DUO-CEL User Manual - control Equipment Ltd.

image

Contents

1. Fuse Falleg Yelow 24Vdc output activated Earth Fault Yellow OFF No cable faults to Earth FLASH One or more cable faults to Earth Repeater Fault Yellow OFF No Repeater faults FLASH One or more Repeater faults Remote Control Fault Yellow OFF No faults on Remote Control input FLASH Fault on Remote Control input Controls On Yellow OFF User Controls disabled ON User Controls enabled FLASH Select mode active SurPPLY on GENERAL FIRE EVACUATE GENERAL FAULT GENERAL TEST SILENCE GENERAL DISABLEMENT 9 BUZZER ALERTIEVAC ON SILENCE FIRE SIGNAL ON RESOUND FIRE SIGNAL FLT DIS TST 5 ALARMS SOUNDER FLT DIS TST SYSTEM FAULT PSU FAULT FUSE FAILED DISABLE EARTH FAULT REPEATER FAULT DUO CEL REMOTE CONTROL FAUL CONTROLS ON 220 SELECT Zone Location Indications Indicator Colour Operating Condition OFF No Alarm on zone FLASH New Alarm on zone ON Alarm accepted on zone Red NOTE With Detector MCP discrimination the left LED is for MCPs EVACUATE the right LED for Detectors ALERT User Zone Location Text User Zone Yellow OFF No Fault on zone circuit FLASH Fault on zone circuit Location Text ON Zone circuit Disabled or in Test PAGE 5 of 6 EQUIPMENT PUBLICATION ISSUE No amp DATE 1 7 2 DUO CEL OM_DUO CEL_USER 13 10 10 User Controls suPPLY on
2. The panel buzzer will sound e General Fault LED will flash e One or more fault LEDs will flash identifying which element of the system is faulty e When the fault is corrected the fault indication will clear automatically except for the Fuse Failed indication which requires the Reset button to be pressed 2 7 To Silence the Buzzer e Press the Silence Buzzer button e The buzzer will silence 2 8 System Fault Indication In the event of a complete system failure a System Fault will be indicated e The SYSTEM FAULT and GENERAL FAULT LED illuminate All other LEDs will be extinguished e The internal buzzer will sound continuously Warning In this condition the panel is not functional and fire alarm cover is no longer available PAGE 3 of 6 DUO CEL OM_DUO CEL_USER 13 10 10 2 9 User actions in the event of a fault e Determine the area affected by the fault and decide whether special actions such as fire patrols are needed in that area EQUIPMENT PUBLICATION ISSUE No amp DATE 1 e Call your service engineer immediately e Record the event in the system log book 3 Panel Operation 3 1 Disablement amp Test Conditions Each zone circuit can be disabled or placed into the test mode individually All sounder circuits can be disabled or placed into the test mode as a group The Fire Signal output can be disabled or placed into test mode 3 1 1 To test disable or re enable one
3. CATIONS scsssssssscisccosssssssonscosesceicsecssscesecccssovecsssensesssbalieestesasdsenseesesssscedeensecbsssosscosevesssedsscoseieceosees 5 7 1 USERINDICA TIONS 5 7 2 TISER A 6 PAGE 2 of 6 DUO CEL OM_DUO CEL_USER 13 10 10 EQUIPMENT PUBLICATION ISSUE No amp DATE 1 1 Introduction This document contains the necessary information for operating the DUO CEL Conventional Fire Detection control panel 2 User Operation Fire and Fault Conditions This panel is capable of operating the fire alarm sounders in various ways e Sounder circuits can operate per zone or all together e Sounder circuits can be continuous or pulsed All users should be fully aware of the particular configuration of their system and should have received training in the basic operation of the system The following information is provided as a quick reference guide only 21 Ifa fire is detected On the DUO CEL Fire Alarm Panel general Fire LED will flash and the buzzer will sound o The relevant zone Fire LED s will flash indicating the location of the fire The Fire Signal output and LED will operate The Fire Alarm sounders will operate immediately pulsed or continuous zonally or together as per configuration Fire Relay will operate immediately Locate the source of the fire alarm an LED will be visib
