1.      Manual burner switch O      The manual switch should always be set to Automatic   AUT   The positions 0  Manual and max I   Il are  special settings  which should only be operated by  specialists when faults exists     The burner may be directly controlled with the manual  switch  However  the control unit continues to operate   Never use the manual switches to switch OFF the    system  when you have to temporarily leave the system     Buderus                                           Fig 3  ZM432    Display    General fault   e g  site error  sensor error   external faults    internal wiring fault    module error  manual mode   These fault messages appear  as plain text on the   MEC 2 programmer     Burner function indicators    Display  gt     Display sm    Burner fault  Burner operating  Display A Increasing the burner operating output  Display y Reducing the burner operating output  Boiler circuit function indicators   Display  Display    Display A    Display y    Boiler circuit in summer mode    Boiler pump active    3 way mixing valve opens towards the boiler    3 way mixing valve opens towards the  heating circuit    We reserve the right to make any changes due to technical modifications     10 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006        Only the first stage will be enabled for  single and two stage burners  For  modulating burners  the burner output can  be infinitely increased using    and  infinitely reduced using W     AUT
2.     Re loading DHW    The DHW temperature has fallen during night set back DHW  below the set temperature and can be corrected if measured  required  if the indicator in the button illuminates       Press the button     The green LED in the button flashes  until the DHW  cylinder has been reloaded    The DHW circulation pump runs permanently during  reloading     Starting the DHW circulation pump    Pressing the button only starts the DHW  circulation pump  if the DHW is still at its set    temperature     Reloading       DHW circulat    Pump is on  3 minutes       If you started this function in error  press the  button again     DHW    Reloading is then stopped  measured    Reloading  stopped       We reserve the right to make any changes due to technical modifications  Buderus    Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006 23    Setting constant operation     Open the cover  then press and hold down the  button      Turn the dial until  DHW  is shown        Release the button  Heat circ      Press the button     DHW is now produced at all times  The standard    DHW  display re appears after 3 seconds        55   C    Perm operation       Switching OFF DHW heating     Open the cover  then press and hold down the  button      Turn the dial until   DHW  is shown        Release the button     Press the button  OFF    DHW heating is switched OFF   The standard display re appears after 3 seconds     DHW    Setting up automatic mode      Open the co
3.    Check whether the boiler is under at least 1 bar pressure    If this is the case    Reset the high limit safety cut out by removing the domed nut and pressing  the reset button located underneath the nut    If unsuccessful    Notify your heating engineer        Remote control  fault    The control unit works with the  last values set on the remote  control     Notify your heating engineer        Boiler sensor    The heating system may heat    Consult your heating engineer        DHW sensor is faulty     fault  with higher temperatures to   Notify your heating engineer which temperature sensor is faulty   Outside sensor safeguard the DHW flow    fault    Flow sensor   fault   DHW sensor For safety reasons  no hot Notify your heating engineer    fault water will be produced if the       Heating circuit X   in manual mode   DHW in manual mode   Boiler circuit in manual  mode    Burner in manual  mode          Depending on switch  positions  pumps  actuators   etc  will be operated manually   The control functions continue  to operate in manual  operating mode  but will have  no effect on the heating  system        The switch was set to manual  for maintenance purposes or to remedy a  fault    Return the manual switches to AUT after the fault has been remedied        Table 3 Fault table    Buderus  62    We reserve the right to make any changes due to technical modifications     Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006       27 Emergency mode 
4.    Control device unit    Never open the control unit  Never attempt to  dismantle individual components     Heating with manual override    For emergency operation  manual switches are  provided on the control unit and on the modules  In  position each respective pump will be activated  The  mixers stay at zero volts and should be manually  adjusted     Check the settings on individual modules for possible  incorrect settings prior to making adjustments for  manual operation     If the control system indicates a fault you may  temporarily run your heating system manually                  o      e  Bo     o                                                          O Set the boiler water thermostat  a  to 60   C   90   C  in case of failure                  Set the ON OFF switch to          Set the burner emergency operation to  w    ag  The 1st burner stage will always be directly controlled   Set the 2nd burner stage via the manual switch of the  module                 set the DHW heating to 60   C     aur TO Safeguard the DHW provision in emergencies  set     the manual switches to y   Boiler circuit to w  Mixer circuit to w  DHW to w          Fig  15 Heating with manual override    We reserve the right to make any changes due to technical modifications     Buderus    Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006 63                   Fault Settings for an emergency operation  ON OFF switch   Manual Manual Boiler water Manual switch  on switch swi
5.    The display briefly shows the heating circuit and then  the last set program for this heating circuit  The  program description flashes     Heating circ  2    Timer    Program choice    Family       Buderus We reserve the right to make any changes due to technical modifications   32 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006       Release the button     The display shows the 1st switching point of the Family program  selected program   Monday  at 05 30 hrs      Turn the dial to the switching point  which you want    to move     Family program    Tuesday  at 05 30 hrs      Press and hold down the button   The time of the switching point flashes       Turn the dial to Tuesday 06 30     e a  Release the button Tuesday    If you want to revert to the previous switching time  press at 06 30 hrs  and hold down the button again  and turn the dial  back to the original switching point     Program  Own  2    Return to the standard display    Press the  J  button        We reserve the right to make any changes due to technical modifications     Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006       Buderus  33    Inserting switching points    You may interrupt heating phases by inserting switching  points     Example  The standard  Family  program for heating  circuit 2 provides constant heating on Fridays from  05 30 until 23 00 h  Insert two new switching points if  for  example  you do not want to heat on fridays from 10 0
6.   Display    Display for set room  temperature    Enter DHW  temperature reloading    Set time    Modify temperature  values   Summer and winter  changeover    Back to the  standard display    Program selection    Select heating circuits domestic hot water    circuit       Fig  7 MEC 2 programmer    We reserve the right to make any changes due to technical modifications     Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    Buderus       7 Getting started    Initial start up       Check that all manual switches on the programmer  and the modules used are set to AUT       Set the control unit ON OFF switch to  1      The MEC2 programmer will then start up  Data is then  matched between the control unit and the MEC2  A little  later  the display of the MEC2 programmer indicates the  standard display preset at the factory     Shutting down      Set the ON OFF switch to  0        in an emergency  switch OFF the emergency stop  switch outside the boiler area     Buderus    Setting the room temperature for all  heating circuits allocated to the  MEC 2    USER NOTE      Heating circuits with the MEC 2 pro   Buderus grammer are selected as  MEC heat   circ         Heating circuits without MEC 2 pro   grammer are selected as  Heating cir   cuit and heating circuit number  or as   Heating circuit name and heating cir   cuit number      Setting the day room temperature      Press and release the button whilst the cover  is closed       Turn the dial until the 
7.   Noon   appears     Buderus          Standard  Noon  program    Day mode  Night  mode 6 00 8 00 11 30 13 00 17 00 22 00    New program  Own program 2     Day mode  turn to 17 00  Night    mode 6 00 8 00 11 30 22 00          Fig  11 Connecting heating phases    Heat circ  sel     Heating circ  2    Timer    Heating circ  2       Timer    Program choice       We reserve the right to make any changes due to technical modifications     40 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006       Release the button     The display shows the 1st switching point of the  selected program     Connecting heating phases      Turn the dial until the switching point of that heating  phase is displayed  which you want to join to another   In this example 13 00       Press and hold down the button   The time begins to flash       Turn the dial to the next switching point  In this  example 17 00   As soon as the switching point 17 00 has been  reached  the display changes to  Switch  periods is  combined   On the bottom line blocks are display   which disappear one after the other     USER NOTE    You can interrupt the deleting process be   Buderus  fore all of the blocks have disappeared by    releasing the button or by turning the  dial back     Both switching points  13 00  and  17 00  will be joined   and the new program with the continuous heating phase  saved as  Own program 2   as soon as all blocks have  disappeared     Return to the standard display    Press 
