 1728 1735 1736 1826 amp 1828 units can be downloaded via WinG3 See
122. ownload will probably solve the problem FAULT Checksum MMI program GOMceOIL Unit xx A fault in the control unit xx MMI board 5011 software This is a very serious fault Call for service personnel engineer immediately FAULT Checksum system program Control unie xx A fault in the control unit xx Main board 5010 software This is a very serious fault Call for service personnel engineer immediately BAUL Control wait sox aas mo Comtacit WLL COMmerrOl Unle sx meitworK x network x network 0 or network 1 Can be shown in conjunction with new S W download e Check the TLON network cable connections e Faulty TLON connection board 1590 e The control unit has no power FAULTS Control unit xx has wrong information Can be shown in conjunction with new software download and or when commissioning a system This fault can be generated due to a bad TLON network i e communication problems One or more control units might have data stored that is not the same in all control units If a control unit restarts in conjunction with this fault a synchronization will start automatically otherwise a synchronization has to be started via menu H8 S8 or via WinG3 NOTE It is important that all control units that are supposed to exist SSD downloaded via WinG3 are running and are connected to the TLON network The TLON network programming has to be done It will take 90 120 seconds until this fault is corrected 50 Panasonic Ele
123. p A6 Display statistics for communication A7 Activate address setting mode for DU Scroll to menu A6 A6 Display statistics for communication Display statistics for control unit fo COM loop 0 Write control unit number and loop number and press W lt A No reply from control unit If the control unit don t exist or don t answer i 117 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Number of pollings nnnnnnn Note The values are not Parity fault 000000 00 0 live updated Number of bit faults 000000 00 0 No answer 000000 00 0 Bit length fault 000000 00 0 A6 Display statistics for communication Scroll to another menu or press ESC 118 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 28 8 Activate address setting mode for DU H5 A7 This function can be used by commissioning service engineer to activate the address setting mode in the following Display Units connected to the c i e e Ext Presentation unit 1728 e Alert Annunciation units 1735 amp 1736 e Ext FBPs 1826 amp 1828 A specific unit or all units connected to one c i e can be activated for address setting NOTE The units have to be in operation and in quiescent condition i e the units have to have an address already Text in display Comments Menu According to chapter Ac
124. page 92 29 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 12 Evacuate This function is only valid for the Belgian British Standard Hungarian Spanish and Ukrainian conventions When the soft key Evacuate P7 is pressed all outputs programmed for sounders type Alarm devices will be collective turned ON steady This is indicated by the following information in the alphanumeric display The sounders will remain turned ON until they are turned OFF by pressing the soft key Evacuate off P7 NOTE 1 The alarm devices sounders will always be activated steady sound continuously irrespective of the fact that the outputs can be set to anything else for fire alarm e g intermittent NOTE 2 The text Menu above the soft key P4 is visible in the display only if the door in the c i e is open while the text Evacuate Evacuate off above P7 is always visible in the current conventions Alt when a programmable input is activated One input per c ie 10 Alt when the programmable input is de activated 30 Panasonic Electric Works Nordic AB MEW01163 13 Operating Instructions Fire alarm system EBL512 G3 V1 0 x Open door 13 1 A special key is used to open the control unit door to get access to the front system The same type of key is also used to open the ext FBP door If any door in the system is ope
125. r and address 00 Disablements by time channels are listed in menu H4 U2 Menu According to chapter Access see page 78 Scroll to menu H4 H4 Present system status el U1 Disablement Press lt to show all U2 Disablement by time channel disablements in the system U3 Open doors U1 U4 Sensor values U5 Sensors activating SERVICE signal U6 Event log U7 Information If there are no disablements when lt is When lt is pressed the disablements will be shown in the A list in which you can display Some examples scroll with VW or A Zone XXX address XX disabled If printer 5058 is mounted Zone XXX is disabled automatic re enablement the soft key Print will be 3 visible else not Press Alarm points are disabled by time channel in CU XX Print for a print out pressed the list view will Esc menugj Print Esc menufl Print cree ESC U1 Disablement Scroll to another menu or press ESC 99 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 27 2 Disablement by time channel H4 U2 A list of all disablements by time channel s in the system NOTE All other disablements are listed in menu H4 U1 Menu According to chapter Access see page 78 Scroll to menu H4 H4 Present system status U1 Disablement U2 Disablement by time channel U3 Open doors U4 Sensor values U5 Sensors activating SERVICE signal U6 Event l
