1.     attached documents     6 Installation    The relevant national regulations and the  generally recognized rules of engineering  apply for the installation and operation     The improper installation and operation  of safety switches may result in the  invalidation of the guarantee     6 1 Mounting    The switch can be mounted without opening  its enclosure  with the exception of the 10 A  safety switch      When being mounted directly onto the wall   the safety switches shall rest evenly only at  the fastening points provided for them    The chosen screw shall match the fastening  hole  see dimensional drawing  and they shall  not damage the hole  e g  use of a washer      The safety switches are to be fastened to all  fastening spots     If the screws are overtightened  the  apparatus may be damaged     6 2 Opening the device   Electrical connection    Before opening the apparatus  ensure  that it has been isolated from the voltage  supply  or take appropriate protective  meassures     Before opening   set the switch to the    ON     position     Switching at the shaft of the switch base  while the enclosure is open  is not  permitted  in order that the switch can be  properly reclosed      The electrical connection of the apparatus  may only be carried out by skilled staff     After dismantling built in components in  order to facililate the introduction of  cables  such components will have to be  properly fitted in again prior to the  electrical connection     The prop
2.    250 A  Tension nominale    Courant nominal    Fusible de court circuit adm  plac   en amont   Puissance de coupure AC 23     1 2 3 Interrupteur de s  curit   400 A  Tension nominale    Courant nominal    Fusible de court circuit adm  plac   en amont   Puissance de coupure AC 23     1 2 4 Interrupteur de s  curit   630 A  Tension nominale    Courant nominal    Fusible de court circuit adm  plac   en amont   Puissance de coupure AC 23     Interrupteurs de s  curit    type industriel KO     20  C     40  C  standard catalogue      40  C     80  C  IP 65  standard catalogue   Il  avec plaque m  talique    2 50 Nm  1 65 Nm  2 50 Nm  3 50 Nm  5 00 Nm   7 5 Nm par ex  type  E1WF e  Ex e   10 0 Nm par ex  type  E1WF e  Ex e   15 0 Nm par ex  type  E1WF e  Ex e   25 0 Nm tpar ex  type  E1WF e  Ex e   30 0 Nm par ex  type  E1WF e  Ex e   45 0 Nm par ex  type  E1WF e  Ex e     T  le d   acier avec rev  tement par poudre de  polyester    Type Moeller  P7  3 p  les  400 V  50 60 Hz   160A   160 A gG gL   160 A    Type Moeller  P7  3 p  les  400 V  50 60 Hz   250A   250 A gG gL   250A    Type Moeller  P7  3 p  les  400 V  50 60 Hz   400 A   400 A gG gL   400 A    Type Moeller  P7  3 p  les  400 V  50 60 Hz   630 A   800 A gG gL   630 A    Cooper Crouse Hinds GmbH 9    4 Domaine d utilisation    Les interrupteurs de s  curit   conviennent au  service dur en zone industrielle     Pour l   enveloppe  y compris les pieces  m  talliques ext  rieures  des mati  res de  qualit   sup  rieure on
3.    appareil  Fermeture du couvercle    Le garrot de l interrupteur de s  curit   doit    tre mis en position    MARCHE     Lorsque le  couvercle est pos    il faut veiller    ce que  l axe de l interrupteur s engage dans le trou  d entra  nement du garrot de l interrupteur     Tout corps   tranger doit   tre   t   de  l appareil     Le couvercle du bo  tier doit   tre ferm   et  verrouill   avec la cl   sp  ciale pr  vue    cet  effet     6 6 Mise en service    Avant la mise en service de l appareil  les  v  rifications sp  cifi  es dans les r  glements  nationaux individuels devront   tre ex  cut  es   De plus  il faudra v  rifier son fonctionnement  et installation corrects en conformit   avec ce  mode d   emploi et avec d   autres r  glements y  applicables     L utilisation incorrecte de ces  commutateurs peut annuler la garantie     7 Maintien Entretien    La r  glementation nationale en vigueur  pour le maintien et l entretien du mat  riel    lectrique devra   tre respect  e     Avant d ouvrir l enveloppe  d  brancher  l appareil de la tension ou prendre des  mesures pr  ventives appropri  es     Les intervalles de service requis d  pendent  de l emploi sp  cifique et devront donc   tre  fix  s par l utilisateur en tenant compte des  conditions d   utilisation     En particulier  le fonctionnement fiable du  verrouillage du couvercle ainsi que  l int  grit   du dispositif de verrouillage  devront   tre v  rifi  s     Si  lors d   un entretien  on constate que des  trava
4.    personal erfolgen     Nach der Demontage von Einbauten zur  leichteren Einf  hrung der Kabel und  Leitungen muss das Einbauger  t vor dem  elektrischen Anschluss wieder ordnungs   gem     montiert werden     Die ordnungsgem     abisolierten Anschluss   leitungen der Kabel sind unter Ber  cksichti   gung einschl  giger Vorschriften anzuschlie   Ben     Die Isolation der Anschlussleitungen  muss bis an die Klemme heranreichen     e    GOOPER Crouse Hinds    Der Leiter selbst darf nicht besch  digt  sein     Die minimal und maximal anschlie  baren  Leiterquerschnitte sind zu beachten     Alle Schrauben und  oder Muttern der  Anschlussklemmen  auch die der nicht  benutzten  sind fest anzuziehen     Achtung    Das Aufpressen der Kabelschuhe auf das  Kabel ist fachgem     durchzuf  hren    Es ist sicherzustellen  dass die erfor   derlichen Mindestluftstrecken eingehalten  werden     6 3 Kabel und Leitungs   einf  hrungen  KLE    Verschluss Stopfen    Es d  rfen generell nur geeignete KLE und  Verschluss Stopfen verwendet werden     F  r bewegliche Leitungen sind  Trompetenverschraubungen oder andere  geeignete Einf  hrungen mit zus  tzlicher  Zugentlastung zu verwenden     Die f  r die eingebauten KLE ma  geben   den Montagerichtlinien sind zu beachten     Beim Einsatz von KLE mit einer niedrigeren  als der f  r das Ger  t zutreffenden IP   Schutzart  siehe Seite 3   wird die IP   Schutzart des gesamten Ger  tes reduziert     Nicht benutzte Einf  hrungs  ffnungen sind mit  einem
