Home

Installation Manual

image

Contents

1. Indoor unit No 1 No 2 No 3 No 4 No 7 No 8 AlB AJB AJB AB AJB AJB A B Remote controller ne B Connection of power wires and communication wires Remove knockouts on the piping wiring panel on the front of the unit and the panel on the bottom to get the power and communication wires through the holes Knockout for the communication wire Knockout for the power wire Joa II p T Zp p Piping wiring panel zu Knockout for the power supply wire NOTE Be sure to separate the power wire and communication wires 42 EN Power supply terminal block Cord clamps Communication terminal block Power supply wires Cord clamp Earth screw Communication amp e O wires Power supply wire connection 1 Insert the power supply wire through the cutout on the side of the electrical control box and connect the power supply wire to the power supply terminal block and the earth line to the earth screw After that fix the power supply wire with the 2 cord clamps 2 Be sure to use round type crimping terminals for power connection Also apply insulating sleeves to the crimping parts Use a driver of appropriate size to fix the terminal screws Se eee L1 L2 L3 JL N e e e eja H L2 L3 N
2. Table 2 Combined HP HP Combined outdoor units HP pore reed al 8 8HP 1 5 10 10HP 2 5 12 12HP _ 3 5 14 14HP _ _ 8 5 16 16HP 10 5 18 10HP 8HP a 0 0 20 10HP OHP 3 0 22 12HP OHP 5 0 24 12HP 2HP 75 26 16HP OHP 8 5 Standard type 28 16HP 2HP 9 5 30 16HP 4HP 11 5 32 16HP 6HP i 12 5 34 12HP 2HP OHP 3 0 36 12HP 2HP 2HP 4 0 38 16HP 2HP OHP 6 0 40 16HP 2HP 2HP 7 0 42 16HP 4HP 2HP 8 0 44 16HP 6HP 2HP 10 0 46 16HP 6HP 4HP 12 0 48 16HP 6HP 6HP 14 0 16 8HP 8HP 0 0 24 8HP 8HP 8HP 4 0 26 10HP 8HP 8HP E 4 0 28 10HP OHP 8HP 2 0 30 10HP OHP 10HP 0 0 32 8HP 8HP 8HP 8HP 6 0 E S 34 10HP 8HP 8HP 8HP 6 0 36 10HP OHP 8HP 8HP 6 0 38 10HP OHP OHP 8HP 6 0 40 10HP OHP OHP 10HP 5 0 42 12HP OHP OHP 10HP 4 0 44 12HP 2HP OHP 10HP 2 0 46 12HP 2HP 2HP 10HP 0 0 48 12HP 2HP 2HP 12HP 2 0 Charging of refrigerant Keeping the valve of the outdoor unit closed be sure to charge the liquid refrigerant into the service port at the liquid side f the specified amount of refrigerant cannot be charged fully open the valves of the outdoor unit at liquid and gas sides operate the air conditioner in COOL mode and then charge refrigerant into service port at the gas side In this time choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant The liquid refrigerant may
3. 10mm or more 1 9 9 9 Earth line Power supply wire 43 EN Screw size and tightening torque Screw ise Tightening torque Nem Power supply terminal M6 2 5 to 3 0 Earth screw M8 5 5 to 6 6 Communication wire connection Get the communication wire through the cu terminals then fix it with the communication cable clamp I fur ve vs ve us ve TO TO INDOOR UNIT TO CENTRAL OUTDOOR CONTROL UNIT LER EN Us Ue Communication wiring between outdoor units Screw size and tightening torque out on the side of the electrical control box and connect it to the communication wire U3 U4 Central control device U1 U2 Communication wiring between Indoor Outdoor unit Screw size Tightening torque Nem Communication wire terminal M4 1 2 to 1 4 22 44 EN 45 EN m Regulation of high frequency wave This equipment complies with IEC 61000 3 12 provided that the short circuit power Ssc is greater than or equal to Ssc 1 atthe interface point between the user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessary that the equipment is connected only to a supply with a short circuit power Ssc greater than or equal to Ssc
4. 1 If exceeding the main pipe size set the size to the same as the main pipe size 13 No Piping parts Name Selection of pipe size Remarks Connecting pipe size of indoor unit Liquid Capacity rank Gas side side Branching section 007130124 15m or less real length 99 5 06 4 n o e 5 v Indoor Unit ap Real length exceeds 15m 9127 96 4 Indoor unit Cone g pipe 015 to 018 type 012 7 96 4 024 to 056 type 015 9 99 5 072 to 096 type 022 2 912 7 Selection of branching section Y shaped branching joint Total capacity code of indoor units Equivalent to Model name Equivalent to HP capacity i i Y shaped 6 Branching section Saneti g joint Below 6 4 Below 18 0 RBM BY55E Y shape 6 4 to below 14 2 18 0 to below 40 0 RBM BY105E branching joint 14 2 to below 25 2 40 0 to below 70 5 RBM BY205E 25 2 or more 70 5 or more RBM BY305E Selection of branching section Branching header Total capacity code of indoor units P Equivalent to Model name Equivalent to HP capacity For 4 Below 14 2 Below 40 0 RBM HY1043E 2 branches 142 to below 25 2 40 0 to below 70 5 RBM HY2043E 7 Branching section Branching header Branching header c Below 14 2 Below 40 0 RBM HY1083E branches 142 to below 25 2 40 0 to below 70 5 RBM HY2083E 2 Up to a total of 6 0 maximu
5. Unit mm Model type A B MAP0804 MAP1004 MAP1204 700 990 MAP1404 1604 920 1210 2 When drawing out the refrigerant pipe from the underside set the height of the stand to 500mm or more 500mm or more outdoor unit NO GOOD Iso o OLD 3 Do not use 4 stands on the corner to support the GOOD uy Wb 4 Mount the vibration proof rubber including vibration proof blocks so that it fits under the whole clamping leg GOOD Anchor bolt Vibration proof rubber NO GOOD d Install the vibration proof rubber so that the bent part of the fixing leg is grounded The bent part of the fixing leg is not grounded NO GOOD GOOD NO GOOD so 16 EN 5 Be careful of the connecting arrangement of the header unit and follower units Set the outdoor units in order of capacity from the one with the largest capacity A Header unit gt B gt C gt D Be sure to use a header unit for the leading outdoor unit to be connected to the main pipe Figure 1 and 3 outdoor unit Be sure to use a T shaped branch joint RBM BT14E RBM BT24E separately purchased to connect each Be careful of the direction of the Outdoor unit connection piping kit for the liquid side As shown in Figure 2 a Outdoor unit connection piping kit cannot be attached so that the refrigerant of the main pipe flows directly into
6. 4 1 2 3 4 1 x x x x x 2 x o x x x 3 x x o x x 4 x o x x 5 x x x o x 6 x o x o x Z _ _ x x o o x 8 x o x 9 _ _ x x x x o 10 x o x x 11 _ _ x x x 42 _ _ x o o x o 13 x x x o o 14 x o x o 15 _ _ x x o 16 _ _ x o o o o 17 x x x x 18 _ _ x x x 19 _ _ o x o x x 20 o o o x x 21 x x x 22 _ _ x o x 23 o x o x 24 _ _ o o x 25 x x x 48 EN 49 EN SW13 Sw14 Line system address 1 2 3 4 1 2 3 4 26 Oo x x 27 _ _ _ Oo x Oo x Oo 28 Oo x Oo not used for system address setting Do not change their positions 2 Be sure to disconnect the relay connectors between the U1U2 and U3U4 terminals on all the header outdoor units that will be connected to the central control Factory default disconnected TO TO TO CENTRAL INDOOR CONTROL OUTBOOR LER Turn on indoor units first and then turn on outdoor units About 1 minute after turning the power on confirm that the 7 segment display on the interface P C board of the header outdoor unit indicates U 1 L08 U 1 flash Press SW 15 to start the automatic address setting It may take up to 10 minutes normally about 5 minutes to complete one line s setting oO A AQ The 7 segment display indicates
7. Thank you for purchasing this Toshiba air conditioner This Installation Manual describes the installation method of the outdoor unit For installation of indoor units follow the Installation Manual supplied with the indoor unit Moreover as this installation manual includes the important articles concerning the Machinery Directive Directive 2006 42 EC please read through the manual and make sure you understand it After installation give this Installation Manual the Owner s Manual and the Installation Manual supplied with the indoor unit to the customer and tell the customer to keep them safe Prepare an exclusive power source for indoor units independent to that for outdoor units Y shaped branching joints or a branching header separately purchased are required for connecting pipes between indoor and outdoor units Choose either of them considering the system capacity concerning piping For installing branching pipes refer to the installation manual of the Y shaped branching unit or branching header separately purchased Outdoor connecting branching joints are required for connecting between outdoor units Generic Denomination Air Conditioner Definition of Qualified Installer or Qualified Service Person The air conditioner must be installed maintained repaired and removed by a qualified installer or qualified service person When any of these jobs is to be done ask a qualified installer or qualified service person to
8. S A E i La Lb Lc 2 o o UO 5 o LA LB Outdoor unit connection piping kit For linking of outdoor units a ipii its The longest piping between outdoor units c LO lt 25m Es a n Branching header Indoor unit connecting L7 mn branching First branching pipe section Indoor unit a b c d L3 The longest piping length L lt 235 m The longest piping length from the first branch Li lt 90 m Y shaped branching joint L4 L5 i f g h i Indoor unit 27 EN Height difference between indoor units H2 lt 40m 414 System restriction Outdoor unit combination Up to 4 units Total capacity of outdoor units Up to 48 HP Indoor unit connection Up to 48 units Total capacity of indoor units H2 lt 15m 135 of outdoor units capacity varies depending on the height difference between indoor units 15m H2 105 of outdoor units capacity Cautions for installation Set the outdoor unit first connected to the bridging pipe to the indoor units as the header unit Install the outdoor units in order of their capacity codes A header unit gt B gt C gt D When connecting gas pipes to indoor units use Y shaped branching joints to keep pipes level When piping to outdoor units using Outdoor unit connection piping kits intersect the pipes to the outdoor unit and those to indoor units at a right angle as shown in
9. Whencarrying outthe pump down work shut down the compressor before disconnecting the refrigerant pipe Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or other gas to be sucked in raising the pressure inside the refrigeration cycle to an abnormally high level and possibly resulting in rupture injury or other trouble Never recover the refrigerant into the outdoor unit Be sure to use a refrigerant recovery machine to recover the refrigerant when moving or repairing It is impossible to recover the refrigerant into the outdoor unit Refrigerant recovery into the outdoor unit may result in serious accidents such as explosion of the unit injury or other accidents 1 Refer to the Definition of Qualified Installer or Qualified Service Person NCAUTION New refrigerant air conditioner installation This air conditioner adopts the new HFC refrigerant R410A which does not destroy ozone layer The characteristics of R410A refrigerant are easy to absorb water oxidizing membrane or oil and its pressure is approx 1 6 times higher than that of refrigerant R22 Accompanied with the new refrigerant refrigerating oil has also been changed Therefore during installation work be sure that water dust former refrigerant or refrigerating oil does not enter the refrigerating cycle To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connect
10. the header unit Liquid piping Y Figure 1 GOOD Header unit Followerunit Follower unit B c 5 E Main pipe To the indoor unit Gas piping Y Figure 3 GOOD Header unit Followerunit Follower unit B E B SS 2 EM Ej FER ERIT REB Main pipe To the indoor unit Extension valve Y Figure 2 NO GOOD Header unit Followerunit Follower unit A B c zl NO GOOD Main pipe To the indoor unit Inverse connection of a gas side branch unit Y Figure 4 NO GOOD Header unit Follower unit Follower unit A Main pipe To the indoor unit t To gas side branch unit When attaching a Y shaped branch unit for the gas side attach it level with the ground Be sure not to exceed 15 degrees Regarding a T shape branch joints for the liquid side there is no restriction for its angle Horizontal line ACT ee ER eas B A arrow view Within 15 degrees A Within 15 Horizontal line Do not connect a branch unit degrees vertically B a