126. r the redundant network 27 The TLON connection board is mounted on the main board 5010 Network cable connections are made on the main board 5010 terminal block TA 66 Panasonic Electric Works Nordic AB MEW01163 18 3 18 4 18 5 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Add a Control Unit in a TLON network When adding a control unit to a running installation you have to have the same software S W version in all control units Often the new control unit has a newer version than the existing control units Normally the latest version is the best to use i e the control units in the running installation have to be upgraded As an alternative it is possible to download an earlier S W version in the new control unit Both alternatives are described in chapter New system program S W version download page 70 Open the current project in TLON Manager add one control unit and install download it according to the separate TLON network documentation Also see 18 2 1 above Open the SSD for the current system via WinG3 Add one control unit and the units connected to it and download the new SSD according to chapter Programming SSD download page 68 Make two TLON networks one It is very important that two or more presentation numbers Zone Address in the systems are not the same The system properties have to be the same Use one of the systems e g the largest and add to
127. ready activated by a detector activating a heavy smoke heat alarm Heavy smoke heat alarm is a confirmation on that the smoke or heat is heavy increasing and can be used for special actions e g activation of smoke ventilation etc The following happens in case of a heavy smoke heat alarm e Outputs programmed for heavy smoke heat alarm are activated e Each heavy smoke heat alarm is presented i e Heavy smoke or Heavy heat will be added to the normal fire alarm information First alarm 002 03 Alarm number 1 of 1 Heavy smoke Zone Address 02 03 SMOKE User definable alarm text for 002 03 LED Fault Disablements General disablements L10 is indicating that one or more zones alarm points are isolated disabled 17 See EBL512 G3 Planning Instructions S General heavy smoke heat alarm and individual alarm points zones 39 Panasonic Electric Works Nordic AB MEW01163 15 4 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x The printer if available will print each heavy smoke heat alarm e g Heavy Smoke Zone 002 Address 03 SMOKE YY MM DD hh mm User definable alarm text if progr Heavy smoke heat alarm will be reset when the fire alarm respectively is reset see chapter Alarm reset page 44 Alert Annunciation alarm AA alarm When the AA function is enabled indicated by the LED Routing equipment Fire briga
128. ric Works Nordic AB MEWO01163 2 Operating Instructions Fire alarm system EBL512 G3 V1 0 x Definitions Explanations 2 1 2 2 2 2 1 2 2 2 2 2 3 2 2 4 2 2 5 2 2 6 2 2 7 Definitions explanations abbreviations etc frequently used or not explained elsewhere in the document PEWN AB Panasonic Electric Works Nordic AB Alarm points Units which can generate a fire alarm in the control unit i e analog detectors sensors conventional detectors manual call points etc Smoke detector Analog and conventional photoelectric optical smoke detectors are available Sensor Sensor Analog detector Analog detector Contains an A D converter The Control Unit pick up the digital values sensor values for each detector individually All evaluations and decisions are then made in the c i e Analog detectors are addressable an address setting tool is used for detector types 33xx 430x An analog detector has to be plugged in an analog sensor base ASB Analog Sensor Base ASB A sensor is plugged in an ASB which is connected to a COM loop see below Conventional detector Detector with only two statuses i e normal and fire alarm The detector contains a closing contact and a series alarm resistor Normally plugged in a conventional detector base CDB see below connected to a conventional zone line input with an end of line device Some types are connected directl
129. rs have been acknowledged 127 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 31 5 Clear weekly average H8 S4 If a sensor analog smoke detector is replaced without having generated SERVICE signal its week average sensor value has to be cleared and set to the default value otherwise the new clean sensor will inherit the old sensor s value It is possible to clear the week average sensor value for each sensor individually via this menu NOTE First replace the sensor and then clear the week average value as soon as possible Authorised service personnel only must do this Used incorrectly it can cause nuisance fire alarms The first week average sensor value after clearing will be calculated within one hour then each week Menu Procedure according to chapter Access code for service maintenance H5 and H8 see page 110 S2 Re connect loop zone line input Acknowledge SERVICE signal Clear weekly average Test of alarm devices Safe shut down of control unit Activate address in alarm mode Synchronize the control units Change code for service maintenance 10 Change code for PC communication Scroll to menu S4 S4 Clear weekly average al Clear weekly average zone loo address 00 Write the wanted zone and press address and press lt S4 Clear weekly average Continue like above or scroll to another menu or press ESC 128 Panasoni
