Operating Instructions Standard presence detector

image

Contents

1. Load switches off in spite of the presence of persons and insufficient lighting levels Cause Preset shut off delay too short Remedy Prolong delay with time potentiometer Cause Detection problem surface to be monitored not completely in the detector s field of view View obstructed by furniture or columns Remedy If needed use another presence detector extension unit to enlarge the field of detection see chapter Use of extension units on page 37 Load switched on without any noticeable movement detected Cause Sources of disturbance in the field of detection Remedy see chapter Installation on page 11 Load switches off briefly and then on again Cause After shut off the ambient brightness falls below the preset minimum brightness level so that the device switches on again immediately when movement is detected Remedy Increase the shut off threshold by turning the lux potentiometer a little bit towards the sun symbol Light Management YIVINIG standard presence detector Ref no PMS 360 WW Tip With fewer movements expected in the monitored area the shut off delay should be selected longer to prevent premature switching off of the lights Use of extension units The standard presence detector on a Light Management 3 wire extension unit insert for presence detectors enlarges the detection field of the main unit Important e The extension unit is not suitable for direct switching of
2. case all movements detected will again lead to switching on of the lamps depending on prevailing brightness conditions This feature offers the possibility of deactivating the automatic mode on pur pose if for instance a room is to be darkened The lighting can be switched on via extension input 1 independent of brightness The brightness evaluation remains active This means that the lighting is switched off after 10 minutes if is not needed 10 Light Management YIVINIG standard presence detector Ref no PMS 360 WW Field of detection The standard presence detector has a 360 field of detection The PIR sensor array is composed of 6 levels of detection and 80 lenses 0 1m 2m 3m 4m om DO oo oo pa oD View from above figure J The field of detection measures approx 5 m in diameter at desktop level approx 80 cm On the floor the diameter of the detection field measures approx 8 m These ranges are referred to an installation under the ceiling and a fitting height of 2 5 m and tangential i e lateral direction of movement Important Range reductions must be expected if movement is directed towards the presence detector In such a case a detection in the outer 4 m range is not granted If a person moves too fast towards the presence detector there may be the impression of reduced detection range Observe also the possible on delays of the lamps used These facts are especially important when the
3. extension unit insert In this case the detection and treatment of signals is independent of brightness see chapter Use of extension units on page 37 Important The load rating specifications are set out in the operating instructions of the individual flush mounting inserts Light Management YIVINIG standard presence detector Ref no PMS 360 WW 3 Safety instructions Attention Electrical equipment must be installed and fitted by qualified electricians only The device is not suitable for safety disconnection Depending on the type of flush mounting insert used the deactivation of the device does not isolate the load electrically from the power mains When working on the load or on the device the device must be safely disconnected from the power mains Non observation of the installation instructions may cause fire or other hazards Installation The standard presence detector is installed exclusively under the ceiling Select a flush mounting insert in accordance with the load to be used install in the ceiling and connect to the power supply and or load see connection diagrams page 48 Plug the presence detector standard into the insert without exerting pressure on the lens The electrical contact is established through the connector pins Sources of interference Do not install in the direct vicinity of heat sources such as lamps figure B The cooling lamp may be interpreted by the PIR sensors as
4. load remains on after detection of movement and the retriggering function is active If no movement is detected the device switches off after the preset shut off delay LED ON gt monitored surface sufficiently illuminated by the activated lights The load remains on after detection of movement and the retriggering function is active If no movement is detected the device switches off after the preset shut off delay Light Management YIVINIG standard presence detector Ref no PMS 360 WW LED flashing gt monitored surface very bright due to the light from burning lamps and external light The load is switched off after 10 minutes at the latest with or without detection of movements since the brightness at the working surface even without lighting is higher than the preset brightness Important ln the first seconds after shutoff this brightness may seem to be insufficient Einstellhilfe Load remains on even at high levels of external light Cause Preset brightness value too high Remedy Turn lux potentiometer towards moon symbol Load is not activated despite insufficient brightness and movement detection Cause 1 Preset brightness value too low Remedy Turn lux potentiometer towards sun symbol Cause 2 Device deactivated from extension unit e g pushbutton Remedy Re activate from extension unit Cause 3 Device set to 0 chapter Settings on page 15 Remedy Re activate from extension unit
