Home
Operating instructions
Contents
1. Transport the equipment with care Equipment and its internal parts can be damaged by dropping by shock Equipment must only be operated by technically qualified personnel Never operate the equipment without heat carrier liquid Do not start up the equipment if itis damaged or leaking Cable not only supply cable is damaged Switch off the equipment and pull out the mains plug for servicing or repair moving the equipment Do not carry out any technical changes on the device Have the equipment serviced or repaired by properly qualified personnel only The Operating Instructions include additional safety notes which are identified by a triangle with an exclamation mark Carefully read the instructions and follow them accurately Disregarding the instructions may have serious consequences such as damage to the equipment damage to property or injury to personnel We reserve the right to make technical alterations YACE0082 04 10 06 Safety notes 3 LAUDA High temperature cooling HTC with LiBus Control 1 1 Safety information e A high temperature cooler is used to cool temperature stabilizing liquids as prescribed This leads to hazards due to the hot temperature stabilizing liquids the emission of water and to general hazards due to the use of electrical energy e The user is largely protected by the application of the relevant standards It is not possible to include all possibilities Th
2. Non cooling mode and the maximum cooling power is reduced in the Cooling mode An application specific optimum can be achieved by the step by step adjustment Optimization is particularly advantageous with large baths from P 12 upwards Guide value If with the P8 the external selec tor is set to 50 vertical position then the time required for cooling extends by approx 50 e g from 200 C to 100 C from previ ously 8 minutes to 12 minutes In this way better circulation is achieved with a tempera ture accuracy up to 0 02 C Then optimize the control parameters accord ing to the Proline operating manual Set the Proline bypass valve 5 to Exter nal In this operating mode the pump flow must always be shared between the external load and the HTC To do this connect the external load to the second pump connection on the Proline thermostat A serial arrangement is unfavorable because the valve K1 of the HTC see 3 is closed in some operating states so that only a very small part of the flow is left to pass through the HTC bypass D1 It may be necessary to also adjust the flow through the reducing valves so that both the HTC and the external load receive sufficient flow Then optimize the control parameters accord ing to the Proline operating manual Starting up 11 LAUDA High temperature cooling HTC with LiBus Control 7 Draining frost protection If the HTC high temperature coole
3. for service and support LAUDA Service Center Telephone 49 0 9343 503 236 English and German E Mail service lauda de When ordering replacement parts please state the type of unit and number on the rating label on the rear panel of the unit This avoids queries and supply of incorrect items The serial number is combined like following for example LCZ 9663 06 0001 LCZ 9663 article order number Ref No 06 manufacturing year 2006 0001 continuous numbering YACE0082 04 10 06 Maintenance 15 LAUDA High temperature cooling HTC with LiBus Control 10 Technical Data The figures have been determined according to DIN 12876 Ambient temperature range C 5 40 Temperature range cooling water C 5 30 Temperature range heat carrier liquid C 5 300 Temperature accuracy K 0 3 Safety features Warning No cooling water present Warning at emptying Bath liquid temperature gt 60 C Cooling power Ultra 350 water kW 4 7 at tran 300 C at pump level 8 4 7 at tban 200 C 2 8 at tban 150 C 0 9 at toath 100 C Cooling power water water kW 10 5 at tban 95 C at pump level 4 8 7 at bam 80 C 5 8 at tran 60 C 2 8 at trat 40 C 1 5 at trat 30 C For cooling circuit volume flow L min 5 For cooling water input temperature C 15 Required cooling water pressure bar 3 5 to 5 with throttle diaphragm 1 0 to 3 5 without throttle diaphragm Maximum permi
4. temperature cooler HTC Ensure that the inputs and outputs are connected correctly If the inputs and out puts are mistakenly interchanged the seals on the internal solenoid valves will be damaged HTC rear view 8 Cooling water feed Cooling water outlet LiBus connecting lead to the thermostat YACE0082 04 10 06 Functional elements 5 3 3 1 3 2 3 3 LAUDA High temperature cooling HTC with LiBus Control Device description Principle of operation In conjunction with the HTC high temperature cooler LAUDA heating thermostats with LiBus control e g Proline heating thermostats can very effectively and safely be used with cooling water for active cooling at temperatures up to 300 C This is achieved in the HTC in that only so much hot thermostatic medium is introduced into a coaxial heat exchanger via the valve K1 that the cooling water does not ex ceed a temperature of approx 60 C as measured on the sensor T2 A bypass in the HTC facilitates an adequate bath circulation of the temperature stabilizing liquid in the heating thermostat even when cool ing is not taking place K1 closed The HTC high temperature cooler is supplied electrically directly through the LiBus connection from a thermostat K1 Valve for temperature stabilizing liquid K2 Cooling water valve D1 Bypass D2 Throttle diaphragm in the cooling water T1 Temperature sensor for temperature stabi feed lizing liquid T2 Temperature sens
