1. Auto alignment must always be performed after this To use hand alignment as part of beam installation 1 Ensure detector and reflector are mounted opposite in clear line of sight 2 Select Auto alignment first and press Cross x after two seconds 3 Select Hand alignment 4 Steer beam until the returned signal strength is above 800 5 Perform Auto alignment Beam Alignment This option allows the installer to optimise beam alignment either manually or automatically Alignment On selecting this option the Auto screen is displayed as shown This can be toggled between Auto and Hand manual by using the Left lt amp Right gt arrow keys Pressing the Tick Y key selects the option currently displayed pressing Cross x returns to the main Settings Menu NOTE User must set zero 100 page 9 after either of these functions for correct operation Auto This option uses the infrared beam to search for a maximum returned value and returns to the Settings Menu when complete Please note this will take up to 12 minutes to complete RX gain and TX power are optimised automatically Hand This option displays the current returned signal value of the infrared beam The installer can use the Left X Right gt Up A amp Down W arrow keys to steer the motor until a maximum value is achieved There is no auto repeat function on any key To move
2. The System Controller can not locate a Detector at the selected number This is also shown during power up Pointers e Wait 45 seconds for system power up e Ensure peelable mask is removed from detector First fix e Check wiring 19 E 02 NO VALID SERIAL NUMBER The Detector serial number is not valid there is a potential fatal error with the Detector Pointers e Contact manufacturer D Z 0J mai E pa pe E 03 EEPROM Write There was an error writing to the EEPROM Pointers Power down system for 1 Minute e If error code seen again call manufacturer D C NJ L Wu E 08 Compensation has not been set to default of zero Pointers e Re align beam using auto optimise Error Codes A list of error codes for the Detector and System Controller explanations amp trouble shooting E 09 Received signal strength out of range Pointers e Ensure correct distance has been set Ensure correct reflector type has been used e Re align beam using auto optimise D E 10 di E 10 REFLECTOR NOT FOUND The beam can not align onto the reflector retry LASER targeting or manual alignment Pointers e Ensure correct distance has been set Ensure correct reflector type has been used e Ensure clear line of sight to reflector e Re align beam using auto optimise D E 11 di
3. indicates the current curser position e Each digit can be changed by using the Up A 8 Down Y arrow keys e Use the Left lt amp Right gt arrow keys to move between digits e When all the digits have been set correctly press the Tick Y key If the Pass Code is correct the Settings Menu will be displayed If the Pass Code is incorrect the display will return to the prompt After three incorrect attempts the system will lock access for three minutes NAVIGATION e Pressing the Cross F key at any time returns the display to the User Menu e Note If no keys are pressed for 30 seconds the system will Lock and Sleep Settings Menu This menu allows detectors to be installed and settings modified p E FDRDOOGA lee D OH GKBSe 3 A AD OH Als e Home Position Detector Settings LASER Targeting Beam Alignment Fire Threshold Page 10 Page 9 Page 11 Page 12 Page 13 Page 17 Page 16 Page 15 Page 14 Controller Settings Software Utilities Fire Test Fire Fault Delay E e DADOS dy Ie AD OHRG Ale AD OH OBa e AD OLB Ku e e A valid Pass Code See page 7 must be entered before any of these functions can be accessed e The menu is navigated by the use of the Left lt amp Right gt arrow keys which moves the cursor Items are selected by the use NAVIGATION of the Tick key Pressing the Cross x key exits this menu and returns the system to a locked state Detecto
4. system START Mount and cable to all hardware DO NOT MOUNT REFLECTOR Apply power to system and wait 40 seconds for Detector to power up ANGERS LASER RADIATION AVOID DIRECT EYE EXPOSURE POWER OUTPUT lt 5mW CLASS Illa LASER Wavelength 630 680 nm Enter Pass Code Factory default 1234 See page 7 MER Select current Select Detector to Set Distance Set Home Position operating mode Hi be installed default 8 50m See page 10 or Lo default Lo only No 1 at See page 5 See page 17 present See page 9 ge AD ODGKUSe 5 00 e ADMOHGKuUS a Select LASER Mount Reflector Manually Steer Auto optimise Set Zero 100 Targeting As close to LASER to reflector EEE a See page 11 LASER position as See page 11 possible NOTE FOR INSTALLATION OF 8 18m PLEASE USE THE ENCLOSED SHORT RANGE MASK PEEL OFF THE WHITE BACKING COVER TO REVEAL ADHESIVE SURFACE AND PLACE SQUARELY ON TO THE STANDARD 10cm X 10cm REFLECTOR See detector install guide for more details 1 Display amp Controls Icon descriptions Seconds User Prompt Latched Reset Signal Strength Feet Signal Clarity Compensation Detector Number LA Metres Fire Degrees A Busy Warning Key Present gl Transmit Numeric Display Signal Strength Received System Locked Signal Strength Unlocked IV Cursor Bar Graph Set Home LASER Assisted Fire System Controller Pos