5. Light Management YIVINIG standard presence detector Ref no PMS 360 WW Operating Instructions Standard presence detector 1 Presence detector basics Stand Dez 08 82534303 Like a movement detector or an alarm system detector the standard presence detector too belongs to the family of PIR detectors At first glance all three types are equivalent Due to their different internal design and different signal detection and treatment procedures these types are suitable for different applications e Depending on brightness a movement detector switches the light on when movement is detected It switches the light off independent of brightness when no movement is detected anymore at the latest however after 90 minutes forced shutoff e Analarm system detector reports detected movements independent of brightness to an alarm center The number of pulses generated within a fixed time span is often adjustable e A presence detector is designed to switch on the light depending on brightness when presence is detected and then to switch it off again when it is no longer needed i e when it is already too bright or when there is no one in the room anymore What the detector does therefore is to detect the presence of persons depending on a preset brightness The differences between these PIR detectors lie essentially in the design of the Fresnel lense the adaptation to ambient conditions the type of fitting and the type
6. a thermal change and lead to repeated switching If necessary restrict the detection field with the supplied snap on mask see chapter Snap on mask on page 19 Do not install close to fans radiators or ventilation ducts Moving air e g draught through open windows might be detected and lead to repeated switching Select the best suited place for the installation The field of detection should not be restricted by furniture columns etc Avoid direct sunlight into the sensor window The sensors can be irreparably damaged by the high thermal energy Light Management YIVINIG standard presence detector Ref no PMS 360 WW The brightness sensor should be installed away from windows to avoid the undesirable influence of scattered light Install the presence detector standard free from vibrations to avoid switching triggered by sensor movements Adjustments figure C To adjust the brightness or the shut off delay withdraw the trimming ring from the presence detector standard The controls are then accessible Shut off delay 1 second test operation The time potentiometer permits adjusting the time intervals in fine steps between ca 10 seconds and 30 minutes Brightness adjustable between 10 lux moon symbol and 1000 lux sun symbol and manual setting 0 Important In the 0 setting the presence detector standard can onl
7. device is used as ceiling detector If the installation heights are increased the detector s sensitivity to movements is lower Sideview figure K 11 Light Management YIVINIG standard presence detector Ref no PMS 360 WW 4 Technical data Angle of detection 360 Nominal field of detection at desktop level 2 approx 5m Nominal field of detection at floor level approx 8m Height of installation for nominal field of detection approx 2 5 m The nominal field of detection varies with the height of installation Number of lenses levels of detection 80 6 Nominal voltage AC 230 V 50 Hz Switching capacity see insert instructions Shut off delay 1 sec in test mode approx 10 sec 30 min Brightness approx 10 1000 lux Number of extensions connected to flushmounting insert passive e g pushbuttons unlimited active see instructions for 3 wire extension nit insert Length of extension unit connection cable 00 m max Technical specifications subject to change Application of inserts The standard presence detector can be used exclusively for switching applications The detector is used in combination with the inserts of the Light Management series Dimmerinserts can be used as switching inserts universal touch dimmer Art Nr 1254 UDE figure L standard touch dimmer Art Nr 1225 SDE figure L relay insert Art Nr 1201 URE figure M Tronic switchi
8. fully satisfactory please observe the instructions in the chapters Standard setting Test LED function and Setting guidelines on pages 25 35 Standard setting If it is not possible to simulate the desired lighting conditions with the means available room has no darkening facility a standard setting can be selected For this setting the lux potentiometer must be adjusted as shown in figure I time 10min 10s test 30min Any readjustments can be made with the help of the test LED and the setting guidelines see pages 27 35 There is no response to movements inside the field of detection when the preset brightness load switched off is exceeded by additional light such as daylight or light from nearby lamps In this case the test LED is lit up or flashes and the lighting remains off Functions of the test LED When the first attempt to adjust the brightness was not satisfactory the setting can be verified and the brightness be readjusted with the help of the test LED and the setting guidelines page 31 35 States of the test LED and their meaning load disconnected LED OFF gt monitored surface too dark load switched on after detection of movements LED ON or LED flashing gt monitored surface bright enough load remains off even after detection of movements States of the test LED and their meaning load connected LED OFF gt monitored surface too dark The
