Home
        PU1000/PU600 Installation manual
         Contents
1.     LED is lit when the output voltage is  approximately 15  higher or 10  lower than  nominal output voltage  When the output voltage is  normal  the relay contact is in the position printed  on the front panel     5 2 Over temperature   All models have thermal protection  If the converter  is overheated it reduces its maximum output power   The    OVER TEMP    LED is lit and the alarm relay  is set to alarm  This will not occur in normal  operation with an ambient temperature below   55  C when the unit has sufficient cooling  The  converter is convection cooled and there should be  a minimum of 30 50mm of free space at upper and  lower parts of the converter  If this is not possible   we recommend the use of an external fan     Note that the expected life of the converter is  dependant on converter temperature  For every  10  C that the temperature is decreased the expected  life is approximately doubled  It is therefore crucial  to cater for good ventilation and if possible reduce  ambient temperature     6 Sense    6 1 External sense   External sense is used when voltage regulation at  the load is critical  The converter regulates the  voltage at the load and not at the output of the  converter and does thereby compensate for voltage  drop in the cables between the converter and the    10229 15 doc  Page 7  10     POLYAMP  LAL      INSTALLATION MANUAL    load  The maximum voltage compensation is 5  of  nominal output voltage     Do not disconnect the negative power conne
2.   BNE eas Bo EERE Beak BEERS 10    10229 15 doc  Polyamp AB  Sweden www polyamp com Page 3  10     POLYAMP  i      INSTALLATION MANUAL    1 Before installation    On the front panel label the following is displayed   Converter type  input voltage range  nominal output  voltage  serial number  options  article number   isolation voltages and ambient temperature range   The converter type name consists of model name  PU1000 or PU600 followed by input code and  output voltage  Two examples     e              PU1000 110 48    has input code    110     and nominal output voltage 48Vd c     e              PU600B24    has input code    B    and  nominal output voltage 24Vd c     Input  output and case are galvanically separated  from each other  You can thus choose how you  want the system connected     The input is protected against reverse polarity by a  parallel diode at the input on models with input  code 24  48  72  A  B and C  This diode  however   is only intended to blow an external input fuse  110   220  440 and D input codes have an inrush current  limit thyristor  which also works as a series diode     The input shall be fused with an approved fuse with  a slow blow characteristic and high breaking  capacity  See table 1     PU1000 input fuses  Time delay fuse    Input voltage code          PU600 input fuses  Input voltage code Time delay fuse  A 80 A  B 50    C 20       10      Table 1  Recommended input fuses     There are two reasons we do not include the fuse     1  
3.  E E OTO EEE OTA E A 8  8 OUTPUT OVER VOLTAGE PROTECTION        eseessecessseessccecsseceessecesssecssoceesseceesecsscoeesseceesseceessecsssseessoceesse 8  9  INRUSH CURRENT LIME visa iscesccscscecssessieeactaestcasiacteoscudestcasesogsvacsbeatessessecadeassasesscsesedessdasseassesdeescedvascasedeesosss 8  10 ISOLATION VOLTAGE TEST  sssssssessstsossvecsesssvecsssesensesvnsesisonssessevensessesvasesdescsdevisccssesessecseseossssabiosesecsoosssee 8  10 1 DC ISOLATION  TEST OUTPUT TO CASE s                             8  10 2 DC ISOLATION TEST INPUT TO OUTPUT AND INPUT TO CASE      ccccccececececececececececececececececececececececececeeeeeeeeess 9  10 3 AC ISOLATION TEST INPUT TO OUTPUT AND INPUT TO CASE      ccccccecececececececececececececececececececececececececeeseesecs 9  11 TROUBLE SHOOTING i essscssesscssssevssscvssccsestsccseevscsesvectecssacceeseebessssusdeccedectesessssessbsoessssubscssedsssesseutenccoseseiossense 9       THERE IS N   OUTPUT                                                                      9  11 2 THE INPUT FUSE BLOWS WHEN THE INPUT IS CONNECTED         cccccececececececececececececececececececececececececeeseececeeecs 9  11 3 THE CONVERTER STARTS AND STOPS REPEATEDLY       ccccccecececececececececececececececececececececececececececececececececcs 10  11 4 THE CONVERTER STOPS AFTER SEVERAL HOURS     ccccccecececececececececececececececececececececececececececececececececececececs 10  11 5  FAULT REPORT        bs duces          bas Bo eis Beck      
