K-BUS R Switch Actuators User manual

image

Contents

1. nnn onan nnn nnn nnn nnn nnn nnn naman anaman 9 3 1 Overview 9 3 2 Parameter window All General 9 3 3 Parameter window Channel X Switch actuator 12 3 3 1 Parameter window X Time 16 3 3 2 Parameter window X Preset 22 3 3 3 Parameter window X Logic 23 3 3 4 Parameter window X Scene 25 3 3 5 Parameter X Threshold 26 3 3 6 Parameter window X Safety 28 3 3 7 Parameter window X Forced 29 3 4 Parameter window Channel X Dynamic regulating Actuator 30 3 4 1 Parameter window X Function Dynamic regulating Actuator 33 3 4 2 Parameter window X Monitoring
2. 43 3 6 2 Monitoring function object of Dynamic Regulating Actuator 44 3 6 3 Forced function communication object Dynamic Regulating Actuator 45 3 6 4 Timing function communication object Dynamic Regulating Actuator 45 4 Priority level description 45 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 1 Introduction This manual provides you the detailed technical information about the Switch Actuators not only the installation and programming details but also the usage explanation in actual application They can be installed in the distribution boards on 35mm mounting rails according to EN60715 These switch actuators can be used to control the switch loads such as e Lighting e Heating control e Signal devices 1 1 Product and function overview The switch actuators are the modular installation devices with 2 8 and 12 outputs for selection using EIB BUS connection terminals to connect to the system The switch actuators are connected to the AC power supply directly instead of an extra voltage supply It is able to use the Engineering Tool Software ETS ETS2 v1 3 or later with a VD2 VD3 file to allocate the physical address and set the parameters but a VD3 file i
3. 33 3 4 3 Parameter window X Forced 35 3 4 4 Parameter window X Regular 36 3 4 5 Parameter window X Safety 37 3 5 Communication object Switch Actuator 38 3 5 1 Communication object All General 38 3 5 2 General communication object Switch Actuator 39 3 5 3 Timing function communication object Switch Actuator 40 3 5 4 Preset function communication object of Switch Actuator 41 3 5 5 Logic function communication object of Switch Actuator 42 3 5 6 Scene function communication object of Switch Actuator 42 3 5 7 Threshold function communication object of Switch Actuator 43 3 5 8 Forced function communication object Switch Actuator 43 3 6 Communication object Dynamic Regulating Actuator 43 3 6 1 General communication object Dynamic Regulating Actuator
4. Scene handle For example scene in the parameter setup has the same output result as scene 0 in the communication object Scene handle Table 2 6 scene function communication object Switch Actuator 42 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 3 5 7 Threshold function communication object of Switch Actuator Threshold 1 change A Change threshold 1 A Communication object ma Threshold input A 15 Threshold input A 1 Byte Low vv Fig 2 27 threshold function communication object Switch Actuator No Function Object name Data type Flags 14 Change threshold 1 X Output X 1Byte W C This object is used to change the value of the threshold 1 15 Threshold input X Output X 1Byte W C This object is used to receive the threshold sent by other devices Table 2 7 threshold function communication object 3 5 8 Forced function communication object Switch Actuator Communication object Number Function Object Type Priority RJWIC T ju ma Forced output A 16 Forced output A 1 Bit Low vv Fig 2 28 forced function communication object Switch Actuator No Function Object name Data type Flags 16 Forced output X Output X 1bit W C This object will be started after enabling the forced function Enable the forced function with 1
5. and the other behaviors will be ignored except the forced function enable the forced function with 0 Table 2 8 forced function communication objects 3 6 Communication object Dynamic Regulating Actuator 3 6 1 General communication object Dynamic Regulating Actuator Communication object Number Function Object Type Priority RIWIC T jU ae Output A 14 continuous of regulating A 1 Byte Low vv ae Output A 4 on off of regulating A 1 Bit Low vv Communication object Number Function Object Type Priority RIWI IC T ju ma reply status continuous 1 byte 13 Status continuous 1 byte A 1 Byte Low v v ma reply status continuous 1 bit A 5 Status continuous 1 bit A 1 Bit Low Communication object Number Function Object Type Priority R W C T U ma Reply status of contact A 3 Reply status of contact A 1 Bit Low v v Fig 3 29 general communication object Dynamic Regulating Actuator 43 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators No Function Object name Data type Flags 14 continuous of regulating X Output X 1Byte W C This object will be enabled when selecting byte continues in the parameter Control telegram is received as is used to receive the control command of 1Byte with range from 0 to 255 the valve will be off with 07 on with 255 4 on off of reg
6. contact close 0 contact open Yes 0 contact close 1 contact open Under the selecting of Yes J contact close 0 contact open when there is some request from other devices the object Reply status of contact will send 1 to other devices if the contact is closed While if it is 32 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators open it will send 0 to the other devices It is quite the contrary when selecting Yes 0 contact close 1 contact open 3 4 1 Parameter window X Function Dynamic regulating Actuator This window in Fig 2 16 will pop out when selecting active in the parameter Special functions of dynamic regulating actuator mode for channel X is and it decides whether enable the function of dynamic regulating actuator 1 1 6 Switch actuator 4 fold universal All General A Function Channel A Channel B Function for monitoring is disable Channel C Kak Channel D Function of forced operation is disable Function of regular switch is disable Function of safety operation is disable Fig 2 16 setup window A Function Parameter function for monitoring is function of forced operation is function of regular switch is function of safety operation is Options enable disab
7. Contact position if tele value is 1 O is opposite of 1 if changed open Special functions of switch actuator mode for channel A is inactive Fig 2 3 parameter window channel X It is able to choose an operation mode and its corresponding functions for every output and the functions are activated separately Parameter Channel X work mode is This parameter is used to define the output mode Options Switch Actuator Dynamic regulating actuator Switch Actuator is used in the normal switch control such as lighting The outputs are controlled by various functions such as logic operation timing function and safe function More details can be found below Parameter If bus voltage recovery contact is The output can adopt a defined status on bus voltage recovery via this parameter Options Unchange open closed As before bus voltage fail When selecting Unchange the contact of the relay will remain the same as the last status before power off when selecting open the contact will be open while it is closed when selecting closed The contact position after voltage recovery is the same as that before power off with As before bus voltage fail 13 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators Parameter If bus voltage fail contact is The output can adopt a define
8. but its priority level is secondary only to force Table2 1 communication object table All General 3 5 2 General communication object Switch Actuator Communication object ma send the switch status channelA 3 send the switch status A Communication object Function j R W C T U Parent value reply the switch status channelA 3 reply the switch status A Communication object j ji Priority R W C T U Parent value Ge output a 4 Switch actuator A 1 Bit Low Hi Fig 2 22 general communication object per output No Function Object name Date byte Flags 3 send the switch Output X 1bit C T status X This object will be enabled when selecting Transmit after change in the parameter Set the reply mode of switch status for channel X which will indicate the contact status details will be defined by parameter Object value of switch status in Channel X 39 E www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 3 reply the switch Output X 1bit R C T status X This object will be enabled when selecting always respond after read only in the parameter Set the reply mode of switch status for channel X which will indicate the contact status details will be defined by parameter Object value of switch status in Channel X 4
