1.   RC Fault relay contact Min  switching capacity  10 mA for 24 V    RA  open if there is a fault or the   Max  switching capacity   drive is off     2A for 250 V   and 30 V   on inductive load  cos    0 4   L R   7 ms    5 A for 250 V   and 30 V   on resistive load  cos      1  L R   0   0V UO common 0V  All Voltage or current analog   Analog input 0   5V or 0   10 V  impedance 40 kQ  30 V max   input Analog input 0   20mA or 4   20mA  impedance 250 Q  with no  additional resistor    5V Power supply for reference     Precision    0   5   potentiometer 2 2 to 10 kQ je Max  current available  10 mA  DO Output which can be PWM open collector analog output at 2 KHZ   configured as analog or   voltage 30 V max   impedance 1 kQ  10 mA max   logic output Open collector logic output     voltage 30 V max   impedance 100 kQ  50 mA max   LH Programmable logic inputs    Power supply   15 V  max  30 V   Impedance 5 kQ  LI2 e State 0 if  lt  5 V  state 1 if  gt  11V  LI3  LI4   15V Logic input power supply   15 V   15  protected against shorts circuits and overloads   Max  customer current available 100 mA       15       Wiring diagram for factory settings      Supply terminals at the top  motor terminals at the bottom    Connect the power terminals before the control terminals    Single phase supply 100   120 V    foe el  TI J    ATV11eeeeF1e ima 22              TI   ATV11eeeeM2e lu AA  lt a  LS a     3 phase supply 200   240 V     ATV11eeeeM3e  9 An      a a    l  1   se  5    4      ee 
2.   check the motor load  Wait for the   motor overload drive to cool before restarting    OSF e Check the line voltage    overvoltage   OLF    Braking too harsh or driving load  Increase the deceleration time  add a braking   overvoltage resistor if necessary and activate the brA function if it is compatible with the   during deceleration application    PHF This protection only operates with the drive on load     Check the power connection and the fuses    Reset    Check the line supply   drive compatibility    If there is an unbalanced load  inhibit the fault via IPL   nO  FUn menu            charging circuit          USF   Check the voltage and the voltage parameter   undervoltage  Cre   Replace the drive           24         ZS  Ss N         O       5    OO    m  Ess el  EH Ne            Ween SS  VVDED302031 W9 1623801 01 12 A02    028297 2002 05       
3.  It automatically  returns to the SFr frequency as soon as the thermal state permits        LF    4    if ACt   LF or LFr   12    if ACt   HF        21          Code    Description    Factory setting       Fler    Catch on the fly   Enables a smooth restart if the run command is maintained after the  following events      loss of line supply or disconnection     fault reset or automatic restart     freewheel stop    The motor resumes from the estimated speed at the time of the restart  then follows the ramp to the reference speed    This function requires 2 wire control  tCC   2C  with tCt   LEL or PFO    n O  function inactive   y E 5  function active   The function intervenes at each run command  resulting in a slight delay   1 second max      If continuous automatic injection braking has been configured  Ct  this  function cannot be activated     nO       dQ    ACE    FEd  LEd    Analog logic output DO   Assignment     n O  not assigned     OBE r  analog output   current in the motor  The full signal corresponds  to 200  of the nominal drive current      r F r  analog output   motor frequency  The full signal corresponds to  100  HSP      F E A  logic output   frequency threshold reached  closed  state 1  if the  motor frequency exceeds the adjustable threshold Ftd      Sr A  logic output   reference reached  closed  state 1  if the motor  frequency is equal to the reference      CEA  logic output   current threshold reached  closed  state 1  if the  motor current exceeds 
