USER MANUAL
Contents
1. The positive pole of the battery is connected to the 6KS UPS with red wire and the 10KS 3T1 10K UPS in parallel with blue and brown wires the negative pole of the battery is connected to the 6KS UPS with black wire and the 10KS 3T1 10K UPS in parallel with black and white wires the green and yellow ribbon wire is connected to the ground of the battery cabinet 17 3 To complete the connection by plugging the connector of the external battery cable into the external battery socket of the UPS Do not attempt to connect any loads to the UPS now You should connect the input power wire to the right position first And then set the breaker of the battery pack in the ON position After that set the input breaker in the ON position The UPS begins to charge the battery packs at the time The blue amp brown or red wires for connection to the positive terminal of the battery pack output GE The black amp white or black wires for connection to the PSSS negative terminal of the The receptacle for ES battery pack output connecting eS The green and yellow ribbon wire for connection to the ground of the battery cabinet 5 4 Parallel operation 1 Brief introduction of the redundancy N X is currently the most reliable power supply structure N represents the minimum UPS number that the total load needs X represents the redundant UPS number i e the fault UPS number that the system can handle simultaneously The bigge
2. UPS is used in parallel mode the Jumper between JP1 and JP2 must be removed 16 5 3 Operating procedure for connecting the long backup time model UPS with the external battery 1 The nominal DC voltage of external battery pack is 240VDC Each battery pack consists of 20 pieces of 12V maintenance free batteries in series To achieve longer backup time it is possible to connect multi battery packs but the principle of same voltage same type should be strictly followed For 6KS 10KS 3T1 10KS the connector of the external battery cable is used to plug into the external battery socket of the UPS the other end of the external battery cable is made of three open wires with ring terminals to connect with the external battery pack s for 3T1 15KS 20K select the UL1015 6AWG 25mm wire or other insulated wire which complies with AWG Standard for the UPS battery wirings The procedure of installing battery bank should be complied with strictly Otherwise you may encounter the hazardous of electric shock 1 ADC breaker must be connected between the battery pack and the UPS The capacity of breaker must be not less than the data specified in the general specification 2 Set the battery pack breaker in OFF position and connect the 20 pieces of batteries in series 3 You must connect the external battery cable to the battery first if you connect the cable to the UPS first you may encounter the hazardous of electric shock
3. and screw up the connector screw the cover board of the parallel port back again Remove the maintenance cover board of the new UPS and set the maintenance switch from UPS to BPS Turn on the battery switch and the input breaker of the new UPS measure the difference voltage between the output line wires of new UPS and the parallel system to check if the voltage difference between them is less than 1V If the difference is less than 1V close the output breaker If the difference is more than 1V check if the wirings are abnormal Remove the cover board of the parallel port located on the UPS which has transferred to the maintenance bypass and push the other end of the parallel cable into the slot of the parallel kit and fasten the connector Screw the cover board of the parallel port back again Close the input breakers of all of the UPSs including the new UPS in the parallel system After all of the UPSs transfer to the Bypass mode screw the maintenance cover board back again 27 10 Turn on each UPS in turn and observe their display Make sure that each UPS displays normal and all the UPSs transfer to the INV mode together Measure the voltage on the JP1 and JP2 on the terminal block of each UPS to check if the voltage difference between them is less than 1V If the voltage difference is more than 1V the output relay of the UPS may not be closed 11 Measure the voltage of each JP2 on each UPS to check if the v
4. least 0 5m of space on each side 3 Condensation to water drops may occur if the UPS is unpacked in a very low temperature environment In this case it is necessary to wait until the UPS is fully dried inside out before proceeding installation and use Otherwise there are hazards of electric shock 13 2 Installation Installation and wiring must be performed in accordance with the local electric code and the following instructions by professional personnel For safety please cut off the mains power switch before installation The battery breaker also needs to be cut off if it is a long backup time model S model 1 2 Open the terminal block cover located on the rear panel of the UPS please refer to the appearance diagram For 6K S UPS it is recommended to select the UL1015 10AWG 6mm wire or other insulated wire which complies with AWG Standard for the UPS input and output wirings For 10K S 3T1 10KS UPS it is recommended to select the UL1015 8AWG 10mm wire or other insulated wire which complies with AWG Standard for the UPS input and output wirings For 311 15KS 20KS UPS it is recommended to select the UL1015 6AWG 25mm wire or other insulated wire which complies with AWG Standard for the UPS input and output wirings Note Do not use the wall receptacle as the input power source for 9 the UPS as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be b
