        VSP Manual - Heat-Timer Corporation
         Contents
1.  heat is required  Check the System Start setting  see pg  11   If the outdoor tempera   ture sensor reading is above the setting  the VSP will not give heat  Also check if the VSP is in the Thermostat mode   see pg  8   In the thermostat mode  the VSP will never give heat if terminals EXT and COM are not shorted together     OUTPUT light is FLASHING when heat is required  The Output light flashes when the Secondary loop pump is  running  but the Injection pump is off  This will occur when the VSP is satisfied with the temperature of the Secondary  loop  See Insufficient Heat conditions below     OUTPUT light is FLASHING or ON but Secondary loop pump is not running  Turn off the power to the  Secondary loop pump  The VSP power must remain connected  Then disconnect all wires attached to the VSP Black  wires  Test for continuity across the Black wires  If the wires are continuous  the VSP is working properly  Check the  Secondary loop pump and its power     OUTPUT light is ON but Injection pump is not running  If the Output light is on  the Injection pump should be  running  However  if it is running at a very low speed  it may be hard to detect  It is possible to test the Injection  pump output with a voltmeter which can read at least 120 VAC     Warning  This test can only be performed with the Injection Pump power connected  The 120VAC power  can cause severe personal injury  This test should only be performed by a qualified electrician or electrical  contractor     Place t
2.  sensor  then the setting must be set to the boiler manufacturer s specification   The Set Point  SP  should be set to the desired temperature for the Secondary loop    The Setback  Sb  value determines how many degrees the Secondary loop temperature will be decreased when the  EXT Input in the Setback mode  see pg  13  is shorted  Start with the factory default setting of 20  F     DISPLAY VALUES and ADJUSTMENTS    PRESS VSP Release center button to read value  LEFT If value needs adjustment  press the UP or DOWN button    BUTTON DISPLAY For large adjustments hold either button down    Air Thisis the temperature of the outdoor sensor  If it does not read  Once Oidean Temp  correctly  check theTroubleshootinguide     rEE Thisis the temperature of the water returning to the boiler  If this sens  Twice f is not installed it will diI  PN _ If the sensor isinstalled and does not  Return Temp    read correctly  check thd roubleshootinguide   Thisis the outdoor temperature below which the VSP will activate the  SES Secondary loop pump and control the variable speed pump  If the QM  3 times setting isselected  the VSP will activate or control both pumps  System Start   regardless of outdoor temperature  If the OFF setting is selected  the  VSP will never activate either pump   Set Point Operation  No Effect  rGt Reset Operation  The higher the curve number selected  the faster t  4 times   temperature of the Secondary loop will be increased as outdoor  Reset Ratio  temperature decre
3.  will halve the speed of the Injection pump  until the boiler return temperatures recover  Check if the VSP is in Setback and therefore running lower water tempera   tures  If neither of these conditions are causing insufficient heat  then adjust the Set Point  see pg  13      14    SENSORS    Each of the three VSP sensors are interchangeable and can be tested in  the same way  If the Secondary loop sensor is open or shorted  the main  display will show OPn or SHt  If either the Outdoor or the Boiler Return  sensor is open or short  the display will first flash the code for the sensor   either Airor rEt  and then flash OPn or SHt  To test the sensor  remove  the pair of sensor wires connected to the VSP terminals  Take a resis   tance reading across the detached wires going to the sensor  If the  reading shows     OPEN or a resistance greater than 100 000Q  Check the wires  going to the sensor  They may have been broken or become discon   nected  If the wires are fine  check the resistance at the sensor itself   If the value is still open  the sensor has been damaged and needs to  be replaced     SHORT or a resistance less than 100Q  Check the wires going to  the sensor  They may have become shorted together in the run of the  wire  If not  check the resistance at the sensor itself  If there still is no  resistance  the sensor has been damaged and needs to be replaced     Resistances from 200 to 100 000Q  Find the temperature that  corresponds to the resistance value on the c