5.   Wartung   5 9 Disposal Recycling                8 8 Reparation Remise en   tat         11  8 Reparatur   Instandsetzung 5 10 Declaration of conformity       12 9 Evacuation des d  chets              9 Entsorgung   Wieder           Recyclage See 11  VErWErtUNGg    nersnnnnnsnnnnnnnnnnnn 5 10 D  claration de conformit              12  10 Konformit  tserkl  rung         12       Mm  Gel  N    2 Cooper Crouse Hinds GmbH D e Crouse Hinds    2 Sicherheitshinweise    Die Sicherheitsschalter sind nicht  f  r explosionsgef  hrdete  Bereiche geeignet     Zielgruppe dieser Anleitung sind Elektro   fachkr  fte und Unterwiesene Personen     Umbauten oder Ver  nderungen an den  Sicherheitsschaltern sind nicht gestattet   Sie sind bestimmungsgem     in unbe   sch  digtem und einwandfreiem Zustand  zu betreiben    Als Ersatz und zur Reparatur d  rfen nur  Originalteile von Cooper Crouse Hinds    CEAG verwendet werden     Reparaturen d  rfen nur von Cooper  Crouse Hinds   CEAG oder einer qualifi   zierten Elektrofachkraft in   bereinstim   mung mit national geltenden Regeln  durchgef  hrt werden    Vor Inbetriebnahme m  ssen die  Sicherheitsschalter entsprechend der im  Abschnitt 6 genannten Anweisung  gepr  ft werden    Alle Fremdk  rper m  ssen vor der ersten  Inbetriebnahme aus den Sicherheits   schaltern entfernt werden    Die Deckel der Sicherheitsschalter sind  nur in  EIN  Stellung abnehmbar   Beachten Sie die nationalen Sicherheits   und Unfallverh  tungsvorschriften und die  nachfo
6.  En caso necesario podr   solicitar de  su representante Cooper Crouse Hinds    CEAG estas instrucciones de servicio    en  otro idioma de la Union Europea      Se desiderate la traduzione del  manuale operativo in un   altra lingua  della Comunit    Europea   potete richiederla al vostro  rappresentante Cooper Crouse Hinds    CEAG      En   vers  ttning av denna montage   och sk  tselinstruktion till annat EU    spr  k kan vid behov   best  llas fran Er Cooper Crouse Hinds    CEAG  representant     Betriebsanleitung  Sicherheitsschalter Industriebaureihe    KO    Operating instructions  Safety switches  Industrial design    COOPER Crouse Hinds KO    Mode d   emploi    Interrupteurs de s  curit    Type industriel     KO    GHG 980 700x P0001 D E F  _          CEAG     Se for necess  ria a traduc  o destas  instrug  es de opera    o para outro  idioma da   Uni  o Europeia  pode solicita la junto  do seu representante Cooper Crouse   Hinds   CEAG      Indien noodzakelijk kan de vertaling  van deze gebruiksinstructie in een  andere EU taal worden   opgevraagd bij Uw Cooper Crouse   Hinds   CEAG   vertegenwoordiging      Montagevejledningen kan overs  ttes  til andre EU sprog og rekvireres hos  Deres   Cooper Crouse Hinds   CEAG  leverandor      Tarvittaessa t  m  n k  ytt  ohjeen  k    nn  s on saatavissa toisella EU n  kielell   Teid  n   Cooper Crouse Hinds   CEAG    edustajaltanne      Eav yxpe  aode    uetappaon   TOY oodnylov   xpnosws oe ai   yAwooa tys  EE  unrope   va   
7.  Verschluss Stopfen zu verschlie  en   um die Mindestschutzart herzustellen     Es ist darauf zu achten  dass bei der  nstallation der KLE die f  r den Leitungs   durchmesser geeigneten Dichtungseins  tze  verwendet werden  Bei ausschneidbaren  Dichtungseins  tzen ist sicherzustellen dass  der Einsatz ordnungsgem     dem Leitungs   durchmesser angepasst wird        Zur Sicherstellung der erforderlichen  Mindestschutzart sind die KLE fest anzuzie   hen     Bei   berm    igem Anziehen kann die  Schutzart beeintr  chtigt werden     6 4 Flanschplatten    M  ssen Flanschplatten demontiert werden   z B  zum Bohren von Einf  hrungs  ffnungen    ist bei der Montage zur Aufrechterhaltung  der Mindestschutzart auf den korrekten Sitz  der Flanschplatte zu achten     Metallische Flanschplatten m  ssen in den    Potentialausgleich miteinbezogen  werden     COOPER Crouse Hinds    Sicherheitsschalter  Industriebaureihe KO    6 5 Schlie  en des Ger  tes    Deckelverschluss    Der Schaltgriff der Sicherheitsschalter muss  in der EIN   Stellung stehen  Beim Aufsetzen  des Deckels ist darauf zu achten  dass die  Achse des Schalters in die Mitnehmer  ffnung  des Schaltgriffes eingreift     Alle Fremdk  rper sind aus dem Ger  t zu  entfernen     Zum Schlie  en des Ger  tes ist der  Geh  usedeckel mit dem Innenvierkant   schl  ssel des Vorreiberschlosses zu  verschlie  en     6 6 Inbetriebnahme    Vor Inbetriebnahme des Betriebsmittels sind  die in den einzelnen nationalen Bestimmun   gen genannte
8.  down     Overtightening might impair the  protection category     6 4 Flange plates    Should flange plates have to be removed  e   g  for drilling entry openings   attention will  have to be paid to the proper fit of the flange  plate while mounting in order to maintain the  minimum protection category     Metal flange plates shall be included in  the potential equalisation     8 Cooper Crouse Hinds GmbH    Safety switches  industrial design KO    6 5 Closing the device   cover closure    The switch toggle of the safety switches shall  be in ON position  When placing the cover  take care that the shaft of the switch engages  in the tappet hole of the switch toggle     Any foreign matter shall be removed from  the apparatus     To close the apparatus the enclosure cover  shall be closed using the internal square  spanner of the catch lock     6 6 Taking into operation    Prior to taking the apparatus into operation   the tests specified in the relevant national  regulations are to be carried out  Apart from  that  the correct functioning and installation of  the apparatus in accordance with these  operating instructions and other applicable  regulations shall be checked     The improper operation of safety  switches may result in the invalidation of  the guarantee     7 Maintenance Servicing    The relevant national regulations which  apply to the maintenance servicing of  electrical apparatus  shall be observed     Before opening the enclosure make sure  that the apparatus 
