         Contents
1.       FRAGILE    and  ARROW   indicator should be intact if the equipment has been transported in an  upright position  In case of rupture  or if they are suspect  inform the carrier and Uninterruptible Power Supplies Ltd  immediately     Other claims for shipping damage must also be filed immediately and the carrier must be informed within 7  days of receipt of the equipment   Packing materials should be stored for further investigation     i CAUTION  Visible transport damages must be notified to the carrier immediately after receipt     Ensure that the received UPS corresponds to the description indicated in the delivery note     3 2 1 Site transportation    If you transport the UPS equipment after it has been off loaded  for example  for storage or moving to a different  installation location  please observe the following precautions     CAUTION  Transportation    To avoid the UPS cabinets and or battery cabinet falling over  use the shipping brackets on the rear and  front to secure the cabinets        Do not tilt the cabinets more than 10 from vertical     CAUTION  Potential dangers        If the cabinet has been tilted it might damage the equipment and it should not therefore be connected to  the mains electricity supply        The weight of the UPS system could cause serious injuries to persons or anything in the surrounding area        UPS454 01 02 PW8000DPA User Manual    01 12 13  7    Uninterruptible    Power   Supplies Ltd    3  Installation A KOHLER COMPANY      
2.       UPS CABINET    v       3L1 3L2 3L3 3N PE    1          O    Output  Supply     O                               INPUT UPS  CABLE TERMINAL  Phase L1 1L1  Phase L2 1L2  Phase L3 1L3  NEUTRAL 1N  EARTH PE  BYPASS UPS  CABLE TERMINAL  Phase L1 2L1  Phase L2 2L2  Phase L3 2L3  NEUTRAL 2N  EARTH PE  OUTPUT UPS  CABLE TERMINAL  Phase L1 3L1  Phase L2 3L2  Phase L3 3L3  NEUTRAL 3N  PE                Fuse B  A    Cable B  mm     Fuse C  A    Cable C  mm   Cable D  mm    ST 40 3 x 80 5x 16 3 x 80 4 x 16 5x 16  ST 60 3x 125 5x35 3x 125 4x35 5x35  ST 80 3 x 160 5 x 50 3 x 160 4x50 5 x 50  ST 120 3 x 224 4x95  1x50 PE  3 x 224 4x95 5x95  ST200 3 x 350 5x185 3 x 350 4x185 4x185          Fuse and Cable recommendations to IEC 60950 1 2001  The fuse and cable rating details in the above tables are a recommendation only     The UPS must be installed to prescribed IEC or local regulations  e g  BS7671 2008     Figure 3 8 Dual Input Feed   Connection block diagram       UPS454 01 02 PW8000DPA User Manual    01 12 13     19    Uninterruptible    Power   Supplies Ltd          3  Installation A KOHLER COMPANY   3 9 Connecting the UPS Output Supply   WARNING  Opening or removing the UPS enclosure covers will create the risk of exposure to dangerous  voltages if power is connected to the UPS    3 9 1 Safety notes   Ensure you read and understand the following safety notes before you begin the UPS electrical installation    1  All operations detailed in this section must be performed by an author
3.     as shown in Figure 3 5  There are three terminal block connections for each UPS module  annotated Battery     N       The  cables at the top of these terminal blocks are connected to the battery isolators associated with each individual UPS  module  The battery strings are connected to the bottom of the terminal blocks  as shown in Figure 3 9     Note  Figure 3 9 depicts the ST 60 Cabinet  which houses  up to  three UPS modules     Battery configuration options   Several battery configurations are possible  depending on the required load power and battery autonomy time  Several  examples are shown in the following diagrams    Common battery configuration    Where a    common battery    configuration is implemented  all the UPS modules are fed by a common battery source  which  may comprise a number of parallel battery strings   Where this type of installation is used     common battery    links must  fitted to the bottom of the battery connection terminal blocks as shown in the left hand diagram of Figure 3 9        UPS454 01 02 PW8000DPA User Manual    01 12 13     21    Uninterruptible    Power   Supplies Ltd    3  Installation A KOHLER COMPANY       3 10 3 Connecting the battery cables      WARNING  This procedure must be carried out by  or under the supervision of  the system commissioning  engineer     1  Ensure that the UPS input bypass supply isolators fuses are open on the input distribution board and verify that no  power is being fed to the UPS     Ensure that t
4.    A licence is issued with every software serial number for use of what is known as the  UPS service  on a single server in  connection with one UPS and an unlimited number of connected WINDOWS workstations  For operation with two or more  servers  a further licence is required for each additional server  In this case it is of no importance whether the UPS service  on these servers is active or whether the server was stopped by a remote UPS service  The same applies to the use of  RCCMD with the    remote send receive  modules for    multi server shutdown    under NT  UNIX and other operating systems     The service programs are generally supplied as single licences  In order to use a single CD ROM for several    multi server  shut down  units you must acquire additional licence codes     7 4 6 RCCMD Server shutdown    In order that remote shutdown of servers can take place  initiated by the SNMP card or WAVEMON software  further  licenses must be purchased  The license s for the RCCMD client  or listening  software that resides in each target server        52    UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Supplies Ltd ta      KOHLER COMPANY T  Options       7 5 PowerREPORTER    management software  PowerREPORTER is a remote monitoring and management service which provides peace of mind protection by offering    a continuous  24 7 365  watch over mission critical facilities  Continuous monitoring is an affordable insurance policy to  detect issues a
5.    Supplies Ltd       Uninterruptible    Powerm  Supplies Ltd    A KOHLER COMPANY       Document Control                            ISSUE DATE REVISION SUMMARY  Issue 1 0 0 09 09 09 Initial issue   Issue 1 1 0 01 06 10 GENERAL  Style update to align with Kohler documentation   Issue 1 2 0 18 11 11 Update illustrations  specification and general error corrections  Part number changed to 454 01 00   Issue 1 3 0 05 04 13 Updated contact details  Issue 1 3 1 28 05 13 Updated 24Hr contact details  Issue 1 4 0 20 12 13 Added ST 200 model details and updated layout                                            UPS454 01 02 PW8000DPA ST User Manual Dated 20 12 13       Uninterruptible    Power   Supplies Ltd    A KOHLER COMPANY       Uninterruptible Power Supplies Ltd has taken every precaution to  produce an accurate  complete and easy to understand manual and  will therefore assume no responsibility nor liability for direct   indirect or accidental personal or material damage due to any  misinterpretation of or accidental mistakes in this manual        2005 Uninterruptible Power Supplies Ltd    This manual may not be copied nor reproduced without written  permission of Uninterruptible Power Supplies Ltd        UPS454 01 02 PW8000DPA ST User Manual Dated 20 12 13    Table of Contents       1  Safety    1 1 Description of symbols used in this manual  1 2 User precautions    2  General Description    2 1 Reliability and Quality Standards  2 2 PW8000DPA ST System  2 3 System Configuration
6.    Supplies Ltd ta    3  Installation   KOHLER COMPANY       SINGLE INPUT FEED  standard   Mains  3x400 230V     Static Switch Static Switch Static Switch    UPS Module 6       2   2  o   o  z  o  Q  2    UPS Modules 2   5    Maintenance Bypass IA1    UPS CABINET    BATTERY  CABINET       Cabinet Mounted     Single Input Feed                         Input 3x400V 230V Output 3x400V 230V  Fuse A Cable A  mm   Max P   CableD mm2  Inom      Agl CB  Current  ST 40 3x80A 5x16 68A 5x16 58A  ST 60 3x125A 5x35 102A 5x35 87A  ST 80 3x160A 5x50 136A 5x50 116A  ST 120 3x224A 4x95  1x50 PE  208A 5x70 174A  ST200 3x350A 5x185 333A 5x185 290A             Notes     1  Fuse and Cable recommendations to IEC 60950 1 2001    2  The fuse and cable rating details in the above tables are a recommendation only    3  The UPS must be installed to prescribed IEC or local regulations  e g  BS7671 2008    4  DC Cables and Battery fuses are bespoke to the installation     Figure 3 3 PowerWAVE 8000DPA ST fuse  amp  cable rating for single input supply       1 2 UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Supplies Ltd ta      KOHLER COMPANY 3  Installation       INPUT FEED BYPASS FEED  Mains  3x400 230V  Mains  3x400 230V     Static Switch Static Switch Static Switch       UPS Module 1  UPS Module 6    7    UPS Modules 2   5               1  1  1         BATTERY Maintenance Bypass IA1    CABINET       UPS CABINET       Cabinet Mounted     Dual Input Feed                Input 3x400V
7.    please complete the enquiry form shown below and return or FAX it to        Uninterruptible Power Supplies Ltd     Woodgate   Bartley Wood Business Park Tel  01256 386700   Hook 0800 731 3269  24 Hr    Hampshire Fax  01256 386701   RG27 9XA Email  service upspower co uk          UPS454 01 02 PW8000DPA User Manual    01 12 13  5    Uninterruptible    Power   Supplies Ltd    2  General Description A KOHLER COMPANY       2 6 Extended Service enquiry form    Fax to  01256 386701 www upspower co uk    Uninterruptible Power Supplies Ltd   Woodgate   Bartley Wood Business Park   Hook   Hampshire   RG27 9XA    Tel  01256 386700    Names Misses ee eer Pee ea  JOD Title      gidiciieieancnd eli edhe eens  COMPANY  Ncc         AddresS                          dueniehinue rue retis EEE EEC te e cs eret te ete Er ee eed esi deep cata    PoStCOdO              uniensenelescedeniner d fa nre RRMRDADRI INDOOR EOYrRe dan XR PR SERERE AERE   MM ZZ    e eE a arae E EE E  1o PEE  E mail     3        uaHBiSHuEun eei MEI i    Please contact me to discuss   C  Extended Warranty options for my PW8000DPA ST UPS    C  Extended warranty options for my UPS System as below     Man  fact  re r riirii ieta iaae   Model Ne eeror a a   Rating KVA      eite t Re PEE reaa ERR  C  Replacement Batteries                        eeciseeseee entente innen  C  Others derem arn ranean eter ERR UE aE Ei deen ste  please specify     Thank you for your enquiry  which will receive our prompt attention   If you need to c
8.   1  Use a screened cable with a single pair  0 6 mm   and maximum length of 100 m     2  Connectthe cable as shown in Figure 7 1        UPS454 01 02 PW8000DPA User Manual    01 12 13     49    Uninterruptible    Power   Supplies Ltd    K  Options A KOHLER COMPANY       7 3 Generator ON facilities    The Generator ON facility must use a normally   open contact which closes to signal that a  generator is running and supplying the UPS  input power                          UPS Generator On On Generator  When used  this facility enables the option to Port  inhibit the operation of the battery charger and   or static bypass  See    Set up User menu    screen    in section 4 3 8         X1 1  X1 2       1  Use a screened cable with a single pair OO Terminal block     0 6 mm   and maximum length of 100 m                 2  Connectthe cable as shown in Figure 7 2                                Figure 7 2 Generator ON Connection    7 4 UPS Monitoring and automated control software    7 4 44 SNMP Card slots    Simple Network Management Protocol  SNMP  is a world wide  standardised communication protocol that can be used to  monitor any network connected device via a simple control language and display the results in an application running  within a standard web browser     The PW8000DPA ST contains two SNMP slots  one is designed to house a Modem Ethernet SNMP adapter card and the  other a Modem GSM adapter  Alternatively  SNMP connectivity can also be implemented using an external SNM
9.   2 4 Advanced Design Features   2 4 1 Input booster technology   2 4 2 Flexible battery management   2 4 3 Decentralized Parallel Architecture  DPA   2 5 Warranty   2 5 1 Extended warranty   2 5 2 Additional service maintenance support  2 6 Extended Service enquiry form    3  Installation    3 1 Introduction  3 2 Receipt of the UPS  3 2 1 Site transportation  3 3 Unpacking  3 3 1 Nameplate  3 4 Batteries  3 5 Storage  3 5 1 UPS  3 5 2 Battery  3 6 Positioning  3 6 1 Planning the installation  3 7 UPS Power Cabling  preparation and planning   3 7 1 General requirements  3 8 Connecting the UPS input supply  3 8 1 Safety notes  3 8 2 Preparing the input cabling  3 8 8 Connecting the UPS input power cables  3 9 Connecting the UPS Output Supply  3 9 1 Safety notes  3 9 2 Preparation for the output cabling  3 9 3 Connecting the UPS output cables  3 10 Connecting the batteries  3 10 1 Safety Notes  3 10 2 Battery cabling  3 10 3 Connecting the battery cables  3 10 4 Internal battery for ST 40 and ST 60 cabinets  3 10 5 External battery enclosures            k mk    onna AAU UOUNNN N    Qo dco dodoocoo        NO NDPNOPFPNODPFNOPFNOPNRPKNPKNPNSAA           ANN 00000000 0 O0 O       UPS454 01 02 PW8000DPA ST User Manual Dated 05 04 13    Uninterruptible    Power   Supplies Ltd    A KOHLER COMPANY       3 11 Module interfacing facilities  3 11 1 Smart Port JD1  Serial RS 232  and USB Port  3 11 2 X1  amp  X2 Dry Port  volt free contacts     4  Operation    4 1 Commissioning  4 2 UPS co
10.   31  31  32  32  32  33  33  34  34  34  35  35  35  36  36  37  37  37  37  38  38  39  40  41  42  42  42  42  43  43  43  43  44    45    45  45  45  45  46  46  46    47    47  47  47  48       UPS454 01 02 PW8000DPA ST User Manual Dated 05 04 13    Uninterruptible    Powerm  Supplies Ltd      KOHLER COMPANY       7T  Options   7 1 Introduction   7 2 Remote emergency stop   7 3 Generator ON facilities   7 4 UPS Monitoring and automated control software  7 4 1 SNMP Card slots  7 4 2 The importance of UPS management  7 4 3 WAVEMON Shutdown and Monitoring Software  7 4 4 Functional description  7 4 5 Licensing  7 4 6 RCCMD Server shutdown   7 5 PowerREPORTER    management software  7 5 1 Functional description    8  Specification  8 1 Mechanical Characteristics   UPS Cabinet  8 2 Mechanical Characteristics   UPS Module  8 3 Input Characteristics  8 4 Battery Characteristics  8 5 Battery Capacity Usage  8 6 Heat Dissipation Per Module With Non Linear Load  8 7 Output Characteristics  8 8 Standards  8 9 Environmental Characteristics  8 10 Communication Options  8 11 Fuses  amp  Cables Quick Reference    49    49  49  50  50  50  51  51  52  52  52  53  53    55    55  56  56  56  56  57  57  57  58  58  59       UPS454 01 02 PW8000DPA ST User Manual Dated 05 04 13    Uninterruptible    Supplies Ltd ta      KOHLER COMPANY          IV    UPS454 01 02 PW8000DPA ST User Manual Dated 05 04 13    Uninterruptible    Supplies Ltd t      KOHLER COMPANY 1  Safety       1 Safety    1 1 