8.   The burner operates in automatic mode    0  The burner is switched OFF  Except when  the burner emergency mode switch is set  to   Max I Il  The burner continuously operates at    maximum output     Boiler circuit function  ANI     0  Manual boiler circuit switch oO   The manual switch should always be set to AUT  The  positions 0 and Manual are special settings  which  should only be operated by installers in case of errors         Any installed boiler pump will be switched  ON   The boiler circuit valve can be manually  operated    AUT  The boiler circuit operates in automatic  mode    0  Any installed boiler pump will be switched  OFF   The boiler circuit valve can be manually  operated     Current functions are displayed by LED   s     We reserve the right to make any changes due to technical modifications     Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    Buderus  11    Heating circuitand DHW module  FM441    The FM441 function module controls one heating circuit  with valve plus one DHW circuit with circulation pump     One module per control unit may be installed in any slot     The manual switches on the module are only provided  for service and maintenance functions     AUT  OI Ww  Ifthe manual switch YY  is not set to automatic   a corresponding message appears on the MEC 2 and    the fault indicator illuminates     Never use the manual switches to switch OFF the  system when you have to temporarily leave the  installation     The co
9.   The factory setting is 0   C    The setting range is  5   C to  5   C    for example Displayed room temperature  22   C    Actual room temperature  24   C    Matching temperature values      Open the cover       Simultaneously press and then release the and Calibration MEC  Room temperature    buttons     The display shows  Calibration MEC   Correction      0 0   C         Press and hold down the  10 button   The setting to be changed flashes  Calibration MEC      Turn the dial until  for example    2   C is displayed  Room temperature     Release the  1   button  Correction    The display now shows the adjusted room temperature    2 0  C  for instance   24   C        Buderus We reserve the right to make any changes due to technical modifications     58 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    24 Operating tips for cascade systems    For cascade systems or heating system with many  heating circuits  the control unit may comprise several  control units     The basic unit is always a Logamatic 4311 control unit   and the additional units are Logamatic 4312 control  units  Both control unit types are generally operated in a  similar way     Because the MEC 2 programmer can only process data  from one control unit  these must be operated  sequentially     To change to another control unit to enable that unit to  be operated  remove the MEC 2 programmer from the  former control unit and plug it into the next     The following messages are the
10.  Buderus    Boiler temp     Outdoor temp        Burner 1st stage    Hours run       USER NOTE    The consumption values are purely for  comparison  and may not be used for ac   counting purposes  The operating values of  heating circuits will only be displayed if you  have already selected the relevant heating  circuits  The consumption values will only  be displayed if you have already selected  this function     Buderus    Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006 27    12 Selecting the standard program    A standard program is a switching program with typical  switching times set up in the factory  You can select from  eight standard programs  see overview of standard  programs  page 31   The  Family  program is factory  pre set     The standard programs can be used separately for each  heating circuit  You can modify or supplement the  switching points of a standard program to create your  own individual program     If you select  New   all previously entered switching  points will be deleted  and you can arrange your own  individual program  Your heating system will operate  constantly in day mode  if neither a switching point nor a  program is entered     You may create an individual program for every heating  circuit  Your individual program will be saved and    displayed as  Own  with the  Heat  circ  no   Setting    not possible  USER NOTE    single heat circ   select    This function is not available for heating   Buderus circuit sel
11.  Issue 02 2006    21 Entering date and time     not currently available in the UK and should be switched off   The date is set at the factory     Date and time are synchronised daily via a radio signal   where available   This also automatically changes  between summer and winter  Well screened boiler  rooms may impede the reception of the radio clock  signal  which makes it necessary for you to set the date  and time manually     The MEC 2 contains a radio receiver  not currently  available in the UK and should be switched off   which  constantly monitors and corrects the time switch inside  the control unit  This means  that you need never set the  time during commissioning  after prolonged power  failure  after the heating system has been switched OFF  for longer periods on its mains electrical isolator or for  changing from summer to winter and vice versa  Please  note  this facility is subject to the availability of the radio  clock signal     For the MEC 2 remote control  the reception of the  radio clock signal is subject to place and location     Reception of the radio clock signal is indicated by the  symbol     on the display     In case of reception problems  please observe the  following       The radio reception is weaker in rooms surrounded  by steel reinforced walls  in cellars  high rise  buildings  etc         The distance from sources of interference  such as  computer monitors and TV sets  should be at least  1 1 50m         Atmospheric interference is not 
12.  changeover temperature  below  which you want to heat  In the example 18   C        Release the   7   button     Buderus    52 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    Setting   not possible  MEC heat  circ   select    Heat circ  sel     MEC heat  circ     Summer winter    MEC heat  circ     Summer winter    Summer from       We reserve the right to make any changes due to technical modifications     Setting up constant summer mode    Selecting a heating circuit    Press and hold down the button       Turn the dial until the required heating circuit is  displayed       Release the button       Press and hold down the   7   button   The heating circuit is briefly shown in the display   Then the mask with the currently set changeover  temperature will be displayed  The adjustable  temperature setting flashes       Turn the dial to a changeover temperature below  10  C       Release the   7   button   The heating system will constantly operate in  summer mode     Setting up constant winter mode    Selecting a heating circuit    Press and hold down the button       Turn the dial until the required heating circuit is  displayed        Release the button       Press and hold down the   7   button   The heating circuit is briefly shown in the display   Then the mask with the currently set changeover  temperature will be displayed  The adjustable  temperature setting flashes       Turn the dial to a changeover temperature above  30   C        Rel
13.  e Issue 02 2006 13       Strategy module FM447    The strategy module is designed to control a cascade  system and carries out special functions  e g  central  fault display messages     The strategy module is not equipped with controls     Buderus                         Fig 6 FM447    Display General fault    e g  site error  sensor error   external faults    internal wiring fault   module error  manual mode   These fault messages appear  as plain text on the   MEC 2 programmer     Indicators for burner functions    Display A Switch on one further burner stage   Display y Switch off one further burner stage   Display I 1st stage or base load of the respective boiler   burner    Display Il 2nd stage or modulation load of the    respective boiler  burner   Boiler display 1  burner 1   Boiler display 2  burner 2     Jee     Boiler display 3  burner 3     We reserve the right to make any changes due to technical modifications     14 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    6 MEC 2 programmer       Constant heating mode    Automatic heating  mode in accordance  with a time switch    Constantly reduced  heating mode    Enter weekdays    Enter holidays    Select standard display             MEC 2 programmer             qi       Common flow  45  C  Outdoor temp                                                                                   Radio clock signal     This feature does not  function in the UK and Eire  and should be switchet off   
14.  fault s        Leave the heating system switched ON  all the time     e Contact your heating installer if a fault  occurs     Buderus    Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006 5    2   For your safety    2 3 Cleaning the control unit      The control unit should only be cleaned with a damp  cloth     2 4 Disposal       Dispose of the control unit packaging in an  environmentally responsible manner       The lithium battery in the CM431 module may only be  replaced by your installer     Buderus We reserve the right to make any changes due to technical modifications   6 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    3 Tips on energy efficient heating    Buderus control units ensure optimum comfort and  many technical options  as well as energy savings and  simple operation     Observing the following tips you could save energy   money and protect the environment       Ask your installer to instruct you in the correct use of  this equipment during commissioning  If in doubt   ask       Read the operating instructions for your heating  system thoroughly       Have your system adjusted to the conditions of your  property     Have your heating system regularly serviced       During the cold season air rooms  but only for short  periods  this prevents rooms getting too cold     e Check the settings of thermostatic radiator settings in  each room       Never set the temperature of living accommodation  or domestic ho
15.  is displayed     Release the button  Timer    Program choice             Family    Buderus We reserve the right to make any changes due to technical modifications     36 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    The display shows the 1st switching point of the    selected program  i  ite Family program    Monday  at 22 00 h    Selecting and cancelling switching   points     Turn the dial to the switching point  which you want  to delete       Simultaneously press and hold down the and  buttons     Family program  Delete  The bottom line shows 8 blocks  which are deleted in Monday 22 00                second intervals from left to right  When no blocks    are left  the switching point has been deleted  ania maman    The deleting process is terminated if you release the  button before all blocks are gone        We reserve the right to make any changes due to technical modifications  Buderus  Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006 37    Deleting a heating phase    Generally  a heating phase comprises two switching  points  One switching point can only be moved to the  next switching points  A heating phase will be deleted     as soon as its switching points are set to the same time     Example     You have selected the standard  Noon  program for  your heating system and want to delete the heating  phase 11 30 to 13 00 h on Mondays to create a heating  break from 08 00 to 17 00 h     Select a heating circui