4.  closed state of the input controls the running  or stopping  Ga gs N    Example of wiring      4 5 9      LI1  forward  LIx  reverse  3 wire control  pulse control   a  forward  or  reverse  pulse is sufficient to  command starting  a  stop  pulse is sufficient to command stopping   Example of wiring       1   LI1  stop  LI2  forward EFEX E   LIx  reverse   A To change the assignment of tCC press the  ENT  key for 2 s  This    i  Lay LH LR Li      causes the following functions to return to factory setting  rrS  tCt   Atr  PS2  LIA  LIb      Type of 2 wire control    parameter can only be accessed if tCC   2C     L E L  state 0 or 1 is taken into account for running or stopping    E r n achange of state  transition or edge  is necessary to initiate operation   in order to prevent accidental restarts after a power supply interruption    P F D  same as LEL  but the  forward  input always takes priority over the   reverse  input     2G    trn       rb    Reverse  n D  function inactive  L I I to L 11  choice of the input assigned to the reverse command    if tCC   2C   if tCC   3C     LI2  LI3       Dia    SP2  GPa  SPY          Preset speeds   If LIA and Llb   0  speed   reference on Al1   If LIA   1 and LIb   0  speed   SP2   If LIA   0 and LIb   1  speed   SP3   If LIA   1 and LIb   1  speed   SP4   Assignment of input LIA     n D  function inactive    L I ItoL 1  choice of the input assigned to LIA  Assignment of input Llb     n D  function inactive    L I ItoL 1  choice of
5.  of a support  frame  which is a minimum of 10 mm thick and with a square  cooling area  S  of 0 12 m   minimum for steel and 0 09 m   for aluminium  exposed to the open air    Support area for the drive  min 142 x 72  machined on the frame with a surface smoothness of 100 um max and  a roughness of 3 2 um max    Mill the tapped holes lightly in order to remove any burrs    Coat the whole support surface of the drive with thermal contact grease  or equivalent      Attach the drive using 2                M5 screws  not supplied   SST 2 tapped  sp holes  oJ    M5  c0  o  fl  ot     E       E    210 m h   AI   lt n     d  d 0   Minimum  o machined  area                Verify the thermal state of the drive by checking parameter thd  SUP menu   to confirm that the  drive has been mounted correctly     14    Power Terminals                                                                                                                               Altivar ATV 116 Maximum connection capacity Tightening torque in Nm  AWG mm2  U05eee  U09eee  U18Mee AWG 14 1 5 0 75  U18F1e  U29eee  U41eee AWG 10 4 1    Power supply E  Power supply   J Woop o     b  LC  Le  0000o       i    To motor E  lt 0 VD To motor    _ To braking   o braking  module module    Arrangement  specifications and functions of the control terminals         Maximum connection capacity   1 5 mm2   AWG 16     Max  tightening torque    0 5 Nm                                      Terminal   Function Electrical characteristics
6.  the input assigned to Llb  SP2 is only accessible if LIA is assigned  SP3 and SP4 if LIA and Llb are  assigned     and preset speed  adjustable from 0 0 to 200 Hz  1   3rd preset speed  adjustable from 0 0 to 200 Hz  1   ath preset speed  adjustable from 0 0 to 200 Hz  1        if CC   2C   if tCC   3C     if tCC   2C   if tCC   3C     10  25  50    LI3  LI4    LI4  nO        1  The preset speeds can also be accessed in the 1st level adjustment parameters     20          Code    Description    Factory setting       SE    Fault reset     n D  function inactive    L I ito L 1  choice of the input assigned to this function   The reset takes place at a transition on the input  rising edge  0 to 1   Itis  only authorised if the fault has disappeared     nO       rPe    RTE  dE    Second ramp   Assignment of the 2nd ramp control input     n D  function inactive    L I ItoL 1  choice of assigned input   AC2 and dE2 are only accessible if LI is assigned     2nd acceleration ramp time  adjustable from 0 1 to 99 9 s  2nd deceleration ramp time  adjustable from 0 1 to 99 9 s    nO    5 0  5 0       Controlled stop on loss of line supply     n O  locking of the drive and freewheel stopping of the motor     F r P  stop according the valid ramp  dEC or dE2      F SE  fast stop  the stopping time depends on the inertia and the braking  ability of the drive     nO       Deceleration ramp adaptation     n D  function inactive     HE 5  This function automatically increases the deceleration t