9. 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators Note C in Flag column in the below table means that the object has a normal link to the bus W means the object value can be modified via the bus R means the value of the object can be read via the bus T means that a telegram is transmitted when the object value has been modified U means that value response telegrams are interpreted as a write command the value of the object is updated No Function Object name Data type Flags 0 In operation General 1bit C R T This object is always enabled used to send telegram 1 to the bus periodically to proof the device is under normal working condition 1 Safety Priority 1 General 1bit W C U It is able to receive the lbit telegram from the other devices such as sensors and controllers and so on and modify the running condition of the other devices by this object The other devices will be judged as malfunction if this object doesn t receive the relevant telegram for a certain time which will be defined in the window All General and then it will trigger the set action of Safety Priority 1 in X Safety The priority of Safety Priority 1 is lower only to Forced operation and Safety Priority 2 2 Safety Priority 2 General 1bit W C U This object has the same function as Safety Priority 1
10. In this function the output is used to control the cooling heating temperature In some room thermostat will send a control value out to switch the valve e g 2 step control Application description can be found in below text 3 2 Parameter window All General The parameter window All General will be shown in Fig 2 1 which applies to every output www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 1 1 6 Switch actuator 4 fold universal All General All General Channel A Channel B Operation delay after recovery of bus Channel C voltage 1 250s Channel D Sending cycle of In operation telegram 1 240s Osinactive Enable safety priority function disable 1 switch on O switch off Normal object value map switch onyoff ta ki AN switch on contact close switch off contact open Cancel Default l Fig 2 1 parameter window All General Note Switch on mentioned below means the contact of the switch actuator is closed output is on switch off means the contact of the switch actuator is open output is off Parameter Operation delay after recovery of bus voltage 1 250s The parameter determines the delay time to react after the bus voltage recovery the delay time after electrified to avoid the malfunction of the bus and 220V AC caused by the simultaneously
11. The window shown in Fig 2 13 will be seen when selecting enable in the parameter Function of safety for switch is in Fig 2 5 28 EE www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 1 1 6 Switch actuator 4 fold universal All General A Safety Channel A Function AcTime Setting of safety on parameter window General A Preset et aac A Logic Contact position if safety priority 1 unchange A Scene A Threshold Contact position if safety priority 2 unchange ChannelB Channel C Channel D Cancel Default Fig 2 13 setup window X Safety Enable 2 Safety Priority x 1 2 in the parameter window All General which define the relay s contact position for every output individually There are 2 safety priorities for every output and also the Safety Priority 2 is prior to Safety Priority 1 It means when these 2 priorities are triggered at the same time the contact position will follow the setup of Safety Priority 2 Note the contact position will not be changed if the Safety function is disabled while the Safety priority X is triggered setting in the parameter window All General Parameter Contact position if Safety Priority x x 1 2 It defines the contact position after triggering Safety Priority x x 1 2 Options Unchange Op
12. and change the threshold 1 value by the bus on the other hand it cannot change the value with disable However it is not allowable to change the threshold 2 value by the bus Parameter Threshold behaviour The parameter defines the delay status of threshold I value and threshold 2 value Option without hysteresis with hysteresis 27 aa ana www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators The delay can avoid the unnecessary behaviour caused by the input value if its value is between 2 threshold values Parameter If falling below lower threshold contact position If exceeding upper threshold contact position These parameters will be seen with with hysteresis in the parameter Threshold behavior which defines the action when the value of the object Threshold input is lower than the lowest threshold value or higher than the highest value Options Unchange Open Close Parameter If falling below lower threshold contact position If exceeding upper threshold contact position If lower lt object value lt upper contact position These parameters are visible with without hysteresis in the parameter Threshold behavior which defines the relay action in the object Threshold input Options Unchange Open Close 3 3 6 Parameter window A Safety
13. when selecting restart duration of staircase lighting during the staircase lighting while it will ignore the telegram with Ignored the switch on telegram Parameter Warning mode for ending of staircase lighting The parameter points out the alarm type when terminating the staircase lights which will start the prealarm notice before switching off This prealarm time is not included in the starting duration of the staircase There will be no alarm if selecting nothing as well as the lights is off before the prealarm time Options nothing via object flashing the channel output with OFF ON via object amp flashing the channel output 2 types of prealarm are provided by the communication object set the value of the object Warning of staircase as J when starting alarming and then send it to the bus by the lights flashing control the output flashing a short switch and the duration is 1 second These 2 types can be used independently or together It will be the type of by the communication object 19 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators when it is via object or the type of by the lights flashing with flashing the channel output with OFF ON as well as mixed type with via object amp flashing the channel output Parameter The warning time for ending of staircase
14. Rjwic T ju input 1 of logic A 1 Bit Input 1 of logic A ae input 2 of logic A 12 Input 2 of logic A 1 Bit Low vv Fig 2 25 logic function communication object for every output of Switch Actuator No Function Object name Data type Flags 11 Input 1 of logic X Output X 1bit W C This object will be enabled when selecting enable in the parameter The input 1 of logic is 12 Input 2 of logic X Output X 1bit W C This object will be enabled when selecting enable in the parameter The input 2 of logic is Table 2 5 logic function communication objects 3 5 6 Scene function communication object of Switch Actuator Communication object Number Function Object Type Priority RIwWwIC IT U Ee Scene A 13 Scene handle A 1 Byte Low vv Fig 2 25 scene function communication object of Switch Actuator No Function Object name Data type Flags 13 Scene handle X Output X 1Byte W C It is able to invocate or save the scene when sending an 8 bit command by this object which will be enabled when enabling the scene function The definition of the 8 bit command will be described below Assuming an 8 bit command binary coding as FXNNNNNN F invocate the scene with 0 save the scene with yr X 0 NNNNNN scene number 1 64 1 64 in the parameter setup corresponds to the scene number 0 63 received by the communication object