16.  the system       Read these operating instructions carefully       Only enter or change the operating settings specified    WARNING        We reserve the right to make any changes due to technical modifications     in these instructions  Other inputs affect the heating  system control programs and can lead to system  malfunctions     Maintenance  repairs and fault diagnosis should only    be carried out by authorised and qualified personnel     RISK TO LIFE    from electric shock   Never open the control unit       in an emergency isolate the heating  system from the mains supply using the  emergency stop switch located outside  the boiler room or by removing the main  fuse       Arrange for your installer to rectify  immediately any faults in your heating  system     WARNING     CAUTION     RISK OF SCALDING    For thermal disinfection purposes  the  entire DHW system is set in the factory to  heat up to 70  C  activated  Tuesday night  at 01 00         If required  e g  shift work   your  heating installer can alter the activation  time       If the DHW circuit of your heating  system is not equipped with a  thermostatic valve  do not open any hot  water tap without mixing in some cold  water       As there is a risk of scalding at  temperatures above approximately  60  C  ask your heating installer what  temperature the hot water has been set  to     SYSTEM DAMAGE    through frost    The heating system can freeze up if it is  out of use  e g  through a shutdown  because of
17.  would like to heat less whilst you are away       Press and hold down the button  and  simultaneously open the cover of the MEC 2 remote  control     Pause function      Turn the dial until the required number of hours is  displayed       Release the button     The pause function starts immediately  After three  hours  the heating system returns to the automatic  heating mode     Pause function      Call up the pause function and turn the dial to   O hours   if you want to cancel the pause function     We reserve the right to make any changes due to technical modifications     Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006          O hours    3 hours    Buderus  47    18 Holiday program    Using the holiday program you can heat at a lower room  temperature  if you are away for longer periods of time     Select the required heating circuit before calling up the  holiday program  You may select either an individual    heating circuit or all circuits allocated to the MEC 2  All Holiday prog   heating circuits  for which no holiday program was set not possible  up  continue to work normally  F   P X MEC heat  circ     USER NOTE select        MEC heating circuits  see Chapter 8     Buderus page 1 9        Calling up a holiday program    Example     If you are on holiday for the next five days and you want  to heat less during that time  e g  heating circuit 2 with a  reduced room temperature of 12   C     As the holiday program activates immediately af
18. 0  to 13 00 hrs     Select a heating circuit    Open the cover   Press and hold down the button     Turn the dial until  Heating circ  2  is displayed     Release the button     Program selection      Press and hold down the button     The display briefly shows the heating circuit and then the  last set program for this heating circuit  The program  description flashes       Release the button     The display shows the 1st switching point of the  selected program     Buderus       Day mode  e g  21   C   Night mode   Bi  5 30 23 00    Day mode  e g  21   C     Night mode       5 30 10 00 13 00 23 00       Fig 9 Entering switching points    Heat circ  sel     Heating circ  2    Timer    Heating circ  2       Timer    Program choice  Family    Family program    Monday  at 05 30 hrs       We reserve the right to make any changes due to technical modifications     34 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006       Entering the first switching point      Turn the dial anti clockwise  until the blank mask   New Switch Point  is displayed        Press and hold down the button     Turn the dial to the required day     You can select days individually or in blocks     Monday     Thursday  Monday   Friday  Saturday     Sunday  Monday     Sunday    Release the button   Press and hold down the button     Turn the dial until the required time is displayed     Release the button       Press and hold down the   1   button       Turn the dial anti clockwise  
19. 6303 1852     02 2006 GB For the user          Operating instructions    Logamatic 4311 4312 control unit             T   gt    ref  o  Q   gt    m    Please read thoroughly before use        This unit meets all requirements of relevant  European standards directives and  guidelines     Its conformity has been verified  All  associated documents and the original  Declaration of Conformity are available from  Buderus     About these instructions    These operating instructions contain important  information for the safe and correct operation of the  Logamatic 4311 and 4312 control units     Subject to technical modifications     Constant development may lead to minor deviations in  the illustrations  procedures and specifications  described shown     Updating your documentation    Please let us know if you have any suggestions which  would improve our documentation or if you have noticed  any errors     Buderus We reserve the right to make any changes due to technical modifications   2 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    1 IPWGOQUCHON   64465 ham ocddedentad bay KAN weer de eA eee Thee ane 4  2 For your safety so a ook e de ES Heh ee bok KGG SRS Se eee ES 5  3 Tips on energy efficient heating              2 000022 eee eee 7       CONUGIS  AA 8  5 Modules and their functions            0000 cee ee 9  6 MEC 2 programmer    Za Ka KAG na ade e aden ber eens necue KNA WG NG 15  7 Getting started 2644555444 4455 85654608 Ch GES ewes NAA NAA 
20. 8  l  Initial start up    2    ee ee 16  Inserted modules                 4  8  Interrupting a holiday program             50  M  Maintenance message                 60  Matching the room temperature sensor        58  Modules         0a a  9  N  New DHW program               2 4  44  Night room temperature              17  22  O  Operating conditions                  18  Operating settings                 27  65  Buderus    P  Party function       0    46  Pause function                    47  Program selection                    42  R  Radio clock signal                  55  ReloadingDHW                   23  Room temperature                  17  S  Select a heating circuit                42  Selecting the standard program           28  Setting the changeover temperature         52  Settingthedate                   56  Setting the room temperature           16  17  Setting up summer mode               53  Setting wintermode                 53  Setup report              0020048 65  Shuttingdown               2 2 4   16  Starting the DHW circulation pump          23  Strategy module                   14  Summary of standard programs           31  Summer mode                    51  Summer winter changeover             51  Switching OFF DHW heating             24  Switching OFF the DHW circulation pump      25  T  Thermal disinfection                 26    We reserve the right to make any changes due to technical modifications     66 Operating instructions Logamatic 4311 4312 co
21. C or your fax machine if you wish     USER NOTE maint  after   The automatic maintenance message re  Hours run  Buderus  mains active until your local heating instal  required   ler resets it        Buderus We reserve the right to make any changes due to technical modifications   60 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    26 Troubleshooting    Faults and fault displays    Have your heating engineer remedy all faults  immediately     Report the fault initially by telephone to your heating  installer  Set the control unit switch and those on the  modules in accordance with chapter  Emergency  operation   Heating system faults are shown on the  display     The following faults are shown       Burner fault boiler 1   3     Boiler temperature sensor       Outd  Temp  sensor     Heating circuit flow sensor  Heating circuit 1   8  if installed        DHW temperature sensor     Boiler stays cold       DHW remains cold     Remote control no communication with  heating circuit 1   8  if installed      Thermal disinfection     Auxiliary temperature sensor     Heating circuit 1   8  if installed  pump fault       DHW pump fault       DHW inert anode fault     Safety equipment fault     No connection to the bus system     Address used more than once     System flow sensor     System return sensor     Boiler  1   3  not connected     External boiler fault     Flue gas sensor fault     Flue gas temperature exceeded     Address conflict slot 1   4  if in
22. I tf  ty fy    USER NOTE       You can interrupt the deleting process be    Buderus  fore all of the block have disappeared by  releasing the button or by turning the  dial back  The switching points will then be  retained     The heating phase with both its switching points 11 30  and 13 00 will be deleted  when all the blocks have  disappeared  The new program with then be saved with  a continuous heating phase as  Own program 2      Return to the standard display    Press the  J  button        We reserve the right to make any changes due to technical modifications  Buderus    Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006 39    Joining heating phases    Set the  OFF  switching point of the first period to the   ON  switching point of the next switching period to join  2 heating phases     Example     Starting from the standard  Noon  program for heating  circuit 2  you want to join the Monday heating phase  from 11 30 until 13 00 h to the heating phase 17 00 to  22 00 h  In other words you want to heat continually from  11 30 until 22 00 hrs     Select a heating circuit      Open the cover     Press and hold down the button        Turn the dial until  Heating circ  2  is displayed        Release the button     Program selection      Press and hold down the button   The display briefly shows the heating circuit and then  the last set program for this heating circuit  The  program description flashes       Turn the dial until the program selection
