        USER MANUAL
         Contents
1.        2  Choose the operation system you need and follow the instruction  described on the website to download the software     3  When downloading all required files from the internet  enter the  serial No  511C1 01220 0100 478DF2A to install the software     When your computer restarts  the WinPower software will appear as a  green plug icon located in the system tray  near the clock      47     Appendix 1  The Corresponding Form of the  LCD Display                                                                                           No    Operating state sai Alarm warning  1 No Output mode 00 None  2 Deeg e E once every  2 min   3 Line mode 02 None  0 20  Battery capacity Beep once every  Battery sec     mode   21  100  Battery es Beep once every  capacity 4 sec  5 Battery Test mode 04 None  6 Overloaded in Bypass mode 01 Beep twice every sec   7 Overloaded in Line mode 02 Beep twice every sec   8 e Banery moda  03 Beep twice every sec   9 BUS voltage abnormal 05 Continuously beep  10 INV abnormal 06 Continuously beep  11 Overloaded and cut off the output 07 Continuously beep  12 Over temperature 08 Continuously beep  13 Output short circuited 09 Continuously beep  14 Communication abnormal 10 Continuously beep  15 Battery open 11 Continuously beep  16 INV relay failed 12 Continuously beep  17 BAT SCR failed 14 Continuously beep  18 Parallel abnormal 15 Continuously beep  19 ID abnormal 21 Beep once every 10 sec  20 Fan abnormal 22 Beep once every sec  21 Charger and 
2.       To power on the UPS by simply pressing the ON button  continuously for more than 1 second  the buzzer will beep  once     A few seconds later  the UPS turn into Line mode  and the  mode code is    02     If the utility power is abnormal  the UPS will  operate in Battery mode without output interruption of the UPS     2  Turn on the UPS with no utility power supplied  in Battery  mode     1     2     3     After you make sure that the breaker of the battery pack is in  the    ON    position  this step only for long backup time model      Press the ON button continuously for more than 1 second to  power on the UPS  and the buzzer will beep once  UPS  operates in No Output mode  the mode code is    00        A few seconds later  the UPS turn into Battery mode  and the  mode code is    03        3  Turn off the UPS with utility power supplied  in Line mode     1     To turn off the inverter of the UPS by pressing the OFF button  continuously for more than 1 second  and the buzzer will beep  once  The UPS will turn into Bypass mode     DB    6 2    zech    2  Upon completion of the above to turn it off  output of electric  current of the UPS is still present  In order to cut off the output  from the UPS  simply cut off the utility power supply  a few  seconds later  there are not any display is shown on the display  panel and no voltage output is available from the UPS output       Turn off the UPS with no utility power supplied  in Battery    mode     1  To power off the UP
3.     25     3  How to join a new UPS     1     2     Before joining a new UPS  user need to prepare the input and  output wires  the output breaker  and the parallel cable     Turn off the input and output breakers of the new unit  Connect  the input wires  output wires and battery wires  Remove the  short connection wire between JP1 and JP2 on the terminal  block     Turn off the UPS systems that are running  After all of the  running UPSs transfer to the Bypass mode  remove the  maintenance cover board of each UPS and set the  maintenance switch from    UPS    to    BPS     then turn off the input  breaker of each UPS     If the UPS system that is running is a stand alone UPS  you  need to remove the short connection wire between JP1 and  JP2 on the terminal block     Remove the cover board of the parallel port on the new UPS   push one end of the parallel cable into the slot of the parallel kit  and screw up the connector  screw the cover board of the  parallel port back again     Remove the maintenance cover board of the new UPS and set  the maintenance switch from    UPS    to    BPS        Turn on the battery switch and the input breaker of the new  UPS  measure the difference voltage between the output line  wires of new UPS and the parallel system to check if the  voltage difference between them is less than 1V  If the  difference is less than 1V  close the output breaker  If the  difference is more than 1V  check if the wirings are abnormal     Remove the cover board 
4.     70    67   Power    4  Display Panel    Select Button sg    Enter Button  lt     ON Button    OFF Button  Select Button  Enter Button       LCD Screen       ON Button   Alarm Silence             OFF Button    Turn on UPS system  By pressing the ON button    I    the UPS  system is turned on    Deactivate acoustic alarm  By pressing this button an  acoustic alarm can be deactivated     When mains power is normal  the UPS system switches to  Bypass mode by pressing OFF button    bs  and the inverter is  off  At this moment  if Bypass is enabled  then the output    terminals are supplied with voltage via the bypass if the  mains power is available     If the UPS system is in No Output mode or Bypass mode  the  output voltage range  frequency range and Bypass  disable enable could be selected by pressing Select button   and confirmed by pressing Enter button     If the UPS system is in No Output mode or Bypass mode  the  output voltage range  frequency range and Bypass  disable enable could be selected by pressing Select button   and confirmed by pressing Enter button        By pass Operating Inverter Operating  information information  A  E    Input Information  99 8yac 4 e EKOS          Output   gt     PREVA Information  Z    sven pa    888 Voc   ow  MODE 88        88  FE    A     gt  Load    Information    Mode Fault Warning      TC oui  Code Information FAULT          e MASS DOSARE          Iva   28  Wer KEE e BYPASS DOLE       Output voltage and frequency  and Bypass ena
5.    1okvazkw   skvavto skw  0 5KW   2okva takw   4KW    Frequency  Hz  50 60 50 60 50 60 50 60 50 60  E Voltage    176 276 Vac    176 276 Vac    304 478 Vac    304 478 Vac    304 478 Vac    Voltage 240VDC 240VDC 240VDC 240VDC 240VDC  Battery    Voltage 208 220 230 240Vac    26 27 26 25A   43 45 43 42A   43 45 43 42A   65 68 65 63A   87 91 87 83A    Dimension   WxDxH  mm 260x570x717   260x570x717   260x570x717   260x570x717   260x570x717    wma   co   a5  o   oe  os   s  s   s      2  Electrical Performance         Mod O   Notage     Frequency     Power Factor   Factor  46 54Hz  eee   98  S  MOK S Single phase 56 64Hz  Full load   46 54Hz   gt 0 95  3T1 10K 10KS 15KS 20KS Three phase 56 64Hz  Full load        Output    Voltage Power Frequency f f A Current  Regulation Distortion Overload capacity crest ratio       as onze AUS in 105  130  load transfers to  Line mode  AC THD lt 2   Bypass mode after 10 minutes   41    0 7lag  mode  Full load   gt 130  load transfers to Bypass  3 1  RN ER  Linear  mode after 1 second and maximum  freadency in Battery Load  shutdown the output after 1  mode minute    3  Operating Environment    Humidity Altitude Storage temperature       ve ee   06400    Note  if the UPS is installed or used in a place where the altitude is  above than 1000m  the output power must be derated in use  please  refer to the following           Altitude  M    1000   1500   2000   2500   3000   3500   4000   4500   5000  Derating   490  95    91    86    82    78    74
