PR750ELCD User's Manual

image

Contents

1. CyberPower Reliability Quality Value PR750ELCD User s Manual K01 0000224 00 IMPORTANT SAFETY INSTRUCTIONS This manual contains important safety instructions Please read and follow all instructions carefully during installation and operation of the unit Read this manual thoroughly before attempting to unpack install or operate your UPS CAUTION The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection DO NOT plug the UPS into an outlet that is not grounded If you need to de energize this equipment turn off and unplug the UPS CAUTION DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT CyberPower Systems does not sell products for life support or medical applications DO NOT use in any circumstance that would affect the operation and safety of life support equipment medical applications or patient care CAUTION Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected CAUTION To prevent the risk of fire or electric shock install in a temperature and humidity controlled indoor area free of conductive contaminants Please see specifications for acceptable temperature and humidity range CAUTION To reduce the risk of electric shock do not remove the cover except to service the battery There are no user serviceable parts inside except for the battery CAUTION To avoid electrical shock turn off the unit and unplug it from the AC
2. BASIC OPERATION DESCRIPTION Status Setup Control Test EAE Expansion Port Provides SNMP Card Communication IN 0 w n PR750ELCD 1 Power Switch Power On Indicator Used as the master on off switch for equipment connected to the battery power supplied outlets 2 Online Indicator This LED is illuminated when the utility power is normal and the UPS outlets are providing power free of surges and spikes 3 On Battery Indicator During a severe brownout or blackout this LED is illuminated and an alarm sounds two short beeps followed by a pause to indicate the UPS is operating from its internal batteries 4 Fault This LED is illuminated if there is a problem with the UPS 5 Replace Battery Indicator This LED is illuminated to remind users to replace the battery 6 Tab Status Button For UPS status information press the button for 1 second For additional information including the use of the button as a Tab please refer to the Function Setup Guide 7 Enter Setup Button Press the Setup button for 1 second to enter setup menu and then select the functions for configuration For more information about the Setup Enter button please refer to the Function Setup Guide 8 Up Control Button Press the Control button for 1 second to enter control menu and then select the functions for configuration This button is also used to scroll up For more information about the Control Up button please refe
3. module on the wall c Replacing the LCD on the UPS To place the LCD back on the UPS roll up the LCD cable return it to the space between the front panel amp battery cover and replace the LCD CYBERPOWER GREENPOWER UPS TECHNOLOGY CyberPower s Green Commitment CyberPower is dedicated to the development of green products and has adopted Green practices throughout its business including membership in Climate Savers Computing Initiative CSCI accordance with the Restriction on Hazardous Substances ROHS Waste Electrical and Electronic Equipment WEEE protocols as well as ISO 14001 and IECQ QC080000 CyberPower pledges to provide the ENERGY SAVING advanced energy solution for the environment and become a leading eco friendly TECHNOLOGY organization in the UPS industry Reduce Energy Cost with GreenPower UPS Technology CyberPower s goal is not only to provide eco friendly products but also to bring the best value for consumers The advanced energy saving design improves the operating_efficiency and eliminates waste energy consumption As a result consumers will enjoy significant energy cost savings with the adoption of GreenPower UPS technology BATTERY REPLACEMENT CAUTION Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery Service the battery under the supervision of personnel knowledgeable of batteries and their precautions CAUTION U
4. power source before servicing the battery or installing a computer component CAUTION DO NOT USE WITH OR NEAR AQUARIUMS To reduce the risk of fire do not use with or near aquariums Condensation from the aquarium can come in contact with metal electrical contacts and cause the machine to short out INSTALLING YOUR UPS SYSTEM UNPACKING The box should contain the following 1 UPS Unit x 1 2 Emergency Power Off Cable gray x 1 3 Serial Cable x 1 4 USB Cable x 1 5 User Manual x 1 6 Management software Disk x 1 7 Function Setup Guide x 1 8 IEC to IEC Power cord x1 OVERVIEW The PR750ELCD provides automatic voltage regulation for inconsistent utility power The PR750ELCD features 405 Joules of surge protection and provides battery backup during power outages The PR750ELCD ensures consistent power to your computer system and its included software will automatically save your open files and shut down your computer system during a utility power loss HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT 1 Make sure that the total Volt Amp VA requirements of your computer monitor and peripheral equipment does not exceed 750VA 2 Ensure that the equipment plugged into the battery power supplied surge outlets does not exceed the UPS unit s rated capacity 750VA 675W for PR750ELCD If the rated unit capacities are exceeded an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip
5. space heater vacuum paper shredder or other large electrical device into the battery power supplied outlets The power demands of these devices will overload and possibly damage the unit 4 Plug the UPS into a 2 pole 3 wire grounded receptacle wall outlet Make sure the wall branch outlet is protected by a fuse or circuit breaker and does not service equipment with large electrical demands e g air conditioner refrigerator copier etc Avoid using extension cords 5 Depress the power switch to turn the unit on The power on indicator light will illuminate and the unit will beep 6 If an overload is detected an audible alarm will sound and the unit will emit one long beep To correct this turn the UPS off and unplug at least one piece of equipment from the battery power supplied outlets Wait 10 seconds Make sure the circuit breaker is depressed and then turn the UPS on 7 Your UPS is equipped with an auto charge feature When the UPS is plugged into an AC outlet the battery will automatically recharge 8 To maintain optimal battery charge leave the UPS plugged into an AC outlet at all times 9 To store your UPS for an extended period cover it and store with the battery fully charged Recharge the battery every three months to ensure battery life 10 The LCD module is wall mountable for extended distance control Follow the steps below for installation procedure a Remove the LCD module from the front panel b Hang the LCD
6. For more information visit www cpsww eu or contact Cyber Power Systems Inc E MAIL sales cpsww eu All rights reserved Reproduction without permission is prohibited CE A 10
7. ency it can be used to immediately cut off power from the UPS OPTION 1 USER SUPPLIED NORMALLY CLOSED SWITCH 4 5 JUMPER 5 N C EPO SWITCH RJ11 PLUG N O EPO SWITCH RJ11 PLUG NO CONNECTION 14 SNMP HTTP Network Slot Remove the cover panel to install an optional RMCARD to remotely monitor and manage your UPS over a network 15 Circuit Breaker Located on the back of the UPS the circuit breaker provides overload and fault protection 16 AC Input Connect the AC power cord to a properly wired and grounded outlet HARDWARE INSTALLATION GUIDE 1 Your new UPS may be used immediately upon receipt However recharging the battery for at least 8 hours is recommended to ensure that the battery s maximum charge capacity is achieved Charge loss may occur during shipping and storage To recharge the battery simply leave the unit plugged into an AC outlet The unit will charge in both the on and off position Note This UPS is designed with a safety feature to keep the system from being turned on during shipment The first time you turn the UPS on you will need to have it connected to AC power or it will not power up 2 If you will use the software connect the USB cable to the USB port on the UPS 3 With the UPS unit off and unplugged connect the computer monitor and any externally powered data storage device Zip drive Jazz drive Tape drive etc into the battery power supplied outlets DO NOT plug a laser printer copier
8. from the batteries Install the replacement batteries by connecting the wire bundle composed of one red wire and one black wire to the connector from the battery pack 8 Put the batteries back into the compartment 9 Re install the battery compartment cover and push both round knobs back into place 10 Remove the LCD module before putting the front panel back on the UPS 11 Replacing the LCD on the UPS To place the LCD back on the UPS roll up the LCD cable return it to the space between the front panel amp battery cover and replace the LCD 12 Recharge the UPS for 8 16 hours to fully charge the battery NOOR WD REMINDER Batteries are considered HAZARDOUS WASTE and must be disposed of properly Almost any retailer that sells lead acid batteries collects used batteries for recycling DEFINITIONS FOR ILLUMINATED LCD INDICATORS Operation Mode Load Power Load VA Load Amps Load Energy Estimated Runtime Setup Wizard Language Utility Power MIN O P Voltage MAX O P Voltage LCD Auto Sleep Cycling Display Audible Alarm Temporarily Mute Sensitivity Charge Mode Low Battery Warning gt gt gt gt gt gt gt gt gt gt gt gt VVVV VV VV VV VV Battery Information Input Output Last Self Test Date amp Time Auto Self Test Date amp Time Battery Change Date Firmware Update Power Meter Reset Back to Default Delay Turn On Delay Turn Off Reboot Duration Minimum Rest