5. Operating instructions Controlled high temperature cooling With LiBus Control Valid from series LCZ 9663 06 0001 04 06 YACE0082 04 10 06 from software version of Control system from software version of protection system from software version of Operating system from software version of solenoid valve 1 44 1 33 1 53 1 38 LAUDA LAUDA DR R WOBSER GMBH amp CO KG Post office box 1251 97912 Lauda K nigshofen Germany Telephone 49 09343 503 0 Fax 49 09343 503 222 E Mail info lauda de Internet http Awww lauda de LAUDA High temperature cooling HTC with LiBus Control Contents EE E 3 ET SAFETY INFORMATION cional arnet eege eege tada 4 12 OTHER SAFETY INFORMATION aid 4 2 Functional cle mente iii aa 5 ek IDEVICESASSCHIPUOM it A i Rk e cs a O A d 6 el PRINCIPLE OF OPERATION A ee dando ros ads 6 3 20 EENG WATER a o ee La 6 3 3 CONTROLLER AND SAFETY DEVICES caciones dd d ii 6 3 4 SUBSTANCES MATERIALS IN THE WATER CIRCUITS 0ooooocccccccccoconononccnnnnnnnnnnnnonnnnnnnnnnnnnnnnnnnnnnnnnnnnmnnnnnnnnnnnnannnes 7 Ei UNPACKING disci Wat Ae as Ae OA a ege le a TS 7 5i Preparations A ies od eden ae ae os ened aa eee eles 8 Dil TING ANO CONNECTIONS oido SEENEN Seed id 8 B STARING SUP EE 10 6 1 OPTIMIZING THE THERMOSTAT CONTROL WITH THE HTC 11 6 1 1 Internal mode without external Joad es 11 6 1 2 External mode with external Joad 11 T Draining frost protection os aea ia o
6. a inside the equipment D autre part nous confirmons que l appareil mentionn ci dessus a t nettoy correctement que les tubulures sont ferm es et qu il n y a aucun produit toxique agressif radioactif ou autre produit nocif ou dangeureux dans la cuve Stempel Datum Betreiber Seal Cachet Date Date Responsible person Personne responsable Formblatt Form Formulaire Unbedenk doc LAUDA DR R WOBSER GmbH amp Co KG Erstellt published tabli LSC PfarrstraBe 41 43 Tel 49 0 9343 503 0 And Stand config level Version 0 1 D 97922 Lauda K nigshofen Fax 49 0 9343 503 222 Datum date 30 10 1998 Internet http www lauda de E mail info lauda de UNBEDENK DOC
7. d dd id E AEN 12 7 1 DRAINING THE COOLING WATER CIRCUIT c cccsccsscccceussccceesseccceeussccetensescedzessecesaeusnccezensencuceussseduensecedeeeedees 12 7 2 DRAINING THE THERMOSTATIC MEDIUM CIRCUIT ssinssessssisicstrinitrtsrtitittnettnrier rtnn At AAEE EEEE Ene E AEAEE rE EREE EEEE Ee 13 8 Special functions of the HTC software 14 BA DISPEAYS E aan Se Ah ee a ke ahs Rove as a ane tel ed es le eet oa cede at 14 8 2 RESETTING THE HTC TO THE FACTORY SETTING isiin aaaea A AE AAEE ERRANA REE 14 9 Maintenance rata EEN 15 91 CLEANING THE SURFACE OF THE DEVICE cin id cid 15 9 2 CLEANING THE LINES OF THE THERMOSTATIC CIRCUIT nn nnnnnn nn aaneen anaana 15 9 3 MAINTENANCE AND REPAIR 0 A e E 15 10 Technical Dali EE 16 Explanation of signs Danger This sign is used where there may be injury to person nel if a recommendation is not followed accurately or is disregarded Note Here special attention is drawn to some aspect May IER include reference to danger Reference Refers to other information in different Sections 2 Contents YACE0082 04 10 06 High temperature cooling HTC with LiBus Control LAUDA 1 Safety notes Before operating the equipment please read carefully all the instructions and safety notes in Section 1 1 If you have any questions please phone us Follow the instructions on setting up operation etc This is the only way to avoid incorrect operation of the equipment and to ensure full warranty protection
8. ey remain essentially subject to the judgment and re sponsibility of the operator e The devices may only be used as intended that is as described in this operating manual This in cludes operation by instructed specialist personnel e The devices are not designed for use under medical conditions according to DIN EN 60601 1 or IEC 601 1 1 2 Other safety information e Only use the supplied pipe connections or metal corrugated hoses e Protect tubing for water cooling with hose clips against slipping off Prevent kinking of tubing e Check the hoses from time to time for any material fatigue e Take into account the thermal expansion of the heat carrier liquid with increasing bath temperature e Cool the thermostatic medium to below 60 C before cleaning maintenance emptying or moving the high temperature cooler e Have repairs carried out only by specialists e Values for temperature control and indicating accuracy apply under normal conditions according to DIN 12876 High frequency electromagnetic fields may under special conditions lead to unfavour able values This does not affect the safety 4 Safety notes YACE0082 04 10 06 High temperature cooling HTC with LiBus Control LAUDA 2 Functional elements Example Operating side of P 8 with HTC connected on the Space saving connection with the Proline Thermostatic Baths P 5 P 8 P 18 and P 26 with siting of the HTC at the side Connection between P 8 and the high