11. CAUTION High temperature parts You might get burned when removing this panel CAUTION High temperature parts You might get burned when removing this panel CAUTION Do not touch the aluminum fins of the unit Doing so may result in injury CAUTION Do not touch the aluminium fins of the unit Doing so may result in injury CAUTION BURST HAZARD Open the service valves before the operation otherwise there might be the burst CAUTION BURST HAZARD Open the service valves before the operation otherwise there might be the burst CAUTION Do not climb onto the fan guard Doing so may result in injury CAUTION Do not climb onto the fan guard Doing so may result in injury 4 EN 5 EN 1 Precautions for safety The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual NWARNING General Before starting to install the air conditioner read through the Installation Manual carefully and follow its instructions to install the air conditioner Otherwise falling down of the unit may occur or the unit may cause noise vibration or water leakage Only a qualified installer 1 or qualified service person 1 is allowed to do installationwork If installation is carried out by an unqualified individual a fire electric shocks injury water leakage noise and or vibration may result fusing separately sold p
12. Method 2 Clearing all the indoor unit addresses on a refrigerate line at once from the outdoor unit 1 Turn off the refrigerant line to reset to the factory default and set the header outdoor unit of the line as below 1 Disconnect the relay connectors between the U1 U2 and U3 U4 terminals Leave them as they are if they have already been disconnected 2 Turn on dip switch 2 of SW30 on the interface P C board of the header outdoor unit if the Switch is OFF Leave it as it is if it has already been set to ON Central control controller Z Z i meaner Follower unit Header Follower unit Header U3 U4 U3 U4 U3 U4 U3 U4 U3 U4 T us ue u1 u2 us ue u1 u2 us ue u1 u2 us ue U1 U2 U1 U2 U1 U2 A B aJe a B AJB A B BS Remote Remote controller controller ae Remote N Indoor units to have their addresses initialized 2 Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the addresses About one minute after turning on the power confirm that the 7 segment display on the header outdoor unit indicates U 1 and operate the interface P C board on the header outdoor unit of the refrigerant line as fo
13. 01 Compressor 1 H01 02 Compressor 2 03 Compressor 3 Compressor breaking down 01 Compressor 1 H02 02 Compressor 2 03 Compressor 3 Compressor error Locked 01 Compressor 1 H03 02 Compressor 2 03 Compressor 3 Current detection circuit error H05 TD1 sensor miswiring H06 Low pressure protective operation H07 Oil level down detection 01 TK1 sensor error 02 TK2 sensor error H08 03 TK3 sensor error 04 TK4 sensor error 05 TK5 sensor error Temperature sensor error for oil level TD2 sensor miswiring 01 TK1 oil circuit error 02 TK2 oil circuit error H16 03 TK3 oil circuit error 04 TK4 oil circuit error 05 TK5 oil circuit error Oil level detector circuit error H25 TD3 sensor miswiring L04 Outdoor system address duplication L06 Number of prior indoor units Duplication of indoor units with priority L08 Indoor unit group address unset L10 Outdoor unit capacity unset L17 Mismatch of the outdoor unit model L28 Outdoor connected quantity over L29 IPDU number information IPDU quantity error L30 Detected indoor unit address External interlock of indoor unit L31 Other compressor errors P03 Discharge temperature TD1 error 01 Compressor 1 P04 02 Compressor 2 03 Compressor 3 High pressure SW system operation 00 Phase missing power failure detection P05 01 Compressor 1 02 Co
14. 048 5 14 056 6 16 072 8 22 4 096 10 28 Table 2 boar ano aes N o of mee nati aad sia N o of Standard model we to yr units M none T quia nt to ph la units MMY MAP0804 8 22 4 13 MMY MAP1004 10 28 16 MMY MAP1204 12 33 5 20 MMY MAP1404 14 40 23 MMY MAP1604 16 45 27 MMY AP1624 16 45 27 MMY AP1814 18 50 4 30 MMY AP2014 20 56 33 MMY AP2214 22 61 5 37 MMY AP2414 24 68 40 MMY AP2424 24 68 40 MMY AP2614 26 73 43 MMY AP2624 26 73 43 MMY AP2814 28 78 5 47 MMY AP2824 28 78 5 47 MMY AP3014 30 85 48 MMY AP3024 30 85 48 MMY AP3214 32 90 48 MMY AP3224 32 90 48 MMY AP3414 34 96 48 MMY AP3424 34 96 48 MMY AP3614 36 101 48 MMY AP3624 36 101 48 MMY AP3814 38 106 5 48 MMY AP3824 38 106 5 48 MMY AP4014 40 112 48 MMY AP4024 40 112 48 MMY AP4214 42 118 48 MMY AP4224 42 118 48 MMY AP4414 44 123 48 MMY AP4424 44 123 48 MMY AP4614 46 130 48 MMY AP4624 46 130 48 MMY AP4814 48 135 48 MMY AP4824 48 135 48 For combination of the outdoor units refer to Combination of outdoor units 12 Header Follower Follower Follower unit A unit B unit C unit D f i Pe fro ER RH RR Outdoor unit Erg I 1 1 1 2
15. 1 Furthermore when similar equipment or other equipment which may cause harmonic current emissions are to be connected to the same interface point with this equipment to reduce the risk of possible problems which may be caused from addition of those harmonic current emissions it is recommended to make sure that the short circuit power Ssc at the interface point is greater than the sum of the minimum Ssc required by all the equipment which will be connected to the interface point Ssc 1 Model Ssc kVA MMY MAPO0804HT8P JP E 1004 MMY MAP0804T8P JP E MMY MAP1004HT8P JP E 1290 MMY MAP1004T8P JP E MMY MAP1204HT8P JP E 1560 MMY MAP1204T8P JP E MMY MAP1404HT8P JP E 1692 MMY MAP1404T8P JP E MMY MAP1604HT8P JP E 1942 MMY MAP1604T8P JP E 9 Address setting On this unit it is required to set the addresses of the indoor units before starting air conditioning Set the addresses following the steps below NCAUTION Be sure to complete the electric wiring before setting the addresses f you turn on the outdoor unit before turning on the indoor units the CODE No E19 is indicated on the 7 segment display on the interface P C board of the outdoor unit until the indoor units are turned on This is not a malfunction It may take up to ten minutes normally about five minutes to address one refrigerant line automatically Settings on the outdoor unit are required for automatic add
16. Auto 1 Auto 2 gt Auto 3 After the indication U 1 U 1 flash starts flashing on the display When the flashing stops and U 1 U 1 light remains lit on the display the setting is complete Repeat steps 4 to 6 for other refrigerant lines CON After completing address setting of all systems turn off dip switch 2 of SW30 on the interface P C boards of all the header outdoor units connected to the same central control except the unit that has the lowest address For unifying the termination of the wiring for the central control of indoor and outdoor units 25 9 Connect the relay connectors between the U1 U2 and U3 U4 terminals of the header outdoor unit of each refrigerant line oT db dD n qo D d U1 U2 U3 U4 U5 U6 TO TO TO CENTRAL INDOOR CONTROL OUTDOOR LER 10 Set the central control address For the setting of the central control address refer to the installation manuals of the central control devices Header unit interface P C board SW15 swo4 SWO Cl ON O D600 D601 D602 D603 D604 me 88888 SW13 SW14 SWO01 SW02 SW03 ON ON JE HE 50 EN 51 EN Switch settin Outdoor units setting manually The items in b
17. The refrigerant R410A which is used in the air conditioner is safe without the toxicity or combustibility of ammonia and is not restricted by laws to be imposed which protect the ozone layer However since it contains more than air it poses the risk of suffocation if its concentration should rise excessively Suffocation from leakage of R410A is almost non existent With the recent increase in the number of high concentration buildings however the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space individual control energy conservation by curtailing heat and carrying power etc Most importantly the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners If a single unit of the multi conditioner system is to be installed in a small room select a suitable model and installation procedure so that if the refrigerant accidentally leaks out its concentration does not reach the limit and in the event of an emergency measures can be made before injury can occur In a room where the concentration may exceed the limit create an opening with adjacent rooms or install mechanical ventilation combined with a gas leak detection device The concentration is as given below Total amount of refrigerant kg Min volume of the indoor unit installed room m3 lt Concentration limit kg m The co
18. 0 100 MMY AP3414 82 5 100 MMY AP3614 85 5 100 MMY AP3814 90 5 100 MMY AP4014 93 5 125 MMY AP4214 3N 50Hz 380 400 415V 982 125 MMY AP4414 101 5 125 MMY AP4614 106 2 125 MMY AP4814 109 5 125 High efficiency model Model Phase and frequency Nominal Voltage MA MA MMY AP1624 3N 50Hz 380 400 415V 46 9 63 MMY AP2424 70 4 80 MMY AP2624 72 4 80 MMY AP2824 3N 50Hz 380 400 415V 745 100 MMY AP3024 76 5 100 MMY AP3224 93 8 125 MMY AP3424 95 9 125 MMY AP3624 97 9 125 MMY AP3824 100 0 125 MMY AP4024 3N 50Hz 380 400 415V 102 0 125 MMY AP4224 105 0 125 MMY AP4424 108 0 125 MMY AP4624 111 0 125 MMY AP4824 114 0 125 38 EN 39 EN LiLaL3N LiLaL3N LiL2L3N LiL2L3N QQ OO QQ OO QOOO o o o Circuit breaker Main switch Earth leakage breaker Fuse 20 E Specifications for communication wiring Design of communication wiring Summary of communication wiring Header outdoor Follower outdoor U1 U
19. Group Indoor units automatic setting Line system address 1 1 2 2 Indoor unit address 1 1 Group address 0 1 26 NCAUTION Relay connector connection Never connect relay connectors between the U1 U2 and U3 U4 terminals before completing address setting of all the refrigerant lines Otherwise the addresses cannot be set correctly E Manual address setting using the remote controller Procedure when setting indoor units addresses first under the condition that indoor wiring has been completed and outdoor wiring has not been started manual setting using the remote controller Y Wiring example of 2 refrigerant lines Refrigerant line 1 Refrigerant line 2 A r E r 1 Outdoor l Outdoor 1 unit i unit n 11 i i n 1 1 Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 1 Indoor unit 2 i P Remote Sing oy N e x RSA M cuu anaia N pie epe O controller Line system address 1 1 1 2 2 Indoor unit address 1 2 3 1 2 Group address i 2 2 2 P Header unit Follower unit Follower unit Follower unit Follower unit In the example above disconnect the remote controller connections between the indoor units and connect a wired remote controller to the target unit directly before address setting S
20. Outdoor Outdoor Central remote remote remote controller controller Indoor Indoor Indoor Indoor Remote Remote Remote controller controller controller controller Indoor Indoor Indoor Indoor Remote Remote Remote controller controller controller 46 EN 47 EN Address setting procedure 1 1 Turn on indoor units first and then turn on outdoor units About one minute after turning the power on confirm that the 7 segment display on the interface P C board of the header outdoor unit indicates U 1 L08 U 1 flash It may take up to 10 minutes normally about 5 minutes to complete one line s setting 3 Press SW 15 to start the automatic address setting The 7 segment display indicates Auto 1 Auto 2 gt Auto 3 U 1 U 1 flash starts flashing on the display When the flashing stops and After the indication complete U 1 U 1 light remain lit on the display the setting is Interface P C board on the header outdoor unit swo4 SWO5 O O D600 D601 D602 D603 D604 c c c ce euo gg o LI swo1 SW02 SW03 9 REQUIREMENT When 2 or more refrigerant lines are controlled as a group be sure to tur
21. and louvers of the unit are activated At first the current indoor unit address is displayed in SET DATA No system address is indicated TOY GENE me ra mr TANLA LA A L wt TEMP Cv CA ON OFF 4 8 Finish 6 5 7 Press to finish setting 4 Push the TIME buttons repeatedly to change the value of the indoor unit address in SET DATA Change the value in SET DATA to that of a new address 5 Push the 5 button to confirm the new address on SET DATA UNIT LOUVER Pushthe gt button left side of the button repeatedly to select another address to change Each time you push the button the indoor unit numbers in a refrigerant line are indicated one after another Only the fan and louvers of the selected indoor unit are activated Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique 7 Pushthe 5 button All the segments on the LCD display light up 8 Push the button to finish the procedure 57 EN 29 E Resetting the address Resetting to the factory default address undecided Method 1 Clearing each address separately using a wired remote controller Set the system address indoor unit address and group address to 0099 using a wired remote controller For the setting procedure refer to the address setting procedures using the wired remote controller on the previous pages