5. the UPS by pressing the OFF button continuously for more than 1 second and the buzzer will beep once The UPS will turn into Bypass mode 24 6 2 mb 2 Upon completion of the above to turn it off output of electric current of the UPS is still present In order to cut off the output from the UPS simply cut off the utility power supply a few seconds later there are not any display is shown on the display panel and no voltage output is available from the UPS output Turn off the UPS with no utility power supplied in Battery mode 1 To power off the UPS by pressing the OFF button continuously for more than 1 second and the buzzer will beep once 2 When being powered off the UPS will turn into No Output mode Finally not any display is shown on the display panel and no voltage is available from the UPS output Suggestions Please turn off the connected loads before turning on the UPS and turn on the loads one by one after the UPS is working in INV mode Turn off all of the connected loads before turning off the UPS Parallel Operation Parallel Machine Maintenance This UPS system has parallel machine function if you want to add single machine to parallel system please follow operational process of joining new machine if because of cutting down load or attainting UPS and you must remove UPS please follow operational processes of removing parallel machine How to install a new parallel UPS system 1 Befor
6. PS immediately without charging the batteries first but the backup time may be less than the standard value 12 If it is necessary to connect the inductance load such as a monitor or a laser printer to the UPS the start up power should be used for calculating the capacity of the UPS as its start up power consumption is too big when it is started bee SR JP1 JP2 Input Ground Output Ground Output Neutral Output Line C JP2 Input Neutral Input Line JP1 Input and output Terminal Block wiring diagram of 6K S 10K S Important notes If the UPS is used in single mode JPI and JP2 must be connected by 10AWG 6mm If the UPS is used in parallel mode JP1 and JP2 must be disconnected 15 Input Ground Input Neutral Input Line Wire A Input Line Wire B Input Line Wire C aaajalaarale Output Ground Output Neutral Output Line Battery Battery Input and output Terminal Block wiring diagram of 3T1 10KS Important notes If the UPS is used in single mode JPI and JP2 must be connected by 10AWG 6mm If the UPS is used in parallel mode JP1 and JP2 must be disconnected Input Ground Input Neutral Input Line Wire Input Line Wire B Input Line Wire C IRSA z Output Ground Output Neutral Output Line Battery Battery Input and output Terminal Block wiring diagram of 3T1 15KS 20KS Important notes If the UPS is used in single mode JPI and JP2 must be connected If the
7. Preference Language Help SEDEER UPS Status UPS Normal Ze BYPASS Frequency Max Volt On Battery Min lona Model Voltage Com Port BATTERY Standard Inn i Temp iLL Capacity a pra 13 53 35 Agent Start Installation procedure 1 Goto the web site htto www ups software download com winpower htm 2 Choose the operation system you need and follow the instruction described on the website to download the software 3 When downloading all required files from the internet enter the serial No 511C1 01220 0100 478DF2A to install the software When your computer restarts the WinPower software will appear as a green plug icon located in the system tray near the clock 4 7 Appendix 1 The Corresponding Form of the LCD Display no oprtngemo ERG Alarm warning l Beep once every sec A Battery capacity Pn mode 21 e AERE Beep once every 4 sec capacity EN Overloaded in Bypass mode Beep twice every sec Overloaded in Line mode Beep twice every sec Overloaded in Battery mode Early warning INV abnormal BUS voltage abnormal 10 INV abnormali Beep twice every sec Continuously beep Continuously beep Continuously beep Over temperature Continuously beep Output short circuited Continuously beep Communication abnormal Continuously beep Battery open Continuously beep INV relay failed Continuously beep BAT SCR failed Continuously beep Continuously beep ID abnormal Char
8. USER MANUAL LCD 6 20Kva models Uninterruptible Power Systems Please comply with all warnings and operating instructions in this manual and on the unit strictly Save this manual properly Do not operate this unit before reading through all safety information and operating instructions carefully CONTENTS 1 Safety and EMC instructions RE EE EE EE 1 1 1 Installation di IA TI a DD GD 1 1 2 Operation AAA AAA AAA AAN 2 1 3 Maintenance servicing and faults EE 2 14 Transport EE Breet rege T A S T T 3 1 5 Storage RO 4 1 6 Standards ia aC A TAC 4 2 Description of commonly used symbols 5 3 Introduction nadaa aaa dada 6 3 1 System and model description ENEE 6 3 2 Product Specification and Performance SERRO RODE RE DER PEREIRA RE EMENDA eT Eee T 4 Display Panel t s setsertrrtsrtsersrrsrrssnnsnnsnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn nna 9 B Installation AAA ERR E RT PER ERC E LT 1 3 5 1 Unpacking and Inspection eeeseeeseeeseesssesssseesseesseeesseeesseeneros 13 5 2 Input and output power cords and protective earth ground installation PEPE re E CHEN NACH e NR E ECK NENG e a e Rs NN NEEN AAA 1 3 5 3 Operating procedure for connecting the long backup time model UPS with the external battery RENE E E 1 T 5 4 Parallel operation A A S 1 8 6 Operation RP PR RR RO RL ERR 2 4 6 1 Operation Mode aaa aaa aia aaa iaa aaa aaa ri a Dane dad 2 4 6 2 Parallel Operation EE 2 5 6 3 Backup time for the standard model lo Meel ah e o ae a
9. by burning them It could cause explosion x Do not open or destroy batteries Effluent electrolyte can cause injury to the skin and eyes It may be toxic x Please replace the fuse only by a fuse of the same type and of the same amperage in order to avoid fire hazards x Do not dismantle the UPS except the qualified maintenance personnel 1 4 Transport Please transport the UPS only in the original packaging to protect against shock and impact 1 5 Storage x The UPS must be stockpiled in the room where it is ventilated and dry 1 6 Standards Safety IEC EN 62040 1 1 EMI Category C3 Category C3 Warning This is a product for commercial and industrial application in the second environment installation restrictions or additional measures may be needed to prevent disturbances 2 Description of commonly used symbols Some or all of the following symbols may be used in this manual It is advisable to familiarize yourself with them and understand their meaning ESSES a e Turn on the UPS Idle or shut down the UPS Alternating current Do not dispose with source AC ordinary trash Direct current source DC 3 Introduction 3 1 System and model description This Online Series is an uninterruptible power supply incorporating double conversion technology lt provides perfect protection specifically for computer equipment communication systems to computerized instruments lts true online double conver