4.  a short circuit    e If there is an external short circuit  remove  1t    e Ifthe load is too large decrease the load or  consult your Polyamp dealer    4  Check that the     INHIBIT    input is not short   circuited  See 7 Inhibit on page 8    5  Check that the     SENSE    is connected correctly   See 6 Sense on page 7    6  The unit is broken  Contact your Polyamp  dealer     11 2 The input fuse blows when the  input is connected  1  Check that the input voltage polarity is correct   2  Check that the input fuse is of time delay type  and with correct current rating  See Table 1     10229 15 doc  Page 9  10     POLYAMP  LAL       INSTALLATION MANUAL    Some models have    inrush current limit     Fore  further information consult 9 Inrush current  limit on page 8    2  The unit is broken  Contact your Polyamp  dealer     11 3 The converter starts and stops  repeatedly    All models have an over under voltage protection  which shuts down the converter if the input voltage  is not within specified limits  see front label      1  The cables to the converter input may be under   sized  causing too high voltage drop in the  supply cables    2  Your supply does not have enough current  capacity so the input voltage to the converter  drops below specified limit     11 4 The converter stops after several  hours   If the red    gt OVER TEMP    LED is lit  the unit has   not sufficient cooling or the ambient temperature is   to high  See 5 2 Over temperature on page 7 for   further
5.  information     11 5 Fault report    We suggest that you return a faulty converter to     POLYAMP AB  Box 229   Backgatan 10    597 25   TVIDABERG  SWEDEN    Tel   46 120 85400  Fax   46 120 85405    or to your local Polyamp distributor     To help us locate the fault  please describe the fault  and how and when it occurred     Polyamp AB  Sweden www polyamp com    10229 15 doc  Page 10  10     
6. DC networks should be fused at the distribution  point to protect the cable    2  Different applications require different types of  fuses    If the converter is mounted in an electric vehicle  an   external series diode on the input is recommended    Please contact your Polyamp dealer     Polyamp AB  Sweden    www polyamp com    If the converter supplies a DC motor  we  recommend an external parallel diode at the motor  poles to protect against reverse voltages     For the disconnection ability  an external  disconnection device  which is able to disconnect  both polarities  shall be incorporated with the input  power supply cord  The disconnection device must  be properly labelled and easy accessible     2 Installation    The converter shall be mounted in an enclosure   which meets the demands of EN60950 regarding  fire  voltage hazard and mechanical strength     The converter is supplied with mounting brackets   With these you can mount the converter in any  direction  The converter is convection cooled and  in order to get sufficient cooling there shall be a  minimum of 30 to 50 mm space at upper and lower  parts of the converter  If this is not possible  we  recommend the use of an external fan     Note that the expected life of the converter is  dependant on converter temperature  For every  10  C that the temperature is lowered the expected  life is approximately doubled  It is therefore crucial  to cater for good ventilation and if possible to  reduce ambient temperat
7. POLYAMP  LAL pu1o0PU60 INSTALLATION MANUAL    PU1000 PU600  Installation manual    fae geome or tOO       out 6    pas r a Bg          Schulz Y Electronic    Schulz Electronic GmbH  Dr  Rudolf Eberle Stra  e 2  D 76534 Baden Baden    Fon  49 7223 9636 0  Fax  49 7223 9636 90    vertrieb schulz electronic de  www schulz electronic de    10229 15 doc  Polyamp AB  Sweden www polyamp com Page 1  10     POLYAMP  ueu pu1o90Pu60o INSTALLATION MANUAL    Warranty  All Polyamp DC DC converters are warranted against defective material and  workmanship  This warranty is valid for 24 months from the date of delivery   We will repair or replace products which prove to be defective during the  warranty period  The warranty is valid only if the converter is used within  specification     Manual    This manual is as complete and actual as possible at the time of printing   However  the information may have been updated since then  Polyamp AB  reserves the right to make changes in this manual without notice     The exclamation point within an equilateral triangle is intended to alert the user to presence of important  operating and maintenance instructions in the literature accompanying    The lightning flash with arrowhead  within an equilateral triangle  is intended to alert the user to presence of  uninsulated    dangerous voltage    within the products enclosure that may be of sufficient magnitude to constitute  a risk of electric shock to persons    Caution   To prevent the risk of electr