6.   an optional accessory  for AS400 communication  protocol  Please contact your local distributor for details  The following is  the pin assignment and description of DB 9 connector in AS400 card                          Pin   Description UO Pin   Description HO  1 UPS Fail Output 6 Bypass Output  2 Summary Alarm Output 7 Battery Low Output  3 GND Input 8 UPS ON Output  4 Remote Shutdown Input 9 Line Loss Output  5 Common Input                          4 5           BYPASS       SUMMARY ALARM    REMOTE SHUTDOWN    LINE FAIL  COMMON    DB 9 Interface of AS400 communication protocol     46     13  Software for all models    Free Software Download     WinPower   WinPower is a brand new UPS monitoring software  which provides  user friendly interface to monitor and control your UPS  This unique  software provides safely auto shutdown for multi computer systems  while power failure  With this software  users can monitor and control  any UPS on the same LAN no matter how far from the UPSs                         E wimower Manager Ver  D     agent Reed  P fal ES  Spim Log Ws Isok Motor Emmo Lee Help  VN pAMe    Rod UPS States UPS Hanel   1518    OH LAN  agent  4 ey a piy m o   Seege  fore LINE requency goo Ha 4  Be 3 Max Volt mov aa   Kai Tita Volt 160       Medal ON LINE  om Post TEM     Tenp 50 CG     reino Qi y  Rudari 50 V    ici 1m0      204  33335 St  oes at of 13 AS Age Sei    Installation procedure     1  Go to the web site   htto   www ups software download com winoower htm
7.   the other end of the external battery cable is made of three open  wires with ring terminals to connect with the external battery  pack s   for 3T1 15KS 20K  select the UL1015 6AWG 25mm    wire or other insulated wire which complies with AWG Standard  for the UPS battery wirings  The procedure of installing battery  bank should be complied with strictly  Otherwise you may  encounter the hazardous of electric shock     1  ADC breaker must be connected between the battery pack  and the UPS  The capacity of breaker must be not less than  the data specified in the general specification     2  Set the battery pack breaker in    OFF    position and connect  the 20 pieces of batteries in series     3  You must connect the external battery cable to the battery  first  if you connect the cable to the UPS first  you may  encounter the hazardous of electric shock  The positive pole  of the battery is connected to the 6KS UPS with red wire  and  the 10KS 3T1 10KS UPS in parallel with blue and brown  wires  the negative pole of the battery is connected to the  6KS UPS with black wire  and the 10KS 3T1 10KS UPS in  parallel with black and white wires  the green and yellow  ribbon wire is connected to the ground of the battery cabinet      16     3  To complete the connection by plugging the connector of the  external battery cable into the external battery socket of the UPS   Do not attempt to connect any loads to the UPS now  You should  connect the input power wire to the right positio
8.  current  protective function if necessary     9  To connect the load with the UPS  please turn off all the loads  first  then perform the connection and finally turn on the loads  one by one     10  No matter the UPS is connected to the utility power or not  the  output of the UPS may have electricity  The parts inside the  unit may still have hazardous voltage after turning off the UPS   To make the UPS have no output  power off the UPS  and then  disconnect the utility power supply     11  Suggest charging the batteries for 8 hours before use  After  connection  turn the input breaker in the    ON    position  the  UPS will charge the batteries automatically  You can also use  the UPS immediately without charging the batteries first  but  the backup time may be less than the standard value    12  If it is necessary to connect the inductance load such as a  monitor or a laser printer to the UPS  the start up power should  be used for calculating the capacity of the UPS  as its start up  power consumption is too big when it is started     ollollo  o  oj  o     N L JP1 JP2 L N                               siolloliolio  E 8 E e    Input Ground                Output Ground  Input Neutral Output Neutral  Input Line t Output Line    JP1 JP2                   Input and output Terminal Block wiring diagram of 6K S  10K S     Important notes  If the UPS is used in single mode  JPI and JP2  must be connected by 10AWG 6mm    If the UPS is used in parallel  mode  JP1 and JP2 must be d
9.  enter the UPS       The UPS can be operated by any individuals with no previous  experience     1 3 Maintenance  servicing and faults      The UPS operates with hazardous voltages  Repairs may be  carried out only by qualified maintenance personnel     x Caution   risk of electric shock  Even after the unit is disconnected  from the mains power supply  building wiring terminal    components inside the UPS are still connected to the battery  which are potentially dangerous     ER      Before carrying out any kind of service and or maintenance  please  disconnect the batteries  Verify that no current is present and no  hazardous voltage exists in the capacitor or BUS capacitor  terminals       Batteries must be replaced only by qualified personnel       Caution   risk of electric shock  The battery circuit is not isolated  from the input voltage  Hazardous voltages may occur between  the battery terminals and the ground  Verify that no voltage is  present before servicing       Batteries have a high short circuit current and pose a risk of shock   Take all precautionary measures specified below and any other  measures necessary when working with batteries         remove all jewellery  wristwatches  rings and other metal  objects        use only tools with insulated grips and handles     x When changing batteries  replace with the same quantity and the  same type of batteries       Do not attempt to dispose of batteries by burning them  It could  cause explosion     x Do not op
10.  g  laser printers  etc  to the UPS output      Place cables in such a way that no one can step on or trip over  them    x UPS has provided earthed terminal  in the final installed system  configuration  equipotential earth bonding to the external UPS  battery cabinets    x An integral single emergency switching device which prevents  further supply to the load by the UPS in any mode of operation  should be provided in the building wiring installation    x An appropriate disconnect device as short circuit backup    protection should be provided in the building wiring installation      1     x For three phase equipment connection to an IT power system  a  four pole device which disconnect all phase conductors and the  neutral conductor should be provided in the building wiring  installation    x This is permanently connected equipment  it must be installed by  qualified maintenance personnel      Earth connection essential before connecting to the building wiring  terminal     1 2 Operation      Do not disconnect the earth conductor cable on the UPS or the  building wiring terminals in any time since this would cancel the  protective earthing of the UPS system and of all connected loads       The UPS output terminal block may be electrically lived even if the  UPS system is not connected to the building wiring terminal       In order to fully disconnect the UPS  first press the OFF button   then disconnect the mains lead       Ensure that no liquid or other foreign objects can