10. closed Measure the voltage of each JP2 on each UPS to check if the voltage value is less than 5V Generally 2V If the difference is more than 5V that means the UPS needs to be regulated again or you need to check that the parallel cable of the parallel kit are normal Turn off each UPS in turn and after all of them transfer to the Bypass mode remove the maintenance cover board of each UPS and set the maintenance switch from BPS to UPS and screw the maintenance cover board back again Turn on the UPSs in the Line mode to perform the parallel operation 26 3 How to join a new UPS 1 2 Before joining a new UPS user need to prepare the input and output wires the output breaker and the parallel cable Turn off the input and output breakers of the new unit Connect the input wires output wires and battery wires Remove the short connection wire between JP1 and JP2 on the terminal block Turn off the UPS systems that are running After all of the running UPSs transfer to the Bypass mode remove the maintenance cover board of each UPS and set the maintenance switch from UPS to BPS then turn off the input breaker of each UPS If the UPS system that is running is a stand alone UPS you need to remove the short connection wire between JP1 and JP2 on the terminal block Remove the cover board of the parallel port on the new UPS push one end of the parallel cable into the slot of the parallel kit
11. could be displayed 35 SETTING 50 60Hz 208 220 230 240 Vac BYPASS ON OFF No Output mode 10 2 Bypass mode The LCD display in Bypass mode is shown in the following diagram The information about the utility power the battery the UPS output and the load could be displayed The symbol of Ea and EEN indicates the bypass is working The UPS will beep once every 2 minutes in Bypass mode CHARGING SETTING 50 60Hz 208 220 230 240 Vac BYPASS ON OFF Bypass mode The UPS does not have the backup function when it is in Bypass mode The power used by the load is supplied from the utility power via internal filter 36 10 3 Line mode The LCD display in Line mode is shown in the following diagram The information about the utility power the battery the UPS output and the load could be displayed The symbol of ES and ET indicates the UPS is working in line mode CHARGING BATTERY SETTING 50 60Hz 208 220 230 240 Vac BYPASS ON OFF Line mode If output overloaded the OVER LOAD is shown and the UPS will beep twice every second You should get rid of some unnecessary loads one by one to decrease the loads connected to the UPS less than 90 of Its nominal power capacity Note Please follow the following steps to connect the generator e Activate the generator and wait until the operation is stable before supplying power of the generator to the UPS be sure that the UPS is in idle mode Then
12. ct appliances or items of equipment which would overload the UPS e g laser printers etc to the UPS output Place cables in such a way that no one can step on or trip over them x UPS has provided earthed terminal in the final installed system configuration equipotential earth bonding to the external UPS battery cabinets An integral single emergency switching device which prevents further supply to the load by the UPS in any mode of operation should be provided in the building wiring installation x An appropriate disconnect device as short circuit backup protection should be provided in the building wiring installation 1 For three phase equipment connection to an IT power system a four pole device which disconnect all phase conductors and the neutral conductor should be provided in the building wiring installation X This is permanently connected equipment it must be installed by qualified maintenance personnel x Earth connection essential before connecting to the building wiring terminal 1 2 Operation Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cancel the protective earthing of the UPS system and of all connected loads The UPS output terminal block may be electrically lived even if the UPS system is not connected to the building wiring terminal Xx In order to fully disconnect the UPS first press the OFF button then disconnect t
13. e installing a new parallel UPS system user need to prepare the input and output wires the output breaker and the parallel cable 2 Turn off the input and output breakers of each UPS Connect the input wires output wires and battery wires Remove the 25 short connection wire between JP1 and JP2 on the terminal block Remove the maintenance cover board of each UPS and set the maintenance switch from UPS to BPS Remove the cover board of the parallel port on the UPS connect each UPS one by one with the parallel cable screw the cover board of the parallel port back again Turn on the battery switch and the input breaker of the each UPS measure the difference voltage between the output line wires of each UPS to check if the voltage difference between them is less than 1V If the difference is less than 1V close the output breaker lf the difference is more than 1V check if the wirings are abnormal Close the input breakers of all of the UPSs in the parallel system After all of the UPSs transfer to the Bypass mode screw the maintenance cover board back again Turn on each UPS in turn and observe their display Make sure that each UPS displays normal and all the UPSs transfer to the INV mode together Measure the voltage on the JP1 and JP2 on the terminal block of each UPS to check if the voltage difference between them is less than 1V If the voltage difference is more than 1V the output relay of the UPS may not be