4. EQUIPMENT PUBLICATION ISSUE No amp DATE DUO CEL WRITTEN BY RKP OM_DUO CEL_USER CHECKED BY AJC 1 13 10 10 APPROVED BY JBJ DUO CEL Fire Detection Alarm Control Panel and Repeater User Operation Manual DANGER THIS EQUIPMENT CONTAINS HAZARDOUS VOLTAGES THAT CAN CAUSE DEATH SERIOUS PERSONAL INJURY OR EQUIPMENT DAMAGE THIS EQUIPMENT CONTAINS NO USER SERVICEABLE PARTS DO NOT REMOVE THE FRONT COVER REFER ALL MAINTENANCE TO SUITABLY QUALIFIED PERSONNEL PAGE 1 of 6 EQUIPMENT DUO CEL WRITTEN BY RKP PUBLICATION OM_DUO CEL_USER CHECKED BY AJC ISSUE No amp DATE 1 13 10 10 List of Contents LUINTRODUCTION 66 ccccscccsuscssscsuccscsscvctessesssses sssucessbusedessestucduscsss suvscess ssuscsdusuedtssudeestsssaesbeevesesssusdesssescdssssnes 3 2 USER OPERATION FIRE AND FAULT CONDITIONS ccsssscsssssccssssccccssseccessscccessssccsensccccessaccecesseccscssseeceses 3 2 1 TRA DETECTED so ee AIA EEE RIE i Sits 3 2 2 SILENCE THE FIRE ALARM SOUNDERS ccccscsssesssesesccssceceeeesseeeeseceeeeuseeesesusueusususesesusuauauauaueusuauauauaueeauauauauenaeenaes 3 2 3 RESOUND THE FIRE ALARM SOUNDERS AFTER SILENCING cccccccscssssscsssescscsceseeesseeessseeseeeuseseausueeeuseeuauauaseueeenaes 3 2 4 TO RESET THE PANEL FROM A FIRE ALARMS uu cccccesesssescscsesceeeeeeeeeeeeeeeseeeeeeeseeeeeseauaeauseeeauaueuauauauauauaeauauauaeauauauanenauanans 3 2 5 TO OPERATE THE F
5. GENERAL FIRE GENERAL FAULT GENERAL TEST GENERAL DISABLEMENT ALERTIEVAC ON FIRE SIGNAL ON FIRE SIGNAL FLT DIS SOUNDER FLT DIS TST SYSTEM FAULT PSU FAULT FUSE FAILED EARTH FAULT REPEATER FAULT REMOTE CONTROL FAUL CONTROLS ON WRITTEN BY RKP CHECKED BY AJC EVACUATE SILENCE BUZZER SILENCE RESOUND DUO CEL Access Controls Keyswitch Switch Functionality Button Availability Evacuate Operates all sounders continuously and illuminates the Alert Evac On LED until the Silence Resound Alarms button is operated When controls are unlocked Silence Buzzer Silences the internal buzzer on the Panel amp Repeaters When controls are locked or unlocked Silence Resound When any sounders are active press to silence sounders When controls are unlocked Alarms Press again to resound the silenced sounders Reset Press to clear any fault amp alarm conditions and return the Whenicontrols are unlocked panel to the quiescent state Displays Alarm Counter When controls are locked Disable only the currently disabled circuits When controls are unlocked Toggles the selected circuit between Disabled amp Enabled When controls are unlocked and in states circuit select mode Press to illuminate all LEDs and sound the buzzer for 5 Wim seconds Test IIluminates only the circuits c
6. IRE ALARM SOUNDERS IN EVACUATE 3 2 6 FAULTS DETECTED AE S 3 2 7 TO SILENCE THE BUZZER bees Cotesia seb dace E E 3 2 8 SYSTEM FAULT INDICATION 3 2 9 USER ACTIONS IN THE EVENT FAULT covicecevseseseesovceste soeseoestovucste 4 3 OPERA TION sisstccctesssiestisececs svesvecebecestucheessonsisdeveecesesbseussseuteddsuesessdgatveecssestessusoondssovesesessscavsusobestenstestesssebesvevseseeus 4 3 1 DISABLEMENT amp TEST CONDITIONS 2 4 3 1 1 To test disable or re enable or more circuits 4 3 1 2 To view Only the disa bled cireuils n oenen i enra a eee cae tesa EEE sa peta act E E E 4 3 1 3 ToView Only the circuits in eea aaea ear RE 4 3 2 DISPLAY DEST O E E E E E A E E EES 4 4 DUO CEL REPEATER PANEL OPERATION sseesseseessececssecescsecssoceesseceessecsscoecssocecsseceeseecsscoeessoceesseceesseesssseesseoeessee 4 5 ROUTINE TESTING AND MAINTENANCE cccsssscssssssccssssccccssscccssssccccsssacccessccccessscccesscscccesscsecessacccesssaccscsssscceses 4 6 USER RESPONSIBILITIES ssccccscscecsssvnsssinsossossusenssossccessntsessssvincsodevsasessseteosslestsseseesesusdensesesiesssesscossuvenscosescesesbsseosseueesodees 4 7 DUO CEL USER INDI
7. Indications This section gives an overview of the functions available to the end user 7 1 User Indications General Indicator Section Indicator Colour Operating Condition Supply On Green OFF No mains or battery power ON Panel has power battery and or mains General Fire Red OFF Quiescent FLASH New Alarm Condition ON Alarm Accepted General Fault Yellow OFF No faults present FLASH One or more faults present General Test Yellow OFF No circuits in Test ON One more circuits in Test General Disablement Yellow OFF No circuits Disabled ON or more circuits Disabled Alert Evac On Red OFF No Alert or Evacuate FLASH Remote Alert Evacuate active ON Panel Evacuate active Fire Signal On Red OFF Fire Routing output not active ON Fire Routing output active OFF No fault on Fire Routing output FLASH Fault on Fire Routing output Pire Disisi Yellow ON Fire Routing output Disabled or in Test OFF No Fault on Sounder circuits FLASH Fault on one or more Sounder Sounder Fit Dis Tst Yellow circuits ON Sounder circuits Disabled or in Test OFF System is working correctly ON System is in the SAFE state System Fault Microcontroller failed EEPROM data corrupted PSU Fault Yellow OFF power supply is healthy FLASH PSU fault and or battery fault OFF Auxiliary 24Vdc output available FLASH Electronic Fuse on Auxiliary