22. be charged suddenly therefore be sure to charge refrigerant gradually 33 EN 17 B Full opening of the valve Open the valves of the outdoor unit fully MAP080 MAP100 MAP120 MAP140 MAP160 Liquid side Packed valve Using a 4mm hexagonal wrench fully open the valve rods Ball valve Using a flathead screwdriver turn it counterclockwise by 90 until it hits the stopper Full open Flare nut Valve unit Using flathead screwdriver turn it counterclockwise by 90 until it hits the stopper Full open Position of screwdriver slot Fully closed Fully opened Slot When opened fully do not apply excessive torque after the screwdriver hits the stopper otherwise a problem may be caused on the valve 5 Nem or less Balance pipe Balance packed valve Using a 4mm hexagonal wrench fully open the valve rods Gas side Ball valve Using a wrench turn it counterclockwise by 90 until it hits the stopper Full open 9 s Fully closed IOS Fully opened 34 EN 35 EN B F GAS label This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Chemical Name of Gas R410A Global Warming Potential GWP of Gas 1975 NCAUTION 1 Stick the enclosed refrigerant label adjacent to the charging and or recovering location 2 Clearly write the charged refrigerant quantity on the ref
23. by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work Qualified installer The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations The qualified service person who is allowed to do the electrical work involved in installation repair relocation and removal has the qualifications pertaining to this electrical work as stipu
24. do them for you A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table below Agent Qualifications and knowledge which the agent must have The qualified installer is a person who installs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install maintain relocate and remove the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations The qualified installer who is allowed to do the electrical work involved in installation relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated
25. figure 1 on 6 Installation of the outdoor unit Do not connect them as in figure 2 on 6 Installation of the outdoor unit Allowable length and allowable height difference of refrigerant piping Allowable i Item value Pipes Total extension of Less than gekw Lessthan34HPor soom f A LB La Lb Lc Ld L1 L2 L3 L4 pipe quid pipe L5 L6 L7 a b c d e f g h i j real length 96kW or more 34HP or more 500m Equivalent length 235m Farthest piping length L 1 LA LB Ld L1 L3 L4 L5 L6 j Real length 190m Equivalent length 120m 2 Main piping length L1 Real length 100m 2 Pipe length earth ivalent piping length f first branch Li en est equivalent piping length from the first branch Li 90m 3 L3 LA L5 amp L6 j Farthest equivalent piping length between outdoor units LO 25m LA LB Ld LA Lb LA LB Lc 1 Maximum equivalent piping length of pipes connected to outdoor units 10m La Lb Lc Ld Maximum real length of pipes connected to indoor units 30m a b c d e f g h i j Maximum equivalent length between branching sections 50m L2 L3 L4 L5 L6 L7 Upper outdoor 70m 4 Height between outdoor and indoor units units H1 i Lower outdoor Height i 40m 5 difference units Height between indoor units H2 40m Height between outdoor units H3 5m 1 Farthest outdoor unit from the first branch D farthest indoor unit j 2 If the t
26. front panel Pipes can be drawn out forward or downward from the outdoor unit When drawing out the pipe forward draw it out to the outside via the piping wiring panel and leave a space of 500mm or more from the main pipe connecting the outdoor unit with the indoor unit considering service Rigt Loro Z Drage piping k work or other work on the unit For replacing the rawing out forward compressor 500mm or more space is required i Tr P p q Left piping 1 77 Right piping When drawing out the pipe downward remove the Drawing out jownwar knockouts on the base plate of the outdoor unit draw the pipes out of the outdoor unit and perform piping on the right left or rear side Downward length of the balance pipe should be 5m or less Ball valve of gas N y Side Ball valve of liquid side e COR Ball valve of gas s side Packed valve of liquid side Packed valve of balance pipe Packed valve of balance pipe MAP080 MAP100 MAP120 MAP140 MAP160 10 REQUIREMENT For a welding work of the refrigerant pipes be sure to use nitrogen gas in order to prevent oxidation of the inside of the pipes otherwise clogging of the refrigerating cycle due to oxidized scale m
27. the gas side liquid side and balance pipe side NWARNING Never use oxygen flammable gases or noxious gases in an airtight test Low pressure High pressure gauge gauge Connected to indoor unit Cm Main piping Gas side valve fully closed M T VL Vu Gauge Header outdoor unit v manifold tz So oe LI n Service port Brazed Packed valve details ias T Reducing aml I valve To gauge manifold To outdoor unit Copper pipe Liquid side service port a Man K Gas side valve Pay Liquid side valve N H E t Balance Pi 7 N Service port service port EN es o0 m roe i P outdoor as side aui E nit service port Fuly Liquid valve fully closed Nitrogen i i as Balance valve Piping at site i closed gt Piping at site Hy Piping at site B X N Service port Balanced pipe side valve fully closed L Connected to other follower units Able to detect a serious leakage 1 Apply pressure 0 3MPa 3 0kg cm G for 5 minutes or more 2 Apply pressure 1 5MPa 15kg cm G for 5 minutes or more Available to detect slow leakage 3 Apply pressure 3 73MPa 38kg cm G for approx 24 hours If there is no pressure decrease after 24 hours the test is passed NOTE However if the environmental temperature changes from the moment of app
28. to install the air conditioner Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise vibration water leakage or other failure The designated bolts M12 and nuts M12 for securing the outdoor unit must be used when installing the unit Install the outdoor unit property in a location that is durable enough to support the weight of the outdoor unit Insufficient durability may cause the outdoor unit to fall which may result in injury Install the unit in the prescribed manner for protection against strong wind and earthquake Incorrect installation may result in the unit falling down or other accidents Be sure to fix the screws back which have been removed for installation or other purposes Refrigerant piping Install the refrigerant pipe securely during the installation work before operating the air conditioner If the compressor is operated with the valve open and without refrigerant pipe the compressor sucks air and the refrigeration cycles is over pressurized which may cause a injury Tighten the flare nut with a torque wrench in the specified manner Excessive tighten of the flare nut may cause a crack in the flare nut after a long period which may result in refrigerant leakage Ventilate the air if the refrigerant gas leaks during installation If the leaked refrigerant gas comes into contact with fire toxic gas may be produced After the installation work co
29. u2 Usue U02 A A I I lt L1 1 L5 Table 1 l I i I L2 l Y i s s Indoor unit 192 JU vien f AE i ATE AT8 Table 3 F l l if l l Remote controller Remote controller Table 1 Communication wiring between indoor and outdoor units L1 L2 L3 Central control wiring L4 Wiring 2 core non polarity Type Shield wire Size Length 1 25 mm Up to 1000 m 2 0 mm2 Up to 2000 m 1 1 Total length of Communication wiring length for all refrigerant circuits L1 L2 L3 L4 Table 2 Communication wiring between outdoor units L5 Wiring 2 core non polarity Type Shield wire Size Length 1 25 mm to 2 0 mm Up to 100 m L5 Table 3 Remote controller wiring L6 L7 Wire 2 core non polarity Size 0 5 mm to 2 0 mm Up to 500 m L6 L7 Length Up 400 m in case of wireless remote controller in group control Up to 200 m total length of communication wiring between indoor units L6 221 Group control through a Remote Controller Group control of multiple indoor units 8 units through a single remote controller switch
30. 0804 MMY AP3024 MMY MAP1004 MMY MAP1004 MMY MAP1004 MMY AP3224 MMY MAP0804 MMY MAP0804 MMY MAP0804 MMY MAP0804 MMY AP3424 MMY MAP1004 MMY MAP0804 MMY MAP0804 MMY MAP0804 MMY AP3624 MMY MAP1004 MMY MAP1004 MMY MAP0804 MMY MAP0804 MMY AP3824 MMY MAP1004 MMY MAP1004 MMY MAP1004 MMY MAP0804 MMY AP4024 MMY MAP1004 MMY MAP1004 MMY MAP1004 MMY MAP1004 MMY AP4224 MMY MAP1204 MMY MAP1004 MMY MAP1004 MMY MAP1004 MMY AP4424 MMY MAP1204 MMY MAP1204 MMY MAP1004 MMY MAP1004 MMY AP4624 MMY MAP1204 MMY MAP1204 MMY MAP1204 MMY MAP1004 MMY AP4824 MMY MAP1204 MMY MAP1204 MMY MAP1204 MMY MAP1204 12 EN 5 Carrying in the outdoor unit B Weight centre and weight NCAUTION Weight centre of an outdoor unit Handle the outdoor unit carefully observing the following items When using a forklift or other machinery for loading unloading in transportation insert the prongs of the forklift A B into the rectangular holes for handling as shown below When lifting up the unit insert a rope able to bear the unit s weight into the rectangular holes for handling and Anchor bolt position tie the unit from 4 sides 100 Apply padding in positions where the rope comes into contact with the outdoor unit so that no damage is caused to the outer surface of
31. 2 U3 U4 U5 U6 U1 U2 U3 U4 US U6 Central control IN D N controller 77 el y m m U1 U2 I ii uaus L H Communication wiring between outdoor units Shield wire Y Z i Y 1 i H H T P BACON E POO re _ Communication wiring between indoor and outdoor units bue Shield wire ne Communication wiring between indoor units Shield wire tp e Pod peg 1 tt i bd a bz gt IN m U1 U2 A U2 A B A B u1 u2 A B Vr X 1 T5 y v V V ndoor unit j Indoor unit Indoor unit 1 Indoor unit i A 4 n n M ra N UN A B A B A B Remote controller Remote controller Remote controller Group control Communication wiring and central control wiring use 2 core non polarity wires Use 2 core shield wires to prevent noise trouble In this case both ends of the communication wire must be grounded Use 2 core non polarity wire for remote controller A B terminals Use 2 core non polarity wire for wiring of group control A B terminals 40 EN 41 EN Be sure to keep the rule of below tables about size and length of communication wiring Central control controller iU1 U2 JU3ju4l Super modular multi system Remote controller A T Table 1 i L4 l r Ab T Header 1 Header Follower Follower Follower I Header Follower unit unit uni unit unit 1 unit unit t U3 U4 i alua u3 U4 usua ps4 i jua U4 usua Outdoor unit i i u1uz usue jua usua 0102 usuel u1 u2 us ue 0102 U5 U6 I u1
32. 30 when setting system addresses using the remote controller These 2 address numbers cannot be used on outdoor units and the CODE No E04 Indoor outdoor communication error will appear if they are mistakenly used 2 If you set addresses to indoor units in 2 or more refrigerate lines manually using the remote controller and will control them centrally set the header outdoor unit of each line as below Seta system address for the header outdoor unit of each line with SW13 and 14 of their interface P C boards Turn off dip switch 2 of SW30 on the interface P C boards of all the header outdoor units connected to the same central control except the unit that has the lowest address For unifying the termination of the wiring for the central control of indoor and outdoor units Connect the relay connectors between the U1 U2 and U3 U4 terminals on the header outdoor unit of each refrigerate line After finishing all the settings above set the address of the central control devices For the setting of the central control address refer to the installation manuals of the central control devices 27 B Confirming the indoor unit addresses and the position of an indoor unit using the remote controller Confirming the numbers and positions of indoor units To see the indoor unit address of an indoor unit which you know the position of Y When the unit is individual the indoor unit is paired with a wired remo
