Home

1 Distboard Manager – User guide Table of Contents

image

Contents

1. 14 Circuit Length Enter the entire length of one of the conductors normally the phase conductor Up to this point are details normally found within distribution board charts the details here or from any test schedule are transferred to Charts when you press CTRL M Earthing amp Continuity 15 R1 Phase Enter the resistance of the phase conductor in its entire length 16 Rn Neutral Enter the resistance of the neutral conductor in its entire length 17 R2 Earth Enter the resistance of the earth conductor in its entire length 18 Total R1 R2 You can not write into this column the total of R1 R2 will be automatically calculated for you as Radial or Ring Insulation Resistance Meg Ohms Test instrument is set to twice the normal operating voltage beware of connected equipment 19 P P For all single phase circuits the entry will be N a For all other circuits a measured value must be entered i e 200 20 P P For all single phase circuits the entry will be N a For all other circuits a measured value must be entered i e 200 21 P N For all circuits a measured value must be entered i e 200 22 N E For all circuits a measured value must be entered i e 200 23 E P For all circuits a measured value must be entered i e 200 RCD Test instrument is set to the mA rating of the protective device 24 X1 The protective device must isolate the supply within a specified time depending upon the earthing ar
2. 513 5 3 3 84 3 07 6B6 6 B 6 60898 6 13 6D6 6 D 6 60898 1 58 6B10 6 B 10 60898 413 6 13 6C10 6 e 10 60898 413 3 07 6D10 6 D 10 60898 413 1 53 6B1030 6 B 10 30 61009 413 6 13 6C1030 6 c 10 30 61009 41 3 3 07 6D1030 6 D 10 30 61009 41 3 1 53 6gG80 6 gG 80 BS 88 2 2 414 13 50 10 80 6T1 6 1 8 00 6 40 6T2 6 2 4 57 3 66 6T3 6 3 3 20 2 56 Note Pressing a header box will sort the table in an ascending descending order by the column header pressed 1 Code You can not enter details into this column but you will need the code produced here to enter into the test schedules 2 la Enter a current rating of device 3 Type Enter the type of the device 4 kA Enter the kA rating of the device 5 mA Enter the mA rating of the device normally applies to RCBO s 6 BSEN Enter the BSEN of the device 7 Table Enter the table from BS7671 where specific protective device Zs values are to be used from 8 BS7671 Enter the actual Zs value per protective device as detailed in BS7671 9 New Zs You can not enter details into this column this column displays the New Zs after the of Zs to remain has been entered in the Prefs General Info section Note If an entry in the column BS7671 is not used a figure will be automatically calculated for you this will take into account the percentage of Zs to remain entered in the Prefs General Info section Boards This is a database fo
3. Bus Enter the Distribution Board s busbar rating in amps 7 Ways For non split load boards enter No of ways in total 8 kA Enter the Distribution or Panel Board s kA rating 9 Split For split load boards enter No of ways dedicated to Power 10 Height Enter the Distribution Board s external height dimensions 11 Width Enter the Distribution Board s external width dimensions 12 Depth Enter the Distribution Board s external depth dimensions 13 Weight Enter the Distribution Board s total weight in Kg 14 Ver Enter the Distribution Board s Excel depth of each of the MCB s normally 17 25 15 Hor Enter the Distribution Board s Excel width between the two rows of MCB s normally 13 92 Note If you print a label and find its different from the value entered you can adjust to find the Excel value On the Labels tab within the adjusting table click the buttons till you find the correct label enter those new values as Ver Hor Labels This is where you can generate Distribution Board MCB labels information here is used from details stored within the test schedules and when inserted give the distribution board the professional finish both external and internal busbar cover legends are generated EXTERNAL PANEL BUSBAR PANEL Bench Bench Distribution Board DB1 Sockets 1 Sockets 1 6 6 Bench Bench Sockets 2 Sockets 2 MCB Start No 6 6 1 Bench Bench Sockets 3 Socke
4. if you select No the test schedules will commence printing 12b Do you want normal page numbers No 12c Please enter the first page Enter number 84 12d Please enter the last page Enter number 123 as this is to produce test schedules 84 to 123 of 123 13 Select the printer as CutePDF 14 Name the PDF file as 84 to 123 15 Close DM copy 2 16 You can join both PDF files together to create 1 single PDF file or print both PDF files to an A4 printer NOORWN Ee Shortcut Keys 1 CTRL Shift Z This will run the macro InsertMACAddress This is a shortcut to display the PC s MAC address 2 CTRL Z This will run the macro GetPHYSAddress This is a shortcut to display the PC s MAC address 3 CTRL F Use only when in a test schedule Means FORMAT SCHEDULE Use this option to reset or clean up schedules 4 CTRL M Use only when in a test schedule Means MOVE DATA TO CHART Use this option to create new Charts 5 CTRL R Use only when in a test schedule Means RESET RCBO SETTINGS Use this option on a blank schedule only 6 CTRL Shift C This will run the macro TransferInfo This can transfer all the details from an active DM Backup test schedule to an active DM test schedule you must ensure both files are open prior to using this shortcut key Macro s 1 Chart Use only when in a test schedule Means MOVE DATA TO CHART Use this option to create new Charts 2 Format Use only when in a tes
5. 00 100 00 100 00 MCB RCBO Codes 55 DBITI 1 12 11 100 00 100 00 100 00 100 00 56 DBHSG 1 12 8 79 17 100 00 100 00 100 00 Poles Amps Type kA mA 57 DBFPX1 1 12 4 75 00 100 00 88 89 100 00 58 DBFPX2 1 12 4 75 00 100 00 100 00 100 00 ora uo 95 5s dos sg 11 1 Distribution Status In this box you can enter a unique distribution board by number i e 1 to 80 as presented down the left most column or to enter an area you made up within the System Board Name amp Location Area column i e LON L1E L2S L3W 2 If you leave the Match board or area box blank you will be presented with the global totals of your LV system 3 You can toggle between test schedule error checking or display the number of distribution board ways by clicking either message Board Reference to show Board amp No of Ways or Populated Cabled Dead amp Live Tests to show Board Reference 4 If an error message appears as the header title reads Board Reference simply left click the distribution board reference to be taken to that schedule to see your error 5 Displayed within the left hand side are details showing 1 of board populated 2 of board populated which is cabled 3 of what is cabled dead tested 4 of what is cabled live tested all results are shown per board 6 The middle section relates to cabling top displays sub mains as well as phase orientated conductors in various sizes 7 The middle section mi