11.   as  applicable        UPS454 01 02 PW8000DPA User Manual    01 12 13  39    Uninterruptible    Power   Supplies Ltd                   4  Operation   KOHLER COMPANY  2  Simultaneously press the two ON OFF push buttons on the UPS control LINE 2 BY PASS  panel     a  The UPS will run through an automated start up sequence accompanied LOAD  by the following indications  LINE 1 INVERTER  LINE 2 LED lights red then changes to green          BE NE    INVERTER LED lights green   BATTERY LED lights green  constant    m BATTERY  b  LCD displays the LOAD PROTECTED message  L  3  The UPS module is now on line and connected to the parallel system  T    4 5 3 Transfer to maintenance bypass mode    If required  the load can be transferred to the maintenance bypass supply to enable the UPS module to be powered down  for maintenance or servicing  This will connect the load to the unprotected bypass mains supply     WARNING  Before you close the maintenance bypass switch  IA1  ensure that the UPS is operating in its  on bypass mode  All the operations in this section must be performed by authorised and trained personnel     This procedure describes the sequence of operations to transfer the load to the maintenance bypass supply and then shut  down the UPS module s      Prior to commencing this procedure  check and confirm the following UPS system status  on all working UPS modules in a  multi module system        The mimic panel LED indications should be as shown below  on all working UPS mo
12.   for UPS Module 4  for UPS Module 5    Battery fuse  Battery fuse  Battery fuse  Battery fuse  Battery fuse                                                                                                                                  for UPS Module 6    Battery fuse                                                                                                                                                                To Modules 1  amp  2       To Modules 3  amp  4       To Modules 5  amp  6       To Modules 7  amp  8       To Modules 9  amp  10       TO UPS BATTERY ISOLATORS    TO UPS BATTERY ISOLATORS    1 2 To Modules 1  amp  2  N   2   To Modules 3  amp  4  N   3   To Modules 5  amp  6  N   4     To Modules 7  amp  8  N   5   To Modules 9  amp  10  N     TO UPS BATTERY ISOLATORS    1  To Modules 1  amp  2      2   To Modules 3  amp  4      3   To Modules 5  amp  6      4     To Modules 7  amp  8      5   To Modules 9  amp  10        UPS CABINET  200kVA Example     To Modules 1  amp  2           To Modules 3  amp  4      To Modules 5  amp  6      To Modules 7  amp  8      To Modules 9  amp  10      TO UPS BATTERY ISOLATORS    TO UPS BATTERY ISOLATORS    1 2 To Modules 1  amp  2  N   2   To Modules 3  amp  4  N   3   To Modules 5  amp  6  N   4     To Modules 7  amp  8  N   5  To Modules 9  amp  10  N     TO UPS BATTERY ISOLATORS    1 2 To Modules 1  amp  2      2   To Modules 3  amp  4      3   To Modules 5  amp  6      4     To Modules 7  amp  8      5  To Modules
13.  20kVA UPS Module   Output Rated Power per Module Cosq 0 8 kVA 10 20  Output Rated Power per Module Cosq 1 0 KW 10 20  Output Current In   Cos  1 0  400 V  A 14 5 29  Output Rated Voltage V 3x380 220V or 3x400 230V or 3x415 240V  Output Voltage Stability 96 Static         1    Dynamic  Step load 0  100  or 100  0   lt      4   Output Voltage Distortion   With Linear Load lt  1 5    With Non linear Load  EN62040 3 2001  lt  3    Output Frequency Hz 50 Hz or 60 Hz  Output Frequency Tolerance   Synchronized with mains  lt      2      selectable for bypass operation  or  lt      4   Free running    0 1           Bypass operation At Nominal Input voltage of 3x400 V     15   or 199 V to 264 V ph N   Permissible Unbalanced Load   100     All 3 phases regulated independently    Phase Angle Tolerance Deg      0 deg     With 100  Unbalanced load    Overload Capability on Inverter   125  load 10 min   150  load60 sec    Output short capability  RMS  A Inverter  3 x In during 40 ms   Bypass  10 x In during 20 ms  Crest   Factor 3 1    8 8 Standards          10kVA UPS Module 20kVA UPS Module   Safety EN 62040 1 1 2003  EN 60950 1 2001 A11 2004  Electromagnetic Compatibility EN 62040 2 2005  EN61000 3 2 2000    EN61000 3 3 1995 A1 2001  EN61000 6 2 2001  Emission Class C2  Immunity Class C3  Performance EN62040 3 2001  Product certification CE  Degree of protection IP 20          UPS454 01 02 PW8000DPA User Manual    01 12 13  57    Uninterruptible    Powerm  Supplies Ltd    8  Specificati
14.  230V Input 3x400V 230V Output 3x400V 230V  FuseB Cable B  mm   Max I P Fuse C Cable C  mm     Cable D  mm   I  nom    Agl CB  Current  Agl CB   ST 40 3x80A 5x16 68A 3x80A 4x16 5x16 58A  ST 60 3x125A 5x35 102A 3x125A 4x35 5x35 87A  ST 80 3x160A 5x50 136A 3x160A 4x50 5x50 116A  ST 120 3x224A 4x95  1x50 PE  208A 3x224A 4x95 5x70 174A  ST200 3x250A 5x185 333A 3x350A 4x185 5x185 290A                   Notes    1  Fuse and Cable recommendations to IEC 60950 1 2001    2  The fuse and cable rating details in the above tables are a recommendation only    3  The UPS must be installed to prescribed IEC or local regulations  e g  BS7671 2008    4  DC Cables and Battery fuses are bespoke to the installation     Figure 3 4 PowerWAVE 8000DPA ST fuse  amp  cable rating for dual input supply       UPS454 01 02 PW8000DPA User Manual    01 12 13  1 3    Uninterruptible    Power   Supplies Ltd                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                         3  Installation A KOHLER COMPANY  olo CofC  C O O OJ O OE     OfO OJo Oo o o SS SS uma ST 40  olo oolo o olo
15.  8 Gnd connected  GND 6              O  X1 9  12Vdc   12Vdc source  OUT O         _    Max 200mA load  X1 10 Gnd  GND           _               UPS454 01 02 PW8000DPA User Manual    01 12 13     29    Uninterruptible    Power   Supplies Ltd                      3  Installation A KOHLER COMPANY  Output Interfaces Terminal blocks X2  DRY PORTS   Provision of signals for the automatic and orderly shutdown of servers  AS400 or Automation building systems  All voltage  free contacts are rated 60 VAC max  and 500 mA max    Pin Contact Signal Function  X2 1 NO Alarm MAINS_OK Mains Present  X2 2 Mains Failure  NC  X2 3 Common  Com  X2 4 NO Message LOAD ON INV Load On Inverter  X2 5  Load on bypass   NC  X2 6 Common  Com  X2 7 NO Alarm BATT_LOW Battery Low  X2 8 Battery OK  NC  X2 9 Common  Com  X2 10 NO Message LOAD ON MAINS Load On Mains  BYPASS MODE   X21  Load on Inverter   NC  X2 12 Common  Com  X2 13 NO Alarm COMMON_ALARM Common Alarm  X2 14 No Alarm Condition  NC  X2 15 Common  Com  Figure 3 17 Dry Port  X2  Connections  30 UPS454 01 02 PW8000DPA User Manual    01 12 13        Uninterruptible    Powerm  Supplies Ltd      KOHLER COMPANY 4  Operation       4 Operation    4 4 Commissioning    The PW8000DPA ST UPS is a high quality  complex electronic system that must be commissioned by a fully trained and  authorised Uninterruptible Power Supplies Ltd  field service engineer before it is put into use     The commissioning engineer will       Connect the UPS battery      Check the 
16.  9  amp  10        UPS CABINET  200kVA Example     Figure 3 14 External battery cabinet connection for ST 200 cabinet       UPS454 01 02 PW8000DPA User Manual    01 12 13     27    Uninterruptible    Power   Supplies Ltd                                                                                                                                           3  Installation   KOHLER COMPANY  3 11 Module interfacing facilities  7 8  1  2  3  4  1 2 3 4 5 6  6  1  JR2 RS485   Notused   2 X2 Customer interface on Phoenix Terminals  potential free contacts   7  3 x1 Customer inputs   4 LEDs Interface Board Status LEDs  8  5  JD1 RS232  Sub D9 female  PC Interface   6 USB PC Interface   7 SLOT 2 PowerReporter Slot for optional modem ethernet card only   8 SLOT 1 Slot for optional SNMP card only   Figure 3 15 UPS Interfacing connectors  ST40   ST120   The PW8000DPA ST system contains a communications card which provides various I O interface facilities  Two LEDs   4  located on the board provide indication of the board   s status     Green LED   blinking twice per second indicates normal operation     RedLED   board alarm  indicates possible board replacement when lit    3 11 1 Smart Port JD1  Serial RS 232  and USB Port  The SMART PORT is an intelligent RS 232 serial port that allows the UPS to be connected to a computer  The connector  is a standard D Type  9 pin  female  and the USB is a standard USB port   When installed  the optional SMART PORT software  WAVEMON  this connection
17.  CAUTION  Storage        The UPS should be stored in the original packing and shipping carton        The recommended storing temperature for the UPS system and batteries is between  5 CT and 440 C       The UPS system and the battery sets must be protected from humidity    9096 RF  non condensing      3 3 Unpacking    WARNING  The UPS system  the battery cabinet  option  and the batteries are heavy and may tip during  transportation causing serious injury if the unpacking instructions are not followed closely     If the packages are received in good order  i e  the    tip  amp  tell       FRAGILE    and  ARROW  indications on the packing  container are intact  then perform the following steps to unpack the UPS     1  If the cabinet is shipped inside a wooden case  remove the screws at the base and sides of the case then carefully  remove the case from the equipment    Cut the wrappers and remove the packing container by pulling it upwards    Remove the plastic sheeting covering the UPS    Remove the UPS from the pallet    Retain the packaging materials for future shipment of the UPS     oar oN    Examine the UPS for any sign of damage   Notify your supplier immediately if damage is apparent     7  Open the cabinet door and ensure that all the UPS modules are correctly and securely fitted in their compartments   Ensure that a protection cover is fitted to the front of any empty UPS compartments     3 3 4 Nameplate    The technical specifications of the PW8000DPA ST are provide
18.  CB      Cable A  mm     Max I P Current Cable D  mm   ii l nom     ST 40 3x80A 5x16 68A 5x16 58A  ST 60 3x125A 5x35 102A 5x35 87A  ST 80 3x160A 5x50 136A 5x50 116A  ST 120 3x224A 4x95   1x50 PE  208A 5x70 174A  ST 200 3x350A 5x185 333A 5x185 200A  Notes     1  Fuse and Cable recommendations to IEC 60950 1 2001  2  The fuse and cable rating details in the above tables are a recommendation only    3  The UPS must be installed to prescribed IEC or local regulations  e g  BS7671 2008    4  DC Cables and Battery fuses are bespoke to the installation        UPS454 01 02 PW8000DPA User Manual    01 12 13     59    Uninterruptible    Power   Supplies Ltd    8  Specification A KOHLER COMPANY       INPUT FEED BYPASS FEED  Mains  3x400 230V  Mains  3x400 230V     Static Switch Static Switch Static Switch    UPS Module 6       E    3  3   o  z   e   o  2    UPS Modules 2   5    Maintenance Bypass IA1    UPS CABINET    BATTERY  CABINET       Cabinet Mounted     Dual Input Feed                   Input 3x400V 230V Input 3x400V 230V Output 3x400V 230V    Fuse B Cable B Max I P Fuse C Cable C Cable D    Knom    AgI CB     mm     Current  Agl CB   mm    mm     ST 40 3x80A 5x16 68A 3x80A 4x16 5x16 58A  ST 60 3x125A 5x35 102A 3x125A 4x35 5x35 87A  ST 80 3x160A 5x50 136A 3x160A 4x50 5x50 116A  ST 120 3x224A 4x95   1x50 PE  208A 3x224A 4x95 5x70 174A  ST 200 3x350A 5x185 333A 3x350A 4x185 5x185 290A                      Notes    1  Fuse and Cable recommendations to IEC 60950 1 2001   2  The fuse 
19.  Maintenance    Uninterruptible    Power   Supplies Ltd    A KOHLER COMPANY       5 5 Battery testing  The battery test takes approximately 3 minutes to complete and should be performed only if       There are no alarm conditions     The battery is fully charged     The input mains supply is present     The battery test procedure can be performed from the UPS front panel and can be carried out irrespective of the operating  mode  off line or on line  and whether or not the load is connected     5 6 Battery maintenance    The battery maintenance shall be done by an authorized Uninterruptible Power Supplies Ltd Service Partner     5 7 Battery disposal and recycling    Batteries contain dangerous substances that can harm the environment if disposed of carelessly  If you have reason to  change the batteries  always consult with your local environmental waste disposal organisations to obtain the  recommended disposal and recycling information     ay    ed             46    UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Powerm  Supplies Ltd      KOHLER COMPANY 6  Troubleshooting       6 Troubleshooting    6 1 Alarms    If an alarm condition occurs  the red ALARM LED will illuminate on the UPS control panel and the audible alarm will  sound  In this case proceed as follows     1  Silence the audible alarm by pressing the RESET button   2  Identify the cause of the alarm by viewing the events register in the main menu  See paragraph 4 3 3    3  In case of doubt
20.  allows the computer to monitor the  mains voltage and the UPS status continuously and display a message in the event of any UPS system changes   Figure 3 16 and show the connection to a PC from the UPS for PC s with a 9 pin serial port and 25 pin serial port  respectively   28 UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Powerm  Supplies Ltd      KOHLER COMPANY    3  Installation       Interface Cable Interface Cable Interface Cable  UPS end Computer end UPS end  9 Pin D Type 9 Pin D Type 9 Pin D Type   Male   Female   Male     Interface Cable  Computer end    25 Pin D Type   Female        Figure 3 16 Connector Cable   PC Serial Port    3 11 2 X1  amp  X2 Dry Port  volt free contacts     All the Input and Output interfaces are connected to Phoenix terminals  cable 0 5 mm      Input Interfaces Terminal block X1    Connection of Remote Shut down facilities  Generator Operation  Customers specials     see also OPTIONS section            Terminal   Contact   Signal    X1 1 N4 O  12Vdc   Customer IN 1  default as ONGENERATOR operation    NC   Generator ON   X1 2 Gnd  GND 6           O  X1 3 N4 O  12Vdc   Customer IN 2   Function on request  to be defined on purchase   X1 4 Gnd  GND 6           O  X1 5 IN  4 O  3 3Vdc   Battery Temperature  If connected  the battery charger current is temperature dependent  X1 6 Gnd  GND 6              O  X1 7 IN  4 O  12Vdc Remote shutdown  Do not remove the factory mounted bridge until an external remote shut down is  X1
21.  b  The BYPASS LED is green  gius 2    c  The LCD displays MANUAL BYP IS CLOSED     Powering down a UPS module    ee    When the load is connected to the maintenance bypass supply  as described  above  the UPS module s  can be totally powered down  for example  if required  for maintenance testing  using the following procedure     Note  Carry out the following procedure on each UPS module in a parallel system   6  Onthe UPS control panel simultaneously press both ON OFF buttons     a  TheLCD panel will indicate  LOAD OFF  SUPPLY FAILURE     7  Open the fused battery isolator for the UPS module in the UPS cabinet or in LINE 2 BY PASS  the external battery cabinet rack  as applicable                                   LOAD  WARNING  The UPS module cabinets are still live at the input LINE 1 INVERTER  and output power terminals due to the closure of maintenance    bypass switch        BATTERY  WARNING  The load is now supplied from the bypass mains  and is not protected against power failure     4 5 4 Complete system shutdown    If the load does not need power for an extended period of time the UPS system can be shutdown completely using the  following procedure     WARNING  All the operations in this section must be performed by authorised and trained personnel     CAUTION  This procedure will totally disconnect load power  Ensure that it is safe to lose power to all the  loads connected to the UPS system before you begin this process     pp      1  Isolate all load equipment c