9. line thermostat When the Proline heating thermostat demands cooling from the HTC high temperature cooler the blue LED Cooling illuminates on the Proline control panel Under partial power this flashes The control parameters may need to be adapted Tried and tested control parameters for the P 8 with bath medium ULTRA 300 Pump level 8 Xp 16 0 Tn 80 3 If water or aqueous solutions are used as the bath medium a pump level of maximum 4 on the Proline thermostat is sufficient This reduces acoustic noise without impairing the cooling power Pump levels for oil and water gt 10 10 Starting up YACE0082 04 10 06 High temperature cooling HTC with LiBus Control 6 1 YACE0082 04 10 06 LAUDA Optimizing the thermostat control with the HTC If the best possible temperature stability is to be achieved then the control and the setting of the bypass valve on the Proline operating panel 5 must be optimized Different settings are advantageous depending on whether the internal bath is used internal mode or whether an external load is connected external mode 6 1 1 Internal mode without external load 6 1 2 External mode with external load The bypass valve 5 is set step by step from External to Internal until the desired bath temperature stabilization is achieved In this operating mode part of the bath liquid flow is not passed through the HTC The bath circulation is here improved in the
10. nal external selector on the Proline ther mostat to external mode Check whether on the Proline thermostat the control software version 1 44 or higher is installed Update it if necessary Plugin the LiBus lead of the HTC into a free socket on the thermostat Connect the HTC to the thermostat using the two sup plied corrugated hoses Follow the directions of flow as labeled on the thermostat and the HTC Illustration in Chapter 2 and on the next page 8 Preparations YACE0082 04 10 06 High temperature cooling HTC with LiBus Control Example Operating side of P 12 with HTC connected on the right Example Operating side of P 18 with HTC connected at the rear LAUDA Space saving connection of the Proline Heating Thermostat P 12 with siting of the HTC at the side O Connection between P 12 and HTC Ensure that the inputs and outputs are connected correctly If the inputs and outputs are mistakenly interchanged the seals on the internal solenoid valves will be damaged Space saving connection with the Proline Heating Thermostat P 18 with siting of the HTC behind the thermostat O Connection between P 18 and HTC Ensure that the inputs and outputs are connected correctly If the inputs and outputs are mistakenly interchanged the seals on the internal solenoid valves will be damaged quired es With the connection of the HTC high temperature cooler the bath level in the therm
11. ng liquid valve is reset to the factory setting 14 Special functions of the HTC software YACE0082 04 10 06 High temperature cooling HTC with LiBus Control LAUDA 9 Maintenance 9 1 Cleaning the surface of the device Cleaning can be carried out with water to which a few drops of surfactant washing up liquid have been added and using a damp cloth 9 2 Cleaning the lines of the thermostatic circuit When the thermostatic medium is changed the remainder of the previous liquid must be rinsed out To do this open the valve in the thermostatic circuit as outlined in Section 7 2 and rinse with a suitable solvent Then blow dry The HTC and the thermostat are NOT flame proof Provide adequate ventilation No solvent may enter the HTC high temperature cooler 3 Carry out appropriate decontamination if dangerous material is spilt on or in the unit The cleaning or decontamination method is determined through the user s specialist knowledge In case of doubt contact the manufacturer 9 3 Maintenance and repair 3 Contaminated water in the cooling circuit can lead to blockage of the sieve and under some circumstances of the heat exchanger Check the sieve 5 regularly for contamination LAUDA high temperature cooling HTC are largely maintenance free If the heat carrier liquid becomes dirty it has to be replaced Have the equipment serviced or repaired by properly qualified personnel only Your contact