7. S  LUUT  Reference                1                lt  m   potentiometer  aa      3 phase motor Braking module and  200   230 V resistor  optional     1  Fault relay contacts  for remote indication of the drive status    2  Internal   15 V  If an external source is used    24 V max    connect the 0 V of the source to the OV terminal     and do not use the   15 V terminal on the drive    3  Galvanometer or low level relay     Note  Fit interference suppressors to all inductive circuits near the drive or coupled to the same circuit  relays   contactors  solenoid valves  etc     Choice of associated components   See the Altivar 11 catalog     16    Functions of the display and the keys      Exits a menu or  parameter  or aborts the  displayed value to return  to the previous value in  the memory           3 7 segment   displays         Enters a menu or a  parameter  or saves the  displayed parameter or      Returns to the previous  value    menu or parameter  or  increases the displayed  value       Pressing A or     does not store the selection     Save the selection  En   Example     Parameter Value or assignment  d   The display flashes when a  F               ark  testa   lar value is stored        Kales  Gees     Next parameter       Goes to the next menu or  parameter  or decreases  the displayed value                Normal display  with no fault present and no startup     rdY  Drive ready    43 0  Display of the parameter selected in the SUP menu  default selection  frequ
8. U29ee E  U ranges        U41ee E  U ranges         ATV TIP a b c G H     mm mm mm mm mm mm  all ratings 72 142 101 6031 13141 2x5       13    Mounting and Temperature Conditions      F Sage    Sr Install the unit vertically  at   10                         Do not place it close to heating elements          Leave sufficient free space to ensure that the air required for cooling purposes can circulate   gt d  gt d from the bottom to the top of the unit   Free space in front of unit  10 mm minimum   a   N When IP20 protection is adequate  it is recommended that the protective cover on the top     gt   290 fa of the drive is removed  as shown below     e From  10  C to 40  C   d gt 50 mm  no special precautions   d  0  mounted side by side   remove the protective cover on the top of the drive  as  shown below  the degree of protection becomes IP20       From 40  C to 50  C  s d gt  50 mm  remove the protective cover on the top of the drive  as shown below  the  degree of protection becomes IP20       From 50  C to 60  C  s d  gt  50 mm  remove the protective cover on the top of the drive  as shown below  the  degree of protection becomes IP20   and derate the drive nominal current by 2 2  for  every   C above 50  C        Mounting the drives on machines    ATV 11Peeeeee drives can be mounted on  or in  a steel or aluminium machine frame  observing the following  conditions    Maximum ambient temperature  40   C   Vertical mounting at   10     The drive must be fixed at the centre
9. d HSP  High speed when the reference is maximum   parameters       The ItH parameter  Motor thermal protection       The preset speeds SP2 SP3 SP4    5 The speed reference if it is other than 0   5 V  0  10V or 0  20mA or 4  20mA      5   Configure the following in the drC menu   The motor parameters  only if the factory configuration of the drive is not suitable     6   Start the drive    Factory configuration    The Altivar 11 is factory configured for the most common operating conditions     Logic inputs      LI1  LI2  2 directions of operation   2 wire control on transition  LI1   forward  LI2   reverse      LIS  LI4  4 preset speeds  speed 1   speed reference or LSP  speed 2   10 Hz    speed 3   25 Hz  speed 4   50 Hz        Analog input Alt  speed reference  0   5 V       Relay R1  the contact opens in the event of a fault  or drive off     DO output  analog output  image of the motor frequency   If the factory configuration is not suitable  the FUn menu can be used to modify the functions and the I O  assignments                                                                                                                    Dimensions  ATV 11H a b c G H     20 4   mm mm mm mm mm mm  Wy Fan     U05eeE  U ranges 72 142  lt 125 6041 13141 2x5    ies U09ee U range  L       Ti  FI   J U09ee E range 72 142  lt 138 60 1 12041 2x5  x I  U12eeE range  U18Me E range  1    U18Me U range 72 147 138 6041 13141 2x5     G lz    G        Ui8FTUrange 117 142 156 10641 13141 4x5  a a 
