Home

INSTALLATION/OPERATING INSTRUCTIONS ® - Heat

image

Contents

1. 75 4004 Fax 973 575 4052 http www heat timer com 8 HT 059242 00 REV A
2. INSTALLATION OPERATING INSTRUCTIONS DiGr sPAN TMC Temperature Monitoring Control Temperature Range 30 to 250 F 35 to 120 C The TMC displays and monitors a system s temperature and provides an alarm light and output if the system temperature reaches a critical point The alarm condition can only be cleared by opening the locking enclosure and pressing the manual reset button The TMC is ideal for domestic hot water systems see pg 5 When the domestic water temperature rises above the selected set point the TMC will enter the alarm mode The TMC will control a Normally Closed solenoid valve In the alarm mode the solenoid valve will shut down the flow of hot water into the domestic system To open the solenoid valve and let the hot water back into the system two things must happen the domestic water temperature must fall below the critical point and the manual reset button must be pressed Other typical uses of the TMC include e Freeze condition alarms e Refrigeration system alarms e Hydronic heating systems high temperature alarms and control for solenoid valve to disable the heating system e Space temperature alarm systems In areas where power losses are common the TMC can be ordered with a battery backup This will prevent the need for manually resetting the system whenever there is a power failure The battery backup will keep the TMC active for approximately two hours and will recharge when power is restored The TMC
3. aT a a LEGEND 2 THERMOMETER g DEAR TUES F GATE VALVE TEMPERING VALVE Zl CHECK VALVE Heat Timer tempering valve mixes hot water with cold return water to control the temperature of the water being supplied to the domestic hot water system The Normally Closed solenoid valve is installed in the hot water line The TMC sensor is installed in the flow of the water being supplied to domestic system The sensor should be located 6 to 10 past the valve but before any takeoffs If the TMC registers the domestic water temperature has risen above the maximum acceptable temperature the TMC will enter the Alarm mode The solenoid valve will shut and prevent the hot water from entering the system The alarm will sound to alert staff Once the problem has been corrected the manual reset button must be pressed and the domestic system can return to normal operation 5 OPERATION CONTROL EXAMPLE Set Point 120 F Differential 2 F Alarm on Hot Alarm on Cold On arise in Temp to 120 F Alarm Mode Active On a fall in Temp to 118 F Alarm Mode Active Alarm light is ON Alarm light is ON LED is OFF LED is OFF Clearing the Alarm Mode Clearing the Alarm Mode Temperature falls to 118 F or below Temperature rises to 120 F or above LED is ON LED is ON Press Manual Reset Button Press Manual Reset Button Adjusting the Set Point e When set to Alar
4. can also be ordered in a weatherproof enclosure for mounting outdoors or other areas which require a NEMA 4 enclosure ACCESSORIES e 120VAC Normally Closed Solenoid valve available in sizes 1 2 to 2 e 1 2 NPT x 3 8 Brass Well HT 904011 00 e Visual Audio Alarm HT 925011 00 see pg 8 for wiring SPECIAL ORDER e Battery backup provides up to 2 hours of operation if 120VAC power fails Battery recharges when power is restored e NEMA 4 enclosure for mounting outdoors e TMC may be ordered for pressure or humidity applications LIMITED ONE YEAR WARRANTY This Heat Timer device was thoroughly tested for defects and workmanship before leaving our factory We do warrant the equipment to be free of defects under normal use for a period of one year from the date of installation Transportation charges for factory repairs must be prepaid Damage to the Heat Timer device or any of its components due to misuse abuse improper installation or caused by power failures fire flood or lightning are not covered by this warranty The company assumes no liability for indirect or consequential damages of any nature This Heat Timer warranty applies only to the original purchaser user is not assignable or transferable and does not cover damage to the device occurring in shipment Any service repairs modifications or alterations to the unit not expressly authorized by the company will invalidate the warranty This warranty is in lieu of all other warranties e
5. ct Temperature Display 23089 SHT Display The TMC sees a short across the input terminals and the Alarm r ITT mode will be active If you remove the sensor wires from the TMC terminals the display should change to read OPN If the display does not change to OPN the TMC may be damaged Incorrect Temperature Display Remove the wires from the SENSOR screws The display should change to read OPN and the Alarm mode should activate if it was not already active If they don t the TMC may be damaged Take an ohm reading across the detached sensor wires The ohm reading should correspond to the chart on the right If the ohm reading is significantly different the sensor may be damaged Alarm mode does not activate Turn power to the TMC off Turn power back on and check the TMC s operating modes are correct see pg 4 When the TMC has finished displaying the operating modes the TMC should be in the Alarm mode If it isn t the TMC may be damaged Alarm mode does not activate at the desired temperature First complete the steps in the previous section When the operating modes have been set correctly check the set point and differential values If the TMC is set to Alarm on Hot then the Alarm mode should become active when the tempera ture rises to the set point If the TMC is set to Alarm on Cold then the Alarm mode should become active when the temperature falls to the set point MINUS the differential The Alarm mode can not be cleared un