4. 0  F  Delta T Secondary Loop 10  F  Maximum BTUs Required 200 000    First calculate the Primary Loop Temperature minus the Secondary Loop Temperature   140   100   40    The Delta T of the Secondary Loop is 10    Checking the first chart  Pipe Size 1 2   Globe Valve 20   the intersection of the row marked 40  Primary   Secondary  loop temp  and the column marked 10  Delta T  provides 50 000 as the maximum amount of BTUs  This is too low   Move on to the next chart     Checking the second chart  Pipe Size 1 2   Globe Valve 100   the intersection of the two values provides 112 500 as  the maximum amount of BTUs  This is too low  Move on to the next chart     Checking the third chart  Pipe Size 3 4   Globe Valve 100   the intersection of the two values provides 212 500 as the  maximum number of BTUs  This is just slightly more than the required Maximum BTU value  Use 3 4  Injection piping  with any of the following pumps  Taco 007  Grundfos 15 42  B amp G NRF22     injection Piping Size 1 2   Delta T of Secondary Loop    Globe Valve Opening0     10 15 20  Primary Loop 100 110 000 115 000 120 000    Temperature 80   90 000 95 000 100 000 Typical  60 70 000 75 000 80 000 Maximum _ Pump Models   minus   2 9 Injection Taco 007  i 40   50 000 55 000 60 000 BTUs Grundfoss 15 42  Secondary Loop 20 30 000 35 000 40 000 B amp G NRF22  Temperature 10   20 000 25 000 30 000  Injection Piping Size 1 2  I    p 3    gt   Globe Valve Opening  00  Delta T of Secondary Loop  10 15 20 l  i Prima
5. INSTALLATION OPERATING INSTRUCTIONS    A Variable Speed Pump Control       The VSP is a hydronic heating control  The temperature of the heating water is controlled by regulating the speed of a  pump which injects water from a hot boiler loop  Primary loop  into a cooler heating loop  Secondary loop   As the speed  of the pump increases  more hot water is sent into the Secondary loop  and the temperature of the heating water increases     The VSP can be used as an outdoor reset control  When the outdoor temperature falls below an adjustable start point   the heating system is activated  The temperature of the Secondary loop water is then automatically regulated based on  outdoor temperature  The outdoor reset function maintains constant and comfortable ambient building temperatures in all  weather conditions     The VSP can also be used as a set point control  In this mode of operation  the VSP will control the pump speed to hold a  constant temperature  determined by the user  in the Secondary loop  The outdoor start temperature can be set to ON so  the set point will be held regardless of outside temperature     The VSPis equipped with a Primary loop sensor  This sensor monitors the temperature of the boiler return water  If the  boiler return water falls below an adjustable temperature  the VSP can be configured to slow down the speed of the  injection pump to help the boiler return water temperatures recover     The VSP can be enabled or disabled from a standard thermosta
6. T Input can be configured to provide one of the following two functions    Setback Mode   e The EXT Input can be used to accept an input from an external clock to lower the temperature of the Secondary loop  when the building is not occupied  or when the occupants are sleeping    e When the EXT to COM terminals are open  the VSP will run normally    e When the EXT to COM terminals are shorted together the temperature of the Secondary loop will be reduced by the  number of degrees of Setback  see pg  13     Thermostat Mode   e The EXT Input can be used to accept an input from a thermostat to activate the heating system    e When the EXT to COM terminals are open  the VSP will not be active  Both pump outputs will be disabled    e When the EXT to COM terminals are shorted together  the VSP will activate the heating system if there is a call for heat   based on System Start setting described on pg  11      SENG THE OPERATING MODES    Whenever the VSP is powered up  it will display the software version number and then the current operating modes   Each display will remain on the screen approximately 5 seconds  If the modes are correct  there is no need to make any  adjustments    e Once the modes have been set for a particular application  they will be retained in memory and will not need to be reset    e Note that if you do change an operating mode  you will need to reset all other settings    e An operating mode can only be changed when it is being displayed in the start up seq
7. ases  for Reset curves see pg  12    Set Point Operation  No Effect  Reset Operation  The Offset will adjust the calculated Secondary lop  5 times temperature  determined by the outdoor temperature  Reset Ratio am  Setback  by the amount displayed   LO No Return Water Sensor  Set to OFF  6 times i g With Return Water Sensor  Set to the boiler manufacturer s  Low Min Return  specification for minimum boiler return temperature   Reset Operation ONLY  Thisisthe highest Secondary loop water  Jti H   temperature the VSP will maintain   imes s        IMPORTANT  The VSP isnot a safety control  All appropriate  Hi Max Suppl  ai safety controls must be installed   Set Point Operation ONLY  Thisisthe Secondary loop water  Sie temperature the VSP will maintain   7 UMEE Set Point IMPORTANT  The VSP isnot a safety control  All appropriate  safety controls must be installed   Sb    This is the number of degrees the Secondary loop water temperature  8 times will be lowered if the VSP is put into Setback   Setback  9 times Secondary Loop  Thisis the temperature reading of the Secondary loop sensor  If it dae  Default2 Temp  not read correctly  check th   roub eshootinqguide     1 These are sensor readings  They can not be adjusted         2 The display of each setting will remain active for approximately 20 seconds after the last adjustment  Then the  display will revert to the default reading     10    OPERATION    Injection    Digital display defaults to read Pee pump output    secondary l