15. Switch X Output X 1bit W C This object is used to trigger the switch operation It will start the switch operation with I and end with 0 When enabling input 0 in the logic function the object Switch X is used to modify the logic value of input 0 rather than trigger the switch operation Table 2 2 general communication table per output 3 5 3 Timing function communication object Switch Actuator Cunmnunication object Function Privrity E Output A 5 Output of staircase lighting A 1 Bit Low vv Communication object Number Function Object Type Priority RjwWic IT lu E Output A 5 Switch out with delay A 1 Bit Low vv Communication object Number Function Object Type Priority R JWIC T ju Ga output A 5 Switch out with flashing A 1 Bit Low Bra Communication object Number Function Object Type Priority R W C T ju mal Disable function of time A 6 Disable time function A 1 Bit Low vv Communication object Number Function Object Type Priority R W C T ju mal Warning of staircase lighting A 7 Warning of staircase A 1 Bit Low vv Communication object Number Function Object Type Priority R Wi C T U ae staircase duration A 8 Duration of staircase A 2 Byte Low LAI Fig 2 23 Switch Actuator timing communication object for every output No Function Object name Datatype Flags 5 Output of staircase lighting X Output X 1bit W C It is used to
16. contact position stays the same with unchange it will be open with Open and off with Close When ending the operation position will be reversed if it is changed after starting for instant selecting open or close otherwise it will remain the same Note The parameter only works after receiving object Switch x and defines the direction of the contact after receiving it More details can be found in the below form Parameter Switch X value 1 Switch X value 0 Unchange Unchange Unchange Open Contact open OFF Contact close ON close Contact close ON Contact open OFF Parameter Special functions of switch actuator mode for channel X is This parameter defines whether enable the special functions of the switch actuator The parameter window X Function will be seen with active and able to set the special functions individually in Fig 2 4 Enable or disable the special function in X Function seen in Fig 2 5 Options active inactive 15 jk ana anan na www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 1 1 6 Switch actuator 4 fold universal All General Channel A Channel 4 Function i Channel B Channel work mode is Switch actuator Channel C A r Channel D If bus voltage recovery contact is unchange If bus voltage fail conta
17. gate function Explanation of gate function it will use the previous logic value as the enable mark of the next logic If the enable mark of the previous logic is 7 that means it is able to use the next logic value as the operation result E g the value of input 0 is 1 that means the value of input 1 can be used as the operation result if the value of input 1 is 1 that means the value of input 2 can be used as the result too Options AND OR XOR Gate function Parameter Result is inverted This parameter defines whether negate the logical operation results Negate it with yes don t with no Options no yes Parameter Value of input 1 after bus voltage recovery This parameter defines the default value of the object Input x of logic x 1 2 after bus voltage recovery Options 0 1 Value before power off The value will be the one before power off after bus voltage recovery when selecting value before power Parameter Value of input 2 after bus voltage recovery This parameter defines the default value of the object Input x of logic x 1 2 after bus voltage recovery Options 0 1 Unchange The default logic value is unsure when selecting Unchange 3 3 4 Parameter window A Scene The parameter window shown in Fig 2 11 will burst out when selecting enable in Function of scene for switch is in Fig 2 5 25 aa ana aii www video star com c
18. lighting 0 59s The parameter is visible after selecting a prealarm type and the duration of the prealarm second Options 0 59 Parameter Modify the duration via object 0 60059 seconds It will activate the object Duration of staircase with 2 bytes when selecting Enable to modify the staircase lighting time however it cannot modify the time with disable Options disable Enable Note If the values of telegram for modification the duration is 0 the staircase lighting will be disabled 3 3 1 3 Selection Flashing The parameter window in Fig 2 8 X Time flashing switch will be shown up when selecting flashing switch in The mode of time function 1 1 6 Switch actuator 4 fold universal All General Channel amp Function ATme The mode of time function flashing switch ChannelB Delay for switch on Channel C 0 240 minutes Channel D 0 59 seconds Delay for switch off 0 240 minutes 0 59 seconds Number of ON impulses 1 255 0 no limited Contact position after flashing unchange The mode of control for flashing Start with 1 Stop with 0 Fig 2 8 parameter window X Time flashing switch It is able to set the flashing time in Delay for switch on or Delay for switch off which will restart the flashing when receiving the relevant telegram by the
19. lt aN GVSs Guangzhou Video star Electronics Industrial Co Ltd Elg KNX K BUS Switch Actuators User manual Ver 2 KA R 0416 1 KA R 0816 1 KA R 1216 1 KNX EIB Intelligent Installation Systems K BUS BUS A a c D E J g 3 x t i 1 i 0 e e e 6 d s p A g WA ziw E17 ENR CE www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators Contents 1 Introduction 2 nnn nnn nnn nnn nnn nnn nnn nnn nnn 3 1 1 Product and function overview 3 2 Technical Properties amp Dimension and Connection Diagram 4 2 1 Technical Properties 4 2 2 Dimension and Connection Diagram 6 2 2 1 KA R 0416 1 6 2 2 2 KA R 0816 1 7 2 2 3 KA R 1216 1 8 3 Commissioning
20. room There are 2 options of control mode for every output 1 bit control and 1 byte control Under the 1bit mode it will receive 1 bit command by the communication object on off of regulating under the lbyte mode it will receive 1 byte command by the communication object continuous of regulating 0 means the valve is off while 100 is on And 0 100 means during a cycle period the valve will be 30 ee www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators on for x of the period while off for the rest time 1 1 6 Switch actuator 4 fold universal All General Channel A Channel Channel B i Jynamic regulating actuat Channel C Channel A work mode is Dynamic regulating actuator v Channel D If bus voltage fail contact is unchange If bus voltage recovery the duty cycle of dynamic regulate O OFF PWM cycle time for continuous control 3 1 240 minutes PWM cycle time for continuous control 0 0 59 seconds Control telegram is received as 1 bit on off control Reply the status of contact state nothing Special functions of dynamic regulating actuator mode for channel 4 is inactive Fig 2 15 setup window channel X Dynamic regulating Actuator Parameter If bus voltage fail contact is This parameter defines the contact position when the bu
21. send 1 to the bus when the alarm is starting R W C This object will be enabled when selecting enable in the parameter Modify the duration via object 8 Duration of staircase K Output X 2Byte 0 60059 seconds to modify the duration of the staircase lighting Table 2 3 timing function communication table 3 5 4 Preset function communication object of Switch Actuator Communication object Number Function Object Type Priority RiIwICIT ju ma Output A 9 Call preset 1 2 A 1 Bit Low vv Communication object Number Function Object Type Priority RiIwICIT ju ma Store preset 1 2 A 10 Store preset 1 2 A 1 Bit Low vv Fig 2 24 preset function communication object for every output of Switch Actuator No Function Object name Data type Flags 9 Call preset 1 2 X Output X 1bit W C This object is used to call the preset value call 1 with 0 and 2 with 1 10 Store preset 1 2 X Output X 1bit W C It can be used to save the current switch status as the new preset value save the new preset value 1 with 0 and 2 with 1 Table 2 4 preset communication objects 41 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 3 5 5 Logic function communication object of Switch Actuator Communication object Number Function Object Type Priority
22. switch on the staircase lighting by this object which will be enabled when selecting staircase lighting in the parameter The mode of time function 5 Switch out with delay X Output X 1bit W C It is used to switch on the time delay by this object which will be enabled when selecting delay switch in the parameter The mode of time function 5 Switch out with flashing X Output X 1bit W C It is used to switch on the flash output by this object which will be enabled when selecting flashing switch in the parameter The mode of time function 40 See ee www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 6 Disable time function X Output X 1bit W C This object will be started only when enabling the time function which can be enabled by this object It will enable the timing function when receiving the value 1 will disable it when receiving 0 It will not carry out the controlled telegram sent by the time function during disabled time until enable the time function and restart the time counting function Enable is a default setting after bus voltage recovery 7 Warning of staircase X Output X 1bit C T It will be enable while selecting warning by this object in the parameter Warning mode for ending of staircase It will