8. Turn the V ADJ potentiometer approximately  one  1  turn counter clockwise on all converters  but one  This will not affect the output voltage  yet    2  Turn the V ADJ potentiometer counter  clockwise on the remaining converter  if your  load current exceeds 5  of the total rated    current  this should be the only unit with the          MASTER    LED lit  until you reach the output  voltage you desire   If you turn more than one     1  turn counter clockwise you must repeat from    step 1     3  The other units should now also be adjusted to  approximately the same output voltage   Otherwise the output voltage will drop if the    master converter breaks down  Turn clockwise  on the V ADJ potentiometer on the other units  slowly until the   C  MASTER    LED is lit or  almost lit     4 Multiple loads at the output    If you are using several loads  we recommend  fusing them separately with fast acting fuses on the  positive output branch  Some considerations  regarding short circuits should be taken  See below     4 1 Short circuits    1     If there is a short circuit in one branch and the  total current in all branches does not exceed  105  of the nominal current of the converter   see label on front panel   the output voltage  will not be affected  The time for the fuse to  blow can be calculated from the data sheet of  the fuse if you know the short circuit current  trough the fuse     If there is a short circuit in one branch and the  total current in all branches does e
9. ction  from the converter to the load before the positive   when the converter is running and external sense is  used  This might damage the converter and it is also  not advisable for Your own protection to make  adjustments in the installation with voltage applied     1  Remove the jumpers from the sense inputs at  the removable connector    2  Connect a twisted pair  0 25mm   1 5        between the sense terminals of the converter    and the load  see Figure 4  The sense leads and  the power cables shall be of approximately the  same length and drawn as close to each other as  possible  Beware of correct polarity              5  51 52 53 54 55 56    Figure 5  Feature contact     6 2 Internal sense   If external sense is not used  the jumpers shall be  connected between     SENSE               V            between     SENSE    and     V     as they are at  delivery  The converter then regulates the voltage at  its output screw terminals     7 Inhibit    The converter is shut down if the inhibit input is  short circuited by a relay or an electrical switch   The current through the short circuit is 20mA  Note  that there is no electrical isolation between the  inhibit and the output     Polyamp AB  Sweden       www polyamp com    1  Use a twisted pair  0 25mm   1 5mm   with a  maximum length of 3 0m for connection of the  inhibit     8 Output over voltage protection    All models are equipped with an internal output  over voltage protection circuit  OVP   It consists of  an a
10. dditional voltage regulator operating in parallel  with the main regulator  The output voltage is  limited to approximately 15  above the nominal  output voltage  As long as the OVP circuit is active  the alarm relay is set to     ALARM    state and the red          NOT OK    LED is lit     9 Inrush current limit    Models with input codes 110  220  440 and D are  equipped with    inrush current limit    feature  The  input capacitors are charged through a resistor to  reduce the input current during start up  When the  converter starts this resistor is shunted by a  thyristor  which also acts as a series diode     All models have a    slow start    feature  To reduce  input current during start up the output capacitors  are charged    slowly     approximately 0 15      10 Isolation voltage test    Each converter has been isolation tested in factory  before delivery see Table 2  Warning  An  isolation test shall only be performed by  personnel aware of the dangers and hazards of  the test     Input Isolation  Output   Isolation  code In out  voltage   out case  In case Vd c     24 48   2 0kVd c   72          110  220   2 5kVa c   440 C  D    Table 2  Isolation voltages on different  converters           10 1 DC isolation test output to case   1  Disconnect all cables from the converter    2  Connect the input terminals of the converter to  case    3  Connect the output terminals together    4  Connect your isolation tester between output  and case  See Figure 6  Raise the vol