130. s in alarm Menu Next zone SMOKE after the presentation number is automatically added depending on the type of alarm point i e SMOKE HEAT MULTI or MCP User definable alarm text For each alarm point can an individual alarm text be shown if programmed or the default control unit alarm text if programmed For each zone it is an individual alarm text if programmed Up to 40 alphanumeric characters can be used Additional information First alarm Latest alarm Alarm number and number of zones in alarm LEDs Alarms queued L6 blinking 0 4 0 4 sec are indicating that more than one fire alarm is activated To scroll through the alarms use the push button Alarms queued P8 The fire alarms are stored in a circular buffer and when scrolling from the last to the first alarm the LEDs Alarms queued will be turned off for three seconds Next zone Use the soft key Next zone P5 to scroll through the zones in alarm When scrolling through the zones the first alarm point activated in the next zone will be shown The Next zone button will be available only if there are alarms in more than one zone The first alarm will be automatically displayed again 20 seconds after the latest time the Alarms queued or Next zone buttons where used The printer if available will print each fire alarm e g 37 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3
131. s in the c i e and it returns back to the c 1 e Control Unit C U C LE Control Unit Control and Indicating Equipment Unit to which the alarm points are connected via a COM loop Indicates fire alarm fault condition etc Fire Brigade Panel amp Control Panel see below included or not included Printer included or not included Fire Brigade Panel FBP Unit intended for fire alarm presentation etc for the fire brigade personnel Can be a part of the control unit front or a separate unit external FBP In the ext FBP a printer can be included or not included Control panel CP A part of the control unit front intended for the building occupier service personnel etc to communicate with the control unit system System Several control units connected via a TLON network co operating control units Panasonic Electric Works Nordic AB MEW01163 2 12 2 13 2 14 2 15 2 16 2 17 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Network TLON LonWorks Echelon Node TLON Conn board Gateway Sub net Backbone net Router Repeater Brief explanations to the words expressions to be found in connection with a network See also separate TLON Technical description TLON TeleLarm Local Operating Network a LonWorks based network for communication between several units nodes The protocol is LonTalk and the transmission works with doubly
132. sages alarm texts shown in the display in the control unit ext FBP and other Display units Via a PC and TLON Manager you can create and download install the TLON network configuration project 48 Connected to the USB connector above the front panel 2 Connected to the modular connectors J10 TLON network 0 or Jil TLON network 1 on the main board 5010 109 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 28 1 Access code for service maintenance H5 and H8 Access code to level 3A is required If login to level 2B was made with code for level 3A no code is required here Text in display Comments Menu According to chapter Access page 78 Scroll to menu H5 or MEIA H8 f H8 Maintenance a Access code If login was made with code for level 3A no code is needed Enter code for level Access code The digits are replaced 3A 4 digits with in the display NO ACCESS This info is shown if you enter a not correct access code Try again H5 A1 Calibration of supervised outputs The access code was Code for level 3A A2 Sensitive fault detection mode correct 4 digits A3 Service mode for COM loop Press lt or scroll to the A4 Display current consumption in control unit wanted menu and press A5 Display current consumption on COM loop maT A6 Display statistics for communication A7 Activate address setting mode for DU
133. sec depending on the situation If nothing is shown above the key in the display the key has no function for the moment Alarms queued grey Used when LEDs Alarms queued L6 are lit to scroll browse through the queued alarm points Function see chapter Fire alarm page 35 under LEDs Alarms P4 P7 Soft keys grey The operation function is shown above the key in the display i e the soft key area The function of a soft key may vary queued NOTE Fire alarms are Fire alarm incl heavy smoke heat alarm Alert Annunciation AA alarm Key cabinet alarm 16 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x LED indicators on the Control Panel CP LED indicator Indicating L7 System fault yellow EBLS512 G3 is not running because of S W CPU or memory fault L8 Test mode yellow One or more zones are in test mode see page 80 and 121 Fault Disablements L9 General fault yellow Fault s in the system i e not acknowledged fault s and or not corrected fault s See also page 120 General disablements Disablement s in the system i yellow Also valid for Single encapsulated reset see page 45 Alarm devices yellow Steady cont Output s type Alarm device are disabled Blinking One or more supervised outputs type Alarm device have generated fault s This is also valid when the c i e has no contact with a unit with such an o