11.  of    230Vac        240Vac        50Hz        60Hz         Bypass Disable        Bypass Enable    in turn  And if press the Enter button  for more than one second at this time  the flickering black round dot  would turn to flicker less and the output voltage rating or frequency  rating or bypass state setting would be modified to the selected value   And if no any pressing on the Select or Enter button lasting for more  than ten seconds  the flickering black round dot would disappear  no  setting have be modified     The only one voltage rating could be selected in    208Vac        220Vac         230Vac        240Vac    at any time  only one frequency rating could be  selected in    50Hz        60Hz    at any time  and the output voltage and  frequency would be changed to the corresponding value after turning on    the UPS by pressing the ON button     The UPS would turn into Bypass mode in several seconds after    Bypass  Enable    is selected  and turn into No Output mode in several seconds  after    Bypass Disable    is selected      Note  When the output voltage rating be set to 208V  the output power  must be derated to 90      Here is an example for changing the output voltage from 220Vac to  230Vac through the LCD panel      4 1           CO IVAC  HZ e23vac  S0Hz 50 Hz    l  55                STEP 1  One flickering black round dot would appear in front of     208Vac    after pressing the Select button           Co IVAC    S0Hz    ee 3vac     BYPASS fe    SGHz       20
12. 8 Vac  gt       Ava e 50HZ BYPASS DISABLE      BYPASS ENABLE                STEP 2  The flickering dot would move to the front of    230Vac    after  pressing the Select button two times again      4 2           Pesvac   EZA        223vac    S0Hz     GHz       MODE O   l G5          Ld                 STEP 3  The dot in the front of 230Vac would turn to flickerless after  pressing the Enter button  and the flickering dot would move to  the next    240Vac                 223v     EMESI     223Vvac  Guz    S0Hz    l  MODE Q   55    208 Vac e 230 Vac e SHZ BYPASS DISABLE  220 Vac 240 Vac 60 HZ e BYPASS ENABLE                STEP 4  The output voltage rating have been modified to    230Vac     and  UPS work in Bypass mode      4 3           Co 3Vac             g 3OVAC  S0Hz S0Hz  a INVERTER lia  S4    208 Vac e 20Vac e SOHZ BYPASS DISABLE  220 Vac 240 Vac 60 HZ   BYPASS ENABLE          STEP 5  The output voltage would be 230Vac after the UPS is turned    on     AA        12  Communication Port  12 1 RS232 Interface    The following is the pin assignment and description of DB 9 connector        12 2 Intelligent slot    This series is equipped with an intelligent slot for Webpower  optional  accessory  or other optional card to achieve remote management of the  UPS through internet   intranet  Please contact your local distributor for    further information     12 3 AS400 Interface  Option     Except for the communication protocol as mentioned above  this series  UPS has AS400 card
13. Explanation Symbol Explanation  Alert you to pay    A special attention    Protective ground    fhi  A ja igh m   Alarm silence    Turn on the UPS 2 Overload indication    Turn off the UPS  j L Battery    Idle or shut down    Alternating current x Do not dispose with  source  AC  ordinary trash       Direct current  source  DC              3  Introduction    3 1 System and model description    This Online Series is an uninterruptible power supply incorporating  double conversion technology  It provides perfect protection  specifically for computer equipment  communication systems to  computerized instruments     Its true online double conversion design eliminates all mains power  disturbances  A rectifier converts the alternating current from the  utility power to direct current  This direct current charges the  batteries and powers the inverter  On the basis of this DC voltage   the inverter generates a pure sinusoidal AC voltage  which is  constantly powering the loads     Computers and Peripherals are thus powered entirely by the UPS  In  the event of power failure  the maintenance free batteries power the  inverter     This manual is applicable to the following models        Model No  Type  6K  10K Standard   3T1 10K  6KS  10KS  3T1 10KS Long backup time  3T1 15KS  3T1 20KS                                           S    Model  Long backup time    3 2 Product Specification and Performance    1  General Specification    Power   Power Rating     ekva a 2kw   2KW   1okvazkw  
14. S  it is recommended to select the UL1015  10AWG 6mm   wire or other insulated wire which complies  with AWG Standard for the UPS input and output wirings     3  For 10K S  3T1 10K 10KS UPS  it is recommended to select  the UL1015 8AWG 10mm   wire or other insulated wire which  complies with AWG Standard for the UPS input and output  wirings    4  For 3T1 15KS  20KS UPS  it is recommended to select the  UL1015 6AWG 25mm   wire or other insulated wire which  complies with AWG Standard for the UPS input and output  wirings    Note  Do not use the wall receptacle as the input power source for  the UPS  as its rated current is less than the UPS   s maximum  input current  Otherwise the receptacle may be burned and  destroyed     5  Connect the input and output wires to the corresponding input  and output terminals according to the following diagram     Note  you must make sure that the input and output wires and the  input and output terminals are connected tightly     6  The protective earth ground wire refers to the wire connection  between the equipment which consumes electric equipment  and the ground wire  The wire diameter of protective earth  ground wire should be at least as above mentioned for each  model and green wire or green wire with yellow ribbon wire is  used      13     7  After having completed the installation  make sure the wiring is  correct     8  Please install the output breaker between the output terminal  and the load  and the breaker should with leakage