23. M426  Additional STB                                     Table 1 Modules and their functions      These units are not currently available in the UK and Eire  please  contact Buderus    O   Basic equipment   X Optional equipment     Combination installation not possible    USER NOTE    The menus displayed on the MEC 2 pro   Buderus  grammer depend on which modules are fit   ted and on their respective settings     We reserve the right to make any changes due to technical modifications  Buderus    Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006 9    Burner and boiler circuit module  ZM432    The ZM 432 module is part of the basic equipment level  of Logamatic 4311 and Logamatic 4312 control units   The manual switches on the module are only provided  for service and maintenance functions     If the manual switches are not set to Auto  a  corresponding message appears on the MEC 2  programmer and the fault indicator illuminates     Never use the manual switches to switch OFF the  system when you have to temporarily leave the  installation  The control functions continue to operate in  manual mode     Burner function     Flue gas test  button  x  for flue gas test    Press and hold  flue gas test  button for a few seconds     The central heating control operates for 30 minutes with  a higher flow temperature  During the flue gas test  the  fault display and for summer mode will flash     Press the emissions test switch again to cancel the flue  gas test
24. On all weekdays DHW should be heated from 06 30 h  until 09 00 h     Select a heating circuit      Open the hinged cover     Press and hold down the button       Turn the dial until  DHW  is shown        Release the button     Calling up a program    Press and hold down the button       The menu item  Program choice  appears together  with the pre set DHW program  by heat  circs        Turn the dial to  new        Release the button     To enter the new switching point proceed as for   Entering the first switching point   page 35     Buderus  44       Factory setting  DHW   automatic    HK1       HK2                   WW  5 00 6 00 7 00 8 00 9 00 10 00 11 00    Example  DHW   new program       HK1       HK2       WW  5 00 6 00 7 00 8 00 9 00 10 00 11 00                      Fig  12 Entering a new DHW program    Heat circ  sel     DHW    Timer    Program choice  by heat  circs       Timer    Program choice       We reserve the right to make any changes due to technical modifications     Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    16 Entering anew DHW secondary circulation pump program    In the menu item  Program selection  you can  determine  whether the DHW circulation pump should  be used automatically subject to the heating circuits   Program selection acc  to heating circuits  or whether  an individual switching program  Own DHW program  selection  should be used  The factory setting is   Program choice by heat  circs   With the factory s
25. ability and the  thermal insulation of the building  If the  Time del   outdoor temp   exceeds the factory set changeover  threshold of 17   C  Summer mode is indicated in the  display with the symbol ji DHW heating remains active   Press the button  if you wish to heat for a short  time in summer mode     The heating system returns to automatic summer mode  if you press the button     Winter mode    Central heating and DHW heating are active  if the  Time  del  outdoor temp   falls below the factory set  changeover threshold of 17   C     We reserve the right to make any changes due to technical modifications     Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    Buderus  51    Automatic changeover between  summer and winter   You must select the required heating circuit before  calling up the summer winter changeover  You may    select either an individual heating circuit or all circuits  allocated to the MEC 2     USER NOTE        MEC heating circuits  see Chapter 8     Buderus page 1 9     Selecting a heating circuit    Press and hold down the button       Turn the dial until the required heating circuit is  displayed  Example  MEC heat  circ        Release the button     Setting the changeover temperature       Press and hold down the   7   button   The heating circuit is briefly shown in the display     Then the mask with the currently set changeover  temperature will be displayed  The adjustable  temperature flashes       Turn the dial to the
26. as strong at night  than during the day  which is why reception is almost  always possible  where generally available      We reserve the right to make any changes due to technical modifications     Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    Buderus  55    Setting the date      Press and hold down the button  The day  flashes in the date display     Set date      Set the day by turning the dial  The day of the week  is automatically matched       Release and press and hold down the button  again  Wednesday  Only the month flashes in the date display       Set the month with the dial       Release and press and hold down the button  again  The year indication flashes       Set the year with the dial  Using      I  you can 07 01 1997  terminate the date input at any time  The date will be  saved with the changes made thus far     01 01 1997       Tuesday       Set date  07 01 1997    Tuesday    Set the time      Press and hold down the button  The hours  and minutes flash     Set hour      You change the time in minute steps by turning the  dial       Release the button  The time has now been  saved     15 52 58       Buderus We reserve the right to make any changes due to technical modifications     56 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    22 Flue gas test       USER NOTE    Module ZM432    Observe the relevant national  Buderus  requirements regarding limiting the flue  gas losses of your heating syste
27. e entered  if  you are heating DHW according to your own  switching program  time switch   Program choice  own DHW    The circulation pump is switched OFF  automatically during the DHW holiday program     You can cancel your holiday program at any time by  calling it up and setting the number of days away to 0     We reserve the right to make any changes due to technical modifications     Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006       Buderus  49    Interrupting a holiday program    You may interrupt your holiday program at any time  using the or button and heat according to  the set day and night temperatures  Room set       Press the button  Permanent day  21  C    Press the button  Permanent night   Continuing a holiday program    Permanent day         Press the button     Now the heating system operates in holiday mode     Buderus We reserve the right to make any changes due to technical modifications     50 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    19 Setting summer winter changeover    Apart from the outside temperature  Logamatic 4311  and Logamatic 4312 control units consider the ability to  store heat and the thermal insulation of the building in  question  in the following the  Time del  outdoor temp     and automatically change over  with time delay   between summer and winter mode     Summer mode    The heating operation will be switched OFF with a delay   which depends on the heat retaining cap
28. ease the   7   button     Your heating system will constantly operate in winter  mode     We reserve the right to make any changes due to technical modifications     Heat circ  sel     MEC heat  circ     Summer winter    Perm  summer    Heat circ  sel     MEC heat  circ     Summer winter    Perm  winter       Buderus    Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    53    20 Changing the standard display    The factory set standard display shows the boiler  temperature  if MEC 2 has been plugged into the control  unit     The actual room temperature will be displayed if a  MEC 2 remote control has been mounted in the wall  mounting holder     The outside temperature is displayed on the bottom line     Instead of outside temperature you can select one of the  following displays       Boiler temperature  if MEC 2 is fitted to the wall   mounting frame        Boiler temp       Flue gas temperature    DHW temperature Outdoor temp     Outdoor temp     Time    Date  Room measured  22 5   C  Outdoor temp   0  C  Example     The date should be displayed on the bottom line       Press and hold down the button   The heading for the display setting flashes     Boiler temp        Turn the dial until  Date  appears in the display       Release the button  Date    The changes are saved     45   C    20 12 1996       Buderus We reserve the right to make any changes due to technical modifications   54 Operating instructions Logamatic 4311 4312 control devices e
29. ection  MEC heat  circ    An  individual heating circuit with  Heat  circ   and heat  circ  no  or  Name heat  circ  and  heat  circ  no  should be selected        Buderus We reserve the right to make any changes due to technical modifications     28 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    Selecting a standard program    Example  Heating circuit 2 should operate in  accordance with the  Late evening  standard program       Open the cover       Press and hold down the button  if  Heating Heat circ  sel   circ  2  is not displayed       Turn the dial until  Heating circ  2  is displayed       Release the button     Heating circ  2      Press and hold down the button   Heating    circ  2  then briefly appears on the display  Tier    Heating circ  2    Then the mask with  Program choice  and the program     which was last selected  appears     pp Timer    Example   Family   The program description flashes     Program choice    Family       We reserve the right to make any changes due to technical modifications  Buderus  Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006 29       Turn the dial until the required standard program is    displayed  Example   Late evening  Timer    Program choice  Late evening      Release the button   The display shows the program description and the  first switching point     L  Evening prog     Turning the dial enables you to see in sequence and  if  necessary  modify the switching point
30. et  program  the DHW circulation pump automatically starts  30 minutes before the earliest switching of any heating  circuit in this control unit  and ends when the last heating  circuit is shut down     If your DHW circulation pump should not operate  according to the automatic program  you can enter a  new  individual DHW circulation pump program     Example     On all weekdays the circulation pump should run from  06 30 h until 09 00 h     Selecting a heating circuit    Open the cover   Press and hold down the button   Turn the dial until  DHW circulat   is displayed     Release the button     Calling up a program      Press and hold down the button       The menu item  Program choice  appears together  with the pre set DHW circulation pump program  by  heat  circs        Turn the dial to  new       Release the button     To enter the new switching point proceed as for   Entering the first switching point   page 35     We reserve the right to make any changes due to technical modifications           Factory setting  DHW CP   automatic    HK1    HK2       ZP                5 00 6 00 7 00 8 00 9 00 10 00 11 00    Example  DHW secondary circulation pumps     program    HK1       HK2       ZP             5 00 6 00 7 00 8 00 9 00 10 00 11 00          Fig  13 Entering a new circulation pump program    Heat circ  sel     DHW circulat     Timer    Program choice  by heat  circs       Timer    Program choice       Buderus    Operating instructions Logamatic 4311 4312 control device