22.  battery cabinet rack  as applicable   5  The UPS module is now totally shut down  ENE BATTERY  6  Remove the two screws on the front of the UPS module that are fixing it to  the cabinet     7  Using the two black handles  pull the UPS module forwards until the rear  connectors are disconnected  DO NOT FULLY EXTRACT THE UNIT     A WARNING  Wait at least 2 minutes to allow the module   s electrolytic capacitors time to discharge     8  After two minutes  fully withdraw the UPS module from the cabinet by pulling it horizontally     9  If you are not intending to replace the UPS module immediately  fit a blanking cover over the UPS compartment  opening and secure it in place using the screws removed earlier     4 7 2 Refitting the UPS module    1  Remove the blanking cover  if fitted      2  Using two people  lift the UPS module and slide it two thirds of the way into the UPS compartment  make sure not to  plug the UPS module into the rear connector      3  Push UPS module firmly into its final position  to assure good contact on the rear plugs     A    Secure the module in place using the screws removed earlier   Start the UPS module and bring it on line  See paragraph 4 5 2      ge    4 8 Replacing a UPS module in a CAPACITY multi module system    WARNING  All the operations in this section must be performed by authorised and trained personnel         serious injury or damage  We recommend that the modules are handled by two persons at all times   Always employ suitable liftin
23.  contact your nearest service agent or call Uninterruptible Power Supplies Ltd  on 0800 731 3269     6 2 Menu  Commands  Event Log  Measurements     A detailed description of the Menu  Commands  Event Log and Measurements that can be operated and displayed on the  LCD panel can be found in paragraph 4 3     6 3 Fault Identification and Rectification Messages and Alarms       Alarm Condition   Meaning Suggested Solution  UPS FAULT There is a fault in the UPS and therefore normal Call the authorised service centre for  operation cannot be guaranteed  assistance     Fi IMS BYF   RECT FALLT   Mains power supply is outside prescribed tolerance    The input power to UPS is high low or missing   If site power appears to be OK  check the input  circuit breakers etc  supplying the UPS     OUTPUT SHORT There is a short circuit at the UPS output  Check all output connections and repair as  required   OVERLOAD Load exceeds the UPS rated power  Identify which piece of equipment is causing    the overload and remove it from the UPS    Do not connect laser printers  photocopiers    electric heaters  kettles etc  to the UPS   OVER TEMPERA TURE UPS temperature has exceeded the allowed value    Check the ambient temperature of the UPS is   less than 30   C    If the ambient temperature is normal call the   authorised service centre for assistance   BATTERY CHARGER OFF   The attached battery and the battery charger set up   Call the authorised service centre for    do not correspond or battery 
24.  of battery blocks into the UPS control system  using  the control panel Service Set Up menu  when the system is commissioned        22 UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Supplies Ltd ta      KOHLER COMPANY 3  Installation                                                    o o    e   de dz   lt   lt   N N  x x  o o       d dm Ec       lt   lt   lt   lt   lt   n  N N N N  x x x x x  o o o o o                                    Aak    L1  P ESSE EE EE EE 3C  fefe is joo O c  le lejeje e ejere   e i                                                                                                                                                                                              fo     UPS Mod  1 UPS Mod  2  Fused battery isolator Fused battery isolator  1x10kVA Module fitted 1x20kVA Module fitted 2x20kVA Modules fitted   1 x 40  7Ah Batteries  1 x 50  7Ah Batteries  2x40  7Ah Batteries    Figure 3 10 ST 40 Cabinet internal battery configuration       UPS454 01 02 PW8000DPA User Manual    01 12 13  23    Uninterruptible    Supplies Ltd ta                                     3  Installation A KOHLER COMPANY  Es   a          UPS Mod  1 UPS Mod  2 UPS Mod  3  Fused battery isolator Fused battery isolator Fused battery isolator  1x10kVA Module fitted 2 x 20kVA Module fitted 3 x 20kVA Module fitted 3 x 20kVA Module fitted  1x 2 x 40  7Ah Batteries 2x 2 x 40  7Ah Batteries 3x 2 x 40  7Ah Batteries 3x 1 x 50  7Ah Batteries  Figure 3 11 ST 60 Cab
25.  power and charged A 15 2 30 4  battery per Module  output Cos    1 0   Max  Input Power with rated output power and discharged kW 11 5 23  battery per Module  output Cos    1 0   Max  Input Current with rated output power and discharged A 16 6 33 3  battery per Module  output Cos    1 0    8 4 Battery Characteristics   10kVA UPS Module 20kVA UPS Module   Variable Number of 12V Battery Blocks No  24 50   36 50    Maximum Battery Charger Current A 4A 4A    Battery Charging Curve  Temperature compensation  Battery Test   Battery Type       Ripple free  IU  DIN 41773   Standard  temp  sensor optional   Automatic and periodically  adjustable   Maintenance free VRLA or NiCd    Depending of the effective load in kW used by the module          8 5 Battery Capacity Usage               10kVA UPS Module 20kVA UPS Module  Number of battery blocks 24 28 30 34 50 36 40 40 48 50  Max  Power in KW 8 8 10 10 16 20 16 20  Max  autonomy  min   999 5 999 5 5 999 999             56    UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Powerm  Supplies Ltd      KOHLER COMPANY 8  Specification       8 6 Heat Dissipation Per Module With Non Linear Load                        10kVA UPS Module   20kVA UPS Module  Heat dissipation with 10096 non linear load per module W 550 1100   EN 62040 1 1 2003  BTU h 1887 3745  Airflow  25     30  C  with non linear load per module m3 h 150 150   EN 62040 1 1 2003   Dissipation at no load Ww 130 170  8 7 Output Characteristics  10kVA UPS Module
26. 0  ST 80  ST 120 Power cable and connection sizes  14 UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Supplies Ltd t 3  Installation      KOHLER COMPANY                                  ST 200  External Batt  2L1 2L2 2L3  2N  Cabinet  lelelelele   lTelelelele  elelelele  Die g  s     llelele  e    Offs l eleleil e                  Common Single Dual 5   Battery Feed O O O O  Links Links   1L1 1L3   Input Mains  PE  Protective  safety  earth   2L1 2L3   Bypass Mains  Dual feed only    3L1 3L3   Output to Load   PE   Protective Earth    N  Nawta Bypass Mains Supply  Dual input feed only   External Batt     left        lord    Remove links for Dual input   NOT NEUTRAL LINK     Remove links for separate  battery installation and connect  batteries to individual terminals     Note that when using individual  batteries  each battery is  connected to two UPS modules           UPS Output  load supply     oz  B   lors  zv  Tor   v  OH  2  CO  IE    UPS Input Mains Supply                               UPS Separate Battery Common Battery Input Bypass Input Rectifier Output Load  Range    N     3 N   3 N PE   3 N PE   ST 200 5 x 35   T  3 x  2x M10   B    3 x M12  B  4 x M12  B  4x M12  B    1 batt feeds 2 modules   PE 1 x M10  B   PE 1x M12  B   PE 1x M12  B   PE 1x M12  B   Notes     1  Fuse and Cable recommendations to IEC 60950 1 2001    2  The fuse and cable rating details in the above tables are a recommendation only    3  The UPS must be installed to prescrib
27. 20kVA Example   TO UPS BATTERY ISOLATORS    EXTERNAL BATTERY CABINET                                                                                                                                                                               a P a P p a   444 ZZZZZZ   06061101           5 S KHANMTNO     QN m s lO 0     Om s 1 0  vB vg vg vg vg wg X000 vm s s53 222222232  523  23 35 35 35 35 SOTTO 909909099 99009932  S v Sod REA Lu EL 900000000000009009  Fa Fa Fa 5e ga S B  ZAEZEAE2E  EZ2E  E2z2zLIL  2z222l  L2 22 Po pe P    2 LLLLLL LAL LLL OLA Lee  A g A    aes af ad ae 555555 555555555555   z    zb      2     EmL  mL   f2f      je NIN ain tiv uu oo  OlOJO  OOJO OO OO OJIOO Ooo CJOJOJO OJO OJOJOJOJO O   OJOO   OJO Ooo OIO O  OOI O OC  OJOIOJO OJO oloo ojo  OJOJO  OOO O00 Oloo OO  OOJO OJIOIOJOIOO OIOOOO O         PE PE  For reasons of clarity  the wiring for modules 1 3 5 only is shown in detail  EXTERNAL BATTERY CABINET UPS CABINET  120kVA Example   TO UPS BATTERY ISOLATORS   p e a  gt  p Hp        ZZZZZZII11I 11      5 Es    5 E     Noms ini SENMENN     o m st  0  v3 v3 v8 vg v3 98 9002020 o9o u oZuooguoxo  az  Bz 22 22 22 Zs Sopop 9009999999993  EDO ef d ep cep pp 2232223 222222 2222z2Z  oS oS aS oS os os   EZ   2 2127 Zu2 E72   2 LLLLLL SLO LOL LLALeR  ae ae ac ae ao ae 222525225 555 555 555555     z  z    z     f2    zb  zl    je Cx  ex  ex ewm tjt uu ooo   IO ojojo O  OjO OJ DO   DOO Oloo OQOQO  OO O  OJO O   OJO O   OJOIO   O OIO   OIOJO  IOJOJO ololo lololo OJO OJO 
28. 4 5 2      How to transfer the load to the maintenance bypass      See paragraph 4 5 3       How to shut down the entire UPS system  See paragraph 4 5 4      4 5 1 Starting the UPS system from the maintenance bypass    This procedure describes the sequence of operations necessary to power up the UPS module s  whilst the load is  connected to the Maintenance Bypass supply  and then transfer the load to the UPS Inverter s    On Line  mode      personnel       WARNING  All the operations in this section must be performed by authorised and trained    Prior to powering up the system  check and confirm the UPS system status       The load is supplied via the closed maintenance bypass switch  IA1      All UPS modules are powered down     Powering up the UPS module s      Perform steps 1 3 below on each UPS module     1     Close the fused battery isolator for the UPS module in the UPS cabinet  or in                             LINE 2 BY PASS   the external battery cabinet rack  as applicable    a  The UPS mimic panel LINE 1 LED will be permanent green  LOAD  b  The BATTERY LED will be flashing green  push INVERTER             c  TheLCD display will indicate LOAD OFF  SUPPLY FAILURE     E  BATTERY    On the UPS control panel press and release both ON OFF buttons LINE 2 BY PASS  simultaneously then wait 60 seconds       RE nn DERI   a  The UPS module will begin to power up    Lio  b  Initially LINE 2 LED will be red  then change to green     c  Atthis stage the LCD display will indica
29. 54 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Power   Supplies Ltd    A KOHLER COMPANY    7  Options         Options    7T 1 Introduction    The PW8000DPA ST UPS has the following available options       Remote emergency stop facilities    Generator ON facilities      1xCustomer input function  customer defined     WaveMON shutdown and management software    SNMP Card for network management and remote monitoring      Modem Ethernet interface for PowerReporter    management software    7 2 Remote emergency stop       The remote emergency stop facility takes  the form of a normally closed contact  which opens to operate the emergency  stop sequence     On leaving the factory the remote  emergency stop function is disabled and it  must be activated by a hardware code on  the SETUP SERVICE menu  Please  contact your distributor to enable this  operation if required     The remote shutdown facility is connected  to terminal port X1 7     X1 8 on the  communication card located on the  PW8000DPA ST front frame     In order to allow the safe removal   maintenance or testing of the remote  emergency stop device  without affecting  the UPS operation  it is recommended that                                                          a terminal block with linking facilities is  installed between the UPS and the remote  emergency stop mechanism     Remote shutdown  UPS Remote  Shutdown Port        X1 7  X1 8    Terminal block    Figure 7 1 Remote emergency stop cabling  
30. ANY 2  General Description       LS    pee ge hw hoe uer vu    repr pru Ere pc pr EIE vL En peg                                                                                                                 ST 40 Cabinet ST 60 Cabinet ST 80 Cabinet ST 120 Cabinet ST 200 Cabinet  2x20kVA modules 3x20kVA modules 4x20kVA modules 6x20kVA modules 10x20kVA modules  80 Batteries 240 Batteries No Batteries No Batteries No Batteries    Figure 2 1 PW8000DPA ST module configuration    2 4 Advanced Design Features    2 4 4 Input booster technology    The UPS module s inbuilt advanced booster technology results in a perfect sinusoidal input power quality at 0 99 input  power factor with a harmonic content of 3  THD i   This leads to a more reliable total system operation and savings in  generator and transformer sizing as losses in the windings are minimised  It also means that traditional harmonic filters  are no longer required   The high power factor presented by the UPS on the incoming mains supply minimises cabling and fusing costs due to the  resulting lack of reactive power consumption  This  together with the accompanying low harmonic currents  provide the  following benefits      No additional losses in wires and cables      Noextra heating of transformers and generators      Noover sizing of generators      No false circuit breaker tripping and malfunction      Noerratic operation of computers  telecommunication  monitors  electronic test equipment etc      Noresonance with pow
31. D displays are as illustrated here         EN    9  The UPS is now operating in its on line mode  The load is protected and    supplied by inverter power  ENSE BATTERY        T  4 5 2 Individual UPS module start stop procedure    If a multi module system is designed with built in redundancy  it is possible to stop and start one UPS module without  affecting the operational status of the overall system     i e  one UPS module can be taken off line whilst the remaining  modules remain operating in their on line mode and maintain a protected load supply     A WARNING  All the operations in this section must be performed by authorised and trained personnel     UPS module shut down   Use this procedure to power down one module in a redundant module system     1  Simultaneously press the two ON OFF buttons on the UPS control panel                 LINE 2 BY PASS  a  The LED display will give the indications shown    i   LOAD  2  Open the fused battery isolator for the UPS module in the UPS cabinet or in E      LINE 1 INVERTER  the external battery cabinet rack  as applicable  E       3  The UPS module is now totally shut down     mE BATTERY    WARNING  Although the UPS module is shut down it is still    connected to the input bypass mains     UPS module start up   Use this procedure to start a UPS module and connect it to a multi module system that is already running     1  Close the fused battery isolator for the UPS module in the UPS cabinet or in the external battery cabinet rack