15. S by pressing the OFF button continuously  for more than 1 second  and the buzzer will beep once     2  When being powered off  the UPS will turn into No Output  mode  Finally not any display is shown on the display panel  and no voltage is available from the UPS output     Suggestions  Please turn off the connected loads before turning  on the UPS and turn on the loads one by one after the UPS is  working in INV mode  Turn off all of the connected loads before  turning off the UPS     Parallel Operation      Parallel Machine Maintenance    This UPS system has parallel machine function  if you want to add  single machine to parallel system  please follow operational process  of joining new machine  if because of cutting down load or attainting  UPS  and you must remove UPS  please follow operational  processes of removing parallel machine       How to install a new parallel UPS system     1  Before installing a new parallel UPS system  user need to  prepare the input and output wires  the output breaker  and the  parallel cable     2  Turn off the input and output breakers of each UPS  Connect  the input wires  output wires and battery wires  Remove the  short connection wire between JP1 and JP2 on the terminal    EM    block  Remove the maintenance cover board of each UPS and  set the maintenance switch from    UPS    to    BPS        Remove the cover board of the parallel port on the UPS   connect each UPS one by one with the parallel cable  screw  the cover board of the pa
16. USER MANUAL    LCD 6 20Kva models    Uninterruptible Power System       Please comply with all warnings and operating  instructions in this manual and on the unit strictly   Save this manual properly  Do not operate this unit  before reading through all safety information and    operating instructions carefully     TABLE OF CONTENTS     Safety and EMC Instructions                 1  1 1 Installation seen E ge TEE REES ST 1  Re ceia hehe 2  1 3 Maintenance  servicing and faults                      2  UR e e E 3  1 5 Storage     gt  see ss isa isad Ee 4  1 6 Standards EE 4     Description of commonly used symbols     5     Introduction                                  6  3 1 System and model description                       7  3 2 Product Specification and Performance              7   Display Panel te 22  eapso see ee 9     Installation 22 242222 sees pocos EE 12  5 1 Unpacking and Inspection    lt  s eesssss 2 esheranbecae  12  5 2 Input and output power cords and protective earth   ground installation massas esse e gege 12  5 3 Operating procedure for connecting the long backup   time model UPS with the external battery             16  ER WEE 17     Operation   ohne ignites a tado do are aa 23  6 1 Operation Mode                    ee iii 23  6 2 Parallel Operation E 24  6 3 Backup time for the standard model                   29    Battery Maintenance                         30    Notes for Battery Disposal and Battery  Replacement   ts ere ys Sana sia dn 31    9 Trouble S
17. ackaging and check the package contents  The   shipping package contains    e AUPS   e A user manual     A communication cable   o A battery cable  for 6KS 10KS 3T1 10KS only    2  Inspect the appearance of the UPS to see if there is any damage  during transportation  Do not turn on the unit and notify the carrier  and dealer immediately if there is any damage or lacking of some  parts     5 2 Input and output power cords and protective earth  ground installation    1  Notes for installation    1  The UPS must be installed in a location with good ventilation   far away from water  inflammable gas and corrosive agents    2  Ensure the air vents on the front and rear of the UPS are not  blocked  Allow at least 0 5m of space on each side    3  Condensation to water drops may occur if the UPS is unpacked  in a very low temperature environment  In this case it is  necessary to wait until the UPS is fully dried inside out before  proceeding installation and use  Otherwise there are hazards of  electric shock      12     2  Installation    Installation and wiring must be performed in accordance with the local  electric code and the following instructions by professional personnel     For safety  please cut off the mains power switch before installation   The battery breaker also needs to be cut off if it is a long backup time  model     S    model      1    Open the terminal block cover located on the rear panel of the  UPS  please refer to the appearance diagram     2  For 6K S  UP
18. are not failed           The Warning code  is    23     the buzzer  beeps every  second        The charger of the  UPS is defective        Please contact the distributor or  service center         32           The Fault code is     11     the UPS  beeps continuously     Battery low or battery  not connected     Check the battery  If the battery is  damaged  replace the battery  immediately and ensure that the  battery breaker is in    ON     position        The utility power is  normal  but the  UPS can not turn  into Line mode    Maintain switch loose    Please contact the distributor or  service center        Battery discharging  time diminishes    Battery not yet been  fully charged     Keep UPS connected to utility  power persistently for more than  10 hours to recharge the  batteries again        Check the loads and remove the       eS overibaded  non critical equipment   Replace the batteries  Please  contact the distributor to obtain  Battery aged     the parts and replacement  service        The UPS cannot  power on after  pressing the ON  button       The ON button is  pressed too briefly     Press the ON button for more  than 1 second        The UPS is not  connected to the  battery or the battery  pack voltage is too low     Check the battery or recharge the  battery           UPS fault        Please contact the distributor or  service center        When you contact the service center  please provide the following    information     e Model No  and the serial No  o
19. battery failed 23 Beep once every sec        4 8        Appendix 2  Rear Panel    Communication  Por     Inte ligent Slot    Cooling Fan  Parallel Port    Pxtema  Bullery    Input Breaker Ma nterance    Bypass Sw ter       Terminal Blucks  aver          Back view of 6K Back view of 6KS    Communicatiar  Por           a            E L4  Intelligent Slol    Gooling Fan     Parallel  Part    Maintenance  Bypass Sw tch    Inpul Breaker       Terminal Blacks  Cover          Back view of 10K 3T1 10K Back view of 10KS 3T1 10KS     49        Fan    Intelligent Slot Parallel Port    RS232    Maintenance    Input Breaker Switch    Terminal Blocks  Cover       Back View of 3T1 15KS 20KS     5 0     614 03714 03    
20. ble    disable  Selection Information    Battery Information    LCD Display       Display Function       Input Information         B86vac Indicates the input voltage value  which could be  displayed from 0 to 999Vac       DO Hz Indicates the frequency value of input voltage  which  could be displayed from 0 to 99Hz       H Indicates the input voltage is higher than the SPEC  range  if the voltage is normally  it can not be displayed       L Indicates the input voltage is lower than the SPEC range   if the voltage is normally  it can not be displayed       Output Information       g D a VAC Indicates the UPS output voltage value  which could be  displayed from 0 to 999Vac       a D H Z Indicates the frequency value of the UPS output voltage   which could be displayed from 0 to 99Hz       Load Information       Indicates the load percent in Watt or VA  only the  t ow i e   BB Me va maximum value of them could be displayed from O to  199                  10        SHORT Indicates the UPS output is short and the UPS would  shut down    OVER LOAD Indicates the load is over the SPEC range    Battery Information             D Em D Voc Indicates the battery voltage value  which could be  displayed from 0 to 999Vdc       Indicates the battery capacitance percent  which could be  188     E  displayed from 0 to 199     OVER CHARGE Indicates the battery is over charged  and the UPS would    be switched to Battery mode          LOW Indicates the battery is weak  and the UPS would shut  do