33. 5 26 to below 36 73 0 to below o349 49 1 101 0 36 or more 101 0 or more 241 3 9022 2 Size of main piping Total capacity codes of all outdoor units Gas Liquid Equivalent to Equivalent to side side HP capacity 8 to below 12 22 4 to below 33 5 022 2 912 7 Outdoor unit connection piping 12 to below 14 33 5 to below 38 4 028 6 912 7 Pipe size differs based kit of header unit PPS i 3 Main piping 14 tobelow 22 384tobelow615 286 215 9 on the capacity code First branchin See Table 2 section 22 to below 36 61 5 tobelow 34 9 gioi 36 to below 46 101 1tobelow 9413 g222 130 0 46 or more 130 0 or more 41 3 022 2 Maximum equivalent length of main pipe is 70m or less The actual length is 50m or less Pipe size between branching sections 1 Total capacity codes of indoor units at downstream side Gas Liquid I side side Equivalent to HP Equivalent to Pipe size differs based capacity on the total capacity code value of indoor Below 2 4 Below 6 6 912 7 99 5 units at the Branching section 2 4 to below 6 4 6 6 to below 18 0 15 9 9 5 downstream side If 4 Branching pipe the total value z 9 pip 6 4 to below 12 2 18 0 to below 34 0 22 2 912 7 exceeds the capacity Branching section code of the outdoor 12 2 to below 20 2 34 0 to below 56 5 228 6 915 9 unit apply the capacity code of the 20 2 to below 35 2 56 5 to below 98 5 934 9 919 1 outdoor unit See 35 2 or more 98 5 ore more 941 3 922 2 Table 1 and 2
34. AVE SWINGIFIX VENT UNIT LOUVER Pair the indoor unit to set and the remote controller one to one Turn on the power 1 Push and hold the 5 amp LCD starts flashing and TEST buttons at the same time for more than 4 seconds 52 EN lt Line system address gt 2 Push the TEMP Cv C4 buttons repeatedly to set the CODE No to 2 3 Push the TIME buttons repeatedly to set a system address Match the address with the address on the interface P C board of the header outdoor unit in the same refrigerant line 4 Push C button It is OK if the display turns on Indoor unit address 5 Push the TEMP Cv G amp D buttons repeatedly to set the CODE No to 2 6 Push the TIME buttons repeatedly to set an indoor unit address 7 Push the O button It is OK if the display turns on lt Group address gt 8 Push the TEMP Cv GD buttons repeatedly to set the CODE No to 4 9 Push the TIME buttons repeatedly to set a group address If the indoor unit is individual set the address to 77 7 header unit 7 7 7 follower unit G77 Individual 0000 Header unit 0001 In case of group Follower unit 0002 control 10 Push the amp button It is OK if the display turns on 11 Push the button The address setting is complete Gilg flashes You can control the unit after has disappeared NOTE 1 Do not use address numbers 29 or
35. Balance pipes 9 5 8 1 Outdoor unit connecting pipes 8 8 2 2 3 Main piping 8 Outdoor unit connection piping kit For linking of outdoor units 6 4 Branching pipe 7 Branching header First branch Y shape 6 Y shaped branching joint branching joint 5 Indoor unit connecting pipe 4 4 Indoor unit e 6 e 6 6 6 6 a a s d 5 5 5 5 5 Indoor unit 7 7 7 24 EN 25 EN No Piping parts Name Selection of pipe size Remarks Connecting pipe size of outdoor unit Type Gas side Liquid side Outdoor unit MAP080 022 2 912 7 v Same as connecting Outd it 1 Outdoor unit connecting pipe MAP 100 9222 912 7 pipe size of the connection piping MAP120 928 6 912 7 outdoor unit kit MAP140 028 6 015 9 MAP160 028 6 015 9 Pipe size for connecting piping between outdoor units Total capacity codes of outdoor units at the HD downstream side Gas Liquid Balanc side side epipe oe to gas s to Pipe size differs based Between Outdoor Main connecting P y pn nS el capac m 2 unit connection piping between 16 to below 22 49 0 to below 2286 gis9 units at the piping kits outdoor units 61 5 P downstream side See Table 2 22 to below 26 61 5tobelow gs49 194 73 0 9
36. L button to return to step 2 After returning to step 2 select another system address and check the indoor unit addresses of the line 6 Push the button to finish the procedure m Changing the indoor unit address using a remote controller To change an indoor unit address using a wired remote controller Y The method to change the address of an individual indoor unit the indoor unit is paired with a wired remote controller one to one or an indoor unit in a group The method is available when the addresses have already been set automatically SWINGFIX UNIT LOUVER CE 9 3 qp 005 5 Finish 1 Execute it while the units are stopped Push and hold the ar 5 and amp buttons at the same time for more than 4 seconds If 2 or more indoor units are controlled in a group the first indicated UNIT No is that of the head unit 2 Pushthe e button left side of the button repeatedly to select an indoor unit number to change if 2 or more units are controlled in a group The fan and louvers of the selected indoor unit are activated The fan of the selected indoor unit is turned on Push the TEMP Cv CA buttons repeatedly to select 7 for CODE No 4 Push the TIME buttons repeatedly to change the value indicated in the SET DATA section to that you want 5 Push the 5 button 28 6 Push the button left side of the button repeate
37. TOSHIBA Leading Innovation gt gt gt AIR CONDITIONER MULTI TYPE HFC Installation Manual Outdoor Unit For commercial use Model name lt Heat Pump Model gt lt Cooling Only Model gt MMY MAPO0804HT8P E MMY MAPO0804T8P E MMY MAP1004HT8P E MMY MAP1004T8P E MMY MAP1204HT8P E MMY MAP1204T8P E MMY MAP1404HT8P E MMY MAP1404T8P E MMY MAP1604HT8P E MMY MAP1604T8P E MMY MAPO804HT8JP E MMY MAP0804T8JP E MMY MAP1004HT8JP E MMY MAP1004T8JP E MMY MAP1204HT8JP E MMY MAP1204T8JP E MMY MAP1404HT8JP E MMY MAP1404T8JP E MMY MAP1604HT8JP E MMY MAP1604T8JP E LUTTE LT nm II II Jl Ii Ill II TN TNI LEER TT A Hl Wo LEE IL NA I J JUU H i Hl L i Ta I 98l H Um fl IN l W id Uu WI y I v 1 EN Original instruction ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R410A an environmentally friendly refrigerant Contents 1 Precautions for safety Accessory parts Installation of new refrigerant air conditioner Selection of installation place Carrying in the outdoor unit Installation of the outdoor unit Refrigerant piping Electric wiring o ON O ao A WO NM Address setting 10 Testr n io s maquinas ees male 11 Troubleshooting 12 Machine card and logbook
38. and fan OE Compressors 2 3 and fan OF Compressors 1 2 3 and fan 33 1 2 Machine card and logbook E Machine card After test run fill the items on the machine card and paste the card on an accessible place on the product securely before delivery to the customer Describe the following items on the machine card name address and telephone number of the installer his service department the service department of the party concerned or at any addresses and telephone numbers of fire department police hospitals and burn centres E Logbook Update the log periodically after maintenance as defined in EN378 4 Describe the following items on the logbook 1 2 NO BW details of the maintenance and repair works quantities kind of new reused recycled refrigerant which have been charged on each occasion the quantities of refrigerant which have been transferred from the system on each occasion see also EN378 4 if there is an analysis of a reused refrigerant the results shall be kept in the logbook source of the reused refrigerant changes and replacements of components of the system result of all periodic routine tests significant periods of non use 66 EN WARNINGS ON REFRIGERANT LEAKAGE Check of Concentration Limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out its concentration will not exceed a set limit
39. ating Install the outdoor unit in a place with good drainage Forinstallation be careful of the strength and level of the foundation so that abnormal sounds vibration or noise are not generated REQUIREMENT Installation in a snowfall area 1 Install the outdoor unit on a higher foundation than the snowfall or set up a stand to install the unit so that snowfall will not affect the unit Setup a stand higher than the snowfall Apply an angled structure to the stand so that drainage will not be prevented Avoid using a stand with a flat surface 2 Mount a snowfall hood onto the air intake and the air discharge Leave enough space for the snowfall hood so that it will not be an obstacle for the air intake and the air discharge Snowfall hood for air discharge locally procured Snowfall hood for air discharge 4 faces locally procured Stand locally procured 1 To install multiple outdoor units arrange them with 20mm or more spaces in between Fix each outdoor unit with M12 anchor bolts at 4 positions 20mm projection is appropriate for an anchor bolt 20mm or more 20mm or more 8 n E m al I M12 anchor bolt 4 positions unit Anchor bolt positions are as shown below Continuous hole 15 x 20 long hole
40. ause an accident After connecting wires to the terminal block take off the traps and fix the wires with cord clamps Follow the same structure for both the control wiring and refrigerate piping Do not conduct power to indoor units until vacuuming of the refrigerant pipes has finished For the wiring of power to indoor units and that between indoor and outdoor units follow the instructions in the installation manual of each indoor unit B Power supply specifications Do not bridge the power between outdoor units through the equipped terminal blocks L1 L2 L3 N Power supply for outdoor units NO GOOD Power wiring selection Select the power supply cabling of each outdoor unit from the following specifications Cable 5 core in conformance with design HO7 RN F or 60245 IEC 66 To decide nominal cross sectional area of conductor refer to following table of Maximum Overcurrent Protection Amps Standard model MCA Minimum Circuit Amps MOCP Maximum Overcurrent Protection Amps Power Supply MCA MOCP Model A A Phase and frequency Nominal Voltage A A MMY MAP0804 23 5 32 MMY MAP1004 25 5 32 MMY MAP1204 3N 50Hz 380 400 415V 28 5 40 MMY MAP1404 332 40 MMY MAP1604 36 5 50 MMY AP1814 49 0 63 MMY AP2014 51 0 63 MMY AP2214 54 0 63 MMY AP2414 57 0 63 MMY AP2614 3N 50Hz 380 400 415V 62 0 80 MMY AP2814 65 0 80 MMY AP3014 69 7 80 MMY AP3214 73
41. ay occur contaminate the refrigerant Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust does not Be sure to use a double spanner to loosen or tighten the flare nut If a single spanner is used the required level of tightening cannot be obtained Tighten the flare nut with the specified torque If it is hard to loosen or tighten the flare nut of the balance pipe or packed valve of the liquid side with a double spanner loosen or tighten the flare nut while holding the valve mounting plate with a spanner rice hel Tightening torque Nem 6 4mm 14 to 18 1 4 to 1 8 kgf m 9 5 mm 33 to 42 3 3 to 4 2 kgf m 12 7 mm 50 to 62 5 0 to 6 2 kgf m 15 9 mm 63 to 77 6 3 to 7 7 kgf m Pipe connection method of valve at the gas side Example Packed valve of balance pipe X Ball valve of gas side Packed valve of liquid side Type o at Draw out forward Draw out downward Cut the L shaped pipe at the horizontal straight Cut the L shaped pipe at the vertical straight section then braze the supplied attachment section then braze the supplied attachment pipe and the socket and pipe procured locally pipe and the socket and pipe procured locally i bia rfi MAP080 Liquid Bl Gas pipe pipe Liquid 9 Gas pipe MAP100 eee pipe AT Atta
42. chment M pipe Ss Balance pipe Balance nies ent p pipe Socket pipe Socket M SB Pipe r Pipe Section gt X a Pip lt to be cut Section to be cut Cut the L shaped pipe at the horizontal straight Cut the L shaped pipe at the vertical straight section then braze the supplied attachment section then braze the supplied attachment pipe and the socket and pipe procured locally pipe and the socket and pipe procured locally Gas Liquid pipe Liquid J E n MAP120 228 6 pipe Gas pipe pipe Gas pipe Gas Balance Attachment pipe H Balance Attachment Y pipe ot Pipe Py EET Section o iz Pipe LJ tobe cut Section to be eS cut 20 EN Pipe Type diameter Draw out forward Draw out downward Cut the L shaped pipe at the horizontal straight Cut the L shape pipe at the vertical straight section then braze the supplied attachment section then braze the supplied attachment pipe and the socket and pipe procured locally pipe and the socket and pipe procured locally H Gas MAP140 iui pipe Liquid Gas pi H 928 6 Liquid iq as pipe MAP160 pipe Gappa y pipe pipe E ttachment pipe Balance Attachment uA alance pipe pipe Socket M pipe eg m lt Section NS Pipe N Pipe to be cut Section lt to be cut Extruding margin of copper pipe with flare machinin Copper pipe outer When using R410A When using dia tool co