11. e reason breaks down  another  converter automatically becomes    current master        To achieve good power sharing  the voltage drop  between the minus poles must be kept as low as  possible  see Figure 1  The plus poles can either be  connected as in Figure J or have separate cables to  the load     At light load  if the total load is less than 5  of the  total rated power  the yellow   C  MASTER    LED  might flicker between the units  As the load  changes different units   C  MASTER    LED might  be lit  All this is normal     10229 15 doc  Page 5  10     POLYAMP  a      gt  bani INSTAL EATON MANDAT       Figure 1  Current share connection with series  diode     3 3 Voltage adjustment with current    sharing  The converters must be running with 5  of nom   load or more  and the    current share    must be  connected  If each converter output voltage is  adjusted to the same voltage  which they are at  delivery  the yellow        MASTER    LED might be  lit on most units     To increase the output voltage     1  Choose a unit where the      MASTER    LED is  lit  Turn the V ADJ potentiometer clockwise  until you reach your desired output voltage    2  The other units should now also be adjusted to  approximately the same output voltage   otherwise the output voltage will drop if the  master converter breaks down  Turn the V ADJ  potentiometer slowly clockwise on the other  units until the   C  MASTER    LED is lit or  almost lit     To decrease the output voltage     1  
12. ic shock  do not open enclosure  No serviceable parts inside  Refer servicing to  qualified service personnel only    10229 15 doc  Polyamp AB  Sweden www polyamp com Page 2  10     POLYAMP  LAT              _pu1o90PU600 INSTALLATION MANUAL    CONTENTS    1 BEFORE INSTALLATION                                                             S raiti iS aS 4  2  INSTALLATION      ateo                                           4  3 PARALLEL CONNECTION       eseesseceessecesssecssccecssoceessecescsecsscceesseceessessccsecsscccesseceesoecsssseesscceesseceessseesssseesseceesse 5  32 1    SERIES DIODE ON THE OUTPUT ontran anan a Or E E E E E        5  322 CURRENT SHARING C AEE A EEEE EE E EE EE 5  3 3 VOLTAGE ADJUSTMENT WITH CURRENT SHARING          s seserererererertrtrtrtrtrtrtrtrtrtrtttrtrtrtrtrtrertrerererererererererere 6  4 MULTIPLE LOADS AT THE OUTPUT       e sseeessececssecesssecsscceessececssecsssseesscceesseceessecesscessoceesseceesseesscseessoceessee 6  4 1 SHORT CIRCUITS Sn 6  E  S A EEA TA E S O E EER E EEEO T 7  5 1 OVER AND UNDER VOLTAGE ALARM     cccccccccccccccccecececececesesesesecesecesesesesscesesesesesecssssssessescssssaseceseuseseeesseuseaeanaes 7  5 2 OVER TEMPERA TURE                   e neh aes eas 7   I aI ETA E E T E EEEE E E E E A 7  6 1 EXTERNAL SENSE  u  cccccccccccccccccccccscceccscsesesesesesesesesesesesesesesssesesssssesesesssesecesscesesssasesesesscesscssesasasessssusesseseseseeeuaes 7  6 2  DNH N EA ANS ERI INR          EA E E E 8  anA A E E E E E E O E
13. olyamp com    If your isolation test equipment cannot supply this  current  you can perform a DC isolation test with  4000Vd c  2500V x V2 x 1 1  4000Vd c where  1 1   safety factor   Follow the instructions in 0  10 2 DC isolation test input to output  and input to case above but test with 4000Vd c   instead of 2000Vd c  The leakage current should  not exceed 5         AC isolation test     Disconnect all cables from the converter     Connect the output terminals of the converter to  case  See Figure 7    3  Connect the input terminals together    4  Connect your isolation tester between input and  case  See Figure 7  Raise the voltage of the  isolation tester from 0 to 2500Va c  The voltage  should not be applied for more than one  1   minute or the Y capacitors might be damaged    5  Turn off the isolation tester and discharge the   test voltage with a 10 MQ resistor between   input and case     Ne    11 Trouble shooting    11 1 There is no output voltage   1  Check that the input fuse is not broken    2  Check that the input voltage polarity is correct    3  Check that the input voltage is within the  specified limits  see front label    4  If the red         NOT OK    LED is lit  the  converter may be in current limit due to  excessive output current or an external short   circuit on the output    e Disconnect the input    e Disconnect the load    e Connect the input again and measure the  output voltage    If the converter now starts the load was too  heavy or there was