6. 13 Eid Am 200 200 zaa ya enS 19m PAREN KI S 6 6 B 10 60898 Lightirig Row 1 Radial 6491 Da 10 4 150 N50 0 48 0 0 2004 gt 200 gt 200 0 S200 6 133 Y Yol 22 8 6 B 10 60898 lNghting Row 2 Radia 6491B p B 10 4 1 50N 1 80 80 00 se 0 45 445 N76 90 2300 gt 200 5208 gt 2200 exi v ok 23 E 6 B aol 60898 D ghtips Row 3 adia eX91b p s 10 4 1 50 NL50 0 47 ox oN 200 2200 gt 200 200 3200 7 LOX 6x3 Ok 22 16 Df 10 40898 IN ANNNN Rajal AC SwA G2 31 400 4x9 35 00 Ee 0 23 0 N a gt 2002200 gt 2Q0 w200 0 55 N9 58N Y OK 1 9 16 D 10 60898 P mp Set Radi M 4 SWA G2 3YX 4 00 4 00N 25 00 03 0 23 3 48 gt 200 gt 200 2200 4200 E 0987 Y OK 1 3 16 D x 898 SN 4C SWA G2 AUT ES 35 00 ae um 0 237 0 46 200 A 00 E 2200 0 55 958 v OK 1 10 E X L3 m H nu LA C A J j ERE E EL 12 gy i Notes Exclusions Ee mm 630A 207A 33 M l Megger Monday 05 Jan 2015 E2 mm gt 630A 211A 33 M2 MFT1710 TBC This document including its test results is an example E3 mm r3 630A 225A 3696 M 3 SN0122103556 Inspector E4 mm EN 630A 1637A 3 Cal Thursday 01 Jan 2015 Witness There are only a few rules which you must follow when creating or modifying test schedules Each test schedule can only hold 12 x 3 phase or 36 x 1 phase circuits the chart shown is a TP amp N chart showing 12 ways Always use refe
7. 60947 3 0 06 0 06 0 06 3 40 3 40 340 Supply Origin Details 1 Livened Enter the date at which this particular cable board went live enter as dd mm yyyy 2 Feed Enter a circuit reference i e TXS 1L123 this will become the circuit origin 3 SW Enter the switch isolator ACB air circuit breaker rating in amps 4 BSEN Enter the BSEN number of switch isolator ACB air circuit breaker 5 Ph Enter the phase s of the supply enter as L1 L2 L3 or 3 6 Uo Enter the Uo Range from Prefs the above supply falls under normally 2 7 Vt Enter the Voltage Type the supply falls under enter X for DC or leave blank for AC Submains Cabling 1 ID Enter an ID specific to the cable this should be the reference to be used on site SWA cables 2 Cable Enter the cable type examples are 3x4C185SWA 3 x 4C 185mm or 4C16SWA 4C 16mm or 3C4FP400 3C 4mm 3 CPC Enter the CPC material type examples are C185 Copper 185mm or B Bar Bus Bar 4 L Enter the length of the circuit this applies to both feed amp earth cables not combined length 5 Earth Enter the earthing arrangement Enter as TT TN S or PME Board Name amp Location 1 Board Enter the distribution board reference as detailed on site drawings 2 Area Enter the area examples are LON Level Zero
8. amp Circuit Information Earthing amp Continuity Insulation Resistance Meg RCD ELR Misc Circuit lt Trip Tri Circuit Circuit Cabling Cable CPC Circuit R1 Rn R2 Total aa E E ER al eae o E RI Rr R2 Too oos pu ne EP xi xs ER Max S 3 815 Ref BSEN Time Description Type Type mm mm Length Phase Neutral Earth R1 R2 S Es ns 20 B 6 60898 INN Radial 4gSWA G2 31 2 50 2 50 6609 0 03 0 03 0 03 0 96 Na gt 200 gt 200 gt 200 208 015 184 0k 1 1 20 B 6 60898 DB No 1 Radia 4C SWA G2 31 2 50 2 50 66 00 0 03 0 03 0 03 ae gt 200 gt 200 gt 200 gt 200 gt 200 0 14 1 84 OK 1 ej 20 B 6 60898 VVVVV Ragidl 4 SWA 31 2 50 256 66 00 A0 03 0 03 0 03 Wa _ gt 200 206 200 015 A847 Y Jok 1 32 c 10 60898 DIVVVV dial c sy i 31 400 A00 spi ior 0 04 wr Ai gt 200 gt 200 200 718 0 17 0 58 1 2 32 C 10 60898 ELT Radial JacSwayG2 34 4 00 00 3500 7 0 04 A 0 04 2200 200 gt 200 5200 gt 200 0 16N 058 7v J k JN 32 c 10 60898 WV Radi fac in G2 31 4 00 QN 3500 0 04 70 04 oo ET 200 Na gt 200 280 gt 20 0 17 9 58 OK p 6 D 10 60898 oats 0 1 RadiaN3c S 1 50 1 50N 181 08 0 08 0 08 Dais 5200 2200 200 gt 200 gt 2 024 1 1 3 10 D 10 60898 Mot f No 2 Radial 38 SWAG2 31 J 1 50 1 50 26 00 0 06 0 06 0 06 0 N gt 200 gt 200 200 gt 2
9. amp Small Motors 4 5 10 4 Uo Volts Generally 230v 230 3 7 10 5 Divide answer of 4 by answer of 3 Ohms 0 72 High Inrush Current gt 10 20 Access Prefs System Boards Labels Yes Yes Yes Yes Yes Yes Charts Status Active Search Test Sheets Future Use Yes Yes Yes Yes 90 For further information about this software please email alanwelsman alanwelsman co uk 1 Top of screen Enter the site address which DM is to be used on e g Abbey Lodge Mill this area highlights green if empty 2 General Info as follows 2 1 Enter the of BS7671 Zs value to remain this is normally 80 Multiply by a correction factor normally 1 2 2 Enter the max board population this is normally 75 Breaker breakdown prefix normally P 2 3 Enter Old or New phase colours this is normally New Force cable as phase colour this is normally blank otherwise Y 2 4 Enter test instrument Continuity amp Resistance Serial No refer to instrument for its serial number 2 5 Enter test instrument Earth Loop amp PSC Serial No refer to instrument for its serial number 2 6 Enter test instrument RCD Serial No refer to instrument for its serial number 2 7 Enter test instruments Calibration Date Enter the date the test instruments were calibrated on not when they expire 2 8 En
10. schedule details as follow 1 Supplementary Earth Bonding Conductor size in mm inc resistance values for services such as Gas Water Oil or User defined 2 Equipotential Earth Bonding Conductor size in mm inc resistance values for services such as Gas Water Oil or User defined 3 Test Kit S No s amp Cal Date You can not write into this row details are copied here from Prefs General Info 4 Notes and or Exclusions Enter notes or exclusions for any circuit detailed on this test schedule 5 Test Date You can not write into this box details are entered here from System Livened 6 NICEIC Ref Enter the reference of the NICEIC serial number which makes up the test certificate 7 Inspector Enter the person s name who has tested the electrical installation does this person hold a C amp G 2391 certificate 8 Witness Enter the person s name who has witnessed the Inspectors testing procedure and can verify tested satisfactory 15 Printing If your LV system combination of Panel Boards and Distribution Boards are greater than the maximum number of distribution boards DM can hold currently set at 80 test schedules you may need to clone DM to produce more distribution boards If this is the case you still have the ability to produce test schedules as though all have been printed from one version of DM When you fill out the NICEIC testing certificate on the bottom will be a box to complete saying Sheets of Th
11. 00 200 0 20 0 92N Y OK 1 3 16 D 10 0898 A ient Radial 3C ar 3 50 2 50 zem ue Ew 0 06 0 12 5209 2 200 200 gt 2 021 0 58 oi 1 32 C 10 30 61009 0 4s aners Sockets Ring 6491BJ e 10 400 4 00 86 00 0 07 Q 07 0 07 0 04 200 208 gt 290 gt 200 2200 28m 19mS O 13 i YY K 10 4 32 c 10 30 N61008 0 4s Cleaners Sockets Ring 64938 p e 10 4 N4 00N 4 00 74890 0 08 0 88 Q 08 044 5 200 2200 Ne20 200 75200 28mS 19ms A 58 Y ok 7 40 6 6 60898 fotor No Radial 3 SwA 2 31 i00 Ka 76 00 06 06N 0 0 1 gt gt 200 gt 200 Se 2200 Sis Y OK 1 9 C 608 ANA Radial J4c SwA G2 1 10 00 1000 7112 90 9 05 O5 X005 940 Aya 7 200 208 gt 200 7520 Y OK _N 1 5 63 10 60898 DB No3 adjd 4c SWALG2 31 10 00 i0 06 1100 0 05 0 05 0 05 70 09 7 gt 260 gt 200 200 e208 260 i Xs Y ok N 1 BN 36 60898 VV R amp dial AC SWA Ai 10 00 16 00 112 00 Soy p5 0 057 0 10 7208 Ja gt 200 gt 200 a 0 19 Y 029 Y ok N1 6 Na 32 C 30 61009 0 Bench Sacket3 1 Rin EE Nys gj 4 00 4 0 No 0 05 905 0 05 0 0A gt 290 2007 200 gt 20 Nago Sm 3 S UN SSWY ek 6 7 32 c 10 v0 61009 0 4s Bent Sockets 2 King 64918 D s 10 4 4 00 4 00 V 5X0Q i2 v0 12 7 0 12 amp O6N Ne20 gt 200 2200 2200Y 2308 28ms Y ms 6 15 0 58 ol 6 1 332 c 10 30 e109 02s Bate ae GENK B o s 10 4 4 00 GENE AGES 0 1