5. will flash green every 10 seconds e Status LED When the beam is in Fault the LED will flash yellow every 10 seconds or red every 10 seconds when itis in Fire System Controller e Detector Status LEDs LED 1 2 3 and 4 reading from left to right Flash every 10 seconds mimicking the respective Detector status LED e Health LED LED 5 When the System Controller is functioning correctly the LED flashes green every 10 seconds European Approval Information Fire Fighting Enterprises Ltd 9 Hunting Gate Hitchin SG4 OTJ 07 0832 CPD 0565 EN54 12 Line detector using an optical beam Fire Saftey Documentation See doc 0044 003 Complies with EN54 12 for sensitivity levels between 25 and 35 with a maximum delay to fire of 20 seconds Protective cage must be fitted to comply with EN54 12 Operational Parameters American approval operational information Operational parameters Typical Operation 1x Detector System Controller and Conventional AIM All figures are quoted for 25 deg C Approximate Dimensions Parameter Description Height Depth Weight in System Controller including base Operating Voltage to System Controller Operating Current low current mode Detector including easy fit base Universal Bracket Reflector Single Operating Current high current mode Response Threshold Sensitivity Default 35 Delay to Fire user settable Default 10 sec Delay to Fault
6. E 11 AUTO OPTIMISE FAILED The routine timed out whilst trying to maximise signal strength the reflector may have been obscured Pointers e Ensure correct distance has been set e Ensure correct reflector type has been used e Ensure clear line of sight to reflector e Re align beam using auto optimise D E 12 di E 12 CAN T ZERO The reflector was not properly covered or the beam is not aligned onto the reflector Pointers e Ensure reflector was uncovered when set was selected e Ensure reflector was covered with a non reflecting material 20 Appendix A IMPORTANT PLEASE NOTE Appendix A contains specific technical details relating to Fireray 5000 Conventional units only 21 Wiring Diagram FR5000 Wiring Diagram for Single amp Multiple Systems on a Zone TO THE TO THE DETECTOR DETECTOR 14V TO 28V DC 14V TO 28V TO THE FIRE PANEL FIRE RESISTOR ZONE l _ Wiring for for all other beams multi beam system ln Wiring for single or last beam on a Zone Please Note e The operation for Fire and Fault should always be checked for correct connection to the fire panel e Contact the Fire Panel manufacturer for the values of the Fire Resistor and the End Of Line component EOL 22 Operational Parameters European approval operational information Operational parameters Typical Ope
7. FIRERAY 5000 range 0044 003 04 IMPORTANT PLEASE NOTE The beam path MUST be kept clear of obstructions at all times Failure to comply may result in the Detector initiating a Fire or Fault signal NOTE The word Fire will be flashed on the System Controller when a Fire is detected In addition the Detector number and Fire symbol will flash until any key is pressed Introduction CONTENTS Page 1 Page 2 Page 3 Page 4 Page 5 6 Page 7 Page 8 Page 9 Page 10 Page 11 Page 12 Page 13 Page 14 Page 15 Page 16 Page 17 Page 18 Page 19 20 Page 21 Page 22 Page 23 This guide details the setting up amp operation of the Fireray 5000 range of beam smoke detectors Quick Start Display amp Controls Icons Display amp Controls LED Indicators How to use this Guide Viewing Menu Main operation menu providing read only access to operating parameters Enter Pass Code To gain access to the Settings Menu Settings Menu Main programming menu providing access to adjust operating parameters Detector Settings Home Position LASER Targeting Beam Alignment Fire Threshold Fire Fault Delay Fire Test Software Utilities Controller Settings Operating Parameters Error Codes Explanations and Trouble Shooting Appendix A Fireray 5000 Conventional System Controller wiring diagram Operational Parameters Quick Start A quick start guide to install a Detector
