Operating Instructions Fire Alarm System EBL512
Contents
1. All control outputs programmed as type e Control general e Ventilation Fire ventilation e Extinguishing e Interlocking can via menu H2 B3 be collectively disabled for a specified control unit or all control units This is indicated by LED Fault Disablements General disablements L10 They will remain disabled until they are re enabled again via menu H2 B3 See also chapter Activate Reset outputs H8 S8 page 147 An output can be activated for an output test See also chapter Activate deactivate interlocking output H9 C2 page 150 An interlocking output can be activated for an output test 38 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 13 Evacuate When the soft key Evacuate P7 is pressed all outputs programmed for sounders i e type Alarm devices will be collectively turned ON steady This is indicated in the LCD The sounders will remain turned ON until they are turned OFF by pressing the soft key Evacuate off P7 NOTE 1 The alarm devices sounders will always be activated steady sound continuously irrespective of the fact that the outputs can be set to anything else for fire alarm e g intermittent NOTE 2 The text Menu above the soft key P4 is visible in the display only if the door in the c 1 e is open while the text Evacuate Evacuate off above the soft key P7 is always visibl
2. to re enable Re enabled type will disappear from the list indicated with a beep Disable or Re enable another type or press ESC Scroll to another menu or press ESC or Escape menu Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 24 5 Routing equipment H2 B5 Disabled outputs are listed in menu H4 U1 from which it is possible to get a print out Outputs for routing equipment fire brigade tx and fault tx can be disabled and re enabled via this menu Can be useful during an installation and test period when only local alarms are required Disabled output for routing equipment is indicated by LEDs Fault Disablements General disablements L10 and Fire brigade tx L12 Disabled output will stay disabled until re enabled again via this menu Menu According to chapter Access see page 88 Scroll to menu H2 H2 Disable or re enable a B2 Output B3 Output type B4 Alarm devices B5 Routing equipment B6 Alert annunciation function Escape menu Scroll to menu B5 B5 Routing equipment Via menu B5 can the standard outputs fire and fault for routing equipment be disabled Disable mawecana Use 4 b to Fault toggle between Fire Fault Press to disable which will be indicated with V and a beep The type will directly be shown in the Re enable list 103 Panasonic Eco Solutions Nordic AB MEW01552
3. FAULT Charging external power supply CONT aod Nun EER The fault is to be found in the external power supply equipment which has a charging fault output connected to a programmable input in control unit no xx SPN ONL Clavel io mialey a KONWNE O UE TEE a The fault is to be found in the external power supply unit 3366 Charging is stopped due to too high output current FAULT Checksum MMI program CO Maes SONES A fault in the control unit xx MMI board 5011 software LED System fault is turned on This is a very serious fault Call for service personnel engineer immediately FAULT Checksum system program CO Eis O les Winston lt x 62 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x System fault is turned on This is a very serious fault Call for service personnel engineer immediately FAUCET OCU a a aver e O e Ea a ERT CON eO Une OC Ae MS eee lt network x network O or network 1 Network 0 In a redundant network the communication is normally on Network 0 only Network 1 In a redundant network is Network Inormally in a supervised quiescent state until there is a fault cut off or short circuit on Network 0 Check the TLON network cables connections Also for mixed Network 0 and Network 1 cables Faulty TLON connection board 1590 5090 The control unit has no power Can be shown in conjunction with new S W download Cis CO
4. NOTE By restart and power off the Fault tx output s will be activated Menu According to chapter Access see page 88 Scroll to menu H8 a S2 Acknowledge SERVICE signal Clear weekly average Test of alarm devices Safe shut down of control unit Activate address in alarm mode Synchronize the control units Activate Reset outputs Scroll to menu S5 S5 Safe shut down of control unit al Shut down control unit do Write control unit number Yes and press W to select Yes y Ready for shut down break the power The SSW is now saved and el Automatic restart within xxx seconds the Main board and MMI board CPUs are at rest xxx will start at 300 seconds and countdown to 000 before You can now power off the the control unit will restart automatically During the control unit countdown the buzzer will start sounding since the If not the control unit will communication between the Main and MMI boards has restart automatically after stopped Can be silenced via push button Silence buzzer 300 seconds 5 minutes gt No safe shut down might also generate a fault FAULT Read write site data SSW control unit xx when you power up the control unit again 141 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Power off Power on FAULT Restart control unit 00 code 53 After a restart see page or address 0 84 there will always
5. The RTC component has a capacitor as a backup power supply Normally date day of the week and time only have to be set when the power is turned on the control unit for the first time If required the clock might be corrected so that the time stamps for fire alarms faults etc will be correct The calendar and clock can be set in any c i e for the whole system Every day at midnight the calendar and clock will be synchronised NOTE If you don t want to change anything press ESC instead of lt to return to menu H3 Menu According to chapter Access see page 88 Scroll to menu H3 WERSAL EOE EOK ee YY Y MM DD hh mm The date amp time shown Tuesday was valid when this menu Wednesday was opened When Thursday required change the date Friday time and or weekday Saturday press Y or A to Sunday select the weekday The clock starts again as from the date time etc shown in the display when you press 41 If no changes shall be done press ESC instead of al nS a H3 Set calendar and clock Scroll to another menu or press ESC NOTE When the Russian Ukraine Australian or the New Zealand language is selected the date is shown as follows DD MM YYYY 4 The capacitor can supply the RTC for a couple of days When the power has been turned off it 1s recommended to check set the date and time in menu H3 107 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating
6. The normal alarm window will be automatically displayed again after the menu system is escaped or 5 minutes after the latest manoeuvre in the menu system The alarm window will also be automatically displayed again if any of the soft keys Esc menu P4 or ESC is pressed or push button Alarms queued P8 16 2 2 Acknowledged and Isolated alarm Acknowledged and Isolated alarm is a fire alarm function only used in New Zealand Acknowledged alarm A fire alarm presented in the display can be acknowledged by pressing the soft key Acknowledge P7 47 Panasonic Eco Solutions Nordic AB MEWO01552 16 2 3 16 3 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Acknowledged alarms are indicated in the display by Acknowledged alarm in the same position as Heavy smoke Heavy heat see below This indication is the only difference between a normal fire alarm and an acknowledged alarm Acknowledged alarms have to be reset like normal fire alarms Isolated alarm A normal fire alarm or an acknowledged alarm presented in the display can be isolated as follows When the New Zealand FB Silence switch outside switch is turned OFF from activated to not activated any fire alarm and acknowledged alarm will be isolated disabled Isolated alarms are indicated in the display by Isolated alarm in the same position as Heavy smoke Heavy heat see below Isolated alarms do not activate
7. Panasonic Operating Instructions MEW01552 Revision Fire Alarm System EBL512 G3 V2 0 X Author Jan Pettersson Date of issue 2013 01 07 This page has deliberately been left blank Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Table of contents 1 Introduction 7 2 Definitions Explanations 9 2 1 PESN AB 9 2 2 Alarm points 9 22 1 Smoke detector 9 222 Sensor 9 2 2 3 Analog detector 9 2 2 4 Analog Sensor Base ASB 9 22 5 Conventional detector 9 2 2 6 Conventional Detector Base CDB 9 ADAE Addressable 9 2 2 8 Conventional zone line input External line 10 23 Output unit 10 2 4 Output Control output 10 2D Short circuit isolator ISO 10 2 6 Display unit DU 10 2 0 COM loop 10 2 8 Control Unit C U C LE 10 2 9 Fire Brigade Panel FBP 10 2 10 Control panel CP 10 2 11 System Installation 1 2 12 Network TLON LonWorks Echelon Node TLON Conn board Gateway Sub net Backbone net Router Repeater 11 2 13 LED 11 2 14 External Indicator LED 11 2 15 Display LCD 1 2 16 Door open Door Key switch 1 2 17 Site Specific Data SSD 12 2 18 Software S W System program 12 2 19 EBLWin 12 2 20 Web server EBLWeb config tool 12 3 Overview 13 3l The EBL512 G3 system 13 3 1 1 Printer 13 3 1 2 Expansion boards 13 3 1 3 Power supply 13 3 2 Software S W versions 14 3 3 Documents 14 3 4 Applications 14 3 PC program
8. Scroll to another menu or press ESC NOTE After the calibration it is recommended do a Safe shutdown of the control unit see menu H8 S5 page 141 This will save the SSW data e g the calibration values in a Flash ROM 52 Control unit outputs SO S3 and 4583 outputs 0 1 One end of line resistor 33K in the last unit or one resistor 33K in up to five units 3364 outputs VOO VO1 One end of line capacitor 470 nF in the last unit or one capacitor 470 nF in up to five units 119 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 27 2 Sensitive fault detection mode H5 A2 To increase the possibilities to detect faults during the commissioning it is possible to use the Sensitive fault detection mode The time delay for each fault will then be reduced i e you might find some faults now instead of later The Sensitive fault detection mode turned on is indicated by the LED Routing equipment Fault tx activated L13 and the Fault output for routing equipment is activated and by in the display s symbol area NOTE Don t forget to turn off this mode after the commissioning Menu According to chapter Access see page 88 Scroll to menu H5 mM A oe do A1 Calibration of supervised output A2 Sensitive fault detection mode Service mode for COM loop Display current consumption in control unit Display current consumption on COM loop Displa
9. 00 29 Check fuse F8 on the main board 5010 in control unit no xx Also indicated by LED Fault Disablement Fire brigade tx L12 blinking Fuse T500mA L 250V TRS JESU EE S ZAN T RGB GC OUE OU UNG ANE a DO G O50 O This is valid for the external power supply 3366 connected on the COM loop The output might be turned off or the current output limit 4A is exceeded NOVELS mA erte aanne L Aa ETON Wienke o lt CONE OT NE SOx 1735 1736 Alert Annunciation Unit AAU The AAU unit xx connected to control unit no xx is programmed as another type in the SSD or a fault in the unit FAULT Battery not connected COM rO EIEE 61 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Battery voltage is below 18 9 V Batteries 2 x 12 V are missing or not connected correctly Fuse F2 on the Main board 5010 is blown Other battery fuse is blown This check is done every 14 minute but when the fault is generated the check is done every 30 sec Fuse T6 3A H 250V 5x20 mm ceramic EAD Battery ec mille ale mul eta SOx KOCK The charging function in the external power supply 3366 connected on the COM loop is not OK e Batteries 2 x 12 V are missing or not connected correctly e The p c b is faulty and has to be replaced FAUTE RECN rC CONC ONTE t o The battery charging function is not OK The main board 5010 may have to be replaced
10. Fire brigade tx L12 blinking Calibration not performed via menu H5 A1 Short circuit break on the connected cable equipment Connected equipment might be stolen End of line capacitor s missing or not correct value 1 5 capacitors 470 nF NOTE The calibrated value has to be in the range 470 nF 5 x 470 nF 2350 nF FAULT Temperature sensor control unit xx The sensor is not correctly connected or is missing PAUE 2 MON Slomeaneclk UNS eireai lt O CONECTO C UNIE NAX FACE EE ON SPO alec ENNE tw or k rn Con CEO Wicalic Sox TLON connection board 5090 No communication connection with the TLON network The board for Network 0 or 1 in control unit no xx has to be replaced AOE Mee Aa nore TATO alee On MOO wie Le Auber al We lt 0 lt Can be shown in conjunction with new software download and or when commissioning a system This fault can be generated due to a bad TLON network 1 e communication problems One or more control units might have data stored that is not the same in all control units If a control unit restarts in conjunction with this fault a synchronization will start automatically otherwise a synchronization has to be started via menu H8 S8 or via EBLWin 74 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x NOTE It is important that all control units that are supposed to exist SSD downloaded via EBLWin are running
11. If a real fire alarm is activated for example by an alarm point not in test mode the normal fire alarm functions will be activated i e fire alarm presentation outputs sounders activated routing equipment fire brigade tx activated etc See also chapter The information area priority order page 25 NOTE If the control unit door is left open the output s for routing equipment fire brigade tx might be disabled if set so in EBLWin The test mode will be automatically ended one hour after the latest test alarm See also chapter Perform ZONE TEST Test mode H7 page 131 Menu According to chapter Access see page 88 i H1 Perform monthly test Check that all LEDs light up Press The buzzer in the C U sounds and all dots in the display are shown All LEDs light up incl LEDs in units connected via I O Matrix board 4582 If a printer is mounted in the c 1 e it will print out Zones to be set in test mode H2 22 222 22 Start test Write zone numbers Zones to be set in test mode Press 4 to start the test e g 001 002 003 001 002 003 004 mode 004 90 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Zones in test mode LED Test mode L8 001 002 003 004 End test will light up Perform the tests The zone s will stay in test mode until the test mode is ended The test mode is ended in this menu or automatically o
12. V2 0 x 9 Disable or Re enable alarm devices Outputs programmed for sounders i e type Alarm devices can via menu H2 B4 be collectively disabled for all control units This is indicated by LED Fault Disablements General disablements L10 and Alarm devices L11 which are steady ON In case of a fire the sounders will remain disabled i e the alarm devices will not sound until they are re enabled again via menu H2 B4 NOTE Outputs of type Alarm devices cannot be individually disabled not even via menu H2 B2 Disable or Re enable Output See also chapter Test of alarm devices H8 S4 page 139 All outputs of type Alarm device for a specified control unit or all can be activated for an alarm device test 35 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 10 Silence buzzer The buzzer in the control unit will sound for e Fire alarm 0 4 0 4 sec e Co incidence alarm 2 zone or 2 unit dependent fire alarm When only one zone or one zone address alarm point is in alarm status 0 8 5 sec e Pre warning 0 8 5 sec e Quiet alarm 0 8 5 sec e Fault continuous e Disablements and Faults 1 sec directly after the door to the c 1 e is closed e Activated interlocking input 0 8 0 8 sec if this option is selected via EBLWin Press Silence buzzer P1 to silence the buzzer In case of a new alarm pre wa
13. e Drawings Normally information found in one of the documents is not found in another document i e the documents complement each other For the TLON Network TLON Manager Web server etc are separate documents available Applications The EBL512 G3 system is intended for small medium and large installations The intelligent control units offer the system designer and end user a technically sophisticated range of facilities and functions Programming PC programs EBLWin TLON Manager and EBLWeb and commissioning of the control units system is very easy Start with one control unit and later when it is required add more units The TLON Network makes it possible to install the control units in one building or in different buildings PC programs The following PC programs are used together with the EBL512 G3 system EBLWin The PC program EBLWin is used for programming and commissioning of one or more control units 1 e to autogenerate i e to identify the units connected on a COM loop and make default settings which can be edited saved and used as site specific data SSD 14 Panasonic Eco Solutions Nordic AB MEWO01552 3 5 2 3 5 3 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x e create and download make a backup upload of site specific data SSD e download new software settings convention configurations control unit amp system properties etc e create and dow
14. is Shown in the display And after a few seconds if everything is all right else see Memory fault below A fault will be generated and the following text message will be shown in the display and the buzzer will sound FAULT Restart control unit nn code xx address yyyyyy Regarding code xx and address yyyyyy see page 71 This fault is also indicated by LEDs Routing equipment Fault tx activated L13 and Fault Disablements General fault L9 After the fault 1s acknowledged via menu H6 the LEDs will be turned OFF if there are no other faults After any restart required individual disablements have to be done Memory fault In case of a fault in the Main board 5010 S W system program or the MMI board 5011 S W the following fault message might be shown Not shown in the display only via EBLWin the Web server or via another unit in the system This is also indicated by LED System fault L7 and the buzzer sounds steady continuous The Fault tx output is activated 86 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x A new download of the S W system programs are required and or the Main board and or the MMI board have to be replaced NOTE After SSD download the following messages might be shown Checksum fault in downloaded data ts Control unit will now restart FAULT Restart control unit nn code xx address yyy
15. list Use the soft key gt I to toggle between Set in test mode and End test mode list al e OO sess sce s sts cesses see sossao After the testing select a Zone zone in the End test q al Endtest mode mms ods lst and press The test mode has to be Zone 001 ended for all zones 132 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x The zone s will stay in test mode until the test mode is ended The test mode is ended in this menu or automatically one hour after the latest test alarm You will be automatically logged out 15 minutes after the latest action using of any key but the zone s will stay in test mode until the test mode is ended see above Perform the test as quickly as possible since the output s for routing equipment fire brigade tx are disabled also the parts of the zones in test mode not visible for the test personnel are disabled In order to shorten the testing time any time delay for the detectors zones in test mode will be disabled 1 e fire alarm will be detected faster than normally In the tested alarm point the LED will light up and the LEDs Fire L1 in the c 1 e will light up approx 10 seconds then the alarm point will be automatically reset The printer if available will print out every tested alarm point Zone xxx Address xx Time HH MM An alarm point in test mode will not be able to generate
16. 003 address 01 autom re enable at 17 05 Use tiene It Ch i toggle between Disable Ea and Re enable list of disablement A Disable Select in the Re enable Zone ___ address list V in this Automatic re enable No example there is only BRe cnable lst 1 TT ov item and press al om Zone 003 address 01 autom re enable at 17 05 keebi Sune orzon address will disappear from the list indicated with a beep Change type nl of disablement a Disable Disable or Re enable Zone 00 address 00 another Zone Zone Automatic re enable No Address or press ESC Change type of disablement ESC B1 Zone or Zone Address Scroll to another menu B2 Output or press ESC or B3 Output type Escape menu B4 Alarm devices B5 Routing equipment B6 Alert annunciation function Escape menu NOTE The sensor values for disabled analog smoke detectors in NORMAL mode will not be used for calculation of the week average sensor value 1 e only the values saved before and after the disablement will be used for this calculation 96 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 24 2 Output H2 B2 All programmable outputs in the c i e and outputs in units connected to the COM loops except outputs of type Alarm device can be individually disabled If you try to disable an output of type Al
17. 3 x 999 events are available 1 Alarm log alarm events e g fire alarm fire alarm reset etc 2 Interlocking log interlocking events only 3 General event log all other type of events The origin of the event e g CU00 see below can instead be EBLWin WebG3 or Ext External system no connected via Web server H4 Present system status U1 Disablement Disablement by time channel Open doors Sensor values Sensors activating SERVICE signal Technical warning Event log U8 Information U7 Event log Select event log MNETALLH0 0 Interlocking log General event log Command Reset all alarms 2009 12 03 09 25 30 FIRE ALARM zone 123 address 45 2009 12 03 09 09 15 FIRE ALARM zone 123 address 46 2009 12 03 09 07 01 Event 15 to 13 of 21 Print According to chapter Access see page 88 Use V or A to select alog E g the Alarm log If there are no events List is empty will be shown It is a dynamic list in which you can scroll with VW or A The most recent event is on top of the list If printer is mounted the soft key Print will be visible else not Press Print to select and print the events the latest hour day week or month Scroll with VW or A to view more events U6 Event log Scroll to another menu or press ESC NOTE During printing Print will be replaced with Abort printing 116 Panasonic Eco Solutions Nordic AB M
18. A5 The current consumption an average value for each COM loop can be displayed NOTE No or very small current consumption lt 10 mA cannot be presented correctly precisely since the accuracy is 5 mA Menu According to chapter Access see page 88 Scroll to menu H5 di A1 Calibration of supervised output Sensitive fault detection mode Service mode for COM loop Display current consumption in control unit Display current consumption on COM loop Display statistics for communication Activate address setting mode for DU SSD information Scroll to menu A5 Display current consumption on COM loop al Display current consumption on COM loop 0 Write loop number and control unit 00 press lt control unit number and press lt 4 If the control unit don t exist or don t answer Current consumption on COM loop 0 The current consumption control unit 00 is xxxx mA accuracy is 5 mA lt 4 or ESC A5 Display current consumption on COM loop Scroll to another menu or press ESC 124 Panasonic Eco Solutions Nordic AB MEWO01552 27 6 Scroll to menu A6 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Display statistics for communication H5 A6 The statistics can be used during commissioning service etc Number of pollings is the number of pollings questions sent out by the control unit to all the units connected on the COM loop Parity fault is the received number of parit
19. Instructions Fire alarm system EBL512 G3 V2 0 x 26 Present system status H4 If a printer is mounted an option for control unit 5000 it is possible to get a print out from some of the menus In this case the soft key Print P5 shall be used NOTE During printing Print will be replaced with Abort printing When Abort printing is pressed the soft key text immediately changes back to Print but the items already stored in the print buffer will be printed up to five items 26 1 Disablement H4 U1 This is a dynamic list of all disablements in the system Also alarm point s and or zones disabled via Single reset with automatic disablement see page 56 are shown in the list A disabled zone programmed with address 00 will be displayed as ZZZ 00 Disablements by time channels are listed in menu H4 U2 Menu According to chapter Access see page 88 Scroll to menu H4 H4 Present system status oe a Via menu U1 will all U2 Disablement by time channel disablements in the Open doors system except Sensor values disablements by time Sensors activating SERVICE signal channels be shown Technical warning Press 4 Event log Information Ps Zone XXX address XX disabled If there are no disable yyyy mm dd hh mm ments List is empty will be shown Itis a Zone XXX is disabled dynamic list in which you Automatic re enable hh mm can scroll with Y or yyyy mm dd hh mm A Information is shown about disableme