9.  or supplement of the  product range     e i  COOPER Crouse Hinds    2 Consignes de s  curit      Les interrupteurs de s  curit   ne  conviennent pas    l   emploi en  atmosph  re explosive     Les interrupteurs de s  curit   ne doivent  pas   tre ni transform  s ni modifi  s    Seuls des interrupteurs de s  curit   intacts  et parfaits doivent   tre employ  s pour la  fonction qui leur est d  volue    Seules des pi  ces de rechange  homologu  es d   origine Cooper Crouse   Hinds   CEAG doivent   tre utilis  es comme  remplacement et pour des r  parations   Des r  parations ne doivent   tre ex  cut  es  que par Cooper Crouse Hinds   CEAG ou  par un   lectricien qualifi   en conformit    avec la r  glementation nationale en  vigueur    Avant la mise en service  les interrupteurs  de s  curit   doivent   tre v  rifi  s selon  instruction donn  e dans la section 6   Avant la premi  re mise en service  tout  corps   tranger doit   tre   t   de  l interrupteur de s  curit      Le couvercle de l interrupteur de s  curit    ne peut   tre enlev   qu   en position     ferm  e       Respectez les prescriptions nationales de  s  curit   et de pr  voyance contre les  accidents ainsi que les consignes de  s  curit   qui suivent dans ce mode  d emploi et qui sont mis en italique  comme ce texte     3 Conformit   avec les normes    Les interrupteurs de s  curit   remplissent les  propri  t  s de s  paration selon   DIN EN 60947 et poss  dent la puissance de  coupure de moteur AC 23 selon   
10. 500 A   500 A  500 A gG gL   500 A   350A    Type ABB OETL  6 p  les  400 V  690 V 50 60 Hz  630 A   630 A 630 A gG gL   630 A  350A    Les donn  es techniques des diff  rents   l  ments d installation doivent   tre prises des    guides correspondants     Des dessins de mesure et des stromlaufplaene d   lectricit   extraire vous des    documents ci joints     6 Installation    Pour l installation et l exploitation de ces  appareils  la reglementation nationale en  vigueur  en Allemagne par ex  ElexV  loi de  s  curit   des appareils  ainsi que les r  gles  de la technique g  n  ralement reconnues  devront   tre respect  es     L installation ou l   utilisation incorrecte de  ces interrupteurs de s  curit      bornes  peut entra  ner la perte de la garantie     6 1 Montage    Le montage de l   appareil peut se faire sans  ouvrir l enveloppe     Dans le cas d un montage directement au  mur  les interrupteurs ne doivent reposer au  niveau du mur que sur les points de fixation  pr  vus    La vis choisie doit   tre en rapport avec le  pas de fixation  voir plan cot    et ne doit pas  avarier celui ci  par ex  emploi d   une  rondelle      Les interrupteurs de s  curit   doivent   tre  attach  s    tous les points d ancrage     Un serrage excessif des vis de fixation  peut endommager l appareil     Reportez vous    la notice de montage  correspondante     6 2 Ouverture de l   appareil    Raccordement   lectrique    Avant ouverture de l   enveloppe  mettre  l appareil hors tension e
11. DIN EN 60947     De plus  les interrupteurs de s  curit    correspondent    d   autres exigences comme  par ex     ceux de la norme EN 60947 3    DIN EN 60947 ainsi qu      la directive CE  concernant du mat  riel   lectrique pour     emploi en des limites de tension d  finies   73 23 CEE      Is ont   t   con  us  construits et test  s selon       tat actuel de la technique et selon DIN EN  SO 9001        A a  COOPER Crouse Hinds    1 Caract  ristiques techniques    1 1 Donn  es techniques   Temp  rature ambiante admissible    D   autres temp  ratures sont possibles avec des mod  les sp  ciaux   Temp  de stockage dans l emballage original   Indice de protection selon EN 60529 CEI 529   Classe d   isolation selon EN 60598 CEI 598   Couples de serrage test  s    Vis du couvercle   Ecrou borgne bas de l entr  e plastique M12  Ecrou borgne bas de entr  e plastique M16 M20  Ecrou borgne bas de l entr  e plastique M25  Ecrou borgne bas de l   entr  e plastique M32 M50  Ecrou borgne bas de l entr  e m  tallique M 16  Ecrou borgne bas de l   entr  e m  tallique M 20  Ecrou borgne bas de l   entr  e m  tallique M 25  Ecrou borgne bas de l   entr  e m  tallique M 32  Ecrou borgne bas de l   entr  e m  tallique M 40  Ecrou borgne bas de l   entr  e m  tallique M 50  Enveloppe  standard catalogue      1 2 1 Interrupteur de s  curit   160 A  Tension nominale    Courant nominal    Fusible de court circuit adm  plac   en amont   Puissance de coupure AC 23     1 2 2 Interrupteur de s  curit
12. Ex e metal cable entry M16 7 5 Nm  Cap nut of the Ex e metal cable entry M20 10 0 Nm e g   Cap nut of the Ex e metal cable entry M25 15 0 Nm e g   Cap nut of the Ex e metal cable entry M32 25 0 Nm e g   Cap nut of the Ex e metal cable entry M40 30 0 Nm e g   Cap nut of the Ex e metal cable entry M50 45 0 Nm e g     Enclosure material  catalogue version      1 2 Safety switch 160 A Type Moeller  P7  3 pole   Rated voltage  400 V  50 60 Hz  Rated current  160A   Perm  short circuit back up fuse  160 A gG gL  Switching capacity AC 23  160A    1 2 2 Safety switch 250 A Type Moeller  P7  3 pole  Rated voltage  400 V  50 60 Hz    Rated current  250 A  Perm  short circuit back up fuse  250 A gG gL  Switching capacity AC 23  250A    1 2 3 Safety switch 400 A Type Moeller  P10  3 pole  Rated voltage  400 V  50 60 Hz    Rated current  400A  Perm  short circuit back up fuse  400 A gG gL  Switching capacity AC 23  400A    1 2 4 Safety switch 630 A Type Moeller  P10  3 pole  Rated voltage  400 V  50 60 Hz    Rated current  630 A  Perm  short circuit back up fuse  800 A gG gL  Switching capacity AC 23  630 A    type  type  type  type  type     20   C up to  40   C  standard version     IP 65  standard version   Il   with metal flange    e g  type E1WF e  Ex e     E1WF e  Ex e   E1WF e  Ex e   E1WF e  Ex e   E1WF e  Ex e   E1WF e  Ex e     Sheet steel with powder coating    e    GOOPER Crouse Hinds    4 Field of application    The safety switches are suitable for heavy   duty use in industr