8. alues and settings can be altered A valid Pass Code is required to unlock system e The Left lt amp Right gt arrow keys move you between items on the same level e The Up A amp Downy arrow keys either select items on other levels or change the value of a selected item e The Up Down Left amp Right arrow keys are also used to manually steer the selected Detector e Selections are made by pressing the Tick Y key IGATION e The Cross X key is used to exit an option without saving any changes e Inactivity will cause the system to time out after 15 minutes in Engineering mode 30 seconds in User Mode Viewing Menu This menu allows the operating parameters of the Detector s and System Controller to be viewed Controller parameters Blank screen Sleep p IL H is default state of the woe display on pressing any III Zax key the display will wake A D IL H Detector parameters INF A IE D IL E gt GEB l bood a e Pressing Tick Y at any point in this menu will prompt for the Pass Code to be entered NAVIGATION e Pressing Cross x puts the system back into Sleep e Navigate screens using the Left lt Right gt Up A 8 Down W arrow keys 5 SCREEN DESCRIPTIONS ON OPPOSITE PAGE Viewing Menu Screen descriptions Controller parameters Current Mode System Controller Status ange either Hi A or Lo A Normally good problems Or are indi
9. cated by an error Software version depending on setting code See page 19 20 Blank screen Sleep is default state of the Received signal Compensation Threshold Delay display on pressing any strength for the selected level for selected Detector sensitivity for selected to Fire for selected key the display will wake Detector Detector Detector Scroll Detector parameters through each Detector in turn to select other detectors if fitted Status Software of selected Detector version of selected Normally good problems Detector are indicated by an error code See page 19 20 Temperature of selected Detector in Distance of selected Detector as either 8 50m or 50 100m Delay to fault for selected Detector either deg C or deg F dependent on setting e Pressing Tick Y at any point in this menu will prompt for the Pass Code to be entered AVIGATION e Pressing Cross x puts the system back into Sleep e Navigate screens using the Left lt Right gt Up A 8 Down yw arrow keys ONLY AVAILABLE ON MULTI DETECTOR UNIT 6 Enter Pass Code Allows the Engineer to enter the Pass Code to Unlock the system Factory default Pass Code 1 23 4 Detector settings Is the default screen of the Settings Menu Ed which is displayed after the correct Pass Code has been entered A D COL GKU e e Prompt is accessed by pressing the Tick Y key from the User Menu e Flashing
10. d for 8 18m operation 1 Reflector required for 18 50m operation Distance between detector amp reflector Fire Threshold Range 4 Reflectors required for 50 100 m operation 8m 10m 26 2 32 8ft 10 18 Note The auto aligning characteristics of this device will reduce the need for maintenance although a regular inspection 10m 15m 32 8ft 49 2ft 15 25 and testing regime should still be implemented to ensure trouble free use of the product 15m 22m 49 2ft 72 2ft 15 35 22m 40m 72 2ft 131 2ft 25 50 40m 60m 131 2ft 196 8ft 35 50 60m 100m 196 8ft 328 1ft 50 24
11. ing for dust build up and building movement At 100 auto align is invoked Range 50 to 4095 Sets the intensity of the IR LED The higher the value the greater the intensity Set automatically by auto optimise Received Gain Range 1 to 255 Sets the received signal amplification from the IR receiver The higher the value the greater the gain Set automatically by auto optimise Fire Threshold Range 10 to 60 Sets the amount the signal needs to fall by to signal a fire where 10 is the most sensitive i e a setting of 35 means the signal needs to fall to or below 65 to be a fire Delay to Fire Delay to Fault Distance Range 2s to 30s Sets the time the system needs to be below the 10 seconds fire threshold before a fire signal is sent to the fire panel Range 2s to 30s Sets the time the system needs to be below the 10 seconds 13 before a rapid obscuration fault is sent to fire panel Note the signal needs to fall to lt 13 within 2s 8m 50m or 50m 100m Sets the beam operating length Effects initial transmit power at start of auto optimise Auto align Latched non latched Disables or enables auto align Sets if the system will latch into a fire when one is detected Non latching Faults are always non latching 18 Error Codes A list of error codes for the Detector and System Controller explanations amp trouble shooting D E 01 di E 01 DETECTOR NOT FOUND
12. ition Targeting Threshold Fire Test Settings Detector Settings Beam Fire Fault Software Alignment Delay Utilities Y x e Graphic symbols used throughout programming guide indicate Tick amp Cross lt gt A W Graphic symbols used throughout programming guide indicate Left Right Up amp Down Display amp Controls LED Indicators Detector Two LED indicators Health GREEN LED flashes every 10 seconds indicating the beam is in normal operation Status Red Yellow Bi Colour LED YELLOW flashes every 10 seconds indicating a Fault RED flashes every 10 seconds indicating a Fire System Controller Five LED indicators From left to right 1 2 3 amp 4 are Detector Status indicators Status Red Yellow Bi Colour LED YELLOW flashes every 10 seconds indicating a Fault RED flashes every 10 seconds indicating a Fire LED 5 is the System Controller status a GREEN LED flashes every 10 seconds to indicate the System Controller is functioning correctly ONLY AVAILABLE ON MULTI DETECTOR UNIT This Guide How to use this guide Default screens When displaying settings Screens can be navigated one or the other would be between and either one of them Indicated by a bold border displayed selected and System Controller Bezel surround Indicates the system is Locked and items may only be viewed 8 el _ Indicates the system is Unlocked so that v