6. ed see pg 3 for button positions Press and hold either the upper right button to increase the differential or the lower right button to decrease the differen tial until the desired value is displayed Wait approximately 10 seconds If the differential was changed the display will flash Then the TMC will return to displaying the sensor temperature If you don t want to wait 10 seconds press the upper left button once and the sensor temperature will be displayed immediately LED Light e The small LED light should be on whenever the TMC is in the Normal mode e Ifthe TMC is in the Alarm mode and the LED is off the Alarm mode can not be cleared This is because the system tempera ture is outside the safe range of operation see Control Example above e Ifthe TMC is in the Alarm mode and the LED in on the Alarm mode can be cleared by pressing the Manual Reset Button Alarm Light e The large Alarm Light will be on whenever the TMC is in the Alarm mode e To clear the Alarm mode and light the small LED light must be on and the Manual Reset Button must be pressed 6 TROUBLESHOOTING TEMPERATURE VALUE No Display Check the 120VAC 60hz power to the TMC Turn the power off and in dearees F in Ohms back on 59075 OPN Display The TMC does not see a sensor connected and the Alarm mode will 42683 be active Check the sensor wires are continuous and have not been broken or 31215 disconnected Then follow the procedure for Incorre
7. ely NOTE When alarming on a Hot System temperature the alarm will activate at the set point value Startup When the TMC is powered up it will be in the Alarm mode Use the three upper buttons to adjust the set point and differential as described above If the system temperature is in the appropriate range the red LED should be on If it is not on the TMC Alarm mode can not be cleared Press the lowest button or the Manual Reset Button see pg 3 The TMC should enter the NORMAL mode WARNING Whenever the TMC loses power it requires the Manual Reset Button lowest button see pg 3 be pressed This is a safety feature of the TMC and can not be disabled NOTE The TMC can be special ordered with battery backup The rechargeable battery will keep the TMC active for approximately two hours if power fails TYPICAL APPLICATION 9 TMC SENSOR HEAT TIMER mih TMC i an CIRCULATING PUMP rf Ni D CONTINUOUS RUNNING M SOLENOID COLD WATER j T VALVE TEMPERED CI ia Zi i C fh PURCHASED N C WATER H To Se TEMPERED WATER A UL Li ia CIRCULATING T Eai gt RETURN LINE A HEAT TIMER HOT TEMPERING VALVE WATER A 573 OPTIONAL POSITION HOT a tom 1 1 32 MINIMUM WATER aa G a SUPPLY Z d z 7 J SOURCE N i U
8. ence To restart the sequence it is necessary to remove power to the TMC and then power it again Set the operating modes as described in sequence below For Fahrenheit or Celsius Temperature Operation If the display shows F then the TMC will operate in Fahrenheit degrees If the display shows C then the TMC will operate in Celsius degrees To change the mode hold down the center button while pushing either the UP or DOWN button to toggle between the displays of F and C When the correct temperature mode is selected release the buttons and wait approximately 5 seconds Hor C Alarm on Hot or Alarm on Cold If the display shows H then the TMC will enter the Alarm mode when the system temperature rises above the set point If the display shows C then the TMC will enter the Alarm mode when the system temperature falls below the set point MINUS the differential To change the mode hold down the center button while pushing either the UP or DOWN button to toggle between the displays of H and C When the correct heating or cooling mode is selected release the buttons and wait approximately 5 seconds WARNING When alarming on a Cold system temperature the alarm will activate at the set point MINUS the differ ential For example with a set point of 34 F and a differential value of 2 F the TMC will enter the Alarm mode when the temperature falls to 32 F It is critical that the TMC set point and differential are set appropriat
9. less the system temperature is in the appropriate range as indicated by the LED being on If the LED is on pushing the Manual Reset Button should clear the Alarm mode TMC does not activate an alarm Remove all connections from terminals 5 through 10 see pg 3 If the Alarm mode is not active turn TMC power off and back on The red Alarm light should be on Test for continuity across both pairs of terminals marked ALARM and COM Terminals 6 7 and 9 10 If there is continuity across the terminals then the TMC is working correctly Check the alarm and alarm wiring for the problem TMC does not open a NC solenoid valve The red Alarm light must be off and the LED light must be on Remove all connections from terminals 5 through 10 see pg 3 Test for continuity across both pairs of terminals marked NORMAL 9944 and COM Terminals 5 6 and 8 9 If there is continuity across the terminals then the TMC is working correctly Check the valve and valve wiring for the problem Vis U Larm Wiring TMC Terminals O Q INYV IV fel eo ae 120VAC Vis U Larm Heat Timer Controls for the HVAC R amp Plumbing Industry Steam heating controls Hydronic heating controls Sequencing controls Radiant heat controls Digital set point controls Precision tempering valves VARIVALVE air vents 2 3 and 4 way motorized valves Snow melt controls Heat Timer Corporation 20 New Dutch Lane Fairfield NJ 07004 Phone 973 5