12. nto contact with the cooling water are of stainless steel Viton silver solder brass copper 4 Unpacking After unpacking firstly check the device and accessories for any damage in transit If contrary to ex pectations the unit is found to be damaged the shipping company must be immediately informed so that verification can take place Please also inform the LAUDA Service Center Contact 9 2 Standard accessories Quantity Article LAUDA Article number 1 This Operating instructions YACE0082 2 Hose olive G for 2 hoses EOA 001 Corrugated hoses for the connection of Proline 2 Thermostatic Baths P 5 C P 8 C P 12 C LZM 040 P 18 C and P 26 C YACE0082 04 10 06 Unpacking 7 LAUDA High temperature cooling HTC with LiBus Control 5 Preparations 5 1 Siting and connection IER Site the unit on a level surface The unit must not be put into operation if its tempera ture due to storage or transport has been reduced be low the dew point Wait approx 1 hour Connect the external cooling water feed and return Secure hoses against slippage by using hose clips A sieve O and a throttle diaphragm are located in the cooling water feed In domestic water supply networks with 3 5 to 5 bar pipe pressure the throttle diaphragm reduces the amount of cooling water The diaphragm must be removed for pressures below 3 5 bar Higher pressures up to 10 bar are not critical Set the inter
13. o stat falls because the HTC is filled when the pump is switched on gt Top up if re changer aged Contaminated cooling water may lead to blockage of the sieve or of the heat ex Ensure that the inputs and outputs are connected correctly If the inputs and outputs are mistakenly interchanged the seals on the internal solenoid valves will be dam Pay attention to the maximum permissible pressures 10 YACE0082 04 10 06 Preparations LAUDA High temperature cooling HTC with LiBus Control 6 Starting up Ensure that the direction of flow of the cooling water corresponds to the printed ar rows Ensure that cooling water is always available in operation even when temporarily no cooling power is being demanded Ensure that the unit is connected to a Proline heating thermostat according to Chap ter gt 5 Ensure that the HTC is connected via the LiBus to a heating thermostat which is compatible with the LiBus Ensure that in the Proline thermostat the control software version 1 44 or higher is installed The correct connection of the HTC is displayed in the menu module of the heating thermostat Ensure that on the Proline thermostat the internal external selector is switched to external mode Provide cooling water The HTC high temperature cooler operates automatically after switching on the Proline heating thermostat and is controlled to the requirements as specified on the Pro
14. or for cooling water Cooling water For proper cooling the HTC high temperature cooler needs a cooling water flow of approx 5 litres min To prevent the flow of cooling water becoming unduly large a throttle diaphragm is built into the cooling water feed In normal domestic water supply networks with 3 5 to 5 bar it reduces the flow of cooling water to the required amount The diaphragm must be removed for water pressures below 3 5 bar Higher pressures up to 10 bar are not critical Controller and safety devices The closed loop control technology of the HTC high temperature cooler is able to adapt the cooling power to the requirements of the temperature stabilizing task In this respect a control accuracy of 0 3 K in the cooling operating mode and approx 0 02 K in the non cooling operating mode can be achieved The cooling water is used particularly sparingly The electronic monitoring ensures that no boiling processes can arise in the HTC high temperature cooler Also when the supply of cooling water fails Device description YACE0082 04 10 06 High temperature cooling HTC with LiBus Control LAUDA 3 4 Substances materials in the water circuits All of the parts which come into contact with the thermostatic medium are of stainless steel Viton silver solder brass Brass is subjected to 150 C maximum so that the LAUDA temperature stabilizing liquids Ultra 300 and Ultra 350 can be used All of the parts which come i
15. ot forget to fit the plugs on the pump connectors of the Proline thermostat after removing the HTC high temperature cooler Never draw up flammable media into an industrial vacuum cleaner YACE0082 04 10 06 Carry out appropriate decontamination if dangerous material is spilt on or in the unit The cleaning or decontamination method is determined through the user s specialist knowledge In case of doubt contact the manufacturer Draining frost protection 13 LAUDA High temperature cooling HTC with LiBus Control 8 Special functions of the HTC software 8 1 Displays Master mm Podu gt HEC gt Shobu enter the display mode with the enter key then page with the cursor keys Er Module software version Pix Displays switching state of Solenoid Valve 1 thermostat circuit 7 CLOSED Is OPEN Pe x Displays switching state of Solenoid Valve 2 cooling water O CLOSED OPEN Eix Temperature of NTC1 in the thermostat circuit in C Ee x Temperature of NTC2 in the cooling water circuit in C Vert Displays 24V supply voltage Dor H Serial number high word 5nr_L Serial number low word End Quits the display level Command Module software version Menu gt Retire gt gt AMSTE Module serial number Menu gt EA DAE RANEA 8 2 Resetting the HTC to the factory setting Master Miodu gt HEL gt dEF press the enter key for a few seconds The cooli