43. d sar ISU x 3 7 segment display A SW05 Sw15 Push switch 7 segment display B SW01 SW02 SWO03 ary switches 62 EN 63 EN 1 7 Troubleshooting In addition to the CODE No on the remote controller of an indoor unit you can diagnose failure type of an outdoor unit by checking the 7 segment display on the interface P C board Use the function for various checks Set every dip switch to OFF after checking 7 Segment display and check code Rotary switch setting value Swo1 Indication SW02 SW03 D600 D601 D602 D603 D604 LED 88 888 Outdoor unit check code Outdoor unit number A U1 to U4 B Check code display f a check code has an auxiliary code the display indicates the check code for three seconds and the auxiliary code for one second alternately Check code indicated on the 7 segment display on the outdoor unit Indicated when SWO1 1 SW02 1 and SWO3 1 Check code Indication on 7 segment display on the outdoor unit Auxiliary code Check code name 03 Compressor 3 E06 Number of indoor units which received normally Decrease of number of indoor units E07 In
44. dly to select another indoor UNIT No to change Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique 7 Push the amc button left side of the button to check the changed addresses UNIT LOUVER 6 If the addresses have been changed correctly push the button to finish the procedure Y To change all the indoor unit addresses using an arbitrary wired remote controller The method is available when the addresses have already been set automatically When communication wirings of 2 or more refrigerant lines are interconnected for central control NOTE You can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote controller Enter the address check change mode and change the addresses 3 2 If no number appears on UNIT No no outdoor unit exists on the line Push button and select another line following step 2 Cancels the line selection Execute it while the units are stopped Push and hold the TIME and buttons at the same time for more than 4 seconds At first the line 1 and CODE No AT Address Change are indicated on the LCD display 2 Push eo left side of the button and SWING FIX Cr 5 buttons repeatedly to select a system address 56 EN 3 Push the amp button The address of one of the indoor units connected to the selected refrigerant line is indicated on the LCD display and the fan
45. door outdoor communication circuit error E08 Duplicated indoor addresses Duplication of indoor addresses E12 9f Communication between indoor and outdoor units Automatic addressing start error 02 Communication between outdoor units E15 No indoor unit during automatic addressing E16 PH coge ENTER units Capacity over number of connected indoor units E19 e irc nong units Number of header outdoor unit error E20 or kei s Min ias Other lines connected during automatic addressing E23 Sending error between outdoor units communication E25 Duplicated follower outdoor address set up E26 Number of outdoor units which received normally Decrease of connected outdoor units E28 Detected outdoor Follower outdoor unit error E31 IPDU quantity information IPDU communication error F04 TD1 sensor error F05 TD2 sensor error F06 01 TE1 sensor TE1 sensor error 02 TE2 sensor TE2 sensor error F07 TL sensor error F08 TO sensor error F12 TS1 sensor error 01 Compressor 1 F13 02 Compressor 2 TH Heat sink sensor error 32 Check code Indication on 7 segment display on the outdoor unit Auxiliary code Check code name Outdoor temp sensor miswiring EIS m Outdoor pressure sensor miswiring TE1 TL F16 Outdoor temp sensor miswiring Outdoor pressure sensor miswiring Pd Ps F22 TD3 sensor error F23 Ps sensor error F24 Pd sensor error F31 Outdoor EEPROM error
46. ess 0 82 28 58 28 58 0 04 28 75 935 13 12 0 20 or less 1 00 34 92 34 90 0 04 35 11 12 14 13 0 25 or less 1 20 38 10 38 10 0 05 38 31 12 15 14 0 27 or less 1 26 41 28 41 28 0 05 41 50 12 15 14 0 28 or less 1 35 E Selection of pipe size Capacity code of indoor and outdoor units Selection of pipe material For the indoor unit the capacity code is decided at each capacity rank Table 1 The capacity codes of the outdoor units are decided at each capacity rank The maximum number of connectable indoor units and the total value of capacity codes of the indoor units are also decided Table 2 NOTE Compared with the capacity code of the outdoor unit the total value of capacity codes of the connectable indoor units differs based on the height difference between the indoor units When the height difference between the indoor units is 15m or less Up to 13596 of the capacity code Equivalent to HP of the outdoor unit Equivalent to HP of the outdoor unit When the height difference between the indoor units is over 15m Up to 105 of the capacity code 22 EN 23 EN Table 1 Capacity code Indoor unit capacityrank Equivalent to HP REI fo 007 0 8 2 2 009 1 2 8 012 1 25 3 6 015 147 4 5 018 2 5 6 024 2 5 Tah 027 3 8 030 3 2 9 036 4 11 2
47. exchange the vacuum pump with a refrigerant canister and advance to the additional charging of refrigerant 31 EN 16 E Adding refrigerant After finishing vacuuming exchange the vacuum pump with a refrigerant canister and start additional charging of refrigerant Calculation of additional refrigerant charge amount Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipes at the local site For refrigerant to be charged in pipes at the local site calculate the amount and charge it additionally NOTE If the additional refrigerant amount indicates minus as the result of calculation use the air conditioner without additional refrigerant Heat pump Outdoor unit type MAPO080 MAP100 MAP120 MAP140 MAP 160 type Charging amount kg 11 5 Cooling only Outdoor unit type MAPO080 MAP100 MAP120 MAP140 MAP160 type Charging amount kg 10 5 10 5 10 5 11 5 11 5 Additional refrigerant charge amount at local site Real length of liquid pipe x Additional refrigerant charge amount per 1m liquid pipe Table 1 Corrective amount of refrigerant depending on HP of co operating outdoor units Table 2 Table 1 Liquid pipe dia mm 64 9 5 127 15 9 19 1 222 ie garant amount m liquid 0 025 0 055 0 105 0 160 0 250 0 350 32 EN
48. f the piping wiring panel with the piping cover or fill silicon or putty into the space between the pipes n case of drawing out the pipes downward or sideward also close the openings of the base plate and the side plate Under the opened condition a problem may be caused due to the entering of water or dust When using the piping cover When not using the piping cover Piping wiring panel Piping wiring panel f fa Drawing out sideward f Close the opening with the Fill silicon or putty into the d pipe cover periphery of the pipes Drawing out Drawing out frontward Drawing out frontward Drawing out downward downward Pipe holding bracket Attach pipe holding brackets following the table below Diameter of pipe mm Interval 15 9 019 1 2m 022 2 041 3 3m 36 EN 37 EN 19 8 Electric wiring NWARNING The appliance shall be installed in accordance with national wiring regulations Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire NCAUTION Perform wiring of power supply complying with the rules and regulations of the local electric company Do not connect 380V 415V power to the terminal blocks for control cables U1 U2 U3 U4 U5 U6 otherwise the unit may break down Be sure that electric wiring does not come into contact with high temperature parts of piping otherwise the coating of cables may melt and c
49. igerant N Exclusive to R410A Charging hose and operation check N Exclusive to RA10A Charging cylinder Charging refrigerant Unusable Use the Refrigerant charging balance Gas leak detector Checking gas leak N Exclusive to RA10A Vacuum pump Vacuum drying eee a counter flow preventive adapter is Vacuum pump with counterflow Vacuum drying R22 Existing article Flare tool Flare processing of pipes Usable by adjusting size Bender Bending processing of pipes R22 Existing article Refrigerant recovery device Recovering refrigerant N Exclusive to R410A Torque wrench Tightening flare nut N Exclusive to 12 7mm and 15 9mm Pipe cutter Cutting pipes R22 Existing article i i Exclusive to R410A Refrigerant canister Charging refrigerant A Enter the refrigerate name for identification inne machine Nitrogen gas Welding of pipes R22 Existing article Refrigerant charging balance Charging refrigerant R22 Existing article 9 EN 4 Selection of installation place Upon customer s approval install the air conditioner in a place which satisfies the following conditions Place where it can be installed horizontally Place which can reserve a sufficient service space for safe maintenance or checks Place where there is no problem even if the drained water overflows Avoid the following places Salty places seaside area or places with much gas sulfide hot spring area If selecting such a place special main
50. ing sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the new refrigerant R410A For connecting pipes use new and clean piping designed for R410A and please care so that water or dust does not enter To disconnect the appliance from main power supply This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm The installation fuse all type can be used must be used for the power supply line of this conditioner Do not wash air conditioners with pressure washers Electric leaks may cause electric shocks or fires 2 Accessory parts Part name Q ty Shape Usage Owner s Manual 1 Be sure to hand it to the customers Installation Manual 1 Be sure to hand it to the customers CD ROM For other languages that do not appear in this Installation Manual Owner s manual 1 _ Installation manual Please refer to the enclosed CD ROM Attached pipe for 22 2 Fi i Connecting pipe for gas side piping MAP080 MAP100 type Attached pipe for 28 6 1 Connecting pipe for gas side piping MAP120 MAP140 MAP160 type F GAS label Fill the items on the label after adding refrigerant 8 EN 3 Installation of new refrigerant air conditioner This air conditioner adopts the new HFC refrige
51. ing the trial run The indication on the LCD display returns to the status of procedure 1 5 Push the e button to exit the trial mode TEST disappears on the LCD display and the status changes to normal stopped mode 30 When executing a test run using the interface P C board on the outdoor unit You can execute a test run by operating switches on the interface P C board of the header outdoor unit Individual trial which tests each indoor unit separately and corrective trial which tests all the indoor units connected are available Individual test operation Y Starting operation 1 Set the running mode to COOL or HEAT on the remote controller of the indoor unit to be tested The unit will run in the current mode unless you set the mode otherwise 7 segment display IA IB U1 1 2 Set the rotary switches on the interface P C board of the header outdoor unit SW01 to 16 SW02 and SWO03 to the address of the indoor unit to be tested SW02 SW03 Indoor unit address 1to 16 1 1to 16 Setnumber of SW02 1to 16 2 17 to 32 Set number of SW02 16 1to 16 3 33 to 48 Set number of SW02 32 1to 16 4 49 to 64 Set number of SW02 48 7 segment display A B J Address display of the corresponding indoor unit 3 Push and hold SW04 for more than 10 seconds 7 segment display A B Addre
52. installation servicing and removal Do not touch the aluminium fin of the outdoor unit You may injure yourself if you do so If the fin must be touched for some reason first put on protective gloves and safety work clothing and then proceed Do not climb onto or place objects on top of the outdoor unit You may fall or the objects may fall off of the outdoor unit and result in injury When working at height put a sign in place so that no one will approach the work location before proceeding with the work Parts or other objects may fall from above possibly injuring a person below Also be sure that workers put on helmets When cleaning the filter or other parts of the outdoor unit set the circuit breaker to OFF without fail and place a Work in progress sign near the circuit breaker before proceeding with the work When working at heights put a sign in place so that no one will approach the work location before proceeding with the work Parts and other objects may fall from above possibly injuring a person below The refrigerant used by this air conditioner is the R410A You shall ensure that the air conditioner is transported in stable condition If you find any part of the product broken contact your dealer Do not disassemble modify repair or move the product yourself Doing so may cause fire electric shock injury or water leaks Ask a qualified installer or qualified service person to do any repairs or to move the p