10. eee   Aiva  i    Guide d exploitation Variateurs de vitesse pour  User   s manual moteurs asynchrones   EENG Variable speed drives    Guia de explotaci  n    Guida all impiego for asynchronous motors     Frequenzumrichter   fur Drehstrom Asynchronmotoren   Variadores de velocidad   para motores asincronos   Variatori di velocita   per motori asincroni     ATV 11eccceeE U       Schneider  FP Electric       Variateurs de vitesse pour moteurs asynchrones Page 1       Variable speed drives for asynchronous motors Page 13       Frequenzumrichter f  r Drehstrom Asynchronmotoren  Seite 25       Variadores de velocidad para motores asincronos Pagina 37       Variatori di velocita per motori asincroni Pagina 49    fe   zZ   lt   5   lt   E          Steps for Setting   p the Drive  1   Fit the drive    2   Connect the following to the drive        The line supply  ensuring that it is     within the voltage range of the drive    voltage free     The motor  ensuring that its coupling corresponds to the supply voltage    The control via the logic inputs  5 The speed reference via the logic or analog inputs    3   Switch on the drive  but do not give a run command    4   Configure the following       The nominal frequency  bFr  of the motor  if it is other than 50 Hz for the E range or other than 60 Hz for the  U range  only appears the first time the drive is switched on        The ACC  Acceleration  and dEC  Deceleration  parameters       The LSP  Low speed when the reference is zero  an
11. en 20  stopped  1 to 100  when  operating  Value too high  overspeed  instability   Value too low  lengthening of response time  UF r  IR compensation 0 to 200  50  Used to optimise the torque at very low speed  or to  adapt to special cases  example  for motors connected  in parallel  lower UFr    an Er  Nominal motor current marked on the rating plate 0 25 to 1 5 In  1  Acc  to rating  EL I  Limiting current 0 5 to 1 5 In  1  1 5 In  obt  Nominal motor slip 0 to 10 0 Hz Acc  to rating  Calculate using the formula  nSL   parameter FrS x  1   Nn Ns   Nn   nominal motor speed marked on the rating plate  Ns   motor synchronous speed  SL P  Slip compensation 0 to 150   of nSL  100  Used to adjust the slip compensation around the value set by the nominal motor slip nSL  or to adapt  to special cases  example  for motors connected in parallel  lower SLP      05  Nominal motor cosine o marked on the rating plate 0 50 to 1 00 Acc  to rating           1  In   nominal drive current    19       Application functions menu FUn                ECL a af   Type of control  e 7     ei co  Reminder of the configuration  Fes                                           The parameters in clear boxes can only be modified when the drive is stopped and locked     Parameters in shaded boxes can be modified with the drive operating or stopped        Code    Description    Factory setting       ECC  ACE    ECE    Type of control      E   2 wire control   3 E   3 wire control   2 wire control  The open or
12. ency reference      dcb  DC injection braking in progress    nSt  Freewheel stop  If there is a fault  it is shown with a flashing display     17    1st level adjustment parameters       Displays the drive status    Menu  Motor control fae D  Menu  Application functions Bi li Menus            Menu  Monitoring   SUF l                         1st level  adjustment  parameters          The parameters in clear boxes can only be modified when the drive is stopped and locked     Parameters in shaded boxes can be modified with the drive operating or stopped                                                              Code  Description Adjustment range Factory setting  bF r  Motor frequency 50 Hz 50  E range   or or  60 Hz 60  U range   This parameter is only visible the first time the drive is switched on   It can be modified at any time in the FUn menu   ACC   Acceleration ramp time 0 1 s to 99 9 s 3  Range  0 Hz to motor nominal frequency FrS  parameter in drC menu    dEC  Deceleration ramp time 0 1 s to 99 9 s 3  Range  motor nominal frequency FrS  parameter in drC menu  to 0 Hz   LSP  Low speed 0 Hz to HSP 0  Motor frequency to 0   HSP  High speed LSP to 200 Hz  bFr  Motor frequency to max  reference   Check that this setting is appropriate for the motor and the application   IE H  Motor thermal current 0 to 1 5 In  1  According to drive  rating  purem used for motor thermal protection  Set ItH to the nominal current marked on the motor rating  SEN The memory of the motor therma