23. 4 5x60 Weight In kg KAUR 0416 1 0 3 KAIR 0816 1 0 5 KA R 1216 1 0 7 Electrical endurance load 100 000 cycles 30 000 cycles Incandescent lamp 1 250 W 2 500 W Fluorescent lamp not compensated 1 200 W 2 500 W Fluorescent lamp Parallel compensated 650 W 70 uF 1 300 W 140 RE Fluorescent lamp duo combination 2x1 200 W 2x2 500 W Halogen lamp 230 VAC 1 200 W 2 500 W Low voltage halogen lamp with transformer 500 VA 500 VA Mercury arc sodium discharge lamp not compensated 1 000 W 2 000 W Mercury arc sodium discharge lamp parallel compensated 1 000 W 70 uF 2 000 W 140 uF Dulux lamp not compensated 800 W 1 600 W Dulux lamp parallel compensated 560 W 70 uF 1 100 W 140 uF 5 E www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators Note The above load is only for single lamps In the case of several lamps in parallel the load will be reduced although the power is unchanged but the instantaneous impact of current will increase and easy to make the relay contacts melted In normal use the maximum output current is preferably less than 10A and inductive load and capacitive load will be lower Application programs Type Max number of Max number of Max number of communication objects group addresses associations KA R 0416 1 59 85 85 KA R 0816 1 115 160 160 KA R 1216 1 171 250 250 2 2 Dimension and Connection Diag
24. 620 39338465
25. Parameter The mode of control flashing The parameter states the mode of the flashing output Options star with 1 stop with 0 star with 0 stop with 1 star with 1 0 can not be stopped It will start flashing with 7 received by the object Switch when selecting star with 1 stop with 0 it will stop flashing with 0 It will start flashing with 0 received by the object Switch when selecting star with 0 stop with 1 it will stop flashing with I It will start flashing with either or 0 received by the object Switch when selecting star with 1 0 can not be stopped Under this circumstance it cannot terminate the flashing by sending the telegram until the preset ending time 21 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 3 3 2 Parameter window X Preset This parameter window in Fig 2 9 will burst out when selecting enable in the parameter Function of preset for switch is j PITEN Ta ae All General A Preset Channel amp Function F AcTime Action for preset 1 object value 0 Ls Channel B Action for preset 2 object value 1 Channel C Channel D Setting for preset via telegram is Fig 2 9 setup window X Preset It is able to not
26. actuator 4 fold universal All General Channel amp Function e 9 i atime The mode of time function staircase lighting Channel B Duration of staircase lighting E Channel C 0 1000 minutes 2 Channel D 0 59 seconds The mode of control for staircase lighting is During the lighting time if receive the 0 Start with 0 1 can not be stop Start telegram restart duration of staircase lighting Warming mode for ending of staircase nothin lighting nahing_ Modify the duration via object disabl 0 60059 seconds disable Fig 2 7 parameter window X Time Staircase lighting The staircase lighting function is switched on via the object Output of staircase lighting And also it is available to program the value of Output of staircase lighting The staircase lighting time starts when it is switched on and will be switched off immediately after the set time when there is no prealarm setting Parameter Duration of staircase lighting 0 1000 minutes This parameter describes the duration time when switching on the staircase light function minutes Options 0 1000 Parameter Duration of staircase lighting 0 59 second 18 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators This parameter describes the duration time whe
27. alues Output life expectancy Output switching times Connections Operation display maketing video star com cn www video star com cn Operation voltage Current consumption EIB KNX Power consumption EIB KNX Type KA R number of contacts U rated voltage I rated current Max switching current Power loss per device at max load Mechanical endurance Electrical endurance Operation period per output Delay times after switching on Delay times after switching off EIB KNX Load output connection terminal Red Led and push button Green Led flashing Indication of the contact position 21 30 V DC via EIB bus lt 12 mA Max 360 mW 0416 1 0816 1 1216 1 4 8 12 250V AC 50 60Hz 16A 16A 16A 20A 250V AC 2W AW SW gt 10 gt 10 55ms 30ms 25ms Bus connection terminal 0 8mm Screw terminal assigning the physical address the application layer works normally close means the output is on 4 Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators open means the output is off Housing IP20 to EN60529 Safety class I to EN61140 Temperature range Operation 5 C 45 C Storage 25 C 55 C Transport 25 C 70 C Ambient condition Humidity lt 93 except dewing Design Modular DIN Rail Component 35mm Din rail modular installation MDRC Dimension LxWxH mm KA R 0416 1 90x71 5x60 KAIR 0816 1 90x143x60 KAIR 1216 1 90x21
28. ct is unchange Object value of telegram switch ere after bus voltage recovery death AA Set the reply mode of switch status no reply for channel Contact position if tele value is 1 0 is opposite of 1 if changed Special functions of switch actuator a mode for channel A is a open Fig 2 4 starting setup window X Function 1 1 6 Switch actuator 4 fold universal All General A Function Channel A amp Function am Function of time for sith is lt ChannelB eer Channel C Function of preset for switch is disable Channel D Function of logic for switch is disable Function of scene for switch is disable Function of threshold for switch is disable Function of safety for switch is disable Function of forced for switch is disable Fig 2 5 setup window X Function 3 3 1 Parameter window X Time This parameter window will become visible when selecting enable in the parameter Function of time for 16 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators switch is in the setup window X Function See Fig 2 6 1 1 6 Switch actuator 4 fold universal All General Channel A amp Function ATme The mode of time function delay switch Channel B Delay for switch on C
29. d status after the bus voltage failure via this parameter Options Unchange open closed When selecting Unchange the contact of the relay will remain the same as the last status before power off when selecting open the contact will be open while it is closed when selecting closed Parameter object Value of Telegram Switch after bus voltage recovery This parameter will be visible when enabling the logic function input 0 to define the default value of the communication object Switch X after bus voltage recovery which can be 0 or 1 If selecting not write the value 0 is written into the object Telegram Switch and remains until this value is changed via the bus Options not write to write with O to write with 1 Parameter Set the reply mode of switch status for channel X This parameter defines the status of the current switch status when the telegram is sent Options no reply always respond after read only Transmit after change If selecting no reply there is no telegram to send out if selecting always respond after read only the status telegram will not be sent out until receiving the status telegrams from other devices if selecting Transmit after change it will send the status automatically when there is any changes on the output The value 0 or 1 of the communication object reply the switch status x and se