12. 1L3 2L1 212 203 3L1 3L2 3L3 4L1 4L2 413 5L1 61 6L2 613 2 LVSB 1 12 1L1 1L2 1L3 2L1 2L2 203 3L1 3L2 3L3 4L1 4L2 4L3 5L1 5L2 5L3 6L1 62 6L3 7L1 7L2 7L3 8L1 8L2 8L3 9L1 9L2 9L3 10L1 10L2 10L3 11L1 11L2 11L3 12L1 1212 1213 2 LVSB 13 24 311 132 133 t4L1 14L2 14L3 15L1 15 2 15 3 16L1 16L2 1613 17L1 17L2 17L3 18L1 18 2 18 3 19L1 19L2 19L3 20L1 202 20L3 21L1 21L2 21L3 22L1 2212 2213 23L1 23L2 233 24L1 2412 2413 3 PBSMS 1 12 2L1 212 213 3L1 3L2 3L3 4L1 4L2 4L3 5L1 5L2 5L3 6L1 6L2 6L3 7L1 7L2 7L3 8L1 8L2 8L3 9L1 9L2 9L3 10L1 1012 1013 3 PBSMS 13 24 1341 1312 1313 17L1 17L2 1713 18L1 18L2 18L3 19L1 19L2 19L3 20L1 2012 20L3 21L1 21L2 21L3 2211 2212 2213 4 PBSMF 1 12 2L1 212 213 3L1 3L2 3L3 4L1 4L2 4L3 5L1 5L2 5L3 6L1 6L2 6L3 7L1 712 7L3 8L1 8L2 8L3 9L1 9L2 9L3 10L1 1012 1013 4 PBSMF 13 24 131 13L2 1313 17L1 17L2 17 3 18L1 18L2 18L3 19L1 19L2 19L3 20L1 20L2 20L3 21L1 21L2 21L3 22L1 2212 2213 5 PBSMG 1 12 2L1 212 213 3L1 3L2 3L3 4L1 4L2 4L3 5L1 5L2 5L3 6L1 6L2 6L3 7L1 7L2 7L3 8L1 8L2 8L3 9L1 9L2 9L3 101 1012 1013 11L1 11L2 1113 5 PBSMG 13 24 x 15L1 15L2 1513 16L1 16L2 16 3 17L1 17L2 17L3 18L1 18 2 18 3 19L1 19L2 19L3 20L1 20L2 20L3 21L1 212 2113 22L1 2212 2213 23L1 2302 2313 6 DBPLANT 1 12 111 12 113 211 2012 203 3L1 312 313 4L1 402 4L3 511 61 6L2 6L3 7L1 7L2 713 8L1 8L2 8L3 11L1 1112 1113 1201 1202 1213 1 Cabling Req If you enter Y into this box you will only see circuits yet to be cabled 2 Testing Req If you enter Y into this box you will only see circ
13. 2 seconds Any circuit using a protective device greater than 32 amps regardless of AC or DC voltage type will have a 5 second disconnection time 8 Table for MCB Types This table shows how to calculate the Max Zs for a protective device The measured or calculated Zs for Ze R1 R2 must not go above the Max Zs 9 Page Zoom If you are fed up with adjusting the page each time you view different worksheets this section removes that issue Here you can set each worksheet page zoom value as follows Example for Access Below the Access page tab are two empty boxes the left box you enter Yes or No If you enter Yes leave the box to the right empty automatic zoom is now in operation If you enter No then enter in the box to the right the 75 of page zoom you want for that particular page Do this for all the DM tabs except the tab labelled Future Use MCB s This is a database of protective devices i e MCB RCBO Cartridge fuses etc use their Max Zs values within all test schedules MCB Database Code Manufacturer Model la Type kA mA BSEN Table BS7671 New Zs a 2D6 2 D 6 60898 4 60 2B10 2 B 10 60898 41 3 18 40 2C10 2 e 10 60898 413 9 20 3B10 3 B 10 60898 413 12 27 3 3 BS 1362 414 232 18 56 4D6 4 D 6 60898 2 30 4B10 4 B 10 60898 413 19 17 15 34 5 5 BS 1361 414 16 40 13 12 5 5 BS 3036 414 17 7 14 16 5T1 5 1 9 60 7 68 5T2 5 2 5 48 4 38
14. 8 Y 48 77 08 100 00 97 30 100 00 6491BBrni5 710 connected 13 CHILLER 1 12 1 6491B Brn 10 0 57 14 DBCU 1 12 6 22 22 100 00 100 00 100 00 6491B Brn2 5 11564 15 DBVP1 1 12 6491B Brn 4 0 34303 DB way s i6 __DBVP2 1 12 6491B Brn 6 0 114 populated 17___DBVP3 1 12 Emu Brecker Brekdown 20 DBMAP3 1 12 1P 2D6 1P 4D6 1P 6D6 21 DBSPI1 12 16 2 7 9 21 DBSP1 13 24 16 52 08 100 00 100 007 100 00 22 DBSP2 1 12 16 1P 10C6 1P 10D6 1P 16D6 22 DBSP2 13 24 16 56 25 100 00 100 00 100 00 1 2 2 23 DBSP3 1 12 16 23 DBSP3 13 24 16 43 75 100 00 100007 100 007 1P 20D6 3P 2D6 3P 4D6 24 DBSP4 1 12 16 1 3 2 24 DBSP4 13 24 16 64 58 100 00 100007 100 007 25 DBSP5 1 12 16 3P 10D6 3P 16D6 3P 20D6 25 DBSP5 13 24 16 66 67 100 00 100 007 100 007 4 12 5 26 DBSL1 1 12 8 37 50 100 00 100 00 100 00 27 DBSL2 1 12 8 58 33 100 00 100 00 100 007 3P 2506 3P 40D6 1P 6B10 28 DBSL3 1 12 8 33 33 100 00 100 00 100 00 1 2 1 29 DBSL4 1 12 8 50 00 100 00 100 00 100 00 64918 15 502 30 DBSL5 1 12 8 75 00 100 00 100 00 100 007 6491B2 5 10762 1P6B1030 iP6CiO 1P 6C1030 31 DBIT3 1 12 11 63 64 100 00 100 00 100 00 6491B 4 34065 14 116 61 32 DBFP1 1 12 16 6491B 6 38 32 DBFPi 13 24 16 52 08 100 00 100007 100 00 6491B 10 21 1P 10B10 1P10CiO 1P16B10 33 DBFP2 1 12 16 3 29 16 33 DBFP2 13 24 16 56 255 100 00 100 00 100 00 34 DBFP3 1 12 16 iP16B1030 1P16C10 iP 20810 34 DBFP3 13 24 16 43 75 100 00 100007 100 007 12 3 122 35 DBF
15. Dining Room Radial 6491B 2 50 2 50 28 00 Y N 6 22 DBSL4 1 12 312 6 B 10 30 61009 Stairwell No 1 Level 2 Radial 6491B 2 50 2 50 40 00 Y N 7 23 DBSL5 1 12 72 6 C 10 60898 RB2000 Controller FCU s Radial 6491B 2 50 2 50 12 00 Y N 2 24 DBSL5 1 12 743 6 C 10 60898 Office amp Meeting Radial 6491B 2 50 2 50 50 00 Y N 3 25 DBSL5 1 12 83 6 C 10 60898 Reception Foyer amp Riser Radial 6491B 2 50 2 50 X 70 00 Y N 11 26 DBIT3 1 12 62 6 C 10 60898 I T Lighting Radial 6491B 2 50 2 50 6 00 Y N 2 27 DBIT3 1 12 12 63 C 10 60898 Surge Protection Radial 6491B 10 00 10 00 1 00 Y N 1 28 DBFP1 1 12 7 3 20 B 10 30 61009 Cleaners Sockets Stair 2 Radial 6491B 4 00 4 00 28 00 Y N 2 29 DBFP1 1 12 913 20 B 10 60898 Automatic Doors Radial 6491B 4 00 4 00 26 00 Y N 2 30 DBFP2 1 12 53 20 B 10 60898 Fire Smoke Dampers Radial 6491B 4 00 4 00 80 00 Y N 8 31 DBFP2 1 12 7 2 20 B 10 60898 Fire Smoke Dampers Radial 6491B 4 00 4 00 80 00 Y N 3 32 DBFP2 1 12 113 32 B 10 30 61009 Cleaners Sockets Ring 6491B 4 00 4 00 112 00 Y N 4 33 DBFP4 1 12 712 20 B 10 60898 Fire Smoke Dampers Radial 6491B 4 00 4 00 68 00 Y N 5 34 DBFP4 1 12 82 20 B 10 60898 Fire Smoke Dampers Radial 6491B 4 00 4 00 70 00 Y N 9 35 DBFP5 1 12 912 20 B 10 60898 Fire Smoke Dampers Radial 6491B 4 00 4 00 62 00 Y N 8 36 DBFP5 1 12 10L2 6 B 10 30 61009 Ass td WC Shaver Radial 6491B 2 50 2 50 20 00 Y N 1 You will see there is a header bar beneath each title is a space to write a single wor
16. Distboard Manager User quide Thank you for taking an interest or purchasing Distboard Manager for Microsoft Excel 2002 amp onwards NOTE All the databases and charts listed in this document including information contained within them are made up results I hope it helps you as much as it has helped me during my ongoing career as an electrician although much effort has already gone into the creation of Distboard Manager I am always happy to receive any comments or concerns you may have purely in relation to Distboard Manager and its functionality to alanwelsmanGalanwelsman co uk Distboard Manager s sole purpose is to help make your daily routine easier by helping you manage your LV system from small scale single board domestic installations to large scale three phase industrial installations you don t even need to be an electrician to use Distboard Manager as long as you can comfortably navigate your way around Microsoft Excel and are familiar with electrical test results you are already qualified Use Distboard Manager to point out failures in LV Distribution Board schedules provided to you by highly paid consultants pre load them into Distboard Manager and by using Distboard Manager s Search engine create multiple reports of inconsistencies you know as an electrician go against your electrical installation background a few examples such as 1 Ring circuits with 1 single item on them 2 Radial circuits protected by devices greater t