13. et  If they have not been reset  the drive  will display  rdY  or    nSt    but will not start     Faults displayed    The cause of the fault must be removed before resetting    Faults SOF  OHF  OLF  OSF  ObF  and PHF can be reset via a logic input if this function has been configured   Faults OHF  OLF  OSF  ObF  and PHF can be reset via the automatic restart function  if this function has been  configured  All faults can be reset by switching the drive off then on again              motor short circuit   insulation fault    Fault Remedy  OCF e Ramp too short  check the settings   overcurrent   Inertia or load too high  check the size of the motor drive load      Mechanical locking  check the state of the mechanism   SCF   Check the cables connecting the drive to the motor  and the insulation of the motor        InF     internal fault      Check the environment  electromagnetic compatibility    Replace the drive                          line phase failure      CFF   Return to factory settings or call up the backup configuration  if it is valid  See   configuration fault parameter FCS in the FUn menu    SOF   Instability  check the motor  gain and stability parameters    overspeed   Driving load too high  add a braking module and resistor and check the size of the  motor   drive   load    DHF   Check the motor load  the drive ventilation and the environment  Wait for the drive to   drive overload cool before restarting    OLF   Check the setting of the motor thermal protection
14. ime  if this  has been set at too low a value for the inertia of the load  thus avoiding the  overvoltage fault     YES       AdE    ACE    EdE  Sdt    Automatic DC injection   Operating mode     n O  function inactive     HE 5  DC injection on stopping  duration adjustable via tdC  when  operation is no longer controlled and the motor speed is zero  The value  of this current can be adjusted via SdC         E  Continuous DC injection on stopping  when operation is no longer  controlled and the motor speed is zero  The value of this current can be  adjusted via SdC    In 3 wire control the injection is only active when UI  is at 1    tdC is only accessible if ACt   YES  SdC if ACt   YES or Ct     Injection time on stopping  adjustable from 0 1 to 30 0 s  Injection current  adjustable from 0 to 1 2 In  In   nominal drive current     YES    0 5  0 7 In          SFE    ACE    SFr       Switching frequency   Frequency range     L F r  random frequency around 2 or 4 kHz according to SFr    L F  fixed frequency of 2 or 4 kHz according to SFr     HF  fixed frequency of 8  12 or 16 kHz according to SFr    Switching frequency      2  2 kHz  if ACt   LF or LFr      4  4 kHz  if ACt   LF or LFr      B  8 kHz  if ACt   HF      12 12 kHz  if ACt   HF      16 16 kHz  if ACt   HF    When SFr   2 kHz  the frequency automatically changes to 4 kHz at high  speed    When SFt   HF  the selected frequency automatically changes to the  lower frequency if the thermal state of the drive is too high 
15. l state returns to zero when the drive is switched off   SP   2  preset speed  2  0 0 to 200 Hz 10  SP3  3    preset speed  2  0 0 to 200 Hz 25  SP4  40 preset speed  2  0 0 to 200 Hz 50  A It   Configuration of the analog input 5U  10U  0A  4A 5U              5 U  voltage 0   5 volts  internal power supply      IO U  voltage 0   10 volts  external power supply     OA  current 0   20 mA    4 A  current 4   20 mA           1  In   nominal drive current   2  The preset speeds only appear if the corresponding function has remained at the factory setting or has been  reconfigured in the FUn menu     18       Motor control menu drC             En     amp                        Nominal motor voltage    Motor nominal cosine    The parameters in clear boxes can only be modified when the drive is stopped and locked     Parameters in shaded boxes can be modified with the drive operating or stopped                                                           Drive performance can be optimised by entering the values marked on the motor rating plate  Code  Description Adjustment range Factory setting  Un 5  Nominal motor voltage marked on the rating plate  100 to 500 V Acc  to rating  F eS  Nominal motor frequency marked on the rating plate  40 to 200 Hz 50   60Hz dep  on  bFr  SEA  Frequency loop stability 0 to 100  when 20  stopped  1 to 100  when  operating  Value too high  lengthening of response time  Value too low  overspeed  possible instability   FLG  Frequency loop gain 0 to 100  wh