53. ish the procedure All the indoor units in the group stop Y To check all the indoor unit addresses using an arbitrary wired remote controller When communication wirings of 2 or more 54 EN refrigerant lines are interconnected for central control A ON OFF C Execute it while the units are stopped You can check indoor unit addresses and positions of the indoor units in a single refrigerant line When an outdoor unit is selected the indoor unit numbers of the refrigerant line of the selected unit are indicated one after another and the fan and louvers of the indicated indoor units are activated 1 Push and hold the TIME and 5 buttons at the same time for more than 4 seconds At first the line 1 and CODE No gr Address Change are indicated on the LCD display Select an outdoor unit 2 Pushthe ce left side of the button and wwcr buttons repeatedly to select a system address 3 Push the e button to confirm the system address selection The address of an indoor unit connected to the selected refrigerant line is indicated on the LCD display and its fan and louvers are activated 4 Push the e button left side of the button Each time you push the button the indoor unit numbers of the selected refrigerant line are indicated one after another Only the fan and louvers of the indicated indoor unit are activated To select another system address 5 Push the C
54. lated by the local laws and regulations and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or Qualified service individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work person The qualified service person who is allowed to do the refrigerant handling and piping work involved in installation repair relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified service person who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work 2 EN 3 EN Definition of Protective Gear Whe
55. llows SW01 SW02 SW03 SW04 Clearable addresses Confirm that the 7 segment display indicates 2 1 2 A d buS and turn SW04 ON for more than five System indoor unit group address seconds Confirm that the 7 segment display indicates 2 2 2 A d nEt and turn SW04 ON for more than five Central control address seconds 3 Confirm that the 7 segment display indicates A d c L and set SW01 SW02 and SW03 to 1 1 1 respectively 4 After a time U 1 L08 appears on the 7 segment display if the address clearing has been completed successfully If the 7 segment display indicates A d n G the outdoor unit may still connected with other refrigerant lines Check the connection of the relay connectors between U1 U2 and U3 U4 NOTE Take care to carry out the procedure above correctly otherwise addresses in other refrigerate lines may also be cleared 5 Set the addresses again after finishing the clearance 58 EN 59 EN 101est run B Before test run Confirm that the valve of the refrigerate pipe of the outdoor unit is OPEN Before turning on the power confirm that the resistance between the terminal block of power supply and the earth is more than 1MQ using a 500V megohmmeter Do not run the unit if it is less than 1MQ NCAUTION Turn on the power and turn on the case heater of the compressor To save the compressor when it is activated leave the power on for mo
56. lying pressure to 24 hours after that the pressure will change by about 0 01MPa 0 1kg cm G per 1 C Consider the pressure change when checking the test result REQUIREMENT When pressure decrease is detected in steps 1 3 check the leakage at the connecting points Check the leakage using a foaming agent or other measures and seal the leak with re brazing flare retightening or other methods After sealing execute an airtight test again 30 EN il Vacuum drying Be sure to perform vacuuming from both liquid and gas sides Be sure to use a vacuum pump equipped with the counter flow prevention function so that oil in the pump will not flow back into piping for air conditioners If oil in the vacuum pump enters in the air conditioner with R410A refrigerant a problem may be caused in the refrigerating cycle After finishing the airtight test and discharging nitrogen gas connect the gauge manifold to the service ports of the liquid side gas side and balance pipe side and connect a vacuum pump as shown in the figure below Be sure to perform vacuuming for the liquid gas and balance pipe sides Low pressure High pressure Connected to indoor unit gauge gauge 1n Packed valve fully closed Main pipe gas side x Gauge Header outdoor unit manifold Service port ln 1 Packed valve details Brazed p p g o 1 T
57. m equivalent to HP capacity codes is connectable to one line after branching of header When the total capacity codes of all outdoor units are 12 to below 26 equivalent to HP and you use a branching header for the first branching section use a RBM HY2043E or RBM HY2083E regardless of the total capacity codes of outdoor units at downstream side In addition you cannot use a branching header for the first branching section when the total capacity codes of all outdoor units are over 26 equivalent to HP Outdoor unit connection piping kit For linking of outdoor units Total capacity code of outdoor units i Model name Equivalent to HP Edu to Outdoor unit p y I i connection piping i T 8 Branching section kit For linking of QuidooE Unit 7 Below 26 0 Below 73 0 RBM BT14E outdoor units kit For li kin p i it For linking o 26 0 or more Above 73 0 RBM BT24E outdoor units 3 Downstream side when regarding the main piping as the start point 26 EN B Allowable length of refrigerant pipes and allowable height difference between units Height difference between outdoor units H3 lt 5m Height difference between outdoor and indoor units H1 lt 70m EH Follower unit Outdoor unit fl i A B C Header Follower Follower 8 unit unit unit l D SE EH EB E o Ld
58. mpressor 2 03 Compressor 3 Inverter DC voltage error on compressor 64 EN 65 EN Check code Indication on 7 segment display on the outdoor unit Auxiliary code Check code name 01 Compressor 1 03 Compressor 3 P07 02 Compressor 2 Heat sink overheat error 03 Compressor 3 P10 Detected indoor unit address Indoor overflow error P13 Outdoor unit flow back error detected 01 TS condition P15 02 TD condition Gas leak detection P17 Discharge temperature TD2 error P18 Discharge temperature TD3 error P19 Detected outdoor unit number 4 way valve inverse error P20 High pressure protective operation 0 IGBT circuit 1 Position detection circuit error 3 Motor lock error Outdoor fan IPDU error P22 4 Motor current detected C TH sensor error NOTE D TH sensor error Ignore 0 F appearing in the position of E Inverter DC voltage error outdoor unit s fan 01 Compressor 1 P26 02 Compressor 2 G TR short protection error 03 Compressor 3 01 Compressor 1 P29 02 Compressor 2 Compressor position detecting circuit error 1PDU number information 01 Compressor 1 02 Compressor 2 03 Compressors 1 and 2 04 Compressor 3 05 Compressors 1 and 3 06 Compressors 2 and 3 07 Compressors 1 2 and 3 08 Fan 09 Compressor 1 and fan OA Compressor 2 and fan OB Compressors 1 2 and fan O0C Compressor 3 and fan OD Compressors 1 3
59. n on all the indoor units in the group before setting addresses f you set the unit addresses of each line separately each line s header indoor unit is set separately In that case the CODE No L03 Indoor header unit overlap is indicated as running starts Change the group address to make one unit the header unit using wired remote controller Example Controlling 2 or more refrigerant lines as a group System wiring diagram Outdoor Outdoor Indoor Indoor Indoor Indoor N N N Remote controller Group control 24 Address setting procedure 2 1 Set a system address for each system using SW 13 and 14 on the interface P C board on the header outdoor unit of each system Factory default Address 1 NOTE Be sure to set a unique address on each system Do not use a same address as another system refrigerant line or a custom side Interface P C board on the header outdoor unit SW06 SW07 SW09 SW10 ON ON ON ON m m m 1234 1 o z o z NIE oll E Switch settings for a line system address on the interface P C board on the outdoor unit O switch ON X switch OFF Line system address SW13 SW14
60. n the air conditioner is to be transported installed maintained repaired or removed wear protective gloves and safety work clothing In addition to such normal protective gear wear the protective gear described below when undertaking the special work detailed in the table below Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury burns electric shocks and other injuries Work undertaken Protective gear worn All types of work Protective gloves Safety working clothing Electrical related work Gloves to provide protection for electricians and from heat Insulating shoes Clothing to provide protection from electric shock Work done at heights 50 cm or more Helmets for use in industry Transportation of heavy objects Shoes with additional protective toe cap Repair of outdoor unit Gloves to provide protection for electricians and from heat E Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote ELECTRICAL SHOCK HAZARD electric power supplies before servicing Disconnect all remote electric power supplies before servicing Moving parts Do not operate unit with grille removed Stop the unit before the servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing
61. ncentration limit of R410A which is used in multi air conditioners is 0 3kg m NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device Outdoor unit e g charged mt e g amount 10kg iQ Of charged amount 15kg Room D Room E Room F Indoor unit For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10kg The possible amount of leaked refrigerant gas in rooms D E and F is 15kg Important NOTE 2 The standards for minimum room volume are as follows 1 No partition shaded portion 7 Yj ZZ 2 When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas opening without a door or an opening 0 15 or larger than the zz respective floor spaces at the top or bottom of the door Outdoor unit Refrigerant piping Wf 7 ZZ Z Indoor unit 7 Z YY fy 7 A Z Z y YY Uy lt r If an indoor unit is installed in each partitioned room and the refrigerant piping is interconnected the smallest room of course becomes the object But when a mechanical ventilation is installed interlocked with a gas leakage detec
62. nfirm that refrigerant gas does not leak If refrigerant gas leaks into the room and flows near a fire source such as a cooking range noxious gas may be generated When the air conditioner has been installed or relocated follow the instructions in the Installation Manual and purge the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle Failure to purge the air completely may cause the air conditioner to malfunction Nitrogen gas must be used for the airtight test The charge hose must be connected in such a way that it is not slack Ifrefrigerant gas has leaked during the installation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may be generated Electrical wiring Only a qualified installer 1 or qualified service person 1 is allowed to carry out the electrical work of the air conditioner Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and or electrical leaks When connecting the electrical wires repairing the electrical parts or undertaking other electrical jobs wear gloves to provide protection for electricians and from heat insulating shoes and clothing to provide protection from electric shocks Failure to wear this protective gear may result in electric shocks When executing address setting test run or trouble