14. e number indicate the quantity vis Y Suv SV e V ISSA i A CHARGING SH a Hz Z _MAINS SETTING 50 60Hz 208 220 230 240 Vac BYPASS ON OFF Parallel mode 10 6 Warning mode The LCD display in warning mode is shown in the following diagram The information about the utility power the battery the UPS output and the load could be displayed The WARNING indicates the UPS is working in warning mode When the UPS operating in warning mode the information in code display alternates between symbol warning code and parallel code e d V ESA CHARGING o Hz BATTERY MAINS OUTPUT SETTING 50 60Hz 208 220 230 240 Vac BYPASS ON OFF Warning mode Fan Error 3 9 10 7 Fault mode The LCD display in fault is shown in the following diagram The information about the utility power the battery the UPS output and the load could be displayed The symbol FAULT indicates the UPS is working in fault mode When the UPS operating in fault mode the information in code display fault code ooo V nnn MEM CHARGING ON Hz MAINS SETTING 50 60Hz 208 220 230 240 Vac BYPASS ON OFF Fault mode Bus Fault Note If mode code is 10 it means that Inner Communication Fault and all the information of the UPS have not be shown except fault code information like the following diagram Communication Fault mode 4 0 11 Setting by LCD Module The output voltage rating and
15. e o id 3 0 7 Battery Maintenance A III II III eee rier eee 3 1 8 Notes for Battery Disposal and Battery Replacement 3 2 9 Trouble Shooting O ES A 3 3 10 Operating mode for all models ee 3 5 10 1 No Output mode ENTENTE 3 5 10 2 Bypass mode EE 3 6 10 3 Line mode A tl EEN 3 T 10 4 Battery mode Battery Test mode AEREA ea vin E PESE REDEE 3 8 10 5 Parallel mode RRE 3 8 10 6 Warning mode SE 3 9 10 7 Fault mode ERRATA A AA A A AA A AR A AAA AAA A AA A 4 0 11 Setting by LCD Module ASAS AR ARA AAA ARA A AAA AAA 4 1 12 Communication Port aa 4 5 12 1 RS232 Interface ee CRE RC ARA AA AAA 4 5 12 2 Intelligent slot a a a a aa a a a aa 4 5 12 3 AS400 Interface Option RR RR RR RR RC CEE ESO RD T T 4 5 13 Software for all models AMA 4 7 Appendix 1 The Corresponding Form of the LCD Display 48 Appendix 2 Rear Panel ge AAA AAA 4 9 1 Safety and EMC instructions Please read carefully the following user manual and the safety instructions before installing the unit or using the unit 1 1 Installation x Condensation may occur if the UPS is moved directly from a cold to a warm environment The UPS must be absolutely dry before being installed Please allow an acclimatization time of at least two hours x Do not install the UPS near water or in damp environment Do not install the UPS where it would be exposed to direct sunlight or near heat x Do not block ventilation openings in the UPS s housing Do not conne
16. e output after 1 frequency in Battery Anie mode Voltage Power Frequency Regulation Factor tolerance Distortion Overload capacity 3 Operating Environment Temperature Humidity Altitude Storage temperature EE me cac Note if the UPS is installed or used in a place where the altitude is above than 1000m the output power must be derated in use please refer to the following Altitude M 1000 1500 2000 2500 3000 3500 4000 4500 5000 1009 95 91 86 82 78 74 70 67 Derating Power 4 Display Panel Select Button Enter Button WARNINGFAULT AA av EH l l E mm cow EM Ee EM ERROR LCD Screen GEN misis Y SEBA GG A DISCHARGING BH Hz BATTERY MAINS OUTPUT SETTING 50 GH 206 220 230 240 Vas BYPASS ON OFF ON Button Alarm Silence OFF Button ON Button OFF Button Select Button Enter Button Turn on UPS system By pressing the ON Button the UPS system is turned on Deactivate acoustic alarm By pressing this Button an acoustic alarm can be deactivated When mains power is normal the UPS system switches to No output or Bypass mode by pressing OFF Button and the inverter is off At this moment if Bypass is enabled then the output sockets are supplied with voltage via the bypass if the mains power is available If the UPS system is No output or Bypass mode the output voltage and frequency and Bypass disable enable c
17. e the battery individually All the batteries should be replaced at the same time following the instructions of the battery supplier Normally the batteries should be charged and discharged once every 4 to 6 months Charging should begin after the UPS shuts down automatically in the course of di scharging the standard charging time for the standard UPS should be at least 12 hours 3 1 8 Notes for Battery Disposal and Battery Replacement 1 2 Before disposing of batteries remove conductive jewelry such as necklace wristwatches and rings lf it is necessary to replace any connection cables please purchase the original materials from the authorized distributors or service centers so as to avoid overheat or spark resulting in fire due to insufficient capacity Do not dispose of batteries or battery packs in a fire they may explode Do not open or mutilate batteries released electrolyte is highly poisonous and harmful to the skin and eyes Do not short the positive and negative of the battery electrode otherwise it may result in electric shock or fire Make sure that there is no voltage before touching the batteries The battery circuit is not isolated from the input potential circuit There may be hazardous voltage between the battery terminals and the ground Even though the input breaker is disconnected the componenis inside the UPS are still connected with the batteries and there are potential hazardous voltag
18. econd The UPS cannot The UPS is not power on after connected to the Check the battery or recharge the pressing the ON battery or the battery battery button pack voltage is too low UPS fault Please contact the distributor or SC service center When you contact the service center please provide the following information e Model No and the serial No of the UPS e The date when the problem arose e Complete description of the problem including the LCD display code alarm warning and power condition and load capacity If your UPS is a long backup time model you may also provide the information of the external battery pack Battery aged 3 4 10 Operating mode for all models The different codes could be displayed on the LCD screen corresponding to their own operating modes and they are illustrated as the follow Operating mode Warning Code Table ID Loss 21 Charger Bad Fan Error 22 IP Fuse Open 3 Inverter Fault E Negative Output Power Fault O Overload Fault Over temperature Fault Inverter Short Communication Fault Battery Open Inverter Relay Short Bus Faut OS Inverter Fault mp Overload Faut 07 Over temperature Fault 08 Inverter Shot 09 Communication Faut 10 Battery Open 11 Inverter Relay Short 12 10 1 No Output mode The LCD display in no output mode is shown in the following diagram The information about the utility power the battery the UPS output and the load