31. gamatic 4312 control units  offer the following functions  subject to the function  modules which have been fitted       10 channel timer with weekly program      Automatic time adjustment from a radio clock signal   This feature does not function in the UK and Eire  and should be switched off       Automatic adjustments between summer and winter    Domestic Hot Water  DHW  production 30 minutes  before heating operation    Domestic hot water priority  Holiday program    Frost protection    8 standard programs for selection  You can also  create your own personal program  if none of the  above programs meet your requirements     Run on time for heating circuit pump and DHW  cylinder loading pump 3 minutes  subject to  operating conditions    Protection against condensate  Flue gas test  Automatic adoption of heating curve    Self learning start up and switch off optimisation    Selection between external and room temperature  control    We reserve the right to make any changes due to technical modifications     4 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    2    2     For your safety    1 Correct use    The Logamatic 4311 and 4312 control units are only  intended to control heating systems in lager houses   public and commercial properties     2 2 Please observe these notes    Only operate the control units as intended and when  they are in perfect working order     Arrange for your heating engineer to instruct you in  the correct operation of
32. ha AeS 16  8 Setting the room temperature            00  e eee eee 19  9 DHW  Domestic Hot Water  control                    0000 eee ee 23  10 DHW circulation pump control                     000002 25  11 Calling up displays                 0 020200 cee 27  12 Selecting the standard program            eee 28  13 Changing a program           00 e eee 32  14 Creating a new heating program            a  42  15 Entering a new DHW program           a  44  16 Entering a new DHW secondary circulation pump program             45  17 Party Pause function            0 000 nes 46  18 Holiday program     2a a KAKA LAK EN eee LA beh eee ARSE KPA WA KA 48  19 Setting summer winter changeover             a  51  20 Changing the standard display              0 00 e eee eens 54  21 Entering date and time           00 022 ee 55  22 Flue gas test  ic GAAN GB eed es debe KA e EBA AN os ne GWA ES be 57  23 Matching the room temperature sensor                    2  0 5 58  24 Operating tips for cascade systems                    00000 eee 59  25 Automatic maintenance message               seers 60  26 TFOUDIESNOOTING   224 4244 645 Gad sds Gee eer bee UNA ete ehe ees eee LG 61  27 Emergency mode ss a kA KK KAKAIN DAL seb eee BAHA eesweeasawids 63  28 Setup report 2 2 342 oie ae oe AA be KNA AKA KTA NG NGA KALAN 65  29  Keyword INdEeX    0 da ak a KANA AKA NAA BA KIA BAN aed ANY NA LANA NA KY 66  We reserve the right to make any changes due to technical modifications  Buderus    Operating instruct
33. he button      Turn the dial until  Heating circ  2  is displayed   e    Release the button     Program selection      Press and hold down the button     The display briefly shows the heating circuit and then the  last set program for this heating circuit  The program  description flashes       Turn the dial to  Family       Release the button    Then the standard  Family  program for heating circuit 2  is active again    Return to the standard display     Press the  S  button        USER NOTE    The program you have created will be sa   Buderus  ved as  Own program 2  and may be  called up at any time     We reserve the right to make any changes due to technical modifications     Heat circ  sel     Heating circ  2    Timer    Heating circ  2       Timer    Program choice  Own 2    Timer    Program choice    Family       Buderus    Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    43    15 Entering a new DHW program    In the menu item  Program choice  you can determine   whether the DHW heating should be implemented  automatically  subject to the heating circuits or whether  an individual switching program should be used  The  factory setting is  Program choice by heat  circs   With  the factory set program  DHW is heated up  automatically 30 minutes before the earliest switching  point of any heating circuit     If your DHW heating should not operate according to the  automatic program  you can enter a new  individual  DHW program    Example     
34. ions Logamatic 4311 4312 control devices e Issue 02 2006 3    1 Introduction    Logamatic 4311 and Logamatic 4312 control units are  designed for modular applications and will  subject to  type and extent of the system  be equipped with up to  four additional function modules    The modular design enables  with a full compliment of  equipment  the connection of up to eight heating circuits  with mixing valves     The modules include controls for manual operation and  operating displays     Logamatic 4311 and Logamatic 4312 has a safety  function built in to the unit     The basic equipment level of Logamatic 4311  comprises       Weather compensated control of one boiler    Use of single stage  two stage or modulating burner    Boiler control unit      MEC 2 programmer    The basic equipment level of Logamatic 4312  comprises       Weather compensated control of one boiler     Use of single stage  two stage or modulating burner    Boiler control unit   e Boiler display for indicating the boiler temperature  The MEC 2 programmer is the central control unit     Functions and operating setting are shown in the  display     Buderus    The buttons enable functions to be called up  If you push  a button and hold it down  you can change the  respective setting using the dial     The new value will be accepted and stored after you  release the button     The unit automatically returns to the standard display  if  no entry is detected within approx  5 min     The Logamatic 4311 and Lo
35. limiter service units mode  and MEC 2 Burner  Fig  1 Controls  Slot  1 2 A B 3 4             Q           o Wo   e                                                                                 Module     FM442    FM442    Heating circuit 3  heating circuit 4    Heating circuit 1  heating circuit 2       ZM432       Boiler circuit  burner    l  Programmer       FM441 FM447    Strategy  for   cascade systems    Heating circuit 5   Domestic hot water  Circulation pump or heating  circuit 5   heating circuit 6    if module FM442 is in slot 3     MEC 2          Fig 2 Module configuration    Buderus  8    We reserve the right to make any changes due to technical modifications     Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006       5 Modules and their functions                         All modules which are or can be fitted into your The following pages contain information as to which  Logamatic 4311 4312 control unit are shown here  modules you can use   Logamatic  4311 4312  MEC 2 programmer O x  programmer module CM431 o o  Central module ZM432  3 ae   O O  Burner   boiler circuit functions  Function module FM441 x xX  1 heating circuit   1 DHW circuit  Function module FM442 x x    2 heating circuits  Module Function modue Bukas  x x  Solar heating circuit      Function module FM445  LAP LSP  loading system       Function module FM446  Interface EIB      Function module FM447  Strategy  Function module FM448  Central fault message  Additional module Z
36. m     RISK OF SCALDING  During the flue gas test  the water can  WARNING  reach a temperature of over 60   C  This  creates a risk of scalding at the taps                                  Only draw off mixed hot and cold water  during or just after a flue gas test   Note that when single lever mixing taps  are in their usual position  the water that  comes out of the tap will be too hot       Never draw off only hot water when  using two handle mixing taps  Always  mix with cold water     K3 Emissions test switch on the ZM 432 module                   Fig  14 ZM432    The control unit must be switched ON     Press the emissions test switch for several seconds to Flue g  test act   start the flue gas test     The flue gas test lasts 30 minutes and will be indicated Boiler temp   on the display  During the flue gas test  the fault display  and   T   for summer mode will flash  The control unit  automatically reverts to its previous operating mode  when the test has been completed        The flue gas test is cancelled by pressing Fi again     We reserve the right to make any changes due to technical modifications  Buderus    Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006 57       23 Matching the room temperature sensor    If the room temperature shown on the display varies  from the actual temperature measured with a  thermometer  the display value can be adjusted using   Calibration MEC      Calibration effects a parallel offset of the heating curve 
37. n        Turn the dial until the required day room temperature Room set  is displayed        Release the button   To let the heating system operate in automatic mode     Press the button     21  C    Permanent day       Night room temperature    First change to night mode  if you want to change the  night room temperature  whilst your heating system is  still operating in day mode     The night temperature is subject to the  Set back type   selected at the service level     For the setback types  Room setback  and  Outdoor  setback   the system only heats up to the set night room  temperature  if the actual temperature falls below the set  night room temperature limit     No night room temperature can be selected for the  Cut   off  setback type     The system heats to the set night room temperature  if  the  Reduced  setback type has been selected       Press and hold down the button       Turn the dial until the required night room Room set  temperature is displayed       Release the button   To let the heating system operate in automatic mode     Press the button     17  C    Perm  night       Buderus We reserve the right to make any changes due to technical modifications     20 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    Setting the room temperature for  heating circuits without remote  control   For all heating circuits  to which no remote control was    allocated during the installation  the room temperature is  set as follows       Ope