17. Memshield 3 EBM182 B 60439 3 125A 18 1021mm 440mm 140mm MEM Eaton Memshield 3 EBM182H B 60439 3 250A 18 1342mm 440mm 140mm Schneider Powerpact 4 MG6C18 3B T2 60439 1 amp 3 630A 18 36 1808mm 850mm 270mm 98kg Schneider Powerpact 4 MG8C18T 3B T2 60439 1 amp 3 800A 18 50 2210mm 850mm 270mm 122kg Schneider Acti 9 Isobar SEA9AN18 A 61439 3 125A 18 16 300mm 489mm 117mm 18 12 57 Schneider Acti 9 Isobar SEA9BN18 B 61439 3 250A 18 16 862mm 470mm 140mm 18 12 57 MEM Eaton Memshield 2 AM16 A 60439 3 125A 16 MEM Eaton Memshield 2 BM161 B 60439 3 125A 16 MEM Eaton Memshield 2 BM162 B 60439 3 200A 16 MEM Eaton Memshield 3 EAM16 A 60439 183 125A 16 254mm 454mm 140mm ABB Protecta ECS116C A 60439 1 amp 3 100A 16 265mm 368mm 110mm 17 25 13 92 ABB Protecta EPB25 316C B 60439 1 amp 3 250A 16 830mm 400mm 125mm 20 2Kg 17 25 13 92 Schneider Acti 9 Isobar SEA9BN16 B 61439 3 250A 16 16 862mm 470mm 140mm 18 12 57 GPS GPS01 F4 T2 60439 1 amp 3 2160A 15 2325mm 3010mm 750mm 1500Kg 17 25 13 92 Note Pressing a header box will sort the table in an ascending descending order by the column header pressed 1 Manufacturer Enter the Distribution Board s manufacturer 2 Range Enter the Distribution Board s range 3 Model Enter the Distribution Board s model number 4 Type Enter the Distribution Board s type Type A normally single phase Type B normally three phase 5 BSEN Enter the Distribution Board s BSEN number 6
18. North L1E Level 1 East L2S Level 2 South L3W Level 3 West etc 3 Location Enter the room or location the distribution board has been installed to Board Specifics 1 Model Enter the model of the distribution board ensure to use the same model ref no as entered within the Boards section 2 SW Enter the switch isolator rating in amps this is the main switch fitted within the distribution board itself 3 BSEN Enter the BSEN number of switch isolator 4 K If your distribution board is either single phase or a kit has been used to convert from 3 phase to single phase enter Y Note You must enter a value in the Area column against your distribution board reference Status may not display records ELR Ohms PSC kA 1 L1 Enter the measured Earth Loop Resistance Ohms reading of the L1 phase to Earth not phase to phase 2 L2 Enter the measured Earth Loop Resistance Ohms reading of the L2 phase to Earth not phase to phase 3 L3 Enter the measured Earth Loop Resistance Ohms reading of the L3 phase to Earth not phase to phase 4 L1 Enter the measured Prospective Short Circuit kA reading of the L1 phase to Earth not phase to phase 5 L2 Enter the measured Prospective Short Circuit kA reading of the L2 phase to Earth not phase to phase 6 L3 Enter the measured Prospective Short Circuit kA reading of the L3 phase to Earth not phase to phase Repeat the above for
19. P4 1 12 16 35 DBFP4 13 24 16 64 58 100 00 100007 100 00 1P 2081030 1P 20C10 1P 32B1030 36 DBFP5 1 12 16 31 1 275 36 DBFP5 13 24 16 70 83 100 00 100 007 100 00 37 DBFLI 1 12 8 37 50 100 00 100 00 100 00 1P 63C10 1P63E35 1P 100E35 38 DBFL2 1 12 8 58 33 100 00 100 00 100 007 3 1 7 39 DBFL3 1 12 8 37 50 100 00 100 00 100 007 40 DBFLA4 1 12 8 45 83 100 00 100 00 100 007 3Pi6CiO 3P32C10 3P63C10 41 DBFL5 1 12 8 66 67 100 00 100 00 100 007 1 1 3 42 DBIT2 1 12 11 63 64 100 00 100 00 100 00 43 DBHSF 1 12 8 12 50 100 00 100 00 100 007 3P63E35 3P 80E35 3P 100E35 44 DBGPI1 12 16 64918 15 502 12 5 49 44 DBGPi 13 24 16 54 17 100 00 100007 100 00 6491B 25 11404 45 DBGP2 1 12 16 6491B 4 34447 3P 200E35 3P 250E35 3P 400E35 45 DBGP2 13 24 16 52 08 100 00 100 007 100 00 6491B 6 38 1 2 5 46 DBGP3 1 12 16 6491B 10 302 46 DBGP3 13 24 16 54 17 100 00 100007 100 007 6491B 16 267 3P 630E35 3P 1000E35 3P 1250E35 47 DBGP4 1 12 16 6491B 25 1793 2 1 1 47 DBGP4 13 24 16 56 25 100 00 100 00 100 007 6491B 35 513 48 DBGP5 1 12 16 6491B 50 265 48 DBGP5 13 24 16 60 42 100 00 100 00 100 00 6491B 70 122 49 DBGLI1 12 8 45 83 100 00 100 00 100 00 6491B 120 34 50 DBGL2 1 12 8 58 33 100 00 100 00 100 00 6491B 150 12 51 DB6L3 1 12 8 45 83 100 00 100 00 100 007 6491B 185 261 52 DBGL4 1 12 8 45 83 100 00 100 00 100 007 53 DBGL5 1 12 8 66 67 100 00 100 00 100 007 54 DBK 1 12 8 62 50 100
20. all circuits of each of the PB s panel boards not DB s distribution boards Status RED TAB This is where you can find up to date information about your LV system 10 laslboavd manager Distribution Status WAANCO Ult OIE Match board or area Board amp No of Ways Populated Cabled Dead amp Live Tests Cabling amp Qty s Overall Cabled amp Tested 1 TXS 1 12 6 88 89 100 00 43 75 10000 19CSWA25 200 re 2 LVSB 1 12 24 2x4C SWA 185 0 153 2 LVSB 13 24 24 100 00 100 00 83 33 100 00 2CSWA250 92 o 3 PBSMS 1 12 24 2CSWA350 32 3 PBSMS 13 24 24 66 67 100 00 64 58 100 00 3CSWA10 0 281 O 4 PBSMF 1 12 24 3x4C SWA 185 0 46 4 PBSMF 13 24 24 66 67 100 00 70 83 100 00 3CSWA25 642 o 5 PBSMG 1 12 24 3C SWA 35 0 146 e 5 PBSMG 13 24 24 80 56 100 00 74 14 100 00 3CSWA4 0 382 o 6 DBPLANT 1 12 12 77 785 100 00 96 43 100 00 4C SWA 120 0 34 7 DBLIFTI 1 12 1 4C SWA1500 12 o 8 DBLIFT2 1 12 1 4C SWA 16 0 267 e 9 DBLIFT3 1 12 1 4C SWA 185 0 62 0 10 _DBLIFT4 1 12 1 4C SWA 25 0 1701 Circuits 11 DBLIFT5 1 12 1 4C SWA350 335 Yocabi 12 MCP 3 01 1 12 48 4C SWA 50 0 265 12 MCP 3 0113 24 y 48 4C SWAT700 122 12 MCP 3 0125 36 48 5C SWA 40 5 Breakers 12 MCP 3 01 37 4
21. d or a wildcard i e instead of writing the full word distribution you simply write dis and all entries with those letters inside them are listed don t forget to add the stars In this demonstration I entered the letter N into the attribute column the attribute column is included onto every test schedule I have used the letter N instead of New typing this simply means show all the New circuits This can be performed at the very end of the job to list the extra circuits for cost analysis Any letter or code can be used A could mean circuit Amended other codes could refer to site instructions for alterations etc The searching layout is that of a typical test schedule search for details using up to all of the search boxes If more than 36 searches are found simply change the number 1 top left to a higher number to continue the list To select any of the displayed results right mouse click that cell value to be transported to that particular s schedule and text box If you wish to change multiple entries across all the test schedules so they are the same carry out the following 1 Use Search Circuit Description s 3 search boxes to find a circuit description of choice this will search across all test schedules 2 Inspect carefully from the list of descriptions words you would like to change then press the title Circuit Description 3 A box labelled Look for will become visible enter an exact text you want to chang
22. ddle displays neutral conductors and the bottom displays earthing conductors in various sizes 8 The right hand section is to display global details starting at the top in red shows the of Live testing completed below in green Shows the of Dead testing completed below in blue shows the of cabling completed the number of circuits yet to cable the number of breakers which have been cabled and the total number of populated ways 9 The right hand section bottom is to display all the protective devices in use they are sorted into single and three pole devices then into current ratings showing how many per type are installed Note 1 You can adjust the of board populated in the Prefs General Info Item 2 section Note 2 When you create modify or delete test schedules ensure you press the Refresh button this is a small square button located on the right hand side of the box labelled Overall Cabled amp Tested this button can be pressed any time Note 3 When you match a board or area the details of that distribution board will be detailed for you Active GREEN TAB This is where you can see at a glance all the circuits installed throughout your entire LV system T A d 1055 MCE s installed ttooara manager f danndemancoue danvdanam edanndanancouk gt 204 Cabling Req gt Testing Req gt Board MCB s currently installed throughout all the distribution boards 1 TXS 1 12 1L1 1L2