19. ected when the UPS is in No output or Bypass mode and only one of them could be active in the same time The two frequency value of the output voltage could be selected when the UPS is in No output or Bypass mode and only one of them could be active in the same time Bypass disable or enable could be selected when the UPS is in No output or Bypass mode and only one of them could be active in the same time Notes For 311 10KS UPS only the information of phase C will be shown while for 3T1 15KS 20KS UPS only the information of phase A will be shown 12 5 Installation The system may be installed and wired only by qualified electricians in accordance with applicable safety regulations 5 1 Unpacking and Inspection 1 Unpack the packaging and check the package contents The shipping package contains o AUPS e A user manual e A communication cable e A battery cable for 6KS 10KS 3T1 10KS only 2 Inspect the appearance of the UPS to see if there is any damage during transportation Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of some parts 5 2 Input and output power cords and protective earth ground installation 1 Notes for installation 1 The UPS must be installed in a location with good ventilation far away from water inflammable gas and corrosive agents 2 Ensure the air vents on the front and rear of the UPS are not blocked Allow at
20. ependent on the external battery pack capacity and the load level as well as other factors The backup time of standard model may vary from different models and load level Please refer to the following 60 50 T T E E 40 SE o E E E O E 30 D D m j K O O A un 20 o A 10 0 25 50 75 100 0 25 50 75 100 Load level Load level Backup time of 6K Backup time of 10K 3 0 7 Battery Maintenance This series UPS only requires minimal maintenance The battery used for standard models are value regulated sealed lead acid maintenance free battery These models require minimal repairs The only requirement is to charge the UPS regularly in order to maximize the expected life of the battery When being connected to the utility power whether the UPS is turned on or not the UPS keeps charging the batteries and also offers the protective function of overcharging and over discharging The UPS should be charged once every 4 to 6 months if it has not been used for a long time In the regions of hot climates the battery should be charged and discharged every 2 months The standard charging time should be at least 12 hours Under normal conditions the battery life lasts 3 to 5 years In case if the battery is found not in good condition earlier replacement should be made Battery replacement should be performed by qualified personnel Replace batteries with the same number and same type of batteries Do not replac
21. es Therefore before any maintenance and repairs work is carried out switch off the breaker of the battery pack or disconnect the jumper wire of connecting between the batteries Batteries contain hazardous voltage and current Baitery maintenance such as the baitery replacement must be carried out by qualified personnel who are knowledgeable about batteries No other persons should handle the batteries 3 2 9 Trouble Shooting Problem Possible cause Solution The Fault code is 08 and the buzzer beeps continuously The Fault code is 09 and the buzzer beeps continuously The Fault code is 05 or 06 the UPS beeps continuously The UPS turn into Battery mode The Fault code is 07 the UPS beeps continuously The Warning code is 23 the buzzer beeps every second The UPS transfers to fault mode due to internal overheat The UPS output is short circuited The UPS transfers to fault mode due to its internal fault The voltage or frequency of the utility power is out of the input range of the UPS The UPS is overloaded or the load equipment is faulty The charger of the UPS is defective 33 Make sure the UPS is not overloaded the air vents are not blocked and the ambient temperature is not too high Wait for 10 minutes for the UPS to cool down before turning on again If failed please contact the distributor or service center Remove al
22. frequency rating and bypass state could be set directly through LCD Display The output voltage rating could be set to 208V 220V 230V and 240V The output frequency rating could be set to 50Hz and 60Hz The bypass state could be set to enable and disable But all the settings could only be done when the UPS is in Bypass or No Output mode In Bypass or No Output mode press the Select button on the LCD panel for more than one second a flickering black line would be shown underside 50 on the screen And if press the Select button continuously again the flickering black line would move to 60 next to around 208 220 230 240 ON OFF in turn And if press the Enter button for more than one second at this time the flickering black line would turn to flicker less and the output voltage rating or frequency rating or bypass state setting would be modified to the selected value And if no any pressing on the Select or Enter button lasting for more than ten seconds the flickering black line would disappear no setting have be modified The only one voltage rating could be selected in 208 220 230 240 at any time only one frequency rating could be selected in 50 60 at any time and the output voltage and frequency would be changed to the corresponding value after turning on the UPS by pressing the ON button The UPS would turn into Bypass mode in several seconds a
23. fter ON is selected and turn into No Output mode in several seconds after OFF is selected Note When the output voltage rating be set to 208V the output power must be derated to 90 Here is an example for changing the output voltage from 220 to 230 through the LCD panel 4 1 DV eV 3 5 A CHARGING S0 Hz SETTING 50 60Hz 208 220 230 240 Vac BYPASS ON OFF STEP 1 One flickering black line would appear underside 50 after pressing the Select button Bv CHARGING SETTING 50 60Hz 208 220 230 240 Vac BYPASS ON OFF STEP 2 The flickering line would move to underside 230 after pressing the Select button four times again 42 CHARGING SETTING 50 60Hz 208 220 230 240 Vac BYPASS ON OFF STEP 3 The line underside 230 would turn to flicker less after pressing the Enter button and the flickering line would move to the next 240 TE y ENANA Pu TAS Jn LD d p lt CHARGING SETTING 50 60Hz 208 220 230 240 Vac BYPASS ON OFF STEP 4 The output voltage rating have been modified to 230 and UPS work in Bypass mode 4 3 Ll wiy Y Ev Tu EIR LOL LD T P e GEI EI 550 Hz 50 60Hz 208 220 230 240 Vac BYPASS ON OFF CHARGING B ERY STEP 5 The output voltage would be 230Vac after the UPS is turned on 44 12 Communication Port 12 1 RS232 Interface The following is the pin assignment and description of DB 9 con