20. Nordic AB MEW01552 Rev 31 Operating Instructions Fire alarm system EBL512 G3 V2 0 x Interlocking outputs and inputs H9 31 1 Activated interlocking outputs inputs H9 C1 Menu Scroll to menu H9 a Depending on activated outputs and or inputs the following will be shown ESC H9 Interlocking outputs and inputs C1 Activated interlocking outputs inputs C2 Activate deactivate interlocking output C3 Disable re enable interlocking output C1 Activated interlocking outputs inputs Interlocking area AAA point PP output active User definable text message if progr yyyy mm dd hh mm Interlocking area AAA point PP input output active User definable text message if progr yyyy mm dd hh mm Interlocking area AAA point PP input active User definable text message if progr yyyy mm dd hh mm 3of5 C1 Activated interlocking outputs inputs 149 According to chapter Access see page 88 Via menu C1 can activated interlocking outputs and inputs be listed It is a dynamic list in which you can scroll with VW or A If printer is mounted the soft key Print will be visible else not Press Print fora print out of all items in the list Scroll to another menu or press ESC Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 31 2 Activate deactivate interlocking output H9 C2 The o
21. S W SSW Via RESET button on MMI board SSD 53 S W SSW FFD WASV Reset command via EBLWin or FFD WASV SSD 03 53 TLON Manager Warm restart S W SSW Automatically after download of site FFD WASV SSD 03 specific data SSD via EBLWin S W SSW Warm restart Automatically after download of FFD WASV SSD 00 50 S W via EBLWin s w SSW Automatically by the S W itself FFD WASV SSD 13 due to some internal disturbance S W SSW Automatically due to some external FFD WASV SSD 01 02 alt disturbance S W SSW 04 20 NOTE During the restart the fault output relay for the Fault tx will be activated the supervised 24 V DC outputs SO S3 will be not supervised and S0 S3 programmed as normally high will be low for a few seconds 3 Both rectifier mains and battery disconnected Code 50 53 only if the c 1 e has an MMI board 5011 Tf the time runs out 1 e no safe shut down the c 1 e will do a restart code 03 42 If in the middle of a process also the SSW might be deleted 43 The old S W will be deleted 4 Depending on the restart reason also the SSW might be deleted Always followed by an address If this happens call for service personnel engineer 85 Panasonic Eco Solutions Nordic AB MEWO01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x During the restart no fire alarm can be activated and the following
22. The AA function will be turned off until re enabled via this menu Menu According to chapter Access see page 88 Scroll to menu H2 H2 Disable or re enable el B1 Zone or Zone Address B2 Output B3 Output type B4 Alarm devices B5 Routing equipment B6 Alert annunciation function Scroll to menu B6 B6 Alert annunciation function Via menu B6 can the Alert Annunciation function be disabled ad Disable Press 4 to disable Alert annunciation which will be indicated with V and a beep The disablement will directly be shown in the Re enable list ma Disable Alert annunciation N a REN O o e ese eee ce eee oa oe Alert annunciation off Use the soft key gt I to toggle between Disable and Re enable 105 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Disable Alert annunciation HRe enable list ME Alert annunciation off Disable Alert annunciation B1 Zone or Zone Address B2 Output B3 Output type B4 Alarm devices B5 Routing equipment B6 Alert annunciation function Escape menu 106 Press to re enable Alert annunciation off will disappear from the list indicated with a beep Disable or press ESC Scroll to another menu or press ESC or Escape menu Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 25 Set calendar and clock H3
23. a fault An alarm point in alarm when the test mode is ended will activate a normal fire alarm for each zone to end p Set in test mode R No zones in test mode Set the test mode Zone doo new zones in test mode or press ESC H7 Perform ZONE TEST The LED Test mode L8 is turned OFF If more zones are to be tested continue as above If not scroll to another menu or press ESC NOTE_1 During the test the following information will be shown in all other c 1 e displays Zone 001 in test mode Zone 002 in test mode etc NOTE_2 If an alarm point e g a manual call point is in alarm state when the test mode is ended there will be a fire alarm activated NOTE_3 When the Fire door closing function is used the fire door will be closed also when the detectors controlling the door are tested in test mode 133 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 30 Maintenance H8 30 1 Password for service maintenance Only authorised personnel have access to the level 3A menus e g H8 and a password for level 3A Service technician is required 30 2 Dis Re connect loop zone line input H8 S1 Before physical connection disconnection of loop units etc the loop or zone line shall be disconnected voltage free in order to avoid damage on the units and the c 1 e Zone line input requires an 8 zones expansion board 4580
24. and are connected to the TLON network The TLON network programming has to be done It will take 90 120 seconds until this fault is corrected PAULI Wrong tye expansion board x TOCE CONE rO arise ea o lt This is valid for the I O Matrix board 4582 no x connected on COM loop x in the control unit no xx Check the board type set with jumpers JP4 and JP5 on the I O Matrix board The type should be the same as programmed via EBLWin PAULI Wrong eype exXpamsilom loOard x CONECTO EUNT EX Valid for the 8 zones exp board 4580 the 8 relay outputs exp board 4581 and the Inputs and outputs exp board 4583 mounted in control unit no Xx Check the type of board which should be the same as programmed via EBLWin PAC Vie ONG CyPer Or UNIT Zone address xx technical number xXxXxxxx Check the type of unit which should be the same as programmed via EBLWin FAULT Zone line input Zone xxx Address xx CUS xe Oars HONeOOc Ge x EMP unm Valid for the 8 zones exp board 4580 zone line input x xxx xx zone address The board is mounted in control unit xx Break on the zone line wrong no end of line device short circuit 1f not programmed for fire alarm at short circuit FAULT Zone Tine Input zone xxx address NOX Eee gua Cenk Toso x Valid for the Multipurpose I O unit 3361 monitored zone line input Z Break on the zone line or wrong no end of line capacitor 470 nF or short circuit 1f not programmed for fir
25. another menu or press ESC TG change the convention via EBLWin Level 2 has to be selected which require a special password Alt EBLWin can be re installed 128 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 28 FAULT Acknowledge H6 Regarding fault indication etc see chapter Fault page 59 See also chapter Fault acknowledge page 77 All faults and the status action are stored in the event log and can be listed see chapter Event log H4 U7 page 116 In menu H6 can be listed up to 300 faults Not corrected not serviced and not acknowledged faults no status information Not corrected not serviced but acknowledged faults Acknowledged Corrected serviced but not acknowledged faults Serviced The most recent fault is shown on top of the list Menu According to chapter Access see page 88 Scroll to menu H6 H6 FAULT Acknowledge i tCisS Y FAULT Low battery capacity control unit 00 If there are no faults List is empty will be eee slay shown It is a dynamic list in which you can FAULT No reply zone 045 address 06 scroll with Y or A technical number 000005 If printer 1S mounted the Alarm text for 045 06 user definable soft key Print will be yyyy mm dd hh mm Serviced visible else not Press Print for a print out of FAULT No reply zone 021 address 05 all faults the latest technical number 000114
26. any control outputs do not activate the output for routing equipment Fire brigade tx do not activate the c 1 e buzzer and do not activate the LEDs Fire L1 in the c 1 e Isolated alarms have to be reset like normal fire alarms Isolated alarms also have to be re enabled via menu H2 B1 before they can activate a new fire alarm again Test mode alarm Regarding Test mode see chapter Perform monthly test H1 page 90 and chapter Perform ZONE TEST Test mode H7 page 131 When an alarm point in a zone set in test mode is tested it is presented in the display as a fire alarm but with the information Test mode added If a printer is available the test mode alarm will be printed with the information test mode added The LEDs Fire will be blinking like for a fire alarm but no outputs will be activated except the fire door outputs The test mode alarm will be automatically reset after approx 10 seconds Heavy smoke alarm Heavy heat alarm An analog detector can activate a heavy smoke heat alarm for a higher alarm level than the normal fire alarm level i e a normal fire alarm is already activated by a detector activating a heavy smoke heat alarm Heavy smoke heat alarm is to confirm heavy or increasing smoke heat and can be used for special actions e g activation of smoke ventilation etc LED Fault Disablements General disablements L10 is indicating that one or more zones alarm points
27. cause alarm It can be ions from plastics flour dust oil haze aerosols strong perfumes strong ventilation insecticides disinfecting sprays etc If many odd and unnecessary alarms occur the environment must be examined and perhaps other detector types have to be chosen Steam hot air Smoke and heat detectors are influenced by steam and hot air e g from an oven dry blower heater etc 159 Panasonic Eco Solutions Nordic AB MEWO01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Exhausts Exhausts from cars trucks lift trucks lawn mowers etc influences smoke detectors sensors If windows and doors are open exhausts can slip in that way Lack of maintenance Smoke detectors sensors are influenced by their environment and become dirty In an analog system like EBL512 G3 a Service signal is given when it is time to exchange the smoke detectors sensors to new ones The alternative is to exchange detectors at given periods to be on the safe side Change in activities or wrong choice of detector If the activities in the premises are altered the detector choice might also need to be altered Due to special environments see above an in appropriate detector type might have been chosen from the beginning and thus cause unnecessary alarms Miscellaneous Choosing another type of detector can solve certain problems Bear also in mind that the coverage area can be different
28. control unit restart synchronization will start automatically Synchronization can also be started via EBLWin and via this menu H8 S7 The control units have to be synchronized when the following fault message is shown FAULT Control unit xx has wrong information During the synchronization there will be information displayed for all control units in the system U rotating clockwise Synchronization in progress for the control unit CU respectively y Synchronization completed successfully for the control unit CU respectively lt Blank gt Synchronization failed for the control unit CU respectively Menu According to chapter Access see page 88 a S2 Acknowledge SERVICE signal Clear weekly average Test of alarm devices Safe shut down of control unit Activate address in alarm mode Synchronize the control units Activate Reset outputs Scroll to menu S7 Synchronize the control units al Start synchronization Press W to select Yes Yes Press 4 to start the synchronization To be continued on the next page 145 y al After a while Panasonic Eco Solutions Nordic AB Rev Synchronization in progress CU00 U CU01 U CU02 CU03 U CU04 U CU05 U CU06 U CU07 U CU08 U CU09 Operating Instructions Fire alarm system EBL512 G3 V2 0 x CU10 U CU11 U CU12 CU13 CU140 Synchronization completed yyyy mm dd hh mm CUOO vV CU01 V CU02 vV CU03 vV CU04 v
29. door to get full access to the push buttons on the front 1 e the Fire Brigade Panel FBP and the Control Panel CP EBL512 G3 type 5001 has no front display and printer and is housed in a grey metal cabinet without a door 16 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Yb Fire LI e L2 Extinguishing P1 L3 Ventilation P2 L4 Fire brigade tx L5 Operation P3 L6 P4 P7 P8 Panasonic Fire Alarm Technology L7 L8 System fault Test mode a Lv L9 L10 General fault General disablements Ll 1 L12 Alarm devices Fire brigade tx Ll 3 L14 Fault tx activated Fire brigade tx delay SanssnnnnnnnnnnnnnnnnnnnnnnNnNNANANNNNANANNNNANANNNNANANNNNANANNNNANANNNNANANANNANANNNNNNANNNNANANNNANNANANAANANANAANANANAANANANAANANANAANANANAANANANNANANANAANANANAANANANANNANANAANANANAANANANANNANANANNANANANNANANNANANANANNANANANNANANAANANANANNANNNNANANANANNANANAANANANAANANANAANANANANNANANANNANANAANANANANNANANANNANANANNANENANNENENEEEEG Figure 2 The EBL512 G3 front with display The Fire Brigade Panel FBP is the upper part and the Control Panel CP is the lower part The look might vary according depending on language country etc A front with texts in English is shown in the figure See also chapter LED indicators and push _ buttons page 19 aceeceeneenueaueaneeeuenueausaaeegeeneenusaueeaeenuenusnuseaeeeenuenuseuseaeeaeenusauseaeeauenuseUseaeeeeOu
30. function Normally when an alarm point or zone having activated fire alarm is reset whilst still is in alarm status it will activate a new fire alarm within 20 seconds This is in accordance with the EN54 2 standard When Single with automatic disablement reset is performed an alarm point or zone still in alarm status will not only be reset but also disabled i e it will not activate a new fire alarm within 20 seconds It has to be re enabled via menu H2 B1 before it can activate a new fire alarm This function set via EBLWin is a violation to the EN54 2 standard LED Fault Disablements General disablements L10 is indicating one or more disablements in the system NOTE When All or Single reset is used automatic disablement encapsulation function can be used by pressing Reset P3 and approx 0 1 sec later also press Alarms queued P8 and hold them pressed for gt 0 5 sec The alarm point or the whole zone conventional currently shown in the middle of display with large digits will be reset and disabled Acknowledged and Isolated alarm Acknowledged alarm and Isolated alarm are fire alarm functions only used in New Zealand Acknowledged alarm Acknowledged alarms have to be reset like normal fire alarms Isolated alarm Isolated alarms have to be reset like normal fire alarms Isolated alarms also have to be re enabled via menu H2 B4 or B5 before they can activate a new fire alarm again Test
31. in a conventional detector base CDB see below which is connected to a conventional zone line input Some types e g water proof types are connected directly on zone line An end of line device has to be connected in the last unit on the zone line Conventional Detector Base CDB A conventional detector is plugged in a CDB connected to a conventional zone line input Addressable A unit with a built in address device i e each unit is individually identified handled and indicated in the c 1 e The unit can be an I O unit with a zone line input to which one or more conventional alarm points can be connected Panasonic Eco Solutions Nordic AB MEWO01552 2 2 8 2 3 2 4 2 5 2 6 2 7 2 8 2 9 2 10 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Conventional zone line input External line Input intended for one or more conventional alarm points End of line device in the last alarm point Output unit Addressable unit with programmable control outputs Connected to a COM loop see below Output Control output Defined or programmable function Relay output or voltage output supervised monitored in the c 1 e or an output unit connected on a COM loop Short circuit isolator ISO Addressable unit for automatic disconnection of a part segment of a COM loop see below in case of short circuit on the loop According to EN54 2 one ISO is required per 32 alarm
32. in the control unit or an Addressable multipurpose I O unit 3361 connected on a COM loop One or more disconnected loops are indicated by LED Fault Disablements General disablements L10 and listed in menu H4 U1 NOTE When you re connect a COM loop all the statistics shown in menu H5 A6 will be erased and set to 0 Menu According to chapter Access see page 88 Soroll to menu H8 i a Dis Re connect loop zone line input Via menu S1 can a COM TE SERVICE signal loop an exp board zone Clear weekly average line input and an address Test of alarm devices able zone interface input Safe shut down of control unit be Dis Re connected Activate address in alarm mode Synchronize the control units Activate Reset outputs el Disconnect Use the soft key Change COM loop ol control unit 00 type of disablements to toggle between COM loop Zone line input exp board Zone interface input loop unit to disconnect which will Change type be indicated with V and a of disablement beep 134 Panasonic Eco Solutions Nordic AB Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x MEWO01552 Write COM loop number and control unit number a gt ESC Disconnect COM loop ol control unit 00 Re connect list 1 COM loop 0 control unit 00 Bee Change type of disablements Disconnect COM loop _ control unit _ Re connect list 1 COM loop 0 control unit O
33. menu to the main menu H1 H10 or from a main menu to leave the menu system Use the soft key Escape menu when it is available to leave the menu system from any menu Note no text above a soft key the key is not available 1 e it has no function You will be automatically logged out 15 minutes after the last action 1 e 1f the key pad or a push button has not been used for 15 min and directly when you close the door A new login is then required If you leave the menu system without closing the door you have access to the menu system again only by using the soft key Menu A new login is not required Some lists are dynamic lists 1 e the number of items per page depends on the size of each item Some lists are static lists 1 e a fixed maximum number of items per page NOTE In the following chapters are all the menus described The Text in display column shows the essential text and might not look exactly as shown in the display 89 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 23 Perform monthly test H1 The control unit and the installation shall be tested on a regular basis If one twelfth of the alarm points are tested each month the whole installation will be tested after one year In test mode only the alarm points are tested 1 e no outputs no sounders will be activated during the test Alarm devices can be tested via menu H8 S4
34. mode alarm Test mode alarm is automatically reset after approx 10 seconds 56 Panasonic Eco Solutions Nordic AB MEWO01552 17 3 17 4 17 9 17 6 17 7 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Heavy smoke heat alarm reset If a heavy smoke heat alarm has been activated it will be reset at the same time as the corresponding fire alarm is reset Also the output s will be reset i e de activated Alert Annunciation Regarding the function see chapter Alert Annunciation alarm AA alarm page 49 and EBL512 G3 Planning Instructions chapter Alert annunciation Reset of the AA alarm s can be done via push button Reset on an AA unit 1735 1736 or an AA controller 1740 or in the c 1 e NOTE Reset via an AA unit is possible only during the investigation time and of AA alarm s only not normal fire alarms If more than one AA alarm is activated they will be reset all at a time Key cabinet alarm reset A key cabinet alarm has to be reset like the normal fire alarms After reset a fault message is shown in the display to inform the user that the key cabinet has been opened FAULT Key cabinet control unit xx yyyy mm dd hh mm NOTE The date is for the Australian New Zealand Russian and Ukrainian languages shown as dd mm yyyy Xx control unit number 00 29 If the key cabinet is closed again the status information is changed to serviced This key cabinet faul
35. or ESC A6 Display statistics for communication Scroll to another menu or press ESC 126 Panasonic Eco Solutions Nordic AB MEWO01552 27 1 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Activate address setting mode for DU H5 A7 This function can be used by commissioning service engineer to activate the address setting mode in the following Display Units connected to the c 1 e e Ext Presentation unit 1728 e Alert Annunciation units 1735 amp 1736 e Ext FBPs 1826 amp 1828 A specific unit or all units connected to one c 1 e can be activated for address setting NOTE The units have to be in operation and in quiescent condition 1 e the units have to have an address already Menu According to chapter Access see page 88 Scroll to menu H5 Scroll to menu A7 al or ESC Sensitive fault detection mode Service mode for COM loop Display current consumption in control unit Display current consumption on COM loop Display statistics for communication Activate address setting mode for DU SSD information A7 Activate address setting mode for DU Activate address setting mode for DU Write control unit number Control unit do display unit 00 All and the unit s address or press gt to select All i e all display units on the selected control unit Address setting mode for display unit 00 The address can now be control unit 00 activated edited in the display
36. require a routine test of the routing equipment Press press 4 1 e select No for no test If so the monthly test is completed see below or Press W and 4 e select Yes to start such a test If so the following will happen in the system e The c i e Fault tx output will be de activated note that this output is activated in normal state indicated by the LED Fault tx activated L13 60 seconds count down starts e After 30 seconds also the c i e Fire brigade tx output and corresponding programmable outputs type routing equipment will be activated indicated by the LED Fire brigade tx L3 e After another 30 seconds the test will be ended and the outputs and LEDs will return to normal VW and lt d Test of routing equipment in progress nn starts at 060 and will nnn seconds left count down to 000 91 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Monthly test is completed Press lt Scroll to another menu or press ESC NOTE_1 During the test the following information will be shown in all other c 1 e displays Zone 001 in test mode Zone 002 in test mode Zone 003 in test mode Zone 004 in test mode NOTE_2 If an alarm point e g a manual call point is in alarm state when the test mode is ended there will be a fire alarm activated NOTE_3 When the Fire door closing function is used the fire door will b
37. system EBL512 G3 V2 0 x SCI A lt gt SCI B If one SCI no 0 is used the information will be SCI A lt gt SCIOO or SCIOO lt gt SCI B and so on There will also be a FAULT No reply message for each unit not found by the c 1 e If there are several short circuits on the loop the message shows the isolator just before the break in the A direction incl the following isolator There will also be shown FAULT Multiple Pane S ace NOTE Each 10 minute a check is performed if all short circuits are corrected repaired If so the communication automatically returns to communicate in the A direction only FAUCI Sites Soeceinter Gave S52 COM bicOU eer a oc The Site Specific Data SSD in control unit no xx is not downloaded correctly a checksum fault etc A new SSD download via EBLWin is required PAULI See Spo Cre daea alert APN UNE TAE LONC a hin 2x oe a x FAULT obite cpecilic data external Presentar ron Unt xx CU x FAULI Site Speci rico data fire bDrigade Bane E CONTO Vuln lt x Alert Annunciation Unit 1735 1736 Ext Presentation Unit 1728 Ext Fire Brigade Panel 1826 1828 There is no SSD Site Specific Data downloaded to the unit or something is wrong in the downloaded SSD FAULT Supervised input x expansion board X ee OMe Only alse EAX 1 NOTE The fault has to be acknowledged i e and it can last up to 10 minutes after the acknowledgement before the
38. text will be shown Example fault message FAULT No reply zone xxx address xx technical number xxxxxx User definable alarm text yyyy mm dd hh mm Serviced Number of not ackn faults in system 1 NOTE When the Russian Ukraine Australian or the New Zealand language is selected the date is shown as follows dd mm yyyy 7 Some units may also have an internal delay time which makes the delay time even longer e g the Multipurpose I O unit 3361 has an internal delay time of 30 seconds which results in 45 30 75 seconds delay time in total The buzzer in the control unit can be suppressed for faults generated in other control units Suppressed buzzer during fault is set via EBLWin 59 Panasonic Eco Solutions Nordic AB MEWO01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x e Inthe c i e display can up to three fault messages be shown simultaneously In the display down to the left is displayed the number of not acknowledged faults e Ifa fault has been corrected serviced before it has been acknowledged the status information is Serviced see above e Fire alarm presentation has higher priority than the fault messages however during fire alarm presentation the faults can be shown via the menu system see page 47 NOTE Two faults also have their separate information texts shown close to the soft key area also during fire alarm Extinguishing fault and Extinguishing wire fau