30. econds Note if the function is activated the controller must send the telegram periodically out and the monitoring time must be longer than the internal time of the control telegram Parameter The duty cycle of dynamic regulating during fault This parameter defines the duty cycle of the PWM under the failure mode that is the dynamic action under the failure mode Options Unchange 0 OFF 10 26 34 aaa anaa www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 90 230 100 ON Explanation of the option Unchange the dynamic action of PWM remains the same as before Parameter sending object report fault is This parameter defines whether to send the report out in the failure mode When enabling it it will send the failure report out if there is no action during the monitoring time and then carry out the dynamic action under the failure mode until it is interrupted by other operation It will restart the timing when carrying out the new action Options disable enable The object report fault will be activated when selecting enable The relay will be in the failure mode with 1 while not with 0 Note it will not send the report out with non low priority level And monitor belongs to the low priority level 3 4 3 Parameter window X Forced The function X Forced in Fi
31. ect Safety Priority x x 1 2 during the Control period this Safety Priority x will be initiated It will end the trigger of Safety Priority x when the object Safety Priority x x 1 2 receives the telegram again and the Control period of Safety Priority x will be reset at the same time Option 0 240s It will not activate any Safety Priority x when selecting 0 The monitoring time of Safety priority should be more than double as long as the cyclical sent time of the sensor to avoid the alarming in case some individual signal is neglected 3 3 Parameter window Channel X Switch actuator The parameter window Channel X is shown in Fig 2 3 It works for all the outputs Channel X or X mentioned below means any output of the switch actuator which has the same parameter setup interface and communication objects 12 i aS www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 1 1 6 Switch actuator 4 fold universal All General Channel A CO Channel B R Channel C Channel A work mode is Switch actuator Channel D If bus voltage recovery contact is unchange If bus voltage fail contact is unchange Object value of telegram switch after bus voltage recovery not write Set the reply mode of switch status for channel A no reply
32. elay Table 2 9 general communication objects Dynamic Regulating Actuator 3 6 2 Monitoring function object of Dynamic Regulating Actuator Communication object Number Function Object Type Priority RiIWic T ju ae report fault A 7 report fault regulating A 1 Bit Low ING vv Fig 3 29 monitoring function communication object Dynamic Regulating Actuator No Function Object name Data type Flags 7 report fault regulating X Output X 1bit C R T This object is enabled when selecting enable in the parameter sending object report fault is used to check whether the room thermostat is under malfunction or not It will go into the fault mode with 1 Table 2 10 monitoring communication objects Dynamic Regulating Actuator 44 oS _ ej www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 3 6 3 Forced function communication object Dynamic Regulating Actuator Communication object Number Function Object Type Priority RIWwic T ju mal forced operation A 16 forced operation regulating A 1 Bit Low vv Fig 3 31 forced function communication object Dynamic Regulating Actuator No Function Object name Data byte Flags 16 forced operation regulating X Output X 1bit W C This object will be started when enabling the forced function Start t
33. en Close 3 3 7 Parameter window X Forced The window of the function forced in Fig 2 14 will be visible with enable in the parameter Function of forced for switch is in Fig 2 5 29 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 1 1 6 Switch actuator 4 fold universal All General A Forced Channel 4 Function A Time A Preset Logic amp Scene amp Threshold A Safety Channel B Channel C Channel D Contact position if forced operation unchange Fig 2 14 setup window X Forced This function will be used in some special situation such as emergency and are activated by the object Forced output with the highest priority in the system which means only forced operation are valid in this case Parameter Contact position if forced operation This parameter defines the contact position of the forced operation Options Unchange Open Close 3 4 Parameter window Channel X Dynamic regulating Actuator The window of Channel X Dynamic regulating Actuator in Fig 2 15 will be visible with Dynamic regulating Actuator in Channel X work mode is In the running mode of Dynamic regulating Actuator it is used to control the solenoid valves by a thermostatic controller or temperature sensor to realize the temperature constancy in the
34. eting video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 1 1 6 Switch actuator 4 fold universal All General A Threshold Channel A amp Function E A Time Threshold 1 value amp Preset A Logic Scene Taha Change threshold 1wia object disable Channel B Channel C Behaviour Channel D Threshold 2 value 200 Threshold behaviour without hysteresis If falling below lower threshold contact position unchange If lower lt object value lt upper contact position unchange If exceeding upper threshold contact position unchange Fig 2 12 setup window X Threshold The object Threshold input of 1Byte is enabled when activating the threshold function It will trigger the switch to make one operation if the value of the object Threshold input is lower or more than the default threshold There are 2 individual thresholds are ready to use always and the threshold 1 value is set by the bus Parameter Threshold 1 value Threshold 2 value This parameter defines the value of threshold 1 and threshold 2 Options 0 255 for threshold 1 0 255 for threshold 2 Parameter Change threshold 1 via object This parameter defines whether change the threshold value by bus or not Options disable enable It is able to start the object Change Threshold value I by selecting enable
35. g 2 18 will be visible if selecting enable in the function function for forced is 1 1 6 Switch actuator 4 fold universal All General A Forced Channel A 4 Function f dynamic regulatin amp Monitor per dec pte ae unchange Channel B Channel C Channel D C ox Jl Cancel Jl Default Fig 2 18 parameter window A Forced In this mode the output will be forced to switch to the set position and it has the highest priority The other operations will be ignored in this forced mode which will be activated when the object forced operation 35 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators regulating 1 and ends with 0 Parameter The duty cycle of dynamic regulating during forced operation This parameter defines the value of PWM in forced mode Options Unchange 0 OFF 10 26 90 230 100 ON It will not change the PWM action of the forced operation with Unchange that is the duty cycle of PWM will retain the same current value When it is going back to the normal operation mode from the forced mode that is the forced mode is finished the relay will carry out the same dynamic action as in the forced mode until it is change by the other operation 3 4 4 Parameter window X Regular The window of X Regular in 2 19 will pot out when selecting enable in the pa
36. hannel C 0 240 minutes Channel D 0 59 seconds Delay for switch off 0 240 minutes 0 59 seconds Fig 2 6 setup window X Time Parameter The Mode Of Time function The parameter defines the type of the timing function setup Options Delay switch Staircase lighting Flashing 3 3 1 1 Selection Delay switch The parameter window of the time function in Fig 2 6 will be shown when selecting Delay switch Parameter Delay for switching on 0 240 minutes This parameter defines the stating time of the switch delay minutes Options 0 240 Parameter Delay for switching on 0 59 seconds This parameter defines the starting time of the switch delay seconds Options 0 59 Parameter Delay for switching off 0 240 minutes This parameter defines the closing time of the switch delay minutes 17 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Options 0 240 Switch Actuators Parameter Delay for switching off 0 59 seconds This parameter defines the closing time of the switch delay seconds Options 0 59 3 3 1 2 Selection Staircase lighting function The parameter window of the staircase lighting function in Fig 2 7 will be visible when selecting Staircase lighting function in the parameter The mode of time function 1 1 6 Switch