8. ecification   The High Supply  Ai  value must be adjusted to the maximum temperature value specified for the Secondary loop  components    The Setback  Sb  value determines how many degrees the Secondary loop temperature will be decreased when the  EXT Input in the Setback mode  see pg  13  is shorted  Start with the factory default setting of 20  F     INITIAL SETTINGS FOR A SET POINT CONTROL  see SP previous page     After setting the operating mode  the VSP will display the temperature of the Secondary loop  This is the default value  for the VSP display    To see and or adjust the other parameters  press then release the center button marked PRESS TO READ  The VSP will  display a code to indicate which parameter will be displayed next  After two seconds  the value of the parameter will  be shown    For those parameters where the values can be set  shown on chart pg  10   press the UP or DOWN button to change  the value while it is being displayed  Holding down the UP or DOWN button will cause the value to change more  quickly    The System Start  StS  temperature setting is the outdoor temperature above which the VSP will not give heat  Set to  ON if the system set point should be held regardless of outside temperature    The reS et Ratio  rSt  and Offset  OFF  values have no effect and do not need to be adjusted    The LOw return  LOncomes factory set to OFF  This is the correct setting if you are not using the Boiler return water  sensor  If you do use the Boiler return
9. econdary Loop    20  510 000  425 000  340 000  255 000  170 000  127 500    Delta T of Secondary Loop    20  780 000  650 000  520 000  390 000  260 000  195 000    20  1 260 000  1 050 000   840 000  630 000  420 000  315 000    l Delta T of Secondary Loop    10    1 760 000  i 1 440 000  1 120 000  800 000  480 000  320 000    10  i 2 310 000  1 890 000  1 470 000  1 050 000  630 000    420 000    15  1 840 000  1 520 000  1 200 000   880 000  560 000  400 000    15  2 415 000  1 995 000  1 575 000  1 155 000   735 000  525 000    20  1 920 000  1 600 000  1 280 000   960 000  640 000  480 000    Delta T of Secondary Loop    20  2 520 000  2 100 000  1 680 000  1 260 000   840 000  630 000    Maximum  Injection  BTUs    Maximum  Injection  BTUs    Maximum  Injection  BTUs    Maximum  Injection  BTUs    Maximum  Injection  BTUs    Typical  Pump Models   Taco 007  Grundfoss 15 42  B amp G NRF22    Typical  Pump Models   Taco 007  Grundfoss 15 42    B amp G NRF22    Typical  Pump Models   Taco 0010  Grundfoss 26 64    Typical  Pump Models   Taco 0012  Grundfoss 43 75    Typical  Pump Models   Taco 0012  Grundfoss 43 75    CAUTION  Sizing Charts are based on Indusiry Standards  Values are approximations only  Actual  piping arrangements may affect outputs  The correct pipe and pump sizes for any application should  be performed by a qualified engineer or contractor     VSP WIRING DIAGRAM    120VAC  LINE NEU  Outdoor    E q Sensor BLUE    Wire Sensor RED D    COM Screw    i z  
10. ge the space tempera   ture  See chart on 10 to adjust the OF Fset     12    Water Temperature  in   F     Reset Ratio Curves       1 4 1 3 1 2 1 1 5  ax poga a a a  E ene  T ae T  170 Dale fi  pas dee ae Anes dene aime A 6 1 25 1  160 Beek  yaaa ca aa SF ae 51 5   150 berg Ls    o AET MET AE fea Li  ed APL LLL  gia  421  140 Pay i ES E E S A glans any seam aisia came  190 fA ff A pce 394  120   F Les AL es ee i 24 1  110 Ws Given 1 8 1  100 d T EE E E EAEE EE O E  70 60 50 40 30 20 10 O  10  20  Outdoor Temperature  in   F   Ratios represent Outdoor Water  Offset Examples  0   Offset e130  Y E  The ratiosbegin 5       at 100   Water    440  y 2  Temperature     100  70 60 50 40  Outdoor Temperature   20   Offset Sto  4 E      oO  The ratios begin 510  at 80   Water  amp  90    2  Temperature     80  70 60 50 40  Outdoor Temperature   20   Offset   2 150  Y 7      The ratiosbegin 5 ie  at 120   Water SB 130    2  Temperature     120  70 60 50 40  Outdoor Temperature    LOW  MINIMUM  RETURN   The LOw return  LOr  setting is designed to help speed recovery in the event of low boiler return water temperatures   The boiler manufacturer may require a minimum return water temperature to protect their boiler  Check with the boiler  manufacturer for the specified temperature     If the VSP registers that the temperature of the water returning to the boiler is below the LOw return  the VSP will immedi   ately halve the Injection pump speed and not allow the speed to increase again unt
11. hart  If the sensor  appears to be outputting correctly  check that the wires were properly  connected to the VSP  If they were  the VSP may have been damaged   If the sensor is not outputting correctly  take another reading at the  sensor itself  If this is correct  the problem is in the wiring between  the sensor and the VSP  Otherwise  the sensor has been damaged   and should be replaced     15    TEMPERATURE   in degrees F   0  10  20  25  30  35  40  45  50  55  60  70  80  90  100  110  120  130  140  150  160  170  180  190  200    VALUE   in Ohms   42683  31215  23089  19939  17264  14985  13040  11374  9944  8714  7653  5941  4649  3667  2914  2332  1879  1524  1243  1021  842  699  583  489  412       Heat Timer Controls for the HVAC R  amp  Plumbing Industry  Steam heating controls  Hydronic heating controls  Sequencing controls  Radiant heat controls  Digital set point controls  Precision tempering valves  VARIVALVE   air vents  2 3  and 4 way motorized valves  Snow melt controls    Heat Timer Corporation  20 New Dutch Lane  Fairfield  NJ 07004  Phone  973 575 4004 Fax  973 575 4052  http   www heat timer com HT  059220 00 REV A    16    