14. tage of the  isolation tester from 0 to 2000Vd c  Check that    10229 15 doc  Page 8  10     POLYAMP  LAL      INSTALLATION MANUAL    the leakage current does not exceed 5uA  The  voltage should not be applied for more than a  few seconds or the Y capacitors might be  damaged    5  Turn off the isolation tester and discharge the  test voltage with a 10 MQ resistor between  output and case                             Figure 6  Output to case isolation voltage test     10 2 DC isolation test input to output    and input to case     Disconnect all cables from the converter    2  Connect the output terminals of the converter to  case    3  Connect the input terminals together    4  Connect your isolation tester between input and  case  See Figure 7  Raise the voltage of the  isolation tester from 0 to 2000Vd c  Check that  the leakage current does not exceed 5uA  The  voltage should not be applied for more than a  few seconds or the Y capacitors might be  damaged    5  Turn off the isolation tester and discharge the  test voltage with a 10 MQ resistor between  input and case             Figure 7  Input to output and input to case  isolation voltage test     10 3 AC isolation test input to output  and input to case  You can also test 2500Va c  for one  1  minute    between input to output and case on units with  input codes 110  220  440  C and D     Beware of the rather high capacitive earth  currents  about 100mA  that will occur during  this test     Polyamp AB  Sweden    www p
15. th your external input  disconnection device    Beware of hazardous voltages    e The output voltage can be adjusted  10  to   5  of nominal output voltage with the  potentiometer marked V ADJ on the front  panel  Clockwise turn increases the output  voltage  The potentiometer has 15 turns  If  you are using current sharing  the procedure  of adjusting the output voltage is described  in3 3 Voltage adjustment with current  sharing on page 6      Replace plastic cover    6  When the converter is disconnected  switch off  the input voltage with the disconnecting unit   Disconnect the input cables first  then output  and last the protective case connection             3 Parallel connection    If a redundant power supply system is requested   two or more converters can be connected in  parallel  To achieve redundancy the number of  converters must be dimensioned to carry the whole  load even if one converter is faulty  Connect your  load to the   output after the series diode  see  Figure 1     Another reason for connecting two or more  converters in parallel is to get more power  Use the  output with series diode  see Figure 1     You should not use external sense when the unit  are in parallel on the output     3 1 Series diode on the output   The series diode protects the converter output from  external voltage sources  A series diode is  necessary if the output is connected in parallel with  another power supply or if you require redundant  operation  If a converter breaks do
16. ure     To meet the EMC specifications in the enclosed   declaration of conformity    use twisted pairs for  connecting input  output  alarm  inhibit and voltage  sense  Shielded cables are not necessary     1  Remove plastic cover    2  Connect protective earth to the connection  marked no 40  Use a ring terminal that has been  crimped by an appropriate tool    3  Connect the output  The converter output is  short circuit proof by a constant current limit  which works unlimited in time  Therefore there  is no need to fuse the load  unless you use  multiple loads  see below   The current limit is  fixed to 105  of nominal output current    e If the converter is to be connected in parallel  at the output or if you use current sharing for  equal current sharing  please consult 3  Parallel connection on page 5    e If you intend to use multiple loads  please  consult 4 Multiple loads at the output on  page 6    e If you intend to use the alarm  please consult  5 Alarm on page 7    e If you intend to use output voltage sense   please consult 6 Sense on page 7    e If you intend to use inhibit  please consult 7  Inhibit on page 8     10229 15 doc  Page 4  10     POLYAMP  LAL        INSTALLATION MANUAL    4  Connect the input cables  Bundle input cables  together at the terminals separated from the output  cables  Make the same arrangement on the output  side  This is to make sure one cable will not bridge  the insulation barrier in case of coming lose     5  Start the converter wi