32. Description of symbols used in this manual    WARNING  The warning symbol is used where there is danger of an electrical shock  equipment damage or  personal injury     CAUTION  The caution symbol is used to highlight important information to avoid possible equipment  malfunction or damage      gt   gt             2 User precautions    WARNING  Keep this manual with the UPS for future reference     WARNING  The UPS and peripheral equipment must be installed and commissioned by suitably qualified and  trained personnel who are aware of the potential shock hazards     WARNING  Do not attempt to install this UPS system until you are satisfied that ALL the safety instructions and  hazard warnings contained in this manual are read and fully understood     WARNING  High leakage current   Ensure that the UPS has been correctly earthed before you connect the mains power supply     WARNING  This UPS must not be started up or put into use without having first been commissioned by a fully  trained engineer authorised by the manufacturer     WARNING  All servicing must be performed by qualified personnel  Do not attempt to service the UPS yourself   You run risk of exposure to dangerous voltages by opening or removing the UPS covers  Uninterruptible Power  Supplies Ltd will assume no responsibility nor liability due to incorrect operation or manipulation of the UPS     WARNING  The PW8000DPA ST is a Class A UPS product  according to BS EN 62040   In a domestic  environment the UPS may ca
33. Installation       Dual Input Feed  Refer to the schematic drawing and connection table in Figure 3 8     1  The UPS is supplied  as standard  with facilities for a single cable feed for the rectifier and bypass supplies  For a dual  feed configuration remove the links between 1L1   2L1  1L2   2L2  and 1L3   2L3 on the Input Terminal Block  See  Figure 3 5   Leave the Neutral link connected between 1N   2N     2  Connect the UPS input supply cables to terminals 1L1  1L2  1L3 and 1N on the UPS main terminal block  See Figure  3 5   Ensure correct  clockwise  phase rotation     A CAUTION  The input Neutral cable must ALWAYS be connected     3  Connect the UPS bypass supply cables to terminals 2L1  2L2  2L3 and 2N on the UPS main terminal block  See  Figure 3 5   Ensure correct  clockwise  phase rotation     A CAUTION  The bypass Neutral cable must ALWAYS be connected     4  Secure the cables to the fixing rail located under the UPS connection terminals     Note  The UPS commissioning engineer will configure the UPS system for a dual input operation at the time of  commissioning        UPS454 01 02 PW8000DPA User Manual    01 12 13  1 7    Uninterruptible    Power   Supplies Ltd    3  Installation A KOHLER COMPANY                                                                                                                                                                                  L1        e    Main  12     ains  INPUT UPS  CABLE TERMINAL  Single Feed Links ile _  Phase 
34. L2 1L2  Phase L3 1L3  NEUTRAL 1N  EARTH PE  IL1 IL2 IL3 1N PE 2L2 2L3 2N PE  F2    o  tifier    Rectifier a  3 3    8  2     5 o  n   2    Static Switch Static Switch  Maintenance Bypass IA1  UPS CABINET OUTPUT UPS  Y CABLE TERMINAL  3L1 3L2 3L3 3N PE Phase L1 3L1  Phase L2 3L2  D D D D D Output Phase L3 3L3  Supply NEUTRAL 3N  1 l I ii EARTH PE  Fuse A  A  Cable A  mm   Cable D  mm    ST 40 3 x 80 5x 16 5 x 16  ST 60 3 x 125 5x35 5x35  ST 80 3 x 160 5x50 5x50  ST 120 3x224 4x95  1x50 PE  5x70  ST200 3x350 5 x 185 5 x 185             Fuse and Cable recommendations to IEC 60950 1 2001  The fuse and cable rating details in the above tables are a recommendation only   The UPS must be installed to prescribed IEC or local regulations  e g  BS7671 2008     Figure 3 7 UPS with Single Input Feed   Connection block diagram       1 8 UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Power   Supplies Ltd    A KOHLER COMPANY    3  Installation                   L1     Mains Supply L1     Bypass Supply  L2        L2  L3           L3  N N  PE PE  Fuse B     Fuse C                        IL1             IL2 IL3          1N PE                      2L1 2L2 2L3 2N PE                      F1             F1            F2                   Rectifier                           Inverter                    Rectifier          UPS Module 1      Inverter                UPS Modules 2   6             Static Switch          Static Switch                      Maintenance Bypass IA       
35. OJO  OO o  OO oe OIO O   DI OIlO OQOO OO O Oloo                                                                                           o O ei                olojo  O O O  ie                    Figure 3 13 External battery cabinet connection  ST 120 Cabinet shown     Figure 3 13 shows typical methods for connecting the UPS cabinet  ST 120 in the example  to an external battery  installation  The top diagram illustrates connection for an    individual battery    installation  and the lower diagram shows a     common battery    installation     A similar connection diagram for the ST 200 cabinet is shown in Figure 3 14  Note that the ST 200 cabinet only contains  connections for five external battery strings  however each connection is wired to the battery circuit breakers of two UPS  modules  Therefore where an    individual battery    configuration is used with the ST 200 each battery is in fact connected to  2 UPS modules  rather than an individual module as is the case for the lower powered cabinets        26    UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Supplies Ltd ta      KOHLER COMPANY    3  Installation       EXTERNAL BATTERY CABINET    for UPS Module 1 2  for UPS Module 3 4  for UPS Module 5 6  for UPS Module 7 8  for UPS Module 9 10    Battery fuse  Battery fuse  Battery fuse  Battery fuse  Battery fuse                                                          EXTERNAL BATTERY CABINET    for UPS Module 1  for UPS Module 2  for UPS Module 3
36. P adapter  connected to the UPS RS232 output  JD1      An SNMP Ethernet adapter contains an RJ 45 connector which allows it to be connected to the network using a standard  network cable  Once connected  the UPS Management software agent  which is already installed in the SNMP adapter   then monitors the UPS operating parameters and outputs its data in SNMP format to the connected network  In a multi   module UPS system the SNMP interface can communicate  system wide  data or data for an individual UPS module     The SNMP adaptor requires a PC with terminal connections  and for normal operation at least one network connection   Ethernet  is also required          External SNMP Adapter    SNMP MONITOR         mui                Figure 7 3 SNMP Internal and external adapters       50 UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Supplies Ltd ta      KOHLER COMPANY T  Options       7 4 2 The importance of UPS management    The utility supply is inevitably unreliable every now and then  and assuring continuous power to all the facilities connected  to it can be a difficult task  The situation is further complicated if worldwide systems are managed via a Local Area  Network  LAN  or Wide Area Network  WAN      However  by using the PW8000DPA ST UPS system in conjunction with purpose designed network management tools  a  systems administrator can take measures to back up data and prevent system errors or data loss even in the event of a  relatively long util
37. T multi module system    WARNING  All the operations in this section must be performed by authorised and trained personnel     serious injury or damage  We recommend that the modules are handled by two persons at all times   Always employ suitable lifting aids and safety platforms where possible        WARNING  A UPS module weighs up to 22kg  If the UPS module is handled inappropriately it might cause    If a UPS module is faulty in a redundant multi module system  the load will continue to be protected by the remaining  modules which will continue to operate in the on line mode  Under these circumstances the faulty module may be  replaced without having to transfer the load to bypass        42    UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Power   Supplies Ltd    A KOHLER COMPANY 4  Operation       4 7 4 Extracting the UPS module    1  Identify the faulty UPS module with the alarm condition and RESET the alarm  The audible noise will stop  If the red  ALARM LED remains on  there is a fault in the module     Verify that load is being supplied by the other module s  by checking that their LCD panels show LOAD PROTECTED                                   3  On the UPS module to be replace  simultaneously press the two ON OFF LINE 2 BY PASS  buttons on the UPS control panel   a  The mimic indications should be as illustrated here  LOAD          LINE 1 INVERTER  4  Open the fused battery isolator for the UPS module in the UPS cabinet or in    the external
38. UPS electrical installation and operating environment     Perform a controlled UPS start up      Fully test the UPS system for correct operation and set up      Carry out operator training     Ltd approved engineer must be considered as an electrical hazard  and Uninterruptible Power Supplies  Ltd  will accept no responsibility for its safe operation or the safety of any operating personnel   Furthermore  the manufacturer s warranty will be invalidated immediately if the UPS is powered up or used  before it has been correctly commissioned     WARNING  Any PW8000DPA ST UPS system not commissioned by an Uninterruptible Power Supplies    4 2 UPS control panel    Figure 4 1 illustrates the control panel located on the front of each UPS module     Power Management Display  PMD     Control Menu Navigation Mimic LED Indicators ALARM LED Module ON OFF  and selection keys and RESET key Keys       Figure 4 1 UPS control panel       UPS454 01 02 PW8000DPA User Manual    01 12 13  31    4  Operation    Uninterruptible    Power   Supplies Ltd    A KOHLER COMPANY       4 2 1 Power Management Display  PMD     The 2 x 20 character LCD Power Management Display simplifies communication with the UPS and also provides UPS  monitoring information  See paragraph 4 3      The menu driven LCD enables the operator to       Access the    event register         Monitor the input and output voltage  current  frequency  amp  power      Monitor the battery run time      Perform commands such as UPS start 
39. Y OFF   Normally closed      Serial ports RS232 on Sub D9    USB  Slot for SNMP    Slot for PowerREPORTER       1 x LCD display for each module  RJ45 Plug  for future options     5 Voltage free contacts  For remote signalling and automatic computer shutdown    1 x Remote Shut down  EMERGENCY OFF  normally closed    2 x Programmable Customer Inputs  1st  default as GEN ON  normally open   2nd  free  normally open   1 x Temperature sensor for battery control  1 x 12Vdc output  max 200mA   2 x Programmable Customer s Inputs   15t default as GEN ON  Normally open    2nd free Programmable Customer s Inputs  Normally open   1 x system frame  For monitoring integration in network management and service  1x For monitoring and software management  SNMP card  optional   For monitoring and integration in network management  For monitoring and integration in network management  PowerREPORTER card  optional  for Premium Power Protection             UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Supplies Ltd ta      KOHLER COMPANY    8  Specification       8 11 Fuses  amp  Cables Quick Reference    SINGLE INPUT FEED  standard        i    BATTERY  CABINET       Inverter    Mains  3x400 230V     c  ED   E  o   o  z  o  Q  D    Static Switch    Static Switch    UPS Modules 2   5    UPS Module 6    Static Switch    Maintenance Bypass IA1    UPS CABINET    Cabinet Mounted     Single Input Feed                               Input 3x400V 230V Output 3x400V 230V  Fuse A  Agl
40. a      KOHLER COMPANY       4 3 8 Set up User menu screen    1  Set up language    2  Set up Date and Time    3  Set up battery test    4  Set up operation with Gen Set    4 3 9 Set Up Service menu screen    1  This Menu is reserved for authorized service engineers only     2  Type in password           gt  SET LANGUAGE  SET DATE AMD TIME       ENGL TSH  FRANCAIS  DEUTCH  DUTCH  SPAMTISH  FOL ISH    FOR TOGUESE           gt  SET UP DATE    TIME  SET UP BATT  TEST       0 H  v    HH HIM zz            1 31      gt  SET UP BATT  TEST  SET UP GEH SET OPER           CH 23  gt     HOJE OF DAY       BEE    REPETITIVE  teh       gt  SET UF GEN SET OPER        YM     BATT  CHARGE LOCK       ee B       BYPASS LOCK     gt  SET UF SERVICE  PASSHORD                 gt  PhrHSSH  RDE                36    UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Powerm  Supplies Ltd                     KOHLER COMPANY 4  Operation  4 4 Operating modes  4 4 4 On line  inverter  mode LINE 2 BY PASS     When the UPS is operating in the on line mode  the load is supplied LOAD  through the LINE 1  RECTIFIER  and INVERTER  This provides the LINE 1 INVERTER    highest degree of protection  especially in the event of a mains  disturbance or failure  and is always recommended if the critical load   e g  computer systems  will not tolerate even very brief supply  interruption     In the event of an inverter fault  or overload condition  the UPS  transfers the load to the bypass supply autom
41. and cable rating details in the above tables are a recommendation only    3  The UPS must be installed to prescribed IEC or local regulations  e g  BS7671 2008    4  DC Cables and Battery fuses are bespoke to the installation        60 UPS454 01 02 PW8000DPA User Manual    01 12 13     
42. ass mode    The maintenance bypass mode is effected by means of the IA1 BYPASS SWITCH on the front of the UPS        Switch IAT   Effect       ON Maintenance Bypass Switch Closed  Load on bypass mains    CLOSED  LCD indication  MAINTENANCE BYP CLOSED   LED Indicators will indicate as shown in the table below   OFF Bypass Switch Open     Normal operating condition  Load on inverter    OPEN  LCD indication MAINTENANCE BYP OPEN   LED Indicators will indicate as shown in the table below                 LED Indicator   Switch IAT ON Switch IAT OFF  LINE 1 Green Green  LINE 2 Green Green   BYPASS Green ON  INVERTER RED ON  BATTERY Green Green             UPS454 01 02 PW8000DPA User Manual    01 12 13     37    4  Operation    Uninterruptible    Power   Supplies Ltd    A KOHLER COMPANY       mains disturbance or failure  and we therefore strongly recommend that you switch over to the on line or on        CAUTION  When the UPS is operating on maintenance bypass the load is not protected in the event of a    bypass mode as soon as possible     4 5 Operating Instructions    Under normal operating conditions all the modules in a multi module system are running and operating in the on line  mode  See paragraph 4 4 1      The following procedures are provided in this section       Howto start up the UPS system and transfer the load from the maintenance bypass to the on line mode   See paragraph 4 5 1       How to stop start one UPS module in a redundant multi module system  See paragraph 