23. e press OK when done 4 A box labelled Change to will become visible enter the exact replacement text press OK when done 5 You will now be asked a simple Yes or No option as follows 5a Yes means to replace every entry looking for regardless if its a text on its own or part of a word and change it 5b No means to replace every entry looking for but only change where the word to be replaced is on its own with no other text This feature can not be undone you use this feature at your own risk as you will make changes to text in all schedules Please use caution 13 Test Schedules DB1 1 12 This is 1 of up to 80 test schedules which can be managed using DM Address Abbey Lodge Mill Fictional Lane Surrey SK3 11HN D B 7 Supply Origin MLV1 1L123 Sw Mod NSX400F Sw Rtg 400A Phase s 3 Cab I D 1 Cab Type 4C185SWA CPC SWA Earthing TN S Ref ipeation amp Dine ELR PSC FLR1 0 09 ELR2 0 09 ELR3 0 09 PSC1 3 4kA PSC2 3 4kA PSC3 3 4KA LUN Switch Room No 1 Board Inf Sw Mod NSX630F Sw Rtg 630A Mfr Schneider Rng Powerpact 4 Model MG6C12 Form 3B T2 BSEN 60439 1 amp 3 BUS 630A Ways 12 kA 36 H 1493mm W 850mm D 270mm Wt 89kg Fuse Board Legend Build Cable
24. e NICEIC header forms normally have 3 sheets then you need to add all the relevant test schedules Lets say you have 120 individual 12 way TP amp N distribution boards that s 120 test schedules to print The first 80 test schedules will come from DM copy 1 and the next 40 test schedules from DM copy 2 So knowing the NICEIC sheets make the first 3 sheets your total sheet count is 123 Open DM copy 1 select the first test schedule tab holding the shift key down select the last test schedule tab This will select 80 test schedules now press CTRL P you will be asked the following 7a Do you need page numbers Select Yes if you select No the test schedules will commence printing 7b Do you want normal page numbers Select No if you select Yes the test schedules will start at page 1 to 80 7c Please enter the first page Enter number 4 as the NICEIC sheets take up numbers 1 to 3 7d Please enter the last page Enter number 123 as this is to produce test schedules 4 to 83 of 123 8 Select the printer as CutePDF if you don t have CutePDF you can link to it from http www alanwelsman co uk referrals html 9 Name the PDF file as 4 to 83 10 Close DM copy 1 11 Open DM copy 2 select the first test schedule tab holding the shift key down select the last test schedule tab 12 This will select 40 test schedules now press CTRL P you will be asked the following 12a Do you need page numbers Select Yes
25. e blank to exclude BUS 10 Enter Boards info for Ways Leave blank to exclude Ways 11 Enter Boards info for kA Leave blank to exclude kA mM Enter Boards info for power if load Split Leave blank to exclude Cable 1 Cable 6 Cable 1 2C SWA Cable 6 gt 2x4C SWA Cable 2 gt Cable 7 gt Cable 2 gt 3C SWA Cable 7 gt Cable 3 gt Cable 8 gt Cable 3 gt 4C SWA Cable 8 gt Cable 4 gt Cable 9 gt Cable 4 gt 3C FP400 Cable 9 gt Cable 5 gt Cable 10 gt Cable 5 gt 3x4C SWA Cable 10 gt Uo Range 1 Uo Range 2 Uo Range 3 Uo Range 4 Any 50 V Uo 120 V 120 V lt Uo 230 V 230 V lt Uo 400 V Uo gt 400 V Voltage AC DC AC DC AC DC AC DC AC or DC 0 8 Notel 0 4 5 0 2 0 4 01 01 5 0 3 Note 1 0 2 0 4 0 07 0 2 4 01 5 Maximum disconnection times for circuits using protective devices rated up to 32A I Calculating max Zs values 5 steps Domestic amp Commercial 1 Choose device type Type C Max value 10 B 3 5 2 Choose device rating 32A 32 2 4 T 3 Multiply Type x Rating 320 General Use
26. emember this reference also needs to be written into the System Board Name amp Location Board column 2 The schedule should now set itself up to show the number of ways the number of ways for this particular distribution board should be written within Boards Ways column cross check against the model number pressing CTRL F should format the schedule The following columns are user input fields 14 Fuse Board Legend Build Cable amp Circuit Information 1 MCB Enter the current rating in Amps for the protective device 2 Type Enter the type of the protective device 3 kA Enter the kA rating of the protective device 4 mA Enter the mA rating of the protective device 5 MCB BSEN You can not write into this column 6 Trip Time You can not write into this column 7 Circuit Description Enter a brief description try to keep text to 3 x 6 letter words with spaces in between them 8 Circuit Type Enter Radial or Ring 9 Cabling Type Unless singles i e 6491B is written all other entries must contain a space i e 3x4C SWA or 4C SWA or 3C FP400 10 Code Ct Enter a code from the bottom table found in Charts example 6491B in metal conduit enter B 11 Mthd The installation method can be found by looking at table 4A2 from the current version of the BS7671 regulations 12 Cable mm Enter the circuit phase amp neutral conductor size in mm 13 CPC mm Enter the circuit copper protective conductor size in mm
27. f you disagree with a comment or function I have written into DM again feel free to comment alanwelsman alanwelsman co uk Access This is how DM is unlocked it must first be locked to a PC then each time you need to use it press CTRL Shift Z or CTRL Z keys Prefs This is where you can adjust some of the parameters of DM split into 9 sections as follows v1 09 Welcome to Distboard Manager Abbey Lodge Mill Fictional Lane Surrey SK3 11HN 1 Enter the maximum of BS7671 Zs value Correction factor multiplier gt 80 00 1 2 Enter the warning of board population Breaker Breakdown prefix gt 75 00 P 3 Enter Old or New phase colours Force cable as phase colour New 4 Test instrument Type or Continuity amp Resistance Serial No Megger 5 Test instrument Model or Earth Loop amp PSC Serial No MFT1710 6 Test instrument Serial Number or RCD Serial No gt 5N0122103556 7 Test instrument Calibration Date 01 Jan 2015 8 Enter an RCBO trip time code suffix s 9 Uo nominal phase voltage to earth TN gt 230 10 Table 41 1 applies to circuits up to Amps gt 32 11 Preferred CPC if running external to SWA 6491B 12 Codes for Protective Device Type kA mA Cabling Type amp Installation Method I2 Type kA mA Ct Md 13 Preferred codes for Protective Device BSEN amp Trip Time Trip BSEN Time When copying a Schedule to Chart display Char