24. ger and battery failed Note Pn indicate the quantity of the parallel system Beep once every 10 sec Beep once every sec Beep once every sec Parallel abnormal 4 8 Appendix 2 Rear Panel Communication Port Intelligent Slot Cooling Fan Parallel Port External Battery Maintenance Bypass Switch Input Breaker Terminal Blocks Cover Communication Part Intelligent Slat Cooling Fan Parallel Port External Battery Input Breaker Maintenance Bypass Switch Terminal Blocks Cover Back view of 10K Back view of 10KS 4 9 Intelligent Slot Parallel Port External Battery Socket Input Breaker Maintenance Switch Terminal Blocks Cover Fan Intelligent Slot Parallel Port RS232 Maintenance Input Breaker Switch Terminal Blocks Cover Back View of 3T1 15KS 20KS 50 614 00165 00
25. he mains lead Ensure that no liquid or other foreign objects can enter the UPS The UPS can be operated by any individuals with no previous experience 1 3 Maintenance servicing and faults x The UPS operates with hazardous voltages Only qualified maintenance personnel may carry out repairs x Caution risk of electric shock Even after the unit is disconnected from the mains power supply building wiring terminal components inside the UPS are still connected to the battery which are potentially dangerous X Before carrying out any kind of service and or maintenance please disconnect the batteries Verify that no current is present and no hazardous voltage exists in the capacitor or BUS capacitor terminals k Batteries must be replaced only by qualified personnel x Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Verify that no voltage is present before servicing x Batteries have a high short circuit current and pose a risk of shock Take all precautionary measures specified below and any other measures necessary when working with batteries remove all jewellery wristwatches rings and other metal objecis use only tools with insulated grips and handles x When changing batteries replace with the same quantity and the same type of batteries x Do not attempt to dispose of batteries
26. l o o o 9 e e wa s s jajjesed S yOL S X9 JO weibeip DUU Output Line Input Line Input Neutral Jayeaigindinozsdn 1938318 IndinO Lsdn E a o Pear Jayeaig ndul ZSdN Zd df Zd df 9 0 o o o o Input Ground 20 UIS S S jojjesed SAOL LLE JO wueibeip Buu O co st 23 e Ls s z 3 3 SS Oz c E E o Ss e a J q amp S 3 5 3 3 5 a a a a a Doo E E 1948918 INdINOZSdN 19489318 indinO LSdN jeyeaigindujZSdN Y eresia imaurisan A o III Ao O O RR td df lolalalalajalcla cdf df poa wia sAs ojjeJed SA0Z SASL LLE JO weep Bul EA a Es ad 5 2 3 E O ar N lt 2 An gt a a a D apud D a 3 o OO O ke 1192818 INdINO ZSAN IE ry o e o 2 2 o e e Battery 1 Input Line Wire C Input Line Wire B Input Line Wire A Input Neutral Input Ground 1942918 IndINOLSAN Jjayesalg indy isdn o e o e o e fe fo 2 2 Operation and maintenance 1 To perform the general operation follow the stand alone operating requirement 2 Startup The units transfer to INV mode simultaneously as they start up sequentially in Line mode 3 Shutdown the units shut down sequentially in INV mode When the last one completes the shutdown action each unit will shut down the inverter simultaneously and transfer to Bypass mode It is easy to operate the equipment with no previ
27. l the loads Turn off the UPS Ensure that the load is not failed or the UPS has no internal faults before turning it on again If failed please contact the distributor or service center Please contact the distributor or service center The UPS is running in Battery mode To save your data and close the application program Make sure the utility power is within the input voltage or frequency range permitted by the UPS Check the loads and remove all no critical equipment Recalculate the load power and reduce the number of loads connected to the UPS Check that the loads are not failed Please contact the distributor or service center Check the battery If the battery is The Fault code is Battery low or battery damaged replace the battery 11 the UPS immediately and ensure that the beeps continuously EENEG battery breaker is in ON position The utility power is normal but the E Please contact the distributor or Maintain switch loose l UPS can not turn service center into Line mode Keep UPS connected to utility Battery not yet been power persistently for more than fully charged 10 hours to recharge the batteries again Battery discharging Check the loads and remove the time diminishes DEE non critical equipment Replace the batteries Please contact the distributor to obtain the parts and replacement service The ON button is Press the ON button for more pressed too briefly than 1 s
28. nector Pin Description UO 12 2 Intelligent slot This series is equipped with an intelligent slot for Webpower optional accessory or other optional card to achieve remote management of the UPS through internet intranet Please contact your local distributor for further information 12 3 AS400 Interface Option Except for the communication protocol as mentioned above this series UPS has AS400 card an optional accessory for AS400 communication protocol Please contact your local distributor for details The following is the pin assignment and description of DB 9 connector in AS400 card Description vo Ping Description vo UPS Fail Output 6 Bypass Output Summary Alarm Output Battery Low Output UPS ON Pet 3 mp ma 8 4 Remote Shutdown Input 9 LineLoss Output NA in IA 45 BYPASS SUMMARY ALARM REMOTE SHUTDOWN LINE FAIL COMMON DB 9 Interface of AS400 communication protocol 46 13 Software for all models Free Software Download WinPower WinPower is a brand new UPS monitoring software which provides user friendly interface to monitor and control your UPS This unique software provides safely auto shutdown for multi computer systems while power failure With this software users can monitor and control any UPS on the same LAN no matter how far from the UPSs E Winpower Manager Yer1 0 agent Read Wes a oj xj System Logs UPS Tools Monitor
