1. Load current Power dissipation For power off time gt 5s Closure delay Reclosure delay at chopping operation Electrical safety typically 10V DC 10mA 30V DC 22mA typically 180V AC 10mA 260V AC 14mA 50 60Hz max 6A 85 265V AC DC 14VA 50 60Hz no tolerance in either direction max 6A 400 500V 50 60Hz depending on type Uy 10 acc to DIN EN 61000 2 4 class 3 THD max 10 70 90 115A depending on type 70A type approx 2 2W per A 90 115A type approx 2 1W per A Input DC 0 max 20ms AC 10 max 30ms Input DC 0 max 33ms AC 10 max 43ms Standards and subsequent amendments Protection class Protection type Overvoltage category l IP10 CAT3 4 V2 0 EDEBDAO200 2112 1 EN EDEBDAO0200 2112 1 EN Ambient conditions Standards and subsequent amendments Operating temperature Air humidity Storage temperature Installation Position Space for heat discharge Housing HxW x D Weight V2 0 thyro gy switch DIN EN 60721 3 3 A2 3K5 3Z11 IEC 721 3 3 3K5 3Z11 5 C 55 C gt Please observe power limitation depending on ambient temperature see page 8 5 95 non condensing 25 C 70 C vertical recommended or 45 tilted at least 50 mm to the fan and at least 150 mm to the heat sink outlet 70 90A Typ 220 x 105 x 188 mm 115A Typ 220x105 x 198mm 70 90A Typ approx 2900 g 115A Typ approx 3600
2. ambient temperature e 1154 Typ 904 Typ dir 704 Typ Strom A 30 35 37 40 43 46 48 50 52 55 56 Umgebungstemperatur C 8 Model type overview Special voltages and currents on request 9 Declaration of conformity ENGLISH CE DECLARATION OF CONFORMITY We declare that we have sole responsibility that this product see table meets the conditions of Directives 73 23 EEC and 89 336 EEC and corresponds to the following standards or reference documents EN 61010 1 2002 08 EN61010 1 B1 2002 EN 61010 1 B2 2004 EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 EN 61000 6 4 2007 V2 0 11 KBR Kompensationsanlagenbau GmbH Am Kiefernschlag 7 D 91126 Schwabach Germany Phone 49 0 9122 6373 0 Fax 49 0 9122 6373 83 E mail info kbr de www kbr de EDEBDAO0200 2112 1 EN
3. m User manual ae Technical parameters Thyristor switch for reactive current compensation EDEBDA0200 2112 1_EN KBR GmbH Subject to technical changes EDEBDAO0200 2112 1 EN Contents Intended use 4 Safety hice 6 Application range 1 5 nter terere rite nte eeb liae etse rk rete k retard hore SEACA 7 Installation 8 CONDECION iss T 9 Start up Performance limitation depending on ambient temperature sss sssssirssssrrsserrsesrressee 11 Model type overview unnemnennneeennnsseennnnnsereennnnsernnnnnsnrennnnnssennnnrrennnnntsreennnsrsennnnntrrsennnntrsnnnn 11 Declaration of conformity serere tenenti ttttnnnnnttttnnnnntttnnnnn 11 V2 0 3 thyro g switch 1 Intended use The thyroswitch is a power electronics component for hooking up capacitive loads to the grid The device is intended exclusively for installation in switchgear and controlgear Only detuned up to 14 96 compensation stages may be switched First and foremost symmetrical three phase current compensation is the intended use but it is also possible to switch two separate alternating current compensation stages simultaneously Technical data Input Control input Fusing Power supply Auxiliary voltage Fusing Load circuit Supply voltage Uy Tolerance Uy Harmonic voltage
4. maintenance and servicing may only be performed by qualified electricians A soon as the thyroswitch is connected to the power supply system the capacitive load is charged to to network peak voltage In addition a phase is switched directly to the load This means that the load is under voltage even when switched off and remains connected to the power supply When working on the load the device must be disconnected from the power supply under all circumstances Risk of fatal injury 6 V2 0 EDEBDAO0200 2112 1 EN EDEBDAO0200 2112 1 EN thyro gy switch Even after disconnection from the network a residual charge remains in the capacitive load Before working on the equipment it must be checked that the capacitors are de energized The discharge time of the capacitors must be taken into account Note Power capacitors must be equipped with permanently connected discharge devices and be discharged within five minutes to a residual charge of max 50uC to a voltage of 60V If this has a disturbing effect on the function of the electrical equipment a warning sign must be put up in a clearly visible position stating that the discharge time is longer than five minutes If it is possible to come into contact with the voltage of the capacitors even if the connectors are used correctly and if these connectors can be pulled off without the use of tools the discharge must be possible within one minute See EN 50178 section 5 2 5 For the set