21. d the  buzzer beeps  continuously     The UPS transfers to  fault mode due to  internal overheat     Make sure the UPS is not  overloaded  the air vents are not  blocked and the ambient  temperature is not too high  Wait  for 10 minutes for the UPS to  cool down before turning on  again  If failed  please contact the  distributor or service center        The Fault code is     09     and the  buzzer beeps  continuously     The UPS output is  short circuited     Remove all the loads  Turn off the  UPS  Ensure that the load is not  failed or the UPS has no internal  faults before turning it on again  If  failed  please contact the  distributor or service center        The Fault code is     05    or    06     the  UPS beeps  continuously     The UPS transfers to  fault mode due to its  internal fault     Please contact the distributor or  service center        The Mode code is     03     UPS turn into  Battery mode     The voltage or  frequency of the utility  power is out of the  input range of the  UPS     The UPS is running in Battery  mode  To save your data and  close the application program   Make sure the utility power is  within the input voltage or  frequency range permitted by the  UPS        The Fault code is     07     the UPS  beeps continuously     The UPS is  overloaded or the  load equipment is  faulty     Check the loads and remove all  no critical equipment   Recalculate the load power and  reduce the number of loads  connected to the UPS  Check  that the loads 
22. ebugging  please    perform maintenance according to the steps of removing a  stand alone     4  How to remove a single UPS from the parallel system     1     2     If you need to remove one UPS of the UPSs parallel system  which is on normal running  press the OFF button of the UPS  that is confirmed to be removed twice continuously and the  UPS will cut off its output immediately     Turn off the input breaker  the external mains input breaker  the  output breaker and the battery switch of the UPS that will be  removed     HOT      Press the others UPSs   s OFF button  After all of them transfer  to the Bypass mode  remove the cover board of each UPS and  set the maintenance switch from    UPS    to    BPS    and then turn  off the input breaker of each UPS     After you remove one UPS  you need to connect the short  connection wire of the JP1 and JP2 located on the Terminal  block of the UPS if the remained UPS system only remain one  UPS runs by itself    After all panels of the UPSs do not display anything any more   remove the cover board of the parallel port on the UPS  connected with the parallel cable of the UPS that need to be  removed  Remove the parallel cable and screw the cover board  of the parallel port back again     Remove the cover board of the parallel port located on the UPS  that need to be removed and remove the parallel cable  and  then screw the cover board back again     Close all of the input mains breakers of the remained UPSs   After all UPSs tran
23. egulated sealed lead acid  maintenance free battery  These models require minimal repairs   The only requirement is to charge the UPS regularly in order to  maximize the expected life of the battery  When being connected  to the utility power  whether the UPS is turned on or not  the UPS  keeps charging the batteries and also offers the protective  function of overcharging and over discharging     e The UPS should be charged once every 4 to 6 months if it has  not been used for a long time     e Inthe regions of hot climates  the battery should be charged and  discharged every 2 months  The standard charging time should  be at least 12 hours     e Under normal conditions  the battery life lasts 3 to 5 years  In  case if the battery is found not in good condition  earlier  replacement should be made  Battery replacement should be  performed by qualified personnel     e Replace batteries with the same number and same type of  batteries     e Do not replace the battery individually  All the batteries should be  replaced at the same time following the instructions of the  battery supplier     e Normally  the batteries should be charged and discharged once  every 4 to 6 months  Charging should begin after the UPS shuts  down automatically in the course of discharging  the standard  charging time for the standard UPS should be at least 12 hours      30     8  Notes for Battery Disposal and Battery  Replacement    1     2     Before disposing of batteries  remove conductive jewelry 
24. en or destroy batteries  Effluent electrolyte can cause  injury to the skin and eyes  It may be toxic     x Please replace the fuse only by a fuse of the same type and of the  same amperage in order to avoid fire hazards       Do not dismantle the UPS  except the qualified maintenance  personnel     1 4 Transport      Please transport the UPS only in the original packaging  to protect  against shock and impact      1 5 Storage    x The UPS must be stockpiled in the room where it is ventilated and    dry     1 6 Standards                                                      Safety   IEC EN 62040 1 1     EMI   Conducted Emission                    IEC EN 62040 2 Category C3  Radiated Emission                         IEC EN 62040 2 Category C3   EMS   ED    IEC EN 61000 4 2   Level 4  RS    eee JEGEN 61000 4 3   Level 3   e D  IEC EN 61000 4 4   Level 4  SURGE e r  IEC EN 61000 4 5   Level 4   OS RO RE EC  IEC EN 61000 4 6   Level 3  Power frequency Magnetic field      IEC EN 61000 4 8   Level 3   Low Frequency Signals                 IEC EN 61000 2 2   Warning  This is a product for commercial and industrial application  in the second environment installation restrictions or additional  measures may be needed to prevent disturbances           2  Description of commonly used symbols    Some or all of the following symbols may be used in this manual  It is  advisable to familiarize yourself with them and understand their                   meaning   Symbol and Explanation  Symbol 
25. f battery test mode is same as Battery mode  but    H     and    L    would not be shown unless the input line voltage is higher  or lower than the SPEC range during the time of battery test  The  operating mode code of the UPS is    03    in Battery mode  and the  code is    04    in Battery Test mode     10 5 Parallel mode    The LCD display can show the UPS quantity of the parallel system   and the UPS system that operating in single mode should be  regarded as a special parallel system  single mode is a special  parallel mode     The LCD display in parallel mode is shown in the following  diagram  When the UPS operating in parallel mode  the  information in code display alternates between symbol    Pn    and  Mode code  The symbol    P    means the UPS operating in parallel    Tea    mode  and the number    n    indicate the quantity     228vac 2e2Bvac  S0Hz S0Hz          Ma            BYPASS DISABLE    e 220 Vac 240 Vac 60 HZ   BYPASS ENABLE       Parallel mode    10 6 Warning mode    The LCD display in warning mode is shown in the following  diagram  The information about the utility power  the battery  the  UPS output and the load could be displayed  The symbol    MODE     not be shown and the symbol    WARNING    is shown instead in  code display      3 8     2  SVac 22Svac  GHz GHz         INN hl           wl    e74Vvoc 43           wu      WARNING     BATTERY  208 Vac 230 Vac e DHz BYPASS DISABLE    e 220 Vac 240 Vac 60 HZ e BYPASS ENABLE       Warning mode  Fan Err