43. atically and without  interruption   transfer time   0      4 4 2 On bypass  line interactive  mode    In the on bypass  line interactive  mode the load is normally supplied  from the bypass mains  LINE 2  and the static BYPASS  In the event  of a bypass supply failure the load is automatically transferred to the  inverter within 3 to 5 msec   this is valid for single and parallel module  systems  The battery charger remains active in this mode     Although the on bypass mode offers greater efficiency than the on line  mode  it is recommended only if the load can tolerate interruptions of  up to 3 5 ms  which is the transfer time taken when switching from the  on bypass mode to the on line mode     4 4 3 Maintenance bypass mode    Each cabinet is fitted with a maintenance bypass switch  IA1   which  when closed  connects the UPS module s  output terminals  directly to the UPS bypass mains supply  This facility allows the  UPS system to be shut down for maintenance or repair whilst  maintaining the load on the raw  unprotected  bypass supply     mode before the maintenance bypass switch is    WARNING  ALL the UPS modules in a parallel  A module system must be selected to on bypass  operated closed     Maintenance bypass switch  IA1         E BATTERY    L    T    Figure 4 2 On line mode       LINE 2 BY PASS       00 0        0   LOAD  LINE 1 INVERTER                    BATTERY    Figure 4 3 On bypass mode    MAINTENANCE Switch IA1  BYPASS    UPS       Figure 4 4 Maintenance byp
44. charger fault  assistance   INVERTER FAULT Inverter is faulty  Call the authorised service centre for  assistance   SY HCHROM FAULT The inverter and mains are not synchronised  The frequency of the input voltage to the UPS is    outside operational limits and the UPS static  bypass has been temporarily disabled           BATTERY IM DISCHARGE   Battery is near end of autonomy  Shutdown load connected to UPS before the  UPS switches itself off to protect its batteries   KIAMUAL BP IS CLOSED   Maintenance Bypass closed  This alarm is only displayed if the UPS is on  Load supplied by raw bypass mains  Maintenance Bypass           UPS454 01 02 PW8000DPA User Manual    01 12 13  47    6  Troubleshooting    Uninterruptible    Power   Supplies Ltd    A KOHLER COMPANY       6 4 Contacting Service    Uninterruptible Power Supplies Limited has a service department dedicated to providing routine maintenance and  emergency service cover for your UPS     If you have any queries regarding your UPS please contact us     Uninterruptible Power Supplies Ltd   Woodgate   Bartley Wood Business Park   Hook   Hampshire   RG27 9XA    Tel  01256 386700  0800 731 3269  24 Hr      Fax  01256 386701    Email  service  upspower co uk    We recommend that your UPS is protected by an Extended Warranty Agreement     see Section 2 for details  These  agreements assist us in caring for your UPS correctly  ensuring that it is well maintained and attended to promptly should  any problems occur        48    UPS4
45. charging the batteries  For longer term storage the battery should be fully recharged every 6  months  20  C     Extreme temperature  under charge  overcharge or over discharge will destroy batteries     Key Point  Note the following       Charge the battery both before and after storing     Always store the batteries in a dry  clean  cool environment in their original packaging     Ifthe packaging is removed protect the batteries from dust and humidity       CAUTION  Sealed batteries must never be stored in a discharged or partially discharged state     3 6 Positioning    3 6 1 Planning the installation    A certain amount of pre planning will help ensure smooth  trouble free equipment installation  The following guidelines  should be taken into account when planning a suitable UPS location and environment     1  The equipment must be installed and transported in a upright position     2  The floor at the installed location and en route from the off loading point must be able to safely take the weight of the  UPS and battery equipment plus fork lift during transit     3  The UPS cabinet requires space to bottom front and back to enable cooling airflow  Suitable ventilation airflow must  also be provided  See Figure 3 1   Allow a 200mm minimum clearance at the back of the cabinet     4  All parts of the UPS required for maintenance  servicing and user operation are accessible from the front  Reserve a  minimum of 900mm space at the front of the UPS cabinet     5  Anambient te
46. d on the nameplate which is situated at the front  internal  door  of the UPS     Check that the details on the nameplate corresponds to the purchased material detailed on the delivery note     3 4 Batteries    The standard batteries connected to the UPS are sealed  maintenance free batteries which will be mounted either within  the UPS cabinet or an external battery cabinet  The battery will usually be connected when the UPS is commissioned     Battery life depends very much on the ambient temperature  and optimum battery life will be obtained if the batteries are  operated at a temperature of 20  C     If the UPS is delivered without batteries  Uninterruptible Power Supplies Ltd is not responsible for any damage or  malfunctioning caused to the UPS by the incorrect storage  installation or connection of batteries by third parties        8 UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Powerm  Supplies Ltd      KOHLER COMPANY       3 5 Storage  3 5 1 UPS    If you plan to store the UPS prior to use  store it in a clean dry environment with a temperature between  5  C to  40  C  and RH of less than 90   If the packing container is removed  you must protect the UPS from dust     3 5 2 Battery    The UPS utilizes sealed  maintenance free batteries  whose storage capability depends on ambient temperature  It is  therefore important not to store the UPS for longer than 6 months at 20  C  3 months at 30  C or 2 months at 35  C storage  temperature without re
47. dules                                 LINE 2 BY PASS LED         Colour      LINE 1 Green  LOAD LINE 2 Green  LINE 1 INVERTER  paa   BY PASS OFF    INVERTER Green  EEH BATTERY BATTERY Green      The LCD panel should display LOAD PROTECTED  If anything other than LOAD PROTECTED is displayed then  press the RESET button  and if LOAD PROTECTED is still not displayed there is a problem with the UPS system and  you should seek assistance     Transferring the UPS to the on bypass mode   1  On the control panel  of any one module in a multi module system    a  Press the UP key once to access the menu system   b  Use the UP DOWN keys to move the cursor so that it is adjacent to COMMANDS and then press the ENTER key   c  Use the UP DOWN keys to move the cursor so that it is adjacent to LOAD TO BYPASS then press the ENTER key     The UPS system will transfer the load to static bypass     on all UPS modules in a parallel system   3  Onall UPS module check and confirm that     LINE 2 BY PASS  a  The INVERTER LED has extinguished     A I NI  b  The BYPASS LED is green  LOAD  c  The LCD displays LOAD NOT PROTECTED  yu INVERTER                EEE BATTERY       40    UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Powerm  Supplies Ltd         KOHLER Company 4  Operation  Closing the maintenance bypass switch   4  Close the maintenance bypass switch  IA1   UNE2 BVPASS  5  On all UPS module check and confirm that      A D   N  a  The INVERTER LED has changed to red  LOAD 
48. e     9  After two minutes  fully withdraw the UPS module from the cabinet by pulling it horizontally   10  If you are not intending to replace the UPS module immediately  fit a blanking cover over the UPS compartment    opening and secure it in place using the screws removed earlier     4 8 2 Refitting the UPS module    1   2     Remove the blanking cover  if fitted      Using two people  lift the UPS module and slide it two thirds of the way into the UPS compartment  make sure not to    plug the UPS module into the rear connector      Push UPS module firmly into its final position  to assure good contact on the rear plugs     Secure the module in place using the screws removed earlier     Start the UPS module and transfer the system from the maintenance bypass back to inverter  See paragraph 4 5  1         44    UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Powerm  Supplies Ltd      KOHLER COMPANY 5  Maintenance       5 Maintenance    5 1 Introduction    A WARNING  All the operations described in this chapter must be performed by suitably qualified personnel     5 2 System calibration    To ensure optimum UPS operation and efficient load protection we recommended that the system   s operating parameters  are checked every six months and recalibrated where necessary  The batteries should also be checked every six months   depending on the ambient temperature     5 3 User responsibilities    There are no user serviceable parts contained within the UPS 
49. ed IEC or local regulations  e g  BS7671 2008    4  DC Cables and Battery fuses are bespoke to the installation     Figure 3 6 ST 200 Power cable and connection sizes       UPS454 01 02 PW8000DPA User Manual    01 12 13     15    Uninterruptible    Power   Supplies Ltd          3  Installation A KOHLER COMPANY   3 8 Connecting the UPS input supply   WARNING  Opening or removing the UPS enclosure covers will create the risk of exposure to  dangerous voltages if power is connected to the UPS    3 8 1 Safety notes   Please ensure you read and understand the following safety notes before you begin the UPS electrical installation    1  All operations detailed in this section must be performed by an authorised electrician or qualified personnel    2  Once the electrical installation is completed the initial UPS start up and commissioning must be performed by  qualified personnel authorised by the manufacturer    3  Do not operate the UPS if there is water or moisture present    4  When carrying out any work on the UPS input power cables you must ensure that the UPS supplies are isolated at the  supply distribution panel and  where possible  locked out  Warning notices should be posted where applicable to  prevent inadvertent operation of the input supply isolators    3 8 2 Preparing the input cabling   Before you start connecting the UPS input cables      Ensure that the provided fuses and cables satisfy the ratings shown in Figures 3 3 to 3 5  and are in accordance  with the presc
50. ee phases     DLITFLIT CURRENT  Ase  a  BA ga nmg  cao ca    10  Output Current  all three phases        34 UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Supplies Ltd me      KOHLER COMPANY 4  Operation                               11  Active Output Power  all three phases  ACTIVE POWER  KH    56 66 66 56 8e 88  i REACTIVE POHER    12  Reactive Output Power  all three phases  sk VA    56 66 66 56 88 88   13  Apparent Output Power  all three phases  APPARENT POHER   RMA  GE 66 85 668 86 06   14  Output Power  all three phases  OUTPUT POWER 6x5  48 66 86 68 88 08   i LE   15  Battery capacity B    T T CAPACITY t7   gea  ca             4 3 5 Commands menu screen    1  Transfer Load to inverter  LOAD TO BYPASS          2  Transfer Load to bypass   gt  LOAD T   BYPASS      PERFORM BATT  TEST                3  Battery Test  gt  PERFORM BATT  TEST    4 3 6 UPS Data menu screen                         1  These general UPS Data are installed at the manufacturing plant  UPS SERIAL NUMBER  TiTi    TiTiTITITI   2  Manufacturing date DATE OF MANUFAC TURE  15 63 69   3  EPROM Version EPROM VERS TOM  VE   4  Actual Date and Time DATE TIME  ddr ya hh mm ss             4 3 7 Set Up Service menu screen             1  This Menu is reserved for authorized service engineers only  2 SET UP SERVICE  PARSSIN  OFTI  i  gt  FAaSSH  ORTX  2  Type in password pz                UPS454 01 02 PW8000DPA User Manual    01 12 13  35    4  Operation    Uninterruptible    Supplies Ltd t
51. er factor correction capacitors        UPS454 01 02 PW8000DPA User Manual    01 12 13  3    Uninterruptible    Power   Supplies Ltd    2  General Description A KOHLER COMPANY       2 4 2 Flexible battery management    This equipment employs a flexible battery management which avoids premature deterioration of battery life by advanced  management of battery charging and preventive failure diagnostics     The major benefits are       AC ripple free battery charging due to a dc dc charger separated from the rectifier and inverter      Wide range of number of battery blocks  24 50 blocks of 12V  depending autonomy times       UPS s wide input voltage operating window extends the battery life due to fewer discharge cycles     Battery discharge protection caused by load jumps      Proactive battery protection from false manipulations and inadequate charging voltages      Proactive battery failure detection thanks to Advanced Battery Diagnosis  ABD    Algorithm      User selectable battery tests      Optional temperature compensated charging to enhance battery life     2 4 3 Decentralized Parallel Architecture  DPA     The PW8000DPA ST system features DPA paralleling technology that provides n x redundancy without introducing a  single point of failure  The modules utilizing the DPA technology are completely autonomous be means of individual  power units  bypasses  CPUs  control panels and separate battery configuration     2 5 Warranty    The PW8000DPA ST UPS is supplied with a lim
52. er module of the UPS management software is UPSMAN  which communicates with the UPS via an RS232 USB  interface  Running as a background application  UPSMAN collects and interprets the messages received from the UPS  and places them at the disposal of the client module UPSMON  as well as any connected SNMP based instrumentation  and control system     If UPSMAN detects voltage variations or a power failure  it can execute various  system event  routines  by means of  which  for example  the server is switched off or a warning alarm is sent to the connected users  These  system event  routines are a part of the management software and can be configured in to suit local application requirements     The software of your PW8000DPA ST UPS unit can be integrated into a network in two ways     1  Bythe server which is supplied by the UPS itself and has been integrated into the network  In most cases this server  is used as a sub agent and you only need the WAVEMON software  without an SNMP adapter   You will also need to  establish an RS232 USB connection between the UPS and computer server     2  In many cases the use of what is referred to as an    SNMP adapter    is to be preferred in order to integrate the UPS into  the network  In this case up to 50 computers can be shut down in one RCCMD environment  RCCMD  remote console  command  is an additional software module that is used in order to execute a command  typically a shutdown  command  in a remote system     7 4 5 Licensing 