39. the EBL512 G3 system program Safe shut down of control unit menu H8 S6 will save the SSW data i e not the week average sensor values in a Flash ROM before you power off de energize EBL512 G3 Before the first Safe shut down this memory is empty After each Safe shut down the latest SSW data is saved When EBL512 G3 is powered up the RAM working memory will after the restart read the SSW data saved in the Flash ROM The date amp time and alarm counter value is stored in the memory of the real time clock 1 e the value will be retained also after the c 1 e has been de energized NOTE After any restart a new week average sensor value will be calculated within two minutes for all the analog smoke detectors During these two minutes all fire alarms from analog smoke detectors will be suppressed Thereafter a new average sensor value will be calculated each week Here follows a table describing the different reset alternatives and how the data respectively is affected 84 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Action Data etc Data etc Restart which will be which will be deleted not deleted Power down de energize and SSW SSD 00 50 then power up again Cold restart FFD WASV S W Via menu H8 S6 Safe shut down of FFD WASV SSD 00 control unit Cold restart S W SSW 03 Via RESET button on Main board FFD WASV SSD 03
40. the PC tool EBL Web 12 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 3 Overview 3 1 The EBL512 G3 system EBL512 G3 is a microprocessor controlled intelligent fire alarm system intended for analog addressable smoke detectors as well as conventional detectors and manual call points Programmable control outputs and output units are available Up to 1020 addresses of which up to 512 can be alarm points can be connected to each control unit c 1 e according to EN54 2 EBLS512 G3 is available in several types versions and configurations It can be connected to a TLON network 1 e in a system with up to 30 control units Each control unit has access to all information Product type no 5000 EBL512 G3 c i e With or without a printer With front and display 5001 EBL512 G3 c 1 e Without front display and printer No door EBL512 G3 is developed and designed according to the European standard EN54 part 2 and 4 The Swedish front conforms to SS3654 3 1 1 Printer The control unit EBL512 G3 type 5000 can be delivered with a printer PRN included in the article number or without a printer In Ext Fire Brigade Panel 1826 it is possible to mount an optional Printer 1835 3 1 2 Expansion boards In the control unit c 1 e it is possible to mount up to six expansion boards The following types are available Product type no 8 zones exp
41. the new SSD according to Planning Instructions MEWOI551 Make two TLON networks one It is very important that two or more presentation numbers Zone or Zone Address in the systems are not the same The system properties have to be the same Use one of the systems e g the largest and add to it the control units etc from the other system If it is known from the beginning that two systems shall be one in the future it is possible to give the control units in the system respectively the final control unit numbers right from the beginning in order to get the correct technical numbers in the system documents NOTE Two or more presentation numbers Zone or Zone Address in the systems must not be the same Delete a Control Unit ina TLON network Physically disconnect the control unit This action will generate faults in the other control units Acknowledge the faults It is not possible to merge two TLON Networks into one or copy one system and paste into another system 81 Panasonic Eco Solutions Nordic AB MEWO01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Open the current project in TLON Manager delete the control unit according to the separate TLON network Operating Instructions MEW01361 Open the SSD for the current system via EBLWin Delete the control unit and the units connected to it and download the new SSD 82 Panasonic Eco Solutions Nordic AB MEWO01552 20 O
42. unit DU respectively A7 Activate address setting mode for DU Scroll to another menu or press ESC 127 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 27 8 SSD information H5 A8 SSD name As written in the EBLWin dialog box System Properties Name Downloaded Date and time when the SSD was downloaded User User name for the person who performed the SSD download Computer Computer name if programmed for the PC that was used for the SSD download Domain Domain if programmed for the PC that was used for the SSD download EBLWin key The unique number for EBLWin key Convention i e country specific functions default EBLWin settings etc is set in conjunction with the installation of EBLWin Menu According to chapter Access see page 88 Scroll to menu HS Sensitive fault detection mode Service mode for COM loop Display current consumption in control unit Display current consumption on COM loop Display statistics for communication Activate address setting mode for DU SSD information Scroll to menu A8 A8 SSD information SSD name XXXXXXXXXXXXXXX If printer is mounted the Downloaded yyyy mm dd hh mm soft key Print will be User Nnnnnnn visible else not Press Computer Cccccccccccccc Print to print the SSD Domain Dddddddddddd information EBLWin key 1234567890 Convention XXX 2 or ESC A8 SSD information Scroll to
43. up Memory fault in program area n n l or 2 The unit will not work PAULI No reply zone Xxx address xx technical number xxxxxx The unit cannot be found by the control unit Check the unit s COM loop address with the programming tool 3314 Check the downloaded site specific data SSD The unit might be faulty The detector might be removed from its base There might be a double break or short circuit on the COM loop FAUTE RECI NEE EC ONE eel thebieq oo This is valid for an EBL512 G3 type 5000 with printer Control unit no XX Faulty printer Printer not correctly connected No paper Printer selected in EBLWin but no printer mounted in the c 1 e and vice versa PAUE WSerc wees Saves Cerca WSS COME tole UNIE NX SSW the data that is changed during operation 1 e week average sensor values access codes calibration values and event logs in control unit no xx 70 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x e If the C U was made powerless i e mains and battery disconnected without first doing a Safe shut down of control unit via menu H8 S6 see page 141 this fault might be generated when the C U is powered again After fault acknowledge the SSW will get default values and the fault will be corrected serviced Supervised outputs have to be calibrated via menu H5 A1 e Some external influence has caused a fault in th
44. week NOTE If a sensor 430x and 440x in NORMAL mode is replaced without having generated service signal it has to be reset to the default week average sensor value via menu H8 S3 page 138 Menu According to chapter Access see page 88 Scroll to menu H8 H8 Maintenance al Dis Re connect loop zone line input Acknowledge SERVICE signal Clear weekly average Test of alarm devices Safe shut down of control unit Activate address in alarm mode Synchronize the control units Activate Reset outputs Scroll to menu S2 S2 Acknowledge SERVICE signal el Sensor Zone ZZZ address AA needs service If there are no sensors technical address xxxxxx List is empty will be 2012 12 03 09 09 15 shown This is a dynamic list in which you can scroll The most recent Sensor Zone XXX address AA needs service ave 2 l service signal sensor is technical address xxxxxx dowavontop or aoe 2012 11 03 19 09 35 Use VW or A to select a sensor the selected Sensor 1 2 is selected sensor has a border Press lt to Previous acknowledge the sensor page 136 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Sensor Zone XXX address AA needs service The acknowledged sensor technical address xxxxxx disappears from the list 2012 11 03 09 09 35 Continue like above or press ESC Sensor 1 1 is selected page page S2 Acknowledge SERVICE signal Scroll to anot
45. 010 term block J3 3 4 fuse F8 T500mA L 250 V TR5 See also chapter Fault acknowledge page 70 21 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Push buttons Keypad on the Control Panel CP Key push button Operation function 4 Enter Used to log on 1 e to get access to the menu tree via an access code and to accept a menu and accept input of data Also used by fault signal and service signal to acknowledge the selected fault analog smoke detector Left right keys are used to move the cursor in a menu Up down keys are used to scroll between the menus 1 9and0 Numeric key pad for the digits 0 9 Can be used to input data and in the menu system to jump to a menu with a corresponding number e g 5 for a jump to menu H5 JDE Used to clear delete all visible entry fields ESC Used to stop input of data or to step one step up in the menu system e g from a sub menu to the main menu NOTE To leave the menu system use the soft key Escape menu P4 22 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 6 The display LCD 6 1 Areas in the display Symbol area Information area Soft key area 1 4 e Symbol area Some events are indicated with symbols see 6 2 below e Information area General area for all kind of information and the menu system e Soft key
46. 2 minutes after SSD download amp restart During these 22 minutes can no fire alarm be activated and Weekly 00 0 m will be shown The Weekly value will thereafter be updated every week For the 440x detectors in Advanced mode the Weekly value is 00 0 m by delivery It will be updated the very first time after 13 minutes It will thereafter be calculated every 13 minute but will then only be changed downwards if required After 18 hours it can be changed downwards or upwards and after additional 18 hours 36 hours in all it can be changed downwards or upwards and it is also saved in the detector s EEPROM 1 e that value will be used after the detector has been powerless The Weekly value for the 440x detectors in Advanced mode is also called the Contamination Compensation Value CCV The Performance factor and Min Max values are updated each night 00 00 i e the values shown are from the previous day Algorithm shows the algorithm that is currently in use According to chapter Access see page 88 H4 Present system status U2 Disablement by time channel Open doors Sensor values Sensors activating SERVICE signal Technical warning Event log Information U4 Sensor values Start sensor ooo0o Write the technical number and or press 4 to start as from sensor 000001 111 Panasonic Eco Solutions Nordic AB MEWO01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x For a
47. 32 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 8 1 Silence alarm devices inside switch NOTE The functions in this chapter are normally used in New Zealand only The button Silence alarm devices P2 is called the inside switch and has the following function The inside switch toggles between two states e Alarm devices disabled All programmable outputs of type Alarm devices are disabled 1 e they cannot be activated e Alarm devices not disabled All programmable outputs of type Alarm devices are enabled i e they can be activated If the inside switch is in its disabled state when the c i e door is being closed the buzzer will beep steady continuously and the message Silence switch left active will be shown in the display For priority order see chapter The information area priority order page 25 NOTE The inside switch has no function if the outside switch see below is activated ON 8 2 New Zealand FB Silence switch outside switch NOTE The functions in this chapter are valid for the New Zealand convention only The New Zealand FB Silence switch is also called the outside switch since it is placed outside the c 1 e The outside switch is a key switch connected to a programmable input with the trigger condition New Zealand FB Silence switch The outside switch can be in two states The outside switch is turned
48. 5 sec Single Each fire alarm alarm point zone has to be reset one by one NOTE This function is available only if it is set in EBLWin Press Reset P3 to reset the fire alarm currently shown in the middle of the display with large digits NOTE The push button has to be pressed for min 0 5 sec Output s programmed for that fire alarm alarm point zone will be reset 1 e de activated If more than one fire alarm is activated G e LEDs Alarms queued L6 are lit the next fire alarm in the queue will be shown in the middle of the display It has to be reset the same way as the first one 55 Panasonic Eco Solutions Nordic AB MEWO01552 17 2 3 17 2 4 17 2 5 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x When all fire alarms are reset LEDs Fire L1 and Alarms queued L6 are turned off If there are other conditions e g a fault condition the corresponding information will be shown e g a fault message for the priority order see chapter The information area priority order page 25 All outputs for fire alarm are reset i e de activated If a key cabinet is installed the key to the building has to be put back into the key cabinet within 5 minutes If not a fault will be generated and a fault message will be shown in the display see chapter Key cabinet alarm reset page 57 Single with automatic disablement Like Single reset but incl the so called encapsulation
49. AGS Mies SIvenee Tsavimiceley COMM CMO able ig pox 65 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Only valid in the New Zealand convention New Zealand FB Silence switch outside switch is turned on in control unit no xx 1 e from not activated to activated state FAULT Fire brigade panel xx CONTO LEUTE FBP 1826 1828 Ext Fire Brigade Panel The ext FBP xx connected to control unit no xx is programmed as another type in the SSD or a fault in the unit PAU PUS e Ome Ol l ooe CONCE OTUN TEN Blown fuse F15 Loop 0 F16 Loop 1 F17 Loop 2 or F14 Loop 3 on the main board 5010 in control unit no xx Fuse T1 6A L 250V TR5 NOTE The fuse shall not be replaced The main board 5010 shall be replaced since more components are broken as well PAUE EHEAR Ur EOE ECON MPE EON me ONE ON The control unit current consumption is gt 3 3A gt 6 3A in alarm state and because of this the battery charging is turned off and will be so until the current consumption has decreased to lt 3 3A lt 6 3 A again FAUTE ADE T IOONI T APUC AAAS PE An interlocking input is not activated within the time set for fault activation 5 255 seconds The time is counted from the activation of the output in the interlocking combination area AAA point PP PAUCITATEM EE aore O eUe C OMO COnErO TONTE Short circuit on the connection ribbon cable to or betwe
50. Bp Change type of disablements Disconnect COM loop ol control unit 00 Change type of disablements S1 Dis Re connect loop zone line input 135 The loop will directly be shown in the Re connect list If the specified loop etc doesn t exist it will be indicated with X instead of V anda beep Use the soft key gt I to toggle between the Disconnect and Re connect list Select in the Re connect list with V in this example there is only one item and press lt 4 Re connected loop will disappear from the list indicated with a beep Disconnect or Re connect another loop or press ESC Scroll to another menu or press ESC Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 30 3 Acknowledge SERVICE signal H8 S2 When SERVICE signal is generated in the system following symbol is shown in the display s symbol area See also chapter Sensors activating SERVICE signal H4 U5 page 114 Sensor analog smoke detector Valid only for 430x and 440x sensors in NORMAL mode When service signal from a sensor is acknowledged the sensor is given a default week average sensor value same as for a new clean sensor i e 1 0 1 m First replace the sensor and then acknowledge the service signal as soon as possible The first week average sensor value after acknowledge will be calculated within one hour then each
51. C one a OEE CO O EU e oCinn gt oCiIinn This fault is indicating a cut off break on COM loop x or the COM loop voltage is too low at the end of the loop SCI n lt gt SCI n describes between which Short Circuit Isolators the cut off is located n A B 0 1 2 3 4 5 6 63 A amp B is the built in isolator in the EBL512 G3 A direction and B direction respectively If no SCI is used the information will always be SCI A lt gt SCI B If only one SCI is used e g 4313 no 0 the information will be SCI A lt gt SCI O0 or SCI 0 lt gt SCI B and so on If it is a single break cut off on the loop there will be no other fault messages If there are several breaks on the loop the message shows the last isolator before the break in the A direction incl the following isolator There will also be a FAULT No reply message for each unit that EBL512 G3 cannot find and FAULT Multiple faults NOTE Each 10 minute a new attempt is made to communicate in one direction only When all breaks are repaired corrected the communication automatically returns to communicate in one direction only 63 Panasonic Eco Solutions Nordic AB MEWO01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x SUES Eare Fane nS S CONECO NE FAUTE E Ea E e a Godlistenns CORNET ode sbiesne Earth fault is detected in control unit no xx System voltage is normally 24 V DC 24 V to e
52. EW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 26 8 Information H4 U8 This menu can be used to show the following information for the specific control unit you currently use Main board version The S W software firmware system program version downloaded to the Main board 5010 MMI board version The S W software firmware system program version downloaded to the MMI board 5011 Alarm counter The alarm counter is increased with 1 every time the c i e enters a real fire alarm condition i e fire alarm indication in the display LEDs Fire are lit and the c i e buzzer is sounding Alarms from zones in test mode will not be counted It starts on 000 and goes to 999 It can be reset to 000 via EBLWin Control unit menu Reset alarm counter The value will be retained also after the c 1 e has been completely powerless Max number of allowed alarm points that can be used in this control unit 1 e 128 256 or 512 Configured number of alarm points Serial number The manufacturer s serial number year YY week WW number of the main board NNN Used e g when upgrading max no of allowed alarm points Control unit number 00 29 Menu According to chapter Access see page 88 Scroll to menu H4 H4 Present system status a U2 Disablement by time channel U3 Open doors U4 Sensor values U5 Sensors activating SERVICE signal U6 Technical warning U7 Event log U8 Information Sc
53. G3 V2 0 x 7 1 User level 1 With the door closed anybody has access to the push button Alarms queued P8 to scroll browse through the queued alarms 7 2 User level 2A After the door has been opened with the fire brigade key Door open A symbol in the symbol area the user fire brigade personnel have access to the following push buttons Push Operation function button Pl Silence the buzzer in the c 1 e CD P2 Silence all alarm devices sounders Es P3 Reset fire alarms see below aaa NOTE Fire alarms are Fire alarm incl heavy smoke heat alarm Alert Annunciation AA alarm Key cabinet alarm Co incidence alarm if not reset automatically Acknowledged alarm New Zealand only Isolated alarm New Zealand only 28 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 7 3 User level 2B After the door has been opened with the fire brigade key Door open i symbol in the symbol area you have access to level 2A and after log on as Information only level 2B access to the following menus 29 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 7 4 User level 2C After the door has been opened with the fire brigade key Door open A symbol in the symbol area you have access to level 2A and after log on as Building officer level 2C access to the foll
54. LEU TE Valid for the 8 zones exp board 4580 the 8 relays exp board 4581 and the Inputs and outputs exp board 4583 mounted in the control unit no Xx e EBLS512 G3 cannot communicate with the board Check change the address Check the cables connections e Check if the Main board fuse F13 is broken Fuse T4A L 250V TRS PAU CE NO teem liye lt eamswOmy lO OatsCe oe WOO tr CONE Ols bligisbic goo This is valid for the I O Matrix board 4582 no x connected on COM loop x in the control unit no xx o Check the board s address i e the I O Matrix board no Jumpers JP1 JP2 and JP3 on the board Check if the board is disconnected from the loop PAURE Ney se oly sake tin annn CT aeron UNTE X MEME OLT ican ox FAULT No reply external presentation unit 69 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x XC ONET O REDE FAULT No reply fire brigade panel xx COME eau Alert Annunciation Unit 1735 1736 External Presentation Unit 1728 External Fire Brigade Panel 1826 1828 e The contact with the unit is interrupted Check the cable all connections etc Is correct complete SSD downloaded via EBLWin Check the address and SW mode settings Check if the Main board fuse F19 is broken Fuse T1 6A L 250V TRS If there is a program memory fault in the unit there will be a fault message shown briefly in the unit s display during start
55. Normal alarm devices output type Alarm devices routing equipment etc will not be activated I8 See EBL512 G3 Planning Instructions Any programmable input can also be used to activate a pre warning e g for a High Sensitivity Smoke Detector system 43 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x In case of a pre warning the following happens e The buzzer in the c i e sounds 0 8 sec each 5 sec 0 8 5 Sec e Outputs programmed for pre warning are activated e In the c i e display a presentation number zone address is shown for the first pre warning e In the c i e display a user definable text message the alarm text for fire alarm is shown if programmed Example pre warning zone 123 address 45 within zone 123 Pre warning Zone Address 123 49 so User definable alarm text for 123 45 SMOKE after the presentation number is automatically added depending on the type of alarm point 1 e SMOKE HEAT MULTI or MCP NOTE The text Menu for the soft key P4 is visible in the display only if the door in the CU is open If more than one pre warning is activated the LEDs Alarms queued L6 are blinking and the pre warnings will be automatically scrolled each five seconds Pre warnings are automatically reset see chapter Alarm reset page 39 16 2 Fire alarm The system can handle up to 15360 fire alarms but onl
56. ON i e from not activated to activated state e All programmable outputs of type Alarm devices are disabled 1 e they cannot be activated The inside switch see above has no function e The c i e built in buzzer is silenced e A fault is generated FAULT FB Silence switch active The outside switch is turned OFF i e from activated to not activated state 33 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x e FAULT FB Silence switch active will be Serviced e Any fire alarm ALARM and acknowledged alarm ACKNOWLEDGED will automatically be disabled isolated I e it has to be re enabled via menu H2 B5 Indicated by LED General disablements on the c 1 e front e Any fire alarm ALARM and acknowledged alarm ACKNOWLEDGED will automatically change the state to Isolated alarm see below and in the fire alarm list presented in the display ALARM or ACKNOWLEDGED will be replaced with ISOLATED An example 123456 7890123456 7890123456 7890123456 7890 1 First alarm 002 03 Alarm number 1 of 1 2 ISOLATED alarm Zone Address 3 gt 002 03 5 6 SMOKE T 8 3 User definable alarm text for 002 03 10 11 12 13 14 l Since this fault is always latched it has to be acknowledged via menu H6 34 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3
57. PU The EPU xx connected to control unit no xx is programmed as another type in the SSD or a fault in the unit EAU EXEINGULo NING Syo Caem Conr OOTATE The fault is to be found in the extinguishing system which has a fault output connected to a programmable supervised input in the EBL512 G3 system in control unit no xx Also check the input connections NOTE Close to the soft key area in the display there will be an additional information text Extinguishing fault EAU LE ORACOL ENS Gels EO E ox The factory settings have been changed in control unit no xx e g because of some external disturbance The main board has to be replaced FAULT wan Ee CNNI A NUDE r XAA The LED Fault is lit on a fan control module connected to control unit xx Fan no xx has been activated but the corresponding I O unit 3361 input has not been activated within the programmed time Check the fan and the cables connections NOTE In the Australian and New Zealand conventions this fault is not latched irrespective of if all other faults are latched FAUTE A EaU Wee sbieke OUTI no e UL omen ic CONECTO EEn E The fault is to be found in the Fault warning routing equipment A routing equipment fault output is connected to a programmable supervised input in the EBL512 G3 system in control unit no xx Check the input connections as well Normally used for German routing equipment connected to an expansion board 4583 input 0 P
58. Rev MPNO A e EA EE eg Instructions Fire alarm system EBL512 G3 V2 0 x a Disable routing equipment J mics Fault Disabled routing equipment Fire alarm routing Use the soft key gt I to toggle between Disable and Disabled gt Disable routing equipment Press lt to re enable Fire Fault Disabled routing equipment Re enabled routing equipment will Fire alarm routing disappear indicated with a beep di Disable Routing equipment as Disable or press ESC mics Fault ESC B1 Zone or Zone Address Scroll to another menu B2 Output or press ESC or B3 Output type Escape menu B4 Alarm devices B6 Alert annunciation function Escape menu 104 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 24 6 Alert Annunciation H2 B6 Normal function For alarm points zones programmed for Alert Annunciation via EBLWin is normally the AA function enabled via a time channel e g enabled daytime during working hours and disabled night time As an alternative the AA function can be continuously enabled always on Via this menu H2 B6 it is possible to disable the AA function 1 e the AA function will be turned off for the alarm points zones programmed for Alert Annunciation in spite of the time channel is on or if they are programmed to be continuously enabled