26. f the UPS   e The date when the problem arose   e Complete description of the problem  including the LCD display   code  alarm warning  and power condition and load capacity  If your  UPS is a long backup time model  you may also provide the    information of the external battery pack      3 3        10  Operating mode for all models    The different codes could be displayed on the LCD screen  corresponding to their own operating modes  and they are illustrated as  the follow   Operating mode Operating mode  Mode Code Table  No Output mode Battery mode             Bypass mode Battery test mode       Line mode       Warning Code Table  ID Loss Charger Bad   Fan Error IP Fuse Open  Fault Code Table  Bus Fault Bypass STS Short  Inverter Fault Battery SCR Short                      Overload Fault Parallel Communication Fail       Over temperature Fault Current Un share Fault       Inverter Short Error Model       Communication Fault SCI RX Error       Battery Open Negative Output Power Fault       Inverter Relay Short                10 1 No Output mode    The LCD display in no output mode is shown in the following  diagram  The information about the utility power  the battery  the  UPS output and the load could be displayed  The operating mode  code of the UPS is    00         34        2 iBVac G amp GSVac  S0Hz DH         2 t4Voc Don  MODE DO     100 meng      BATTERY  208 Vac 230 Vac e 5 HZ BYPASS DISABLE  e 220 Vac 240 Vac 60 HZ e BYPASS ENABLE  No Output mode    The UPS have 
27. hooting                               32    10  Operating mode for all models               10 1 ING Qutp  t mode sissies RE teem posta sigs  10 2 Bypass modo  ere ia a  10 3 LING MDG   gt   ses eee seriis i ns su ta ga oe ai Ee  10 4 Battery mode   Battery Test mode                     10 5 Parallel mode neige Ee eeg  10 6 Warning mode    sesrs   gt uecossssocesssasaassssss css     07 E rte EEN  11  Setting by LCD Module                        12  Communication Port                         12 1 RS232 Int  rf  ce     seertmriet erie spe sdamisi nnna  12 2 lnt  llige  tslot ee KE Ee Ee gtt  12 3 AS400 Interface Option  een   13  Software for all models                       Appendix 1 The Corresponding Form of   the LCD Display                      Appendix 2 Rear Panel                            1  Safety and EMC instructions       Please read carefully the following user manual and the  safety instructions before installing the unit or using the unit              1 1 Installation  x Condensation may occur if the UPS is moved directly from a cold  to a warm environment  The UPS must be absolutely dry before  being installed  Please allow an acclimatization time of at least two  hours     x Do not install the UPS near water or in damp environment      Do not install the UPS where it would be exposed to direct sunlight  or near heat      Do not block ventilation openings in the UPS   s housing    x Do not connect appliances or items of equipment which would  overload the UPS  e
28. ion is stable  before supplying power of the generator to the UPS  be sure  that the UPS is in idle mode   Then turn on the UPS according  to the start up procedure  After the UPS is turned on  then the  loads can be connected to the UPS one by one      36     e The power capacity of the AC generator should be at least  twice of the UPS capacity     10 4 Battery mode   Battery Test mode    The LCD display in Battery mode is shown in the following  diagram  The information about the utility power  the battery  the  UPS output and the load could be displayed  The block of     INVERTER     indicates the inverter is working     When the UPS is running in Battery mode  the buzzer beeps once  every 4 seconds  If the ON button on the front panel is pressed  for more than 1 second again  the buzzer will stop beeping  in  silence mode   Press the ON button once again for more than 1  second to resume the alarm function     If the UPS is working in Battery mode for the input line voltage is  higher than the SPEC range  the alarm symbol    H    will be shown   if the UPS is working in Battery mode for the input line voltage is  lower than the SPEC range  the alarm symbol    L    will be shown  if  the input line voltage is lost  both    H    and    L    would not be shown  but the input voltage and frequency are shown as zero     dear    S0Hz  INVERTER ee m       MODE O 3    Ld          BYPASS DISABLE    e 220 Vac 240 Vac 60 HZ e BYPASS ENABLE       Battery mode     37     The display o
29. isconnected      14         o   o   o   o   o   o     C mp JP2 L N  Input Ground      Input Neutral  Input Line Wire A  Input Line Wire B    Input Line Wire C    El  0  gt  0     06          Output Ground               Output Neutral  Output Line  JP1   JP2    Input and output Terminal Block wiring diagram of 3T1 10K 10KS    Important notes  If the UPS is used in single mode  JPI and JP2  must be connected by 10AWG 6mm      If the UPS is used in parallel  mode  JP1 and JP2 must be removed        Slide   es e  s o   o   o   o  SASL          Input Ground Output Ground    E    Input Neutral Output Neutral       Input Line Wire A Output Line  Input Line Wire B Battery    Input Line Wire C t Battery      Input and output Terminal Block wiring diagram of 3T1 15KS 20KS  Important notes  If the UPS is used in single mode  JPI and JP2    must be connected  If the UPS is used in parallel mode  the Jumper  between JP1 and JP2 must be removed      15     5 3 Operating procedure for connecting the long backup  time model UPS with the external battery    1  The nominal DC voltage of external battery pack is 240VDC  Each  battery pack consists of 20 pieces of 12V maintenance free  batteries in series  To achieve longer backup time  it is possible to  connect multi battery packs  but the principle of    same voltage   same type    should be strictly followed     2  For 6KS 10KS 3T1 10KS  the connector of the external battery  cable is used to plug into the external battery socket of the UPS 