13. lash e Please note this will take up to 15 minutes to complete e When complete it will return to the Settings Menu 10 LASER Targeting This option allows the installer to use the integral LASER to align the beam A Ed al DROGA ls e LASER When the cursor is placed over this option the warning symbol will flash This is to indicate that selecting this option will cause the LASER to come on DANGERS LASER RADIATION AVOID DIRECT EYE EXPOSURE POWER OUTPUT lt 5mW CLASS Illa LASER Wavelength 630 680 nm 11 p A un ef ES NOTE The system will signal fault while in this mode e Selecting this option turns the LASER on and the screen above will be shown e The motor control is enabled and the user may now steer the motor to the required position using the arrow keys NOTE One press of an arrow lt gt Av key results in one movement of the Detector head e Pressing either the Tick Y or the Cross x key causes the LASER to turn off and returns to the Settings menu NOTE The LASER should be used as an approximate alignment guide only The LASER and the Infrared Beam are not on the exact same axis therefore once the Beam has been aligned the LASER may appear to be off the reflector If not possible to see the laser due to installation environment eg cannot see reflector or high ambient light then hand alignment must be used see page 12
14. ment and Change Pass Code are accessed by using the Left lt amp Right gt arrow keys Change Pass Code Pressing the Tick key stores the change and returns to the settings menu l i 123 Pressing the Cross key ch Ch ch ignores any changes and returns to the settings menu lt WARN N e e Current Mode Sets the system into either high or low operating current mode e Units of Measurement Changes the units of measurement Care must be taken when changing the Pass Code If lost e Change Pass Code Press the Tick Y key on the Pass Code screen to accesses the option to change the system Pass Code Each the unit can not be unlocked debe medie e digit is accessed by the Left lt 8 Right gt arrow keys the value of each digit being altered by the Up A amp Down YW arrow keys manufacturer This is not e Pressing the Tick Y key commits the new Pass Code and returns to the settings menu covered by the warranty e de e Pressing the Cross x key ignores any change and returns to the settings menu Operating Parameters Mode Pass code Range and effect Parameter Default User Code required to access settings Current Mode Compensation Transmit power Hi the system will draw a constant maximum for configuration Lo The system will draw a constant minimum for configuration Range 50 to 205 Default value 0 on auto optimise This is used by the system to amplify the signal compensat
15. ption places the selected Detector into a fire condition Confirm screen When this screen is displayed the system is waiting for the user to confirm they wish to perform the test Pressing the Tick v key confirms and proceeds Y with the test Pressing the Cross x key exits without performing the test with the signal and threshold unchanged Fire Test Fire screen A fire test is performed by the system The system is now in Fire and the user may press the overriding the set threshold sensitivity Tick Y or the Cross Y key to exit and return to and setting it to 25 The signal level the settings menu is then reduced such that the received signal lt 74 forcing the system into fire On exiting this option the signal level and threshold setting are returned to their original values 15 Software Utilities This option enables communication with the diagnostic port a UN 00 5 Dea 0 Co On selecting this option the Exit this option by pressing either the diagnostics port is enabled and Tick Y or the Cross x key and communication is possible with the return to the settings menu KKK interface application PC BASED SOFTWARE AVAILABLE AS AN OPTION 1 6 Controller Settings This option provides access to the System Controller s operational settings Bp m TIL E u a Current Mode Units of Measurement gt LEFT RIGHT Current Mode Units of Measure