9. m expected runtime out The on off switch is designed to prevent damage by rapidly turning it off and on The UPS will not turn on The battery is worn out Mechanical problem The USB cable is not nn PowerPanel Business connected Edition is inactive The unit is not providing battery power Overload l Output Short The fault LED is illuminated Battery Overcharge Over Temperature Turn the UPS off and unplug at least one piece of equipment Wait 10 seconds reset the circuit breaker by depressing the button and then turn the UPS on Battery not fully Recharge the battery by leaving the UPS charged plugged in Battery is slightly worn Contact CyberPower Systems about replacement batteries at support cpsww eu Turn the UPS off Wait 10 seconds and then turn the UPS on Contact CyberPower Systems about replacement batteries at support cpsww eu Contact CyberPower Systems at support cpsww eu Connect the USB cable to the UPS unit and an open serial port on the back of the computer You must use the cable that came with the unit Shutdown your computer and turn the UPS off Wait 10 seconds and turn the UPS back on This should reset the unit excessive load and restart the CyberPower Systems at support cpsww eu CyberPower Systems at support cpsww eu CyberPower Systems at support cpsww eu Additional troubleshooting information can be found at www cpsww eu
10. ore Capacity Uptime on Battery Reserve Runtime Control Menu gt UPS On Off gt Self Test gt Alarm Test gt Battery Calibration Transfer Event X1 X10 Fault Event F1 F10 Model Name Last Battery Change Next Battery Change UPS Firmware Version LCD Firmware Version Serial Number For more information about functions setup please refer to the Function Setup Guide TECHNICAL SPECIFICATIONS PR750ELCD Capacity VA 750VA 675W Frequency Range 47 63Hz Auto Sensing AVR Function On Battery Output 230Vac 5 Voltage On Battery Output 50 60Hz 1 Frequency Overload Protection On Utility Circuit Breaker amp Internal Current Protection On Battery Internal Current Limiting Lightning Surge Protection Operating Temperature 32 F to 104 F 0 C to 40 C Total of UPS outlets IEC x6 Maximum Dimensions LxWxH 349 x 138 x 162 mm Weight kg Battery Typical Recharge Time Charging Current Max User Replaceable Indicators Power On LCD Display Online On Battery Fault Replace Battery Audible Alarms On Battery Low Battery Overload Communication PowerPanel Personal Windows 7 Vista XP 2000 Server 2003 Linux Edition Software Self Test Auto Charger Auto Restart USB interface Yes Expansion Port EPO Port TROUBLESHOOTING Circuit breaker has tripped due to an overload Circuit breaker button is projecting from the back of the unit The UPS does not perfor
11. r to the Function Setup Guide 9 Down Test Button Press the Test switch for 1 second to enter test menu and then select the functions for configuration This button is also used to scroll down For more information about the Test Down button please refer to the Function Setup Guide 10 Esc Logs Button Press the Logs button for 1 second to view the events or logs that have been recorded This button is also used to exit a menu For more information about Logs Esc button please refer to the Function Setup Guide 11 Battery and Surge Protected Outlets The unit has six battery powered surge suppression outlets for connected equipment to ensure temporary uninterrupted operation of your equipment during a power failure DO NOT plug a laser printer paper shredder copier soace heater vacuum Sump pump or other large electrical devices into the Battery and Surge Protected Outlets The power demands of these devices may overload and damage the unit 12 Serial USB Ports to PC The Serial and USB ports allow connection and communication between the computer and the UPS unit Note Only one port can be used at a time 13 EPO Port Use the provided gray EPO cable to connect to a provided EPO contact switch Follow the appropriate circuit diagram to the right to wire the cable to your EPO configuration The EPO remote switch is a switch installed in an outside area connected to the unit via the Emergency Power Off cable In case of an emerg
12. se only the specified type of battery See your dealer for replacement batteries CAUTION The battery may present the risk of electrical shock Do not dispose of batteries in a fire as they may explode Follow all local ordinances regarding proper disposal of batteries CAUTION Do not open or mutilate the batteries Released electrolyte is harmful to the skin and eyes and may be toxic CAUTION A battery can present a high risk of short circuit current and electrical shock Take the following precautions before replacing the battery 1 Remove all watches rings or other metal objects 2 Only use tools with insulated handles 3 DO NOT lay tools or other metal parts on top of battery or any battery terminals 4 Wear rubber gloves and boots 5 Determine if the battery is inadvertently grounded If inadvertently grounded remove source of ground CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance applicable to a UPS and a remote battery supply not having a grounded circuit BATTERY REPLACEMENT PROCEDURE Turn off and unplug all connected equipment Turn the UPS off and unplug it from the AC power source Remove the front panel of the UPS Pull out both round knobs and remove the battery compartment cover completely off of the unit Remove the batteries from the compartment Disconnect the battery wires