37. he forced mode with 1 and the other behaviors will be ignored end the mode with 0 Table 2 11 forced function communication object Dynamic Regulating Actuator 3 6 4 Timing function communication object Dynamic Regulating Actuator Communication object Number Function Object Type Priority RJWJC T ju ma switch regularly A 10 Trigger switch regularly A 1 Bit Low vv Fig 3 32 timing function communication object Dynamic Regulating Actuator No Function Object name Data type Flags 10 Trigger switch regularly X Output X 1bit Ww C This object will be started when enabling the timing function to trigger the timing Start the timing function with 1 and stop until time is up with 0 Table 2 12 timing function communication objects Dynamic Regulating Actuator 4 Priority level description There are 5 priority levels for the whole system Switch actuator function Forced gt Safety Priority 2 gt Safety Priority 1 gt common switch Time preset logic scene threshold from highest priority to lowest Dynamic regulating switch function Forced gt Safety Priority 2 gt Safety Priority 1 gt monitor PW M continue on off switch regularly from highest priority to lowest Only the higher priority behavior can interrupt the lower priority behavior 45 aa ana nai www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8
38. le The relevant setup interface will appear when selecting enable 3 4 2 Parameter window X Monitoring The monitor function in Fig 2 17 X Monitoring will be shown when selecting enable in the function function for monitoring is 33 E www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 1 1 6 Switch actuator 4 fold universal All General A Monitor Channel amp Function Cyclic monitoring 60 in minutes 0 240 minutes Channel B _ Channel C in seconds 0 59 seconds 0 Channel D The duty cycle of dynamic regulating during fault unchange sending object report fault is disable Fig 2 17 parameter window X Monitoring Parameter Cyclic monitoring in minutes 0 240 minutes in seconds 0 59 seconds This parameter defines the time that the relay monitors the telegram Generally speaking the room thermostatic controller will send the control telegram to the bus in a certain time If the bus cannot receive the telegram in that time it will be judged that the controller goes out of order During the set time the bus cannot receive the telegram for the controller the relay will start the failure mode automatically until receiving a new telegram The monitor time will be recounted when receiving a new control telegram Options 0 240 minutes 0 59 s
39. meter function of safety operation is in Fig 2 16 1 1 6 Switch actuator 4 fold universal All General A Safety Channel A 4 Function ter window G A Monitor Setting of safety on parameter window General AForced The duty cycle of dynamic regulating A Regular during safety 1 operation The duty cycle of dynamic regulating Channel B during safety 2 operation Channel C Channel D unchange unchange Fig 2 20 Parameter window X Safety There are 2 Safety Priority x x 1 2 in the parameter window All General The parameter defines the dynamic action of the triggered relay per output There are 2 individual Safety Priority x x 1 2 for every output and Safety Priority 2 is prior to Safety Priority 1 That is even if Safety Priority 1 is triggered at the 37 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators same time with Safety Priority 2 the contact position will follow the instruction of Safety Priority 2 The priority of the safe operation function is only lower to the forced operation function in the system Parameter The duty cycle of dynamic regulating during safety X operation x 1 2 This parameter defines the duty cycle of PWM in the safe operation mode Options 0 ON 10 26 90 230 100 OFF Unchange Explanation of the option U
40. mported is required for EST3 software It is able to switch from 4 to 12 independent electrical AC loads or three phase loads by the switch actuators with maximum output of 16A per output and manual switch as well as visible switching status There are same following programming functions for each output time function on off delay staircase function with the warning and adjustable staircase lighting time scene preset control 8bit 1bit logic operation AND OR XOR gate function gt gt gt gt gt status response gt forced operation and safe function gt threshold function setup gt control of electro thermal valve function gt selection of preferred status after bus voltage failure and recovery 3 a aa a aa aaa aaa a www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 2 Technical Properties amp Dimension and Connection Diagram 2 1 Technical Properties The switch actuators are modular installation devices in proM design which are easy to install in the distribution boards on 35mm mounting rails via bus connection terminal to connect to EIB KNX system It is able to switch at most 12 individuals outputs by these switch actuators and the loads are connected to them by using screw terminals in groups of 2 contacts and each output is controlled separately by EIB KNX system Power supply Output nominal v
41. n maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 1 1 6 Switch actuator 4 fold universal All General Channel Function 1 gt channel is assigned to A Time 1 64 scene ND 0 no allocation A Preset 6 A Logic Standard output value is A Scene 2 gt channel is assigned to Channel B 1 64 scene ND 0 no allocation Channel C Channel D Standard output value is 3 gt channel is assigned to 1 64 scene ND 0 no allocation Standard output value is 4 gt channel is assigned to 1 64 scene ND 0 no allocation Standard output value is 5 gt channel is assigned to 1 64 scene ND 0 no allocation Standard output value is Fig 2 11 parameter window X Scene Parameter channel is assigned to 1 64 scene NO 0 no allocation It is able to allocate 64 different scene numbers to every output There are 5 various scenes can be set per output Options Scene 1 Scene 64 O no allocation Parameter Standard output value is This parameter defines the switch output status when invocating the scene Options ON OFF 3 3 5 Parameter X Threshold The window in Fig 2 12 will be shown up when selecting enable in the parameter Function of threshold for switch is in Fig 2 5 26 aa aana ii www video star com cn mak
42. n switching off the staircase light function seconds Options 0 59 Note If the minute is set to 0 and the seconds is set to 07 the staircase lighting will be disabled Parameter The mode of control for Staircase lighting is This parameter defines the mode of the staircase lighting function Options Start with 1 stop with 0 Start with 1 no action with 0 Start with 0 1 cannot be stopped When selecting Start with 1 stop with 07 it will switch on the staircase lights with the value I received by the object Output of staircase lighting it will stop the time counting operation and don t change the contact position until changed by other operations with 0 When selecting Start with 1 no action with 0 it will switch on the staircase lights with the value received by the object Output of staircase lighting and no reaction with 0 When selecting Start with 0 1 cannot be stopped it will switch on the staircase lights either with 0 or 1 received by the object Output of staircase lighting but cannot end it by the object Parameter During the lighting time if receive the start telegram Options restart duration of staircase lighting Ignored the switch on telegram It will restart the staircase lights to redo the timing if receive the telegram of the object Output of staircase lighting
43. nchange It will stay the same dynamic action of the PWM when carrying out the safe mode that is the duty cycle of PWM remains current status During the monitoring time of safe mode can be set in the parameter window Fig 2 2 it will restart to count the time from the second cycle when it is interrupted by force And then enter into the safe operation mode after the safe operation monitoring time in this cycle When it is going back to the normal operation mode from the safe operation mode that is the safe operation mode finishes the relay will keep the dynamic action under the safe operation that is the duty cycle of PWM stays the same until interrupted by other operations 3 5 Communication object Switch Actuator The communication object is a media that the bus talks to the other devices that means only communication object can have the right to communicate to the bus More details will be described below 3 5 1 Communication object All General There are 3 objects in All General which plays important role in the regular switch actuator and the dynamic regulating switch See in Fig 2 21 and functions are shown in Table 2 1 no C R W T U Group addresses cH General 0 vy y In operation 1 Bit oH General 1 y y vy safety priority 1 1 Bit Ed General Pi s v v safety priority 2 1 Bit Fig 2 21 communication object All General 38 www video star com cn maketing video star com cn Tel 8620