28. han the current carrying capacity of the cable 3 Circuits feeding sockets for non fixed appliances without RCD protection 4 Circuits which are longer than the recommended length for its conductor size 5 Circuits which have RCD protection for devices which form a life circuit and must be MCB only Note 1 Where written DM simply means Distboard Manager Note 2 When you open DM you will see an information page if you chose to disable macro s the information page is all you will see Note 3 When you close DM you will not be asked to save DM will automatically save upon exiting to ensure all data is saved Note 4 When you select Save As DM will create a backup of itself called Distboard Manager Backup Please be aware before you can use Distboard Manager it has to be locked to your PC within 2 open and close events failure to lock will render Distboard Manager non functional 1 When you purchase DM your registered Paypal email address will be the only email address used for all DM correspondence regards the request for a keycode for the unlocking locking process 2 Please ensure you have installed the component Visual Basic prior to running DM DM will not function correctly without it 3 When you open DM you will be asked to enable disable macro s please enable them 4 Macro s within DM are safe they are small automated programs which run in the background only run when called upon 5 Each time DM is opened you wil
29. ial 3CSWA G2 31 1 50 1 50 26 00 1 re 16 D 10 60898 Motor No 3 Radial 3CSWA G2 31 2 50 2 50 32 00 1 IR 32 C 10 30 61009 0 4s Cleaners Sockets Ring 6491B D B 10 4 4 00 4 00 86 00 10 Be 32 c 10 30 61009 0 4s Cleaners Sockets Ring 6491B D B 10 4 4 00 4 00 48 00 7 IN 40 D 6 60898 Motor No 4 Radial 3CSWA G2 31 6 00 6 00 40 00 1 RM 63 C 10 60898 IVVVVV Radial 4CSWA G2 31 10 00 10 00 112 00 1 5 Nc c 10 60898 DB No 3 Radial 4CSWA G2 31 10 00 10 00 112 00 1 L3 63 C 10 60898 VVVVVV Radial 4CSWA G2 31 10 00 10 00 112 00 1 L1 6 gv L3 RE 32 C 10 30 61009 0 4s Bench Sockets 1 Ring 6491B D B 10 4 4 00 4 00 35 00 7 GBS 32 c 10 30 61009 0 4s Bench Sockets 2 Ring 6491B D B 10 4 4 00 4 00 54 00 KM 32 C 10 30 61009 0 4s Bench Sockets 3 Ring 6491B D B 10 4 4 00 4 00 28 00 In 6 B 10 60898 Lighting Row 1 Radial 6491B D B 10 4 1 50 1 50 80 00 22 8 EN 6 B 10 60898 Lighting Row 2 Radial 6491B D B 10 4 1 50 1 50 80 00 23 Ky 6 B 10 60898 Lighting Row 3 Radial 6491B D B 10 4 1 50 1 50 80 00 22 IR 16 D 10 60898 IVVVVV Radial 4CSWA G2 31 4 00 4 00 35 00 1 9 I 16 D 10 60898 Pump Set Radial 4CSWA G2 31 4 00 4 00 35 00 1 Fe 16 D 10 60898 VVVVVV Radial 4CSWA G2 31 4 00 4 00 35 00 1 L1 10 F L3 L1 11 gv L3 L1 12 7 Cabling Type Codes Ct No 4 CCC B PVC cables in metalic conduit PVC cables in non metalic conduit Installation Method Meanings Md Refer to BS7671 table 4A2 for more information PVC cables in metalic trunking PVC cables i
30. ifier Radial 6491B 4 00 4 00 8 00 Y N 1 5 DBPLANT 1 12 11L1 20 B 10 60898 Paging System Radial 3CSWA 2 50 2 50 12 00 Y N 1 6 DBPLANTi 12 1113 20 B 10 60898 Pneumatic Air Radial 6491B 4 00 4 00 20 00 Y N 1 7 DBPLANT1 12 12011 63 C 10 60898 INNNWWM Radial 6491B 10 00 10 00 1 00 Y N 1 8 DBPLANT 1 12 12012 63 G 10 60898 Surge Protection Radia 6491B 10 00 10 00 1 00 x N 1 9 DBPLANT1 12 12013 63 C 10 60898 VVVVVV Radial 6491B 10 00 10 00 1 00 Y N 1 10 DBSP1 1 12 733 20 B 10 30 601009 Cleaners Sockets Stair 2 Ring 6491B 4 00 4 00 28 00 Y N 2 11 DBSP11 12 10L1 20 B 10 60898 Automatic Doors Radial 6491B 4 00 4 00 8 00 Y N 1 12 DBSP2 1 12 5L3 20 B 10 60898 Fire Smoke Dampers Radial 6491B 4 00 4 00 80 00 Y N 8 13 DBSP2 1 12 7 2 20 B 10 60898 Fire Smoke Dampers Radial 6491B 4 00 4 00 80 00 Y N 3 14 DBSP2 1 12 113 32 B 10 30 61009 Cleaners Sockets Ring 6491B 4 00 4 00 112 00 Y N 8 15 DBSP4 1 12 72 20 B 10 60898 Fire Smoke Dampers Radial 6491B X 4 00 4 00 68 00 Y N 5 16 DBSP4 1 12 8 2 20 B 10 60898 Fire Smoke Dampers Radia 6491B 4 00 4 00 70 00 Y N 9 17 DBSP5 1 12 92 20 B 10 60898 Fire Smoke Dampers Radial 6491B 4 00 4 00 62 00 Y N 8 18 DBSP5 1 12 11L2 20 B 10 60898 Modbus Power FCU Radial 6491B 4 00 4 00 2 00 Y N 1 19 DBSL1 1 12 333 6 B 10 30 61009 Stairwell No 2 Level 2 Radial 6491B 2 50 2 50 40 00 Y N Z 20 DBSL2 1 12 4i 6 C 10 60898 Riser amp Management Store Radial 6491B 2 50 2 50 40 00 Y N 2 21 DBSL2 1 12 53 6 C 10 60898 Day amp
31. l be shown the Access page where you will need to enter your keycode 6 To obtain your keycode press either CTRL Shift Z or CTRL Z keys to display your computer s MAC address 7 When asked Can Distboard Manager be registered to this PC press Yes 8 Send the onscreen MAC code to alanwelsman alanwelsman co uk from the registered Paypal email address 9 From the return email enter the keys exactly as detailed into DM Access this only needs to be done only once 10 When the keys are entered the message UNLOCKED should appear if so proceed to use DM To help you understand and use DM we will go through section in turn Table of Contents Problem Solving System Requirements Feedback Access Prefs MCB s Boards Labels Charts 10 System 11 Status 12 Active 13 Search 14 Test Schedules 1 to 80 15 Printing 16 Shortcut Keys 17 Macro s 18 Copying Using Distboard Manager 19 N a 20 N a WONBOTAWNE Problem Solving If you try to use DM and find things are not working as they should do try the following 1 Close DM then Re Open when asked to enable disable macro s please enable them 2 Status don t display DB details Ensure in System you have entered details into Board Name amp Location Area column 3 Status Active or Search don t display DB details Ensure you press the Refresh buttons on each of the worksheets 4 Screen size does not automatically change Ensure
32. n non metalic trunking Non sheathed cable s in conduit on a wooden or masonry wall or spaced less than 0 3 x conduit diameter from it F1 PVC AWA F2 PVC SWA No 10 CCC B G1 XLPE AWA G2 XLPE SWA Mineral Insulated Non sheathed cable s in suspended cable trunking O2 FP400 SWA LSF O1 FP200 LSF O3 SY LSF No 31 CCC E F Single core or multicore cable s on perforated tray run horizontally or vertically 1 Select any desired test schedule 2 Press the following key sequence CTRL M 3 To jump back to the specific test schedule left mouse click the top Distribution Board Reference link 4 Up to 12 installation method s are detailed in the bottom section of the chart Would you like your company logo inserted into the Chart this can be done for you and at minimal cost System This is where you manage the LV system its primary role is to manage the sub mains cabling not the distribution cabling It is split up into 5 sections treat each row as one separate circuit again by pressing a header will sort the database LV System Setup Supply Origin Details Submains Cabling Board Name amp Location Board amp Switch Specifics ELR 3 PSC kA Livened Feed S Mod SW BSEN Ph uo Vt ID Cabe CPC L Eath Board Area Location BMod S Mod SW BSEN K L1 L2 L3 Lt L2 t3 05 01 2015 MLV 1L123 250A 60947 2 3 2 A 4C185SWA C95 60 TN S DB1 LO Plantroom No 1 EPB25 312C 250A
33. nge normally Rng 4 6 Enter information for Model normally Model 4 7 Enter information for Type normally Type or Form 4 8 Enter information for BSEN normally BSEN 4 9 Enter information for BUS normally BUS Rating in Amps of the Busbar fitted within the Distribution Board 4 10 Enter information for Ways normally Ways For non split load boards enter No of ways in total 4 11 Enter information for kA normally kA 4 12 Enter information for power of load Split For split load boards enter No of ways dedicated to Power 5 Cables used as CPC s 5 1 This is a table for up to 10 types of cables used as CPC s cable 1 normally 6491B cables 2 to 10 not used 6 Ext CPC s Enter the types of cables installed where you will run additional external CPC s 1 This is a table for up to 10 types of cables which you run external CPC s with 1a Cable 1 2C SWA 1b Cable 2 3C SWA 1c Cable 3 4 SWA 1d Cable 4 3C FP400 1e Cable 5 3x4C SWA 1f Cable 6 2x4C SWA 1g Cable 7 Not used 1h Cable 8 Not used 1i Cable 9 Not used 1j Cable 10 Not used OOo 00000 A 0 o 7 Table 41 1 This section is used by DM as a lookup table to obtain disconnection times for protective devices up to 32A depending upon which type of electrical system voltage range is in use the standard range is Uo Range 2 giving us in an AC circuit on a TN system O 4 seconds and on a TT system O