16. line phase loss fault    YES       SCS          Configuration backup     n D  function inactive     Y E 5  saves the current configuration to the EEPROM memory  SCS  automatically switches to nO as soon as the save has been performed   This function is used to keep another configuration in reserve  in addition  to the current configuration  When drives leave the factory the current  configuration and the backup configuration are both initialised to the  factory configuration        nO       22          Code    Description    Factory setting       FOS       Reminder of the configuration     n D  function inactive     r EC  the current configuration becomes identical to the backup  configuration previously saved by SCS  rEC is only visible if the backup  has been carried out  FCS automatically switches to nO as soon as this  action has been performed     FCS automatically switches to nO as soon as this action has been  performed   For rEC and Inl to be taken into account the ENT key must be  held down for 2 s          In      the current configuration becomes identical to the factory setting        nO       Monitoring menu SUP       SUP                E Ech            value   Frequency reference     7  amp         Got Des Drive thermal state  Ou                    When the drive is running  the value displayed is that of one of the monitoring parameters  The default value  which is displayed is the motor reference  parameter FrH      While the value of the required new monitori
17. ng parameter is being displayed  the  ENT  key must be pressed  a second time to confirm the change of monitoring parameter and to store it  From then on the value of this    parameter will be displayed during operation  even after the drive has been switched off      If the new choice is not confirmed by pressing the  ENT  key for a second time  the drive will return to the    previous p    arameter after it has been switched off     The following parameters can be accessed  with the drive stopped or running                          Code Parameter Unit  Frn Display of the frequency reference  factory configuration  Hz  rFr Display of the output frequency applied to the motor Hz  LLr Display of the motor current A  UL n  Display of the line voltage V  EHr Display of the motor thermal state  100  corresponds to the nominal thermal state     Above 118   the drive trips on an OLF fault  motor overload   It can be reset below 100    EHd Display of the drive thermal state  100  corresponds to the nominal thermal state     Above 118   the drive trips on an OHF fault  drive overheating   It can be reset below 80                  23          Faults   Causes   Remedies    Starter does not start  no fault displayed      Check that the run command input s  have been actuated in accordance with the chosen control mode    5 When the drive is switched on  at a manual fault reset  or after a stop command  the motor can only be  powered once the  forward  and  reverse  commands have been res
18. the adjustable threshold Ctd    Ftd is only accessible if ACt   FtA  Ctd is only accessible if ACt   CtA     frequency threshold  adjustable from 0 to 200 Hz  current threshold  adjustable from 0 to 1 5 In  In   nominal drive current     rFr      DEF  In       Aer    Automatic restart    n D  function inactive    JE 5  Automatic restart  after locking on a fault  if the fault has disappeared  and the other operating conditions permit the restart  The restart is performed  by a series of automatic attempts separated by increasingly long waiting  periods  1 s  5 s  10 s  then 1 min for the following periods  If the restart has  not taken place after 6 min  the procedure is aborted and the drive remains  locked until it is disconnected and then reconnected   The following faults permit this function  OHF  OLF  ObF  OSF  PHF   The drive fault relay remains activated if this function is active  The speed  reference and the operating direction must be maintained   This function is only accessible in 2 wire control  CC   2C  with tCt   LEL  or PFO   Check that an accidental start does not present any danger to  personnel or equipment     nO       bFr    Motor frequency   Same as bFr 1st level adjustment parameter   Set to 50 Hz or 60 Hz  taken from the motor rating plate     50  E range   or  60  U range        IPL    Line phase loss fault configuration   This parameter is only accessible on 3 phase drives     n D  inhibition of the line phase loss fault     HE 5  monitoring of the 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
PCoIP® Infrastructure Deployment Guide  ラベルプリンタのご利用について    fichier 1 - CRDP de Montpellier  HP ProBook LG856EA notebook    Kühlschrank V-ZUG AG Ideal 60i  Homelite UT08120D Blower User Manual  Samsung Home Theater Blu-Ray 3D 1000W HT-D5550WK manual do usuário  EFIS-D10 Installation Guide    Copyright © All rights reserved. 