17. voltage of at  least 115  of nominal output voltage of the  converter     Repeat this calculation for all branches and  choose the highest capacitance value     3  It is sometimes difficult to estimate the short   circuit current when the nature of a fault is  unknown  In this case a voltage dip might  appear under some short circuit conditions even  with a large capacitor present  If a voltage dip is  critical in one branch it is recommended to use a  separate DC DC converter supplying this  branch     Fl    on F      Figure 2  Connecting multiple loads     5 Alarm  The alarm relay switches to     ALARM    state if     e The output voltage is not within  15    10  of  nominal output voltage   e The converter is overheated     Otherwise the relay contact is in the position      NORMAL        The alarm relay can be connected in two ways     1  Normally Open  NO     i  Connect twisted pair  0 25mm   1 5mm      from centre pin of the removable alarm  connector and connector pin marked                        Polyamp AB  Sweden    www polyamp com    2  Normally Closed  NC    i  Connect twisted pair  0 25mm   1 5mm     from centre pin of the removable alarm  connector and connector pin marked       NORMAL      ALARM NORMAL       31 32    Figure 3  Alarm contact     The relay is isolated 2500Va c  from input  output  and case  The relay can switch maximum 30V 5A   a c  and d c  values      5 1 Over and under voltage alarm   The alarm relay switches to alarm and the            NOT OK
18. wn with an  internal short circuit on the output and other  converters are connected in parallel on the output   the broken unit will short circuit the others if the    Polyamp AB  Sweden    www polyamp com    series diode is not used  This might cause excessive  heat or even fire in the faulty unit     If the series diode is used  the alarm relay will  switch to     ALARM    on the faulty unit if one  converter breaks down in a redundant power supply  system  Otherwise there will be no alarm indication  from a faulty converter unless all units are in  current limit and the output voltage drops 10   below nominal output voltage     When the series diode is used the total output  power of the converter must be derated  See data  sheet     e      24Vd c  output by 10        On 48Vd c  output by 5      Do not forget to fuse the inputs separately to  achieve redundancy     3 2 Current sharing   All models include the automatic current sharing  feature  which we recommend to use in parallel  configuration  A maximum of 10  10  units can be  connected in parallel     If more than 10 units should be connected in  parallel  contact Polyamp     Connect a cable  0 25 1 0mm     with a maximum  length of 3 0m between the    gt  CURRENT SHARE     connectors of all units     The converter with the highest output voltage will  then automatically become current master     This  converter will then run with a few percent higher  output current than the others  If the master  converter for som
19. xceed 105   of the nominal current of the converter  the  output voltage will drop until the fuse is blown   Depending on the impedance of the short circuit   whether it is abrupt or merely an overload  and  the resistance of the load cables  the effects of a  short circuit will vary     Long cables reduce short circuit currents   resulting in longer delay until the fuse is blown  and hence an increased voltage dip  Light  overload does not necessarily result in a blown  fuse     To reduce the voltage drop at short circuit and  if any branch has more than approximately 30   of the total output current of the converter  a  large external capacitor is recommended  Such a  capacitor will supply the peak current needed to  blow the fuse  see Figure 2  To calculate the  capacitor needed  use the following formula     C 1 2x Isx At  AU  1 2   Safety margin   Is   Short circuit current through the fuse     At   Time before the fuse blows  see data  sheet on the fuse      AU   Acceptable voltage dip before the fuse  blows     Example     You have a 5   fuse with fast characteristic and  the short circuit current is 50    The data sheet    10229 15 doc    Polyamp AB  Sweden www polyamp com Page 6  10     POLYAMP  LAL pu1o9Pusoo INSTALLATION MANUAL    gives you that At   10ms  The output voltage is  24V  and you can accept 10  voltage drop   gt   AU 24 x 0 1  2 4V     The capacitance you need     C 1 2x  Is x At  AU 1 2x 50x 0 01  2 4    250 000uUF    Choose a capacitance with a rated 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
SeaTurtle_Operation Manual (English)  User Manual PetNAD  Instruction Manual  6055 Users Guide 5A1102.vp    USER`S GUIDE 2334  pour les captages d eau potable - (CRPF) de Midi  Directed Audio model 1200/5 User's Manual  Q2Upgrade User Manual  Document    Copyright © All rights reserved. 
   Failed to retrieve file