34. r 4 Recommended Size Adjust the label width and height when you find an exact print size matching your distribution board enter its details as displayed into the Boards section then from this point each time this board is selected the page will auto adjust for you 5 Distribution Board Layout This is to show you how your board is setup for information only 6 RESET Pressing this button will reset the page to normal view only the main label is adjusted in width Charts This is where you can generate Distribution Board charts this is an automated process and has no direct text input istboard manager dlanwelananco uk danwelavan alanwelaman co uk ZOH Distribution Board Reference MLV 1L123 250A 60947 2 3 3 4 3 4 3 4 ABB Protecta EPB25 312C B 60439 1 amp 3 H 718mm W 400mm D 125mm Wt 16 3kg 250A 60947 3 250A 12 Location Plantroom No 1 INNNNAA i520 B 6 60898 Radial 4CSWA G2 31 2 50 2 50 66 00 1 1 Be 20 B 6 60898 DB No 1 Radial 4CSWA G2 31 2 50 2 50 66 00 1 L3 20 B 6 60898 VVVVVV Radial 4CSWA G2 31 2 50 2 50 66 00 1 RE 22 C 10 60898 IVVVVV Radial 4CSWA G2 31 4 00 4 00 35 00 1 2g 32 c 10 60898 DB No 2 Radial 4CSWA G2 31 4 00 4 00 35 00 1 kN 32 C 10 60898 VVVVVV Radial 4CSWA G2 31 4 00 4 00 35 00 1 BM 6 D 10 60898 Motor No 1 Radial 3CSWA G2 31 1 50 1 50 18 00 1 3 NN 0 D 10 60898 Motor No 2 Rad
35. r all the different types of Distribution Boards you may use from different manufacturers The details here are copied to all the test schedules the two columns marked as Labels are used to set the widths of MCB labels specific to each distribution board Distribution Board Database Manufacturer Range Model Type BSEN Bus Ways kA Split Height Width Depth Weight P ABB Protecta EPB25 1212S250CC B 60439 1 amp 3 250A 2x12 1010mm 800mm 125mm 17 25 13 92 ELECSIS LVSB B 60439 1 amp 3 1000A 31 2200mm 4400mm 600mm 1500Kg Schneider Acti 9 Isobar SEA9AN27 A 61439 3 125A 27 16 530mm 417mm 117mm 18 12 57 MEM Eaton Memshield 2 BM241 B 60439 3 125A 24 MEM Eaton Memshield 2 BM242 B 60439 3 200A 24 MEM Eaton Memshield 3 EBM242 B 60439 3 125A 24 1180mm 440mm 140mm MEM Eaton Memshield 3 EBM242H B 60439 3 250A 24 1501mm 440mm 140mm ABB Protecta EPB25 324C B 60439 1 amp 3 250A 24 1140mm 400mm 125mm 17 25 13 92 ABB Protecta PBSMF B 60439 1 amp 3 800A 24 2050mm 1470mm 240mm ABB Protecta PBSMG B 60439 183 800A 24 2050mm 1470mm 240mm ABB Protecta PBSMS B 60439 183 800A 24 2050mm 1470mm 240mm Schneider Acti 9 Isobar SEA9BN24 B 61439 3 250A 24 16 1024mm 470mm 140mm 18 12 57 ABB Protecta ECS120C A 60439 1 amp 3 100A 20 265mm 440mm 110mm 17 25 13 92 ABB Protecta EPB25 320C B 60439 1 amp 3 250A 20 1001mm 400mm 125mm 17 25 13 92 MEM Eaton Memera 2000 AP19 A 60439 3 100A 19 MEM Eaton
36. rangements 25 X5 The protective device must isolate the supply within a specified time depending upon the earthing arrangements ELR Earth Loop Resistance Test instrument is set to Ohms 26 ELR This test measures the total resistance path of Ze Origin R1 R2 Circuit the figure must fall below the permitted value as detailed in the Max column if it fails the value will be highlighted until it is fixed i e change device or upgrade earthing 27 Max This is the figure your ELR value must not go above the figure is the result of several calculations Misc 28 CAB This stands for Cabled if the circuit has been cabled in its entirety enter Y otherwise leave blank 29 POL This stands for Polarity if the circuit s accessories i e sockets amp switches are correctly terminated enter OK 30 CODE This is to help Search find circuits matching your code example N New M Modified etc you make up the code 31 QTY This stands for Quantity enter all the accessories terminated to the circuit count twin sockets as one item The right hand side of the test schedule are details which make up the circuit s test results all the boxes must be filled in It is assumed all circuits detailed above have been physically tested using a test instrument Note the above does not dictate how you must carry out electrical testing in any shape way or form it is a merely a guidance note The bottom section of the test
37. rences of letters i e DB1 then a space then 1 12 13 24 25 36 or 37 48 Example I have a 36 way distribution board and its reference is DB1 Press the HELP button to become familiar with sheet buttons and from the available 6 buttons press the New Chart button When asked to label the new test schedule label as DB1 1 12 create another two called DB1 13 24 and DB1 25 36 As long as you have entered the details of DB1 into the System its Supply Board ELR amp PSC details will be listed Press CTRL F to format test schedules to set them up as single or 3 phase schedules can be used at any time to clean up Press CTRL R to reset all RCBO values don t perform this task if you have RCD test values entered AS you have created modified or deleted new test schedules don t forget to press the Refresh buttons in the Status Active and Search sheets 10 DM can automatically enter your R1 Rn R2 and R1 R2 results ensure the ELR PSC and ELR results are both present then press the small box in between the Rn and R2 boxes 11 DM can automatically enter your ELR results ensure the ELR PSC and R1 R2 results are both present then press the small box in between the ELR and Max boxes WMNATAWNHHY That s the rules outlined you can now start to fill in the test schedule 1 Starting at the top right corner enter a distribution board reference into the box labelled Ref No r
38. t with vertical lines Y 1 Enter information for Origin Leave blank to exclude Origin 2 Enter information for Sw Model Leave blank to exclude gt Sw Mod 3 Enter information for Sw Rating Leave blank to exclude Sw Rtg 4 Enter information for Sw BSEN Leave blank to exclude gt Sw BSEN 5 Enter information for Phase s Leave blank to exclude gt Phase s 6 Enter information for Cab I D Leave blank to exclude gt Cab T O 7 Enter information for Cab Type Leave blank to exclude Cab Type 8 Enter information for CPC Leave blank to exclude CPC 9 Enter information for Earthing Leave blank to exclude Earthing 10 Enter information for Leave blank to exclude Enter Board Specific info for Sw Model Leave blank to exclude gt 1 2 Enter Board Specific info for Sw Rating Leave blank to exclude gt Sw Rtg 3 Enter Board Specific info for Sw BSEN Leave blank to exclude gt Sw BSEN 4 Enter Boards info for Manufacturer Leave blank to exclude Mfr 5 Enter Boards info for Range Leave blank to exclude Rng 6 Enter Boards info for Model Leave blank to exclude Model 7 Enter Boards info for Type Leave blank to exclude Form 8 Enter Boards info for BSEN Leave blank to exclude BSEN 9 Enter Boards info for BUS Leav