12. he leads of the voltmeter across the power inputs of the Injection pump  At the highest speed  the AC Volt  reading will be approximately 120VAC  As the speed is decreased  the reading will decrease down to approximately  10VAC  At the lower speeds  the reading may fluctuate by several Volts  This is considered to be normal     OUTPUT light is OFF or FLASHING but Injection pump is running  When the Output light is off or flashing   the Injection pump should not be running  Check the wiring to see if any other control  a HOA switch  or other switch  input is causing the pump to run  Turn the power off to the VSP  If the Injection pump continues to run  the VSP is  not the cause of the pump running     Insufficient Heat when the OUTPUT light is ON  Reset Operation   Check all the settings  If the Boiler Return  sensor reading is below the LOwreturn setting the VSP will halve the speed of the Injection pump until the boiler  return temperatures recover  The temperature of the Secondary loop will never exceed the High Supply setting for any  prolonged period of time  Check the High Supply is not set too low  Check if the VSP is in Setback and therefore  running lower water temperatures  If none of these conditions are causing insufficient heat  then adjust the reSet ratio  or OF Fset  see pg  12      Insufficient Heat when the OUTPUT light is ON  Set Point Operation   Check all the settings  If the Boiler  Return sensor reading is below the LOw return setting  see pg  13  the VSP
13. il the return temperature rises to the  LOw return setting  This means that the VSP will decrease the load on the Primary loop  but will still provide some heat to  the Secondary loop     NOTE  If a minimum return water temperature is not specified by the boiler manufacturer  or if the Secondary loop size is  such that it will have little impact on the Primary loop temperature  the Boiler Return sensor  see pg  2  may not be  installed  In that case it is necessary to adjust the LOwreturn setting to OFF  see chart on pg  10   Otherwise  set the  LOw return to the boiler manufacturer s specification     HIGH  MAXIMUM  SUPPLY  Reset Operation ONLY     The High Supply  Hi  setting is the maximum Secondary loop temperature the VSP will maintain  In some applications  it  may be necessary to limit the temperature of the water going out to the Secondary loop  This may be done for comfort or  because the Secondary loop components or flooring may be damaged by high temperatures     The High Supply should never be set higher than the maximum value specified by either the Secondary loop component  or the flooring manufacturer  Adjust the High Supply as shown on the chart pg  10     SET POINT  Set Point Operation ONLY     The Set Point  SP  setting is the Secondary loop temperature the VSP will maintain whenever there is a call for heat     The Set Point should never be set higher than the maximum value specified by either the Secondary loop component or  the flooring manufacturer  Adju
14. jection piping diameter  must be at least one pipe  size smaller than the smaller  of the Primary or Secondary  loop piping  See Sizing  Charts on pages 4 and 5     Primary and Secondary pipe  diameters may differ    Injection Pump   Pump motor type must be  fractional hors ower  permanent split capacitor    2  Secondary Loop Globe Valve    Balances the heating sy stem       CAUTION  The Injection pump and pipe sizing should be performed by a qualified engineer or contractor     3    INJECTION PIPE AND PUMP SIZING CHARTS    To determine the proper Injection Piping Size and appropriate pump  it is necessary to know the following four items     Primary Loop Temperature   This is the temperature the Primary loop will maintain    Secondary Loop Temperature   This is the design temperature for the Secondary loop  If an outdoor reset function  is being employed  this is the required temperature of the Secondary loop under maximum load    Delta T of the Secondary Loop   This is the design drop in temperature through the Secondary loop  In most radiant  heat applications  the Delta T is 10  Other types of radiation  such as baseboard  have a higher design Delta T    Maximum Injection BTUs  This is the maximum heat requirement of the Secondary loop  The Maximum Injection  BTUs is based on the Injection pump running at the highest speed  As the pump speed is reduced  fewer BTUS will  be delivered to the system     EXAMPLE   Primary Loop Temperature 140  F  Secondary Loop Temperature 10