63. nventional tool 9 5 12 7 0 to 0 5 1 0 to 1 5 15 9 Extruding margin of copper e with flare tools A Unit mm Copper pipe outer dia A34 A 9 5 13 2 12 7 16 6 HT 15 9 19 7 When using the conventional flare tool to connect R410A pipes with flaring make a margin approx 0 5mm longer than that of an R22 pipe so that the flare size matches the one specified It is convenient to use a copper pipe gauge for size adjustment of the extruding margin CAUTION Wrap the ball valve in a wet cloth to keep it cool and prevent the heat from the torch from damaging it when connecting the pipe to the ball valve on the gas line 41 Coupling size of brazed pipe Connected section External size Internal size K I Ta pe F Unit mm Standard outer dia Connected section External size Internal size Min depth of Min thickness of connected Standard outer dia i i i copper pipe Allowable difference nserhon Oval value ef coupling C F K G 6 35 6 35 0 03 6 45 294 7 6 0 06 or less 0 50 9 52 9 52 0 03 9 62 294 8 7 0 08 or less 0 60 12 70 12 70 0 03 12 81 294 9 8 0 10 or less 0 70 15 88 15 88 0 03 16 00 22 9 8 0 13 or less 0 80 19 05 19 05 40 03 19 19 02 11 10 0 15 or less 0 80 22 22 22 22 0 03 22 36 023 11 10 0 16 or l
64. o gauge manifold To outdoor unit rL t 1 To i Full Liquid side service port outdoor Gas side valve closed m i Liquid side vave X unit tf N H gt R n Balance To Service port Q service on ju I Gas side Packed valve fully closed Vacuum pump service port liquid side Piping at site Fully 7 Balanca Piping at site closed E t valve H N Piping at site l Service port 1 Packed valve fully closed balance Follower units Use a vacuum pump with a high vacuuming degree 100 7kPa 5Torr 755mmHg and large exhaust gas amount 40L minute or larger Perform vacuuming for 2 or 3 hours though the time differs depending on the pipe length Check that all the packed valves at the liquid side gas side and balance pipe side are fully closed If the pressure does not reach 100 7kPa or less continue vacuuming for 1 hour or more If the pressure does not reach 100 7kPa after 3 hours of vacuuming stop vacuuming and check for air leakage If the pressure reaches 100 7kPa or less after vacuuming for 2 hours or more close the valves VL and VH on the gauge manifold fully and stop the vacuum pump Leave it as it is for 1 hour to confirm that the vacuuming degree does not change If the degree of vacuum loss is large moisture may remain in the pipes In that case inject dry nitrogen gas and apply pressure to 0 05MPa and perform vacuuming again After finishing the above procedure of vacuuming
65. old font must be set manually setting example when controlling 2 or more refrigerant lines centrall Outdoor units interface Header unit Follower unit Header unit Follower unit Header unit Factory default SW13 14 1 No setting 2 No setting 1 Line system address required required Dip switch 2 of SW30 Terminator of indoor i Set to OFF i Set to OFF outdoor communication ON Ao Mid after setting o ied after setting ON line and central control q addresses q addresses line Connect after Connect after Connect after Relay connector setting Open setting Open setting Open addresses addresses addresses 4 H Central control Header unit Follower unit Header unit Follower unit Header unit controller U3JU4 usua U3JU4 usua U3JU4 Sr lt gt D 1 Z 1 U1 U2lIU5 U611 L 1U1IU21IU5JU6 U1 U2 U5 U6 IU11lU21lU5JU6 U1 U2 lU51U6 D 1 Relay Relay Relay connector connector connector i U1 U2 U2 U1 U2 U1 U2 U1 U2 H AJB ATB ATB AJB ATB Remote Remote Remote 1 controller controller controller Individual
66. otal capacity of outdoor units is 46HP or more make the equivalent length 70m real length 50m or less 3 Make the difference 65m or less if the height difference between outdoor and indoor units H1 is more than 3m 4 Make the difference 50m or less if the height difference between indoor units H2 is more than 3m 5 Make the difference 30m or less if the height difference between indoor units H2 is more than 3m 28 EN 29 EN B Airtightness test After the refrigerant piping has been finished execute an airtight test For an airtight test connect a nitrogen gas canister as shown in the figure on the next page and apply pressure Be sure to apply pressure from the service ports of the packed valves or ball valves at the liquid side gas side and balance pipe side An airtight test can only be performed at the service ports at the liquid side gas side and balance pipe side on header unit Close the valves fully at the gas side liquid side and balance pipe side As there is a possibility that the nitrogen gas will enter into the cycle of outdoor units re tighten the valve rods at the liquid side and balance pipe side before applying pressure When using MAP140 or MAP160 you do not have to re tighten the liquid side valve rod as their valves at the liquid side are ball valves For each refrigerant line apply pressure gradually in steps at the liquid side gas side and balance pipe side Be sure to apply pressure at
67. ound the outdoor unit make sure that its height does not exceed 800mm Y Combination of outdoor units Cooperating outdoor unit Model name Standard type Unit 1 Unit 2 Unit 3 MMY MAP0804 MMY MAP0804 MMY MAP1004 MMY MAP1004 MMY MAP1204 MMY MAP1204 MMY MAP1404 MMY MAP1404 MMY MAP1604 MMY MAP1604 MMY AP1814 MMY MAP1004 MMY MAP0804 MMY AP2014 MMY MAP1004 MMY MAP1004 MMY AP2214 MMY MAP1204 MMY MAP1004 MMY AP2414 MMY MAP1204 MMY MAP1204 MMY AP2614 MMY MAP1604 MMY MAP1004 MMY AP2814 MMY MAP1604 MMY MAP1204 MMY AP3014 MMY MAP1604 MMY MAP1404 MMY AP3214 MMY MAP1604 MMY MAP1604 MMY AP3414 MMY MAP1204 MMY MAP1204 MMY MAP1004 MMY AP3614 MMY MAP1204 MMY MAP1204 MMY MAP1204 MMY AP3814 MMY MAP1604 MMY MAP1204 MMY MAP1004 MMY AP4014 MMY MAP1604 MMY MAP1204 MMY MAP1204 MMY AP4214 MMY MAP1604 MMY MAP1404 MMY MAP1204 MMY AP4414 MMY MAP1604 MMY MAP1604 MMY MAP1204 MMY AP4614 MMY MAP1604 MMY MAP1604 MMY MAP1404 MMY AP4814 MMY MAP1604 MMY MAP1604 MMY MAP1604 Model name Cooperating outdoor unit High Efficiency Model Unit 1 Unit 2 Unit 3 Unit4 MMY AP1624 MMY MAP0804 MMY MAP0804 MMY AP2424 MMY MAP0804 MMY MAP0804 MMY MAP0804 MMY AP2624 MMY MAP1004 MMY MAP0804 MMY MAP0804 MMY AP2824 MMY MAP1004 MMY MAP1004 MMY MAP
68. rant R410A which does not deplete the ozone layer R410A refrigerant is vulnerable to impurities such as water oxidizing membranes or oils because the pressure of R410A refrigerant is higher than that of the former refrigerant by approximately 1 6 times As well as the adoption of the new refrigerant the refrigerating oil has been also changed Therefore pay attention so that water dust former refrigerant or refrigerating oil does not enter the refrigerating cycle of the new refrigerant air conditioner during installation To prevent mixing of refrigerant or refrigerating oil the size of the charge port of the main unit or connecting section of the installation tool differs to that of an air conditioner for the former refrigerant Accordingly exclusive tools are required for the new refrigerant R410A as shown below For connecting pipes use new and clean piping materials so that water or dust does not enter B Required tools and cautions on handling It is necessary to prepare the tools and parts for installation as described below The tools and parts which will be newly prepared in the following items should be restricted to exclusive use Explanation of symbols AN Newly prepared It is necessary to use it exclusively with R410A separately from those for R22 or R407C Former tool is available Used tools Usage Proper use of tools parts Gauge manifold Vacuuming charging refr
69. re than 12 hours B Methods of test run When executing a test run using a remote controller Operate the system normally to check the running condition using the wired remote controller Follow the instructions in the supplied owner s manual when operating the unit If you use a wireless remote controller for operations follow the instructions in the installation manual supplied with the indoor unit To execute a test run forcibly under the condition that the thermostat automatically turns the unit off due to the indoor temperature follow the procedure below The forcible test run will automatically stop after 60 minutes to prevent continuous forcible running and return to normal running NCAUTION Do not use forcible running except for a test run as it overloads the unit DON OFF FAN MODE SAVE VENT FILTER RESET TEST 1 5 1 Push and hold the button for more than 4 seconds TEST appears on the LCD display and the unit enters the trial mode TEST is indicated on the LCD display during the test run UNIT LOUVER SWINGIFIX 2 Push the 3 Push the C s button to switch the running mode to COOL or HEAT NOTE Do not run the unit in any mode other than COOL or HEAT You cannot change the temperature setting during the test run Errors are detected as usual DON OFF C 5 button 4 Push the QE button to stop running after finish
70. ressing Address setting is not started simply by turning on the power Running the unit is not required for address setting The addresses can be set manually setting addresses using SW15 on the interface P C board on the header outdoor unit setting addresses on the wired remote controller When setting an address manually the wired remote controller must temporarily be paired with an indoor unit one to one when the system is organized for group operation and no Remote controller Automatic addressing Manual addressing REQUIREMENT High voltage parts exist in the electrical control box If you set addresses on an outdoor unit operate the unit through the access door shown on the illustration on the right to avoid electric shock Do not remove the cover of electrical control box After finishing operations close the access door cover and fix it with the screw Access p cover Cover of the electrical control box Fixing screw for the access door cover E Automatic address setting No central control go to Address setting procedure 1 Central control of 2 or more refrigerant lines go to Address setting procedure 2 Example When controlling a single refrigerant line centrally When controlling 2 or more refrigerant lines centrally Address setting procedure To procedure 1 To procedure 2 System wiring diagram Outdoor Central Outdoor Centra
71. rigerant label using indelible ink Then place the included transparent protective sheet over the label to prevent the writing from rubbing off 3 Prevent emission of the contained fluorinated greenhouse gas Ensure that the fluorinated greenhouse gas is never vented to the atmosphere during installation service or disposal When any leakage of the contained fluorinated greenhouse gas is detected the leak shall be stopped and repaired as soon as possible 4 Only qualified service personnel are allowed to access and service this product 5 Any handling of the fluorinated greenhouse gas in this product such as when moving the product or recharging the gas shall comply under EC Regulation No 842 2006 on certain fluorinated greenhouse gases and any relevant local legislation 6 Periodical inspections for refrigerant leaks may be required depending on European or local legislation 7 Contact dealers installers etc for any questions Pre charged Refrigerant at Factory kg specified in the nameplate _ mne Charge on Installation Site g m Heat insulation for pipe Apply heat insulation of pipe separately at the liquid gas and balance sides Be sure to use thermal insulator resistant up to 120 C or higher for pipes at the gas side 18 B Finishing after connecting pipes After piping connection work has been finished cover the opening o
72. roduct Selection of installation location f you install the unit in a small room take appropriate measures to prevent the refrigerant from exceeding the limit concentration even if it leaks Consult the dealer from whom you purchased the air conditioner when you implement the measures Accumulation of highly concentrated refrigerant may cause an oxygen deficiency accident Do notinstall in a location where flammable gas may leaks are possible If the gas should leak and accumulate around the unit it may ignite and cause a fire When transporting the air conditioner wear shoes with protective toe caps protective gloves and other protective clothing When transporting the air conditioner do not take hold of the bands around the packing carton You may injure yourself if the bands should break Install the indoor unit at least 2 5 m above the floor level since otherwise the users may injure themselves or receive electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running Donot place any combustion appliance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Places where the operation sound of the outdoor unit may cause a disturbance Especially at the boundary line with a neighbour install the air conditioner while considering the noise Installation Follow the instructions in the Installation Manual