8. le on the detector which has been activated 2 2 To Silence the fire alarm sounders e Turn the Access Key to the vertical position e the Silence Resound Alarms button once only e The fire alarm sounders will become silent e General Fire LED and the Zone Fire LED s will become steady e Remove the Access Controls Key to lock the controls 2 3 Resound the fire alarm sounders after silencing e Turn the Access Controls Key on the panel door to the vertical position e Press the Silence Resound Alarms button once only e Remove the Access Controls Key to lock the controls WRITTEN BY RKP CHECKED BY AJC 2 4 reset the panel from a Fire Alarm After the fire has been extinguished turn the Access Controls Key on the panel door to the vertical position e Press the Reset button e The General Fire LED and the Zone Fire LED s will clear e Remove the Access Controls Key to lock the controls 2 5 To operate the fire alarm sounders in Evacuate Mode e Turn the Access Controls Key on the panel door to the vertical position e Press the Evacuate button e Alert Evac LED will illuminate and the panel buzzer will operate e fire alarm sounders will operate continuously e Press the Silence Resound Alarm button to silence the fire alarm sounders and clear the Alert Evac LED e Remove the Access Controls Key to lock the controls 2 6 Ifa fault is detected e
9. or more circuits 1 Turn the Access Key to the vertical position 2 Press the Select button to enter the Select Mode e The Controls On LED will flash e cursor indication will pulse rapidly on the yellow Zone 1 fault LED e The yellow fault LED for any circuit currently in test or disabled will be illuminated 3 Press the Select button to move the cursor to the required circuit fault LED For each circuit the cursor is on the General Disablement amp General Test LEDs will indicate the current status for that circuit i General Test amp General Disablement LEDS OFF Circuit is in normal operating mode General Test LED pulsing Circuit is in Test mode iii General Disablement LED pulsing Circuit is Disabled 4 To change the status of the selected circuit press the Disable or Test button as required e Circuit is currently not disabled or in test Press the Disable button to disable Press the Test button to test e Circuit is currently disabled Press the Disable button to re enable Press the Test button to test the disabled condition will also be cleared WRITTEN BY RKP CHECKED BY AJC e Circuit is currently in test Press the Test button to clear the test press the Disable button to disable the test condition will also be cleared 5 To exit from the Select mode either remove the Access Controls Key to lock the controls or press the Select button repeatedly to sc
10. roll the flashing cursor through the remaining circuits until the Controls On LED stops flashing and the flashing cursor is cleared 3 1 2 To view only the disabled circuits 1 Turn the Access Key to the vertical position 2 Press and hold the Disable button Only the General Disablement LED and the fault LEDs of any disabled circuits will be illuminated 3 Release the Disable button to return the display to normal 3 1 3 To view only the circuits in test 1 Turn the Access Key to the vertical position 2 Press and hold the Test button Only the General Test LED and the fault LEDs of any circuits in test will be illuminated 3 Release the Test button to return the display to normal 3 2 Display Test 1 Remove the Access Controls Key to lock the controls 2 Press the Test button All LEDs on the display will illuminate and the internal buzzer will sound for 5 seconds 4 DUO CEL Repeater Panel Operation The repeater panel operation is identical to the Alarm panel except that the disablement amp Test facilities cannot be controlled from the repeater The display is similar but the Disable and Select buttons are not present 5 Routine Testing and maintenance See DUO CEL Log Book for details 6 User responsibilities See DUO CEL Log Book for details PAGE 4 of 6 EQUIPMENT DUO CEL WRITTEN BY RKP PUBLICATION OM_DUO CEL_USER CHECKED BY AJC ISSUE No amp DATE 1 13 10 10 7 DUO CEL User
11. urrently in test When controls are unlocked When controls are unlocked and in Toggles the selected circuit between Test amp Normal states circuit select mode First operation enables the circuit select mode subsequent Select operations move the flashing cursor through the available Whenicoritrols are unlocked circuits until the last circuit then exits the circuit select mode PAGE 6 of 6

Download Pdf Manuals

image

Related Search

Related Contents

Tripp Lite PDU3VSR10L1530 power distribution unit PDU  Origin Storage 64GB 2.5" MLC SATA  日本語版取扱説明書[PDF, 約 1MB]  Operating Instructions - Instrumentation Systems & Services Ltd.  取扱説明書 - CASIO  Owner`s Manual  ARADO DE SUBSUELO COLOSO MODELO ASC-32  Mousetrapper Advance+    Samsung SCH-R480BKAXAR User's Manual  