53. g aids and safety platforms where possible     i WARNING  A UPS module weighs up to 22kg  If the UPS module is handled inappropriately it might cause    If a UPS module is faulty in a capacity parallel system  the load will automatically transfer to the modules  static bypass  which will then operate in the on bypass mode     4 8 4 Extracting the UPS module    1  Identify the faulty UPS module with the alarm condition and RESET the alarm  The audible noise will stop  If the red  ALARM LED remains on  there is a fault in the module     Verify that load is supplied from the bypass supply   3  Close the maintenance bypass switch  IA1         UPS454 01 02 PW8000DPA User Manual    01 12 13  43    Uninterruptible    Powerm  Supplies Ltd       4  Operation A KOHLER COMPANY  4  On all UPS module check and confirm that  LINE 2 BY PASS  a  The INVERTER LED has turned to red      ED    b  The BYPASS LED is green  EUM  c  The LCD panel displays MANUAL BYP IS CLOSED    pial ge    Open the fused battery isolator for the UPS module in the UPS cabinet or in  the external battery cabinet rack  as applicable     The UPS module is now totally shut down     Remove the two screws on the front of the UPS module that are fixing it to  the cabinet     EE BATTERY    Using the two black handles  pull the UPS module forwards until the rear connectors are disconnected  DO NOT    FULLY EXTRACT THE UNIT     A WARNING  Wait at least 2 minutes to allow the module   s electrolytic capacitors time to discharg
54. ge     The email  which provides details relating to the fault  a snapshot of the UPS performance parameters and a device  identification string  is automatically processed and UPSL s Service Centre personnel are alerted        UPS454 01 02 PW8000DPA User Manual    01 12 13  53    Uninterruptible    Supplies Ltd ta     e Options   KOHLER COMPANY       UPSL s Service Centre personnel are then able to liaise with the company s field service team and will remotely diagnose  the UPS incident before reaching the facility with appropriate spare parts within the contracted service agreement  timeframe        54 UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Powerm  Supplies Ltd      KOHLER COMPANY 8  Specification       8 Specification    8 1 Mechanical Characteristics     UPS Cabinet                                                                                                          ST 40   ST 60   ST 80 ST 120    m    EE E i Se 4E  Maximum 2 module 3 modules 4 modules 6 modules 10 modules  Configuration  10 or 20kVA   10 or 20kVA   10 or 20kVA   10 or 20kVA   10 or 20kVA   and and and and and  80 x 7 9Ah batteries 240 x 7 9Ah batter  NO batteries NO batteries NO batteries  ies  Max  Power kW 40 60 80 120 200  Dimensions mm 550x1135x770 550x1975x770 550x1135x770 550x1975x770   WxHxD   Weight of kg 92 173 82 133 174  Empty Cabinet  Weight with kg 130 up to 136 229 up to 238 157up to 169 245 up to 263 360 up to 389  modules and  with 2 Modules   with 3 Modu
55. hat the battery cables are connected under the following conditions   a  No mains voltage is present in the UPS     Do not attempt to complete the battery wiring or close the battery isolators before this system has been  b  Allthe loads are disconnected     commissioned   c  The UPS battery isolators are open and the external battery isolators are open in the external battery cabinet   where used    i e  the terminals to which the battery cables are to be fitted are electrically isolated     3 10 2 Battery cabling                                                                                                                                                    TO UPS BATTERY TO UPS BATTERY       ZZZ         ZZZ      eo00 KE NM     NM  N HK NM KEK NM  vuv vuv vuv vuu vuv vuv   P o  Xu uu E a a me or D mi i cu od Ee  COO DOD COD COO DOD TUUU  OOo 000 000 OOo 000 000  22    SS 222 225    SS 222  NNN NNN NNN NNN NNN NNN  Q n 0   amp G 0 0  2 4  a  a 2 40 6 0 6  2 48   2XDDD DDD DDD DDD DDD DDD  Ololo ojoo      O olojo oloo      O  OJOJO OOJO OJOJO OJOJO   OJO O ooo o O OlOJO oloo o O  PE 1L1 PE   1L1       ZZZ      2L1     ZZZ III 2L1      CN  O0      eA     000m  F   090 ve U4  0  DOD DOD ADD DOD DOD ADD  EEE EES EES ccce Sf amp fece amp s  RAR RRR RRR RAR ARR ARG  COMMON BATTERY INDIVIDUAL BATTERIES    Figure 3 9 Battery connections  ST 60 Cabinet shown     In all modules  the batteries are connected to terminal blocks mounted on the left hand side of the power connection rail  
56. he MAINTENANCE BYPASS isolator  IA1  is open  OFF    3  Ensure that the battery isolators within the UPS cabinet are open    If connecting wiring to an external battery cabinet  or racks     a  Ensure that the fused battery isolators in the external battery cabinet  or racks  are open    b  Connect the protective earth cable  PE  between the UPS and external battery cabinet    c  Connect the battery cables  ensuring the cables are connected to the corresponding     N    terminals   5  If connecting the internal batteries  ST 40 and ST 60 cabinet      a  Connect the batteries to the battery connection terminal blocks ensuring the cables are connected to the  corresponding     N    terminals     Note  DC Cables and battery fuses are bespoke to the installation     3 10 4 Internal battery for ST 40 and ST 60 cabinets  The ST 40 and ST 60 cabinets are designed to house 80 and 240 internal 12V  7 9Ah  battery blocks respectively   Different battery configurations are shown below     For details of the battery connections see Figure 3 5 and Figure 3 9     Important notes     When the cabinets are populated with 10kVA UPS modules the 12V batteries can be connected in strings of 24 50   even numbers only   depending the power sourced on the output     When the cabinets are populated with 20kVA UPS modules the 12V batteries can be connected in strings of 36 50   even numbers only   depending the power sourced on the output     The commissioning engineer will program the correct number
57. inet internal battery configuration  3 10 5 External battery enclosures  The ST 40 and ST 60 cabinets have integral battery storage  however this is not possible with the ST 80  ST 120 and  ST 200 units due to the space required to house a battery of a suitable size  In the case of ST 80 and ST 120 systems the  battery is either contained in an external battery cabinet  or rack mounted   A range of bespoke battery enclosures designed specifically to suit individual site requirements can be supplied for the  ST 80 and ST 120 models     two typical examples are shown in Figure 3 12  In all cases  the battery enclosure is fitted  with suitably rated fused isolators which are connected to the battery connection terminals inside the PW8000DPA ST as  shown in Figure 3 5   Note  DC fuses and cables are bespoke to the installation   24 UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Powerm  Supplies Ltd      KOHLER COMPANY 3  Installation                                                                                                                                                                                                                                           Fe F3 F2 F3 F4 F5  Fused nos isolators  Fused battery isolators       Battery Cabinet 120 Battery Cabinet 200    Figure 3 12 External battery cabinets       UPS454 01 02 PW8000DPA User Manual    01 12 13  25    Uninterruptible    Supplies Ltd    3  Installation   KOHLER COMPANY       UPS CABINET  1
58. ised electrician or qualified personnel    2  Once the electrical installation is completed the initial UPS start up and commissioning must be performed by  qualified personnel authorised by the manufacturer    3  Do not operate the UPS if there is water or moisture present    4  When carrying out any work on the UPS output power cables you must ensure that the UPS supplies are isolated at  the supply distribution panel and  where possible  locked out  Warning notices should be posted where applicable to  prevent inadvertent operation of the input supply isolators    3 9 2 Preparation for the output cabling   Circuit breakers  or equivalent protection  must be fitted between the UPS output and load equipment to provide additional   protection to the UPS in the event of an overload or short circuit  and also provide a means of isolating individual loads if   required    Before you start connecting the UPS output cables to the load distribution panel      Ensure that the potential load does not exceed the UPS model output power rating  OUTPUT POWER  on the  nameplate      Ensure the output circuit breakers are correctly sized with respect to the load rating and associated cabling      The maximum total load rating and maximum load rating of the individual load sockets should be indicated on the  output distribution board      The circuit breakers must comply with the prescribed IEC Standards  e g  BS7671 2008   It is recommended that a  separate output distribution board is pro
59. ited warranty that the UPS and its component parts are free from defects  in materials and workmanship for a period of one year from the date of commissioning  or fifteen months from the date of  original delivery  whichever is the sooner     This warranty is the only warranty given and no other warranty  express or implied  is provided     This warranty is invalidated if the UPS is used without having been commissioned by a fully trained and authorised  engineer     The warranty does not apply to any losses or damages caused by misuse  abuse  negligence  neglect  unauthorised  repair or modification  incorrect installation  inappropriate operating environment  accident  act of God  or inappropriate  application     If the UPS fails to conform to the above within the warranty period then Uninterruptible Power Supplies Ltd will  at its sole  option  repair or replace the UPS  All replaced parts will remain the property of Uninterruptible Power Supplies Ltd     As a general policy  Uninterruptible Power Supplies Ltd does not recommend the use of its products in      life support applications where failure or malfunction of the product can be reasonably expected to cause failure of   the life support device  or to significantly affect it   s safety or effectiveness      applications concerned with direct patient care   Uninterruptible Power Supplies Ltd will not knowingly sell its products for use in such applications unless it receives in  writing assurances satisfactory to Uni
60. ity supply outage  In the case of an abnormal utility supply  suitable UPS management software will also  enable a system administrator to monitor all concerned networks from a central point and identify bottlenecks at an early  stage     In spite of extensive system monitoring  if an administrator fails to intervene in a timely manner serious damage can still  occur  It is important therefore that the installed UPS software will react automatically in such a case and shut down the  supplied system in a safe and controlled manner  Uninterruptible Power Supplies Ltd considers it important to have a  complete solution for its UPS systems  and offers its customers a number of remote control and monitoring tools to  provide optimum protection     Two monitoring system options are available for use with the PW8000DPA ST UPS system     SNMP monitoring software    The SNMP adapter described above requires a PC with terminal connections and  for normal operation  at least one  Ethernet network connection  It also requires that the network operating system in use is SNMP compatible   Uninterruptible Power Supplies Ltd offer suitable monitoring software with SNMP functionality for NetWare  OS 2  all  Windows NT systems on INTEL and ALPHA network platforms     WAVEMON UPS monitoring and control software    WAVEMON is designed to operate in conjunction with many of the systems supplied by Uninterruptible Power Supplies  Ltd and features both UPS monitoring and automatic UPS server shutdo
61. j o o O O O Cabinet  b     Remove links  PE 1L3   1N   PE  3L1   3L3   PE for Dual Feed 1L1 1L3   Input Mains  s   Bx  NOT NEUTRAL LINK  2L1 2L3   Bypass Mains  xternal Batt  2L1 212 213 2N  Dual feed only   Common battery 3L1 3L3   Output to Load  links shown fitted  PE   Protective Earth  N   Neutral  ololo Jalol oloo olo ololo  wee Ojoo gE S S   ooo ooofolo ol o ol o ololo ST 60  E   i         Cabinet  PE T N 1L1 1L2 1L3 1N PE 3L1 3L3  External Batt  2L1 212  2l3     2N 3L2  olojojo o c  olofo     olo  olo    ST 80  Cabinet  PE   PE    N  External Batt  2L1 212 23 2N 3L2 3N  e e  C T TE  QIelo ST 120      Cabinet  3L1 3L3 PE  External Batt   2L1 212 213 2N 3L2 3N  UPS Common Battery Input Bypass Input Rectifier Output Load  Range    N     3 N   3 N PE   3 N PE   ST 40 3 x M5  B  4 x 16 25mm   T  5 x 16 25mm   T  5 x 16 25mm   T   ST 60 3 x M6  B  4 x 35   T  4 x 35   T  4 x 35   T     PE 50   T    PE 50   T   ST 80 3 x M6  B  4 x 50   T  3 x 50   T  3 x 502  T     N 70 95mm    T    N 70 95mm   T    N 70 95mm   T     PE 50mm   T    PE 50   T   ST 120 3 x 2xM5  B  or 4 x 70 95mm   T  4 x 70 95mm   T  4 x 70 95mm   T   3x M10  B    PE 50   T    PE 50   T   Notes   1  Fuse and Cable recommendations to IEC 60950 1 2001   2  The fuse and cable rating details in the above tables are a recommendation only   3  The UPS must be installed to prescribed IEC or local regulations  e g  BS7671 2008    4  DC Cables and Battery fuses are bespoke to the installation   Figure 3 5 ST 40  ST 6
62. l to  form a redundant module system     The UPS modules are assembled in a range of purpose designed free standing cabinets containing up to six UPS  modules  batteries and system switch gear     Cabinet mounted systems are rated according to the maximum number of 20kVA modules that can be housed   i e   40kVA  60kVA  80kVA  120kVA and 200kVA  see Figure 2 1   The 40kVA and 60kVA cabinets also contain the UPS  batteries whereas these must be located externally in the 80kVA  120kVA and 200kVA cabinets     Key Point  All the modules fitted within a cabinet must be of the same rating     i e  it is not possible to mix 10kVA  and 20kVA modules in the same parallel system     2 3 System Configuration    The illustrations in Figure 2 1 show the available cabinets fully populated with either 2  3  4  6 or 10 UPS modules   however each of the systems shown can operate with as little as a single module fitted     Thanks to the advanced PW8000DPA ST system design  if a cabinet is not fully populated it is possible to add further  modules  as required  to increase the system capacity without the need to power down the system or in any way disrupt  the load  This  hot swappable  design also means that individual modules can be exchanged while the equipment is  running without the need to transfer the load to the bypass supply  depending on system redundancy and demanded  load         2 UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Supplies Ltd ta      KOHLER COMP
63. les   with 4 Modules   with 6 Modules   with 10 Modules   no batteries  Colours Front  Graphite grey  Pulverlacke No  4222903402 serie O9RCCAT1   Side walls  Graphite grey  Pulverlacke No  4222903402 serie O9RCCAT1              UPS454 01 02 PW8000DPA User Manual    01 12 13  55    8  Specification    Uninterruptible    Power   Supplies Ltd    A KOHLER COMPANY       8 2 Mechanical Characteristics   UPS Module    Output Active Rated Power kW  Number of 12V Battery Blocks No   Dimensions  WxHxD  mm  Weight UPS Module kg  Colours       10kVA UPS Module 20kVA UPS Module  10 20  24 50   36 50    488 x 132 x 540  3 HU   18 6 21 5  Front  RAL 7016   Depending of the effective load in kW used by the module          8 3 Input Characteristics          Input Voltage Tolerance   ref to 3x400 230V  for Loads in          10kVA UPS Module 20kVA UPS Module  Output Rated Power per Module cosq 0 8 kVA 10 20  Output Rated Power per Module cos  1 0 KW 10 20  Nominal Input Voltage V 3x380 220V N  3x400V 230V N  3x415 240V N    V   23   15   3x308 177 V to 3x460 264 V for   10096 load    30   15   3x280 161 V to 3x460 264 V for  lt  80  load    40   15   3x240 138 V to 3x460 264 V for  lt  60  load                Input Frequency Hz 35   70  Input Power Factor PF 0 99   100  load  Inrush Current A max  In  Input Distortion THDI Sine wave THDi   3    100  load  Max  Input Power with rated output power and charged kW 10 5 21  battery per Module  output Cos    1 0   Max  Input Current with rated output