30. m the  input wiring of each UPS     Connect the output wires of each UPS to an output breaker  panel    Disconnect the Jumper on JP1 and JP2 of the terminal block  first  and connect each output breaker to a main output breaker  and then to the loads     Each UPS need an independent battery pack     Please refer to the wiring diagram in the next page  and opt  suitable breaker     The requirement of the output wiring is as follows     e When the distance between the UPSs in parallel and the  breaker panel is less than 20 meters  the difference between  the wires of input  amp  output of the UPSs is required to be less  than 20     e When the distance between the UPSs in parallel and the  breaker panel is greater than 20 meters  the difference  between the wires of input  amp  output of the UPSs is required  to be less than 10      ER    eise jojjesed  S yOL  S A9 40 Wesbelp Buim    EN  ki   cl E  25 o E    0 E Z 28  oz 3 S 2 6  sg S J3 O  55 5 J TO    gt  s  gt     S S  66 6 SZ SS    Jeyeeug indino ZSAN 4042019 INdINO LSAN    3942919 Induj ZSdN    Za    df so tar     o   o  fo   o  fo  fo   o  fo  fo  fo  fo   e         19     UIS S  S  ojjesed SYOL MOL LLE Jo wesbelp Bury    Output Ground  Output Neutral  Input Line Wire C  Input Line Wire B  Input Line Wire A    Output Line  Input Neutral  Input Ground    3342319 1NdINO ZSdN Jayeasg INdINO LSdN    sayeoug Ndu ZSdN    td    tae ear Lat    fajolalaralelolal fajolalararclaral        20     UIS S  S  ojjesed Sy0Z SASL LLE 40 we
31. n first  And then  set the breaker of the battery pack in the    ON    position  After that  set the input breaker in the    ON    position  The UPS begins to  charge the battery packs at the time     The blue  amp  brown or red wires for connection to the  positive terminal of the battery pack output    The black  amp  white or black   d wires for connection to the  Tere negative terminal of the   The receptacle for Eq battery pack output        E    connecting NEES The green and yellow ribbon wire    for connection to the ground of  the battery cabinet       5 4 Parallel operation    1  Brief introduction of the redundancy    N X is currently the most reliable power supply structure  N  represents the minimum UPS number that the total load needs  X  represents the redundant UPS number  i e  the fault UPS number  that the system can handle simultaneously  The bigger the X is  the  higher reliability of the power system is  For occasions where  reliability is highly depended on  N X is the optimal mode     As long as the UPS is equipped with parallel cables  up to 3 UPSs  can be connected in parallel to realize output power sharing and  power redundancy      17     2  Parallel installation    1     Users need to opt a standard 25 pin communication cable   which should have 25 cores  corresponding stitches and shield   as the UPS parallel cable  The length of the parallel cable is  appropriate to be less than 3 m     Strictly follow the stand alone wiring requirement to perfor
32. no output in the mode     10 2 Bypass mode    The LCD display in Bypass mode is shown in the following  diagram  The information about the utility power  the battery  the  UPS output and the load could be displayed  The operating mode  code of the UPS is    01     The block of    BYPASS    indicates the  bypass is working  The UPS will beep once every 2 minutes in  Bypass mode     223v   ER       223vac  Su      Skz                   63           MODE    208 Vac 230 Vac e SHZ BYPASS DISABLE  e 22 Vac 240 Vac 60 HZ e BYPASS ENABLE       Bypass mode    ag Bs    The UPS does not have the backup function when it is in Bypass  mode  The power used by the load is supplied from the utility  power via internal filter     10 3 Line mode    The LCD display in Line mode is shown in the following diagram   The information about the utility power  the battery  the UPS output  and the load could be displayed  The block of    INVERTER     indicates the inverter is working  The operating mode code of the  UPS is    02        CoBVAc eeSvac  SOHz S0Hz         IT INVERTER rer rz       e 2200 Vac 240 VAC 60 HZ e BYPASS ENABLE       Line mode    If output overloaded  the load percent is shown and alarm will keep  twice every second  You should get rid of some unnecessary loads  one by one to decrease the loads connected to the UPS less than  90  of its nominal power capacity     Note  Please follow the following steps to connect the generator     e Activate the generator and wait until the operat
33. of the parallel port located on the UPS  which has transferred to the maintenance bypass and push the  other end of the parallel cable into the slot of the parallel kit and  fasten the connector  Screw the cover board of the parallel port  back again      2 6     9     Close the input breakers of all of the UPSs  including the new  UPS  in the parallel system  After all of the UPSs transfer to the  Bypass mode  screw the maintenance cover board back again     10  Turn on each UPS in turn and observe their display  Make sure    that each UPS displays normal and all the UPSs transfer to the  INV mode together  Measure the voltage on the JP1 and JP2  on the terminal block of each UPS to check if the voltage  difference between them is less than 1V  If the voltage  difference is more than 1V  the output relay of the UPS may not  be closed     11  Measure the voltage of each JP2 on each UPS to check if the    voltage value is less than 5V  Generally 2V   If the difference is  more than 5V  that means the new UPS needs to be regulated  again or you need to check that the parallel cable of the parallel  kit are normal     12  Turn off each UPS in turn and after all of them transfer to the    Bypass mode  remove the maintenance cover board of each  UPS and set the maintenance switch from    BPS    to    UPS    and  screw the maintenance cover board back again     13  Turn on the UPSs in the Line mode to perform the parallel    operation     Note  If the UPS is abnormal in the above d
34. or     10 7 Fault mode    The LCD display in fault is shown in the following diagram  The  information about the utility power  the battery  the UPS output and  the load could be displayed  The symbol    MODE    not be shown  and the symbol    FAULT    is shown instead in code display        FE iSVac  pZ      2 i9Vac  eu        Skz            ra A Gd VDO   199           gt   BATTERY    208 Vac 230 Vac e Hz BYPASS DISABLE    e 220 Vic 240 Vac 60 HZ e BYPASS ENABLE       Fault mode  Bus Fault      39     Note  If mode code is    10     it means that    Inner Communication  Fault     and all the information of the UPS have not be shown  except fault code information  like the following diagram       FAULT    nm  LJ    Communication Fault mode     40     11  Setting by LCD Module    The output voltage rating and frequency rating and bypass state could  be set directly through LCD Display  The output voltage rating could be  set to 208V   220V  230V and 240V  The output frequency rating could  be set to 50Hz and 60Hz  The bypass state could be set to enable and  disable  But all the settings could only be done when the UPS is in  Bypass or No Output mode     In Bypass or No Output mode  press the Select button on the LCD panel  for more than one second  a flickering black round dot would be shown  in the front of    208Vac    on the screen  And if press the Select button  continuously again  the flickering black round dot would move to the  front of    220Vac     next to the front