39. t schedule Means FORMAT SCHEDULE Use this option to reset or clean up schedules 3 GetPHYSAddress This is a shortcut to display the PC s MAC address 4 HelpMe Run this macro to display the tests schedule Help menu 5 InsertMACAddress This is a shortcut to display the PC s MAC address 6 Master Reset Run this macro to delete all but the first test schedule 7 ResetRCD Use only when in a test schedule Means RESET RCBO SETTINGS Use this option on a blank schedule only 8 ThreePh Run this macro to display the tests schedule Test Sheet Page Setup menu Copying Using Distboard Manager When you purchase Distboard Manager and open it for the first time you will be asked to lock the software to your PC you have 2 open close events to lock the software before the software becomes non functional When you request a keycode or assistance for Distboard manager please communicate via email a response will be returned to you if your email address matches the purchaser s verified paypal email address this will be the only type of communication which will be entertained When you lock the software to your PC Distboard Manager records the current PC s environment If you copy the software and attempt to use it on another PC an environmental comparison check will be carried out if the check fails the software will cease to function Distboard Manager remains the property of Alan Welsman at all times any attempt to disassemble the soft
40. ter an RCBO trip time code suffix normally s for seconds 2 9 Enter the Uo nominal phase voltage to earth TN normally 230 2 10 Table 41 1 applies to circuits up to Amps normally 32 2 11 Preferred CPC if running external to SWA normally 6491B 2 12 Intentionally left blank 2 13 Intentionally left blank 2 14 When copying a Schedule to Chart display Chart with vertical lines Y normally left blank 3 Toggle Supply Info Adjust titles to be viewed in all test schedules to do with Supply Characteristics 3 1 Enter information for Origin normally Origin 3 2 Enter information for Sw Model normally 5w Mod 3 3 Enter information for Sw Rating normally Sw Rtg 3 4 Enter information for Sw BSEN normally Sw BSEN 3 5 Enter information for Phase s normally Phase s 3 6 Enter information for Cab I D normally Cab I D 3 7 Enter information for Cab Type normally Cab Type 3 8 Enter information for CPC normally CPC 3 9 Enter information for Earthing normally Earthing 3 10 Intentionally left blank 4 Toggle Board Info Adjust titles to be viewed in all test schedules to do with Distribution Boards 4 1 Enter information for Sw Model normally Sw Mod 4 2 Enter information for Sw Rating normally Sw Rtg 4 3 Enter information for Sw BSEN normally Sw BSEN 4 4 Enter information for Manufacturer normally Mfr 4 5 Enter information for Ra
41. ts 3 6 6 Board Setup Lighting Lighting TP amp N Row 1 Row 1 Xnroo ueuis owue e MMW q SHEYO 22 22 Ver Hor Lighting Lighting 48 00 1257 i z Row 2 Row 2 23 23 A R lt Lighting Lighting easel Ri gt lt Row 3 Row 3 22 22 17 25 13 92 Recommended Size 4moo ueuisewuejegyueuisiewueje Aq Sueuo 12 Ways YNV ODULWSJ MULJE MMM q SHEYO Cleaners Cleaners SPLIT Sockets Sockets 10 z 10 1 Pwr 7 Cleaners Cleaners Sockets Sockets J i 12 6 12 DB1 From MCB 1 DB1 From MCB 1 Note For best results use Avery inkjet adhesive labels ref J8167 100 199 6x289 1mm or if using a laser printer or copier use Avery laser adhesive labels ref L7167 100 199 1x289 1mm 210 00 192 50 175 00 157 50 140 00 122 50 105 00 87 50 70 00 52 50 35 00 17 50 Mains Meters Printed in colour these sheets produce an excellent finish simply print the label cut around the black boxes peel the backing off then place inside the distribution boards 1 Distribution Board Select from the drop down arrow a specific distribution board 2 MCB Start No Select a starting point to print from 3 Board Setup This will tell you if your Distribution Board is single or three phase simply click the result to have the legends automatically setup note that single phase boards will be setup in their phase colou
42. uits yet to be tested 3 If you enter Y into both boxes circuits where cabling and testing are yet to be completed are displayed Note 1 By entering Y in either option above then selecting the Search tab all circuits are given more detail Note 2 Simply left click any distribution board reference to be taken to that schedule Note 3 When you create modify or delete test schedules ensure you press the Refresh button this is a small square button located on the right hand side of the box labelled MCB s currently installed throughout all the distribution boards this button can be pressed any time 12 Search BLUE TAB This is where you can quickly find a circuit matching any criteria from a maximum total of 2880 circuits Starting on the left side between the words No and Board is a Refresh button Note 3 above applies to this search page Distboard Manager Circuit Search Sheet Qty 140 Length 1473 Mtrs No Cct MCB Type kA mA BSEN Description Circuit Cabling CCT CPC Length Cabled Attrib Qty 1 N 1 DBPLANT 1 12 212 20 B 10 60898 Modbus Power FCU Radia 6491B 4 00 4 00 35 00 Y N 1 2 DBPLANT 1 12 213 6 C 10 60898 RB2000 amp Wifi FCU s Radial 6491B 4 00 4 00 12 00 Y N 2 3 DBPLANT 1 12 43 20 B 10 60898 Fire smoke Dampers Radia 6491B 4 00 4 00 40 00 Y N 3 4 DBPLANTi 12 511 20 B 10 60898 TV Aerial Ampl
43. ware will be deemed as criminal damage This user guide has been written by Alan Welsman and is subject to change without notice DM v1 09 dated 31st January 2015 16
44. when you open DM you enable macro s 5 Excel does not appear to be calculating or changing values Ensure Excel Tools Options Calculations is set to Automatic Hyperlink issues arose after uninstalling Google Chrome on a Windows based PC many DM hyperlinks ceased to function there is an issue where the registry file is not completely reset during the uninstallation process this can be fixed but recommend should be done only by users experienced in the Microsoft Windows system registry file the fix is to search for all values labelled ChromeHTML or FireFoxHTML and rename them as htmlfile System Requirements DM has been written within the parameters of Microsoft Excel version 2002 v10 0 32 bit running on a Microsoft Windows based PC At the time of writing the version s of Microsoft Windows were XP version 7 The current version of DM has been tested using Excel 2003 v11 0 2007 v12 0 2010 v14 0 without any issues At the time of writing is has not yet been tested on Excel 2013 v15 0 Minimum requirements is to have a Windows based computer system running Excel 2002 Feedback If you use DM and believe you have an idea which could be integrated into DM and its future revisions please feel free to email me your comments if your idea does become a part of DM as a thank you from me I will ensure your version of DM including all future revisions of DM are fully activated and functional for as long as you use it I

Download Pdf Manuals

image

Related Search

Related Contents

ウロコ落し新発売 - G・skyECO  F3SN-A/F3SN-B/F3SH-A  POCKETMETER 2 - Machine Mart  MF608 User Manual  Télécharger le programme 2014-2015  Tucano Mask  Télécharger la version PDF de ce numéro  Enviro Puck  R&S FSW-K18 Amplifier Measurements User Manual  Digitus DS-55100 video switch  

Copyright © All rights reserved.
Failed to retrieve file