59. To avoid the Fault tx output s to be activated they can be disabled via menu H2 B5 or via an open door se chapter Open door page 40 Regarding the fault condition see chapters Fault page 59 and Fault messages page 61 NOTE Most of the faults have a delay Each control unit should be tested as follows Perform monthly test menu H1 Remove one battery fuse e g F2 on the Main board 5010 The following fault message is to be shown FAULT Battery not connected CU xx NOTE xx is depending on control unit xx 00 29 Put back the fuse and acknowledge the fault menu H6 Remove fuse F4 on the Main board 5010 The following fault message is to be shown FAULT Supervised output 0 CU xx NOTE xx is depending on control unit xx 00 29 Put back the fuse and acknowledge the fault Check the manual call points the glass Take required measures Use the manual call point test key to activate fire alarm Check some control outputs Are they activated according to programmed control expressions 155 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 33 How to change paper in the printer When the paper roll is almost empty a red line appears on one edge of the paper Change the paper roll before it is completely empty Always have a spare paper roll on site paper width 58 mm Change the paper roll as follows e Read all instructions bef
60. V CU05 vV CUO6 V CU07 V CU08 V CU09 V CU10 V CU11 V CU12 V CU13 vV CU14 vV CU17 V CU18 V CU19 V 146 During the synchronization the progress symbol for each control unit is shown In the example are CU15 amp CU16 not programmed Date and time for the latest completed synchronization The symbol V means that the synchronization succeeded If the symbol V is missing the synchronization has failed Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 30 9 Activate Reset outputs H8 S8 Any output can be activated i e the function can be tested Can also be done via EBLWin The selected output will be activated no matter if the control expression is true or not The selected output will be reset only if the control expression is false not true If the control expression is true when you reset the output via menu H8 S8 the output will remain activated until the control expression is false not true again Menu According to chapter Access see page 88 Scroll to menu H8 a REA EASE SERVICE signal Clear weekly average Test of alarm devices Safe shut down of control unit Activate address in alarm mode Synchronize the control units Activate Reset outputs Scroll to menu S8 S8 Activate Reset output Via menu S8 can loop unit output control unit output and expansion board output be activated and rese
61. V anda beep Use the soft key gt I to toggle between Activate and Deactivate list 150 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Activate Select in the Deactivate Interlocking output area ___ point _ _ list with VW in this Deactivate list 1 example there is only Interlocking output area 001 point 01 i none and press The deactivated output will disappear from the list indicated with a gt beep Activate Continue as above or Interlocking output area oo point 00 press ESC ESC C2 Activate deactivate interlocking output Scroll to another menu or press ESC 151 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 31 3 Disable re enable interlocking output H9 C3 Interlocking outputs Type Interlocking can be individually disabled via this menu and collectively via menu H2 B3 The Interlocking Combination Area Point is to be entered to disable the output Up to 400 interlocking outputs can be disabled per control unit but max 4000 for the whole system Disabled interlocking outputs are listed in menu H4 U1 from which it is also possible to get a print out The LED Fault Disablements General disablements L10 is also indicating one or more disabled interlocking outputs Menu According to chapter Access see page 88 Scroll to m
62. a EBLWin when you are logged on If a real fire alarm is activated by an alarm point not in test mode the normal fire alarm functions will be activated i e fire alarm presentation outputs sounders activated routing equipment fire brigade tx activated etc See also chapter The information area priority order page 25 NOTE If the control unit door is left open the output s for routing equipment fire brigade tx might be disabled if set so in EBLWin There will be an automatic test mode ending one hour after the latest tested alarm point One or more zones in test mode are indicated by the LED Test mode L8 The green polling LED in the 440x detectors will be turned off in test mode The zones are set one by one in test mode and the test mode has to be ended for each zone one by one 131 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Menu According to chapter Access see page 88 Scrollto menu H7 to menu H7 H7 Perform ZONE TEST ng Set in test mode Zone 00 Write the zone number ff Set in test mode Fy Press 4 to start the test e g 001 Zone Wo mode Indicated by V nal and a beep If the specified zone doesn t AERO WEES NN OIG lt eessesese sees eat toc soeeecee Zone 001 exist it will be indicated with X instead of V and a beep All zones set in test mode will be shown in the End test mode
63. a o Regarding the SERVICE signal levels see Planning Instructions chapter SERVICE signal Menu H4 U5 is a list of the sensor s having activated SERVICE signal NOTE SERVICE signal is only information that the sensor has to be replaced with a new clean sensor soon After the replacement the SERVICE signal has to be acknowledged see chapter Acknowledge SERVICE signal H8 S2 page 136 Menu According to chapter Access see page 88 Scroll to menu H4 H4 Present system status ae U2 Disablement by time channel Open doors Sensor values Sensors activating SERVICE signal Technical warning Event log Information Scroll to menu US Sensors activating SERVICE signal ee Sensor Zone ZZZ address AA needs service If there are no sensors technical number xxxxxx List is empty will be 2012 11 10 09 09 15 shown It is a list in which you can scroll Sensor Zone ZZZ address AA needs service l with V or A technical number xxxxxx 2012 10 03 19 09 35 If printer is mounted the soft key Print will be visible else not Press Print for a print out of Number of sensors 2 all items in the list U5 Sensors activating SERVICE signal Scroll to another menu or press ESC NOTE During printing Print will be replaced with Abort printing 114 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 26 6 Technical warning H4 U6 A technical wa
64. alarm incl test mode alarm Heavy smoke heat alarm Alert Annunciation AA alarm Key cabinet alarm Acknowledged alarm New Zealand only 19 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Push buttons on the Fire Brigade Panel FBP Push button Operation function Silence buzzer yellow Used to silence the buzzer in the c 1 e when it is sounding T P2 Silence Alarm devices Used to silence alarm devices sounders in the building EB red P 3 Reset green 3 when they are sounding Silenced Alarm devices 1s indicated to the right in the display s soft key area a symbol near this button see page 23 Used to reset Fire alarms see below Co incidence alarms if not automatically reset For more information see Alarm reset page 55 NOTE P3 has to be pressed for gt 0 5 sec Disable yellow NOTE This button exists in the Australian front only Disables zones in alarm Soft keys grey The operation function is shown above the key in the display i e the soft key area The function of a soft key may vary depending on the situation If nothing is shown above the key in the display the key has no function for the moment Alarms queued grey Used when LEDs Alarms queued L6 are lit to scroll browse through the queued alarm points zone address Function see chapter Fire alarm page 44 under LEDs Alarms que
65. alarm status or via the Reset button P3 See chapter Alarm reset page 55 51 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x An example Co incidence alarm zone 123 address 45 Co incidence alarm Zone Address 23 49 SMOKE User definable alarm text for 123 45 If more than one Co incidence alarm not dependent on each other are activated the LEDs Alarms queued L6 are blinking and the Co incidence alarms will be automatically scrolled each 5 second If two or more zones or alarm points zone addresses dependent on each other are in alarm status at the same time normal fire alarm see above will be activated in the system The co incidence alarm function can be turned on off via a time channel 16 7 Delayed alarm Delayed alarm is an option that has to be enabled via EBLWin for the alarm point respectively The delay time 0 255 sec is for the whole system set via EBLWin System Properties page 1 The delay time will be added at the end of the alarm algorithm when a fire alarm normally would have been activated For that reason this extra delay time should be as short as possible The Delayed alarm will be activated when the delay time countdown has started and will be activated until the delay time has run out and a normal fire alarm is activated No outputs will be activated In case of a Delayed alarm the following happens
66. an acknowledge time and reset within an General heavy smoke heat alarm and individual alarm points zones 49 Panasonic Eco Solutions Nordic AB MEWO01552 16 5 16 5 1 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x investigation time otherwise the output s for routing equipment fire brigade tx will be activated See EBL512 G3 Planning Instructions for more information regarding the AA function Acknowledgement and reset of the AA alarm can be done on an AA unit 1735 1736 or an AA controller 1740 See also chapter Alert Annunciation page 57 First alarm 010 01 Alarm number 1 of 1 Alert annunciation Zone Address 010 01 svoe User definable alarm text for 010 01 Ackn alert annunciation NOTE The Ackn alert annunciation text is only visible if an AA alarm is activated and not if this key is used for the Evacuate function Key cabinet alarm The fire brigade uses a key cabinet to store a key to the building One programmable input per c i e can be used to connect a key cabinet Key cabinet opened before a fire alarm If the key cabinet is opened before a fire alarm e g if somebody illegally breaks into the key cabinet a key cabinet alarm will be activated An example XX Control Unit number 00 29 50 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x First alarm 000 00 Alarm number 1 of 1 A
67. anations to the words expressions to be found in connection with a TLON Network See also separate TLON Technical description TLON TeleLarm Local Operating Network a LonWorks based network for communication between several units nodes The protocol is LonTalk and the transmission works with doubly terminated bus topology Echelon FTT 10 To connect a control unit to the network a TLON connection board has to be plugged in the control unit EBL512 G3 also supports redundant TLON system communication In this case two TLON connection boards have to be plugged in each control unit A network can be one channel FIT 10 or several channels connected via routers In the TLON Network a sub net a channel Routers are also used to increase the maximum cable length node to node in a network Router or Repeater is the same type of unit different configuration All network programming configuration are made with the PC program TLON Manager LED LED Light Emitting Diode Yellow green or red optical indicator lamp External Indicator LED A unit with an red LED connected to a base ASB CDB or a detector with an output for an ext LED Lit when the built in LED in the detector base 1s lit Display LCD LCD Liquid Crystal Display Display in the c i e or Display unit for presentation of fire alarms fault messages etc In EBL512 G3 it is a graphical monochrome LCD 320 x 240 dots with bac
68. and Fire brigade tx L12 and listed in menu H4 U1 Silence buzzer with door switch Via EBLWin can be set that the built in c 1 e buzzer will be silenced when the c 1 e door is open 40 Panasonic Eco Solutions Nordic AB MEWO01552 15 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Technical number Presentation number 15 1 Technical number for COM loop units The technical number NNNNNN is used when programming all units connected to the COM loops Technical number is also used to identify which unit has generated a fault NN N NNN 001 255 The technical address on the COM loop The addresses don t have to be in sequence The connections on the COM loop don t have to be in sequence The address is for each unit set with the programming tool 3314 4414 0 3 COM loop number 00 29 The control unit address number Don t have to be in sequence The connections to the TLON network don t have to be in sequence The address is set with a PC SW TLON Manager NOTE Since technical address OOO cannot be used the total number of addresses is 4 x 255 1020 4 Panasonic Eco Solutions Nordic AB MEWO01552 15 2 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Presentation number For each fire alarm point input zone a presentation number NNN NN has to be programmed The presentation number is shown
69. ansion board 8 relay outputs expansion board Inputs and outputs expansion board Regarding the expansion boards see also the EBL512 G3 Planning Instructions and drawings 3 1 3 Power supply The main power source is a built in switched power supply rectifier 5037 230 V AC 24 V DC 6 5 A The second power source is a backup battery 2 x 12 V In the c i e Printer 5058 is a spare part for the c i e type 5000 with a printer i e it comes without a mounting frame etc 13 Panasonic Eco Solutions Nordic AB MEWO01552 3 2 3 3 3 4 3 9 3 5 1 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x is space for two 27 Ah batteries Larger batteries up to 65 Ah have to be placed outside the c 1 e The batteries and the power supply are connected to the Main board 5010 which handles the charging of the batteries etc See the EBL512 G3 Planning Instructions chapter Power supply for more information Software S W versions Due to continual development and improvement different S W versions can be found When installing a new control unit in a system with older control units you might have to upgrade the S W in the old control units or download an older S W version in the new control unit The same S W version is required in all control units in a TLON Network Documents The following documents are available e Planning instructions MEWO1351 e Operating Instructions this doc
70. are isolated disabled See EBL512 G3 Planning Instructions 48 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x The following happens in case of a heavy smoke heat alarm e Outputs programmed for heavy smoke heat alarm are activated e Each heavy smoke heat alarm is presented with a title 1 e Heavy smoke or Heavy heat will be added to the normal fire alarm information First alarm 002 03 Alarm number 1 of 1 Heavy smoke Zone Address 002 03 SMOKE User definable alarm text for 002 03 1 zone in alarm The printer if available will print each heavy smoke heat alarm e g Heavy Smoke Zone 002 Address 03 SMOKE YYYY MM DD hh mm User definable alarm text if programmed Heavy smoke heat alarm will be reset when the fire alarm respectively is reset see chapter Alarm reset page 55 16 4 Alert Annunciation alarm AA alarm When the AA function is enabled indicated by the LED Routing equipment Fire brigade tx delay L14 the indications print outs actions etc are the same as for a normal fire alarm see above except for the c i e output for routing equipment fire brigade tx which will not be activated directly There will also be a title i e Alert annunciation or Alert annunciation acknowledged will be added to the normal fire alarm information The AA alarm has to be acknowledged within
71. area The function of the soft key respectively is shown here 1 e it will vary depending on the situation convention and language If no text is shown the soft key has no function When Evacuate is not used this soft key may be used for Alert Annunciation acknowledge In the New Zealand convention it is used for Acknowledge alarm Silenced Alarm devices is indicated by the symbol PX to the right in this area 23 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 6 2 The symbol area The symbol area is at the top of the display see chapter 6 1 The following table explains the meaning of each symbol The symbol area Symbol Indicating The door is open in any c 1 e or external FBP in the system See also page 40 See also menu H4 U3 Loss of mains in any c 1 e or ext power supply unit in the system 1 e the unit respectively is out of 230 V AC and is power supplied via batteries The week average sensor value is over the service level for one or more analog smoke detectors in the system See also page 114 and menu H4 US The c 1 e is set in Sensitive fault detection mode via menu H5 A2 see page 120 One or more Technical warnings are generated in the system See also menu H4 U6 Note that the symbol area may be suppressed see 6 3 24 Panasonic Eco Solutions Nordic AB MEWO01552 6 3 Rev Operating Instructions Fir
72. arm device it will be treated as if it does not exist see below Disabled output Even if its control expression trigger condition is fulfilled true the output will not be activated Menu According to chapter Access see page 88 Scroll to menu H2 H2 Disable or re enable nd B2 Output B3 Output type B4 Alarm devices B5 Routing equipment B6 Alert annunciation function Escape menu B2 Output Scroll to menu B2 Via menu B2 can a loop unit output C U output S0 S3 RO R1 and exp board output be disabled Disable output Use the soft key change Loop unit ooo0o output O type of disablements to toggle between Loop unit output Control unit output S Control unit output R Exp board output Write loop unit technical number and output number and press lt 4 to disable which will be indicated with V and a beep The output will directly be shown in the Change type of Re enable list disablements 97 Panasonic Eco Solutions Nordic AB MEW01552 Rev Disable output Loop unit ooooo output 0 Re enable list 1 Loop unit 000001 output 0 Write loop unit technical number and output number e g 000001 and 0 a Be Change type of disablements gt j Disable output Loop unit ___ output _ Automatic re enable No H Re enable list 1 M Loop unit 000001 output O of disablement a Disable output Loop unit ooo0o output 0 gt Change type Cha
73. arth is normally 12 5 V O V to earth is normally 11 5 V Voltage to earth lt 3 4 V Earth fault minus Voltage to earth gt 18 3 V Earth fault plus Check all cables for damage etc The function of the control unit cannot be guaranteed Call for service personnel engineer EAI E N Ea ela itch ollie A avORUUE SNE UN Eaa Check all cables for damage etc connected to the unit SOULE TEx pano mol IO cicek Se Ve laneia oll uliaivie sox This is valid for the exp boards 4580 4581 amp 4583 i e no x mounted in the control unit no xx There is some internal fault on the board which has to be replaced EAUTICRE PAn on local o lt CONERO INEN This is valid for the I O Matrix board 4582 no x connected on COM loop x 0 3 in the control unit no xx There is some internal fault on the board which has to be replaced EAE TE Ce rna l a eee a COn EEO EEX The fault is to be found in the external power supply equipment which has a fuse fault output connected to a programmable input in control unit no xx FAULT External power supply CON T ORNINI E The fault is to be found in the external power supply equipment which has a fault output connected to a programmable input in control unit Xx 64 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x PAULL External preoc ntat ron UNIL Xx COme TOTEN EEE 1728 Ext Presentation Unit E
74. be after 5 min yyyy mm dd hh mm Serviced two restart faults The code will be 00 50 after FAULT Restart control unit 00 code 03 Pawerott Poweron address 0 restart and 03 53 after a yyyy mm dd hh mm Serviced countdown teirt Address 0 This fault has to be acknowledged see chapter FAULT Fault 1 2 is selected Acknowledge H6 page Previous Next 129 page page NOTE Before the very first safe shut down the Flash ROM is empty Then every time safe shut down is performed the valid data will be saved in the Flash ROM i e any old data will be overwritten When the c 1 e is powered up the data stored in the Flash ROM will be used WARNING If safe shut down is not performed just before you power off a control unit then by power on the Flash ROM might be empty i e default settings will be used or the stored data might be old and not valid 142 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 30 7 Activate address in alarm mode H8 S6 One alarm point zone address not a whole zone can be set in alarm The built in LED in the alarm point e g a detector will be turned on to indicate the alarm NOTE All outputs standard and programmable which would have been activated by a normal fire alarm from the same alarm point will now also be activated Menu According to chapter Access see page 88 Scroll to menu H8 a Scroll t
75. c AB MEWO01552 19 3 19 4 19 5 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x In a redundant network two Projects have to be created and installed The Projects have to be identical but with different Project names One project has to be installed for Network no O and one has to be installed for Network no 1 If a redundant TLON Network shall be used a PC is connected to the modular connector J11 Network no 1 and the same procedure as for Network no 0 is done for Network no 1 NOTE After the TLON Network installation download it is highly recommended to restart the control units Add a Control Unit in a TLON network When adding a new control unit to a running installation you have to have the same software S W version in all control units Often the new control unit has a newer version than the existing control units Normally the latest version is the best to use 1 e the control units in the running installation have to be upgraded As an alternative it is possible to download an earlier S W version in the new control unit Both alternatives are described in Planning Instructions MEW01551 Open the current project in TLON Manager add one control unit and install download it according to the separate TLON network Operating Instructions MEWO01361 Also see 19 2 1 above Open the SSD for the current system via EBLWin Add one control unit and the units connected to it and download
76. communication returns to communicate in the A direction only T2 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x A fault on the supervised input x on the expansion board 4583 with address x in control unit no xx Check the cables connections cut off or short circuit FAUINES Supervised OUuLDUL x COME ols Winders 5x If the output is programmed for sounders type Alarm devices it is also indicated by LED Fault Disablements Alarm devices L11 blinking If the output is programmed for fire brigade tx type Routing equipment it is also indicated by LED Fault Disablements Fire brigade tx L12 blinking If the output is programmed for an extinguishing system type Extinguishing there will be an additional information text close to the soft key area in the display Extinguishing wire fault x 0 SO Short circuit break on the connected cable equipment and or blown fuse F4 on the main board 5010 x 1 S1 Short circuit break on the connected cable equipment and or blown fuse F5 on the main board 5010 x 2 S2 Short circuit break on the connected cable equipment and or blown fuse F6 on the main board 5010 x 3 S3 Short circuit break on the connected cable equipment and or blown fuse F7 on the main board 5010 Fuse T500mA L 250V TRS Calibration not performed via menu H5 A1 Connected equipment might be stolen Resistor s mi
77. ctions Fire alarm system EBL512 G3 V2 0 x 31 4 Change password H10 For security reasons the password could be changed Menu According to chapter Access see page 88 Scroll to menu H10 H10 Change password a el Log in name Password H New password Enter the old password Log in name The six digits are replaced the new password and Password by in the display again the new pass New password Verify 1744x word Incorrect password NO change or Password changed ESC 5 The password is now changed to the new one Perform monthly test Scroll to another menu or Disable or re enable press ESC or Escape Set calendar and clock Present system status Service FAULT Acknowledge Perform ZONE TEST menu Maintenance Interlocking outputs and inputs H10 Change password As long as you don t close the door you can enter the menu system again without a password NOTE After change of password it is recommended do a Safe shutdown of the control unit see menu H8 S5 This will save the SSW data e g the new password in a Flash ROM see page 141 If the valid password s are unknown EBLWin has to be used change the password s 154 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 32 Annual control The building occupier is highly recommended once a year to do some tests beside the monthly tests