5. vertically it must be ensured that the heat is always emitted upwards When installing several thyroswitches on top of one another cowls should be used For rated load there is an increase in temperature between fresh air and exhaust air of max 52 C for type 115A max 40 C for type 90A max 35 C for type 70A 115A Typ em A 4072 102 220 204 198 186 5 for type 70A and 90A 194 5 183 for type 70A and 90A 96 85 for type 70A and 90A 93 80 for type 70A and 90A Draufsicht top view R ckansicht back view 8 V2 0 EDEBDAO0200 2112 1 EN QD thyro gy switch ll mu c LIE ow j I rh c r 4 I td m d i 10 30V DC ri I I thyro switch Q 5 Connection DC connection L1 85 265 VAC DC FL ta r d 180 260V AC AC connection thyro switch L1 85 265 VAC DC NJ L ZLLZ 0020vaa303 V2 0 thyro g switch The load current with insulated crimping cable lugs with 8mm rings should be connected with terminal studs tightened with a torque of 5 5 6Nm The cable lugs must be positioned exactly vertically to the PCB When wiring it must be observed that the connections are not directly heated up by the air from the heat sinks As load fuses fuse units for the protection of semiconductors must be used Their size must fu
6. g thyro g switch 2 Safety note Due to the design with forced cooling i e with the use of a fan particularly the unimpeded air intake must be guaranteed The cooling openings must not be covered up The distances specified from neighboring components must be observed For rated load there is an increase in temperature between fresh air and exhaust air of max 52 C for type 115A max 40 C for type 90A max 35 C for type 70A Temperature sensitive components such as cable ducts should be protected accordingly The thyroswitch may only be operated with a power disconnecting device connected in series The thyroswitch cannot function alone as a component and must be configured for use with a compensation unit In detuned systems it is absolutely essential that the thyroswitch is switched before the inductor and capacitor The thyroswitch may only be deployed in the context of its intended use Even when used only as intended a defect cannot be ruled out In this case the currents and voltages in the load circuit could be affected The following errors are possible Current interruption half wave operation or constant energy flow Correct design of protective devices must therefore be ensured during project planning Incorrect operation or wrong connections could lead to destruction of the device or the load The thyroswitch may only be connected with insulated crimp type cable sockets Work such as assembly
7. lfill the requirements of the connected capacitive load It must be ensured that the grounding conductor is connected correctly The grounding conductor connection is an M6 hexagonal screw that can be found on the heat sink beneath the connections for the capacitor and is labeled with the grounding conductor sign In detuned systems it is absolutely essential that the thyroswitch is connected before the inductor and capacitor Terminals 1 and 3 For 10 30V DC input terminal 1 must be connected to plus and terminal 3 to minus Terminals 2 and 3 For 180 260V AC 50 60 Hz input terminals 2 and 3 must be used Terminals 4 and 5 The supply voltage 200 250V AC or 85 265V AC with 50 or 60Hz is connected to terminals 4 and 5 6 Start up 1 Make sure that the thyroswitch is properly connected 2 Attach the plastic housing 3 Switch on the supply voltage Power LED lights up 4 If necessary check the connection of the controller control LED lights up and fan starts up Note The load current may only be released for the first start up if there is no connection i e the thyroswitch is switched off 6 Connect the load current 7 Release the controller if connected and functioning correctly Power Control Thyr1 and Thyr2 light up 8 The fan can be switched on permanently with a jumper 10 V2 0 EDEBDAO0200 2112 1 EN EDEBDAO200 2112 1 EN thyro gy switch 7 Performance limitation depending on
8. up of the discharge equipment it must be remembered that capacitors when switched off are charged to a direct voltage at the level of the network peak voltage The parallel operation of systems with conventional protective relaying and semiconductor technology is only possible for induced systems Otherwise the thyroswitch could be destroyed by charging effects 3 Application range The thyroswitch is particularly intended for systems with frequent and rapidly changing reactive power loads The advantages of the thyroswitch compared to conventional technology are High switching speed Switching performance with low system perturbation Switching without wearing parts Long working life thanks to practically unlimited frequency of operations Fields of application Cranes e Lifts Welding equipment Molding presses Wind turbines The power switch can be operated in conjunction with reactive power controllers programmable logic controllers computer systems and process controllers V2 0 7 thyro g switch 4 Installation The thyroswitch should be installed vertically or max 45 tilted The integrated fan controls the air flow so that nearly all the warm air produced is emitted in one direction Temperature sensitive components installed near the device have to be protected accordingly The safe distances specified must be observed Fan side 550mm Heat sink outlet 150mm If the device is installed

Download Pdf Manuals

image

Related Search

Related Contents

Manual de instruções - Aparelhos de proteção contra sobretensão  Boston Acoustics SoundWare XS Digital Cinema  DeLOCK 4GB IDE Flash Module  Crick 110  LCD - e-TradeCounter.co.uk  Handbuch für H.264 Digital    ce manuel d`utilisation pour 206  Plantilla Departamentos Versión 1.0 Diputación Provincial de  Informazioni generali sul PlateWriter 2000  