13. a utiliser  des presses   toupes    trompette ou  d   autres entr  es convenables avec  d  charge de traction suppl  mentaire     Les directives pour le montage  applicables aux entr  es de c  ble mont  es  doivent   tre respect  es     Si l indice de protection des entr  es de c  ble  mont  es est inf  rieur    celui de l appareil     indice de protection de l   ensemble sera  r  duit    Des ouvertures d   entr  e non utilis  es doivent    tre ferm  es avec un bouchon de fermeture  certifi   pour   tablir l indice de protection  minimum    Lors du montage des entr  es de c  ble il  audra veiller    ce que des garnitures  d   tanch  it   correspondant au diam  tre du  c  ble soient utilis  es  En cas de garnitures  qui doivent   tre coup  es sur mesure  il  audra faire attention    ce que la garniture soit  adapt  e au diam  tre du c  ble    Les entr  es de c  ble doivent   tre serr  es     ond afin de maintenir l indice de protection  minimum        Au cas o   elles seraient forc  es  cela  pourrait   tre nuisible    l indice de  protection     6 4 Plaques brid  es    Au cas o   des plaques brid  es seraient  d  mont  es  par ex  pour al  ser des  ouvertures d entr  e   il faudrait veiller au  propre logement de la plaque brid  e de  fixation lors du montage afin de maintenir  l indice de protection minimum     Des plaques brid  es en m  tal doivent   tre  int  gr  es dans la compensation de  potentiel     Interrupteurs de s  curit    type industriel KO    6 5 Fermeture de l
14. eclaration of consent from Messrs   Cooper Crouse Hinds   CEAG     During operation the instructions stated  in section 7 of the operating instructions  Shall be observed     The sole responsibility with respect to the  suitability and proper use of the control  switches according to the basic  requirements of these instructions  see  technical data  lies with the operator     A a  COOPER Crouse Hinds    Safety switches  industrial design KO    1 2 5 Safety switch 250 A Type ABB  OETL  6 pole    Rated voltage    Rated current    Perm  short circuit back up fuse   Switching capacity AC 23     400 V7690 V 50 60 Hz  270 A   400 A  400 A gG gL  250      250       1 2 6 Safety switch 315 A Type ABB  OETL  6 pole    Rated voltage    Rated current    Perm  short circuit back up fuse   Switching capacity AC 23     400 V  690 V 50 60 Hz  315      400 A  400 A gG gL  315A 315A    1 2 7 Safety switch 400 A Type ABB  OETL  6 pole    Rated voltage    Rated current    Perm  short circuit back up fuse   Switching capacity AC 23     400 V  690 V 50 60 Hz  500 A   500 A   500 A gG gL  500 A  350 A    1 2 8 Safety switch 630 A Type ABB  OETL  6 pole    Rated voltage    Rated current    Perm  short circuit back up fuse   Switching capacity AC 23     400 V 690 V 50 60 Hz  630 A   630 A   630 A gG gL  630 A   350 A    The technical data of the individual installation elements must be taken out from the respective  operating instructions  Dimensional drawings and circuit diagrams take you from the
15. erly bared conductors of cables  shall be connected with due regard to the  respective regulations     The insulation shall reach up to the  terminal  The conductor itself shall not be  damaged     The minimum and maximum conductor    cross sections that can be connected  Shall be observed      Cooper Crouse Hinds GmbH 7    All screws and or nuts of the supply  terminals  also of those remaining vacant   shall be tightened down     Attention   The cable lugs should be crimped onto the  cable in a workmanlike manner     6 3 Cable entries  KLE    blanking plugs    Generally  only certified cable entries and  blanking plugs may be used     Flexible cables shall be used with  trumpet shaped cable glands or other  suitable entries with additional pull relier     The directives for mounting applicable to  the cable entries fitted shall be observed     When mounting cable entries of a lower IP  protection than that of the apparatus  see  page 8   the IP protection of the whole unit will  be reduced     In order to establish the minimum protection  category  unused entry holes shall be closed  with a certified blanking plug     Care has to be taken that when fitting the  cable entries  sealing inserts appropriate to  the cable diameter be used  In case of  sealing inserts that are cut out  it will have to  be ensured that the insert is properly  adapted to the cable diameter     In order to ensure the required minimum  protection category  the cable entries will  have to be tightened
16. etroffene Betriebsmittel an  Cooper Crouse Hinds   CEAG zur  Reparatur zur  ckzugeben     Umbauten oder   nderungen am Betriebsmit   tel sind nicht gestattet  ausgenommen ist das  Anbringen von zus  tzlichen KLE im Rahmen  der Zulassung des Betriebsmittels     9 Entsorgung  Wiederverwertung    Bei der Entsorgung des Betriebsmittels sind  die jeweils geltenden nationalen Abfall   beseitigungsvorschriften zu beachten    Zur Erleichterung der Wiederverwertbarkeit  von Einzelteilen sind Kunststoffteile mit dem  Kennzeichen des verwendeten Kunststoffes  versehen    Programm  nderungen und    erg  nzungen sind vorbehalten     Cooper Crouse Hinds GmbH 5    2 Safety instructions    The safety switches are not  suitable for hazardous areas     For skilled electricians and  trained person in accordance with  national legislation  including the relevant  standards and  where applicable     Modifications to the safety switch or  changes of its design are not permitted     They shall be used for their intended  purpose and in perfect and clean  condition    For replacement and repair  only genuine  Cooper Crouse Hinds   CEAG spare parts  Shall be used     Repairs may only be carried out by  Cooper Crouse Hinds   CEAG or a  qualified electrician in compliance with  the respective national regulations     Prior to their taking into operation  the  safety switches shall be checked in  accordance with the instructions as per  section 6     Before the initial operation  any foreign  matter wil