78. d to the USB connector above the front panel l Connected to the modular connectors J10 TLON network 0 or J11 TLON network 1 on the main board 5010 118 Panasonic Eco Solutions Nordic AB MEWO01552 27 1 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Calibration of supervised outputs H5 A1 Supervised monitored outputs The voltage outputs SO S3 in each control unit The voltage outputs VOO0O VO1 in the COM loop output unit 3364 The voltage outputs 0 2 on the I O exp board 4583 When all alarm devices sounders etc have been connected including required end of line devices and when the SSD is downloaded a calibration has to be done Function The calibrated range is 4K7 50K and 470 5x470 nF respectively If the actual value at any time differs from the calibrated value a small tolerance or if the calibrated value is outside the calibration range a fault will be generated Menu According to chapter Access see page 88 Scroll to menu HS di Start calibration of supervised outputs press lt Calibration completed successfully Ni Calibration of supervised outputs Sensitive fault detection mode Service mode for COM loop Display current consumption in control unit Display current consumption on COM loop Display statistics for communication Activate address setting mode for DU SSD information A1 Calibration of supervised outputs Calibration is ready
79. e 60 minutes will generate a fault If a fault is generated it will automatically be Serviced after these 60 minutes The battery should normally be replaced NOTE The battery check is performed every 12 hour i e it can take up to 12 hours until the fault status will be corrected NOME exe OE aO veo rO NUn ea lt lt System voltage lt 21 V DC in control unit no xx Check the power supply rectifier 5037 output voltage which shall be 24 V DC Replace 5037 if required 67 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x FAUTE how VOE e OU PUE Un Eaa System voltage lt 21 V DC in the external power supply unit 3366 Check the power supply rectifier 1537 output voltage which shall be 24 V DC Replace 1537 if required PAUE E A MNS C ONECO EUNE a gt The fault is activated 1 300 minutes after Loss of mains 1 e no 230 V AC 6 Blown mains fuse Blown fuse F1 on main board 5010 Fuse T6 3A H 250V 5x20 mm ceramic FAULT Mains external power supply CONTEO RUNTER This is valid for external power supply equipment which has a fault output connected to a programmable input in the EBL512 G3 system The fault is activated 1 300 minutes after the input is activated e Loss of mains i e no 230 V AC to the ext power supply equipment e Blown mains fuse e Check the programmable input connections PACOTE EMaANN This is valid fo
80. e SSW This is very serious Call for service personnel engineer FAUTE A Reo E icles ONE rOl ahah gay code xx address yyyyyyyyyy A restart has occurred in control unit no nn SSD and S W download will automatically be followed by a restart Also you can manually do a restart see chapter Restart page 84 The following restart codes are because of some external disturbance and are not normal 1 e call for service personnel engineer xx 01 Watchdog Reset Xx 02 Accidental jump to reset vector xx 04 19 Unexpected interrupt Xx 20 S W monitoring fault Xx 13 will always be followed by an address yyy which is important to write down yy y memory address before restart Write down the address and inform the service personnel engineer FAULT Sensor Zone xxx address xx technical number XXXXXX The analog smoke heat or multi detector is faulty The detector s built in self verification function has reported a fault The detector has to be replaced FAUCET AS NOr C O TEO E O E ae aC O OnE SG OC nn A Se inn SCI nn lt gt SCI nn describes between which Short Circuit Isolators the short circuit is located nn A B 00 01 02 03 04 05 06 07 63 A amp B is the built in isolator in the EBL512 G3 c 1 e A direction and B direction respectively If no SCI is used the information will always be 71 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm
81. e The buzzer in the c i e sounds 0 8 sec each 5 sec 0 8 5 Sec e In the c i e display a presentation number zone address is shown for the first delayed alarm Also a user definable text message the alarm text for fire alarm is shown if programmed Example Delayed alarm zone 123 address 45 within zone 123 52 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Delayed alarm Zone Address 123 49 so User definable alarm text for 123 45 SMOKE after the presentation number is automatically added depending on the type of alarm point 1 e SMOKE HEAT MULTI or MCP NOTE The text Menu for the soft key P4 is visible in the display only if the door in the CU is open If more than one Delayed alarm is activated the LEDs Alarms queued L6 are blinking and the Delayed alarms will be automatically scrolled each 5 second Delayed alarms are automatically reset see chapter Alarm reset page 55 16 8 Alarm Acknowledgement Facility AAF One or more Alarm Acknowledgement Facility Controls are used in the system See EBL512 G3 Planning Instructions chapter Alarm Acknowledge ment Facility AAF for more information regarding the AAF function During the Acknowledgement Period 10 60 sec the following information a list if many is shown in the c 1 e display AAF zone zz activated dd mm yyyy hh mm The AAF Contr
82. e alarm at short circuit 75 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x INO ON EESE aE A TOCE O Shown only in the affected control unit e Check that MMI board is selected in the SSD EBLWin Control unit properties e Fault in the Main board 5010 software or hardware Check the cable between the Main board and MMI board This is a very serious fault Call for service personnel engineer immediately e In conjunction with SSD download Erase the SSD in the control unit and download the SSD again External fault User programmable text Programmable input is connected to any external equipment s fault output User definable fault message lt 40 characters has to be programmed via EBLWin Note The prefix FAULT will not be automatically added 76 Panasonic Eco Solutions Nordic AB MEWO01552 18 2 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Fault acknowledge The LEDs Routing equipment Fault tx activated L13 and Fault Disablements General fault L9 are turned on LEDs Fault Disablements Alarm devices L11 System fault L7 and or Fault Disablements Fire brigade tx L12 might be turned on as well Output s for routing equipment Fault tx is are activated Output s for general fault is are activated Output s for general charge fault might be activated One or more fault messag
83. e alarm system EBL512 G3 V2 0 x System information in the LCD EBL512 G3 control unit number date and time are displayed The exact look is convention language dependent One example of the information area EBL512 G3 Control Unit XX yyyy mm dd hh mm yyyy mm dd Date Year Month Day Control Unit XX 00 29 hh mm Time hour minute NOTE When the Russian Ukraine Australian or the New Zealand language is selected the date is shown as follows dd mm yyyy User definable system information User definable system installation information created and downloaded via EBLWin can be displayed in the middle of the display Two rows are available In total 38 characters This information is shown in all control units in the system One example EBL512 G3 Control Unit 00 Panasonic Eco Solutions Nordic AB 2011 02 02 10 58 26 Panasonic Eco Solutions Nordic AB MEWO1552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 7 User level User name amp Password EBL512 G3 has different user levels for different kind of users To log on to an EBL512 G3 version gt 2 0 a User name and a Password are required Ten different User names with individual Passwords can be used Each User name is for a specific user level which has access to specific menus according to the following table User level User level name Required action according type equipment to EN54 2 No Hole in the Ple
84. e alarm system EBL512 G3 V2 0 x The information area priority order When the control unit system is in normal operation quiescent state i e no fire alarms no faults no disablements no service signals no zones in test mode no activated interlocking in outputs and or Alert Annunciation function not enabled only the LED Operation L5 should be lit and some system information is shown in the control unit display However the system information has the lowest priority and more important information suppresses less important In some cases also valid for the symbol area The priority order is shown in the following table Priority Event N N ed Co incidence alarm N N N 7 Yes Routing equipment left isolated 10 11 12 Zones in Test mode Interlocking input output active Ys 13 14 NOTE Fire alarms are Fire alarm Heavy smoke heat alarm Alert Annunciation AA alarm Key cabinet alarm Acknowledged alarm New Zealand only Isolated alarm New Zealand only The different type of events and the menu system are described in other parts of this document Regarding System information see 6 4 The AAF function is used in conjunction with an AAF Control which is available on the Australian market only 8 Only valid for Belgian British Standard Hungarian Spanish and Ukrainian conventions 25 Panasonic Eco Solutions Nordic AB MEWO01552 6 4 6 4 1 Operating Instructions Fir
85. e closed when the detectors controlling the door are tested in test mode 92 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 24 Disable or re enable H2 A whole zone one or more alarm points within a zone and or control outputs can be disabled via menus H2 B1 B2 This function can be used for temporary disablement e g craftsmen working in the premises etc If the function Enhanced disablement is enabled default disabled alarm points cannot activate Pre warning fire alarm and fault If this function is not enabled via EBLWin disabled alarm points cannot activate Pre warning and fire alarm but fault can be generated This is a violation to the EN54 2 standard An Addressable manual call point can be disabled but shall normally not be disabled However when a whole zone is disabled the addressable manual call points will not be disabled for safety reasons This function can depend on convention country Up to 512 whole zones can be disabled via menu H2 B1 Up to 200 alarm points zones address can be individually disabled via menu H2 B1 COM loops zone interface inputs and or MIO inputs can be disabled via menu H8 S1 Alarm points disabled via time channels are not limited and must not be counted Up to 200 outputs can be individually disabled via menu H2 B2 Disabled output will stay in or return to the normal condition for the output respec
86. e in the valid conventions l The soft key Evacuate is only visible valid in some conventions i e the Belgian British Standard Hungarian Spanish and Ukraine conventions 14 Alt when a programmable input is activated One input per c i e 15 Alt when the programmable input is de activated 39 Panasonic Eco Solutions Nordic AB MEWO01552 14 Operating Instructions Fire alarm system EBL512 G3 V2 0 x Open door 14 1 14 2 A special key is used to open the control unit door to get access to the front system The same type of key is also used to open the ext FBP door If any door in the system is open the following symbol is shown in the display s symbol area See also chapter Open doors H4 U3 page 110 Outputs for routing equipment Fire brigade tx and Fault tx Via EBLWin the following can be programmed default settings shown Disable routing equipment by door switch None Open door in a C U or an ext FBP will not disable the output s for routing equipment Fire brigade tx and fault tx O Any control unit door Open door in any C U will disable the output s for routing equipment Fire brigade tx and fault tx in all C U s O Any door Open door in any C U or any ext FBP will disable the output s for routing equipment Fire brigade tx and fault tx in all C U s Disabled outputs for routing equipment are indicated by the LEDs Fault Disablements General disablements L10
87. e zone and Weekly average zone 001 address 01 cleared address numbers e g 001 and 01 man S3 Clear weekly average Continue like above or scroll to another menu or press ESC 138 Panasonic Eco Solutions Nordic AB MEWO01552 30 5 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Test of alarm devices H8 S4 The programmable outputs of type Alarm device can be collectively activated via this menu H8 S4 which makes it possible to test the alarm devices 55 The test cannot be started if a fire alarm already is activated in the system One or all control units can be selected When the test starts the alarm devices will sound continuously steady for approx 5 seconds be silent for approx 25 seconds sound for approx 5 seconds and so on NOTE Disabled and silenced alarm devices will also be tested The test will continue for one hour if not stopped via this menu H8 S4 or if a fire alarm is activated in the system Menu According to chapter Access see page 88 Scroll to menu S4 S2 Acknowledge SERVICE signal Clear weekly average Test of alarm devices Safe shut down of control unit Activate address in alarm mode Synchronize the control units Activate Reset outputs S4 Test of alarm devices Test of alarm devices control unit do All Write control unit number Press lt to start test or press gt for All Press lt to start the test 5 Includi
88. eaUsouseaeeGueOUsaUseUeeGeeGUCOUCSUsSQeeOUCOUCOUSSUSOGHCNSOUSSUSSGEOGUSEESOUSSOCSQUCRESOUSSOSSOESOESSUSOUSSOUSGUCSESOUSSOUSQHOGESOUSOUSSOUSGUCSESSUSSUSSONOGESOUSOUSSOUSGUCOESEUSSUONCOHSOESOuSSgueouCUSoUSooesoucusousoussoed The FBP is used by the fire brigade personnel to see which alarm point s zone s having activated fire alarm and to take required operational control of the system In the graphical display the information displayed in the upper part is depending on how many alarm points zones having activated fire alarm In the middle part will the fire alarms be shown 1 e one alarm point or one zone together with a user definable alarm text if programmed plus some other information External FBPs are also available The CP is used to communicate with the system i e for commissioning monthly tests maintenance etc To get access to the system a menu tree with main and sub menus and for operational control of the system up to ten User names can be used for three different User level types A Password six digits for each User name is required The CP has several system status LEDs and a keypad The same User names and Passwords for the different user levels will be used for logon to the Web server 17 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x In the Australian front only below the P3 button there is also a yellow Disable push button with
89. en service signal has been activated in the system contact your local dealer for cleaning replacement of the sensors detectors Metal objects must absolutely not be stuck into the sensor detector Static electricity might destroy the detector Defective faulty discarded and replaced sensors detectors shall be taken care of as radioactive waste They shall be packed in chock absorbing material to make a stable parcel PLEASE NOTE Damaged sensors detectors shall also be packed in a sealed packet whose surface must not be contaminated that is not be soiled with loose radioactive dust National regulations have to be followed 161 Panasonic Eco Solutions Nordic AB MEWO1552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 38 Revision history The changes in conjunction with the latest revision are when possible written with red font colour in the document 162 This page has deliberately been left blank Panasonic Panasonic Eco Solutions Nordic AB Jungmansgatan 12 SE 211 19 Malm Sweden Tel 46 0 40 697 70 00 Fax 46 0 40 697 70 99 E mail info pesn eu panasonic com Internet http pesn panasonic se ISO 9001 NATIONAL ACCREDITATION OFCERTIFICATION BODIES
90. en the expansion boards 458x in the control unit xx EBL512 G3 EAUCTE T e O aD INn C Aa CONC rO TUNA E The key cabinet has been opened without a prior fire alarm i e if somebody has opened the key cabinet illegally or The key cabinet has not been closed within 5 minutes after reset of all 66 Panasonic Eco Solutions Nordic AB MEWO01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x fire alarms in the system PAUCI ele satis e Cle OMe Ojos CORTEO E e The two wires L SA and C SB for COM loop no x 0 3 in control unit no xx have been mixed alternated Check correct the wire connections FAULT EO OOP UNTE 937 ONS x adr eSa x technical number XXXXXX The unit not a detector is not all right 1 e the unit is out of order faulty The unit has to be replaced FAULT Low battery capacity CONCE lke Ulin Mie lt Battery in control unit no xx internal resistance gt 0 6 Q The battery might be too old Cables fuses etc for externally placed batteries might cause a voltage drop Check adjust the rectifier power supply voltage 24 V DC Check the charging voltage over the battery respectively 13 5 13 8 depending on the actual charging step Check the voltage over a disconnected battery fully charged gt 13 V In the New Zealand convention only The battery charging is turned off 60 minutes every 24 hour A battery voltage lt 24 4 V during thes
91. enu H9 H9 Interlocking outputs and inputs e C1 Activated interlocking outputs inputs C2 Activate deactivate interlocking output C3 Disable re enable interlocking output Scroll to menu C3 C3 Disable re enable interlocking output Via menu C3 can interlocking outputs be disabled re enabled Disable Write area number and Interlocking output area doo point 00 address and press lt I to disable which will be indicated with V and a beep The output will directly be shown in the Re enable list Write the area number Disable If the specified output and point e g 001 and Interlocking output area 001 point 01 doesn t exist it will be n reer wa 0 eae Interlocking output area 001 point 01 beep Use the soft key gt I to toggle between Disable and Re enable list 152 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Disable Select in the Re enable Interlocking output area point _ _ list with V in this example there is only Re enable list 1 Interlocking output area 001 point 01 a ApH and press The re enabled output will disappear from the list indicated with a beep Disable Continue as above or Interlocking output area doo point 00 press ESC ESC C3 Disable re enable interlocking output Scroll to another menu or press ESC 153 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instru
92. es etc PC S W A PC S W is a program used for programming commissioning etc It has a version number Panasonic Eco Solutions Nordic AB MEWO01552 2 Operating Instructions Fire alarm system EBL512 G3 V2 0 x Definitions Explanations 2 1 2 2 2 2 1 2 2 2 2 2 3 2 2 4 2 2 9 2 2 6 2 2 1 Definitions explanations abbreviations etc frequently used or not explained elsewhere in the document PESN AB Panasonic Eco Solutions Nordic AB Alarm points Units which can generate a fire alarm in the control unit i e analog detectors sensors conventional detectors manual call points etc Smoke detector Analog and conventional photoelectric optical smoke detectors are available Sensor Sensor Analog detector Analog detector Contains an A D converter The Control Unit pick up the digital values sensor values for each detector individually All evaluations and decisions are then made in the c i e Analog detectors are addressable an address setting tool is used for the detector s COM loop address and mode settings An analog detector has to be plugged in an analog sensor base ASB Analog Sensor Base ASB An analog detector is plugged in an ASB which is connected to a COM loop see below Conventional detector A detector with only two statuses i e normal or fire alarm The detector has a closing contact and a series alarm resistor Normally plugged
93. es incl date and time are shown in the control unit display If Fault latching is selected in EBLWin default after the time might be shown Serviced the fault is already serviced corrected Example Fault messages shown in the control unit display FAULT No reply zone 123 address 01 technical number 000025 2009 10 02 15 22 serviced FAULT No reply zone 123 address 03 technical number 000027 2009 10 06 09 25 FAULT No reply zone 234 address 01 technical number 002112 2009 11 06 15 25 Number of not ackn faults in system 5 Extinguishing fault Extinguishing wire fault e Login according to chapter Access page 88 e Use menu H6 access level 2B for fault acknowledge see chapter FAULT Acknowledge H6 page 129 Menu H6 is a list showing a maximum of 300 faults not acknow ledged faults and or acknowledged but not serviced corrected faults Indicating that output for routing equipment Fault tx is activated Only valid for the VdS convention If one of the faults is FAULT Extinguishing system control unit xx also the information text Extinguishing fault will be shown If one of the faults is FAULT Supervised output x control unit xx and the output type is Extinguishing also the information text Extinguishing wire fault will be shown The information texts are shown also during a fire alarm T1 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alar
94. for different types of detectors It is however not always the best action to change detector type Here is a list of other actions programmed via EBLWin which can be used Another alarm algorithm can be used e g during working hours e Alarm delay for smoke detectors sensors can be used e Two zone or two unit dependent co incidence fire alarm activation can be used e In an installation with addressable detectors sensors e g EBL512 G3 the affected detectors can be individually disabled or whole zones for temporary work in the premises Bear in mind that the smoke spreads and consideration must be taken to adjacent detectors zones Disablements can be done automatically via a time channel built in or external or via menu H2 Automatic re enabling can be used e If there is an alarm organisation for the personnel on site the alert annunciation function can be used e Pre warning can be used as information before a fire alarm is activated 160 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 37 Information regarding radioactive radiation source Today Panasonic have no ionization smoke detectors but old detectors connected to the EBL512 G3 installation might be old smoke sensors detectors of the ionization type They contain a small radioactive radiation source normally Americium 241 When these sensors detectors gets dirty and wh
95. her menu or press ESC Previous Next EEA The Service symbol been acknowledged will be turned off when all sensors have 137 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 30 4 Clear weekly average H8 S3 Valid only for 430x and 440x sensors in NORMAL mode If a sensor analog smoke detector is replaced without having generated SERVICE signal its week average sensor value has to be cleared and set to the default value i e 1 0 1 m otherwise the new clean sensor will inherit the old sensor s value Itis possible to clear the week average sensor value for each sensor individually via this menu NOTE First replace the sensor and then clear the week average value as soon as possible Authorised service personnel only must do this Used incorrectly it can cause nuisance fire alarms The first week average sensor value after clearing will be calculated within one hour then each week Menu According to chapter Access see page 88 Scroll to menu H8 H8 Maintenance a S2 Acknowledge SERVICE signal Clear weekly average Test of alarm devices Safe shut down of control unit Activate address in alarm mode Synchronize the control units Activate Reset outputs Scroll to menu S3 S3 Clear weekly average el Clear weekly average zone doo address 00 Write the wanted zone and press address and press lt Write th
96. ier fuse F1 on the main board 5010 LED Operation L5 indicate that the 24 V DC power supply is okay rectifier and or battery The c 1 e will do a restart see chapter Restart page 84 The site specific data SSD created in EBLWin can now be downloaded see Planning Instructions MEW01551 See also chapter Calibration of supervised outputs H5 A1 page 119 35 Cable tie shall be mounted to keep the mains wires well separated from the 24 V DC wires National regulations have always to be followed 79 Panasonic Eco Solutions Nordic AB MEWO01552 19 2 19 2 1 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Control Units ina TLON network The EBL512 G3 system can be build up as a single TLON Network or as a redundant TLON Network i e two networks In the single TLON Network one TLON connection board 5090 has to be plugged in each control unit Network no 0 whereas in the redundant TLON Network two connection boards 5090 have to be plugged in each control unit The redundant TLON Network supports full functionality also in case of a network fault 1 e open circuit or short circuit in one of the TLON networks Network no 0 When the 5090 board is on place and the network cables are connected for each control unit do as for a single control unit see 1 6 in chapter 19 1 above When all control units are powered the TLON network installation see bel