35. rallel port back again     Turn on the battery switch and the input breaker of the each  UPS  measure the difference voltage between the output line  wires of each UPS to check if the voltage difference between  them is less than 1V  If the difference is less than 1V  close the  output breaker  If the difference is more than 1V  check if the  wirings are abnormal     Close the input breakers of all of the UPSs in the parallel  system  After all of the UPSs transfer to the Bypass mode   screw the maintenance cover board back again     Turn on each UPS in turn and observe their display  Make sure  that each UPS displays normal and all the UPSs transfer to the  INV mode together  Measure the voltage on the JP1 and JP2  on the terminal block of each UPS to check if the voltage  difference between them is less than 1V  If the voltage  difference is more than 1V  the output relay of the UPS may not  be closed     Measure the voltage of each JP2 on each UPS to check if the  voltage value is less than 5V  Generally 2V   If the difference is  more than 5V  that means the UPS needs to be regulated again  or you need to check that the parallel cable of the parallel kit  are normal    Turn off each UPS in turn and after all of them transfer to the  Bypass mode  remove the maintenance cover board of each  UPS and set the maintenance switch from    BPS    to    UPS    and  screw the maintenance cover board back again    Turn on the UPSs in the Line mode to perform the parallel  operation  
36. sbeip Bui     o a q  ZE e e Es  55 e 2 2 E Ee  o E E   E E  o 53  cz 3 q   E     E BB  E t   E all al all zo  os E   2 355 555  55 5 a a a a a aa  OO C o a E    E E E      enga MANO ZSdN Jayeag iNndINOLSGN Yy        2 1     soyeosg Ndui ZSdN    I Ie  I  el  2  1 I fo   2  2  I fe   el 21 I    3  Operation and maintenance    1  To perform the general operation  follow the stand alone  operating requirement     2  Startup  The units transfer to INV mode simultaneously as they  start up sequentially in Line mode     3  Shutdown  the units shut down sequentially in INV mode  When  the last one completes the shutdown action  each unit will shut  down the inverter simultaneously and transfer to Bypass mode     It is easy to operate the equipment  with no previous training  You  just need to read through this manual and operate according to the  instructions in it     Input switchboard       UPS UPS UPS       Output switchboard       Load Load Load Load    Parallel Installation Diagram     2 2     6  Operation    6 1 Operation Mode    1  Turn on the UPS with utility power supplied  in Line mode     1     After you make sure that the power supply connection is correct   and then set the breaker of the battery pack in the    ON     position  this step only for long backup time model   after that  set the input breaker in the    ON    position  At this time the fan  rotates and the UPS supplies power to the load via the bypass   The UPS operates in Bypass mode  the mode code is    01  
37. sfer to the Bypass mode  set the UPS  maintenance switch from    BPS    to    UPS    and screw the  maintenance cover board back again  Then turn on all of the  UPSs in the Line mode to perform the parallel operation     If the removed UPS will be used in a stand alone mode  then  JP1 and JP2 on the terminal block should be connected with a  short connection wire     Combine machine warning     1  When UPS combine system work at inverter mode  make  sure that all UPS maintain switches at the same place  that  is to say  be at the position of    UPS     or be at the position  of    BPS        2  When turning on the UPS combine system before enter  into inverter mode  UPS output switch must at the    OFF     position      2 8     3  When UPS combine system work at inverter model  please  do not operate any UPS maintain switch     6 3 Backup time for the standard model    The backup time of the long backup time model is dependent on the  external battery pack capacity and the load level as well as other  factors     The backup time of standard model may vary from different models  and load level  Please refer to the following                                60  50  E e  E E 40  o     E E    ei  oD      gt  30  D D         o O  A Vd 20  O O  10  D 25  60  75  100  0 25  50  75  100   Load level Load level  Backup time of 6K Backup time of 10K     2 9     7  Battery Maintenance    e This series UPS only requires minimal maintenance  The battery  used for standard models are value r
38. such  as necklace  wrist watches and rings     If it is necessary to replace any connection cables  please  purchase the original materials from the authorized distributors  or service centers  so as to avoid overheat or spark resulting in  fire due to insufficient capacity     Do not dispose of batteries or battery packs in a fire  they may  explode     Do not open or mutilate batteries  released electrolyte is highly  poisonous and harmful to the skin and eyes     Do not short the positive and negative of the battery electrode   otherwise  it may result in electric shock or fire     Make sure that there is no voltage before touching the batteries   The battery circuit is not isolated from the input potential circuit   There may be hazardous voltage between the battery terminals  and the ground     Even though the input breaker is disconnected  the  components inside the UPS are still connected with the  batteries  and there are potential hazardous voltages   Therefore  before any maintenance and repairs work is carried  out  switch off the breaker of the battery pack or disconnect the  jumper wire of connecting between the batteries     Batteries contain hazardous voltage and current  Battery  maintenance such as the battery replacement must be carried  out by qualified personnel who are knowledgeable about  batteries  No other persons should handle the batteries     EAR    9  Trouble Shooting       Problem    Possible cause    Solution       The Fault code is     08     an
39. wn soon    Mode Fault Warning code Information          FAULT Indicates the operating mode of the UPS    Mode Fault Warning code or the quantity of the parallel   MODE D D system could be displayed  and the codes are illuminated  WARNING in detail in the following chapter       Inverter operating Information       INVERTER Indicates the circuit of the inverter is working       Bypass operating Information    BYPASS Indicates the circuit of Bypass is working    Output voltage and frequency and Bypass disable enable selection  Information             208 VAC 230 Vac The four value of the output voltage could be selected  when the UPS is in No Output mode or Bypass mode           280 Vac an VAC and only one of them could be actived in the same time   50 HZ The two frequency value of the output voltage could be  selected when the UPS is in No Output mode or Bypass   60 HZ mode  and only one of them could be actived in the same  time   BYPASS DISABLE Bypass disable or enable could be selected when the    UPS is in No Output mode or Bypass mode  and only one    B S ENABLE of them could be actived in the same time                  Notes  For 3T1 10KS 10K UPS  only the information of phase C will be shown   while for 3T1 15KS 20KS UPS  only the information of phase A will be  shown      11     5  Installation    The system may be installed and wired only by qualified    electricians in accordance with applicable safety regulations        5 1 Unpacking and Inspection   1  Unpack the p
    