38. n displayed     MEC is  initialised    Get data      Press the button  if you want the heating  system data to be adopted from the control unit     Send data      Press the button  if you would like to operate  the heating system with modified data from the  MEC 2 programmer     Of course  it is also possible to equip each control unit of  a cascade system with its own MEC 2 programmer  In Connection with  that case  the MEC 2 will not need to be re plugged and ctrl panel with   Get send data  is superfluous  Each control unit is   controlled separately by its own MEC 2  see the address 01  operating instructions  established    We reserve the right to make any changes due to technical modifications     Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006       Buderus  59    25 Automatic maintenance message    If your heating engineer has  with your agreement    activated the  Automatic maintenance message   the  maintenance message  Note maintenance message  is Note  displayed at the predetermined time  on a particular date    or after so many operating hours   maint  message         Open the cover       Turn the dial  maint  after  You will see either  Maintenance by date  or     Maintenance according to operating hours   Date      Notify your heating engineer so they can schedule required    the inspection and maintenance work     The Logamatic telecontrol system enables the  maintenance message to be transmitted automatically  to your mobile  your P
39. n the cover     Press and hold down the button       Turn the dial until the required heating circuit is  displayed       Release the button     Setting the day room temperature      Press and hold down the button       Turn the dial until the required day room temperature  is displayed        Release the button   USER NOTE    You cannot select a room temperature for   Buderus  heating circuits set to  Permanent   such  as  for example  air conditioning or swim   ming pool heating systems     We reserve the right to make any changes due to technical modifications     Heat  circ  sel     Heating circ  2    Room set       21  C    Permanent day       Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    Buderus  21    Setting the night room temperature    First change to night mode  if you want to change the  night room temperature  whilst your heating system is  still operating in day mode  The night room temperature  is subject to the  Set back type  selected at the service  level  For the setback types  Room setback  and   Outdoor setback   the system only heats up to the set  night room temperature  if the actual temperature falls  below the set night room temperature limit     No night room temperature can be selected for the  Cut   off  setback type     The system heats permanently to the set night room  temperature  if the  Reduced  setback type has been  selected     The heating circuit pump remains OFF  until the actual  temperature falls below 
40. ntrol devices e Issue 02 2006    We reserve the right to make any changes due to technical modifications  Buderus  Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006 67    Buderus       Buderus BBT Thermotechnik GmbH   Cotswold Way  Warndon  Worcester WR4 9SW D 35573 Wetzlar  Tel   01905 752794  Fax  01905 753130 www heiztechnik buderus de  www buderus commercial co uk info heiztechnik buderus de    In the UK  Buderus is a trading name of  BBT Thermotechnology Ltd     
41. ntrol functions continue to operate in manual  mode     Heating circuit function    AUT  0an     Manual switch for heating circuit nom       The heating circuit pump is switched ON   The heating circuit valve can be manually  operated    AUT  The heating circuit operates in automatic  mode    0  Only the heating circuit pump is switched  OFF  The control functions continue to  operate    DHW function   a     0   Manual switch for DHW heating oO        The DHW loading pump is switched ON    AUT  The DHW circuit operates in automatic  mode    0  Only the DHW loading pump is switched  OFF  The control functions continue to  operate    Buderus                                        Fig 4 FM441    Display    General fault   e g  site error  sensor error   external faults    internal wiring fault   module error  manual mode   These fault messages appear  as plain text on the   MEC 2 programmer     Heating circuit function indicators    Display  Display      Display A    Heating circuit in summer mode  Heating circuit pump active   3 way mixing valve opens  Display y 3 way mixing valve closes  Indicators for DHW functions   Display Z5  Display   L DHW Cylinder loading pump active    Display  1     Display   Z DHW circulation pump active    DHW stays cold    Thermal disinfection active  Risk of scalding     We reserve the right to make any changes due to technical modifications     12 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006       Heating circuit mod
42. perature    Press and hold down the button       Turn the dial until the required DHW temperature is  displayed       Release the button     Buderus    Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006 17    Setting the summer   winter  changeover    You must select the required heating circuit before  calling up the summer winter changeover  You may  select either an individual heating circuit or all circuits  allocated to the MEC 2       Press and hold down the button       Turn the dial until the required heating circuit is  displayed        Release the button        Press and hold down the   7   button       Turn the dial until the outside temperature is  displayed  below which heating should commence        Release the   7   button   Change operating condition    With the cover closed  the operating conditions of those  heating circuits are changed  which have been allocated  to the MEC 2       Press and release the button with the cover  closed   The system provides constant heat at the set day  room temperature       Press and release the button with the cover  closed   The system operates constantly in set back heating  mode       Press and release the button with the cover  closed     The system operates automatically according to the set  switching program     Buderus We reserve the right to make any changes due to technical modifications     18 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    8 Setting the room 
43. required day room temperature  is displayed        Press the button     Night room temperature      Press and release the button whilst the cover  is closed       Turn the dial until the required night setback room  temperature is displayed        Press the button     We reserve the right to make any changes due to technical modifications     16 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    Setting the room temperature for  heating circuits without an individual  remote control unit    Heating circuits are not allocated to the MEC 2     Setting the day room temperature    Press and hold down the button       Turn the dial until the required heating circuit is  displayed       Release the button     Press and hold down the button       Turn the dial until the required day room temperature    is displayed        Release the button        Press the button     Setting the night room temperature    Press and hold down the button       Turn the dial until the required heating circuit is  displayed       Release the button     Press and hold down the button       Turn the dial until the required night setback room  temperature is displayed       Release the button        Press the button     Setting the room temperature for  heating circuits equipped with  different remote control units    See separate operating instructions for the relevant  remote control     We reserve the right to make any changes due to technical modifications     Set the DHW tem
44. ress and hold down the  button     DHW circulat       Turn the dial until  DHW circulat   is displayed       Release the button     Press the button     The circulation pump is switched OFF   The standard display re appears after 3 seconds        We reserve the right to make any changes due to technical modifications  Buderus    Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006 25    Setting up automatic mode      Open the cover  then press and hold down the    button   sue DHW circulat       Turn the dial until  DHW circulat   is displayed        Release the button       Press the button   The DHW circulation pump operates in automatic  mode   The standard display re appears after 3 seconds     Automatic       In automatic mode the DHW circulation pump runs in  cyclic intervals     The factory setting is set to twice ON for 3 minutes each  per hour     Your local heating installer may change the cycle times  at the service level     Thermal disinfection    As part of thermal disinfection  the DHW is heated once  a week to a temperature required to kill off legionnaires   bacteria     The DHW cylinder loading pump and the DHW  circulation pump run constantly during the  pasteurisation process     RISK OF SCALDING  by hot water in the DHW circuit of the hea     WARNING  ting system if it is not equipped with a ther   mostatic mixer       During and shortly after disinfection  do  not open any hot water tap without mi   xing in some cold water     Buder
45. s e Issue 02 2006 45    17 Party Pause function    Party function    This function only applies to heating circuits  to which  the MEC 2 has been allocated as remote control unit     MEC heat  circ     All heating circuits without MEC 2  operate normally  Please enter  how long the heating   system should only operate with the pre set day room  temperature     Example     You have a party and want to heat for the next four hours  to the pre set day room temperature        Press and hold down the button  and  simultaneously open the cover of the MEC 2 remote  control     Party function    O hours         Turn the dial until the required number of hours is  displayed        Release the  3575 button     The party function starts immediately  After four hours   the heating system returns to the automatic heating  mode     Party function    4 hours      Call up the party function and turn the dial to   O hours  if you want to cancel the party function        Buderus We reserve the right to make any changes due to technical modifications   46 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    Pause function    This function only applies to heating circuits  to which  the MEC 2 has been allocated as remote control unit    MEC heat  circ     All heating circuits without MEC 2  operate normally  Enter how long the heating system  should only operate with the pre set night room  temperature     Example     You are about to leave your home for three hours and 