134. shall fulfil UL94V 0 The batteries are normally maintenance free but the producer s instructions shall always be followed The ambient temperature affects the battery s capacity self discharge and life span The temperature should preferably not be higher than normal room temperature approx 20 22 C For highest safety the batteries used in a fire alarm installation should not be more than four years old CAUTION Risk of explosion if battery is replaced by incorrect type Dispose used batteries according to the producer s instructions and national regulations 148 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 38 How to avoid unnecessary nuisance fire alarms We all realise when life buildings production facilities etc shall be saved it is of utmost importance that an initial fire is detected as soon as possible That s why more and more automatic fire alarm systems are installed In an automatic fire alarm installation especially if smoke detectors sensors are used everybody in the building needs to be informed how to avoid so called unnecessary nuisance fire alarms To avoid trouble and unnecessary expenses there are a couple of things to bear in mind Here are some advice and tips Tobacco smoke The detectors sensors can not sense the difference between smoke and smoke They can not separate tobacco smoke from smoke from a fire Int
135. t generated The code will be 00 and the address 0 This fault has to be acknowledged see chapter FAULT Acknowledge H6 page 120 132 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 31 8 Activate address in alarm mode H8 S7 One alarm point zone address not a whole zone can be set in alarm The built in LED in the alarm point detector will be turned on to indicate the alarm NOTE All outputs standard and programmable which would have been activated by a real fire alarm from the same alarm point will now also be activated Menu Procedure according to chapter Access code for service maintenance H5 and H8 see page 110 S2 S3 S4 S5 S6 S7 S8 S9 Re connect loop zone line input Acknowledge SERVICE signal Clear weekly average Test of alarm devices Safe shut down of control unit Activate address in alarm mode Synchronize the control units Change code for service maintenance S10 Change code for PC communication Scroll to menu S7 S7 S7 Activate address in alarm mode address in alarm mode o Select zone doo address 00 Write the zone number and press address e g 123 45 Press lt 4 to start the fire alarm 133 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x First alarm 123 45 Alarm number 1 of 1 This manually activat
136. t A product has e atype number 5000 EBL512 G3 c i e Configured for 128 256 or 512 alarm points and with or without printer depending on article number 5001 EBL512 G3 c i e No front panel and no Plexiglas in the door Configured for 128 256 or 512 alarm points depending on the article number e an article number is often the same as the type no but a country code can be added e g SE for Sweden If the letters PRT also are added in the article number the product comes with a printer If digits are added to the article number they are showing the number of alarm points configured e g SOOOPRTSE 128 e a product name e g EBL512 G3 CU 128 alarm points with printer HW A HW e g a printed circuit board has e atype number e g 5010 e an article number often the type no and sometimes is a country code added e g 5010SE e aproduct name e g Main Board 128 alarm points e ap c b number e g 9290 3B and can also have a configuration e g CFG 2 and a revision e g REV 2 e sometimes a S W S W A S W has e aversion number e g V1 0 x Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x e sometimes additional information such as Convention different functions facilities Language Number of addresses etc PC S W A PC S W is a program used for programming commissioning etc It has a version number Panasonic Elect
137. terminated bus topology Echelon FTT 10 To connect a control unit to the network a TLON connection board is plugged in the control unit Old installations Some control units not prepared for network connection could be connected via a serial interface and a Gateway A network can be one sub net FTT 10 or several sub nets connected via routers In the TLON Network a sub net a channel Routers are also used to increase the maximum cable length node to node in a network All network programming configuration are made with the PC program TLON Manager LED LED Light Emitting Diode Yellow green or red optical indicator lamp External Indicator LED A unit with an LED Connected to an ASB CDB or a detector with a built in LED Old installations Also connected to an ADB Lit when the built in LED is lit Display LCD LCD Liquid Crystal Display Display in the c i e or Display unit for presentation of fire alarms fault messages etc a graphical monochrome LCD 320 x 240 dots and backlight Door open Door Key switch In EBL512 G3 there is a door switch which is activated when the control unit door is open In some other units this door switch is replaced with a key switch When the door is open a message Door is open in this unit is shown in the LCD Site Specific Data SSD The SSD is unique for each installation All alarm points presentation numbers user definable text