17. heitsschalter 160 A  Bemessungsspannung   Bemessungsstrom    Zul  ssige Kurzschlussvorsicherung   Schaltverm  gen AC 23     1 2 2 Sicherheitsschalter 250 A  Bemessungsspannung   Bemessungsstrom    Zul  ssige Kurzschlussvorsicherung   Schaltverm  gen AC 23     1 2 3 Sicherheitsschalter 400 A  Bemessungsspannung   Bemessungsstrom    Zul  ssige Kurzschlussvorsicherung   Schaltverm  gen AC 23     1 2 4 Sicherheitsschalter 630 A  Bemessungsspannung   Bemessungsstrom    Zul  ssige Kurzschlussvorsicherung   Schaltverm  gen AC 23      20   C bis  40   C  Listenausf  hrung      40   C bis  80   C   IP 65  Listenausf  hrung    bis 690 V   Il   mit Metallflansch   laut Auftrag  im Rahmen der Bescheinigung    2 50 Nm  1 65 Nm  2 50 Nm  3 50 Nm  5 00 Nm   7 5 Nm z B  Typ E1WF e   Ex e   10 0 Nm z B  Typ E1WF e   Ex e   15 0 Nm z B  Typ E1WF e   Ex e   25 0 Nm z B  Typ E1WF e   Ex e   30 0 Nm z B  Typ E1WF e   Ex e   45 0 Nm z B  Typ E1WF e   Ex e     Stahlblech Pulverbeschichtet    Typ Moeller  P7  3 polig    400 V  50 60 Hz  160 A   160 A gG gL  160 A    Typ Moeller  P7  3 polig    400 V  50 60 Hz  250 A   250 A gG gL  250 A    Typ Moeller  P10  3 polig    400 V  50 60 Hz  400 A   400 A gG gL  400 A    Typ Moeller  P10  3 polig    400 V  50 60 Hz  630 A   800 A gG gL  630 A    Cooper Crouse Hinds GmbH    4 Verwendungsbereich    Die Sicherheitsschalter sind zum Einsatz in  rauhen Industriebereichen geeignet     Die eingesetzten Geh  usematerialien  einschlie  lich der au  enliegenden Meta
18. hen Daten der einzelnen Einbauelemente m  ssen den entsprechenden    Anleitungen entnommen werden     Ma  zeichnungen und Stromlaufpl  ne entnehmen Sie den beigef  gten Unterlagen     6 Installation    F  r das Errichten   Betreiben sind die  relevanten nationalen Vorschriften sowie die  allgemein anerkannten Regeln der Technik  ma  gebend     Unsachgem    e Installation und Betrieb  der Sicherheitsschalter kann zum Verlust  der Garantie f  hren     6 1 Montage    Die Montage des Ger  tes kann ohne   ffnen  des Geh  uses erfolgen     Die Sicherheitsschalter d  rfen bei der  Direktmontage an der Wand nur an den  vorgesehenen Befestigungspunkten eben  aufliegen  Die gew  hlte Schraube muss der  Befestigungs  ffnung angepasst sein  siehe  Ma  bild  und sie darf die   ffnung nicht  besch  digen  z B  Verwendung einer  Unterlegscheibe      Die Sicherheitsschalter sind an allen  Befestigungspunkten zu befestigen     Bei   berm    igem Anziehen der Befesti   gungsschrauben  kann das Ger  t besch     digt werden     6 2   ffnen des Ger  tes    Elektrischer Anschluss    Vor   ffnen der Ger  te ist die Spannungs   freiheit sicherzustellen bzw  sind geignete  Schutzma  nahmen zu ergreifen     Vor dem   ffnen ist der Schalter in  EIN    Stellung zu schalten     Ein Schalten an der Achse des Schalter   sockels bei ge  ffnetem Geh  use ist nicht  zul  ssig  um den Schalter wieder korrekt  schlie  en zu k  nnen      Der elektrische Anschluss des Betriebs   mittels darf nur durch Elektrofach
19. ial areas        The enclosure materials employed  including  the exterior metal parts  are made of high   quality materials which ensure a corrosion  protection and resistance to chemical  substances corresponding to the  requirements in a    normal industrial  atmosphere        In case of use in an extremely aggresive  atmosphere  please refer to manufacture    5 Application   Properties    When maintenance  cleaning and repair work  is carried out on systems  machinery and  drives  the safety switches ensure the  reliable switching off on on poles of electrical  energy     In addition to this  the safety switches are so  designed  that they also switch off the drive   e g  via the contactor that precedes the  auxiliary contacts  In relation to the main  contacts  this auxiliary contacts are lagging  while making and leading while breaking     Due to the mechanical design of the safety  switch  compulsory opening of the contacts is  possible     The safety switches fulfil the isolating  properties according to DIN EN 60 947 3    IEC 947 3      To prevent unauthorized switching  the  switches can be locked in the    OFF    position  by means of 3 padlocks  see Fig  1   shackle  diameter of the padlocks up to 4 6 mm      A built in locking device prevents the opening  of the enclosure in the    OFF    position     The data according to sections 3 and 4  Shall be taken into account during use     Applications other than those described  are not permissible without a written  d