10. m on Hot see pg 4 the TMC will enter the Alarm mode when the system temperature rises to the set point as shown above e When set to Alarm on Cold the TMC will enter the Alarm mode when the system temperature falls to the set point MINUS the differential as shown above e To adjust the set point use the following steps l 2 3 4 TMC should be displaying sensor temperature Press the upper left button and release it The display will change to show SP Wait 2 seconds or press the upper or lower right button and the set point will be displayed see pg 3 for button positions Press and hold either the upper right button to increase the set point or the lower right button to decrease the set point until the desired value is displayed Wait approximately 10 seconds If the set point was changed the display will flash Then the TMC will return to display ing the sensor temperature If you don t want to wait 10 seconds press the upper left button once to adjust the differen tial or twice to immediately display the sensor temperature Adjusting the Differential e The differential prevents the TMC from short cycling the Alarm mode To set the differential use the following steps 1 2 3 4 TMC should be displaying the sensor temperature Press and release the upper left button twice The display will change to show d F Wait 2 seconds or press the upper or lower right button and the set point will be display
11. sed NC This means when there is no power applied to the solenoid valve it will be shut The TMC will power the valve open and allow hot water to pass into the system only when the temperature is below the set point and the manual reset button has been pressed The solenoid valve power should be switched through output terminals marked NORMAL and COM These are either terminals 5 and 6 or terminals 8 and 9 see opposite page Wiring an Alarm The alarm output will be active whenever the system temperature has risen or fallen if in the cooling mode out of range Even if the temperature then returns to normal the alarm will not clear until the manual reset button has been pressed The alarm power should be switched through output terminals marked ALARM and COM These are either terminals 6 and 7 or terminals 9 and 10 see opposite page Wiring other Outputs The TMC can be used to activate pumps heaters chillers fans or any other piece of on off equipment The TMC can also be used for two position control such as a valve actuator or damper motor When the TMC is in the Normal mode the outputs NORMAL and COM will be continuous both terminals 5 and 6 or terminals 8 and 9 When the TMC is in the Alarm mode the outputs COM and ALARM will be continuous both terminals 6 and 7 or 9 and 10 IMPORTANT WIRING INFORMATION Class 1 wiring must enter the enclosure through a different KO from Class 2 wiring Double Pole Double Throw relay o
12. utput is rated for 6A 1 3HP at 120VAC Outputs are Dry Contacts Only No voltage is supplied out of terminals 5 through 10 Push the center button to display the set point or differential Alarm light is on when the TMC is in lt the ALARM mode Digital display reads sensor c I lt lt value constantly C LED is on when the TMC is in the NORMAL mode yO O oc Push these buttons g to adjust the set O point or differential MANUAL RESET BUTTON Press button to clear ALARM mode if system temperature is within specification DPDT RELAY OUTPUTS SENSOR 120VAC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 TTTTT INOS INOS rf To system sensor TWINYON NYV1V TWINYON NYV1V 120VAC Solenoid Valve Power Alarm Power Heat Timer Vis U Larm EMS Notifact NC Solenoid Valve or other alarm Setting the Operating Modes Whenever the TMC is powered up it will display the software version number and then the current operating modes Each display will remain on the screen approximately 5 seconds If the modes are correct there is no need to make any adjust ments Once the modes have been set for a particular application they will be retained in memory and will not need to be reset Note that if you do change an operating mode you will need to reset the set point and differential An operating mode can only be changed when it is being displayed in the start up sequ
13. xpressed or implied INSTALLATION Mounting The mounting site should be flat strong enough to hold the TMC and no more than 500 from the sensor Mount the unit away from excessive heat or cold Ambient operating temperature is from 20 F to 120 F The enclosure has one keyhole mounting tab extending from the top of it and two mounting tabs extending underneath Use all three tabs to secure the unit DO NOT drill any holes into or through the enclosure Installing the Temperature Sensor The temperature sensor wires can be extended up to 500 by splicing with 18 gauge shielded wire Do not run wires in conduit with line voltage If measuring liquid temperature the sensor should be inserted into a 3 8 ID well HT 904011 or equivalent The TMC will operate based on the temperature it reads at the sensor location Therefore select a sensor location which is representative of the entire system The sensor wires must be connected to the two terminals 11 and 14 marked SENSOR see opposite page Polarity is not important Either wire from the sensor can be connected to either input terminal Power Connections The TMC requires 120VAC 60hz Connect to the left most input terminals 1 and 12 see opposite page Wiring a Normally Closed Solenoid Valve Hot Water Systems The solenoid valve is designed to shut off the flow of hot water to the system see Typical Application on pg 5 The solenoid valve should be Normally Clo

Download Pdf Manuals

image

Related Search

Related Contents

ET-800 User Manual  

Copyright © All rights reserved.
Failed to retrieve file