138. the Technical Description for the unit respectively Single control unit c i e In a single c i e shall not have a TLON connection board 1590 mounted When a c i e has a TLON connection board 1590 mounted it is expected to be one c i e ina TLON network and TLON network programming is required To download a new software system program version a PC and WinG3 are used The BIN file that shall be downloaded contains software for the main board 5010 software for the MMI board 5011 and a text file i e there is one BIN file for each language country 1 Connect the PC to the USB connector in the c i e and start WinG3 Inthe Tools menu select Download Software to open the dialog box and do the required settings Select the path and the software file name e g English_EBL512G3_100 BIN 100 version 1 0 0 Mark the checkbox Software to download both the main board and the MMI software Mark the checkbox Text to download the text file Mark the checkbox No MMI board if it is an EBL512 G3 type 5001 i e the MMI software and the text file will not be downloaded Select the COM port to be used on your PC 3 The text file contains all the text that will be shown in the c ie display Normally a new text file will come together with new software NOTE If only the text file shall be downloaded do not mark the checkbox Software 70 Panasonic Electric Works Nordic AB MEWO01163 Rev
139. tput C3 Reset interlocking output C4 Disable interlocking output C5 Re enable interlocking output Scroll to menu C1 C1 Activated interlocking outputs inputs a Interlocking area AAA point PP output active Menu C1 is a list in User definable text message if progr which you can scroll Depending on da hike activated output and or YYyy mMM ae soul II I RII Mele AOSD A Ate Set PAIN IO IIIS le Me Press ESC to menu input the following Interlocking area AAA point PP input output active C1 will be shown User definable text message if progr yyyy mm dd hh mm Interlocking area AAA point PP input active User definable text message if progr yyyy mm dd hh mm C1 Activated interlocking outputs inputs Scroll to another menu or press ESC 139 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 32 2 Activate interlocking output H9 C2 The output in each interlocking combination area point can be manually activated via this menu The corresponding interlocking input will be monitored in the same way as if the output was activated by its control expression Reset has to be performed via menu H9 C3 Text in display Comments Menu According to chapter Access see page 78 Scroll to menu H9 H9 Interlocking outputs and inputs a C2 Activate interlocking output C3 Reset interlocking output C4 Disable interlocking output C5 Re en
140. tputs sounders activated routing equipment fire brigade tx activated etc See also chapter The information area priority order page 20 NOTE If the control unit door is left open the output s for routing equipment fire brigade tx might be disabled if set so in WinG3 There will be an automatic test mode ending one hour after the latest tested alarm point Text in display Comments Menu According to chapter Access see page 78 Scroll to menu H7 H7 Perform ZONE TEST t lt Zones to be set in test mode H2 222 222 272 Zones to be set in test mode Press lt to start the test 001 002 003 Moo mode Write the zone numbers e g 001 002 003 004 a Zones in test mode LED Test mode L8 001 002 003 004 End test will light up Perform the tests The zone s will stay in test mode until the test mode is ended but after 60 minutes or if you press Esc menu you will be logged out from menu H7 Perform the test as quickly as possible since the output s for routing equipment fire brigade tx are disabled also the parts of the zones in test mode not visible for the test personnel are disabled In order to shorten the testing time any time delay for the detectors zones in test mode will be disabled i e fire alarm will be detected faster than normally In the tested alarm point the LED will light up and the LEDs Fire L1 in the c i e will light up approx 10 seconds then t
141. u H2 B5 NOTE_3 When the Fire door closing function is used the fire door will be closed when the detectors controlling the door are tested in test mode 82 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 25 Disable or re enable H2 A whole zone one or more alarm points within a zone and or control outputs can be disabled via menus H2 B1 B3 This possibility can be used when a temporary disablement is wanted e g craftsmen working in the premises etc The function Enhanced disablement is enabled as default i e disabled alarm points cannot activate Pre warning fire alarm or fault If this function is not enabled via WinG3 fault can be activated but not pre warning or fire alarm This is a violation to the EN54 2 standard Addressable manual call points can be disabled but shall normally not be disabled However when a whole zone is disabled the addressable manual call points will not be disabled for safety reasons This function can depend on convention country Up to 512 whole zones can be disabled via menu H2 B1 Up to 200 alarm points zones address can be individually disabled via menu H2 B2 and or COM loops zone interface inputs and or MIO inputs can be disabled via menu H8 S1 Alarm points disabled via time channels are not limited and must not be counted Up to 200 outputs can be individually disabled via menu H2 B3 Disable