9. loads and merely transmits movement detection signals independent of brightness to the main unit e The standard presence detector cannot be used on an extension unit insert designed for two wire operation If the main unit and the extension unit are each equipped with a standard presence detector switching is performed dependent on the brightness value detected by the main unit When used in this configuration the setting controls of the attachment on the extension unit are not operational The adjustment is performed only at the main unit When the standard presence detector is used in combination with the Light Management 3 wire extension unit insert the detection system is locked for about 3 seconds after the lights have been shut off before they can be switched on again from the extension unit Activation through extension input 1 of the insert If a flush mounting insert with extension input 1 e g relay insert is used under the main presence detector and switched off through extension input 1 the reactivation within the next 2 minutes is then only possible through extension input 1 Movements detected by the PIR sensors during this interval will not reactivate the device If movements are detected within this 2 minute interval the main unit will be locked again for another 2 minutes The automatic mode of the main unit will be reactivated only if the 2 minute interval has elapsed without movements being detected In this
10. ndependent switching action Combination of standard presence detector with a 2 channel relay insert fig O The device can be controlled from a secondary unit only through extension input terminal 1 Combination of standard presence detector with a pushbutton control unit fig P The device can be controlled from a secondary unit only through extension input terminal 1 AC 230 V 14 YIVINIG Light Management otandard presence detector Ref no PMS 360 WW Connection of 3 wire extension unit insert 1 main unit 2 g Tronic switching insert figure Q Connection of further extension units 3 hbutton T n o contact can be used to trigger a brightness independent switching action The maximum length of the cable connected to extension input 1 is 100 m Connection of mechanical pushbutton T n o contact and or extension unit insert for 2 wire operation with pushbutton attachment 1 main unit 2 g Tronic switching insert figure R When controlling the standard presence detector through extension input 1 of the insert please observe the instructions set out in the chapter Use of extension units on page 37 15 JUNG Light Management Standard presence detector Ref no PMS 360 WW 5 Acceptance of guarantee We accept the guarantee in accordance with the corresponding legal provisions Please return the unit postage paid to our central service de
11. nder those lighting conditions that are required for minimum brightness at the place of work i e lamps switched on with as little scattered light as possible Procedure e Set the time potentiometer to maximum interval 30 minutes figure G e Set the lux potentiometer to daytime operation sun figure G the LED must be off e Activate the device by making a movement inside the field of detection lux 10min 10s 4 Mi aC 0 test 30min x a Some lamps such as fluorescent lamps for instance need a certain time to reach full brightness Therefore e Observe the starting time of the lamps Important Avoid scattered light e g from additional daylight or from nearby lamps e Then turn the lux potentiometer in the direction of the moon symbol figure G until the test LED 4 figure H lights up Important Do not shade the light sensor 5 figure H during this adjustment The sensor must be able to measure the light reflected from the full monitored surface The standard presence detector is then adjusted to the actual brightness prevailing at the monitored surface Light Management YIVINIG standard presence detector Ref no PMS 360 WW e Set the time potentiometer to the desired shut off delay e Leave the field of detection and wait until the presence detector switches off after the time interval just set Important If the first setting is not
12. ng insert Art Nr 1254 TE figure N Triac switching insert Art Nr 1244 TE figure N 2 channel relay insert Art Nr 1202 URE figure O Pushbutton control unit Art Nr 1240 STE figure P 3 wire extension unit insert Art Nr 1223 NE figure Q Important Parallel connection of presence detector main units is not allowed The device cannot be used in combination with the 2 wire extension unit insert as active extension unit 12 Light Management YIVINIG standard presence detector Ref no PMS 360 WW The 2 wire extension unit insert can however be used in combination with a pushbutton attachment as passive extension unit Further installation details are set out in the operating instructions of the insert Connection diagrams Combination of standard presence detector with universal touch dimmer or standard touch dimmer figure L AC 230 V The device can be controlled from a secondary unit only through extension input terminal 1 Combination of standard presence detector with relay insert figure M Pushbutton T n o contact can be used to trigger a brightness independent switching action Combination of standard presence detector with Tronic switching insert or Triac switching insert figure N 13 Light Management JUNG Standard presence detector Ref no PMS 360 WW Pushbutton T n o contact can be used to trigger a brightness i