44. nd the switch status X defines the current status of the relay which can be set in the parameter Object value of switch status when selecting always respond after read only or Transmit after change Parameter Object value of switch status Options O contact close 1 contact open O0 contact open 1 contact close This parameter will be visible when selecting always respond after read only or Transmit after change in Set the reply mode of switch status for channel X It means the contact of the relay will be closed when the 14 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators value of the communication object reply the switch status x and send the switch status X is O when setting 0 contact close 1 contact open while it is open when the value is It means the opposite with setting O contact open 1 contact close Parameter Contact position if tele Value is 1 0 is opposite of 1 if changed This parameter defines the contact position when starting the switch which will be triggered by the communication object switch X When enabling input 0 in the logic function it will use the communication object switch X to modify the value of input 0 rather than triggering the switch operation Options unchange Open Close The
45. ndition to each Safe priority and also enable the correspondent communication object Safety Priority x x 1 2 These objects are important to the entire relay when under the working mode Switch Actuator and Dynamic regulating actuator but each output can react differently depending on the received telegrams whose reactions can be defined in the parameter window X Safety Options inactive enable be safe by Object value 0 enable be safe by Object value 1 If the communication object Safety Priority x receives 0 the Control period of the Safety Priority x will be initiated with enable be safe by Object value 07 if the communication object Safety Priority x receives J the Control period of the Safety Priority x will be initiated with enable be safe by Object value 17 This means during the Control period if the object Safety Priority x receives no corresponding telegram it will trigger Safety Priority and then the correspondent action will be initiated which will be defined in the parameter window X Safety When the setting is inactive it will not initiate any Safety Priority Parameter Control period of safety priority X X 1 2 1 240s 0 inactive It will not be visible unless the parameter set safety priority x x 1 2 is activated If there is no telegram received from the obj
46. object Switch and define the contact position after flashing Parameter Delay for switch ON Min 0 65 535 Sec 1 59 The parameter defines the delayed time to switch on the output when flashing 20 SS St www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators Options 0 240 minutes 0 59 seconds Note it will not be executed unless the time is lower than the relay threshold switch frequency Since there will be not sufficient energy to do it because of the frequent relay switching and it may cause the time delay The same situation will happen after the bus voltage recovery Parameter Delay for switch off Min 0 65 535 Sec 1 59 The parameter defines the delayed time to switch off the output when flashing Options 0 240 minutes 0 59 seconds Note it will not be executed unless the time is lower than the relay threshold switch frequency Since there will be not sufficient energy to do it because of the frequent relay switching and it may cause time delay The same situation will happen after the bus voltage recovery Parameter Number of ON impulses 1 255 O no limited This parameter points out the flashing times Options 0 255 Note 0 means no limited Parameter Contact position after flashing This parameter points out the relay contact position after flashing Options unchange Open Close
47. only invocate the preset value but also save the new value of the current switch status by the bus There are 2 objects to invocate and save the preset value and 2 optional preset values preset 1 and preset 2 It means preset 1 with 0 and preset 2 with 1 Parameter Action for preset 1 object value 0 This parameter defines the relay status when invocating the preset value 1 that is when the object Call preset 1 2 receives the telegram 0 by setting the communication object Call preset 1 2 Options None ON Off Parameter Action for preset2 object value 1 This parameter defines the relay status when invocating the preset value 2 that is when the object Call preset 1 2 receives the telegram 1 by setting the communication object Call preset 1 2 22 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators Options ON OFF Last position of contact Setting of preset 1 When the action trigged by Preset 2 selects last position of contact it will be recovered to the last switch status every time recalling preset 2 When the action trigged by Preset 2 selects setting of preset 1 it will carry out the set parameters of the action trigged by preset 1 every time recalling preset 2 Parameter Setting for preset via telegram is It is used to set whether changing the prese
48. ram 2 2 1 KA R 0416 1 2 2 1 1Dimension drawing www video star com cn one 16A 250V maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 2 2 1 2Connection Diagram L1 L2 L3 16A 1P AC230V 2 2 2 KA R 0816 1 2 2 2 1 Dimension drawing E E oO oa EIJ KNR CE www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 Switch Actuators GVS K BUS KNX EIB 2 2 2 2 Connection Diagram i L2 L3 16A 1P AC230V 2 2 3 KA R 1216 1 2 2 3 1 Dimension drawing A E pl BUS mote Hoge Anad 90 0 mm EIJ KNR CE ee T Tel 8620 39338986 Fax 8620 39338465 www video star com cn maketing video star com cn GVS K BUS KNX EIB Switch Actuators 2 2 3 2 Connection Diagram 16A 1P 16A 1P coco LELARA aac oana 16A 250V 16A 1P AC230V A 3 Commissioning 3 1 Overview Every output has two operation modes main function Switch actuator It is used for normal switching for instance lighting control which uses the object Switch to control the output directly Lots of additional functions such as timming logical safety functions are available to use Application description can be found in below text Dynamic regulating Actuator
49. rameter function for regular switch is 1 1 6 Switch actuator 4 fold universal All General A Regular Channel A Function Time of switch regular in minutes 10 Momitor 0 255 amp Forced ae Automatic switch regularly disable Channel B Channel C Channel D Fig 2 19 parameter window X Regular This function can be used to avoid the device s malfunction because of the dust deposits in the valve area which plays a very important role when in the long Unchange switch status This function can be started by the 36 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators object Trigger switch regularly or internally Parameter Time of switch regular in minutes 0 255 This parameter defines the time span when the regular switch carry out one action and whose unit is minute Options 0 255 Parameter Automatic switch regularly This parameter defines the time interval of starting the automatic regular switching Options disable one times per day one times per week one times per month It will start the time counting of the automatic regular switch function if there is no operation on the relays and recount as long as the relays have operation 3 4 5 Parameter window A Safety The parameter window X Safety in Fig 2 20 will pop out when selecting enable in the para