16. r Settings This option allows the installer to make changes to the Detectors operating parameters DEFAULT IS FOR NON LATCHED RESET Set Detector Number Set Distance Set Fire Latch Reset Auto Optimise On Off Set RX Gain Set Zero 100 Set TX Power ee Set Compensation Leve Pressing the Tick key stores the change and returns to the settings menu Pressing the Cross key ignores any changes and returns to the settings menu Set Zero 100 e This option is selected by pressing the Tick Y key e Prior to selecting this item ensure the beam is properly aligned and the reflector is uncovered e S 00 Step 0 is displayed the installer MUST cover the reflector and then press the Tick Y key whilst it is still covered NAVIGATION e S 01 Step 1 is displayed the installer can now uncover the reflector and then press the Tick Y key e The system will now return to the settings menu ONLY AVAILABLE ON MULTI DETECTOR UNIT ENGINEERING USE ONLY WARNING ALTERING MAY CAUSE MALFUNCTION Home Position Allows the installer to set the Detector position to the Home Position i 2 Home Position e Selecting this option automatically steers the motor to the Home Position e Pressing either the Tick Y or the Cross x key exits this function and returns to the settings menu e Whilst performing this function the Busy icon will f
17. ration 1x Detector System Controller and Conventional AIM All figures are quoted for 25 deg C Parameter Operating Voltage to System Controller Operating Current low current mode Operating Current high current mode Response Threshold Sensitivity Default 35 Delay to Fire user settable Default 10 sec Delay to Fault user settable Default 10 sec Operating distance separation Maximum angular misalignment of Detector from optical axis Maximum angular misalignment of Reflector from optical axis Maximum angular alignment Optical wavelength Fault level Rapid obscuration lt 2 sec Operating temperature Storage temperature Relative humidity non condensing IP rating Contact Voltage Fire amp Fault relays DPCO Contact Current Fire amp Fault relays DPCO Cable length System Controller to Detector Cable gauge 2 core screened fire resistant Housing flammability rating 1 Reflector amp mask required for 8 18m operation 1 Reflector required for 18 50m operation 4 Reflectors required for 50 100 m operation 23 Approximate Dimensions Description Height Depth Weight System Controller including base 9 5 Detector including easy fit base Universal Bracket Reflector Single Protective Cage E LED Indication Detector e Health LED When the beam is in normal operation the LED
18. the motor in any given direction more than once press that key multiple times Pressing Tick Y or Cross XK when finished returns to the main settings menu 12 Fire Threshold This option allows the installer to set the required Fire sensitivity D Q cn LILA La 5 e The main default settings of 25 35 and 50 can be scrolled through by use of the Left amp Right gt arrow keys these can then be changed in steps of 1 by use of the Up A 8 Down W arrow keys i e When the desired level has been set the Tick key is pressed to save the value and the system returns to the settings menu NAVIGATION Y keyisp y i e Pressing the Cross x key ignores any change and returns to the Settings Menu 13 Fire Fault Delay This option allows the installer to set the delays for both Fault and Fire independently Delay 1 Fire Delay 2 Fault On entering this option Delay 1 Fire is displayed Delay 2 Fault is accessed by using the Left lt amp Right gt arrow keys which toggle between the two delays It is not possible to set the Delay to Fire to less than the Delay to Fault e The value of either delay is adjusted in steps of one second by use of the Up A amp Down V arrow keys e Pressing the Tick Y key saves the current delay values and returns to the settings menu NAVIGATION e Pressing the Cross x key ignores any changes and returns the the settings menu 14 Fire Test This o
19. user settable Default 10 sec Maintenance Requirements Operating distance separation Due to the self aligning characteristics of this product no maintenance is required However it is recommended that the Maximum angular misalignment of Detector from optical axis a detector lenses be cleaned periodically with a soft lint free cloth Maximum angular misalignment of Reflector from optical axis Maximum angular alignment Optical wavelength LED Indication Fault level Rapid obscuration lt 2 sec Detector Operating temperature e Health LED When the beam is in normal operation the LED will flash green every 10 seconds Storage temperature e Status LED When the beam is in Fault the LED will flash yellow every 10 seconds or red every 10 seconds when Relative humidity non condensing it is in Fi it is in Fire IP rating Contact Voltage Fire amp Fault relays DPCO Contact Current Fire amp Fault relays DPCO System Controller e Detector Status LEDs LED 1 2 3 and 4 reading from left to right Flash every 10 seconds mimicking the respective Cable length System Controller to Detector Detector status LED e Health LED LED 5 When the System Controller is functioning correctly the LED flashes green every 10 seconds Cable gauge 2 core screened fire resistant Housing flammability rating UL94 VO USA Approval Information 1 Reflector amp mask require