15. n the outdoor temperature rises above this point  the Secondary Pump relay  BLACK wires  and the Injection  pump output  RED wires  will be off  The System Startis adjustable from 30  F to 70  F  The System Start also has two  special modes   OFF  When the System Start is set to OFF  neither the Secondary loop pump nor the Injection pump will run  This can be  used for testing or to disable heat to the particular loop  Do not use this feature to turn off pumps for maintenance  For  this  use the safety disconnect   ON  When the System Start is set to ON  the Secondary loop pump will run regardless of outdoor temperature  The  Injection pump speed will be regulated to control the temperature of the Secondary loop water temperature   Follow the chart on pg  10 to adjust the System Start     11    RESET RATIO  Set Point Operation   reSet ratio  rSt  has no effect     Reset Operation    The reSet ratio  rSt  determines how the Secondary loop  water temperature will vary with outside temperature  With  any ratio  the colder it is outside  the hotter the tempera   ture of the Secondary loop  At a 1 1 reset ratio  Curve 7  a  1 degree drop in outdoor temperature will increase the  Secondary loop temperature by 1 degree  at the 3 1 ratio   Curve 3  an outdoor temperature drop of 3 degrees will  increase the Secondary loop temperature by 1 degree     The ratios are adjustable from 8 1  Curve 1  for the least  amount of heat to 1 4  Curve 12  for the most amount of  heat  see side char
16. nput for a thermostat  When the thermostat input is open   both pump outputs will be disabled    e To change the mode  hold down the center button while pushing either the UP or DOWN button to toggle between the  displays of Sb and thr    e When the correct mode is selected  release the buttons and wait approximately 5 seconds     no or YES  Pump Activation every 24 hours    If the display shows YES then the VSP will activate both the Secondary Loop pump and the Injection pump for 5  minutes every 24 hours  Certain local codes  generally only in Canada  require this    If the display shows no then the VSP will only run the pumps when the system requires it  This setting will prevent  hot water from being pumped into the Secondary loop when there is no call for heat    To change the mode  hold down the center button while pushing either the UP or DOWN button to toggle between the  displays of YES and no    When the correct mode is selected  release the buttons and wait approximately 5 seconds    If any changes were made to the operating modes  the display will flash  Then the VSP will display the temperature of  the sensor in the Secondary loop     ee SETTINGS FOR A RESET CONTROL  see rSt previous page     After setting the operating mode  the VSP will display the temperature of the Secondary loop  This is the default  display    To see and or adjust the other parameters  press then release the center button marked PRESS TO READ  The VSP will  display a code to indicate which 
17. oiler return temperatures  see Low Return pg  13     e The VSP can be configured to control without this sensor input  see NOTE in Low Return pg  13   It is not necessary  to install this well if the input will not be used    e The well should be located in the boiler return of the Primary loop after all returns     HORIZONTAL PIPING CONFIGURATION  The Injection piping can be installed horizontally as shown on the next page    e The Injection supply piping should run horizontally from the Primary to the Secondary loop    e On the Injection return piping it is necessary to install a heat trap to prevent heat from the Primary loop entering the  Secondary loop when the Injection pump is not running    e The return piping must drop down vertically at least 18  and then rise back up vertically at least 18      VERTICAL PIPING CONFIGURATION    e The Injection piping can be installed vertically as shown on the next page   e The Primary loop must be at least 18  vertically above the Secondary loop     Injection System Components    Secondary Loop Sensor  Secondary Loop Te ue    Injection Pump     BOILER  Secondary  Loop       Globe Valve    Boiler Return Sensor    Horizontal Piping Detail    Primary Loop Secondary Loop    Max 4D          Maximum length of pipe  between tees should not  exceed 4 times the pipe  diameter    Min 18    Minimum vertical drop of  inches on heat trap or  between the Primary and  Secondary loops    Injection Piping          8  Min 18     Pipe Sizing   The In
18. oo TE       or  Remote Enable         Pump  Starter   Motor                       Pump Secondary    Loop Sensor         K Sensor       Pump i  Motor  h k    BOILER E Secondary f L  jecti Loop Pum  Boiler Return Injection W P p l  D      Must be connected directly to 120VAC motor  NO PUMP STARTER      If Pump Starter Motor is not rated for 120VAC power  contact the factory for wiring directions    CONTROL INSTALLATION    MOUNTING THE CONTROL  The VSP is designed to mount on a 1900  4x4  electrical box    e Ifthe VSP is to be panel mounted  or if additional room is needed for wiring  an extension kit is available  HT  908520     e Locate the VSP in a convenient location near the variable speed pump  The VSP can not be mounted more than 500   from any sensor location    e Mount the VSP away from excessive heat or cold  Ambient operating temperature is from 20 to 120  F    e After completing all the wiring connections  see opposite page  use the two screws provided to mount the VSP to the  1900 box     INSTALLING THE SENSORS    e All three sensors are interchangeable    e The sensor wires can be extended up to 500  from the controller by splicing with shielded two conductor 18 gauge  wire   Do not connect the shield at the sensor end  Do not run wires in conduit with line voltage    e The Secondary loop sensor should be inserted in the well as described on pg  2    e The Boiler return water sensor  if used  should be inserted in the well as described on pg  2    e The Outdoor sen