50. s power off Options Unchange Close Open The above setting will be valid only when the relay has sufficient energy after the bus voltage off Parameter If bus voltage recovery the duty cycle of dynamic regulate This parameter defines the status of the switch actuator when the bus power is on which will last until receiving the control command or into a failure mode Options 0 OFF 10 26 100 ON Parameter PWM cycle time for continuous control minutes 1 240 minutes and PWM cycle time for continuous control seconds 0 59 seconds It is able to set the period of the pulse width control PWM in this parameter and whose unit is minute and 31 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators second Options 0 59 seconds 1 240 minutes Note it is suggestive to set longer period in the parameter to protect the relays and the controlled devices Under the Ibit control mode the pulse width control PWM is only valid in the malfunction force operation mode safe operation mode and after voltage recovery Parameter Control telegram is received as This parameter defines the control mode of the output as a dynamic regulating actuator Options 7 bit on off control 1 byte continuous In the control mode of bit the function of the dynamic regulating actuator is as the same as the common switch ac
51. t 2 after bus voltage recovery Fig 2 10 setup window X Logic There are 2 logic communication objects to decide the status of individual output which are related to the Switch X It will re operate when receiving a new object value as the final output status close the contact with J open it with 0 The values of the communication object Input 1 of logic makes logic operation with Switch X firstly and then the result after that will makes operations with the value of Input 2 of logic This operation will ignore the objects which are unable and continue to the next step with the ones who are enabled Parameter The input 0 switch object for logic is This parameter is used to enable the function of logic operation of input 0 whose values are wrote by the object Switch X Options disable Enable Parameter The input x of Logical x 1 2 This parameter describes the status of the logic operation of the object Input 1 of logic or Input 2 of logic Options disable Enable 24 oS ji www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators Parameter Function type between input 0 and input 1 input 2 and input 0 1 This parameter introduces the logical relationship of the logic operation providing 3 standard logical operations AND OR XOR and a
52. t value by the bus It is allowable to change the value and enable the object Set preset 1 2 at the same time when selecting enable which can save the current status as the new preset value The current value is saved as new preset 1 when receiving the telegram 0 as new preset 2 when 1 The current status will be saved in the new preset value if selecting None in Action for preset 1 object value 0 and Last value of channel or restore parameterized value of preset 1 in Action for preset2 object value 1 Options enable Disable Note it will save the new preset value after bus voltage recovery 3 3 3 Parameter window A Logic It will show up Fig 2 10 when selecting enable in Function of logic for switch is in Fig 2 5 23 aaa a a aan a www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators 1 1 6 Switch actuator 4 fold universal All General A Logic Channel amp Functi A Sih ii The input 0 switch object for logic is enable A Preset A a Tia kani akah EEN Channel B Function type b i at type between input0 and Channel C inputt AND Channel D Result is inverted NO Value of input 1 after bus voltage g recovery The input 2 of logic is Function type between input2 and inputO 1 Result is inverted Value of inpu
53. tuator the thermostatic room controller control the output by the common switch command When the controller goes out of order and the relay receives no control signal the relay will action automatically by using PWM with duty cycle of 50 In the control mode of byte the sending value of the room thermostatic controller is from 0 to 255 corresponding from 0 to 100 which is so called continuous action control 0 means switch off the valve and 100 to switch it on It will adjust the output control by the duty cycle of the pulse Note in the function of dynamic regulating actuator it will recalculate the duty factor of the pulse every time receiving the telegram of continuous regulating And it will recalculate the time by switching the contact to the Opposite position Parameter reply the status of channel for continuous control It is visible when selecting 1 byte continuous in the parameter Control telegram is received as which is used to report the status of the controlled valve gate with 2 options according to the type of the controlled devices 1 bit and 1 Byte Options nothing yes 0 0 otherwise 1 1 bit yes 0 1 otherwise 0 1 bit yes continuous control value 1 byte Parameter Reply the status of contact state It will send the switch status out when receiving the telegram that the channel status is read by other devices Options nothing Yes 1
54. uggested to select the maximum time interval according to the application to keep the bus load as low as possible Note it is starting to count the time after power up instead of the operation delay after recovery of bus voltage Parameter Enable Safety priority function The parameter is used to set the enable status of the function Safety priority Options Enable Disable If disable is selected it will not activate the function Safety priority if enable is selected 2 Safety priority will be activated whose parameter window can be shown in Fig 2 2 1 1 6 Switch actuator 4 fold universal All General All General Channel A Channel B Operation delay after recovery of bus Channel C voltage 1 250s Channel D Sending cycle of In operation telegram 1 240s O inactive Enable safety priority function set safety priority 1 inactive senget safety priority 2 inactive T switch on O switch off N Normal object value map switch on off switch on contact close switch off contact open Cancel Default Fig 2 2 parameter window Safety priority Parameter set safety priority x x 1 2 11 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators There are 2 safety priorities for selecting It is available to define the trigger co
55. ulating X Output X 1bit W C This object will be enabled when selecting Ibit on off control in the parameter Control telegram is received as to receive the command of 1bit off with 0 on with I 13 Status continuous 1 byte X Output X 1Byte R C T This object will be enabled when selecting yes continues control value Ibyie in the parameter Reply the status of channel for continuous control indicating the running status of the current valve and the duty cycle of PWM 5 Status continuous 1 bit X Output X Ibit R C T This object will be enabled when selecting yes 0 0 otherwise 1 1 bit or yes 0 1 otherwise 0 1 bit in the parameter Reply the status of channel for continuous control indicating the running status of the current valve When selecting yes 0 0 otherwise 1 1 bit the valve will be off with 0 others with 1 selecting yes 0 1 otherwise 0 1 bit the valve will be off with 1 others with 0 Reply status of contact X Output X 1bit C R T we coe This object will be enabled when selecting contact close 0 contact open or yes 0 contact close 1 contact open in the parameter Reply the status of contact state indicating the contact position of the current r
56. working of various relays excluding the initialization time approx 2 seconds of the device Options 1 250 seconds If there are other devices e g monitor require to read the communication target value of the relay during the delay time after power on then this requirement will be recorded and then reacted after the delay time is finished If the delay time is long enough all contacts of the relay can work simultaneously Note the first switching action will only be initiated when enough energy is available to trigger all contacts to react after electrified This means it will take some time for the first switching action after electrified but the telegram will be sent immediately after electrified Considering that it will also generate damage to the power system and bus so it is suggested to set the different delay time to each device Parameter Sending cycle of in operation telegram 1 240s 0 inactive The parameter determines the time interval to send the telegram which shows the actuator is working 10 E www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Switch Actuators normally or not via the bus With the setting 0 the actuator doesn t send the telegram if the setting is not 0 a telegram with the value 7 will be sent cyclically according to the setting to the bus Options 0 240s 0 cyclical send inactive It is s