46. s of the program  Monday    For changing switching points  see chapter  Modifying at 18 30 hrs    the standard program         Return to the standard display    Press the  J  button        The heating system now operates with your individual   Late evening  program for heating circuit 2     When selecting a standard program for other heating  circuits  proceed as with the example shown above     Buderus We reserve the right to make any changes due to technical modifications     30 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    Summary of standard programs    You may select from seven further standard programs   if the  Family  standard program does not meet your  heating requirements                                Day mode Day mode Day mode  Program name Day ON OFF ON OFF ON OFF  Family Mo Th 5 30 22 00  Fr 5 30 23 00  Sa 6 30 23 30  Su 7 00 22 00  Early morning Mo Th 4 30 22 00  Early start Fr 4 30 23 00  Sa 6 30 23 30  Su 7 00 22 00  Late evening Mo Fr 6 30 23 00  Late shift Sa 6 30 23 30  Su 7 00 23 00  Morning Mo Th 5 30 8 30 12 00 22 00  Part time work in the morning Fr 5 30 8 30 12 00 23 00  Sa 6 30 23 30  Su 7 00 22 00  Afternoon Mo Th 6 00 11 30 16 00 22 00  Part time work in the Fr 6 00 11 30 15 00 23 00  afternoon Sa 6 30 23 30  Su 7 00 22 00  Noon Mo Th 6 00 8 00 11 30 13 00 17 00 22 00  Midday at home Fr 6 00 8 00 11 30 23 00  Sa 6 00 23 00  Su 7 00 22 00  Single Mo Th 6 00 8 00 16 00 22 00  Fr 6 00 8 00 15 00 23 00  Sa 7 00 23 30  S
47. stalled        Incorrect module slot 1   4  if installed        Unknown module slot 1   4  if installed        Function module not connected     No master control unit installed      Solar cylinder X in manual mode   not available in the UK       Heating circuit X in manual mode      DHW in manual mode     Boiler circuit in manual mode       Burner in manual mode    We reserve the right to make any changes due to technical modifications     Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    Buderus  61    Fault finding       Message    Effect    Remedy       Burner fault    Central heating stays cold    Reset the burner as described in the boiler or burner documentation        Boiler stays cold    Central heating may stay cold     Check whether the thermostat is set to AUT    Check whether fuel is available    If unsuccessful    Set the burner emergency operation switch on the control unit to manual   Set the burner manual switch on the ZM 432 module to max I    Il  and set the  boiler water temperature using the boiler thermostat    Notify your heating engineer        The DHW  temperature does not  rise    DHW may stay too cold  but  not necessarily     Check whether the thermostat is set to AUT    If unsuccessful    Position the DHW and heating circuit manual switch on the FM 441 module  to manual    Notify your heating engineer        Safety chain activated    Central heating stays cold    Check whether the boiler is completely filled with water 
48. t      Open the cover     Press and hold down the button       Turn the dial until  Heating circ  2  is displayed        Release the button     Program selection      Press and hold down the button   The display briefly shows the heating circuit and then  the last set program for this heating circuit  The  program description flashes       Turn the dial until the program selection  Noon   appears       Release the button   The display shows the 1st switching point of the  selected program     Buderus          Standard  Noon  program   Day mode   Night   mode 6 00 8 00 11 30 13 00 17 00 22 00    New program  Own program 2        gt     Day mode  turn to 13 00  Night  mode 6 00 8 00 17 00 22 00       Fig  10 Deleting a heating phase    Heat circ  sel     Heating circ  2    Timer    Heating circ  2       Timer    Program choice    Midday program    Monday  at 06 00       We reserve the right to make any changes due to technical modifications     38 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006       Selecting and deleting a heating  phase      Turn the dial until the switching point is displayed   which you want to delete     Midday program    Monday  at 11 30 h      Press and hold down the button       Turn the dial to the next switching point of this Switch  periods  heating phase  In this example  13 00   At 13 00 h  the display changes to  Switch  periods is  deleted   The blocks on the bottom line are deleted is deleted     from left to right  L
49. t water higher than necessary     We reserve the right to make any changes due to technical modifications     Do the pre set switching times  day and night setback  operation  for central heating and domestic hot water  heating  meet your life style requirements     Adjust the standard program to meet your  requirements     Utilise the setting options to change over between  summer and winter     Avoid making frequent changes to the temperature  settings for accommodation and domestic hot water  heating     All temperature adjustments take time to take effect   Only change any adjustments you have made the  next day  if your previous modifications have failed to  provide the desired result     A pleasant atmosphere not only depends on the  room temperature  but also the relative humidity  the  drier a room  the cooler it feels  You can improve the  relative humidity with houseplants     Buderus    Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006 7    4 Controls    The Logamatic 4312 control unit is generally operated in the same way as the Logamatic 4311 control unit   The following therefore makes no explicit reference to Logamatic 4312              Q        o Bo  0  Bo     o  AO of    v   v  yar    Kio  A    max  H                                                                                                     amp       O       H  Safety Boiler water F1 F2 Connection Switch for ON OFF switch  temperature thermostat Fuses for external emergency  
50. tch thermostaton   FM 441 2  Logamatic ZM 432 boiler   FM 441 DHW   Logamatic heating circuit  4311 circuit module 4311 module   module   Central heating failed  1  AUT AUT 60 90   C W   Heating circuits failed   DHW heating failed heating circuits are  1  AUT W 60   C AUT   supplied normally   Boiler operation failed  1  W AUT 90   C AUT                            Table 4 Settings for an emergency operation    Manually de couple the heating circuit mixing valve and  position towards  Open  or  Close   safeguard against  return   until the required room temperature has been  achieved  Never close the heating circuit mixer to  prevent the DHW freezing inside the heating system     In case of faults  immediately notify your local heating  installer who will provide a professional service  It would  be helpful for your heating engineer if you could provide  him with precise details regarding the fault condition     We reserve the right to make any changes due to technical modifications     Buderus  64 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    28 Setup report    Operating values                                     Operating values Input range Factory seiting Setting  Factory set programs Family Family  Early morning  Late Evening  Morning  Afternoon  Midday  Single  Senior  New  DHW 30 60   C 60   C  Changeover between summer and 10 30   C 17  C  winter  Day room temperature 11 30   C 21  C  Night room temperature 10 29   C 17  C  Table 5 Opera
51. temperature    for all heating circuits allocated  to the MEC 2    During the installation  your installer will determine   which heating circuits must be controlled by the MEC 2  programmer  These heating circuits are referred to as   MEC heat  circ    You set the room temperature for   MEC heat  circ   with the dial     USER NOTE    Any temperature modification applies to all  Buderus  heating circuits allocated to the MEC 2  programmer at any one time     If you have selected a single heating circuit and you  want to set the room temperature with the  i  button     the following fault message appears  Setting not Setting  possible MEC heat  circ  select   not possible    Factory setting  MEC heat  circ     Day room temperature  21  C select  Night room temperature  17  C    With the cover closed  turn the dial to the required room  temperature  without pressing any other button     You may select the room temperature in degree steps  between 11   C and 30   C  The set temperature is  displayed via an LED by the dial  For temperatures  below 15   C or above 25   C    LED or   LED also  illuminates     We reserve the right to make any changes due to technical modifications     Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006       Buderus  19    Setting the day room temperature    First change to day mode  if you want to change the day  room temperature  whilst your heating system is still  operating in night mode       Press and hold down the butto
52. ter  completing your entry  it would be sensible to only enter  a holiday program on the day you of your departure       Open the hinged cover       Press and hold down the button  Heat circ  sel        Turn the dial until the heating circuit  for which you  want to set up the holiday program  is displayed   Example   Heat  circ  2        Release the button     Heat  circ  2            Press and hold down the  1  button              Holiday program    Heat  circ  2       Buderus We reserve the right to make any changes due to technical modifications   48 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006      Turn the dial to the number of days on holiday     Release the  1  button  Holiday days                Room set        Press and hold down the   1   button   The temperature value flashes     Holiday days      Turn the dial until the room temperature required for  the holidays is displayed  In the example 12   C       Release the   1   button  Room set     The holiday program becomes active immediately     The holiday program terminates automatically with the  expiry of the set number of holiday days  the heating  system then returns to automatic mode     The DHW heating and circulation pump will be  switched OFF  if DHW is only produced subject to  heating circuits  time switch   Program choice by  heat  circs   and all heating circuits are in holiday  mode  You cannot enter a separate DHW holiday  program     A separate DHW holiday program can b
53. the  J  button        We reserve the right to make any changes due to technical modifications     Midday program    Monday  at 06 00 hrs    Midday program    Monday  at 13 00 h       Switch  periods    is combined       Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    Buderus  41    14 Creating a new heating program    Make a note of the switching points and the  temperatures of your new heating program     You can enter up to 42 switching points per week     Selecting a heating circuit    Open the cover  Heat circ  sel     Press and hold down the button     Turn the dial until  Heating circ  2  is displayed     Release the button     Program selection    Heating circ  2      Press and hold down the button   The display briefly shows the heating circuit and then  the last set program for this heating circuit  The  program description flashes     Timer    Program choice  Family         Turn the dial to program selection  New      Timer    Program choice      Release the button   The display then shows the mask for the first new  switching point     New Switch Point    To enter the new switching point proceed as for   Entering the first switching point   page 35        Buderus We reserve the right to make any changes due to technical modifications     42 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    Back to the standard  Family   program    Select a heating circuit      Open the hinged cover      Press and hold down t