97. ies the look the texts the functions etc might vary Products Consists of one or more parts HW according to a Product Parts List A product has e atype number 5000 EBL512 G3 c i e Configured for 128 256 or 512 alarm points and with or without printer depending on article number 5001 EBL512 G3 c 1 e No front panel and no Plexiglas in the door Configured for 128 256 or 512 alarm points depending on the article number e an article number is often the same as the type no but a country code can be added e g SE for Sweden If also the letters PRT are added in the article number the product comes with a printer If digits are added to the article number they are showing the number of alarm points configured e g 5 0100PRTSE 128 e a product name e g EBL512 G3 CU 128 alarm points with printer HW A HW e g a printed circuit board has e atype number e g 5010 e an article number often the type no and sometimes is a country code added e g S010SE e aproduct name e g Main Board 128 alarm points e ap c b number e g 9290 3B and can also have a configuration e g CFG 2 and a revision e g REV 2 e sometimes a S W S W A S W has e aversion number e g V2 0 x Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x e sometimes additional information such as Convention different functions facilities Language Number of address
98. in selected control unit or all Disable output type Use the soft key Change Control outputs in Control unit 00 type of disablements to toggle between Control Ventilation Extinguishing Interlocking Write control unit number when required Press 4 to disable which will be indicated with V and a beep The type will directly be shown in the Re Change type of disablements enable list 99 Panasonic Eco Solutions Nordic AB MEWO1552 Rev do Disable output type Control outputs in Control unit 00 y Re enable list 1 All control outputs Change type of disablements gt Disable output type Control outputs in Control unit 00 All WRe enable list 1 TI All control outputs Change type of disablement E Disable output type ne Control outputs in Control unit 00 Change type of disablements ESC B1 Zone or Zone Address B2 Output B4 Alarm devices B5 Routing equipment B6 Alert annunciation function 100 eer e ee ena eg Instructions Fire alarm system EBL512 G3 V2 0 x Use the soft key gt I to toggle between Disable and Re enable list Select in the Re enable list with V in this example there is only one item and press gl Re enabled type will disappear from the list indicated with a beep Disable or Re enable another type or press ESC Scroll to another menu or press ESC or Escape menu Panasonic Eco Solutions Nordic AB MEW01552 Rev Opera
99. in the c i e display and ext FBP display to identify the point zone activating fire alarm It is also used to disable re enable fire alarm points zones and as trigger conditions in control expressions to activate programmable outputs Together with the presentation number a user definable 40 characters text message alarm text can be displayed if programmed gt 00 99 01 99 The address within the zone 00 Only the zone number will be displayed e g used for conventional zone line inputs 001 999 Zone number NOTE Zone numbers 001 999 can be used but in accordance with the EN54 2 standard not more than 512 alarm points and or zones can be used per C 1 e Also in the Alert Annunciation Units and Presentation Units Display Units 42 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 16 Alarm types In case of a fire analog detectors sensors conventional smoke and or heat detectors manual call points and programmable inputs can activate fire alarm If somebody illegally breaks into a key cabinet this will also activate a fire alarm i e a key cabinet alarm A fire alarm could be an Alert Annunciation alarm i e the activation of the routing equipment fire brigade tx is delayed during an acknowledgement time and an investigation time respectively The analog detectors can also activate two other types of a
100. in unit H5 A4 Control unit The total current consumption including the charging current at 24V for the selected control unit c i e when it is connected to the mains 230 V AC 1 e this function is not working by battery backup Charging The battery charging current for the selected control unit c 1 e Also battery temperature and low capacity voltage will be shown Menu According to chapter Access see page 88 Scroll to menu H5 e Sensitive fault detection mode Service mode for COM loop Display current consumption in control unit Display current consumption on COM loop Display statistics for communication Activate address setting mode for DU SSD information Scroll to menu Display current consumption in control unit A4 e Select control unit do press lt Write control unit number and press 4 Current consumption in control unit 00 From rectifier xxxx mA Charging xxxx mA battery temperature xx C Low capacity voltage diff xxxxx mV lt 4 or ESC A4 Display current consumption in unit Scroll to another menu or press ESC During the battery capacity check the voltage is measured with and without a resistor A difference between these two voltages gt 700 mV will result in a Low battery capacity fault 123 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 27 5 Display current consumption on COM loop H5
101. ire alarms We all realise when life buildings production facilities etc shall be saved it is of utmost importance that an initial fire is detected as soon as possible That s why more and more automatic fire alarm systems are installed In an automatic fire alarm installation especially if smoke detectors sensors are used everybody in the building needs to be informed how to avoid so called unnecessary nuisance fire alarms To avoid trouble and unnecessary expenses there are a couple of things to bear in mind Here are some advice and tips Tobacco smoke The detectors sensors cannot sense the difference between smoke and smoke They cannot separate tobacco smoke from smoke from a fire Intensive tobacco smoking in conjunction with bad ventilation can cause a fire alarm Welding grinding cutting sawing amp drilling These kinds of jobs cause smoke Carpet welding Welding of plastic carpets causes a smoke that can be almost invisible but it still influences the smoke detectors sensors Cooking fumes toasting amp candles It is not only normal smoke that influences smoke detectors sensors It is all kinds of combustion products caused by cooking frying grilling toasting etc Warning Be careful when smoke detectors sensors are mounted near close to such activities Special environments In certain premises a special environment can exist which can influence smoke detectors sensors and
102. ithin zone 002 First alarm 002 03 Alarm number 1 of 1 Zone Address 002 03 SMOKE User definable alarm text for 002 03 1 zone in alarm 2 In case of Selective alarm presentation only for the selected alarms Outputs programmed for General fire alarm and outputs programmed for the activated fire alarm s 45 Panasonic Eco Solutions Nordic AB MEWO01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x After the presentation number is automatically added SMOKE HEAT MULTI or MCP depending on type of alarm point More than one alarm point activating fire alarm Example fire alarm in zone 002 address 03 within zone 002 and nine other fire alarms of which the latest alarm is 003 11 in four different zones First alarm 002 03 Alarm number 1 of 10 Zone Address 002 03 SMOKE User definable alarm text for 002 03 Latest alarm 003 11 4 zones in alarm Menu Next zone SMOKE after the presentation number is automatically added depending on the type of alarm point 1 e SMOKE HEAT MULTI or MCP User definable alarm text For each alarm point and zone line input can an individual alarm text be shown if programmed Up to 38 characters can be used Additional information First alarm Latest alarm Alarm number and number of zones in alarm LEDs Alarms queued L6 blinking 0 4 0 4 sec are indicating that more than one fire alarm is activated To scroll through
103. ity Regarding Fire alarm reset see above Quiet alarm reset Quiet alarms are non latching 1 e they will be automatically reset when the alarm point zone is no longer above alarm level Outputs activated by quiet alarm will be de activated In some cases after a programmable delay time 58 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 18 Fault All faults are delayed in order not to generate any unnecessarily faults e g for COM loop and zone line input faults the delay time is approx 45 seconds In case of a fault condition the following will happen in the control unit e The buzzer in the c i e will sound continuously steady e The fault condition output for routing equipment Fault tx will be activated e Programmable output s for general fault will be activated and output s for general charge fault might be activated e LED Routing equipment Fault tx activated L13 will be turned on indicating that the fault condition output for routing equipment Fault tx is activated e LED Fault Disablements General fault L9 will be turned on e LEDs Fault Disablements Alarm devices L11 System fault L7 and or Fault Disablements Fire brigade tx L12 might be turned on as well e A fault message incl date time and status will be shown in the c 1 e display If itis an alarm point or zone also the User definable alarm
104. klight Door open Door Key switch In EBL512 G3 and ext FBP 1826 there is a door switch which is activated when the door is open In the ext FBP 1828 this door 11 Panasonic Eco Solutions Nordic AB MEWO01552 2 17 2 18 2 19 2 20 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x switch is replaced with a key switch An open door is indicated in the LCD i e an open door icon Site Specific Data SSD The SSD is unique for each installation All alarm points presentation numbers user definable text messages programmable outputs etc are created in the PC program EBLWin and also downloaded in EBL512 G3 unit s with EBL Win Software S W System program The software S W also called Firmware and System program makes the control unit the microprocessor work It is factory downloaded but a new version can via the PC program EBLWin be downloaded in EBL512 G3 on site EBLWin PC program used to create and download the SSD in EBL512 G3 unit s Also used to download another new software version and to upgrade the maximum number of alarm points in EBL512 G3 Can be used during commissioning maintenance of the EBL512 G3 system auto generate COM loop SSD acknowledge faults etc Web server EBLWeb config tool The Web server is used to get EBL512 G3 information as well as remote control via a PC browser and an intranet internet The Web server is configured via
105. larm 1 e Pre warning and Heavy smoke alarm Heavy heat alarm Two unit dependent addressable alarm points normally only smoke detectors and 2 zone dependent zones can activate a Co incidence alarm Quiet alarm is normally used on the Australian market only for fan control In the Australian convention only an Alarm Acknowledgement Facility function can be used During the Acknowledgement Period and the Investigation Period respectively there will only be an indication in the c i e display NOTE Special hardware is required Acknowledged and Isolated alarm is a fire alarm function only used in New Zealand Regarding the different alarm types etc see the following chapters NOTE In the following chapters are all different alarm types described The figures in this document show the essential information and might not look exactly as shown in the display 16 1 Pre warning Activation of Pre warning is an option that has to be enabled via EBLWin for the control unit respectively Note Pre warnings activated in any control unit in the system will always be presented in all control units and all programmable outputs in the system with trigger condition pre warning will be activated if not disabled An analog detector will generate a pre warning for a lower alarm level than the fire alarm level Pre warning can be used when an early warning and or an early action is required e g a soft computer shut down
106. larm from key cabinet control unit XX When printer is available the Key cabinet alarm will be printed like for a normal fire alarm see above Key cabinet alarm is reset like a normal fire alarm see chapter Fire alarm reset page 55 This alarm will also generate a fault message see chapter Key cabinet alarm reset page 57 It is indicated by LED Fault L9 NOTE The Fault tx output s will not be activated by this fault 16 5 2 Key cabinet opened in conjunction with a fire alarm If a normal fire alarm already is activated in the c 1 e the fire brigade personnel can open the key cabinet without activating any key cabinet alarm or fault 16 5 2 1 Restoring the key after a fire alarm When all fire alarms in the system are reset see chapter Alarm reset page 55 the key has to be restored into the key cabinet within 5 minutes If not a fault will be generated see chapter Key cabinet alarm reset page 57 16 6 Co incidence alarm 2 address zone dependence The co incidence alarm function is programmed via EBLWin for the alarm points zones 1n question When only one zone or one zone address alarm point is in alarm status the c i e buzzer sounds 0 8 5 sec and there is a Co incidence alarm presentation in the display Note that LEDs Fire L1 are not indicating a co incidence alarm The co incidence alarm will be automatically Reset after 5 minutes i e if the zone alarm point is no longer in
107. lt Faults normally latched have to be acknowledged which is done via menu H6 see page 129 This menu is a list of all faults in the system not corrected serviced and not acknowledged fault not corrected serviced but acknowledged fault Acknowledged corrected serviced but not acknowledged fault Serviced If a fault cannot be corrected it is important to contact service personnel engineer immediately NOTE As a reminder faults and disablements are indicated by a 2 sec beep when an open c i e door is being closed 2 Can via EBLWin be set to be not latched 60 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 18 1 Fault messages Below follows a list of all fault messages in alphabetical order There is also an explanation to each fault Cheecksiim Laule in cowmlhoOacded Gaba Coie cole ANI E Wainl new tee Sie cede A fault in the downloaded Site Specific Data SSD After the restart a new fault will be generated FAULT Site Specific Data SSD control unit xx A new SSD download will probably solve the problem FAULT 24V for external equipment output x COET OTENE x Power supply output 1 4 J3 5 12 xx 00 29 Check fuse F9 F10 F11 and F12 respectively on the Main board 5010 in control unit no xx Fuse T4A L 250V TR5 PAG AN Torn roO Ina cecumeme mir COmmicol Unites sox Power supply output 0 J3 3 4 xx
108. lutions Nordic AB MEWO01552 17 Operating Instructions Fire alarm system EBL512 G3 V2 0 x Alarm reset 17 1 17 2 17 2 1 17 2 2 Pre warning reset Pre warning is automatically reset Fire alarm reset NOTE The detectors having activated fire alarm shall after reset be inspected tested and replaced when required One of the following alarm reset alternatives is valid This is selected via EBLWin All is default All All activated fire alarms alarm points zones will be reset by pressing Reset P3 once This is in accordance with the EN54 2 standard NOTE The push button has to be pressed for min 0 5 sec When all fire alarms are reset LEDs Fire L1 and Alarms queued L6 are turned off If there are other conditions e g a fault condition the corresponding information will be shown e g a fault message for the priority order see chapter The information area priority order page 25 All outputs for fire alarm are reset i e de activated If a key cabinet is installed the key to the building has to be put back into the key cabinet within 5 minutes If not a fault will be generated and a fault message will be shown in the display see chapter Key cabinet alarm reset page 57 NOTE When Single or Single with automatic disablement is used all alarms can be reset by pressing Reset P3 and approx 0 1 sec later also press Enter and hold them pressed for gt 0
109. m system EBL512 G3 V2 0 x e All faults have to be individually acknowledged one by one by the key pad button e Use or to scroll e Ifa fault has been corrected before it has been acknowledged the text Serviced is added after the time It still has to be acknowledged e When a fault is corrected serviced and acknowledged it will disappear from the list H6 e When all faults have been acknowledged output s for routing equipment Fault tx is are reset i e the LED Routing equipment Fault tx activated L13 will be turned off e As long as there are faults 1 e not acknowledged faults and or acknowledged but not corrected faults the LED Fault Disablements General fault L9 will be lit and general fault and maybe general charge fault output s are activated e Faults corrected faults and acknowledged faults are shown in the General event log menu H4 U6 34 In the Australian and New Zealand conventions the LED L13 is turned on and the output s for routing equipment Fault tx is are activated until there are no faults in the system 78 Panasonic Eco Solutions Nordic AB MEWO01552 19 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Commissioning an installation 19 1 Before you connect the power supply to a control unit all other cable connections shall be made Check once more that they are correct A tip Measure the resistance of each loop wire L amp C re
110. n Analog multi detector 4300 4400 in NORMAL mode If there are no sensors analog detectors when Sensor 001 01 technical address 000001 ae l Momentary XX X m Weekly XX X m SE eae OER Perf factor X XX m Min XX X m T OORO pE Algorithm X XX Max XX X m It is a list in which you can Momentary XX C Min XX C scroll with Y or A Algorithm XX Max XX C If printer is mounted the For an Analog heat detector 3308 3309 in NORMAL mode soft key Print will be visible else not Press Sensor 001 03 technical address 000002 Momentary XX C Min XX C Algorithm XX Max XX C Print for a print out For an Analog multi detector 4400 in Advanced mode Sensor 001 01 technical address 000001 Momentary XX X m Weekly XX X m Perf factor X XX m Min XX X m Algorithm Xxxxxx Max XX X m Momentary XX C Min XX C Max XX C Start sensor ooo0o Write another technical number and press 4 or press ESC ESC U4 Sensor values Scroll to another menu or press ESC NOTE During printing Print will be replaced with Abort printing Regarding the Performance factor The Performance factor can be 0 00 2 55 How the Performance factor Pf is calculated is shown to the left The Performance factor is normally close to 0 00 which means that the detector is mounted in a stable environment The momentary sensor values during 24 hours do not differ a lot from the week average sen
111. ne hour after the latest test alarm You will be automatically logged out 15 minutes after the latest action using of any key but the zone s will stay in test mode until the test mode is ended see above Perform the test as quickly as possible since the output s for routing equipment fire brigade tx are disabled also the parts of the zones in test mode not visible for the test personnel are disabled In order to shorten the testing time any time delay for the detectors zones in test mode will be disabled 1 e fire alarm will be detected faster than normally In the tested alarm point the LED will light up and the LEDs Fire L1 in the c 1 e will light up approx 10 seconds then the alarm point will be automatically reset The printer if available will print out every tested alarm point Zone xxx Address xx Time HH MM A detector in test mode is not able to generate a fault After 15 minutes Zone 001 in test mode You are logged out but the or Zone 002 in test mode zone s are still in test ESC and Zone 003 in test mode mode Escape menu Zone 004 in test mode NOTE See chapter The information area priority order page 25 regarding priority order Menu Zones in test mode Press lt to end test Log in see above 001 002 003 004 End test J select menu H1 step down to this view C Test of routing equipment The LED Test mode is turned OFF Yes Some national regulations also
112. ng Addressable siren 3377 4477 and Addressable sounder base 3379 For the alarm devices 3377 4477 and 3379 the tone with the highest priority level and type alarm device will be automatically selected 139 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Test of alarm devices control unit 00 The test will continue for in progress Press to end test one hour if not stopped via this menu S4 or 1f a fire alarm is activated in the system Press lt to end the test Test of alarm devices ended Press to return to menu S4 Test alarm devices Scroll to another menu or press ESC 140 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 30 6 Safe shut down of control unit H8 S5 It s recommended to do a safe shut down of control unit before you power off a control unit 1 e no 230 V AC and no battery Safe shut down will save the SSW in a Flash ROM and put the CPUs at rest See also chapter Restart page 84 It s recommended to do a safe shut down after commissioning the installation and after the calibration of supervised outputs change of passwords etc in order to save the new valid values codes etc Safe shut down can be performed from any control unit and any control unit can be selected A control unit without a front has to be shut down from another control unit
113. nge type of disablements B1 Zone or Zone Address B3 Output type B4 Alarm devices B5 Routing equipment B6 Alert annunciation function ESC 98 Operating Instructions Fire alarm system EBL512 G3 V2 0 x If the specified output doesn t exist it will be indicated with X instead of V and a beep Use the soft key gt I to toggle between Disable and Re enable list Select in the Re enable list with VW in this example there is only one item and press mam Re enabled output will disappear from the list indicated with a beep Disable or Re enable another output or press ESC Scroll to another menu or press ESC or Escape menu Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 24 3 Output type H2 B3 All outputs of type Control Ventilation Extinguishing and Interlocking can be collectively disabled Disabled output will stay in or return to the normal condition for the output respectively Disabled outputs are listed in menu H4 U1 from which it is also possible to get a print out Menu According to chapter Access see page 88 Scroll to menu H2 H2 Disable or re enable Ci B2 Output B3 Output type B4 Alarm devices B5 Routing equipment B6 Alert annunciation function Escape menu B3 Output type Scroll to menu B3 Via menu B3 can outputs of the same type be collectively disabled
114. nload the user definable alarm texts shown in the display in the control units ext FBPs and other Display Units e see the fault status and acknowledge faults EBLWin shall have the same version number as the EBL512 G3 software version number e g 2 0 x and 2 0 x respectively x indicates only a small correction and is not required to be the same Old SSD files can be opened in a newer higher version of EBLWin saved edited and thereafter downloaded to EBL512 G3 units with the corresponding version TLON Manager The PC program TLON Manager is used for the TLON Network programming installation etc TLON Manager 1 2 and TLON Manager 2 0 can be used EBLWeb Config tool The PC program EBLWeb Config tool is used for configuration of the Web server II 1598 15 Panasonic Eco Solutions Nordic AB MEWO1552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 4 Control Unit Figure 1 Left The EBL512 G3 Control Unit 5000 with printer _ The look might vary according to configuration country etc Right The EBL512 G3 Control Unit 5001 Depending on country convention configuration etc the look language and functions might vary Figure 1 shows an EBL512 G3 type 5000 with a front with texts in English Fronts with texts in other languages are available EBL512 G3 is housed in a grey metal cabinet The door has a Plexiglas ahead of the front and display see Figure 1 A key is required to open the
115. ntrol unit H8 S5 141 30 7 Activate address in alarm mode H8 S6 143 30 8 Synchronize the control units H8 S7 145 30 9 Activate Reset outputs H8 S8 147 31 Interlocking outputs and inputs H9 149 31 1 Activated interlocking outputs inputs H9 C1 149 31 2 Activate deactivate interlocking output H9 C2 150 31 3 Disable re enable interlocking output H9 C3 152 31 4 Change password H10 154 32 Annual control 155 33 How to change paper in the printer 156 34 Replacing a TLON connection board and or the Main board 157 35 Battery maintenance 158 36 How to avoid unnecessary nuisance fire alarms 159 37 Information regarding radioactive radiation source161 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 38 Revision history 162 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 1 introduction EBL512 G3 Operating Instructions is a document intended to be used by the end user and the fire brigade personnel as well as service commissioning engineers Due to continual development and improvement different S W versions are to be found This document is valid for S W version 2 0 x On the date rev date of this document x 0 Since the EBL512 G3 control unit c 1 e is produced for many countr