19. oop temperature RED               Secondary loop    BLACK L   pump output          _ 120VAC    Output light indicates BLUE   power input    when system is active             Push these buttons to adjust    Push this button to display control parameters    sensor values and control LE   Reset Ratio    parameters LFF   Offset  1 Pr   Min Return    FD   Max Set Point      L   Setback  SEC OUT RTN COM EXT COM    Dry contact input for either  Setback or  Remote Enable Disable    Secondary loop sensor  Outdoor sensor    Boiler return sensor Sensor common    OUTPUT LIGHT   The output light has the following three indications    Light Off  The heating system is not active  Neither the Secondary loop pump nor the Injection pump output are active    Light On  The heating source output is active  The Secondary loop pump relay is energized  and the speed of the Injection pump  is being controlled    Flashing  The Secondary loop pump relay is energized to circulate the water through the loop  The Injection pump output is not  active  This would occur when there is a call for heat  but the temperature of the Secondary loop is satisfied so none of  the hot water from the Primary loop is needed in the Secondary loop     SYSTEM START TEMPERATURE    The System Start  StS  is the outdoor temperature below which the Secondary loop pump will be activated to circulate  water through the loop and the Injection pump speed will be regulated to control the temperature of the Secondary loop  water  Whe
20. parameter will be displayed next  After two seconds  the value of the parameter will  be shown    For those parameters where the values can be set  shown on chart pg  10   press the UP or DOWN button to change  the value while it is being displayed  Holding down the UP or DOWN button will cause the value to change more  quickly    The System Start  StS  temperature setting is the outdoor temperature above which the VSP will not give heat  Start  with the factory default setting of 60  F    The reSet Ratio  rSt  determines how quickly the water temperature in the Secondary loop will increase as the outdoor  temperature decreases  see pg  12   Lower numbered curves result in lower water temperatures  The factory default  curve is 7 or  1 1   This means for every degree the outdoor temperature falls  below the System Start temperature  the  Secondary loop temperature will be increased one degree  For baseboard heat  start with 7  For most radiant tubing  applications  start with 3    The Offset  OFF  value is added or subtracted to the calculated water temperature for the Secondary loop  It effec   tively moves the starting point of the reset curves up and down by the number of degrees selected  see pg  12   Start  with the factory default setting of 0    The LOw return  LO comes factory set to OFF  This is the correct setting if you are not using the Boiler return water  sensor  If you do use the Boiler return sensor  then the setting must be set to the boiler manufacturer s sp
21. ry Loop 100   247 500 258 750 270 000    Temperature 80 202 500 213 750 225 000 Typical  Maximum Pump Models     60 157 500 168 750 180 000 aries Taco 007  i minus I Injection  40 112 500 123 750 135 000 BTUs Grundfoss 15 42  Secondary Loop 20 67 500 78 750 90 000 B amp G NRF22  l Temperature 10    45 000 56 250 67 500    Injection Piping Size 3 4   Globe Valve Openingi 00     Primary Loop 100    l Temperature 80    60   l minus 40  Secondary Loop 20  Temperature 10    Injection Piping Size 1   Globe Valve Openingi 00     i Primary Loop 100    Temperature 80   l minus ay  40   Secondary Loop 20   l Temperature 10    Injection Piping Size 1 1 4   Globe Valve Openingi 00     Primary Loop   1007    Temperature 80   i minus 90  40   l Secondary Loop 20  Temperature 10    Injection Piping Size 1 1 2   Globe Valve Openingi 00     Primary Loop 100    l Temperature 80    60     minus 40  Secondary Loop 20  Temperature 10    Injection Piping Size 2   Globe Valve Openingi 00     i Primary Loop 100  Temperature 80   minus 9   l 40  Secondary Loop 20   i Temperature 10      Delta T of Secondary Loop    10  467 500    382 500  297 500    212 500  127 500  85 000    10   1 715 000  585 000  455 000  325 000  195 000     130 000    l 10   4 155 000  945 000  1 735 000  525 000  1 315 000  210 000    15  488 750  403 750  318 750  233 750  148 750  106 250    15  747 500  617 500  487 500  357 500  227 500  162 500    15  1 207 500  997 500  787 500  577 500  367 500  262 500    Delta T of S