16. r is to be separated from the thermostat or if ambient temperatures below 0 C are to be expected the unit must be drained 7 1 Draining the cooling water circuit Turn off the pressure from the cooling water hoses and remove them First read the thermostat operating instructions regarding the unit operating struc ture if you have not already read them Master Madu gt HEL gt unt dl Command gt MA gt DEA gt EARE O To prevent scalding proceed as follows depending on the bath temperature Bath temperature below 60 C Bath temperatures above 60 C Thermostat enters the standby mode Thermostat enters the standby mode The HTC opens the cooling water and However the valves remain closed bath media valves I b i606 is displayed UPEn is displayed Drain the heat exchanger using compressed air on the cooling water feed Alternatively Empty using a waterproof industrial vacuum cleaner on the Cooling water output connection Only drain the water circuits in this way Master To close the valves and quit the menu press Command Menu gt gt gt Eat Ei After draining the circuits completely switch off the Proline unit and withdraw the LiBus connecting lead When blowing out with compressed air water is emitted on the cooling water out put If the draining procedure is to be interrupted press the key repeatedly to re
17. ssible cooling water bar 10 pressure Height mm 255 without media connections Overall dimensions BxL mm 240 x 215 without cooling water connections Weight kg 8 8 We reserve the right to make technical alterations Devices according to EU Directive 89 336 EEC EMC and 73 23 EEC Low voltage with CE label 16 Technical Data YACE0082 04 10 06 BESTATIGUNG CONFIRMATION CONFIRMATION LAUDA An To A LAUDA Dr R Wobser LAUDA Service Center Fax 49 0 9343 503 222 Von From De Firma Company Entreprise StraBe Street Rue Ort City Ville Tel Fax Betreiber Responsible person Personne responsable Hiermit best tigen wir da nachfolgend aufgef hrtes LAUDA Ger t Daten vom Typenschild We herewith confirm that the following LAUDA equipment see label Par la pr sente nous confirmons que l appareil LAUDA voir plaque signal tique Typ Type Type mit folgendem Medium betrieben wurde was used with the below mentioned media a t utilis avec le liquide suivant Dar ber hinaus best tigen wir da das oben aufgef hrte Ger t sorgf ltig gereinigt wurde die Anschl sse verschlossen sind und sich weder giftige aggressive radioaktive noch andere gef hrliche Medien in dem Ger t befinden Additionally we confirm that the above mentioned equipment has been cleaned that all connectors are closed and that there are no poisonous aggressive radioactive or other dangerous medi
18. turn to the higher level menu 12 Draining frost protection YACE0082 04 10 06 High temperature cooling HTC with LiBus Control LAUDA 7 2 Draining the thermostatic medium circuit Master Modu gt HEL gt unt ill Command gt MA gt DEA gt KAREM et To prevent scalding proceed as follows depending on the bath temperature Bath temperature below 60 C Bath temperatures above 60 C Thermostat enters the standby mode Thermostat enters the standby mode The HTC opens the cooling water and However the valves remain closed bath media valves 1 bu D I is displayed LIFEn is displayed Remove the HTC high temperature cooler from the Proline unit Blow into the thermostatic medium feed with compressed air to drain the heat ex changer Master Press to close the valves and to quit the menu Command Menu gt MJA gt Girt gt ZEIL Lei After draining the circuits completely switch off the Proline unit and withdraw the LiBus connecting lead When blowing out with compressed air thermostatic medium is emitted on the thermostatic medium output Do not empty the temperature medium circuit with an industrial vacuum cleaner or similar device because then there is a risk of fire and explosion If the draining procedure is to be interrupted press the key repeatedly to return to the higher level menu Hose couplings are not self closing Do n
Download Pdf Manuals
Related Search
Related Contents
Gebrauchsanweisung Bedieningshandleiding PHS シールド PSLD-01 取扱説明書 Directives Complément CEE Entreprises _v. 01-01 Supermicro X7DB3-B motherboard Notice d`instruction EB2410ITX User Guide Hotpoint 6500 User's Manual NAD C541i CD Player User Manual Copyright © All rights reserved.
Failed to retrieve file