64. mperature of 20  C is recommended to achieve a long battery life  The cooling air entering the UPS must  not exceed  40  C     6  Avoid high ambient temperature  moisture and humidity  The floor material should be non flammable and strong  enough to support the heavy load     7   n summary  the UPS should be located where   a  Humidity     90  non condensing  and temperature   15  C to  25  C  are within prescribed limits     b  Fire protection standards are respected    c  Cabling can be performed easily    d  A minimum 900mm front accessibility is available for service or periodic maintenance   e  Requested air cooling flow is available     f  The air conditioning system can provide a sufficient amount of air cooling to keep the room at  or below  the  maximum desired temperature     g  No dustor corrosive explosive gases are present   h  The location is vibration free   i  Ifthe UPS will be installed in bayed enclosures  partition walls have to be installed        UPS454 01 02 PW8000DPA User Manual    01 12 13     3  Installation    3     Installation    Uninterruptible    Supplies Ltd ta      KOHLER COMPANY       Y  Open  Doors    Battery    Battery          Min Clearance  mm             ST 40 ST 80       ST 60 ST 120    200       Open  Doors    200          ST 200 300 900                   ST 40 ST 60 ST 80 ST 120 ST 200  550 x 1135x770 550x 1975x770   550x 1135 x 770   550x 1975x770 550 x 1975 x 770  Totally front accessibility for service and maintenance  no side  top 
65. nd provide an early warning before they develop into a crisis     The main features and benefits offered by PowerREPORTER are       Realtime email notification sent directly to UPSL Service Centre in response to alarm critical events      Acquisition of key performance data and productivity information  Empowers you with the details needed to better  understand machine performance and quickly troubleshoot downtime events      Combined with a service contract  PowerREPORTER improves service levels  The engineer can determine if site  attendance is necessary and bring relevant spare parts      Monthly Status Report detailing trends and alarms      Optional battery analysis and care service  PowerNSURE   measures battery voltage  temperature  impedance  and prolongs battery service life through the application of battery charge equalization     7 5 4 Functional description  UPS g g UPS with      n n Power REPORTER       Site manager                 Alarm Event Data Q Servers with  IN  amp  monthly report Q Power REPORTER      SS software  UPS Email    server Y     Wu  UPSL 24Hr    g    Helpdesk   Consultant j Roi  specialists A A DON    UPS Service    rO   6  Engineer       Figure 7 5 PowerREPORTER operation    PowerREPORTER communicates constantly with your UPS system in order to automatically detect any error or alarm  messages  In the event of an incident being detected  PowerREPORTER automatically connects with UPSL s Service  Centre via an email  transmitting a status messa
66. nterruptible Power Supplies Ltd that    e the risks of injury or damage have been minimized      the customer assumes all such risks      the liability of Uninterruptible Power Supplies Ltd is adequately protected under the circumstances       CAUTION  The UPS contains batteries that must be re charged for a minimum of 12 hours every six months     at 20 C  to prevent deep discharging  Batteries that have been deep discharged  for whatever reason  are not  covered by this warranty        4 UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Powerm  Supplies Ltd      KOHLER COMPANY 2  General Description       2 5 4 Extended warranty    The standard warranty may be enhanced by protecting the UPS with an extended warranty agreement  maintenance  contract   An extended warranty agreement enhances the standard warranty by providing the following      Regular preventative maintenance inspections      Guaranteed speed of response to operational problems      24 hour telephone support      Fully comprehensive cover  excluding batteries and capacitors      Contact the Service Support Hotline on 0800 731 3269 for further details     2 5 2 Additional service maintenance support    In addition to providing support for the PW8000DPA ST UPS  Uninterruptible Power Supplies Ltd can provide  maintenance and support on a wide range of different UPS products     If you are interested in an extended warranty for your PW8000DPA ST UPS  or for any other UPS products you may have
67. ntrol panel  4 2 1 Power Management Display  PMD   4 2 2 Mimic LED indicators  4 2 3 Operator keys  4 3 Description of the LCD display  4 3 1 Status screens  4 3 2 Main menu screen  4 3 3 Eventlog menu screen  4 3 4 Measurements menu screen  4 3 5 Commands menu screen  4 3 6 UPS Data menu screen  4 3 7 Set Up Service menu screen  4 3 8 Set up User menu screen  4 3 9 Set Up Service menu screen  4 4 Operating modes  4 4 1 On line  inverter  mode  4 4 2 On bypass  line interactive  mode  4 4 3 Maintenance bypass mode  4 5 Operating Instructions  4 5 1 Starting the UPS system from the maintenance bypass  4 5 2 Individual UPS module start stop procedure  4 5 3 Transfer to maintenance bypass mode  4 5 4 Complete system shutdown  4 6 Replacing a UPS module in a single module system  4 6 1 Extracting the UPS module  4 6 2 Refitting the UPS module  4 7 Replacing a UPS module in a REDUNDANT multi module system  4 7 1 Extracting the UPS module  4 7 2 Refitting the UPS module  4 8 Replacing a UPS module in a CAPACITY multi module system  4 8 1 Extracting the UPS module  4 8 2 Refitting the UPS module    5  Maintenance    5 1 Introduction   5 2 System calibration   5 3 Userresponsibilities   5 4 Routine maintenance   5 5 Battery testing   5 6 Battery maintenance   5 7 Battery disposal and recycling    6  Troubleshooting    6 1 Alarms   6 2 Menu  Commands  Event Log  Measurements    6 3 Fault Identification and Rectification Messages and Alarms  6 4 Contacting Service    28  28  29    31  
68. o       Make settings and adjustments via the menu driven LCD display     Start up and shut down the UPS and transfer the load between inverter and bypass     Monitor and display the UPS operating voltages  currents  frequencies and other values on the LCD display        32    UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Powerm  Supplies Ltd      KOHLER COMPANY 4  Operation       Key function summary                KEYS   FUNCTION  ON OFF Used to switch on or switch off the UPS   ON OFF Both keys must be pressed simultaneously   UP  A  Scroll upwards through a displayed menu   DOWN  W  Scroll downwards through a displayed menu   RESET Cancels the audible alarm  If the alarm condition was transient the ALARM LED  will also extinguish  otherwise it will remain ON  red    ENTER Confirms  selects  a chosen menu item        ON OFF Start up and shutdown buttons    The UPS may be switched ON or OFF by simultaneously pressing both ON OFF buttons on the control panel  The inclusion  of two buttons is designed to prevent accidental UPS start up or shutdown     During normal operation  pressing the two ON OFF keys will immediately shutdown the UPS module        n a single module installation this will disconnect the UPS from the load        n a parallel module system the UPS module will shutdown  however  the load may or may not transfer to the  bypass supply in the remaining module s   depending on the prevailing load and available module redundancy     Note  T
69. o shut down all the modules in a parallel system you must press both ON OFF buttons on every module   CAUTION  If the OFF buttons are operated on all the UPS module while the UPS is not on Maintenance  Bypass it will interrupt the load power supply     4 3 Description of the LCD display    4 3 1 Status screens    DESCRIPTION LCD DISPLAY  1  Loadis protected by UPS power supplied by the inverter LOAD     normal operation   The batteries are connected and OK  PROTECTED  2  Load is not protected  It is either supplied by mains power  load LUAD FI    on bypass  or it is supplied by the inverter  normal operation  and NUT PROTECTED    the batteries are not OK     3  Load supply interrupted  The UPS has been switched off by tne LOAD OFF Pas  ON OFF buttons  SUPPLY FAILURE  4  The UPS module is not supplying load  LOAD DTSCOMMECTED FHE    Note  On the right hand side of the LCD there is a 3 digit indicator defining the module s position in a multi module  system  The maximum number of modules in a parallel system is ten        UPS454 01 02 PW8000DPA User Manual    01 12 13  33    Uninterruptible    Power   Supplies Ltd    4  Operation A KOHLER COMPANY       4 3 2 Main menu screen  DESCRIPTION LCD DISPLAY    1  A log of the last 64 events is stored in the Power Management  gt  gt  EWEMT LOG  Display  See paragraph 4 3 3   MEASUREMENTS   2  Allows monitoring of voltages  power  frequencies  currents  pr TEE EIUS  autonomy etc  See paragraph 4 3 4  COMMANDS   3  Enables the commands  L
70. oad to inverter      Load to bypass    and  gt  COMMANDS  battery test to be executed  See paragraph 4 3 5   UPS DATA   4  Allows the UPS personalized information  such as serial number    HPS DATA  to be entered  See paragraph 4 3 6   SET UP USER    5  Allows user to set up Date Time  automatic battery test  etc  abc c NN   See paragraph 4 3 8  SET UP SERVICE   6  Password protected area for service engineer use only  gt  SET UP SERVICE   See paragraph 4 3 8      4 3 3 Event log menu screen  DESCRIPTION LCD DISPLAY       1  Logging Control  a log of the last 64 events is stored in the Power    eae ee  Management Display  LOAD TO INW     2  Every stored event is identified with a sequential number and time    Bz ig   a L4 s8 39  stamp  LOAD TO BYP   3  All events and alarms are indicated with their date and time of EF Bs i18 HG 14739 14  appearance  LOAD OFF  4 3 4 Measurements menu screen  DESCRIPTION LCD DISPLAY  1  Battery Runtime BATT  RUH TIME   MIH   Ei Emm  2  UPS Output Frequency QUTPUT FREQUENCY HZ   TA  BIE  3  Bypass Frequency  BYPASS FREQUENCY  HZ   yp q y  BB o8  4  Battery Voltage BATTERY VOLTAGE oto   A      B E  5  Battery Charger Current BATT  CHARGE CUR  TAJ   0 60     uu     6  Battery Discharge Current  DISCHARGE CURRENT  A7  ea aa  7  Rectifier Input Voltage  all three phases  RECTIFIER VOLTAGE Cv    BEE eaa Baa  8  Bypass Input Voltage  all three phases  BYPASS VOLTAGE   V5    BBE BEE ABE    OUTPUT VOLTAGE   V ac  BBE BEE ga    9  Output Voltage  all thr
71. on   KOHLER COMPANY       8 9 Environmental Characteristics         10kVA UPS Module 20kVA UPS Module  Audible Noise with 10096   5096 Load dBA 55 49 57149  Operation temperature   C 0 40  Ambient Temperature for Batteries   C 20   recommended   Storage Temperature   C  25    70  Battery Storage Time at Ambient Temperature Max  6 months    Max  altitude  above sea level  m 1000m  3300ft  without de rating  De rating factor for use at altitudes above 1000m Height above sea level  m   ft  De Rating Factor for Power  sea level according 1500   4850 0 95   IEC 62040 3  2000   6600 0 91  2500   8250 0 86  3000   9900 0 82    Relative Air humidity Max  95   non condensing     Accessibility Totally front accessibility for service and maintenance  no need for side  top  or rear access    Positioning Min  20 cm rear space  required for fan    Input and Output Power Cabling From the bottom on the front   Efficiency AC AC up to  at Cos  1 0    Load  100 75 50 25     20kVA 95 5  95 5  95 94 5   10kVA  95 5  95 5 95 94 5     Efficiency with Linear Load at cos  0 8 lagging Typically up to 1  higher of above values  Efficiency Non linear Load  EN 62040 1 1 2003  Typically up to 1  lower of above values    Eco Mode efficiency at 100  load   98      depending on Module power              8 10 Communication Options       Power Management Display  PMD   RJ45 Plug  Not used     Customer Interfaces  Outputs  DRY PORT X2    Customer Interfaces  Inputs  DRY PORT X1    1 x Remote Shut down  EMERGENC
72. onnected to the UPS system by opening the fused isolators or circuit breakers in the UPS  output load distribution board     A WARNING  Perform the following steps only after the load has been fully isolated                                   2  Onthe UPS control panel simultaneously press both ON OFF buttons   a  TheLCD panel will indicate  LOAD OFF  SUPPLY FAILURE   3  Open the fused battery isolator for the UPS module s  in the UPS cabinet or LINE 2 BY PASS  in the external battery cabinet rack  as applicable   a  The mimic indications should be as illustrated here  LOAD  LINE 1 INVERTER  4  Open the UPS Input isolators  and Bypass supply isolators in a dual feed    system  at the building power distribution panel   5  The UPS is now voltage free    BATTERY       UPS454 01 02 PW8000DPA User Manual    01 12 13  41    4  Operation    Uninterruptible    Supplies Ltd ta      KOHLER COMPANY       4 6 Replacing a UPS module in a single module system    WARNING  All the operations in this section must be performed by authorised and trained personnel     A UPS module weighs up to 22kg  If the UPS module is handled inappropriately it might cause serious  injury or damage  We recommend that the modules are handled by two persons at all times   Always employ suitable lifting aids and safety platforms where possible     WARNING     4 6 4 Extracting the UPS module    1  Transfer the load to the maintenance bypass supply  See paragraph 4 5 3    2  Simultaneously press the two ON OFF butt
73. ons on the UPS control panel                                   LINE 2 BY PASS  a  The mimic indications should be as illustrated here   i   LOAD  3  Open the fused battery isolator for the UPS module in the UPS cabinet or in LINEA INVERTER  the external battery cabinet rack  as applicable     4  The UPS module is now totally shut down   5  Remove the two screws on the front of the UPS module that are securing it mm BATTERY    to the cabinet     6  Using the two black handles  pull the UPS module forwards until the rear  connectors are disconnected  DO NOT FULLY EXTRACT THE UNIT     A WARNING  Wait at least 2 minutes to allow the module   s electrolytic capacitors time to discharge     7  After two minutes  fully withdraw the UPS module from the cabinet by pulling it horizontally     8  If you are not intending to replace the UPS module immediately  fit a blanking cover over the UPS compartment  opening and secure it in place using the screws removed earlier     4 6 2 Refitting the UPS module  1  Remove the blanking cover  if fitted      2  Using two people  lift the UPS module and slide it two thirds of the way into the UPS compartment  make sure not to  plug the UPS module into the rear connector      3  Push UPS module firmly into its final position  to assure good contact on the rear plugs     A    Secure the module in place using the screws removed earlier     a    Start the UPS module and bring it on line  See paragraph 4 5 2      4 7 Replacing a UPS module in a REDUNDAN