73. roducts make sure to use Toshiba specified products only Using unspecified products may cause fire electric shock water leak or other failure Do not use any refrigerant different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Before opening the service panel of the outdoor unit set the circuit breaker to the OFF position Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts Only a qualified installer 1 or qualified service person 1 is allowed to remove the service panel of the outdoor unit and do the work required Before carrying out the installation maintenance repair or removal work be sure to set the circuit breakers for both the indoor and outdoor units to the OFF position Otherwise electric shock may result Place a Work in progress sign near the circuit breaker while the installation maintenance repair or removal work is being carried out There is a danger of electric shocks if the circuit breaker is set to ON by mistake Only a qualified installer 1 or qualified service person 1 is allowed to undertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work Wear protective gloves and safety work clothing during
74. rrow view At a level position 17 EN When drawing pipes downward Y Figure 5 GOOD Header unit A Followerunit Follower unit C To gas side branch To gas side branch unit Vertical connection of branch units Y Figure 6 NO GOOD To gas side To gas side gt branch unit branch unit Adding only one follower unit is possible Install the additional unit so that its position is opposite to the header unit Use an extension valve for installation See the figure above Specify the pipe diameter in advance to allow for adding another unit 19 EN The refrigerant pipe connecting section is set in the 7 Refrigerant piping NWARNING If the refrigerant gas leaks during installation ventilate the room If the leaked refrigerant gas comes into contact with fire noxious gas may be generated After installation check that the refrigerant gas does not leak If the refrigerant gas leaks into the room and comes into contact with fire such as a fan heater stove or kitchen range noxious gas may be generated E Connection of refrigerant pipe outdoor unit Remove the front panel and the piping wiring panel M5 9 pcs Asshownin the illustration on the right the hooks are atthe right and left sides of the front panel Lift up and remove the
75. shooting through the checking window on the electrical control box put on insulated heat proof gloves insulated shoes and other clothing to provide protection from electric shock Otherwise you may receive an electric shock Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws Use of wiring which does not meet the specifications may give rise to electric shocks electrical leakage smoking and or a fire Check that the product is properly earthed grounding work Incomplete earthing may cause electric shock Do not connect the earth line to a gas pipe water pipe lightning conductor or a telephone earth line After completing the repair or relocation work check that the ground wires are connected properly Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations and laws Install the circuit breaker where it can be easily accessed by the agent Wheninstalling the circuit breaker outdoors install one which is designed to be used outdoors Under no circumstances must the power cable be extended Connection trouble in the places where the cable is extended may give rise to smoking and or a fire Electrical wiring work shall be conducted according to law and regulation in the community and installation manual Failure to do so may result in electrocution or short circuit Donot suppl
76. ss display of the FF is displayed for 5 corresponding indoor unit seconds NOTE The running mode follows the mode setting on the remote controller of the target indoor unit You cannot change the temperature setting during the test run Errors are detected as usual The unit does not perform test run for 3 minutes after turning the power on or stopping running Y Finishing operation 1 Set the rotary switches on the interface P C board of the header unit back SW01 to 1 SW02 to 1 and SWO3 to 1 7 segment display A B U1 1 60 EN 61 EN lt Corrective trial gt V Start operation 1 Set the rotary switches on the interface P C board of the header outdoor unit as below When in COOL mode SW01 2 SW02 5 SW03 1 When in HEAT mode SW01 2 SW02 6 SW03 1 7 segment display A B Ic IH 2 Push and hold SW04 for more than 2 seconds NOTE You cannot change the temperature setting during the test run Errors are detected as usual The unit does not perform test run for 3 minutes after turning the power on or stopping running 7 segment display A o roZ H Y Stop operation 1 Set the rotary switches on the interface P C board of the header unit back SW01 to 1 SW02 to 1 and SWO3 to 1 7 segment display A B U1 1 Interface PC boar
77. te controller one to one or it is a group controlled one 1 Starts running C SWINGIFIX UNIT LOUVER 2 Execute it while the units are running 1 Push the w button if the units stop 2 Push the w button left side of the button A unit numbers is indicated on the LCD it will disappear after a few seconds The indicated number shows the system address and indoor unit address of the unit When 2 or more indoor units are connected to the remote controller group controlled units a number of other connected units appears each time you push the Imm button left side of the button To find an indoor unit s position from its address Y When checking unit numbers controlled as a group Execute it while the units are stopped The indoor unit numbers in a group are indicated one after another The fan and louvers of the indicated units are activated Push and hold the Ca and buttons at the same time for more than 4 seconds ALL appears on UNIT No on the LCD display The fans and louvers of all the indoor units in the group are activated 2 Pushthe 9 button left side of the button Each time you push the button the indoor unit numbers are indicated one after another The first indicated unit number is the address of the header unit Only the fan and louvers of the indicated indoor unit are activated 3 Push the e button to fin
78. tenance is required Places where oil including machine oil steam oil smoke or corrosive gas is generated Places where iron or other metal dust is present If iron or other metal dust adheres to or collects on the interior of the air conditioner it may spontaneously combust and start a fire Places where an organic solvent is used Chemical plants with a cooling system using liquid carbon dioxide Places where a device generating high frequency inverter non utility generator medical apparatus or communication equipment is set Malfunction or abnormal control of the air conditioner or interference to devices listed above may occur Places where discharged air from the outdoor unit blows against the windows of a neighbour s house Places unable to bear the weight of the unit Places with poor ventilation 10 EN 11 EN E installation space Leave space necessary for running installation and servicing A Air discharge 2 Air intake Air intake Air intake Air intake E ERAI ZI a A Installation servicing 1 surface Square hole for handling Outdoor unit top view Rear side 500mm or more Z 10mm or more 500mm or more Front side 10mm or more NOTE e Ifthere is an obstacle above the outdoor unit leave a space of 2000mm or more to the top end of the outdoor unit e If there is a wall ar
79. the outdoor unit There are reinforcing plates on the side surfaces so the rope cannot be passed through Anchor bolt position 920 GOOD NO GOOD NO GOOD SY 129 H E 5 ZJ 5 ZZ gt Plaster amp gt EPA E Rope Rectangular Plaster holes for Side handling NO GOOD Front Back Rectangular Reinforcing 3 a holes for plate p J 4 lifting Prongs of the orklift j L X E gt N a r oi Weight kg No Model type X mm Y mm Z mm Heat pump model Cooling only model MAP080 A MAP100 500 390 645 242 241 MAP120 MAP140 B 605 350 700 329 329 MAP160 13 EN 14 EN 15 EN 6 Installation of the outdoor unit NWARNING Be sure to install the outdoor unit in a place able to bear its weight If strength is insufficient the unit may fall down resulting in human injury Perform specified installation work to protect against strong wind and earthquakes If the outdoor unit is imperfectly installed an accident by falling or dropping may be caused NCAUTION Drain water is discharged from the outdoor unit Especially while he
80. to use an insulation tester set 500V Megger to check the resistance is 1 MO or more between the charge section and the non charge metal section Earth section If the resistance value is low a disaster such as a leak or electric shock is caused at user s side Upon completion of the installation work check for refrigerant leaks and check the insulation resistance and water drainage Then conduct a test run to check that the air conditioner is operating properly Explanations given to user Upon completion of the installation work tell the user where the circuit breaker is located If the user does not know where the circuit breaker is he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner f you have discovered that the fan grille is damaged do not approach the outdoor unit but set the circuit breaker to the OFF position and contact a qualified service person 1 to have the repairs done Do not set the circuit breaker to the ON position until the repairs are completed After the installation work follow the Owner s Manual to explain to the customer how to use and maintain the unit 6 EN 7 EN Relocation Only a qualified installer 1 or qualified service person 1 is allowed to relocate the air conditioner It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire electric shocks injury water leakage noise and or vibration may result
81. tor in the smallest room where the density limit is exceeded the volume of the next smallest room becomes the object Refrigerant piping Outdoor unit Loo X Small Medium Large room Indoor unit room room Mechanical ventilation device Gas leak detector NOTE 3 The minimum indoor floor area compared with the amount of refrigerant is roughly as follows When the ceiling is 2 7m high 40 Range below the density limit of 0 3 kg m countermeasul _not needed m 35 w N a N Range above the density limit of 0 3 kg m countermeasures needed a o Min indoor floor area a o 10 20 30 gt Total amount of refrigerant kg TOSHIBA CARRIER THAILAND CO LTD 144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Amphur Muang Pathumthani 12000 Thailand 1114207199
82. y power from the power terminal block equipped on the outdoor unit to another outdoor unit Capacity overflow may occur on the terminal block and may result in fire When carrying out electric connection use the wire specified in the Installation Manual and connect and fix the wires securely to prevent them applying external force to the terminals Improper connection or fixing may result in fire Test run Before operating the air conditioner after having completed the work check that the electrical parts box cover of the indoor unit and service panel of the outdoor unit are closed and set the circuit breaker to the ON position You may receive an electric shock if the power is turned on without first conducting these checks When you have noticed that some kind of trouble such as when an error display has appeared there is a smell of burning abnormal sounds are heard the air conditioner fails to cool or heat or water is leaking has occurred in the air conditioner do not touch the air conditioner yourself but set the circuit breaker to the OFF position and contact a qualified service person Take steps to ensure that the power will not be turned on by marking out of service near the circuit breaker for instance until qualified service person arrives Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other failure After the work has finished be sure

Download Pdf Manuals

image

Related Search

Related Contents

Delta 37984-OB Installation Guide  Manual do Utilizador Manual de Instalação Telefone Kit  here.  Dear Sonim-customer, Sonim-Retailer and Distributor, Sonim  Boss Audio Systems Flip Down DVD  Shall we open, AP Window by YKK AP  User`s Guide  DEWALT DCK492L2 Use and Care Manual  デマンドコントローラー 取扱説明書  

Copyright © All rights reserved.
Failed to retrieve file