29. oad the two low grids represent 60 load the three low grids represent 90 load all the grids represent 100 load Indicates the battery voltage value which could be displayed from O to 999Vdc Indicates the battery current value which could be displayed from O to 999A Indicates the battery capacitance percent and every grid represent 25 capacitance All the grids represent 100 capacitance CHARGING NEE me EISE of UPS is working and the battery is being discharged DISCHARGING Indicates the charger of UPS is not working OVER Indicates the battery is over charged and the UPS VOLT would be switched to Battery mode LOW Indicates the battery is weak and the UPS would shut down soon 1 1 UPS status Information Indicates the status of the UPS Fault Warning code or the quantity of the parallel system could be displayed and the codes are illuminated in detail in the following chapter Indicates the operating mode of the UPS in graphics mode The will be displayed when the mains power is normal The will be displayed when the UPS is working in bypass mode The will be displayed when the UPS is working in battery mode The will be displayed when the inverter is working normal FAULT Indicates the UPS is working in fault mode WARNING Indicates some warnings occur which need be attention UPS setting Information 208 220 230 240 Vac BYPASS ON OFF The four value of the output voltage could be sel
30. oltage value is less than 5V Generally 2V If the difference is more than 5V that means the new UPS needs to be regulated again or you need to check that the parallel cable of the parallel kit are normal 12 Turn off each UPS in turn and after all of them transfer to the Bypass mode remove the maintenance cover board of each UPS and set the maintenance switch from BPS to UPS and screw the maintenance cover board back again 13 Turn on the UPSs in the Line mode to perform the parallel operation Note If the UPS is abnormal in the above debugging please perform maintenance according to the steps of removing a stand alone 4 How to remove a single UPS from the parallel system 1 lf you need to remove one UPS of the UPSs parallel system which is on normal running press the OFF button of the UPS that is confirmed to be removed twice continuously and the UPS will cut off its output immediately Turn off the input breaker the external mains input breaker the output breaker and the battery switch of the UPS that will be removed Press the others UPSs s OFF button After all of them transfer to the Bypass mode remove the cover board of each UPS and set the maintenance switch from UPS to BPS and then turn off the input breaker of each UPS 28 After you remove one UPS you need to connect the short connection wire of the JP1 and JP2 located on the Terminal block of the UPS if the remained UPS sy
31. ould be selected by pressing Select Button and confirmed by pressing Enter Button If the UPS system is No output or Bypass mode the output voltage and frequency and Bypass disable enable could be selected by pressing Select Button and confirmed by pressing Enter Button UPS Status Battery information information Load information 9 OVER WARNINGFAULT DD OVER EH mm E E e In d De ES Ny Low Es a it Mi error Ml sort G 888V B8B8V BBaVv BRBA BESA BREA 1 DISCHARGING BB Hz BEHz dt ouTPUT SETTING 50 60Hz 208 220 230 240 Vac BYPASS ON OFF UPS Setting Mains power Output information information The LCD Display Mains power Information Indicates the input voltage value which could be displayed from 0 to 999Vac Indicates the frequency value of input voltage which could be displayed from 0 to 99Hz Indicates the input current value which could be displayed from O to 999A Output Information Indicates the UPS output voltage value which could be displayed from 0 to 999Vac 10 Indicates the frequency value of the UPS output voltage which could be displayed from 0 to 99Hz Indicates the UPS output current value which could be displayed from O to 999A Indicates the load or the UPS output is short and the UPS would shut down Indicates the load is over the SPEC range Indicates the load percent and the lowest grid represent 30 l
32. ous training You just need to read through this manual and operate according to the instructions in it Input switchboard UPS UPS UPS Seefe Load Load Load Load Parallel Installation Diagram 23 6 Operation 6 1 Operation Mode 1 Turn on the UPS with utility power supplied in Line mode 1 After you make sure that the power supply connection is correct and then set the breaker of the battery pack in the ON position this step only for long backup time model after that set the input breaker in the ON position At this time the fan rotates and the UPS supplies power to the load via the bypass The UPS operates in Bypass mode To power on the UPS by simply pressing the ON button continuously for more than 1 second the buzzer will beep once A few seconds later the UPS turn into Line mode If the utility power is abnormal the UPS will operate in Battery mode without output interruption of the UPS 2 Turn on the UPS with no utility power supplied in Battery mode 1 2 3 After you make sure that the breaker of the battery pack is in the ON position this step only for long backup time model Press the ON button continuously for more than 1 second to power on the UPS and the buzzer will beep once UPS operates in No Output mode A few seconds later the UPS turn into Battery mode 3 Turn off the UPS with utility power supplied in Line mode 1 To turn off the inverter of