142. utput e g 3377 3379 3364 etc re 7 a Fire brigade tx yellow Steady cont Output s for Routing equipment disabled via menu H2 B3 or B9 or via open door Blinking Routing equipment power supply output or one or more supervised outputs of type Routing equipment have generated fault s This is also valid when the c i e has no contact with a unit with such an output e g 3361 etc Routing equipment Fault tx activated yellow One or more not acknowledged faults Output Fault condition for fault tx routing equipment is activated L12 me E Sensitive fault detection mode see menu H5 A2 is on Fire brigade tx delay The Alert Annunciation function is enabled i e time yellow channel controlling this function is on The AA function is described in the EBL512 G3 Planning Instructions chapter Alert Annunciation LED L14 will be on if the AA function is enabled for at least one alarm point zone Normally is only one time channel used for this function but two or more channels can be used The AA function can as an alternative be continuously on Main board 5010 term block J3 3 4 fuse F8 T500mA L 250 V TRS 17 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Push buttons Keypad on the Control Panel CP Key push button Operation function Used to log on i e to get access to the menu tree via an
143. uzzer With Door Switch E Global Reset of Fan Control Outputs E ash LED on MCP Use Daylight Saving Redundant TLON Use Prewaming M Enhanced Disablement Door Closing by Time Main Power Loss Fault Delay Time minutes E Active 08 50 0 E g during Fire alarm Co incidence alarm or Pre warning etc 7 Including Addressable siren 3377 and Addressable sounder base 3379 26 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 9 Disable Re enable alarm devices The outputs programmed for sounders type Alarm devices can via menu H2 B8 be collective disabled for one several or all control units This is indicated by LED Fault Disablements General disablements L10 and Alarm devices L11 are steady ON In case of a fire the sounders will remain disabled i e the alarm devices will not sound They will remain disabled until they are re enabled again via menu H2 B8 See also chapter Disable re enable alarm devices H2 B8 page 94 27 Panasonic Electric Works Nordic AB MEW01163 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x 10 Silence buzzer The buzzer in the control unit will sound for Fire alarm 0 4 0 4 sec Co incidence alarm 2 zone or 2 unit dependent fire alarm When only one zone or one zone address alarm point is in alarm status 0 8 5 sec Pre warning 0 8 5 sec
144. xxx yyyy mm dd hh mm serviced NOTE The date is in the Ukrainian convention and the Australian convention shown as dd mm yyyy e In the c i e display can at least three fault messages be shown simultaneously On the last row in the display the number of not acknowledged faults is displayed e Ifa fault has been corrected before it has been acknowledged the status information is serviced see above e Fire alarm presentation has higher priority than the fault messages however during fire alarm presentation the faults can be shown via the menu system see page 38 20 Some units may also have an internal delay time which makes the delay time even longer e g the Multipurpose I O unit 3361 has an internal delay time of 30 seconds which results in 45 30 75 seconds delay time in total The buzzer in the control unit can be suppressed for faults generated in other control units Suppressed buzzer during fault is set via WinG3 47 Panasonic Electric Works Nordic AB MEW01163 17 1 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Faults have to be acknowledged which is done via menu H6 see page 120 This menu is a list of all not acknowledged and acknowledged but not corrected serviced faults If a fault cannot be corrected it is important to contact service personnel engineer immediately NOTE As a reminder faults and disablements are indicated by a 2 sec beep when an ope
145. y on zone line Conventional Detector Base CDB A conventional detector is plugged in a CDB connected to a conventional zone line input Addressable A unit with a built in address device i e each unit is individually identified handled and indicated in the c i e The unit can be an I O unit with a zone line input to which one or more conventional alarm points can be connected Panasonic Electric Works Nordic AB MEW01163 2 2 8 2 3 2 4 2 5 2 6 2 7 2 8 2 9 2 10 2 11 Rev Operating Instructions Fire alarm system EBL512 G3 V1 0 x Conventional zone line input External line Input intended for one or more conventional alarm points End of line device in the last alarm point Output unit Addressable unit with programmable control outputs Connected to a COM loop see below Output Control output Defined or programmable function Relay output or voltage output supervised monitored in the c i e or an output unit Short circuit isolator ISO Addressable unit for automatic disconnection of a part segment of a COM loop see below in case of a short circuit on the loop According to EN54 2 One ISO is required per 32 alarm points on the COM loop Display unit DU Addressable unit for fire alarm presentation incl user definable text messages if programmed COM loop Loop a cable with two wires to which all the addressable units can be connected Start