20. igen     Andere als die beschriebenen Anwendun   gen sind ohne schriftliche Erkl  rung der  Fa  Cooper Crouse Hinds   CEAG nicht  zul  ssig     Beim Betrieb sind die in der Betriebsanlei   tung unter Punkt 7 genannten Anweisun   gen zu beachten     Die Verantwortung hinsichtlich bestim   mungsgem    er Verwendung dieser  Sicherheitsschalter unter Bezugnahme  der in dieser Anleitung vorhandenen  Rahmenbedingungen  siehe technische  Daten  liegt allein beim Betreiber     4 Cooper Crouse Hinds GmbH    Sicherheitsschalter  Industriebaureihe KO    1 25  Sicherheitsschalter 250 A  Bemessungsspannung   Bemessungsstrom 40  C    Zul  ssige Kurzschlussvorsicherung   Schaltverm  gen AC 23     1 2 6 Sicherheitsschalter 315 A  Bemessungsspannung   Bemessungsstrom 40  C    Zul  ssige Kurzschlussvorsicherung   Schaltverm  gen AC 23     1 2 7 Sicherheitsschalter 400 A  Bemessungsspannung   Bemessungsstrom 40  C    Zulassige Kurzschlussvorsicherung   Schaltverm  gen AC 23     1 2 8 Sicherheitsschalter 630 A  Bemessungsspannung   Bemessungsstrom 40  C    Zul  ssige Kurzschlussvorsicherung   Schaltverm  gen AC 23     Typ ABB OETL  6 polig    400 V  690 V 50 60 Hz  270 A   400 A  400 A gG gL  250      250 A    Typ ABB OETL  6 polig    400 V   690 V 50 60 Hz  315      400 A  400 A gG gL  315A 315A    Typ ABB OETL  6 polig    400 V 690 V 50 60 Hz  500 A   500 A   500A gG gL   500 A   350 A    Typ ABB OETL  6 polig    400 V  690 V 50 60 Hz  630 A   630 A   630 A gG gL  630 A   350 A    Die Technisc
21. int  gr   pr  vient  l ouverture de l enveloppe en position  ARR  T     Pour l emploi  les consignes des sections  3 et 4 devront   tre respect  es     Des emplois autres que ceux d  crits ne  sont admis qu   avec l approbation   crite  de Cooper Crouse Hinds   CEAG     Lors de l   utilisation  les instructions selon  point 7 de ce mode d   emploi doivent   tre  respect  es     Seul l utilisateur est responsable de  l emploi comme pr  vu de interrupteur de  s  curit    en tenant compte des conditions  g  n  rales expos  es dans la notice  voir  Caract  ristiques techniques      Interrupteurs de s  curit    type industriel KO    1 2 5 Interrupteur de s  curit   250 A  Tension nominale    Courant nominal    Fusible de court circuit adm  plac   en amont   Puissance de coupure AC 23     1 2 5 Interrupteur de s  curit   315 A  Tension nominale    Courant nominal    Fusible de court circuit adm  plac   en amont   Puissance de coupure AC 23     1 2 5 Interrupteur de s  curit   400 A  Tension nominale    Courant nominal    Fusible de court circuit adm  plac   en amont   Puissance de coupure AC 23     1 2 5 Interrupteur de s  curit   630 A  Tension nominale    Courant nominal    Fusible de court circuit adm  plac   en amont   Puissance de coupure AC 23     Type ABB OETL  6 p  les  400 V   690 V 50 60 Hz  270 A   400 A  400 A gG gL   250 A 250A    Type ABB OETL  6 p  les  400 V  690 V 50 60 Hz  315A   400 A   400 A gG gL   315 A 315 A    Type ABB OETL  6 p  les  400 V  690 V 50 60 Hz  
22. is disconnected from  the supply  or take the appropriate  protective measures     The required maintenance intervals depend  on the respective application and shall  therefore be determined by the user  dependent on the conditions of use    When servicing the apparatus  particularly  those parts that are decisive for the type of  protection against explosion  shall be  checked  e  g  intactness of the enclosure   cable glands  efficacy of the gaskets      The reliable working of the cover lock and  the integrity of the padlocking device  Shall be especially checked     If during servicing repairs prove to be neces   sary  section 8 of these operating instructions  shall be observed     8 Repairs Overhaul    Repairs may only be carried out with genuine  Cooper Crouse Hinds   CEAG spare parts     In case the switch base is damaged  only  its replacement will be permitted  In case  of doubt  the respective apparatus will  have to be returned for repair to Cooper  Crouse Hinds   CEAG     Modifications to the apparatus or changes of  its design are not permitted  except for the  mounting of additional cable entries in accor   dance with the approval of the apparatus     9 Disposal Recycling    When the apparatus is disposed of  the  respective national regulations on waste  disposal shall be observed    In order to facilitate the recycling of individual  components  plastic parts are provided with  the identification mark of the plastic material  used     Subject to modifications
23. l have to be removed from the  safety switch    The safety switch cover can only be  removed in    On    position     Observe the national safety rules and  regulations for prevention of accidents as  well as the safety instructions included in  these operating instructions set in italics  the same as this text     3 Conformity with standards    The safety switches fulfil the isolating  properties acc  to DIN EN 60947 as well as  the AC 23 motor switching capacity acc  to  DIN EN 60947     The safety switches meet further  requirements such as those of the   DIN EN 60947 3  IEC 947 3 and the EC  directive on electromagnetic compatibility  89   336 EEC  as well as of the EC directive on  electrical equipment for use within defined  voltage limits  73 23 EEC      They have been designed  manufactured    and tested according to the state of the art  and to DIN ISO 9001     6 Cooper Crouse Hinds GmbH    Safety switches  industrial design KO    1 Technical Data    1 1 Technical details   Perm ambient temperature    Deviating temperatures possible with special versions   Perm storage temperature in original packing   Degree of protection  to EN 60529 IEC 529   Insulation class acc  to EN 60598   IEC 598   Test torques      40   C to  80   C    Cover screws 2 50 Nm  Cap nut of the plastic cable entry M12 1 65 Nm  Cap nut of the plastic cable entry M16   M20 2 50 Nm  Cap nut of the plastic cable entry M25 3 50 Nm  Cap nut of the plastic cable entry M32   M 63 5 00 Nm  Cap nut of the 