22. sor should be mounted in the shade on the north side of the building  never in direct sunlight   Keep  the sensor approximately 10  above ground level and away from doors  windows  exhaust fans  or other heat sources     WIRING THE SENSORS    e The sensor wires have no polarity  Either wire from a sensor can be connected to the appropriately marked VSP screw  terminal  see pg  11  or the sensor common marked COM    e Either or both screw terminals marked COM can be used as the sensor common  They are interchangeable    e Ifthe sensor wires have been extended  connect the shield to a COM terminal    e The two wires from the Secondary loop sensor must be connected to the VSP front screws marked SEC and COM    e The two wires from the Outdoor sensor must be connected to the VSP front screws marked OUT and COM    e The two wires from the Boiler return water sensor  if used  must be connected to the VSP front screws marked RTN and  COM   If not using this sensor  see the NOTE in Low Return pg  13      WIRING THE VSP POWER   e Attach 120VAC line voltage to the two Blue wires extending from the back of the VSP    e Use wire nuts  or wrap the connections with electrical tape    e Class 1 voltages must enter the 1900 box through a different opening from any Class 2 wiring     WIRING THE INJECTION PUMP  The Red wires provide a solid state switching output to the Injection pump    e The Injection pump motor must be a fractional horsepower permanent split capacitor type motor    e The ou
23. st the Set Point as shown on the chart pg  10     SETBACK  The Setback  Sb  setting has no effect if the VSP is in Thermostat mode  see pg  8      When the VSP is initialized to run in the Setback mode  the EXT Input can be connected to an external clock or switch   see pg  11   When the EXTto COM terminals are shorted  the VSP will reduce the temperature of the Secondary loop by  the number of degrees selected  For instance  if the calculated Secondary loop water temperature were 130  F and the  Setback were set to 10    then if the EXT Input were shorted  the calculated water temperature would immediately change  to 120  F     A rule of thumb for adjusting the Setback with baseboard radiation is to decrease the water temperature 4   for each  degree you wish to lower the ambient space temperatures  Therefore  if you wish the space temperatures to be 5   colder  at night or when the building is not occupied  adjust the setback to 20    With radiant heat  adjust the setback only 1 or 2  degrees for each degree you wish to lower the space temperature     Warning  The VSP is an operating control only  If excessive temperatures will cause system  damage  separate limit controls must be installed     13    TROUBLESHOOTING    OPERATION    No Display  Check the 120VAC power into the Blue input wires  If power is present  turn the power to the VSP off and  then back on     Display shows or flashes OPn or SHt  Follow the procedure for SENSORS on next page     OUTPUT light is OFF when
24. t   With most baseboard heating  applications  a 1 1  Curve 7  setting is a good place to start   Radiant heat applications usually require a lower curve     Adjust the re Set ratioin cold weather  If the ambient  space temperatures are too cold in cold weather  increase  the curve number by one  If the space temperatures are  too warm in cold weather  decrease the curve number by  one  After making a change to the ratio  wait 24 hours to  evaluate the impact of the change  See chart pg  10 to  adjust the reSet ratio    OFFSET    Set Point Operation   OF Fset  OFF  has no effect     Reset Operation    The OF Fset  OFF  allows you to adjust the starting points  of the Reset Ratio curves  see side charts   When the   OF Fset is changed  that change is always directly added  or subtracted to the calculated water temperature  For  instance  if the calculated Secondary loop water tempera   ture were 130  F and the OF Fset were changed from 0   to  10    an increase of 10     then the calculated water tempera   ture would immediately change to 140  F     Adjust theOF F set in mild weather  If the ambient space  temperatures are warm in mild weather  decrease the   OF Fset  If the space temperatures are cold in the mild  weather  increase the OF Fset  The rule of thumb for  baseboard radiation is to change the OF Fset by 4   for  every degree you wish to change the space temperatures   For radiant heat applications  change the OF Fset by 1   or  2   for every degree you wish to chan
25. t or switch  Or  the VSP can reduce the temperature of the  heating loop water when the building is not occupied or when occupants are sleeping     Table of Contents    adl oTi oTe EEEE EAT ET toast he AT ESE E EE meee E EAE fats pg  2  Piping Diagrams sereset erar eE aces fe es aves EEE ERE ede EAEE OE eee pg  3  la oT Ne EENE E AE A O TE E pg  4  Control Installation   ie ttina aa a aaea aa iaa aa aantas a a pg  7  Display  Charts 0 5  a E A A pg  10  Operation  e a i ea A eee et ot pg  11  Troubleshooting  ices eee es eh es a ee a ee a ed ee ea pg  14    PIPING  PIPING OVERVIEW    The Primary loop may have multiple injection loops or other takeoffs  However  the piping for each injection system  must meet the requirements described below and shown on the next page    e The Injection piping can be installed in either a horizontal or a vertical configuration       The pipe diameters of the Primary and Secondary loops may differ    e The Injection Piping diameter must be at least one pipe size smaller than the smaller of the Primary or Secondary loop  piping  For example  if the Primary loop diameter is 1 1 4  and the Secondary loop diameter is 1   then the diameter of  the Injection piping must be 3 4  or smaller  See Sizing pages 4 and 5 for actual pipe size    CAUTION  The Injection pump and pipe sizing should be performed by a qualified engineer or  contractor    e The Injection pump motor must be a fractional horsepower permanent split capacitor type  The Injection pump 