33. r the X is the higher reliability of the power system is For occasions where reliability is highly depended on N X is the optimal mode As long as the UPS is equipped with parallel cables up to 3 UPSs can be connected in parallel to realize output power sharing and power redundancy 18 2 Parallel installation 1 Users need to opt a standard 25 pin communication cable which should have 25 cores corresponding stitches and shield as the UPS parallel cable The length of the parallel cable is appropriate to be less than 3 m Strictly follow the stand alone wiring requirement to perform the input wiring of each UPS Connect the output wires of each UPS to an output breaker panel Disconnect the Jumper on JP1 and JP2 of the terminal block first and connect each output breaker to a main output breaker and then to the loads Each UPS need an independent battery pack Please refer to the wiring diagram in the next page and opt sultable breaker The requirement of the output wiring is as follows e When the distance between the UPSs in parallel and the breaker panel is less than 20 meters the difference between the wires of input amp output of the UPSs is required to be less than 20 e When the distance between the UPSs in parallel and the breaker panel is greater than 20 meters the difference between the wires of input output of the UPSs is required to be less than 10 1 9 Output Ground Output Neutra
34. sion design eliminates all mains power disturbances A rectifier converts the alternating current from the utility power to direct current This direct current charges the batteries and powers the inverter On the basis of this DC voltage the inverter generates a pure sinusoidal AC voltage which is constantly powering the loads Computers and Peripherals are thus powered entirely by the UPS In the event of power failure the maintenance free batteries power the inverter This manual is applicable to the following models Model No 10KS 311 10KS 311 15KS 311 20KS S Model Long backup time Standard Long backup time 3 2 Product Specification and Performance 1 General Specification Model Lm ok 10k 1oxs ams miss gris Power Rating A ee eee oe Battery Voltage 208 220 230 240V ac 26 27 26 25A 43 45 43 42A 43 45 43 42A 65 68 65 63A 87 91 87 83A Dimension WxDxH mm 260x570x717 260x570x717 260x570x717 260x570x717 260x570x717 won oo as oo 00 39 s 2 Electrical Performance 6K S 10K S Single phase iia us 56 64Hz Full load 3T1 10KS 15KS 20KS Three phase E SC 56 64Hz Full load Current crest ratio Ee 4Hz in 105 130 load transfers to Line mode AC THD lt 2 Bypass mode after 10 minutes 1 0 7 lag mode Full load gt 130 load transfers to Bypass 3 1 g 01 of Linear mode after 1 second and maximum Sa CARA a Load shutdown th
35. stem only remain one UPS runs by itself After all panels of the UPSs do not display anything any more remove the cover board of the parallel port on the UPS connected with the parallel cable of the UPS that need to be removed Remove the parallel cable and screw the cover board of the parallel port back again Remove the cover board of the parallel port located on the UPS that need to be removed and remove the parallel cable and then screw the cover board back again Close all of the input mains breakers of the remained UPSs After all UPSs transfer to the Bypass mode set the UPS maintenance switch from BPS to UPS and screw the maintenance cover board back again Then turn on all of the UPSs in the Line mode to perform the parallel operation If the removed UPS will be used in a stand alone mode then JP1 and JP2 on the terminal block should be connected with a short connection wire Combine machine warning 1 When UPS combine system work at inverter mode make sure that all UPS maintain switches at the same place that is to say be at the position of UPS or be at the position of BPS 2 When turning on the UPS combine system before enter into inverter mode UPS output switch must at the OFF position 3 When UPS combine system work at inverter model please do not operate any UPS maintain switch 2 9 6 3 Backup time for the standard model The backup time of the long backup time model is d
36. turn on the UPS according to the start up procedure After the UPS is turned on then the loads can be connected to the UPS one by one e The power capacity of the AC generator should be at least twice of the UPS capacity 31 10 4 Battery mode Battery Test mode The LCD display in Battery mode is shown in the following diagram The information about the utility power the battery the UPS output and the load could be displayed The symbol of Mi and EX indicates the UPS is working in battery mode When the UPS is running in Battery mode the buzzer beeps once every 4 seconds If the ON button on the front panel is pressed for more than 1 second again the buzzer will stop beeping in silence mode Press the ON button once again for more than 1 second to resume the alarm function L_i 230V tow V IG IA ODA DISCHARGING nN Hz SETTING 50 60Hz 208 220 230 240 Vac BYPASS ON OFF als Y Battery mode The display of battery test mode is same as Battery mode 10 5 Parallel mode The LCD display can show the UPS quantity of the parallel system and the UPS system that operating in single mode should be regarded as a special parallel system single mode is a special parallel mode The LCD display in parallel mode is shown in the following diagram When the UPS operating in parallel mode the information in code display Pn The symbol P means the UPS 38 113 n operating in parallel mode and th
37. urned and destroyed Connect the input and output wires to the corresponding input and output terminals according to the following diagram Note you must make sure that the input and output wires and the 6 input and output terminals are connected tightly The protective earth ground wire refers to the wire connection between the equipment which consumes electric equipment and the ground wire The wire diameter of protective earth ground wire should be at least as above mentioned for each model and green wire or green wire with yellow ribbon wire is used 14 7 After having completed the installation make sure the wiring is correct 8 Please install the output breaker between the output terminal and the load and the breaker should with leakage current protective function if necessary 9 To connect the load with the UPS please turn off all the loads first then perform the connection and finally turn on the loads one by one 10 No matter the UPS is connected to the utility power or not the output of the UPS may have electricity The parts inside the unit may still have hazardous voltage after turning off the UPS To make the UPS have no output power off the UPS and then disconnect the utility power supply 11 Na Suggest charging the batteries for 8 hours before use After connection turn the input breaker in the ON position the UPS will charge the batteries automatically You can also use the U