116. nts Alarm points disabled by time channel in by time channels control unit XX If printer is mounted the yyyy mm dd hh mm soft key Print will be visible else not Press Print for a print out of all Disablement 1 to 3 of 7 items in the list ESC U1 Disablement Scroll to another menu or press ESC 108 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 26 2 Disablement by time channel H4 U2 A static list up to four items per page of all disablements by time channel s in the system NOTE All other disablements are listed in menu H4 U1 Access see page 88 St i a Via menu U2 will all U2 Disablement by time channel disablements by time Open doors channels be shown Sensor values Press 4 Sensors activating SERVICE signal Technical warning Event log Information Scroll to menu U2 U2 Disablement by time channel E HaT Zone XXX address XX disabled by time If there are no disable channel poa i ts List ty Zone XXX address YY disabled by time o A eee 7 l channel will be shown Itis a static of list up to 4 items per ae page in which you can scroll with VW or A Number of disablement by time channel 2 ESC U2 Disablement by time channel Scroll to another menu or press ESC 109 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 26 3 Open doors H4 U3 If any do
117. o menu S6 S6 Activate address in alarm mode al Select zone 00 address 00 press Write the zone number and Select zone 123 address As address e g 123 45 press di Dis Re connect loop zone line input Acknowledge SERVICE signal Clear weekly average Test of alarm devices Safe shut down of control unit Activate address in alarm mode Synchronize the control units Activate Reset outputs First alarm 123 45 1 zone in alarm Latest alarm 123 45 Press ESC to leave this menu Select zone 23 address 45 The fire alarm has to be reset as a normal fire alarm press a press Reset S6 Activate address in alarm mode Scroll to another menu or press ESC NOTE In all other control units the alarm will be presented as a Test mode alarm 143 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x First alarm 123 45 Alarm number 1 of 1 Phisianvally acdvated tetmode fire alarm will be presented in all control Zone Address unit displays and all ext FBP displays and indicated by the LEDs Fire L1 and Fire brigade tx L4 Alarm text for 123 45 This manually activated fire alarm has to be reset by the push button Reset P3 144 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 30 8 Synchronize the control units H8 S7 After any
118. ol is today available on the Australian market only 53 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x During the Investigation Period 0 3 min the following information a list if many is shown in the c 1 e display AAF zone zz investigation in progress dd mm yyyy hh mm 16 9 Quiet alarm One or more smoke detectors via EBLWin programmed for Quiet alarm have passed the fire alarm level Quiet alarm is used for fan control stop or start is depending on the type of fan Quiet alarm is normally used in conjunction with one I O Matrix board 4582 one application board for fan control and one I O unit for fan control 3361 for control of each fan Indications and actions Detector LEDs are turned on i e also a connected ext LED LEDs Fire L1 are blinking 0 4 0 4 sec the buzzer sounds 0 8 5 sec and there is a Quiet alarm presentation incl a title Quiet alarm in the display Quiet alarm Zone Address 23 49 SMOKE User definable alarm text for 123 45 Programmable outputs for quiet alarm e g 3361 outputs controlling supply air fans and standard fans i e any output with a control expression containing the trigger conditions Quiet Alarm Zone or Quiet Alarm Zone Address Quiet Alarms are automatically reset see page 58 The Fan control panel 4593 can be used for control of up to eight fans 54 Panasonic Eco So
119. ons Alarm points can be individually disabled Menu According to chapter Access see page 88 Scroll to menu H2 H2 Disable or re enable Oo a Via menu B1 can a B2 Output Zone or an alarm point B3 Output type Zone Address be B4 Alarm devices disabled B5 Routing equipment A time for automatic B6 Alert annunciation function re enablement can be set Disabled zones and alarm points are shown Escape in a Re enable list menu a a Use the soft key Zone 000 Change type of Automatic re enable disablements to toggle between Zone 000 and Change type Zone 000 address 00 of disablement aare paaa ma S Write the zone number Zone 00 address 00 and address Automatic re enable To set an automatic re enable time press Y and gt Write the time default is current Change type of disablements time 3 hours Press lt to disable which will be indicated with anda beep The zone will directly be shown in the Re enable list Change type of disablement 95 Panasonic Eco Solutions Nordic AB MEWO1552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Write the zone number If the specified zone and address Zone 03 address 01 y unit doesn t exist it will e g 003 01 Automatic re enable No Yes at 17 05 be indicated with X y Re enable list 1 instead of V and a p a beep Z re one
120. or Single aE yellow with automatic disablement see page 56 L11 Alarm devices yellow Steady cont Output s type Alarm device are disabled Blinking One or more supervised outputs type Alarm device have generated fault s This is also valid when the c 1 e has no contact with a unit with such an output e g 3377 3379 3364 etc Fire brigade tx yellow Steady cont Output s for Routing equipment disabled via menu H2 B3 or B9 or via open door Blinking Routing equipment power supply output or one or more supervised outputs of type Routing equipment have generated fault s This is also valid when the c 1 e has no contact with a unit with such an output e g 3361 etc Routing equipment Fault tx activated yellow One or more not acknowledged faults Output Fault condition for fault tx routing equipment is activated o E H E Sensitive fault detection mode see menu H5 A2 is on L14 Fire brigade tx delay The Alert Annunciation function is enabled 1 e time yellow channel controlling this function is on The AA function is described in the EBL512 G3 Planning Instructions chapter Alert Annunciation LED L14 will be on if the AA function is enabled for at least one alarm point zone Normally is only one time channel used for this function but two or more channels can be used The AA function can as an alternative be continuously on gt Main board 5
121. or in the system is open the following symbol is shown in the z display s symbol area See also chapter Open door page 40 This menu is a dynamic list of all open doors in the system Menu According to chapter Access see page 88 Scroll to menu H4 H4 Present system status a a Via menu U3 will all open U2 Disablement by time channel doors in the system be Open doors shown Sensor values Press 4 Sensors activating SERVICE signal Technical warning Event log Information Scroll to menu U3 U3 Open doors Door open control unit 00 It is a dynamic list in yyyy mm dd hh mm which you can scroll with W or A Door open control unit 01 fire brigade panel 00 yyyy mm dd hh mm If printer is mounted the soft key Print will be visible else not Press Print for a print out of all items in the list Open door 1 to 2 of 2 ESC U3 Open doors Scroll to another menu or press ESC NOTE During printing Print will be replaced with Abort printing 110 Panasonic Eco So MEWO1552 26 4 Action Menu Scroll to menu H4 al Scroll to menu U4 al lutions Nordic AB Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Sensor values H4 U4 The Momentary value in this menu will be updated after every detector polling i e approx every 6 second The very first week average sensor value for the 430x and 440x detectors in NORMAL mode is calculated within 2
122. ore changing the paper roll e Open the control unit door e Open the printer cover i e press the green illuminated release button in the middle on top of the printer front e Remove the remains of the old paper roll e Place the new paper roll in the printer Make sure that it unrolls in the correct direction like the old one e Pull out 50 mm paper and close the cover e Tear off the paper then press the Paper feed button to the right on top of the printer front to check the paper feed function and tear off the paper e Close the control unit door 156 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 34 Replacing a TLON connection board and or the Main board By the TLON network programming some unique data will be stored in a memory on the 5090 TLON connection board and some will be stored in a memory on the 5010 main board Replacing only a TLON connection board 5090 After replacing the board In TLON Manager version 1 2 do Replace Update and Save In TLON Manager version 2 0 do Replace and Update Save is aut done Replacing both a TLON connection board 5090 and also the Main board 5010 After replacing the boards In TLON Manager version 1 2 do Replace Update and Save In TLON Manager version 2 0 do Replace and Update Save is aut done Replacing only the Main board 5010 After replacing the main board pu
123. ow has to take place before the site specific data SSD can be downloaded see Planning Instructions MEWO1551 If you know that one or more of the control units are to be started up later do as follows In EBLWin create SSD only for the control units that shall be connected now Wait to download the SSD until the TLON Network installation is ready In TLON Manager do the TLON Network programming for the project 1 e only the control units that shall be connected now When the TLON Network installation is ready see below download the SSD Later when one or more control units shall be added to the TLON Network Open the project in TLON Manager add the new control unit s and install download according to the separate TLON network Operating Instructions MEW01361 Open the SSD in EBLWin and add the new control unit s and download the SSD to all control units TLON network installation A project a system with two or more control units 1s created in the PC program TLON Manager or has been created earlier A PC is connected to the modular connector J10 Network no 0 in a control unit main board 5010 Open the project in TLON Manager and install download the project see separate TLON network Operating Instructions MEWO1361 3 The TLON connection board is mounted on the main board 5010 Network cable connections are made on the main board 5010 terminal block J4 80 Panasonic Eco Solutions Nordi
124. owing menus H7 Perform ZONE TEST Test mode H10 Change password In this case for Building officer 30 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 7 5 User level 3A After the door has been opened with the fire brigade key Door open symbol a in the symbol area the service maintenance personnel have access to level 2A and after log on as Service personnel level 3A access to all menus 1 e like level 2C and also to the following menus S8 Activate Reset outputs H10 Change password In this case for Service personnel 7 6 Access level 3B Used by Service maintenance commissioning engineers when a PC i e EBLWin is to be connected to EBL512 G3 for backup upload download of site specific data SSD and or download of software EBLWin require a hardware key 7 7 Access level 4 Used by manufacturer or by personnel authorised by the manufacturer for re initialisation reset of the alarm counter change software configurations on line status checking etc A special password is required 31 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 8 Silence Alarm devices In the control unit front the FBP part there is a push button Silence alarm devices P2 When the alarm devices are activated sounding and the push button Silence alarm de
125. perating Instructions Fire alarm system EBL512 G3 V2 0 x Upgrade number of alarm points 20 1 All EBL512 G3 settings are normally factory downloaded before delivery It is however possible to do the following on site e Upgrade the maximum number of alarm points 128 gt 256 gt 512 NOTE The maximum number of COM loop addresses is always 1020 1 e address 1 255 on each COM loop If you wish to upgrade the number of alarm points a PC and EBLWin are used The PC has to be connected to the USB connector in the control unit See Planning Instructions MEWO1351 for more information Control Units in a TLON network All control units connected to a TLON network do not have to have the same max number of alarm points set 83 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 21 Restart A restart will delete or not delete the data in EBL512 G3 Below follows an explanation of the different data abbreviations and a table showing how the data respectively is affected cold or warm restart FF Fire alarms and Faults D Disablements FFD Fire alarms Faults and Disablements SSW Sensor min max values amp performance factor access codes supervised output calibration values and event logs WASV Week Average Sensor Values SSD Site Specific Data i e all the installation programming created and downloaded via EBLWin S W Software i e
126. points Display unit DU Addressable unit RS485 line for fire alarm presentation incl user definable alarm text alert annunciation etc COM loop Loop a cable with two wires to which all the addressable units can be connected Starts in the c 1 e and it returns back to the c 1 e Control Unit C U C LE Control Unit Control and Indicating Equipment Unit to which the alarm points are connected via e g a COM loop Indicates fire alarm fault condition etc Fire Brigade Panel amp Control Panel see below included or not included Printer included or not included Fire Brigade Panel FBP Intended for fire alarm presentation etc for the fire brigade personnel Can be a part of the control unit front or a separate Display unit external FBP In an ext FBP a printer can be included Control panel CP A part of the control unit a part of the front intended for the building occupier officer service personnel etc to communicate with the Control Unit the System 10 Panasonic Eco Solutions Nordic AB MEWO01552 2 11 2 12 2 13 2 14 2 15 2 16 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x System Installation One control unit or several control units connected via a TLON network co operating control units Network TLON LonWorks Echelon Node TLON Conn board Gateway Sub net Backbone net Router Repeater Brief expl
127. r Alarm text for 021 05 user definable week month yyyy mm dd hh mm Acknowledged All To acknowledge a fault select it and press 4 The selected fault has a boarder around it Fault 1 3 is selected Print Previous Next page page 129 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x FAULT Low battery capacity control unit 00 A corrected serviced Acknowledged fault that is acknow yyyy mm dd hh mm ledged will disappear FAULT No reply zone 045 address 06 tomic iat technical number 000005 Alarm text for 045 06 user definable yyyy mm dd hh mm Serviced FAULT No reply zone 021 address 05 technical number 000114 Alarm text for 021 05 user definable yyyy mm dd hh mm Acknowledged Fault 1 3 is selected Pe T ae Previous Pe T ae H6 FAULT H6 FAULT Acknowledge a ss i sSS Scroll to another menu or press ESC 130 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 29 Perform ZONE TEST Test mode H7 Normally zones are tested during the monthly test via menu H1 Via this menu H7 it is also possible to perform the zone test Up to 100 zones can be set in test mode In test mode only the alarm points are tested 1 e no outputs e g sounders will be activated during the test Alarm devices can be tested via menu H8 S4 and any output via menu H8 S8 or vi
128. r the external power supply unit 3366 and the addressable 2 voltage outputs unit 3364 connected on the COM loop The fault is activated after 1 300 minutes after o Loss of mains 1 e no 230 V AC to the 3366 unit Blown mains fuse Fuse F1 blown on the 3366 unit s charger board 3367 Fuse T5A L 5x20 mm 3364 unit o Terminal no 8 Mains OK not connected to the 3366 unit J7 4 or 0 V see drawing 512 G3 38 o no mains signal from the 3366 unit PAULI Multiple faults COM TOOP xX 3 The time is programmable via EBLWin Max 30 min according to the EN54 2 standard Default value depending convention 68 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Conero Unie xx Break cut off short circuit in more than one segment on the COM loop in control unit no xx EATER N EnO We clo kes ne Gy OnE n Ine In a redundant TLON Network the Network 0 cables and Network 1 cables are mixed Check the network installation connections BEAUCET No CONSEC ELONn WIth MMI DOSa ch Clone ecu Clams o lt This fault message cannot be shown in the control unit s display only via EBLWin via Web server and in other control units in the system Fault in the MMI board 5011 software or the MMI board Check the cable between the boards This is a very serious fault Call for service personnel engineer immediately FAULT No reply expansion board x COET O
129. rning co incidence alarm etc or if the push button Silence buzzer is pressed again the buzzer will automatically sound again Silence buzzer by open door In EBLWin the function Silence Buzzer by Door Switch can be selected The buzzer will then be turned off as long as the control unit door is open This function is a violation to the EN54 2 standard EBL512 G3 c i e type no 5001 This unit has no front and no built in buzzer 12 Incl Heavy smoke heat alarm AA alarm Key cabinet alarm and Acknowledged alarm New Zealand only 36 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 11 Disable or re enable Output All control outputs except outputs of type Alarm devices can via menu H2 B2 be individually disabled e Loop unit xxxxxx output x e Control unit xx SO e Control unit xx RO e Control unit xx expansion board x output x This is indicated by LED Fault Disablements General disablements L10 They will remain disabled until they are re enabled again via menu H2 B2 See also chapter Output type H2 B3 page 99 See also chapter Activate Reset outputs H8 S8 page 147 An output can be activated for an output test 37 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 12 Disable or re enable Control Ventilation Extinguishing and Interlocking outputs
130. rning is an event that is neither a fire alarm nor a fault It is an information that something has or has not happened and is generated via a programmable input The text message shown in the c 1 e display is user programmable up to 40 characters One or more activated technical warnings are indicated by EE in the display s symbol area Menu According to chapter Access see page 88 Scroll to menu H4 H4 Present system status a U2 Disablement by time channel Open doors Sensor values Sensors activating SERVICE signal Technical warning Event log Information Scroll to menu U6 U6 Technical warning i If there are no technical warnings List is Technical warning text message 2012 11 10 09 09 15 en ee aoa It is a list in which you Yyyy yyyyyyyyyyy yyyyyyyyyyyy can scroll with W or 2012 10 03 19 09 35 A If printer is mounted the soft key Print will be visible else not Press Print for a print out of 1to2of2 all items in the list ESC U6 Technical warning Scroll to another menu or press ESC NOTE During printing Print will be replaced with Abort printing Technical warnings can be used to activate programmable outputs 115 Panasonic Eco Solutions Nordic AB Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x MEWO01552 26 7 Action Menu Scroll to menu H4 a Scroll to menu U7 a al ESC Event log H4 U7 Three event logs
131. roll to menu U8 U8 Information Main board version 2 0 0 If printer is mounted the MMI board version 2 0 0 soft key Print will be Alarm counter nnn visible else not Press Max number of allowed alarm points xxx Print for a print out Serial number xxxxxxx Control unit NN ESC U7 Information Scroll to another menu or press ESC 117 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 27 Service H5 When commissioning an installation and by maintenance e g when you power on and when you are programming a control unit system menu H5 can be used for certain actions information and help Only authorised personnel have access to the level 3A menus and a password for level 3A Service technician is required Via a PC and EBLWin you can e download backup upload the site specific data SSD e create and download software S W settings configurations control unit and system properties e create and download the user definable text messages alarm texts shown in the display in the control unit ext FBP and other Display units NOTE To be able to log on to an EBL512 G3 c 1 e via a PC and EBLWin the PC has to be provided with an EBLWin key 5094 This USB device has a number a key required for the log on Via a PC and TLON Manager you can create and download install the TLON network configuration TLON project 5 Connecte
132. rrect Try again If the password is correct a main menu list is displayed Press 4 to accept menu H1 or scroll jump to the wanted menu H2 H10 and press NOTE The menu list will be different for user levels Information only and Building officer Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Escape NOTE When the Russian Ukraine Australian or the New Zealand language is selected the date is shown as follows dd mm yyyy Explanations Action in the table use push button key e g 4 Text in display in the table what is shown in the control unit c 1 e display Comments in the table Comments to the text in the Action and Text in display columns Use A and W to scroll between the main menus H1 H10 Use 4 Enter to accept Some main menus have sub menus Use A and V to scroll between the sub menus e g B1 B6 Use 4 to accept NOTE The menus are circular i e if you scroll with VW and the last menu is reached the first menu comes up next Quick jump can be used within each menu e g in menu H1 press 6 for a quick jump to menu H6 1 and then 0 within 1 2 sec 10 In some cases a cursor appears e g Disable zone o O It is then possible to type in digits with the numeric keys 0 9 Use lt gt A and V to move the cursor in a menu Use ESC to return from a sub
133. s 14 3 5 1 EBLWin 14 3 5 2 TLON Manager 15 Panasonic Eco Solutions Nordic AB MEWO01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 3 5 3 EBLWeb Config tool 4 5 6 6 1 6 2 6 3 6 4 Control Unit LED indicators and push buttons The display LCD Areas in the display The symbol area The information area priority order System information in the LCD 6 4 1 User definable system information 7 TA T2 7 3 7 4 7 5 7 6 1 1 8 8 1 8 2 9 10 11 12 User level User name amp Password User level 1 User level 2A User level 2B User level 2C User level 3A Access level 3B Access level 4 Silence Alarm devices Silence alarm devices inside switch New Zealand FB Silence switch outside switch Disable or Re enable alarm devices Silence buzzer Disable or re enable Output Disable or re enable Control Ventilation Extinguishing and Interlocking outputs 13 14 14 1 14 2 15 15 1 13 2 16 16 1 16 2 Evacuate Open door 15 16 19 23 23 24 25 26 26 27 28 28 29 30 31 31 31 32 33 33 35 36 37 38 39 40 Outputs for routing equipment Fire brigade tx and Fault tx 40 Silence buzzer with door switch Technical number Presentation number Technical number for COM loop units Presentation number Alarm types Pre warning Fire alarm 16 2 1 Entering the menus during fire alarm 16 2 2 Acknowledged and Isolated alarm 16 2 3 Tes
134. sor value In an unstable environment the Performance factor will be higher than 0 00 Xm momentary sensor values Prana ar for 24 Sa This could for example be the case in a factory e g dirty activities during Xwa weak average sensor value working hours no or clean activities during the night and is not a problem 14400 pollings during 24 hours as long as there are no nuisance false alarms or other problems Algorithms Table showing the algorithms and the shortenings respectively 112 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Algorithm Short Detectors 3308 3309 430x and 440x all in NORMAL mode name Heat algorithm Class A1 Heat algorithm Class A2 S Heat algorithm Class B S OBO Decision algorithm Default is N 15 and A1 respectively Algorithm Short name Detector 4400 in Advanced mode Default is Normal Algorithm Short name Detector 4401 in Advanced mode Normal area Normal Default is Normal 48 If some other short name is wanted it can be changed in EBLWin Up to six characters can be used Analog multi detector 4300 only 113 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 26 5 Sensors activating SERVICE signal H4 U5 When SERVICE signal is generated in the system following symbol is shown in the display s symbol are
135. spectively before turning on the power Check that the L wire SA that goes out on terminal J5 1 comes back at terminal J5 3 and so on If the loop has short circuit isolators only the C wire SB can be measured Also measure the resistance between the loop wires and 24V OV and Earth J2 1 2 and 3 The resistance should be very high mega ohm Single Control Unit l Take away the rectifier fuse F1 and the battery fuse F2 on the main board 5010 NOTE In a single standalone control unit there shall be no TLON connection board 5090 plugged on the main board Connect the batteries to the main board 5010 terminal block J2 NOTE There shall be an in line fuse F on the cable between the batteries see drawing 512 G3 21 CAUTION RISK OF EXPLOSION IF BATTERY IS REPLACED BY INCORRECT TYPE DISPOSE USED BATTERIES ACCORDING TO THE INSTRUCTIONS Connect the rectifier to the mains 230 V AC NOTE It shall be connected to a household removable fuse for the fire alarm c i e only via a two way circuit breaker The mains cable shall be securely clamped and the wires shall be as short as possible The mains safety earth ground shall however be longer than the other wires to ensure that it is the last to be disconnected if the mains cable clamp should fail The lid protecting the rectifier screw terminals shall after the installation be correctly applied First put back the battery fuse F2 and then the rectif