24. lgenden Sicherheitshinweise in  dieser Betriebsanleitung  die wie dieser  Text in Kursivschrift gefasst sind     3 Normenkonformit  t    Die Sicherheitsschalter erf  llen die Trenn   eigenschaften nach DIN EN 60947 sowie das  Motorschaltverm  gen AC 23 nach   DIN EN 60947     Weitere Anforderungen wie die IEC 947   3   die EG  Richtlinie Elektromagnetische  Vertr  glichkeit  89 336 EWG  sowie die EG   Richtlinie f  r elektrische Betriebsmittel zur  Verwendung innerhalb bestimmter  Spannungsgrenzen  73 23  EWG  werden  von den Sicherheitsschaltern erf  llt        Sie wurden entsprechend dem Stand der  Technik und gem     DIN EN ISO 9001  entwickelt  gefertigt und gepr  ft     COOPER Crouse Hinds    Sicherheitsschalter  Industriebaureihe KO    1 Technische Daten    14 Technische Angaben   Zul  ssige Umgebungstemperatur   Abweichende Temperaturen sind bei Sonderversionen m  glich   Zul  Lagertemperatur in Originalverpackung   Schutzart nach EN 60529 IEC 529    Nennspannung    Schutzklasse nach EN 60598 IEC 598   Leitungseinf  hrung    Pr  fdrehmomente    Deckelschrauben   Druckschraube der KLE M12  Druckschraube der KLE M16   M20  Druckschraube der KLE M25  Druckschraube der KLE M32   M 63  Druckschraube der Metall Ex  e KLE M16  Druckschraube der Metall Ex  e KLE M20  Druckschraube der Metall Ex  e KLE M25  Druckschraube der Metall Ex  e KLE M32  Druckschraube der Metall Ex  e KLE M40  Druckschraube der Metall Ex  e KLE M50  Geh  usematerial  Listenausf  hrung      1 2 1 Sicher
25. llteile  bestehen aus hochwertigen Werkstoffen die  einen anwendungsgerechten Korrosions   schutz und Chemikalienresistenz in  normaler  Industrieatmosph  re  gew  hrleisten     Bei einem Einsatz in extrem aggressiver  Atmosph  re  k  nnen Sie zus  tzliche Informa   tionen   ber die Chemikalienbest  ndigkeit der  eingesetzten Kunststoffe  bei Ihrer zust  ndi   gen Cooper Crouse Hinds Niederlassung  erfragen     5 Verwendung   Eigenschaften    Die Sicherheitsschalter dienen zur sicheren  allpoligen Abschaltung der elektrischen  Energie bei Wartungs   Reinigungs  und  Reparaturarbeiten an Anlagen  Maschinen  und Antrieben     Daneben sind die Sicherheitsschalter zur zu   satzlichen Abschaltung des Antriebes Uber  z B  das vorgeschaltete Sch  tz mit einem  Hilfskontakt ausger  stet  der gegen  ber den  Hauptkontakten beim Einschalten nacheilt  und beim Ausschalten voreilt     Der mechanische Aufbau der Sicherheits   schalter erm  glicht  dass die Kontakte  zwangsweise ge  ffnet werden     Die Sicherheitsschalter erf  llen die Trenn   eigenschaften entsprechend der  DIN EN 60 947 3   IEC 947 3      Die Sicherheitsschalter k  nnen in  AUS    Stellung mit 3 Vorh  ngeschl  sser gegen  unbefugtes Schalten gesichert werden  siehe  Bild 1  B  geldurchmesser der Vorh  nge   schl  sser von 4 bis 6 mm      Eine interne Verriegelungseinheit verhindert   dass ein   ffnen des Geh  uses in der  AUS    Stellung m  glich ist     Angaben aus Punkt 3 und 4 sind bei der  Verwendung zu ber  cksicht
26. n Pr  fungen durchzuf  hren   Au  erdem ist vor der Inbetriebnahme die  korrekte Funktion und Installation des  Betriebsmittels in   bereinstimmung mit dieser  Betriebsanleitung und anderen anwendbaren  Bestimmungen zu   berpr  fen     Unsachgem    er Betrieb der Sicherheits   schalter kann zum Verlust der Garantie  f  hren     7 Instandhaltung   Wartung   Die f  r die Wartung   Instandhaltung von  elektrischen Betriebsmitteln geltenden  nationalen Bestimmungen sind einzuhal   ten     Vor   ffnen des Geh  uses Spannungs   freiheit sicherstellen bzw  geeignete  Schutzma  nahmen ergreifen     Die erforderlichen Wartungsintervalle sind  anwendungsspezifisch und daher in Abh  n   gigkeit von den Einsatzbedingungen vom  Betreiber festzulegen    Im Rahmen der Wartung sind vor allem die  Teile  von denen die Schutzart abh  ngt  zu  pr  fen  z B  Unversehrtheit des Geh  uses   der Dichtungen und der Kabel  und Leitungs   einf  hrungen      Besonders zu pr  fen ist die sichere  Funktion der Deckelverriegelung sowie  die Unversehrtheit der Abschlie  vor   richtung     Sollte bei einer Wartung festgestellt werden   dass Instandsetzungsarbeiten erforderlich  sind  ist Abschnitt 8 dieser Betriebsanleitung  zu beachten     8 Reparatur   Instandsetzung    Instandsetzungsarbeiten   Reparaturen  d  rfen nur unter Verwendung von Cooper  Crouse Hinds   CEAG Originalersatzteilen  vorgenommen werden     Bei Sch  den am Leistungstrenner ist nur  ein Austausch zul  ssig  Im Zweifelsfalle  ist das b
27. nterrupteur de s  curit   630 A 6p 10  2 Sicherheitshinweise             3 2 Safety instructions                  6 2 Consignes de s  curit                   9  3 Normenkonformit  t       eg  NO 3 Conformity with standards    6 3 Conformit   avec les normes        9  4 Verwendungsbereich 4 4 Field of application                  7 4 Domaine d utilisation          aeaasee 10  5 Verwendung Eigenschaften 4 5 Application Properties  7 5 Utilisation Propri  t  s      10  6 Installation    wins 4 6 Installation          7 6 Installation        10  6 1 Montage SEENEN 4 6 1 Mounting    essees 7 6 1 Montage    nessen ase    TO  6 2   ffnen des Ger  tes  6 2 Opening the device  6 2 Ouverture de l   appareil        ted  Elektrischer Anschluss        4 Electrical connection               7 Raccordement   lectrique            10  6 3 Kabel  und Leitungs  6 3 Cable entry blanking plug  8 6 3 Entr  es de cable   einf  hrung  Verschluss 6 4 Flange plates    8 bouchon de fermeture    s s s    11  Stopfen               wa D 6 5 Closing the device  6 4 Plaques brid  es             11  6 4 Flanschplatten       esseeeeeee 5 cover closure                        8 6 5 Fermeture de l   appareil      6 5 Schlie  en des Ger  tes   6 6 Taking into operation       8 Fermeture du couvercle    11  Deckelverschluss     wi 5 7 Maintenance Servicing 8 6 6 Mise en service    11  6 6 Inbetriebnahme                     5 8 Repairs Overhaul          a 8 7 Maintien Entretien              van  D  7 Instandhaltung 