13. of movement or brightness signal transmitted Light Management YIVINIG standard presence detector Ref no PMS 360 WW 2 Function The standard presence detector is therefore used to monitor internal rooms for the presence of persons lt is installed exclusively under the ceiling of the room from where it monitors the working surface below figure A The detector works with a passive infrared sensor PIR sensor and responds to thermal movement triggered by persons animals or objects When movements are detected below a presettable brightness threshold the detector switches on an electrical consumer The device remains on as long as movements are detected When no movements are detected anymore the device switches off after a preset shut off delay If the brightness on the surface under supervision is permanently at least twice as high as the preset brightness e g due to supplementary daylight the test LED flashes and the presence detector switches off after 10 minutes at the latest even if movements are still being detected The standard presence detector is designed for switching purposes only and is used in combination with a Light Management insert for 60 mm flushmounting boxes lt can be combined with all Light Management inserts Dimmer inserts can be used as switching inserts The insert must be selected depending on load to be connected The device can be used together with a Light Management 3 wire
14. partment giving note of a brief description of the defect ALBRECHT JUNG GMBH amp CO KG Service Center Kupferstr 17 19 D 44532 L nen Service Line 0 23 55 80 65 51 Telefax 0 23 55 80 61 89 E Mail mail vki jung de General equipment Service Line 0 23 55 80 65 55 Telefax 0 23 55 80 62 55 E Mail mail vkm jung de instabus EIB equipment Service Line 0 23 55 80 65 56 Telefax 0 23 55 80 62 55 E Mail mail vkm jung de C The C sign is a free trade sign addressed exclusively to the authorities and does not include any warranty of any properties 16
15. y the snap on mask must be used see chapter Snap on mask on page 19 Light Management YIVINIG standard presence detector Ref no PMS 360 WW Snap on mask The snap on mask supplied with the detector can be used to blank out undesired zones or sources of interference see chapter Installation sources of interference on pages 11 13 by restricting the detection range of the device Important The device is delivered with the transparent snap on mask for protection of the lens system Remove the mask to obtain the maximum field of detection The mask is snap fitted on the lens system figure E The removed mask is cut out with scissors along the marked lines figure F Bereiche bis III Cutting out the mask changes the diameter of the detection field on the floor as follows Sectors through Ill see figure F cut outs sector l 2 approx 2 20 m Sector II cut out 2 approx 4 00 m Sectors II and Ill cut out 2 approx 6 00 m Without mask 2 approx 8 00 m The figures are based on a fitting height of approx 2 50 m Adaptation of sensor to the lighting conditions of the monitored surface To prevent the presence detector from being switched out again by the lamp it has just activated brightness exceeded the detector must be adjusted to the actual lighting conditions Light Management YIVINIG standard presence detector Ref no PMS 360 WW The adjustment must therefore be made u
16. y be switched on from an extension unit The shut off brightness in this case is approximately 400 lux This setting permits to deactivate the automatic detection mode Typical application orientation lighting in residential rooms Snap trimming ring back onto the detector after the adjustment The nose of the brightness sensor must engage in the corresponding notch in trimming ring 3 The test LED 4 is useful for diagnosis and adjustment see chapter Test LED functions on page 27 and is visible only after removal of the trimming ring Light Management YIVINIG standard presence detector Ref no PMS 360 WW Installation and test mode e Install the insert e Connect the lamps e g workplace illumination and the power supply e Snap the presence detector onto the insert e Set the time potentiometer to the shortest interval test 1 sec see figure D e Set the lux potentiometer to daytime operation sun symbol see figure D e Switch on the power supply time 10min 10s test 30min The lamps connected are switched on by the presence detector for a measuring cycle of abt 1 minute During the measuring cycle no operation is possible After this time the device switches off and is then in the test mode Each movement now detected switches on the device for at least 1 second with retriggering function A walking test to check the field of detection can now be performed If necessar

Download Pdf Manuals

image

Related Search

Related Contents

Samsung 203B Vartotojo vadovas  Model 28811 Series DECT 6.0 Cordless Handset Speakerphone  JVC CA-UXS59 User's Manual  Graco 3A0590G User's Manual  MP-4000 Controller  INSTALLATION & OPERATION MANUAL - Garland    LED STAR SKY SERIES Star Sky Pro MKII USER`S MANUAL  Shooting – Mode d`emploi  Goldstar GH20 Owner's Manual  