26. tput is designed for AC power only  The maximum rating for the injection pump output is 3A 1 4HP    e The Red wires must be directly in series with the pump power  see pg  6   The signal can not be wired through any  pilot duty relays or pump starters    e Safety limit switches or HOA switches must be wired in series with the pump power    e Use wire nuts  or wrap the connections with electrical tape    e Class 1 voltages must enter the 1900 box through a different opening from any Class 2 wiring     Warning  This Heat Timer control is strictly an operating control  it should never be used as a  primary limit or safety control  All equipment must have its own certified limit and safety controls  required by local codes  The installer must verify proper operation and correct any safety problems  prior to the installation of this Heat Timer control     WIRING THE SECONDARY LOOP PUMP  The Black wires provide a Normally Open  N O  relay output for the Secondary loop pump   e The Black wires are a dry contact output only  They do not source any power   e The Secondary loop pump relay is rated at 8A 1 8HP   e Use wire nuts  or wrap the connections with electrical tape   e Class 1 voltages must enter the 1900 box through a different opening from any Class 2 wiring   e Wire the N O  dry contacts to the pump starter     WIRING THE EXT INPUT    e TheEXT and COM terminals can only accept a dry contact input  If power is applied across these terminals  the VSP  may be damaged    e The EX
27. uence  To restart the sequence  it is necessary to remove power to the VSP and then power it again    e Set the operating modes as described in sequence below    For   C   Fahrenheit or Celsius Temperature Operation   e Ifthe display shows   F then the VSP will operate in Fahrenheit degrees    e Ifthe display shows   C then the VSP will operate in Celsius degrees    e To change the mode  hold down the center button while pushing either the UP or DOWN button to toggle between the  displays of   F and   C    e When the correct temperature mode is selected  release the buttons and wait approximately 5 seconds    rSt or SP  Reset or Set Point Operation   e Ifthe display shows rSt then the VSP will run with as an outdoor reset control  see pg  12   As it gets colder outside   the VSP will automatically increase the temperature of the Secondary loop    e Ifthe display shows SP then the VSP will hold the selected set point temperature in the Secondary loop  To select the  Set Point  see chart pg  10    e To change the mode  hold down the center button while pushing either the UP or DOWN button to toggle between the  displays of rSt and SP    e When the correct mode is selected  release the buttons and wait approximately 5 seconds    Sb or thr   Setback or Thermostat Mode   e Ifthe display shows Sb then the VSP will use the EXT Input  see above  for an external clock or switch to lower the  temperature of the Secondary loop    e Ifthe display shows thr then the VSP will use the EXT I
28. will  control the amount of water pumped from the hot Primary loop into the Secondary loop    e A globe type valve should be installed on the injection return piping  This helps to balance the system    e The distance between the injection tees should be as short as possible  The maximum distance between the two tees  can be no more than 4 times the pipe diameter  For instance  if the pipe diameter is 1  then the length of straight pipe  between the two injection tees can not exceed 4      WSTACOING THE WELLS    Two wells are supplied with the VSP  One is for the Secondary loop sensor and  one is for the Return water sensor    e The wells should not be located more than 500  from the VSP controller    e Both wells are 3 8  ID  3 4  WELL   e The wells are designed to be installed in a tee with a 3 4  bull  HT  350147   e Solder the well into the bull of the tee as shown  Slide the sensor into the  well after the joint has cooled    Secondary Loop Well   e This well should be located past the pump in the Secondary loop supply         e The sensor in this well will measure the temperature of the Secondary  loop  The VSP will control the Injection pump based on the information SENSOR  from this sensor  H    904015    Boiler Return Well   e The sensor in this well will measure the temperature of the water returning to the boiler    e If the sensor is installed  it will allow the control to reduce the demand of the Secondary loop to help speed boiler  recovery in the event of low b
    