28. ntmds   ano   tov Avtimpoowxo tys Cooper  Crouse Hinds   CEAG     Sicherheitsschalter Safety switches  Industrial Interrupteurs de s  curit                                     Industriebaureihe design  KO Type industriel jusqu   a KO  KO  Inhalt  Contents  Contenu   INA E 2 Contents    2 CONTENU  an  dee 2  MaBbild                  2 Dimensional drawings   2 Plans cot  s 2  1 Technische Daten     in 2 1 Technical data                6 d Caract  ristiques techniques       9  1 1 Technische Angaben           3 1 1 Technical details            6 1 1 Donn  es techniques                   9  1 2 1  Sicherheitsschalter 160 A 3p 3 1 2 1 Safety switch 160 A 3p     6 1 2 1 Interrupteur de s  curit   160 A 3p 9  1 2 2  Sicherheitsschalter 250 A 3p 3 1 2 2 Safety switch 250 A 3p     6 1 2 2 Interrupteur de s  curit   250 A 3p 9  1 2 3 Sicherheitsschalter 400 A 3p 3 1 2 3 Safety switch 400 A 3p     6 1 2 3 Interrupteur de s  curit   400 A 3p 9  1 2 4  Sicherheitsschalter 630 A 3p 3 1 2 4 Safety switch 630 A 3p     6 1 2 4 Interrupteur de s  curit   630 A 3p 9  1 2 5 Sicherheitsschalter 250 A 6p 4 1 2 5 Safety switch 250 A 6p     7 1 2 5 Interrupteur de s  curit   250 A 6p 10  1 2 6  Sicherheitsschalter 315 A 6p 4 1 2 6 Safety switch 315 A 6p     7 1 2 6 Interrupteur de s  curit   315 A 6p 10  1 2 7 Sicherheitsschalter 400 A 6p 4 1 2 7 Safety switch 400 A 6p     7 1 2 7 Interrupteur de s  curit   400 A 6p 10  1 2 8  Sicherheitsschalter 630 A 6p 4 1 2 8 Safety switch 630 A 6p     7 1 2 8 I
29. t   t   employ  es qui  assurent une protection appropri  e contre la  corrosion et une r  sistance contre des  agents chimiques en  atmosph  re industrielle  normale        Avec un une application dans extr  me  agressif l atmosph  re  pouvoir vous  suppl  mentaire des information sur le la  stabilit   le commencer des mati  re  avec  votre comp  tent Cooper Crouse Hinds    tablir demander     5 Utilisation Propri  t  s    Les interrupteurs de s  curit   servent a la  coupure fiable de l   nergie   lectrique sur  tous les p  les  lorsque des travaux  d entretien  de nettoyage et de r  paration  sont ex  cut  s sur des syst  mes  des  machines et des appareils moteurs     En outre  les interrupteurs de s  curit   sont  en plus   quip  s pour la d  connexion de la  com mande  par ex  au moyen les contacts  de auxiliaires en combinaison avec les  contacteurs plac   en amont  Ce contacts de  auxiliaires est en retard des contacts  principaux lors de la mise en circuit et les  pr  c  de lors de la mise hors circuit     Gr  ce    la construction m  canique des inter   rupteurs de s  curit   il est possible que les  contacts soient    ouverture forc  e  Ils  remplissent les propri  t  s de coupure selon  DIN EN 60 947 3  CEI 947 3     Les interrupteurs de s  curit   peuvent  en  position ARRET    tre   quip  s de trois  cadenas  pr  venant ainsi tout risque de mise  hors tension non autoris  e  voir fig   1 diam  tre de l   trier  jusqu    4 6 mm      Un dispositif de verrouillage 
30. t prendre les  mesures pr  ventives appropri  es     Avant d ouvrir l enveloppe  l interrupteur doit    tre mis en position  MARCHE      Lorsque l enveloppe est ouverte  il n   est  pas permis de commuter sur arbre du  socle d   interrupteur  pour pouvoir  refermer l interrupteur correctement      Le raccordement   lectrique de l appareil  ne doit se faire que par un personnel  qualifi       Si des composants incorpor  s ont   t     enlev  s afin de faciliter l introduction des  c  bles  ceux ci devront   tre remis d  ment  en place avant le raccordement   lectrique     Le raccordement des c  bles d  nud  s se  fera selon les r  glements correspondants     Afin de maintenir le mode de protection   la connexion des conducteurs doit se  faire tr  s soigneusement     L   isolation doit couvrir le conducteur  jusqu      la borne  Le conducteur lui m  me  ne doit pas   tre endommag       Les sections minimales et maximales ad   missibles des conducteurs doivent   tre  respect  es      Toutes les vis et ou   crous des bornes de  connexion  aussi celles des bornes non  utilis  es  doivent   tre serr  es    fond     Attention  L   emmmanchement par   pression des cosses au cable doit se faire  de mani  re appropriee  Il faut assurer que  les entrefers minimums soient respect  s      6 3 Entr  es de cable  KLE    bouchons de fermeture    G  n  ralement  seuls des bouchons de  fermeture et des entr  es de cable certifi  s  peuvent   tre utilis  s     Pour des c  bles flexibles il faudr
31. ux d entretien sont n  cessaires  il  faudra suivre l   alin  a de ce mode d   emploi     8 R  parations   Remise en   tat    Des r  parations ne doivent se faire qu       l aide des pi  ces de rechange d   origine  Cooper Crouse Hinds   CEAG     En cas de d  fauts sur le socle  d   interrupteur  seul un remplacement sera  admissible  Dans le doute  l appareil  d  fectueux devra   tre renvoy      Cooper  Crouse Hinds   CEAG pour   tre r  par       Il n   est pas permis de transformer ou de  modifier ces appareils  sauf pour le montage  des entr  es de c  ble suppl  mentaires en  conformit   avec l   homologation des  appareils     9 Evacuation des d  chets   Recyclage   Lors de l   vacuation de ce mat  riel    lectrique  la r  glementation nationale  respective en vigueur devra   tre respect  e   Pour faciliter la r  utilisation des composants  individuels  des pi  ces en mati  re plastique  ont   t   rep  r  es de la marque distinctive de  la mati  re plastique employ  e     Sous r  serve de modification ou  d informations suppl  mentaires     Cooper Crouse Hinds GmbH    Neuer Weg Nord 49   D 69412 Eberbach   Germany  Phone  49  0  6271   806 500  Fax  49  0  6271   806 476  Internet  www CEAG de  E Mail  Info ex ceag de    GHG980700xP0001 D E F  _   Auflage 0604   x    
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
5 - Provincia di Torino  Téléchargez la documentation  Plantronics Headphones BackBeat 903+ User's Manual  V-METAL USER MANUAL  iSK 8 (Deluxe) - Phonic Corporation  Nokia IPSO 4.0 Cell Phone User Manual    manual duoIVA-3010.cdr - TEM :: Indústria Eletrônica  Hybrid Fire Grills Owner`s Manual  【別表】大崎ケーブルテレビ 各種料金表    Copyright © All rights reserved. 