54. the set night room temperature  or the outside setback temperature       Press and hold down the button       Turn the dial until the required night setback room Room set   temperature is displayed  17  C      Release the button   Setting the room temperature for Perm  night  heating circuits with different remote  control units       You must set the room temperature for all heating  circuits  to which a remote control without display was  allocated during the installation  using this remote  control     If you try to set the room temperature via the CD    button  the adjacent fault message will be displayed  a  i 2 ae  Setting    not possible    Other  remote control       Buderus We reserve the right to make any changes due to technical modifications     22 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    9 DHW  Domestic Hot Water  control    The FM 441 heating circuit and DHW module should be  installed to provide DHW control  In the factory  this  control unit is set to commence heating the DHW   30 minutes before starting the heating circuits     The DHW control can be set subject to heating circuit or  via an individual time program   DHW program       DHW will not be produced  if all heating circuits are  operating in setback or holiday mode     DHW temperature      Press and hold down the button  DHW  set 60   C      Turn the dial until the required DHW temperature is  shown       Release the button     The DHW temperature has been saved 
55. ting settings  We reserve the right to make any changes due to technical modifications  Buderus    Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006 65    29 Keyword Index    A  Automatic changeover between summer  and winter             20000 0500  52  Automatic DHW operation               24  B  BOST 2  bac g be ae  amp  ean dee Ae wee a 10  Burner functions                    10  Burner switch s ao sos s sosar o e aad 10  C  Cascade systems            000004 59  Changeover between summer and winter       18  Changing the standard display             54  Constant DHW circulation pump operation      25  Constant DHW operation                24  Controls  e i e aa a E A 8  Creating a new heating program            42  D  Day room temperature          16  17  20  21  DHW circulation pump               25  45  DHW control o   o os osoa ona a  23  DHW functions    aoaaa 12  Displays  maa BAG Kh eee LA 27  Domestic hot water temperature          17  23  E  Emergency mode fault                 64  Emissions test switch                 57  F  Fault displays                     61  Fault finding   se e cs e ao a a a a aa 62  Flue gas test     oaoa aa a 10  57  H  Heat economically                   7  Heating circuit and DHW module            12  Heating circuit function                 13  Heating circuit functions                12  Heating circuit module                 13  Heating with manual override             63  Holiday program              222245 4
56. u 8 00 22 00  Senior Mo   Su 5 30 22 00  New                                  Table 2 Standard programs    After selection  the display indicates the highlighted  program description  as shown in the table     We reserve the right to make any changes due to technical modifications  Buderus    Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006 31    13 Changing a program       Move the switching points or insert new ones  if you Day mode  e g  21   C    intend changing the heating phases of any program    MEC 2 saves the modified program as  OWN  and the Night mode      number of the heating circuit  if you make changes to the 5 30 22 00    settings of a standard program   g a standard progra Day mode  e g  21   C     If you have selected a program for an individual heating    circuit  you can do the following  Night mode      display the switching points by turning the dial  9 30 6 30 22 00               modify the switching times in 10 minute steps using ngo    Changing a progam    the  O  button         or select the set room temperature for night or day  mode using the   1  button     Moving a switching point    Example  You want to move the heating ON time for  Tuesdays in the standard  Family  program for heating    circuit 2 from 05 30 to 06 30 h  Heat circ  sel       Open the cover     Press and hold down the button       Turn the dial until the required heating circuit is  displayed        Release the button       Press and hold down the button
57. ule FM442    The FM442 function module controls two independent  heating circuits with valve     Each control unit can accommodate up to four such  modules     The manual switches on the module are only provided  for service and maintenance functions     AUT         If the manual switch      i is not set to automatic  a    corresponding message appears on the MEC 2 and the  fault indicator illuminates     Never use the manual switches to switch OFF the  system when you have to temporarily leave the  installation  The control functions continue to operate in  manual mode     Heating circuit function 1   2  AUT   Manual switch     heating circuit Bom       The heating circuit pump is switched ON   The heating circuit valve can be manually  operated    AUT  The heating circuit operates in automatic  mode    0  Only the heating circuit pump is switched  OFF  The control functions continue to  operate     We reserve the right to make any changes due to technical modifications                       Fig 5 FM442    Display    General fault   e g  site error  sensor error   external faults    internal wiring fault   module error  manual mode   These fault messages appear  as plain text on the   MEC 2 programmer     Heating circuit function indicators    Display   Display    A  y    Heating circuit in summer mode  Heating circuit pump active  Display    3 way mixing valve opens    Display 3 way mixing valve closes    Buderus    Operating instructions Logamatic 4311 4312 control devices
58. until the set room  temperature for setback is displayed  e g  17   C     You cannot enter any temperature values here  You can    only select and save preset day and night temperatures       Release the   1   button     We reserve the right to make any changes due to technical modifications     New Switch Point    New Switch Point    New Switch Point    Friday  at 10 00 h    New Switch Point    Friday  at 10 00 h       Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    Buderus  35    The switching point will only be adopted and the blank  mask for the next new switching point displayed after  you have entered all three details     New Switch Point    Proceed in the same way to enter the 2nd switching  point     The modified program will be saved as  Own 2  and as  heating circuit  2     Return to the standard display     Press the  J  button        Deleting a switching point    Example  You would like to delete the switching point  22 00 in the  Family  program for heating circuit 2     Select a heating circuit      Open the hinged cover       Press and hold down the button  Heat circ  sel     Turn the dial until  Heating circ  2  is displayed     Release the button  Heating circ  2    Program selection      Press and hold down the button   The display briefly shows the heating circuit and then  the last set program for this heating circuit  The  program description flashes     Timer    Heating circ  2      Turn the dial until your  Family  program
59. us We reserve the right to make any changes due to technical modifications     26 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    11 Calling up displays    Displaying operating settings   This function enables you to gain an overview of system  conditions  All operating values relate to the previously  selected heating circuit  The boiler and outside  temperature appear on the standard display  if the  MEC 2 programmer is connected with the control unit       With the cover open  turn the dial clockwise without  pressing any other button         Burner condition 1st stage and hours run    By turning the dial further  the following operational  details will appear in sequence         Burner condition 2nd stage and hours run  this  display only appears for two stage burners      Daily consumption currently  yesterday  the day  before yesterday     Current weekly consumption  last week  two weeks  ago     Current annual consumption  last year  the year  before last     Actual and maximum flue gas temperature     Actual heating circuit room temperature  not  possible  if the MEC 2 is fitted to the control unit      Set heating circuit room temperature     Heating circuit operating state     Actual heating circuit flow temperature       Actual DHW temperature     Set DHW temperature       Operating mode DHW     Operation state DHW circulation pump and cylinder  loading pump    We reserve the right to make any changes due to technical modifications    
60. ver  then press and hold down the  button       Turn the dial until  DHW  is shown        Release the button       Press the button   DHW heating now operates in automatic mode   The standard display re appears after 3 seconds     Automatic day       Buderus We reserve the right to make any changes due to technical modifications     24 Operating instructions Logamatic 4311 4312 control devices e Issue 02 2006    10 DHW circulation pump control    The FM 441 heating circuit and DHW module should be  installed to provide DHW circulation pump control  In the  factory  this control unit is set to commence the DHW  circulation pump operation 30 minutes before starting  the heating circuits  The DHW circulation pump control  can be set subject to heating circuit or via an individual  time program  The DHW circulation pump is switched  OFF  if all heating circuits are operating in set back or  holiday mode     Setting constant operation      Open the cover  then press and hold down the  button     Heat circ  sel       Turn the dial until  DHW circulat   is displayed       Release the button  DHW circulat    Press the button     Now the DHW circulation pump operates constantly   The factory setting is set to twice on for 3 minutes  each per hour    Your local heating installer may change the cycle  times at the service level  The standard display re   appears after 3 seconds        DHW circulat     Perm  operation    Switching OFF the DHW circulation  pump      Open the cover  then p
    