136. ssing or not correct value 1 5 resistors 33K NOTE The calibrated value has to be in the range 4K7 50K FAULT Supervised output x expansion board CONTEO TER A fault on the supervised output x on the expansion board 4583 with address x in control unit no xx If the output is programmed for sounders type Alarm devices it is also indicated by LED Fault Disablements Alarm devices L11 blinking If the output is programmed for fire brigade tx type Routing equipment it is also indicated by LED Fault Disablements Fire brigade tx L12 blinking Calibration not performed via menu H5 A1 Short circuit break on the connected cable equipment Blown fuse F1 Output 0 or F2 Output 1 on the 4583 board Fuse T200mA L 250V TR5 73 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Connected equipment might be missing End of line resistor s missing or not correct value 1 5 resistors 33K NOTE The calibrated value has to be in the range 4K7 50K FAULT Supervised output x technical number xXxXxxxXx This fault message is valid for a COM loop output unit 3364 output If the output is programmed for sounders type Alarm devices it is also indicated by LED Fault Disablements Alarm devices L11 blinking If the output is programmed for fire brigade tx type Routing equipment it is also indicated by LED Fault Disablements
137. st H1 90 24 Disable or re enable H2 93 24 1 Zone or Zone Address H2 B1 95 24 2 Output H2 B2 97 24 3 Output type H2 B3 99 24 4 Alarm devices H2 B4 101 24 5 Routing equipment H2 B5 103 24 6 Alert Annunciation H2 B6 105 25 Set calendar and clock H3 107 Panasonic Eco Solutions Nordic AB MEWO01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 26 Present system status H4 108 26 1 Disablement H4 U1 108 26 2 Disablement by time channel H4 U2 109 26 3 Open doors H4 U3 110 26 4 Sensor values H4 U4 111 26 5 Sensors activating SERVICE signal H4 U5 114 26 6 Technical warning H4 U6 115 26 7 Event log H4 U7 116 26 8 Information H4 U8 117 27 Service H5 118 27 1 Calibration of supervised outputs H5 A1 119 27 2 Sensitive fault detection mode H5 A2 120 27 3 Service mode for COM loop H5 A3 121 27 4 Display current consumption in unit H5 A4 123 27 5 Display current consumption on COM loop H5 A5 124 27 6 Display statistics for communication H5 A6 125 27 7 Activate address setting mode for DU H5 A7 127 27 8 SSD information H5 A8 128 28 FAULT Acknowledge H6 129 29 Perform ZONE TEST Test mode H7 131 30 Maintenance H8 134 30 1 Password for service maintenance 134 30 2 Dis Re connect loop zone line input H8 S1 134 30 3 Acknowledge SERVICE signal H8 S2 136 30 4 Clear weekly average H8 S3 138 30 5 Test of alarm devices H8 S4 139 30 6 Safe shut down of co
138. t a Activate Use the soft key Change Loop unit ooo00 output 0 type of output to toggle between Loop unit output Control unit output SO S3 and RO R1 Exp board output Write loop unit technical number and output number and press 4 to activate which will be indicated with V anda beep The 58 Including Addressable siren 3377 4477 and Addressable sounder base 3379 147 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Change type output will directly be oroutpu shown in the Reset list Write loop unit Activate If the specified output technical number and Loop unit 00000 output 0 V doesn t exist it will be output e g 000001 0 indicated with X instead myn EZ Reset list 1 FRI ARO A A the N NAN TA A A f af dab Loop unit 000001 output 0 i eee Use the soft key gt I to toggle between Activate and Reset list I Activate Select in the Reset list with Loopunit Y in this example there Reset list 1 1S ap ie output and Loop unit 000001 output 0 aia The reset output will disappear from the list Change type indicated with a beep of output ed Activate Continue like above or Loop unit 00000 output 0 press ESC Change type of output S8 Activate Reset output Scroll to another menu or press ESC 148 Panasonic Eco Solutions
139. t back the TLON connection board s in the same position as on the replaced main board In TLON Manager version 1 2 do Update and Save In TLON Manager version 2 0 do Update Save is aut done 157 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 35 Battery maintenance The batteries 2 x 12 V 28 Ah e g Panasonic LC P1228AP are placed inside the control unit Larger batteries lt 65 Ah have to be placed outside the control unit e g in a separate battery cabinet etc The control unit supervise and charge the batteries and a fault will be generated for any battery trouble The batteries rechargeable Sealed Lead Acid batteries shall fulfil UL94V 0 The batteries are normally maintenance free but the producer s instructions shall always be followed The ambient temperature affects the battery s capacity self discharge and life span The temperature should preferably not be higher than normal room temperature approx 20 22 C For highest safety the batteries used in a fire alarm installation should not be more than four years old CAUTION Risk of explosion 1f battery is replaced by incorrect type Dispose used batteries according to the producer s instructions and national regulations 158 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 36 How to avoid unnecessary nuisance f
140. t message is to be acknowledged the same way as normal faults see chapter Fault acknowledge page 77 When the key cabinet fault is acknowledged the LED Fault Disablements General fault L9 will be turned off i e if the key cabinet is closed and if there are no other faults in the system Co incidence alarm A Co incidence alarm can be manually reset with the Reset button P3 on the c 1 e front or automatically reset after 5 minutes i e if the alarm point zone is no longer in alarm state See also chapter Co incidence alarm 2 address zone dependence page 51 Delayed alarm The Delayed alarm will be automatically reset if the alarm point during the delay time countdown no longer is in alarm state or when a normal fire alarm is activated i e when the delay time has run out 57 Panasonic Eco Solutions Nordic AB MEWO01552 17 8 17 9 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Alarm Acknowledgement Facility AAF reset NOTE The AAF function is used in conjunction with an AAF Control which today is available on the Australian market only The indication in the control unit display during the Acknowledgement Period 10 60 sec and the Investigation Period 0 3 min respectively will automatically disappear when e the AA process ends because no detector in the AAF zone is over the fire alarm level e the AA process ends up in a fire alarm which has higher prior
141. t mode alarm 16 3 16 4 16 5 Heavy smoke alarm Heavy heat alarm Alert Annunciation alarm AA alarm Key cabinet alarm 16 5 1 Key cabinet opened before a fire alarm 40 41 4 42 43 43 44 47 47 48 48 49 50 50 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 16 5 2 Key cabinet opened in conjunction with a fire alarm __ 51 16 6 Co incidence alarm 2 address zone dependence 51 16 7 Delayed alarm 52 16 8 Alarm Acknowledgement Facility AAF 53 16 9 Quiet alarm 54 17 Alarm reset 55 17 1 Pre warning reset 55 17 2 Fire alarm reset 55 17 2 1 All 55 17 2 2 Single 55 17 2 3 Single with automatic disablement 56 17 2 4 Acknowledged and Isolated alarm 56 17 2 5 Test mode alarm 56 17 3 Heavy smoke heat alarm reset 57 17 4 Alert Annunciation 57 17 5 Key cabinet alarm reset 57 17 6 Co incidence alarm 57 17 7 Delayed alarm 57 17 8 Alarm Acknowledgement Facility AAF reset 58 17 9 Quiet alarm reset 58 18 Fault 59 18 1 Fault messages 6l 18 2 Fault acknowledge 11 19 Commissioning an installation 79 19 1 Single Control Unit 79 19 2 Control Units in a TLON network 80 19 2 1 TLON network installation 80 19 3 Adda Control Unit in a TLON network 81l 19 4 Make two TLON networks one 81 19 5 Delete a Control Unit in a TLON network 81 20 Upgrade number of alarm points 83 20 1 Control Units in a TLON network 83 21 Restart 84 22 Access 88 23 Perform monthly te
142. the Service mode for COM loop will be terminated automatically NOTE If short circuit is detected when a COM loop is in service mode the loop will be disabled and a fault message will be displayed OOpa CONTO PEUN E bea Seige amici ames Iles Se Isr Independent of where the short circuit is situated on the loop Menu According to chapter Access see page 88 Scroll to menu H5 Scroll to menu A3 ARESA oaao m ola 1 V No0 Calibration of supervised output Sensitive fault detection mode Service mode for COM loop Display current consumption in control unit Display current consumption on COM loop Display statistics for communication Activate address setting mode for DU SSD information Service mode for loop CU 00 Write loop and control unit B Direction numbers Use V or A Both to scroll to the wanted 121 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x lt Service mode control unit 00 COM loop 0 When you leave this menu Supplied from A direction only by pressing ESC or the service mode will be turned off i e the communication will be turned on in the normal way ESC or A3 Service mode for COM loop Scroll to another menu or e press ESC 122 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 27 4 Display current consumption
143. the alarm points use the push button Alarms queued P8 Next zone Use the soft key Next zone P5 to scroll through the zones in alarm When scrolling through the zones the first alarm point activated in the next zone will be shown The Next zone button will be available only if there are alarms in more than one zone The first alarm will be automatically displayed again 20 seconds after the latest time the Alarms queued or Next zone buttons where used The printer if available will print each fire alarm e g 46 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x ee Fire Alarm Zone 002 Address 03 SMOKE YYYY MM DD hh mm User definable alarm text if programmed Reset of the fire alarms see chapter Alarm reset page 55 16 2 1 Entering the menus during fire alarm By pressing the soft key Menu P4 during fire alarm you will get access to the menu system see Access page 88 NOTE Access code is required In this case a part of the display s alarm window will be temporarily suppressed to permit the display of the menu system First alarm 002 03 4 zones in alarm Latest alarm 003 11 menu H2 Disable or re enable H3 Set calendar and clock H4 Present system status H5 Service H6 FAULT Acknowledge H7 Perform ZONE TEST Test mode H8 Maintenance H9 Interlocking outputs and inputs H10 Change password Escape menu
144. ting Instructions Fire alarm system EBL512 G3 V2 0 x 24 4 Alarm devices H2 B4 All outputs of type Alarm device can be collectively disabled Disabled output will stay in or return to the normal condition for the output respectively Disabled outputs are listed in menu H4 U1 from which it is also possible to get a print out Menu According to chapter Access see page 88 Scroll to menu H2 H2 Disable or re enable H2 Disableorre enabe rl el B1 Zone or Zone Address B2 Output B3 Output type B4 Alarm devices B5 Routing equipment B6 Alert annunciation function Escape menu B4 Alarm devices Scroll to menu B4 Via menu B4 can all outputs of type Alarm device be collectively disabled in all control unit Disable Press 4 to disable All alarm devices which will be indicated with V and a beep The type will directly be shown in the Re enable list eo Disable All alarm devices N ss REEE El eeen All alarm devices Use the soft key gt I to toggle between Disable and Re enable list 101 ESC Panasonic Eco Solutions Nordic AB Disable All alarm devices HRe enable list TI All alarm devices Disable All alarm devices B1 Zone or Zone Address B2 Output B3 Output type B4 Alarm device B5 Routing equipment B6 Alert annunciation function Escape menu 102 MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Press
145. tively Collectively disabled outputs via menus H2 B3 B4 are not limited and must not be counted Up to 200 Interlocking outputs can be individually disabled via menu H9 C3 It is not possible to exceed the limits A warning will be shown Max disablements reached Disablement not performed Don t forget to re enable via menus H2 B1 B2 H8 S1 H9 C3 or use automatic re enablement for zones and alarm points Disablements are listed in menus H4 U1 amp U2 from which it is also possible to get a print out LED Fault Disablements General disablements L10 is indicating one or more disablements in the system Disablements are also shown in the display An example Zone 001 disabled yyyy mm dd hh mm Zone 002 address 01 disabled yyyy mm dd hh mm Number of disablements in system 2 93 Panasonic Eco Solutions Nordic AB MEWO01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x NOTE See chapter The information area priority order page 25 regarding priority order Disablements and faults are indicated by a 2 sec beep when you close the control unit door 94 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 24 1 Zone or Zone Address H2 B1 When a whole zone is disabled all alarm points within the zone will be disabled except the addressable manual call points Not valid for the Australian and New Zealand conventi
146. ued NOTE To scroll browse through the queued zones use the soft key Next zone P5 NOTE Fire alarms are Fire alarm Heavy smoke heat alarm Alert Annunciation AA alarm Key cabinet alarm Acknowledged alarm New Zealand only Isolated alarm New Zealand only Encapsulated reset aut disablement Press Reset P3 and approx 0 1 sec later also Alarms queued P8 See also page 56 Multiple reset when Single reset is selected Press Reset P3 and approx 0 1 sec later also Enter Outputs of type Alarm devices will be de activated The soft key P7 has the function Evacuate in the following conventions Belgian British Standard Hungarian Spanish and Ukrainian In all other conventions it has the function Alert Annunciation Acknowledge 20 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x LED indicators on the Control Panel CP LED indicator Indicating System fault yellow EBL512 G3 is not running because of S W CPU or E memory fault no contact between main board and MMI board or c 1 e restart fault code 00 03 L8 Test mode yellow Zones are in test mode see page 90 and 131 Fault Disablements General fault yellow Fault s in the system 1 e not acknowledged fault s and or not corrected fault s See also page 129 i O L10 General disablements Disablement s in the system Also valid f
147. utput in each interlocking combination area point can be manually activated via this menu The corresponding interlocking input will be monitored in the same way as if the output was activated by its control expression The output in each interlocking combination area point can be manually deactivated via this menu NOTE The output will be deactivated also if its control expression still is true and cannot be activated again until after its control expression has been false again Also a latched output will be deactivated If an interlocking output is activated via its control expression and with latching output selected in EBLWin the output has to be deactivated via this menu Menu According to chapter Access see page 88 Scroll to menu H9 H9 Interlocking outputs and inputs el C1 Activated interlocking outputs inputs C2 Activate deactivate interlocking output C3 Disable re enable interlocking output Scroll to menu C2 C2 Activate deactivate interlocking output el Activate Write area number and Interlocking output area Moo point 00 address and press to activate which will be indicated with V and a beep The output will directly be shown in the Deactivate list Write the area number Activate If the specified output and point e eg 001 and Interlocking output area 001 point 01 doesn t exist it will be W Deactivate list 1 ee eee i Interlocking output area 001 point 01 instead of
148. vices is pressed the following will happen e X is shown in the display 1 e to the right in the Soft key area e The activated outputs programmed for sounders 1 e type Alarm devices will be turned OFF de activated If the push button Silence alarm devices is pressed again the sounders will automatically sound again In case of a new alarm the sounders will automatically sound again In EBLWin the option Button Silence alarm devices disables alarm devices can be selected System properties WinG3 1 1 0 Secceseoosesossoocose V Fault latching Silence Buzzer With Door Switch Z Global Reset of Fan Control Outputs Hashing LED on MCP V Use Daylight saving time F Redundant TLON Network V Enhanced Disablement Button Silence alarm devices disables alarm devices Door Closing by Time Main Power Loss Fault Delay Time minutes E Active 14 17 30 In this case the button Silence alarm devices P2 will have the same function as the menu Error Reference source not found See also chapter Disable or Re enable alarm devices page 35 In the New Zealand convention only the FIRE LEDs will indicate steady instead of blinking when the alarm devices are disabled 2 E g during Fire alarm or Alert Annunciation alarm A Including Addressable siren 3377 4477 Addressable sounder base 3379 and Addressable beacon 4380
149. which you can Disable zones in alarm 18 Panasonic Eco Solutions Nordic AB MEWO1552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x 5 LED indicators and push buttons LEDs and push buttons can vary according to type and configuration convention country language See also Figure 2 page 17 LED D on the Fire Brigade Panel FBP LED LED indicator Indicating Fire 5 red Fire alarms see below Quiet alarm normally Australia only See also chapter Alarm types page 43 L ma 2 Extinguishing red Output s for extinguishing equipment activated Ora programmable input type Extinguishing is activated te Ventilation yellow Output s for fire smoke ventilation equipment activated Or a programmable input type Ventilation is activated input type Activated routing equipment is activated Test of routing equipment in progress see menu H1 5 Operation green The c 1 e is powered via the rectifier and or the battery Alarms queued 2 red More than one alarm point zone have activated fire alarm Fire brigade tx red Output Fire alarm for fire brigade tx routing equipment and or corresponding programmable output s of type Routing equipment is are activated Or a programmable L a Use push button Alarms queued P8 to scroll amongst the alarm points zone address or the soft key Next zone P5 to scroll amongst the zones NOTE Fire alarms are Fire
150. xiglas button 2A Fire brigade key To Like 1 Silence open the door buzzer Silence alarm devices amp Reset buttons 2B Information only Like 2A log on as Like 2A keypad Information only Menu H4 H6 H9 amp H10 2C Building officer Like 2A log on as Like 2A keypad Building officer H1 H4 H6 H7 H9 amp H10 Like 2A log on as Like 2A keypad Service personnel H1 H10 ED a P key download PC EBLWin H W SSD amp S W key special password download reset of alarm counter 3A 3B d Information only i e the faults cannot be acknowledged Menu H9 C1 only Via EBLWin menu System are ten different User names with individual Passwords possible to define in the User data dialog box They can be used to log on to an EBL512 G3 version gt 2 0 and or Web server access Three User names and Passwords are default oul User data Usemame Initials Password BL WEB Type o 000000 E InfomationOnly Building officer BO 111111 W E BuildinaOfficer Service personnel SP RREEF Eil E ServicePersonnel l 000000 E T InformationOnty 000000 F F InformationOnly E Ei informationOnly x E InformationOnty Fi informationOniy x E InformationOnty x InformationOnly 21 Panasonic Eco Solutions Nordic AB MEWO1552 Rev Operating Instructions Fire alarm system EBL512
151. y 512 fire alarms can be shown in the c 1 e display If more than 512 fire alarms Outputs programmed for General pre warning and outputs programmed for the activated pre warning s 44 Panasonic Eco Solutions Nordic AB MEWO01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x are activated no more fire alarms will be shown until one or more of the first 512 fire alarms are reset Normally all fire alarms will be presented in all control units default but it is possible to have Selective alarm presentation i e only fire alarms from selected control units will be presented in the control unit respectively Set in EBLWin for each control unit See also chapter The information area priority order page 25 In accordance with the EN54 2 standard the following happens in case of a fire alarm The buzzer in the c i e sounds 0 4 sec each 0 4 sec 0 4 0 4 sec LEDs Fire L1 are blinking 0 4 0 4 sec Output for routing equipment Fire brigade tx and outputs type Routing equipment are activated Outputs for fire alarm are activated In the c 1 e display a presentation number zone address is shown for the first fire alarm In the c 1 e display a user definable text message alarm text 1s shown if programmed In the c 1 e display is also some additional information presented One alarm point activating fire alarm Example fire alarm zone 002 address 03 w
152. y faults and faults in relation to pollings Number of bit faults is the received number of bit faults and faults in relation to pollings No answer is the received number of answer faults no answers and faults in relation to pollings Bit length fault is the received number of bit length faults and bit length faults in relation to the pollings The number of Parity faults Number of bit faults No answer and Bit length faults shall normally be 0 or as close to 0 as possible If not there are some communication problems that have to be investigated Check the COM loop connections and the loop units All values are set to 0 after restart and or after re connection of COM loop via menu H8 S1 Menu According to chapter Access see page 88 Scroll to menu H5 Sensitive fault detection mode Service mode for COM loop Display current consumption in control unit Display current consumption on COM loop Display statistics for communication Activate address setting mode for DU SSD information Display statistics for communication Write loop number and control unit number and press lt 4 125 Panasonic Eco Solutions Nordic AB MEW01552 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Number of pollings nnnnnnn Note The values are not Parity fault 000000 00 0 live updated Number of bits fault 000000 00 0 No answer 000000 00 0 Bit length fault 000000 00 0 lt 4
153. y statistics for communication Activate address setting mode for DU SSD information r Sensitive fault detection mode is not active Press lt to activate ad 2 Sensitive fault detection mode was activated Press lt to deactivate Mal Sensitive fault detection mode is not active Press lt to activate ESC A2 Sensitive fault detection mode Scroll to another menu or press ESC Scroll to menu A2 PYAR ARo ciela aaao e a 120 Panasonic Eco Solutions Nordic AB MEWO01552 27 3 Rev Operating Instructions Fire alarm system EBL512 G3 V2 0 x Service mode for COM loop H5 A3 This mode can be used when commissioning an installation and by maintenance The COM loop communication polling will be turned off but there is still voltage 24 V DC on the loop in the A direction only in the B direction only or in both directions at the same time A volt meter can be used e g to check the voltage voltage drop on different places on the loop or to find a single break on the loop Since there is voltage on the loop short circuit isolators will work normally It is recommended to do this check also when EBL512 G3 is power supplied via the backup battery only since the battery voltage can be different compared with the rectifier voltage due to the battery condition backup duration etc The Service mode for COM loop is indicated by LED Fault Disablements General disablements L10 If you log off this menu
154. yyyyyy This means that the SSD have not been correctly downloaded A new SSD download has to be performed 87 Panasonic Eco Solutions Nordic AB MEWO01552 22 Rev Access Operating Instructions Fire alarm system EBL512 G3 V2 0 x To use the key pad in the control unit to get access to the menus it is necessary to logon with a User name and a Password for level 2B 2C or 3A See also chapter User level User name amp Password page 27 Open the door in the control unit level 2A press the soft key Menu P4 to log in Enter 0 1 or 2 e g oe Enter the password six digits EBL512 G3 Control Unit XX User definable text User definable text yyyy mm dd hh mm Log in as Information only Building officer Service personnel Service personnel Password Service personnel Password ee a o pa Password six digits menu H2 Disable or re enable H3 Set calendar and clock H4 Present system status H5 Service H6 FAULT Acknowledge H7 Perform ZONE TEST H8 Maintenance H9 Interlocking outputs and inputs H10 Change password 88 Door open XX 00 29 year month date hour minute Soft key Menu 0 1 and 2 are default There might be more users in the list if programmed via EBLWin If you enter 0 no password is required The digits will be replaced by in the display No access will be shown if the password was not co
Download Pdf Manuals
Related Search
Related Contents
XPS 8900 Service Manual Philips SCD282 User's Manual tousimis® SAMDRI®-PVT-3D PRODUCTOS DE CONSUMO GARANTÍA ESTÁNDAR User Manual 3Com V7000 Owner's Manual Shimano XT M770 Shift Lever User Manual Applied Biosystems Prism 377 with 96 BILDUNGS - Deutsches Institut für Erwachsenenbildung Copyright © All rights reserved.