74. ontact us immediately call free on   Freefone 0800 731 3269  or E mail us on service upspower co uk  www upspower co uk       6 UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Supplies Ltd ta      KOHLER COMPANY 3  Installation       Installation    3 1 Introduction    This chapter contains all the information necessary for the correct unpacking  positioning  cabling and installation of the  PW8000DPA ST UPS cabinet     WARNING  All the operations described in this section must be performed by authorised electricians or  A suitably qualified personnel   Uninterruptible Power Supplies Ltd  will take no responsibility for any personal or material damage caused  by incorrect cabling or operations  or activities which are not carried out in strict accordance with the  instructions contained in this manual     3 2 Receipt of the UPS    The UPS and accessories are delivered on a specifically designed pallet that is easy to move with a forklift or a pallet jack     CAUTION  When off loading the UPS always keep it in an upright position   Do not drop the equipment   Do not stack the pallets due to the high energy batteries involved and the heavy weight     The packing container protects the UPS from mechanical and environmental damage  This protection is further increased  by wrapping the PW8000DPA ST UPS with a plastic sheet     Upon receiving the UPS  carefully examine the packing container and the UPS for any sign of physical damage  The  outside  Tip amp Tel
75. or rear access required   Min  200 mm rear space  required for ventilation    300mm rear  From the bottom at the front             Dimensions  WxHxD  mm  Accessibility   Positioning   Input Output Power Cabling                               Figure 3 1 UPS Space Recommendations    3 7 UPS Power Cabling  preparation and planning     3 7 1 General requirements    It is the customer s responsibility to provide all external fuses  isolators and cables used to connect the UPS input and  output power supplies  The information in this section should assist in the planning and preparation of the UPS power  cabling     The UPS input supply and bypass supply should be connected to the utility mains through a LV Distribution board and  protected by a circuit breaker or fuse  This provides overload protection and also a means of isolating the UPS from the  mains supply when required  Similarly  the UPS output supply should be connected to the load equipment via a suitably  fused output distribution panel     The UPS can be wired with a  single feed  input  standard   whereby the UPS input supply is connected internally to the  UPS bypass circuit  or it can be wired with a  dual feed  input  whereby the UPS bypass circuit is connected to a dedicated     bypass    supply  See Figure 3 3      Figure 3 3 identifies the UPS input output cabling requirements and provides information regarding fuse ratings  cable  ratings and cable sizing  This information is given for guidance only     P    Fig
76. ribed IEC Standards or local regulations  e g  BS7671 2008      Donot commence this procedure until the UPS is properly installed at its intended final location    3 8 8 Connecting the UPS input power cables   1  To protect personnel during the UPS installation ensure that the connections are performed under the following  conditions    a  No mains voltage is present    b  Loads are shut down and disconnected    c  The UPS is shut down and voltage free    d  The UPS Maintenance Bypass Isolator IA1 is OFF    2  Gain internal access to the UPS and remove the UPS terminal cover    3  Connectthe earth cable from the LV Distribution Board to the protective earth  PE  terminal in the UPS    4  The PW8000DPA ST input supply can be wired for    single feed     standard  or    dual feed    operation  Connect the input  power cable coming from the LV Distribution Board to the UPS input terminals following the appropriate instructions   single feed  or  dual feed  below    Single Input Feed   Refer to the schematic drawing and connection table in Figure 3 7    1  Connectthe UPS input supply cables to terminals 1L1  1L2  1L3 and 1N on the UPS main terminal block  See Figure  3 5   Ensure correct  clockwise  phase rotation    A CAUTION  The input Neutral cable must ALWAYS be connected    2  Secure the cables to the fixing rail located under the UPS connection terminals    1 6 UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Power   Supplies Ltd    A KOHLER COMPANY 3  
77. so the maintenance requirements to be carried out be the  user are minimal beyond ensuring that the local environment in which the UPS operates is kept cool  clean and dust free     5 4 Routine maintenance    It is essential that the UPS system and batteries receive regular preventative maintenance inspection to maximise both  the useful working life and system reliability  When the UPS is commissioned  the commissioning engineer will attach a  service record book to the front of the UPS which will be used to log the full service history of the UPS     hazardous AC and DC voltages  and should be performed only by an authorised engineer who has been    WARNING  Preventative maintenance inspections involve working inside the UPS which contains  A trained by Uninterruptible Power Supplies Ltd        During a preventative maintenance inspection the maintenance engineer will check       Site environment conditions      Integrity of electrical installation      Cooling airflow      Rectifier operation and calibration      Inverter operation and calibration      Static switch operation      Battery status      Load characteristics      Integrity of alarm and monitoring systems     Operation of all installed options     Preventative maintenance inspections form an integral part of all Extended Warranty Agreements  maintenance contracts   offered by Uninterruptible Power Supplies Ltd  For further details see Paragraph 2 6        UPS454 01 02 PW8000DPA User Manual    01 12 13  45    5 
78. te LOAD NOT PROTECTED and  the module mimic LED indications should be as illustrated here     LINE 1 INVERTER         mE BATTERY  Ensure that ALL the UPS modules are in the state shown before continuing  with this procedure        38    UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Powerm  Supplies Ltd      KOHLER COMPANY 4  Operation       Transferring the load to the UPS from the Maintenance Bypass   4  Ensure that the BYPASS LED is green  on all UPS modules         5  Open the maintenance bypass switch  IA1   LINE 2 BY PASS  a  TheLCD panels will display MANUAL BYPASS OPEN      HH              um  b  The INVERTER LED will be extinguished  LOAD      LINE 1 INVERTER  c  An audible alarm will sound                6  Press the RESET button to cancel the audible alarm  on all UPS modules    a  The LCD display will now indicate LOAD NOT PROTECTED    BATTERY    7  On the control panel  of any one module in a multi module system    a  Press the UP key once to access the menu system     b  Use the UP DOWN keys to move the cursor so that it is adjacent to  COMMANDS and then press the ENTER key     c  Use the UP DOWN keys to move the cursor so that it is adjacent to LOAD TO INVERTER and then press the                ENTER key   8  The UPS system will transfer the load to the inverter  on all UPS modules in LINE 2 BY PASS  a multi module system      a  The LCD display s  will now indicate LOAD PROTECTED  LOAD  LINE 1 INVERTER    b  Check and confirm that the LE
79. up and shut down and transfer the load between INVERTER and BYPASS     Access diagnostic and test facilities  service mode       Adjust the UPS configuration and operating parameters  service mode      4 2 2 Mimic LED indicators    The mimic diagram leds indicate the operational status of the UPS power blocks  and change colour between Green and  Red  and OFF  to indicate the active power flow through the UPS     LINE 1  rectifier  and LINE 2  bypass  indicate the availability of the UPS input mains  and bypass mains  power supply   INVERTER and BYPASS  when green  indicates which of the two sources is supplying the critical load power   The BATTERY LED indicator flashes when the battery is supplying the load     e g  following a mains failure     The ALARM LED is a visual indication of an internal or external alarm condition  When activated  it is accompanied by an  audible warning     LED Indication summary          Indicator Status Interpretation  LINE 1 GREEN Mains available  RED Mains not available  LINE 2 GREEN Mains bypass OK  RED Mains bypass not OK or not present  OFF UPS is turned OFF  ALARM OFF No alarm condition  RED Alarm condition  has been reset   INVERTER GREEN Load on inverter  RED Inverter fault  OFF Inverter not operating  switched OFF   BY PASS GREEN Load on bypass  OFF Bypass not operating  switched OFF   BATTERY GREEN Battery OK  RED Battery fault or discharged  Flashing GREEN On Battery             4 2 3 Operator keys  The operator keys allow the user t
80. ure 3 5 shows details of the power terminal connections withing the UPS including connection sizes and recommended  tightening torque  This illustration shows that the UPS unit requires the following power cables     Key Point  This information is given for guidance only  All fuses  isolators and power cables must be rated and  installed in accordance with the prescribed IEC standards or local regulations     e g  BS7671 2008        10    UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Powerm  Supplies Ltd      KOHLER COMPANY 3  Installation       Rectifier  In       three phase  1L1  1L2  1L3      neutral  1N      protective earth  PE  connection for the rectifier input  Bypass  In       three phase  2L 1  2L2  2L3      neutral  2N      protective earth  PE  connection for the bypass if used as  Dual Feed  input  Load  Out       three phase  3L 1  3L2  3L3      neutral  3N      protective earth  PE  connection for the load output  External Battery      Plus         Common  N      Minus         protective earth  PE  connection for the external batteries    Input neutral grounding    P Key Point  Input neutral is required to operate the rectifier     In TN S systems  no 4 pole input switches or circuit breakers should be used   During battery operation the neutral must always be grounded                                                           Figure 3 2 Input neutral grounding       UPS454 01 02 PW8000DPA User Manual    01 12 13  1 1    Uninterruptible 
81. use radio interference  In such an environment the user may be required to  undertake additional measures     AAAA       UPS454 01 02 PW8000DPA User Manual    01 12 13  1    Uninterruptible    Powerm  Supplies Ltd    2  General Description   KOHLER COMPANY       2 General Description    2 1 Reliability and Quality Standards  Congratulations on your purchase of the PW8000DPA ST     Using a unique modular construction  the PW8000DPA ST represents a completely new generation of medium power  3  phase UPS Systems  incorporating the latest technological developments in power engineering  High reliability  upgrade  ability  low operating costs and excellent electrical performance are only some of the highlights of this innovative UPS  solution     Uninterruptible Power Supplies Ltd specialises in the design  building  installation and maintenance of Uninterruptible  Power Systems  This compact and powerful UPS is just one example of our wide range of state of the art power  protection devices and will provide your critical equipment with a steady and reliable power supply for many years     The criteria and methods which are used in the design  manufacture  and maintenance of Uninterruptible Power Supply  Systems are certified to International Standard ISO 9001 EN 29001 and ISO 14001  A full UPS Specification is given in  Chapter of this manual     2 2 PW8000DPA ST System    PW8000DPA ST is a truly modular system based on 10kVA or 20kVA UPS modules which can be connected in paralle
82. vided for the load    3 9 8 Connecting the UPS output cables   1  To protect personnel during the UPS installation ensure that the connections are performed under the following  conditions    a  No mains voltage is present    b  Loads are shut down and disconnected    c  The UPS is shut down and voltage free    d  The UPS Maintenance Bypass Isolator IA1 is OFF    2  Gain internal access to the UPS and remove the UPS terminal cover    3  Connect the protective earth cable from the Load Distribution Board to the output protective earth  PE  terminals  as  shown in Figure 3 5    4  Connectthe UPS output supply cables to terminals 3L1  3L2  3L3 and 3N on the UPS main terminal block  See Figure  3 5   Ensure correct  clockwise  phase rotation    A CAUTION  The output Neutral cable must ALWAYS be connected    5  Secure the cables to the fixing rail located under the UPS connection terminals    6  Ensure the output cables are connected to the correct power terminals on the output  load  distribution panel    20 UPS454 01 02 PW8000DPA User Manual    01 12 13     Uninterruptible    Power   Supplies Ltd    A KOHLER COMPANY    3  Installation       3 10 Connecting the batteries    3 10 1 Safety Notes  WARNING  Opening or removing the UPS enclosure covers will create the risk of exposure to dangerous    voltages if power is connected to the UPS   The final assembly and connection of the battery units must be carried out by the commissioning engineer   1  For personal protection  ensure t
83. wn facilities     7 4 8 WAVEMON Shutdown and Monitoring Software    Fave mi  PMC Sofbware 24 09 2003   1245     stem Serial communication restored    leas System  Serial communication bet  24 08 2000  ES Gyshem  Connected Eo UPS       Annalablc UPS      3 E   3        Figure 7 4 Monitoring screen image       UPS454 01 02 PW8000DPA User Manual    01 12 13  51    7  Options    Uninterruptible    Power   Supplies Ltd    A KOHLER COMPANY       WAVEMON comprises a bespoke software package which is installed on a local PC and communicates with the UPS via  USB or a standard RS232 serial cable of up to 15m in length  It is only required when an SNMP card or adapter box is not  purchased     The main features of WAVEMON are       On screen autonomy time battery time countdown      On screen server log off and shutdown procedure      Time and date stamp event log      Extensive logging of all UPS activity and power quality data      Permits alarm warnings to be monitored remotely via email      Scheduled UPS service mode and other systems status      Graphical user interface for Windows compatible platforms      Automatic unattended local shutdown      Special modules for MS Office software to close and save open documents      Compatible with all optional modules like UPSDIALER  SNMP adaptors  temperature sensors  etc     7 4 4 Functional description    WAVEMON is a client server software application for networks and local workstations  In general  it consists of two parts   the serv
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Analysis of a “Simple” Medical Device  Cuff Clinic Modeles  Pengo DVD/CD Duplicator Burner  Touch Screen Operation  Philips Cordless Telephone  1993 cadillac fleetwood owner`s manual  Enterasys Matrix E1 Gigabit Workgroup Networking Switch  2 Appuyez sur la touche [FAX] du tableau de bord.  RCA RT2250 Stereo Receiver User Manual  検査標章の貼付位置に関する注意事項    Copyright © All rights reserved. 